Commissioning a Project
7.5 Transfer
7.5.2
Starting Manual Transfer
Introduction
You can manually switch the HMI device to "Transfer" mode as follows:
• With a configured operator control during ongoing operation.
• In the Loader of the HMI device.
Requirements
• The project "*.hmi" is opened in WinCC flexible.
• The HMI device is connected to a configuration computer.
• The data channel is configured on the HMI device.
• The HMI device is in "Transfer" mode.
Procedure
Proceed as follows:
1. On the configuration computer, select the "Transfer settings" command in the menu
"Project > Transfer" in WinCC flexible.
The "Select devices for transfer" dialog opens.
2. Select the HMI device in the left area of the dialog.
3. Select the type of connection between the HMI device and the configuration computer.
Set the connection parameters.
4. Set the transfer parameters in the right area of the dialog.
5. If you wish to transfer the compressed project file together with the runtime project to the
HMI device:
Select the "Activate Upload" check box.
6. Start transfer in WinCC flexible with "Transfer".
The configuration computer checks the connection to the HMI device. The project is
transferred to the HMI device. If the connection is not available or is defective, an error
message is displayed on the configuration computer.
Result
When the transfer is completed successfully, the project can be found on the HMI device.
The transferred project is then started automatically.
See also
Operating Modes (Page 7-2)
Configuring the Data Channel (Page 6-33)
Data Transmission Options (Page 7-3)
Overview (Page 7-4)
TP 277, OP 277 (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DH01-0AB0
7-5