Download Rail 310 Operating Manual

Transcript
PowerRail 310
Operating Manual
February 2010
Safety
1 Safety
This instruction sheet gives details of safe installation and operation of the Rail310 electricity meter.
Safety may be impaired if the instructions are not followed. Labels on each meter give details of
equipment ratings for safe operation. Take time to examine all labels before commencing
installation. Safety symbols on the meter have specific meanings.
Refer To User Manual
Risk of Electric Shock
WARNING
The meter contains no user serviceable parts. Installation and
commissioning should only be carried out by qualified personnel
Further information is available at http://www.ndmeter.co.uk.
Page 2
Rail310 Operating Manual
Operation
2 Operation
2.1 Three Meters in One Box
The Rail310 consists of three multi-function electricity meters in a single enclosure. The unit
independently monitors up to three single-phase loads providing a clear digital displays of kW, kWh,
volts and amps.
Three pulse outputs are also available allowing each kWh register to be remotely monitored/logged.
An RS485 Modbus RTU serial communications link may be optionally fitted providing multi-function
meter readings to remote SCADA systems.
2.2 Energy Displays
Press
to select the kWh register for each meter.
Meter 1

kWh
Active Energy Register - Meter 1
Meter
2

kWh
Active Energy Register - Meter 2
Meter
3

kWh
Active Energy Register - Meter 3
and
together and hold for 2 seconds to simultaneously reset the three kWh
Press
registers, if this feature is enabled.
Scaling of the energy registers is set by the nominal input currents and voltages and remains
constant during operation of the meter.
Energy registers will each accumulate from zero to 99,999,999 then restart from zero.
Rail310 Operating Manual
Page 3
Operation
2.3 Current and Voltage Displays
Press
to select from the following displays;
Meter 1
A


True RMS Amps - Meter 1
Meter
2
A


True RMS Amps - Meter 2
Meter
3

A

True RMS Amps - Meter 3
Meter 1
V


True RMS Volts - Meter 1
Meter
2
V


True RMS Volts - Meter 2
Meter

3
V

True RMS Volts - Meter 3
Page 4
Rail310 Operating Manual
Operation
2.4 kW Displays
Press
to select the instantaneous kW displays for each meter.
Meter 1


kW
Active Power - Meter 1
Meter
2


kW
Active Power - Meter 2
Meter
3


kW
Active Power - Meter 3
Rail310 Operating Manual
Page 5
Operation
2.5 Pulse Outputs
Three isolated pulse outputs are provided for connection to external systems such as Building
Energy Management Systems (BEMS), data loggers, remote counters etc.
Pulse 1 is associated with the active energy (kWh) register of Meter 1, Pulse 2 with Meter 2 and
Pulse 3 with Meter 3.
A single pulse occurs for each unit of energy on the display (eg 1 pulse per 0.1kWh). The pulse
rate (amount of energy associated with each pulse) and pulse length is programmable and may be
set to suit the external system.
Pulse outputs take the form of a volt free contact closure.
 Pulse 1 provides a momentary short circuit between contacts C and P1 each time Meter 1
kWh register increments a set number of times.
 Pulse 2 provides a momentary short circuit between contacts C and P2 each time Meter 2
kWh register increments a set number of times.
 Pulse 3 provides a momentary short circuit between contacts C and P3 each time Meter 3
kWh register increments a set number of times.
2.5.1 Pulse LED
A Light emitting diode (LED) on the front panel of the instrument remains ON during each output
pulse of the meter, which is currently shown on the LCD.
Pulse Output Indicator
Page 6
Rail310 Operating Manual
Programming
3 Programming
3.1 Programming Menu
To enter programming mode:
Hold
and
together for 5 Seconds.
A Security Code may be required before changes to programmed parameters are allowed. This
is only required if a Security Code greater than zero is set via serial communications. This is then
stored in non-volatile memory during power interruptions.

4-Digit Security Code
To Enter the Security Code:
Press
or
Press
to select next most significant digit.
to change each digit. (Lowest significant digit first).
When a valid code is entered, the first page of the programming menu is displayed.
A

Programming Menu First Page
Rail310 Operating Manual
Page 7
Programming
3.2 Setting The CT Primary Current
External current transformers (CTs) are required to reduce large currents to a level accepted as
inputs to the meter. The Rail310 meter displays require scaling to match the primary current rating
of the external Current Transformers used.
Each meter in the unit uses the same CT primary current rating.
Press
or
to select the Next/Previous CT Primary current from the preferred list.
A

Setting The CT Primary Current
3.2.1 Fine Adjust CT Primary
If values other than those found in the preferred list are required use Fine Adjust Mode:
Hold
and
Press
or
together for 2 Seconds to select/deselect Fine Adjust Mode “CTF”.
to increment the CT Primary current in steps of 5A.
When the desired CT primary current has been set press
to move to the next parameter.
3.3 Setting The Pulse Output Rate
The amount of energy associated with each momentary pulse output may be programmed. A
single setting is required to scale all three Meter pulse outputs.

kWh
Setting The Pulse Output Rate
Press
or
to select the Next/Previous Pulse Rate from the preferred list.
When the desired Pulse Rate has been set press
to move to the next parameter.
Page 8
Rail310 Operating Manual
Programming
3.4 Setting The Pulse On Time
The length of time (in seconds) each momentary pulse output remains “ON” (short circuit) may be
programmed. A single setting is required to scale all three Meter pulse outputs.

Setting The Pulse Output Rate
Press
or
to select the Next/Previous Pulse On Time from the preferred list.
When the desired Pulse Rate has been set press
to move to the next parameter.
Note:
When selecting a long Pulse On Time it may be necessary to reduce the Pulse Rate to
prevent pulses appearing permanently “ON”.
Rail310 Operating Manual
Page 9
Programming
3.5 Pulse Output Test Mode
This feature allows the pulse output hardware and external system connections to be
commissioned without a measured load.
The test pulse rate is set automatically dependant on the programmed pulse length (maximum
0.5Hz).
Press
to start/stop the test pulses on all outputs.
Pulse Output Test OFF Mode
In this mode no pulses occur on P1-P3 and the display shows the total number of pulses
accumulated during testing:

Pulse Output Test RUN Mode
In this mode pulses occur simultaneously on all three outputs with an Pulse On Time set in
programming mode above. The Pulse Rate is set automatically to be greater than twice the Pulse
On Time.
The display shows the total number of pulses accumulated during testing

Press
and
together to stop the test pulses and simultaneously reset the test counter.
When the test is complete press
to move to the next parameter.
Note: When selecting a long Pulse On Time it may be necessary to reduce the Pulse Rate to
prevent pulses appearing permanently “ON”.
Page 10
Rail310 Operating Manual
Display Scaling
4 Display Scaling
The units, kWh or MWh and the position of the decimal point for the energy/power displays are
automatically set dependant on the CT Primary setting for the meter.
The display pages are scaled as follows:
CT
Primary
Display Resolution
Amps
Volts
Power
Energy
<10 A
0.001A
0.1V
0.001kW
0.001kWh
=10 A
0.01A
0.1V
0.001kW
0.001kWh
<=80 A
0.01A
0.1V
0.01kW
0.01kWh
<=100 A
0.1A
0.1V
0.01kW
0.01kWh
<=800 A
0.1A
0.1V
0.1kW
0.1kWh
<=1,000 A
1A
0.1V
0.1kW
0.1kWh
<=8,000 A
1A
0.1V
1kW
1kWh
<=10,000 A
0.01kA
0.1V
1kW
1kWh
<=25,000 A
0.01kA
0.1V
0.01MW
0.01MWh
Rail310 Operating Manual
Page 11
Installation
5 Installation
5.1 Mounting On A Rail
The Rail310 conforms to DIN 43880, 6-Module Wide. The unit is therefore compatible with a
number of standard distribution systems with 45mm cut-outs. The meter should be mounted on a
35mm symmetrical (“Top-Hat”) DIN rail of minimum length 106mm.
5.2 Pulse Output Connection
The pulse outputs take the form of isolated volt free normally open contacts.
The pulse output circuit is isolated from all other circuits at 2.5kV / 1 minute.
The pulses can be used as an input to a remote counter, pulse logger, building energy
management system etc.
Pulse Output Connections
Page 12
Rail310 Operating Manual
Standard Connections
6 Standard Connections
6.1 Measurement Input Connections
Meter 1 Measurement Input Connections
Meter 2 Measurement Input Connections
Meter 3 Measurement Input Connections
Rail310 Operating Manual
Page 13
Standard Connections
Meters 1-3 With Common Voltage Input
6.1.1 Voltage Measurement Input Fuses
It is recommended to fit a fuse/circuit-breaker to each voltage measurement input. This allows the
Rail310 to be isolated should maintenance be required.
Each meter voltage measurement input takes less than 1mA at nominal 230V.
Recommended fuses should be rated at 250V / 100mA (Type T).
6.1.2 Common Neutral
The voltage measurement inputs must be sourced from a supply with a common neutral point.
Suitable circuits include; several feeders off a single-phase circuit or individual phases of a 3phase 4 wire supply.
6.2 Auxiliary Meter Supply
The Rail310 requires an ac supply to power the measurement circuit and display. This can be any
ac supply meeting the specification stated on the units rating label.
It is acceptable to cross connect the meter supply with one of the voltage measurement inputs
providing the specified ratings are not exceeded.
Rail310 Unit Auxiliary Supply
6.2.1 Auxiliary Supply Fuse
The auxiliary supply is not fused internally in the Rail310. An external fuse must be fitted.
External Auxiliary Supply fuses should be rated:
Page 14
No of Rail310 Units
Fuse Rating
1-10
11-20
20-50
>50
250V / 500mA Anti-Surge
250V / 1A Anti-Surge
250V / 2.5A Anti-Surge
Use multiple fuses as above
Rail310 Operating Manual
Specification
7 Specification
INPUTS
System
Voltage Un
Current In
Measurement
Range
Frequency Range
Burden
Overload
3 Loads with a common neutral
Standard: 3 x 230Vac
Optional: 3 x 120Vac
Standard: 5A from external CTs.
Optional: 1A from external CTs.
Optional: 0.333V from external current sensors
Voltage
50% to 120%
Current
0.2% to 120%
Fundamental 45 to 65Hz
Harmonics
Up to 30th harmonic at 50Hz
Voltage
<0.1VA per meter
Current
<0.1VA per meter
Voltage
x2 for 1 hour
Current
x20 for 0.5 second max
DISPLAY
Type
Data Retention
Format
Scaling
Legends
Custom, Supertwist, LCD
10 years min. Stores kWh & Meter set-up
8 x 9mm high digits with DPs & 2.8mm legends
Direct reading. User programmable CT
CT Primary programmable from 5A to 25,000A
kWh, MWh etc. depending on user settings
AUXILIARY SUPPLY
Standard
Options
Load
Overload
230V 50/60 Hz ±15%
115V 50/60 Hz ±15%
2VA max.
x1.2 continuous
ACCURACY All errors ± 1 digit
kWh
kW
Amps & Volts
PF (Modbus Only)
Better than Class 1 per EN 62053-21 & BS 8431
Better than Class 0.25 IEC 60688
Class 0.1 IEC 60688 (0.01In – 1.2In or 0.1Un – 1.2Un)
±0.2° (0.05In – 1.2In and 0.2Un – 1.2Un)
PULSE OUTPUTS
Function
Pulse Rate
Pulse On Time
Rise & Fall Time
Type
Contacts
Isolation
1 Pulse per unit of energy
Settable between 1 & 1000 counts of kWh register
0.1 sec. default; Settable between 0.1 and 20 sec
< 2.0ms
N/O Volt free contact. Optically isolated BiFET
100mA ac/dc max., 100V ac/dc max: 0.5W Max Load
2.5kV 50Hz 1 minute
MODBUS® Serial Communications (Optional)
Bus Type
Protocol
Baud Rate
Address
Latency
Command Rate
RS485 2 wire + 0v. ½ Duplex, ¼ unit load
MODBUS® RTU with 16 bit CRC
4800, 9600 or 19,200 User settable
1 – 247 User settable
Reply within 250ms max.
New command within 5ms of previous one
GENERAL
Temperature
Humidity
Environment
Operating
-10°C to +55°C
Storage
-25°C to +70°C
< 75% non-condensing
IP20
MECHANICAL
Terminals
Enclosure
Material
Dimensions
Weight
Rising Cage. 4mm2 (12 AWG) cable max.
DIN 43880, 6-Modules Wide
Noryl® with fire protection to UL94-V-O. Self extinguishing
106 x 90 x 58mm (Cut out 106 x 45mm)
~ 250 gms
SAFETY
Conforms to
EN 61010-1 Installation Category III
Rail310 Operating Manual
Page 15