Appendix
A.2 System Alarms
Number
190011
Effect/cause
Remedy
Possible cause 1:
The value entered could not be written to the
configured controller tag because the high or low
limit was exceeded.
Make sure that the value entered lies within the range of
values of the control tags.
The system discards the entry and restores the
original value.
Possible cause 2:
190012
The connection to the controller was interrupted.
Check the connection to the PLC.
It is not possible to convert a value from a source
format to a target format, for example:
Check the range of values or the data type of the tags.
An attempt is being made to assign a value to a
counter that is outside the valid, PLC-specific value
range.
A tag of the type Integer should be assigned a
value of the type String.
190100
The area pointer is not updated because the
address configured for this pointer does not exist.
Type
1 Warning alarms
2 Error alarms
3 Controller acknowledgment
4 HMI device acknowledgment
5 LED mapping
6 Trend request
7 Trend transfer 1
8 Trend transfer 2
No.:
consecutive number shown in WinCC flexible ES.
Check the configuration.
190101
The area pointer is not updated because it is not
possible to map the PLC type to the area pointer
type.
Parameter type and no.:
see alarm 190100
—
190102
The area pointer is updated after the cause of the
last error state has been eliminated (return to
normal operation). Parameter type and no.:
See alarm 190100
—
200000
Coordination is not executed because the address Change the address or set up the address in the
configured in the controller does not exist/is not set. controller.
200001
Coordination is canceled because the write access
to the address configured in the PLC is not
possible.
Change the address or set the address in the controller at
an area which allows write access.
200002
Coordination is not carried out at the moment
because the address format of the area pointer
does not match the internal storage format.
Internal error
200003
Coordination can be executed again because the
last error state is eliminated (return to normal
operation).
—
200004
The coordination may not be executed.
—
A-16
TP 277, OP 277 (WinCC flexible)
Operating Instructions, 09/2007, 6AV6691-1DH01-0AB0