Configuring the device
6.8 Setting the uninterruptible power supply
6.8
Setting the uninterruptible power supply
UPS monitoring is an option you load as an add-on with ProSave.
A UPS ensures that the HMI device is shut down in a controlled manner after a buffer time in
the event of a power failure. This avoids the loss of data. The following uninterruptible power
supplies are supported:
● SITOP DC UPS modules as of a rated power value of 6 A, e.g. 6EP1931-2DC42
Configure the USB port for UPS monitoring.
Requirement
● The UPS is connected to the 24 V input and a USB port.
● You have opened the "Configuration" tab in the "UPS Properties" dialog box with the
"UPS" icon.
①
②
③
④
Text box for the time after which the "Battery mode activated" message is displayed
Check box for enabling battery mode
Text box for the time after which the "Faulty port" message is displayed
Check box for the "Faulty port" message
Procedure
1. If you want to enable battery mode, activate the "Battery mode" check box.
2. Enter the time for terminating applications in the "min" and "s" text boxes.
You will receive a message when UPS takes effect. Applications such as HMI Runtime
and WinAC MP are then terminated depending on the time entered.
3. If the port to which the UPS is connected is faulty and you therefore want to receive a
message, activate the "Port disturbed" check box.
4. Select the message you want from the list box.
5. Enter the time after which the "Faulty port" message is displayed in the "min" and "s" text
boxes.
Port monitoring for the UPS is set.