Commissioning a project
7.5 Transfer project to the HMI device
Procedure
Proceed as follows:
1. On the configuring PC, select the "Transfer settings" command in the menu "Project >
Transfer" in WinCC flexible.
The "Select devices for transfer" dialog opens.
2. Select the HMI device in the left area of the dialog.
3. Select the type of connection between the HMI device and the configuring PC.
Set the connection parameters.
4. Set the transfer parameters in the right area of the dialog.
5. If you wish to transfer the compressed project file together with the runtime project to the
HMI device:
Select the "Enable backtransfer" check box.
6. Start transfer in WinCC flexible with "Transfer".
The configuring PC checks the connection to the HMI device. The HMI device shuts
down the current project and automatically switches to "Transfer" mode The project is
transferred to the HMI device. If the connection is not available or is defective, an error
message is displayed on the configuring PC.
Result
When the transfer is completed successfully, the project can be found on the HMI device.
The transferred project is then started automatically.
See also
Operating modes (Page 134)
Configuring the data channel (Page 109)
Data Transmission Options (Page 136)
7.5.2.4
Starting backtransfer
Requirements
● No project is open on the configuring PC in WinCC flexible
● The HMI device is connected to this configuring PC
● The data channel is configured on the HMI device
● The HMI device is in "Transfer" mode
● The memory card containing the compressed project file is inserted into the HMI device
MP 277
144
Operating Instructions, 07/2014, A5E02479740-02
Similar
MP 277 - Service, Support
MP 277 - Service, Support
WirelessKey PROFESSIONAL manual
WirelessKey PROFESSIONAL manual
Descarga  - Service, Support
Descarga - Service, Support
X5 line c - Ascon S.p.A.
X5 line c - Ascon S.p.A.
"user manual"
Visualization of Dispatching Strategies
Visualization of Dispatching Strategies
TP 277, OP 277 (WinCC flexible) - Service, Support
TP 277, OP 277 (WinCC flexible) - Service, Support
Operating Instructions HMI device MP 177 (WinCC flexible)
Operating Instructions HMI device MP 177 (WinCC flexible)
Catalog ST 80 / ST PC 2010
Catalog ST 80 / ST PC 2010
SIMATIC HMI HMI Device TP 177A, TP 177B, OP
SIMATIC HMI HMI Device TP 177A, TP 177B, OP
900 kB - Nexus Marine
900 kB - Nexus Marine
- Murdoch Research Repository
- Murdoch Research Repository
X1 line c
X1 line c
"user manual"
WinAC RTX ODK User Manual - Service, Support
WinAC RTX ODK User Manual - Service, Support
RPX Lite (RPXL_CW), User Manual
RPX Lite (RPXL_CW), User Manual
Simatic S7-200
Simatic S7-200
SIMATIC HMI HMI device MP 377 (WinCC flexible)
SIMATIC HMI HMI device MP 377 (WinCC flexible)
Operator Control and Monitoring Devices
Operator Control and Monitoring Devices
NETLink PRO Compact Handbuch
NETLink PRO Compact Handbuch
Mobile Panel 277 RO - Service, Support
Mobile Panel 277 RO - Service, Support
KT4H Temperature Controller
KT4H Temperature Controller