A.2 System Alarms
Number
Effect/cause
Remedy
160000
No more data is read or written. Possible causes:
• The cable is defective.
• The PLC does not respond, is defective, etc.
• The wrong port is used for the connection.
• System overload.
Ensure that the cable is plugged in, the controller is
operational, the correct port is being used.
Restart the system if the system alarm persists.
160001
Connection is up because the cause of the
interruption has been eliminated.
—
160010
No connection to the server because the server
identification (CLS-ID) cannot be determined.
Values cannot be read or written.
Check access rights.
160011
No connection to the server because the server
identification (CLS-ID) cannot be determined.
Values cannot be read or written.
Check, for example, if
• the server name is correct
• the computer name is correct
• the server is registered
160012
No connection to the server because the server
identification (CLS-ID) cannot be determined.
Values cannot be read or written.
Check, for example, if
• the server name is correct
• the computer name is correct
• the server is registered
Note for advanced users:
Interpret the value from HRESULT.
160013
The specified server was started as InProc server.
This has not been released and may possibly lead
to incorrect behavior because the server is running
in the same process area as the WinCC flexible
Runtime software.
160014
Only one OPC server project can be started on a
Do not start a second project with OPC server
PC/MP. An alarm is output when an attempt is
functionality on the computer.
made to start a second project.
The second project has no OPC server functionality
and cannot be located as an OPC server by
external sources.
170000
S7 diagnostics events are not indicated because it
is not possible to log on to the S7 diagnostics
functions at this device. The service is not
supported.
—
170001
The S7 diagnostics buffer cannot be viewed
because communication with the controller is shut
down.
Set the controller to online mode.
170002
The S7 diagnostics buffer cannot be viewed
because reading of the diagnostics buffer (SSL)
was canceled with error.
—
170003
An S7 diagnostics event cannot be visualized. The
system returns internal error %2.
—
170004
An S7 diagnostics event cannot be visualized. The
system returns an internal error of error class %2,
error number %3.
—
170007
It is not possible to read the S7 diagnostics buffer
(SSL) because this operation was canceled with an
internal error of class %2 and error code %3.
—
A-14
Configure the server as OutProc Server or Local Server.