Download TP 277, OP 277 (WinCC flexible) - Service, Support

Transcript
Appendix
A.2 System Alarms
Number
Effect/cause
Remedy
80028
The alarm returns a status report indicating that the
logs are currently being initialized. No values are
logged until the alarm 80026 is output.
—
80029
The number of logs specified in the alarm could not
be initialized. The logs are initialized.
The faulty log files are not available for logging
jobs.
Evaluate the additional system alarms , related to this
alarm which is also generated.
Check the configuration, the ODBC (Open Database
Connectivity) and the specified drive.
80030
The structure of the existing log file does not match
the expected structure.
Logging is stopped for this log.
Delete the existing log data manually, in advance.
80031
The log in CSV format is corrupted.
The log cannot be used.
Delete the faulty file.
80032
Logs can be assigned events. These are triggered
as soon as the log is full. If WinCC flexible Runtime
is started and the log is already full, the event is not
triggered.
The log specified no longer logs data because it is
full.
Close WinCC flexible Runtime, delete the log, then restart
WinCC flexible Runtime.
Or:
Configure a button which contains the same actions as
the event and press it.
80033
"System Defined" is set in the data log file as the
Install MSDE again.
data source name. This causes an error. No data is
written to the database logs, whereas the logging to
the CSV logs works.
80034
An error has occurred in the initialization of the
No action is necessary. However, it is recommended to
logs. An attempt has been made to create the
save the backup files or delete them in order to make the
tables as a backup. This action was successful. A
space available again.
backup has been made of the tables of the
corrupted log file and the cleared log was restarted.
80035
An error has occurred in the initialization of the
logs. An attempt has been made to create backups
of the tables and this has failed. No logging or
backup has been performed.
It is recommended to save the backups or to delete them
in order to release memory.
80044
The export of a log was interrupted because
Runtime was closed or due to a power failure.
When Runtime restarted, it was detected that the
export needed to be resumed.
The export resumes automatically.
80045
The export of a log was interrupted due to an error
in the connection to the server or at the server
itself.
The export is repeated automatically. Check:
• the connection to the server
• if the server is running
• if there is enough free space on the server.
80046
The destination file could not be written while
exporting the log.
check whether there is enough space on the server and it
you have permission to create the log file.
80047
The log could not be read while exporting it.
check whether the storage medium is correctly inserted.
80048
—
—
80049
The log could not be renamed while preparing to
export it.
The job can not be completed."
check whether the storage medium is correctly inserted
and if there is sufficient space on the medium.
80050
The log which shall be exported is not closed.
The job can not be completed.
Make sure the "CloseAll Logs" system function is called
before using the "ExportLog" system function. Change
the configuration as required.
TP 277, OP 277 (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DH01-0AB0
A-9