MP 277 - Service, Support Download

Transcript
Installing and connecting the device
4.3 Connecting the HMI device
4.3.3
Connecting the equipotential bonding circuit
Differences in electrical potential
Differences in potential may occur between spatially separated system parts. Such
differences in electrical potential can lead to high equalizing currents over the data cables
and therefore to the destruction of their interfaces. Equalizing currents can develop if the
cable shielding is terminated at both ends and grounded to different parts of the system.
Differences in potential can develop when a system is connected to different mains.
General requirements of equipotential bonding
Differences in electrical potential must be reduced using equipotential bonding to ensure
trouble-free operation of the relevant components of the electronic system. The following
must therefore be observed when installing the equipotential bonding circuit:
● The effectiveness of equipotential bonding increases as the impedance of the
equipotential bonding conductor decreases or as its cross-section increases.
● If two plant parts are interconnected by means of shielded data cables and their shielding
is bonded at both ends to the grounding/protective conductor, the impedance of the
additionally installed equipotential bonding cable must not exceed 10% of the shielding
impedance.
● The cross-section of a selected equipotential bonding conductor must be capable of
handling the maximum equalizing current. Experience has shown that equipotential
bonding conductors with a minimum cross-section of 16 mm² should be fitted between
the control cabinets or the ground point of the supporting arm or the stand for PRO HMI
devices.
● Use equipotential bonding conductors made of copper or galvanized steel. Establish a
large surface contact between the equipotential bonding conductors and the
grounding/protective conductor and protect them from corrosion.
● Use a suitable cable clip to clamp the shield of the data cable flush to the equipotential
bonding rail. Keep the length of cable between the HMI device and the equipotential
bonding rail as short as possible.
● Route the equipotential bonding conductor and data cables in parallel and with minimum
clearance between them.
MP 277
46
Operating Instructions, 07/2014, A5E02479740-02
Similar
MP 277 - Service, Support
MP 277 - Service, Support
WirelessKey PROFESSIONAL manual
WirelessKey PROFESSIONAL manual
Descarga  - Service, Support
Descarga - Service, Support
X5 line c - Ascon S.p.A.
X5 line c - Ascon S.p.A.
"user manual"
Visualization of Dispatching Strategies
Visualization of Dispatching Strategies
TP 277, OP 277 (WinCC flexible) - Service, Support
TP 277, OP 277 (WinCC flexible) - Service, Support
Operating Instructions HMI device MP 177 (WinCC flexible)
Operating Instructions HMI device MP 177 (WinCC flexible)
Catalog ST 80 / ST PC 2010
Catalog ST 80 / ST PC 2010
SIMATIC HMI HMI Device TP 177A, TP 177B, OP
SIMATIC HMI HMI Device TP 177A, TP 177B, OP
900 kB - Nexus Marine
900 kB - Nexus Marine
- Murdoch Research Repository
- Murdoch Research Repository
X1 line c
X1 line c
"user manual"
WinAC RTX ODK User Manual - Service, Support
WinAC RTX ODK User Manual - Service, Support
RPX Lite (RPXL_CW), User Manual
RPX Lite (RPXL_CW), User Manual
Simatic S7-200
Simatic S7-200
SIMATIC HMI HMI device MP 377 (WinCC flexible)
SIMATIC HMI HMI device MP 377 (WinCC flexible)
Operator Control and Monitoring Devices
Operator Control and Monitoring Devices
NETLink PRO Compact Handbuch
NETLink PRO Compact Handbuch
Mobile Panel 277 RO - Service, Support
Mobile Panel 277 RO - Service, Support
KT4H Temperature Controller
KT4H Temperature Controller