Commissioning a project
7.5 Transfer project to the HMI device
Procedure
Proceed as follows:
1. Open the "Transfer Settings" dialog with the Transfer Settings icon.
2. Open the "Channel" tab.
3. Select "Enable Transfer".
4. Select the data channel and set its parameters using "Properties...".
Exception: The "USB device" data channel has no parameters.
5. To start "Transfer" mode automatically:
– Select "Remote Control".
– Close the dialog with "OK".
6. To start "Transfer" mode manually:
– Disable "Remote Control".
– Close the dialog with "OK".
– Close the Control Panel.
– Enable transfer mode in the loader with "Transfer".
Result
"Transfer" mode is set. The project is transferred from the configuration PC via the data
channel selected on the HMI device. If required, configure the corresponding data channel
on the configuration PC.
Transferred data is written directly to the internal memory of the HMI device.
Alternative procedure
You can also set "Transfer" mode on the HMI device using an operating element in the
project. To do this, configure the "SetDeviceMode" system function on an operating element
event, for example, on a button.
You can find more information on this topic in the WinCC online help.
See also
Configuring the data channel (Page 109)
MP 277
138
Operating Instructions, 07/2014, A5E02479740-02