Download "user manual"

Transcript
Process controller
with PROFIBUS DP
and Modbus Master/Slave
1/ DIN - 48 x 96
8
ASCON spa
ISO 9001
C e r t i f i e d
ASCON spa
20021 Bollate
(Milano)
via Falzarego, 9/11
Tel. +39 02 333 371
Fax +39 02 350 4243
http://www.ascon.it
e-mail [email protected]
c
X5 line
User
manual
•
M.I.U.X5
-2/01.01
•
Cod.
J30-478-1AX5
I E
Process controller
with PROFIBUS DP
and Modbus Master/Slave
1/ DIN - 48 x 96
8
c
X5 line
X5
I1 I2 I3
45.80
50
45.80
Information
c
NOTES
ON ELECTRIC
SAFETY AND
ELECTROMAGNETIC
COMPATIBILITY
Please, read carefully these instructions before proceeding with the installation of the
controller.
Class II instrument, rear panel mounting.
This controller has been designed with compliance to:
Regulations on electrical apparatus (appliance, systems and installations) according to
the European Community directive 73/23 CEE amended by the European Comunity directive 93/68 CEE and the Regulations on the essential protection requirements in electrical
apparatus EN 61010-1 (IEC 1010 - 1) : 90 +A1:92 + A2:95.
Regulations on Electromagnetic Compatibility according to the European Community
directive n°89/336/CEE, amended by the European Community directive n° 92/31/CEE and
the following regulations:
- Regulations on RF emissions
EN50081 - 1
residential environments
EN50081 - 2
for industrial environments
- Regulation on RF immunity
EN500082-2
for industrial equipment and system
It is important to understand that it’s responsibility of the installer to ensure the compliance
of the regulations on safety requirements and EMC. This device has no user serviceable parts and requires special equipment and specialised engineers.
Therefore, a repair can be hardly carried on directly by the user. For this purpose, the
manufacturer provides technical assistance and the repair service for its Customers.
Please, contact your nearest Agent for further information.
All the information and warnings about safety and electromagnetic compatibility
are marked with the B sign, at the side of the note.
2
Table of contents
TABLE OF CONTENTS
1
INTRODUCTION.............................................................................................................page
1.1
PRODUCT CODING..........................................................................................page
4
5
2
INSTALLATION .................................................................................................................page
2.1
DESCRIPTION.........................................................................................................page
2.2
OPERATING CONDITIONS ...........................................................................page
2.3
INSTALLATION ........................................................................................................page
6
6
8
9
3
ELECTRICAL CONNECTIONS ................................................................page
3.1
TERMINATION UNIT .........................................................................................page
3.2
CABLING LAYOUT.............................................................................................page
3.3
EXAMPLE OF WIRING DIAGRAM ........................................................page
10
10
11
12
4
OPERATIONS ......................................................................................................................page
4.1
KEYS FUNCTIONS AND DISPLAY .......................................................page
4.2
DATA SETTING.......................................................................................................page
4.3
CONFIGURATION ................................................................................................page
4.4
PARAMETERISATION .......................................................................................page
4.5
PARAMETERS .........................................................................................................page
4.6
ACCESS LEVELS .................................................................................................page
22
22
24
25
34
42
50
5
DISPLAYS..................................................................................................................................page 53
6
COMMANDS ........................................................................................................................page 54
6.1
COMMANDS FROM KEYBOARD ........................................................page 55
6.2
COMMANDS FROM DIGITAL INPUTS ...........................................page 58
6.3
COMMANDS FROM SERIAL COMMUNICATION
(PLEASE, REFER THE ADDENDUM ON THE SERIAL COMMUNICATION)
7
SETPOINT PROGRAMMER ( OPTIONAL )...................................page
7.1
PROGRAM ORGANISATION .....................................................................page
7.2
OPERATING CONDITIONS ........................................................................page
7.3
PARAMETERISATION - PROGRAM MENU ................................page
7.4
PROGRAM STATUS DISPLAYING.........................................................page
7.5
RUN/STOP OF A PROGRAM .................................................................page
8
TECHNICAL SPECIFICATIONS .............................................................page 69
59
59
60
62
64
65
3
1 - Introduction
1 INTRODUCTION
Congratulations for having chosen these universal controllers.
They are the best result of our
experience in designing and manufacturing of smart, powerful and
high reliable controllers.
The process controllers of the
X5 series have been designed
for the industrial environment,
are provided with a complete set
of functions, as a true universal instrument.
They can be used as
Controllers-Programmers with 4
Setpoint profiles of 16 segments.
Memory Chip
Control
Alarms
Retransmission
Data copy/Data store
(option)
Main universal input
(option)
PV/SP
OP1
PV
Auxiliary input
1
OP2
2
OP3
3
OP4
4
Single
action
OP1
OP5
OP2 OP3 OP4 OP5 OP6
OP1 OP2 OP3 OP4
OP6
AUX
Digital input
IL1
IL2
IL3
5
OP1 OP2
Double
action
OP1 OP5
OP5 OP2 OP1
OP3 OP4 OP5 OP6
OP2 OP3 OP4
OP6
OP3 OP4
OP6
OP5
OP6
(option)
6
OP5 OP6 OP1 OP2 OP3 OP4
7 Valve
OP1 OP2
OP3 OP4 OP5 OP6
X5
Setpoint
Fuzzy tuning with automatic selection
One shot
Auto tuning
Digital inputs (IL1,IL2 or IL3) functions
Modbus
RS485
Master
Modbus
RS485
Slave
4
Operating mode
Resources
POWERFUL FEATURES
AND A WIDE RANGE
OF FUNCTIONALITIES
link to other
instruments
(option)
Parameterisation
Supervision
(option)
(option)
One shot
Natural Frequency
Continuous tuning
Adaptive
1 - Introduction
Line
1.1 MODEL CODE
The complete code is displayed
on the instrument label.
The information about product
coding are accessible from the
front panel by mean of a particular procedure described at section 5.1 page 53.
Basic product code
B
C
D
Modello basic
Model:
X5 – A
B C
Power Supply
Outputs
Serial + mathematical package (MP)
Options
Power supply
A
100 - 240V~ (- 15% + 10%) 3
24V~ or 24V–
5
X5
I1 I2 I3
45.80
50
Instrument label
P/N
; X5-3150-0000
CONF :
S/N
: A0A-9919/0013
V~(L-N).100÷240V 50/60 Hz - 4W
45.80
Outputs OP1 - OP2
Relay - Relay
Triac - Triac
B
1
5
Serial Communications
C
None
0
Mathematical package (MP) 1
RS485 Modbus/Jbus SLAVE
5
+ Mathematical package
RS485 Modbus/Jbus
SLAVE + MASTER + (MP) 6
PROFIBUS DP SLAVE
7
+ Mathematical package
RS485 Modbus/Jbus
SLAVE + PROFIBUS + (MP) 8
Accessories
D
– E
F
G
0
Colour
User manual
Setpoint
Options
None
Frequency input
2nd SSR drive/analogue
output (OP6
Frequency input + OP6
D
0
1
4
6
Setpoint Programmer
E
Not fitted
0
4 programs with 16 segments 4
User manual
Italian/English (std)
French/English
German/English
Spanish/English
F
0
1
2
3
Front panel colour
Dark (std)
Beige
G
0
1
5
2 - Installation
2
INSTALLATION
Installation must only be carried out by
qualified personnel.
2.1 GENERAL DESCRIPTION
IP 20 Termination Unit
EN61010 - 1 (IEC1010 - 1)
Panel
surface
Before proceeding with the installation of
this controller, follow the instructions illustrated in this manual and, particularly the
installation precautions marked with the
B symbol, related to the European
Community directive on electrical protection
and electromagnetic compatibility.
B
To prevent hands or metal touching parts
that may be electrically live, the controllers
must be installed in an enclosure and/or
in a cubicle.
Product code label
Mounting clamps
Sealing front panel gasket
Front panel
IP65 protection
EN 650529 (IEC 529)
6
2 - Installation
2.1.1 DIMENSIONAL DETAILS
2.1.2 PANEL CUT-OUT
48 mm
1.89 in
65 mm min
2.56 in min
110 mm
4.33 in
10 mm max
0.39 in max
92+0.8 mm
3.62+0.031 in
10 mm max
0.39 in max
113 mm min
4.45 in min
96 mm
3.78 in
45+0.6 mm
1.78+0.023 in
7
2 - Installation
B
2.2 ENVIRONMENTAL RATINGS
Operating conditions
M
T
%Rh
Altitude up to 2000 m
Temperature 0…50°C
Relative humidity 5…95 % non-condensing
Suggestions
Special conditions
M
T
%Rh
P
Altitude > 2000 m
Temperature >50°C
8
Use forced air ventilation
Humidity > 95 %
Warm up
Conducting atmosphere
Use filter
Forbidden Conditions
C
E
Use 24V~ supply version
D
Corrosive atmosphere
Explosive atmosphere
2 - Installation
2.3
PANEL MOUNTING
2.3.1 INSERT
THE INSTRUMENT
2.3.2 INSTALLATION
SECURING
2.3.3 CLAMPS
REMOVING
2.3.4 INSTRUMENT
UNPLUGGING
1 Prepare panel cut-out
2 Check front panel gasket
position
3 Insert the instrument through
the cut-out
1 Fit the mounting clamps
2 Push the mounting clamps
towards the panel surface to
secure the instrument
1 Insert the screwdriver in the
clips of the clamps
2 Rotate the screwdriver
1 Push and
2 Pull to remove the instrument
B
Electrostatic discharges can
damage the instrument
1MΩ
1
Before removing the instrument
the operator must discharge
himself to ground
1
1
2
3
2
2
1
1
2
1
9
3 - Electrical Connections
1
DN
2
DG
3 C
VP
4
LOGIC
INPUT
OP5
18
2
7
mV/V/mA
15 C
3
20
9
21
10
11
12
A
b
B
0%
22 N/C
RTD
23
24
L
26
N
27
POT
19
8
25
1
13
25
2
14
26
15
27
16
28
3
29 C
REM
OP6
(option)
IN2
(option)
OP3
0,5
Nm
Rear
terminal
cover
Cable size
0,5…1,5 mm2
(22 a 16 AWG)
30 NO
31 NO
Option terminals
OP1
32 C
33 NO
34 NO
35 C
36
5.7 mm
0.22 in
35 screw terminals M3
4
5
17
29
Holding screw 0.5 Nm
OP2
6
18
30
7
19
31
8
20
32
9
21
33
Positive screw
driver PH1
Negative screw
driver 0,8 x 4 mm
OP4
24V—
OUT
10
10
B
3.1 TERMINATION UNIT
28 NC
17
1
6
TC
14
16
5
IN1
13
RS485
(Slave)
DP
RS485
(master)
ELECTRICAL
CONNECTIONS
Profibus
3
Terminals
Pin connector
q 1.4 mm 0.055 in max
34
11
23
35
12
24
36
Ø
Fork-shape
AMP 165004
Ø 5.5 mm - 0.21 in
L
Stripped wire
L 5.5 mm - 0.21 in
3 - Electrical Connections
B
PRECAUTIONS
Despite the fact that the instrument has been designed to work
in an harsh and noisy environmental (level IV of the industrial
standard IEC 801-4), it is recommended to follow the following
suggestions.
Conduit for supply and output cables
A
A
All the wiring must comply with
the local regulations.
The supply wiring should be routed away from the power cables.
Avoid to use electromagnetic
contactors, power Relays and
high power motors nearby.
Avoid power units nearby, especially if controlled in phase angle
Keep the low level sensor input
wires away from the power lines
and the output cables.
If this is not achievable, use
shielded cables on the sensor
input, with the shield connected
to earth.
B
3.2 PRECAUTIONS AND ADVISED CONDUCTOR COURSE
A
1
13
25
1
13
25
2
14
26
2
14
26
3
15
27
3
15
27
4
16
28
4
16
28
5
17
29
5
17
29
6
18
30
6
18
30
7
19
31
7
19
31
8
20
32
8
20
32
9
21
33
9
21
33
34
10
10
EDC
B
34
11
23
35
11
23
35
12
24
36
12
24
36
DC
EDC
B
A=
B=
C=
D=
E=
Supply
Outputs
Analog inputs
Analogue output
Digital input
Serial Comm.s
DC
Conduit for low level sensor cables
11
3 - Electrical Connections
B
3.3 EXAMPLE OF WIRING DIAGRAM (VALVE CONTROL)
Retransm. Commands
Supervisory
V~
Power
supply [3]
switch
RS485
0.5A T
1
13
2
14
26
C 15
27
3 C
OP3
25
4
16
5 IL1
17
29
6 IL2
18
30
7 IL3
19
8
20
32
9
21
33
V~
Allarme
28
[6]
OP1
[5]
[5]
31
[6]
10
OP2
23
Servomotor
35
Rj
24
4…20mA
12
[5]
34
11
12
[6]
36
Pt100
24V
I
°C
Transmitter
Notes:
1] Make sure that the power supply voltage is
the same indicated on the instrument.
2] Switch on the power supply only after that
all the electrical connections have been
completed.
3] In accordance with the safety regulations,
the power supply switch shall bring the
identification of the relevant instrument. The
power supply switch shall be easily accessible from the operator.
4] The instrument is protected with a 0.5 A~
T fuse. In case of failure it is suggested to
return the instrument to the manufacturer
for repair.
5] To protect the instrument internal circuits
use:
- 2 A~ T fuses for Relay outputs
- 1 A~ T fuses for Triac outputs
6] Relay contacts are already protected with
varistors.
Only in case of 24 V ~ inductive loads,
use model A51-065-30D7 varistors (on
request)
3 - Electrical Connections
3.3.1 POWER SUPPLY
B
Switching power supply with multiple isolation and internal fuse
• Standard version:
nominal voltage:
100 - 240V~ (-15% + 10%)
Frequency 50/60Hz
• Low Voltage version:
Nominal voltage:
24V~ (-25% + 12%)
Frequency 50/60Hz
or 24V– (-15% + 25%)
Power consumption 3VA max
Included
0.5A T fused
25
L
B
3.3.2 PV CONTROL INPUT
A L-J-K-S-R-T-B-N-E-W thermocouple type
• Connect the wires with the polarity as shown
• Use always compensation cable of the correct type
for the thermocouple used
• The shield, if present, must be connected to a proper earth.
11
12
B For Pt100 resistance
thermometer
• If a 3 wires system is used, use always cables of the
same diameter (1mm2 min.)
Line 20 Ω/lead maximum resistance
• When using a 2 wires system, use always cables of the
same diameter (1,5mm2 min.) and put a jumper between
terminals 11 and 12
A
b
B
Supply
26
27
wire resistance
150Ω max
10
11
12
Only for two wires system, put a jumper
between terminals 11
and 12
N
C For ∆T (2x RTD Pt100) Special
A When the distance between the controller and the
sensor is 15 mt. using a cable of 1.5 mm2 diameter, produces an error on the measure of 1°C.
R1 + R2 must be <320Ω
A
10
R1
B
11
R2
A
12
Use wires of the same
length and 1.5 mm2
size.
20 Ω/lead maximum
resistance.
13
3 - Electrical Connections
B
3.3.2 PV CONTROL INPUT
C
For mA, mV
C1 With 2 wires transducer
Transmitters
V,mV mA
mA
Rj
[1]
4…20mA
11
12
Rj
12
Input resistance = 30Ω per mA
Input resistance > 10MΩ per mV
Input resistance = 10KΩ per Volt
C2 With 3 wires transducer
Transmitters
36 24V–
PV
[1]
mA
11
4…20mA
Rj
12
[1] Auxiliary power supply for external transmitter 24V– ±20%/30mA
max without short circuit protection
14
Using the frequency input,
the IN1 input is not yet available
+5V
10KΩ
36 24V–
PV
11
3.3.3 PV CONTROL INPUT - IN2 FREQUENCY INPUT
• Low level:
0…2Volt /0.5mA max
• High level:
3…24Volt / ~ 0 mA max
• Frequency range:
0…2KHz / 0…20KHz
selectable in configuration
mode
• Use sensors with an NPN output or a clean contact
23
10KΩ
Hz
24
B
3 - Electrical Connections
B
3.3.4 AUXILIARY INPUT
A - From Remote Setpoint
B- From Potentiometer
Current 0/4…20mA
Input resistance = 30Ω
for the measure of the position
of the motor or the valve
Voltage 1…5V, 0…5V, 0…10V
Input resistance = 300KΩ
100% from 100Ω to 10KΩ max
pot.h Operating Total
travel
travel
pot.I distance distance
18
Rj
B
3.3.5 DIGITAL INPUT
• The input is active when the
logic state is ON, corresponding to the contact
closed
• The input is inactive when the
logic state is OFF, corresponding to the contact open
TTL
o.c.
NPN
o.c.
Isolated
contact
3
C1
Com.
5
IL 1
6
IL 2
7
IL 3
C2
C3
0%
19
mV-V
mA
16
Not available with frequency
input
100%
17
18
0%
15
3 - Electrical Connections
B
3.3.6 OP1 - OP2 - OP3 - OP4 - OP5 - OP6 OUTPUTS (OPTION)
The functionality associated to
each of the OP1, OP2, OP4,
OP5 and OP6 output is defined
during the configuration of the
instrument.
The suggested combinations
are:
A
B
D
E
F
G
L
Control outputs
Main Secondary
(Heat)
(Cool)
OP1
Single
action
OP5
OP1
OP2
OP1
OP5
Double
action
OP5
OP2
OP5
OP6
Valve drive
OP1 ▲
OP2 ▼
Alarms
AL1
AL2
AL3
AL4
OP1
OP2
OP2
OP3
OP3
OP3
OP3
OP3
OP3
OP3
OP4
OP4
OP4
OP4
OP4
OP4
OP4
OP2
OP1
OP2
where:
OP1 - OP2
OP3 - OP4
OP5 - OP6
16
Retransmission
Relay or Triac output
Relay outputs
Analogue/ digital control or retransmission outputs
PV / SP
OP5
OP5
OP6
OP6
OP6
OP6
OP6
OP5
OP6
3 - Electrical Connections
3.3.6-A SINGLE ACTION RELAY
(TRIAC) CONTROL OUTPUT
B
3.3.6-C
DOUBLE ACTION
RELAY (TRIAC)/RELAY (TRIAC) CONTROL OUTPUT
Fuse
Fuse
31
OP1
32
[1] Coil of the heat
load contactor
3.3.6-B1 SINGLE ACTION SSR DRIVE
B
CONTROL OUTPUT
Heat
load
OP1
32
[1] Coil of the heat
load contactor
33
Fuse
OP1
32
9
3.3.6-B2 SINGLE ACTION
ANALOGUE OUTPUT
8
OP5
9
mA mV,V
B
Staic
Relay
[1] Coil of the heat
load contactor
8
OP5
Cool
load
B
Coil of the heat
load contactor
3.3.6-D1 DOUBLE ACTION
RELAY (TRIAC)/SSR DRIVE CONTROL OUTPUT
31
8
[1]
OP2
Fuse
OP5
Heat
load
32
31
Static
Relay
B
9
3.3.6-D2 HEAT / COOL CONTROL OUTPUT
RELAY (TRIAC)/ANALOGUE
B
Fuse
31
OP1
32
[1] Coil of the heat
load contactor
8
Cool
load
mA mV,V
OP5
9
17
3 - Electrical Connections
3.3.6-E1 DOUBLE ACTION CONTROL OUTPUT
DIGITAL / RELAY (TRIAC)
Static
Relay
32
8
[1]
OP2
OP5
33
9
Heat
load
B
Fuse
Coil of the heat
load contactor
3.3.6-E2 HEAT / COOL CONTROL OUTPUT
ANALOGUE/RELAY(TRIAC)
8
Heat
load
mA mV,V
B
32
OP5
OP2
9
33
[1]
Fuse
Coil of the heat
load contactor
3.3.6-F1 DOUBLE ACTION CONTROL OUTPUT
DIGITAL / DIGITAL
Static
Relay
Heat
load
18
B
8
20
OP5
OP6
9
21
Static
Relay
Cool
load
Notes for pages 17 - 18 - 19
OP1 - OP2 Relay output
• SPST Relay N.O., 2A/250 V~
for resistive load,
• Fuse 2A~ T
OP1 - OP2 Triac output
• N.O. contact for resistive load of up to 1A/250
V~ max
• Fuse 1A ~ T
Isolated digital outputs OP5-OP6
• 0…24V–, ±20%, 30 mA max
Isolated analogue outputs OP5-OP6
• 0/4…20mA, 750Ω / 15V max
0/1…5V, 0…10V, 500Ω / 20mA max
[1] Varistor for inductive load 24V~ only
3 - Electrical Connections
3.3.6-F2 DOUBLE ACTION CONTROL OUTPUT
DIGITAL / ANALOGUE
Static
Relay
Heat
load
B
V,mV mA
8
20
OP5
OP6
9
21
Cool
load
3.3.6-G MOTOR POSITIONER OUTPUT
RELAY (TRIAC) / RELAY (TRIAC)
Valve drive PID
without potentiometer
3 pole output with NO contacts
(raise, lower, stop)
31
3.3.6-F3 DOUBLE ACTION CONTROL OUTPUT
ANALOGUE / DIGITAL
8
Heat
load
B
mA mV,V
20
OP5
OP6
9
21
Heat
load
mA mV,V
32
OP2
Static
Relay
Raise
V~
Lower
M
~
33
Cool
load
3.3.6-F4 DOUBLE ACTION CONTROL OUTPUT
ANALOGUE / ANALOGUE
8
OP1
B
V,mV mA
20
OP5
OP6
9
21
Cool
load
19
3 - Electrical Connections
NC
Fuse
28
Heat
load
V~
29
mA mV,V
9
30
V,mV mA
AL4 load
[1]
OP4
V~
35
Fuse
31
V~
32
OP2
AL1 load
[1]
[1]
20
OP6
Cool
load
21
e The relay/triac output OP1, OP2, can be
used as alarm outputs only if they are not
used as control outputs.
OP1
MASTER
SLAVE
1
13
2
14
3 C
Fuse
Fuse
34
AL2 load
33
Fuse
[1] Varistor for inductive load 24V~ only
20
B
3.3.9 SERIAL COMMUNICATIONS
B
(OPTION)
OP5
AL3 load
[1]
NO
8
AL3 load
[1]
OP3
C
3.3.8 OP5 AND OP6 (OPTION)
ANALOGUE CONTROL OUTPUTS
OP5 and OP6 outputs can be configured for
control action
or PV / SP retransmission
• Galvanic isolation
500V~/1 min
• 0/4…20mA, 750Ω / 15V– max
0/1…5V, 0…10V, 500Ω / 20mA max
C 15
• Galvanic isolation
500V~/1 min
Compliance to the EIA RS485 standard
for Modbus/Jbus
• Termination setting dip switches
MASTER
1 2 3 4
3.3.7 OP1-2-3-4 ALARM OUTPUTS B
SLAVE
A
Please, read the
user instructions on
the “X5 controllers
MODBUS/JBUS
protocol”
3 - Electrical Connections
B
3.3.10 PROFIBUS DP (OPTION)
DP
DN
DG
VP
1
2
3
4
Termination resistors 220Ω and
390Ω (1/4 W, ±5%) for external
mounting on the initial and ending PROFIBUS stations only.
DP
5
220Ω
390Ω
To make the connections easier, a D-Sub type (9 poles) connector: model AP-ADP-PRESA-DSUB/9P
Must be used with a 9PIN male ERNI type part no. 103648 or similar connector.
9
DN Initial
PROFIBUS
DG station
390Ω
6
VP
• Galvanic isolation
500 V~ / 1 min
• Compliance to the EIA RS485
standard for PROFIBUS DP
• Connecting cable:
twisted pair cable as per
PROFIBUS spec.s
(e.g. Belden B3079A)
• Max lenght:
100 m at 12 Mb/sec
1
4-40UNC-2B
33
DP
DN Other
X5 D-SUB 9 poles
PROFIBUS
Signal
DG stations
1
3
data/transmission
RxD/TxD-P (DP) Receive
data plus
VP
2
8
data/transmission
RxD/TxD-N (DN) Receive
data negative
3
5
DGND (DG)
4
6
VP (VP)
DP
220Ω
DN Ending
390Ω
Description according to
PROFIBUS specifications
PROFIBUS
DG station
390Ω
VP
Data transmission potential
(ground to 5V)
Supply voltage of the terminating resistance-P, (P5V)
Detailed information concerning wiring and cables can be found on
the PROFIBUS Product Guide or on Internet at:
http://www.profibus.com/online/list
21
4 - Operation
4
OPERATION
Digital input status LEDs (yellows)
ó - IL1 active
ò - IL2 active
ô - IL3 active
Status LEDs (greens)
} Communications running
Ä Tuning running
{ Manual operating mode
Ö Timer/Program running
á Program Waiting
Ü Remote Setpoint active
ú
First stored Setpoint active
ù Second stored Setpoint active
û Third stored Setpoint active
4.1.1 KEY FUNCTIONS AND DISPLAYS IN OPERATOR MODE
Over
range
Under
range
____ 8888
8888
----
X5
I1 I2 I3
45.80
50
45.80
PV control input in engineering units
% Control output
or Program status (see page 64)
SP operating Setpoint
(Local/Remote or Stored)
Control output LEDs (red)
å OP1/OP4 ON - ç OP2/OP4 OFF
Run/stop Timer or a program
Alarm status LEDs (reds)
Å AL1 ON
Ç AL2 ON
É AL3 ON
Ñ AL4 ON
Auto/Man
Entry key for selection and value setting confirmation
Setpoint setting
Menu access
22
4 - Operation
4.1.2 KEYS FUNCTIONS AND DISPLAY IN PROGRAMMING MODE
A
The parameter setting procedure
has a timeout. If no keys are
pressed for, at least, 30 seconds,
the controller switches back,
automatically, to the operator
mode.
X5
35.0
P.b.
Parameter value
Parameter mnemonic
After having selected the parameter or the code, press $
and % to display or modify the
value.
Back to the previous parameter
The value is entered when the
next parameter is selected, by
pressing the è key.
Pressing the back key ê or
after 30 seconds from the last
modification , the value doesn't
change.
From every parameter, pressing
the í key, the controller switches to the operator mode.
Entry key for selection
and value setting confirmation
Value modification
Access to the menu for:
- Parameter setting
- Configuration
- Access selection
23
4 - Operation
4.2 PARAMETER SETTING
4.2.1 NUMERIC ENTRY
(i.e. the modification of the Setpoint
value from 275.0 to 240.0 )
Press $ or % momentarily to change the value of 1 unit
every push
Continued pressing of $ or
% changes the value, at rate
that doubles every second.
Releasing the button the rate of
change decreases.
In any case the change of the
value stops when it has reached
the max/min limit set for the parameter.
In case of Setpoint modification:
press $ or % once to display the local Setpoint instead
of working Setpoint.
To evidence this change the display flashes once. Then the
Setpoint can be modified
24
274.8
275.0
274.8
Operator
mode
working Setpoint
displayed
Local
Setpoint display
275.0
4.2.2 MNEMONIC CODES SETTING
(e.g. configuration see page 26)
Press the $ or % to display the next or previous mnemonic
for the selected parameter.
Continued pressing of $ or % will display further mnemonics
at a rate of one mnemonic every 0.5 sec. The mnemonic displayed
at the time the next parameter is selected, is the one stored in the
parameter.
————Lower
274.8
230.0
Setpoint
modification
————Raise
274.8
°C
Unit
°f
Unit
Engineering
Units
Degree
Centigrade
Degree
Fahrenheit
°f
Unit
none
Unit
Degree
Fahrenheit
no units
defined
240.0
after 2 sec.
°C
240.0
Setpoint entry.
The operation is
acknowledged by
one flash of the
display.
°C
Unit
Degree
Centigrade
ph
Unit
Ph
4 - Operation
4.3
CONFIGURATION PROCEDURE
274.8
Conf
Operator
Mode
275.8
33
Configuration
menu
Menu
Enter the configuration
password
from -999...9999
(33 default from factory)
C.pas
Must be equal to the
value
of the parameter
C.Pas (see page.50)
Press the key until
NO
Back to the operator mode
OK
Yes
Inputs
Configuration
InP.
Conf
(see page 26)
Setpoint
Configuration
S.P.
Conf
(see page 27)
Output
Configuration
Out
Conf
(see pages 28 e 29)
Digital inputs
configuration
L.inP
Conf
(see page 30)
Alarm s
configuration
ALM
Conf
Output
Configuration
EHit
Conf
(see page 31)
25
4 - Operation
4.3.1 INPUTS CONFIGURATION
InP.
LINEAR INPUT
ONLY
Conf
é
0
N° of decimals
/1 /2 /3
sc.dd 0
é
0
é0=10
Inp.
range
sc.lo Low
from min range
Input type
see table 1
up to Sc.Hi
é9999
énone
High range
sc.Hi from Sc.Lo
Unit Engineering
Units
see table 2
to max range
éno
Sqr
Square root
no / yes
éno
Linear inputs
CHar characterisation
no / yes
26
Tab. 1 Input type
Value Description
éIPInp.
nP.
32…1112°F
tc. j 0…600°C
0…1200°C
32…2192°F
tc. k
32…1112°F
tc. l 0…600°C
32…2912°F
tc. s 0…1600°C
0…1600°C
32…2912°F
tc. r
tc. t -200…400°C -328…752°F
32…3272°F
tc. b 0…1800°C
32…2192°F
tc. n 0…1200°C
32…2012°F
tc.ni 0…1100°C
0…2000°C
32…3632°F
tc.U3
32…3632°F
tc.U5 0…2000°C
32…1112°F
tc. E 0…600°C
Custom
range
on
request
cuSt
rtd1 -200…600°C -328…1112°F
rtd2 -99.9...300.0°C -99.9…572.0°F
del.t -50.0…50.0°C -58.0…122.0°F
M.50 0…50 mV
M.300 0…300 mV
0=5 0…5 Volt
Engineering
1=5 1…5 Volt
units
0=10 0…10 Volt
0=20 0…20 mA
4=20 4…20 mA
Frq.L 0…2.000 Hz Frequency
Frq.H 0…20.000 Hz (option)
Tab. 2 Engineering units
Value Description U
é nit
none None
°C Degree centigrade
°f Degree Fahrenheit
MA mA
MU mV
U Volt
bar bar
psI PSI
rh Rh
ph Ph
Hz Hertz
4 - Operation
4.3.2 SETPOINT CONFIGURATION
Tab. 3 Setpoint type
Value Description
éSP
. t
. y
Local
only
loc
reM Remote only
l=r Local/remote only
loc.t Local - trim
reM.t Remote - trim
Prog Programmed (option)
S.P.
Conf
éLoc
S.P.ty
Tab. 4 Rem. Setpoint
Value Description
0=5 0…5 Volt
1=5 1…5 Volt
0=10 0…10 Volt
0=20 0…20 mA
4=20 4…20 mA
Setpoint
type
see table 3
éno
S.P.tr Stored
Setpoint Tracking
see page 43
no/ yes
éP.Sec
units
S.P.tM Time
and Setpoint
slope
P.Sec/
P.Min/
P.Hr
érs.In
REMOTE INPUT
ONLY
é4=20
rS.In Remote
Setpoint input
see table 4
is not present if the
frequency input is active
27
4 - Operation
4.3.3 OUTPUT CONFIGURATION
Out
Conf
éOFF
éPid:r
Cn.ty
Control
type
see table 5
éOFF
M.C.OP
Main output
(Heat)
see table 6
S.C.OP
énone
Secondary output
(Cool)
(Heat/Cool only)
see table 7
rt. 1
éno
énone
1st retransmitted
output selection
none / P.U. / S.P.
rt. 2
é4=20
C.OP.5
Cool output on OP5
(Heat/Cool only)
no / yes
éOFF
S.Out
F.Out
O.rt.1
é
Main output
safety value
OFF/ -100…+100%
éOFF
28
WITH OPTIONAL OP6 ANALOGUE
OUTPUT NOT USED AS COOL CONTROL OUTPUT
WITH OP5 ANALOGUE OUTPUT
NOT USED AS CONTROL OUTPUT
é4=20
st
1 retransmission
output
see table 8
0
rt.L1
rt.H1
O.rt.2
é
1st retransmission
low range
whole range
é9999
Main output
forcing value
OFF/ -100…+100%
2nd retransmitted
output selection
none / P.U. / S.P.
2nd retransmission
output
see table 8
0
rt.L2
2nd retransmission
low range
whole range
é9999
1st retransmission
high range
whole range
rt.H2
2nd retransmission
high range
whole range
4 - Operation
Tab. 7
Tab. 5 Control mode
Value Description
éCn.ty
Of.re Reverse action On - Off
Of.di Direct action
pid.d Direct action P.I.D.
pid.r Reverse action
U.dir Direct action Modul.
U.reU Reverse action valves
H.Cl
. n Linear
Heat/
H.CO
. l Oil charac.
Cool
H.CH
. 2 Water charac.
Tab. 6
Value
Off
OP 1
log
0=5
1=5
0=10
0=20
4=20
Main Output
(Heat)
Description
Not used
Relay / Triac
Digital
0…5 Volt
1…5 Volt
0…10 Volt
0…20 mA
4…20 mA
Value
Off
OP 2
log
0=5
1=5
0=10
0=20
4=20
Tab. 8
éMC
. O
. P
Digital
signal
DC
signal
Secondary output
(Cool)
Description
éSC
. O
. P
Not used
Relay / Triac Digital
Digital
signal
0…5 Volt
1…5 Volt
DC
0…10 Volt
signal
0…20 mA
4…20 mA
Retransmission
outputs
Value Description
0=5 0…5 Volt
1=5 1…5 Volt
0=10 0…10 Volt
0=20 0…20 mA
4=20 4…20 mA
éOr
. t.1
éOr
. t.2
RETRANSMISSION
When OP5 and OP6 outputs are
not configured as control output, they can retransmit the PV
or SP linearised value.
Retransmitted
signal
none P.U. / S.P
r
# t. 1
r
# t. 2
O
# r
. t.I
O
# r
. t.2
Output
range
0=5 /1=5 /0=10
0=20 / 4=20
r
# t.H1
r
# t.H2
Retransmission
high
range
Example:
• T/C S,
range 0…1600°C
• Output range, 4…20 mA
• Retransmitted signal PV on
800…1200°C range
mA
20
The following parameters define
the low and high range.
Retransmission
low
range
#retr = 4=20
#rt.H = P.U.
#rt.L1 = 800
#rt.H1 =1200
r
# t.L1
r
# t.L2
4
°C
800 1200 1600
With
rt. l I greater than
rt.H1 it is possible to obtain
a reverse scale.
29
4 - Operation
4.3.4 DIGITAL INPUTS CONFIGURATION
L.inp
Conf
éOFF
IL1
IL1 digital input
function
see table 10
éOFF
IL2
IL2 digital input
function
see table 10
éOFF
IL3
30
IL3 digital input
function
see table 10
Tab. 10 Digital Inputs
éIl1
functions
éIl2
Value Description
éIl3
Not
used
Off
l=r Local/Remote
A.Man Auto/Man
s.p. 1 1st stored Setpoint
s.p. 2 2nd stored Setpoint
s.p. 3 3rd stored Setpoint
keb.I Keyboard lock
slo.1 s.p. slope disable
H.pU Measure hold
F.Out Output forcing mode
Prg.1 1st program
up to
Prg.2 2nd program
rd
3
Prg.3 3 program
th
Prg.4 4 program
r.=H. Program Run/Stop
rSt Program reset
BLck Reset blocking
4.3.5 ALARM S CONFIGURATION
ALM
Conf
éOFF
alarm type
AL. 1 AL1
see table 11
NOT AVAILABLE
OF
[1] OP1 and OP2 outputs can be
used as alarm outputs if they
are not used as control outputs.
AL. 1 = OFF
éOP1
addressing
A1.Ou AL1
OP1 / OP2 [1]
OP3 / OP4
éno
[2] OP3 and OP4 can be related
to the program (if option
installed).
AL1 latching
/ yeS
Ltch no
éno
bloc
AL1 start-up
disabling
no / yeS
[2]
4 - Operation
Tab. 11 Alarm type
éOFF
éOFF
alarm type
AL. 2 AL2
see table 11
éOFF
alarm type
AL. 3 AL3
see table 11
alarm type
AL. 4 AL4
see table 11
Value
Off
NOT AVAILABLE
OF
NOT AVAILABLE
AL. 2 = OFF
éOP2
A2.Ou
OF
AL. 3 = OFF
éOP3
AL2 addressing
OP1 / OP2 [1]
OP3 / OP4 [2]
éno
A3.Ou
Ltch
bloc
AL2 start-up
disabling
no / yeS
éno
OF
AL. 4 = OFF
fs.H
fs.l
éOP4
AL3 addressing
OP1 / OP2 [1]
OP3 / OP4 [2]
éno
AL21 latching
no / yeS
NOT AVAILABLE
A4.Ou
AL4 addressing
OP1 / OP2 [1]
OP3 / OP4 [2]
éno
Ltch
AL3 latching
no / yeS
bloc
AL3 start-up
disabling
no / yeS
éno
Ltch
AL4 latching
no / yeS
bloc
AL4 start-up
disabling
no / yeS
deU.H
deU.l
band
éAl 1
éAl 2
éAl 3
Description éAl 4
Not used or used by the
programme (AL3/AL4)
High
active
Absolute
Low
active
High
active
Deviation
Low
active
Out
Band
active
lba Loop break alarm
éno
31
4 - Operation
4.3.6 AL1, AL2, AL3, AL4 ALARMS CONFIGURATION
[A] OPERATING
CONDITIONS
It is possible to configure up to 4
alarms: AL1, AL2, AL3, AL4 (see
page 31) selecting, for each of them:
A the type and the operating condition of the alarm (table 11 page
31)
B the functionality of the alarm
acknowledge (latching) #ltch
C the start-up disabling (blocking)
Absolute alarm
#bloc
D the physical output of the alarm
O
# pI
#Op4
O
# p2
Alarm occurrence display
This function can be enabled by
the configuration software.
(please read the user instruction
on the "X5 LINE MODBUS
/JBUS PROTOCOL", supplied
separately)
O
# p3
The outputs can be used for
alarms if they are not used as control outputs
(see par. 3.3.7 page 20)
It is possible to route up to 4 alarm
to a single output (OR of the alarms).
On
Active high
é-fsH
Off
hyd hyu
On
Active low
é-fsl
Off
Low range
The type of alarm is presented
flashing, on the front panel in
alternation with the PV value.
[D] LOOP BREAK ALARM LBA
Alarm threshold
High range
Deviation alarm
On
SP
Active high
é-deH
Off
hyd hyu
3deH
On
Active low
é-del
Off
∆SP
- range
275.0
+ range
Alarm threshold
Band alarm
mA
SP
On
Active out
é-bnd
The red led of the activated
alarm output is on.
32
When the controller connection to
the sensor is discontinued or other
faults are detected in the control
loop, the AL1 alarm becomes
active, after a predefined time of 1
to 9999 sec., from the detection of
the failure. (see page 22)
The alarm state ceases when the
fault condition is no longer present.
Off
hyd hyu
∆SP
full scale
°C
hyd hyu
∆SP
full scale
Alarm threshold
e In case of ON-OFF control, the
LBA alarm is not active.
4 - Operation
[B] ALARM
ACKNOWLEDGE
FUNCTION
ILba
The alarm, once occurred, is presented on the display until to the time
of acknowledge. The acknowledge
operation consists in pressing any
key.
275.0
OP1
Yes
Ltch
[C] START-UP DISABLING
Yes
Bloc
∆SP
SP
Disable
ramp
down
On
Off
Start-up
SP
∆SP
Disable
∆SP
threshold
=
SP± range
ramp
up
On
Off
Start-up
After this operation, the alarm leaves
the alarm state only when the alarm
condition is no longer present.
33
4 - Operation
4.4
PARAMETERISATION - MAIN MENU
274.8
Operator
mode
A
275.0
The parameter setting procedure
has a timeout. If no keys are
pressed for, at least, 30 seconds,
the controller switches back, automatically, to the operator mode.
Setpoint
programmer menu
(if the option is installed)
Setpoint
menu
S.P.
Prog
Menu
Menu
(see page 36)
34
Alarm
menu
AL
Menu
(see pages 62 and 63)
(see page 37)
PID
menu
PId
Menu
(see page 38)
Tuning
menu
Tune
Menu
(see page 39)
4 - Operation
After having selected the parameter or the code,
press $ or % to modify the value (see page
24) The value is entered when the next parameter
is selected, by pressing the è key.
Pressing í go back to the Operator mode
Input
menu
InP
Menu
(see page 39)
Output
menu
Out
Menu
(see page 40)
Communication
menu
Access
menu
Configuration
menu
CoMM
AccS
Conf
Menu
Menu
Menu
(see page 41)
(see page 50)
(see page 25)
35
4 - Operation
S.P.
éLoc
Setpoint menu
4.4.1 PARAMETERISATION - SETPOINT MENU
L=r
Depending on the configuration index shown on page 27, the
following parameters are present or not.
Setpoint selection
local/remote
Loc / reM
Menu
LOCAL ONLY
# oc
INDEX L
LOCAL/REMOTE,
REMOTE OR PROGRAMMED
# =r r
# eM P
# rog
INDEX L
[1] The units of the slope parameters are Digit/sec, digit/min. digit/hr
LOCAL OR REMOTE WITH TRIM ONLY
# oc.t r
# eM.t
INDEX L
énone
S.Sel
é
0
S.SP
. 3
S.P. 1 1st stored
Setpoint
full scale
é
0
S.P. 2
é
é
rtio
Ratio Setpoint
-9.99…99.99
éH.réange
0
Bias
Setpoint
limit
S.P. L low
full scale
Remote
Setpoint bias
full scale
Setpoint
limit
S.P. H high
full scale
éOFF
2nd stored
Setpoint
full scale
0
S.P. 3
éL.réange
é 1:00
Stored Setpoint
selection
none/ S.LOC/
S.SP
. 1 / S.SP
. 2/
Slope up
SL. u 0ff/1…9999
digit/..[1]
éOFF
3th stored
Setpoint
full scale
Slop down
/1…9999
SL. d 0ff
digit/..0ff/1…9999
digit/..[1]
36
4 - Operation
4.4.2 PARAMETERISATION - ALARMS MENU
AL
é
1
Alarms
menu
é
1
1 hysteresis
hy.Iu Alarm
asymmetric upper
Menu
é
1
0…5% Span
in engineering units
hy.3u
é
1
é
1 hysteresis
hy.Id Alarm
asymmetric lower
0
é
1
é
threshold 1
1--- Alarm
[1] see table
tf1é
é
Alarm threshold 2
[1] see table
hy.2u
é
0
é
threshold 3
3--- Alarm
[1] see table
0
4---
é
Alarm delay
OFF/1...9999
1
é
Alarm 2 hysteresis
asymmetric upper
0…5% Span
in engineering units
1
hy.4u
é
1
hy.4d
tf2-
é
Alarm delay
OFF/1...9999
Type and value
Alarm 4 hysteresis
asymmetric upper
0…5% Span
in engineering units
Alarm 4 hysteresis
asymmetric lower
0…5% Span
in engineering units
Mode
N° and
Param.
Absolute
full scale
Active high
Deviation
full scale
Active high
Band
full scale
Active
out of band
-bnd
L.B.A.
Active high
1…9999 sec
-lba
1
0…5% Span
in engineering units
1
Alarm 3 hysteresis
asymmetric lower
0…5% Span
in engineering units
delay
tf3- Alarm
OFF/1...9999
2 hysteresis
hy.2d Alarm
asymmetric lower
é
Alarm threshold 4
[1] see table
0…5% Span
in engineering units
1
0
2---
hy.3d
Alarm 3 hysteresis
asymmetric upper
0…5% Span
in engineering units
[1] A code, specifying the n° and the
alarm type that has been configured
(see page 31), is displayed. At this
point, the user must enter the threshold value, according to the following
table.
Active low
Active low
-fs.H
-fs.l
-de.H
-de.l
1
Alarm delay
tf4- OFF/1...9999
37
4 - Operation
4.4.3 PARAMETERISATION - PID MENU
PID
(not shown for ON-OFF control action)
Menu
PID
Menu
é
5:0
P.b.
é
éOFF
Proportional
band
0.5…999.9%c.s.
60
t.i.
38
band
P.b. C Proportional
Cool channel
0ff/0.1...10.0 digits
O.C.
é 50:0
Derivative
time
0ff/0.1…999.9 sec
5:0
d.Err Error
dead band
0.5…999.9%c.s.
é 1:00
Integral
time
0ff/1…9999 sec
é 12:0
t.d.
é
M.reS
Overshoot control
0.01…1.00
(not displayed if
Heat/Cool)
Manual reset
0ff/1…100% output
(not displayed if
Heat/Cool)
Heat / Cool
Algorithm
OK
YES
é
60
Integral time
t.i. C Cool
0ff/1…9999 sec
NO
é 12:0
Derivative time
t.d. C Cool
0ff/0.1…999.9 sec
4 - Operation
4.4.4 PARAMETERISATION
TUNING MENU (not shown for ON-OFF control action)
Tune
4.4.5 PARAMETERISATION
INPUT MENU
for AT
Tuning
menu
#No
InP
OK
Menu
Input
menu
Menu
#yeS
p.b.
Calculated Proportional
band [1] (display only)
(available when adaptive
tune is selected)
t.i.
Calculated Integral
time [1] (display only)
(available when adaptive
tune is selected)
éOFF
Filter time constant
t.FiL (user enabled/disabled)
éno
Off/0.2…99.9 seconds
é
tune
Initial
tune start
(One shot tune)
no/yes
AdPt
Continuous
Tune start
Adaptive Tune (A.T.)
no/yes
t.d.
0
Calculated derivative
time [1] (display only)
(available when adaptive
tune is selected)
éno
Measure bias
é
In.Sh -60…60 digit
[1] These values
are not automatically stored on the
PID menu parameters P.b.,t.i.,t.d.
0:11
T.SaM
Sampling time
0.1…10.0 seconds
39
4 - Operation
4.4.6 PARAMETERISATION - OUTPUT MENU
é 10:0
Out
Output
menu
Menu
t.c.
é
Cycle time
(time proportional only)
0.2…100.0 sec
0:0
Control Output low limit
Valve drive
algorithm
OP. L (not available in
é100:0
Heat/Cool configuration)
0…100%
60
Control output
é
MU.tM
limit
OP. H high
0…100%
On-Off
Algorithm
PID
Algorithm
é Off
OP.r
é Off
é
St.OP
1
hysteresis
Op.hy Output
0…5% Span
in engineering units
40
é
10
ST.tM
é
Control output
rate limit
(user enabled/disabled)
0ff/0.01…99.99%sec
é
Motor travel time
15…600 seconds
0:5
MU.hy
Heat / Cool
Algorithm
0:5
d.bnd
Dead band
0.0…5.0%
é 10:0
Minimum
output step
0.1…5.0%
t.c. C
Cool
cycle time
(time proportional only)
0.2…100.0 sec.
é100:0
Control Output
soft start value
(user enabled/disabled)
0ff/1…100%
OP.C.H
Cool control output
high limit
(PID only)
0.0…100.0%
é Off
Soft start function
activation time
1…9999 sec.
Op.rC
Cool output rate limit
(user enabled/disabled)
0ff/0.01…99.99%sec
4 - Operation
Serial
communication
menu
CoMM
Menu
é
RS485 Modbus/Jbus
SLAVE
4.4.7 PARAMETERISATION - SERIAL COMMUNICATION MENU
Depending on serial communication choosen (see model code on page 5), there are the following parameters:
RS485 Modbus/Jbus
SLAVE + PROFIBUS DP
Index
c= 5
1
é
address
Add.S SLAVE
communication
(if option installed)
0ff
RS485 Modbus/Jbus
SLAVE + MASTER
Index
c= 6
1
Add.S
/ 1…247
éno
é9600
SLAVE baud rate
bdr.S 1200/2400
MaSt
4800/9600/19200
éJbuS
bdr.M
MbuS / jbuS
énone
bdr.S
PAr.y none/EVEn/odd
Pro.M
SLAVE baud rate
1200/2400
4800/9600/19200
éJbuS
MASTER baud rate
Pro.S
1200/2400
4800/9600/19200
éJbuS
Parity
SLAVE address
communication
(if option installed)
0ff / 1…247
é9600
MASTER
enable
no / yeS
é9600
Pro.S SLAVE
communication protocol
Index
c= 7-8
é
MASTER
communication protocol
MbuS / jbuS
Communication
protocol
MbuS / jbuS
3
Add.P
PROFIBUS DP
address
3…124
41
4 - Operation
4.5
PARAMETERS
For a simpler use of the controller, its parameters have been
organised in menu, according to
their functionality area.
4.5.1 SETPOINT MENU
Setpoint
low limit
Setpoint
high limit
High and low limit of the
Setpoint SP.
The minimum span (S.P.L - S.P.H)
must be greater than 100 digit.
S
# P
. . L
S
# P
. . H
Otherwise, the Setpoint value is
reached according to the configured rate of change.
The new Setpoint value is called
"Target Setpoint". It can be displayed by means the parameter
#t.S.P.
(see procedure at page 53).
Setpoint
ramp up
Setpoint
ramp down
This parameter specifies the
maximum rate of change of the
Setpoint.
Adjustable in digit/sec.,digit/min,
and digit/hour (see page 27)
s
# l. u
s
# l. d
When the parameter is OFF,
this function is disabled and
the new Setpoint is reached
immediately after being
entered.
42
When Remote Setpoint is configured, we suggest to disable
#sl. u and #sl. d parameters
Off.
Target Setpoint
= 350°C
Example
Setpoint
change
Initial
Setpoint
= 250°C
#sL. u
= 10
digit/minute
t
t = 10
1st stored
Setpoint
2nd stored
Setpoint
3th stored
Setpoint
Values of the three Setpoints,
that are activated by mean of
logic inputs, communication
parameters, and keyboard. The
Setpoint active is indicated by
the ú, ù or û green led.
S
# P
. . 1
S
# P
. . 2
S
# P
. . 3
See also page 56.
4 - Operation
Stored Setpoint
tracking
(see chapter 4.3.2 at page 27)
Two different operation mode
can be set:
A- Stand-by mode # no
The memorised Setpoint is
active until its command is
active too. Then the controller
goes back to the Local Setpoint
which becomes the operating
one.
S
# P
. t
. r
B- Tracking mode #yeS
Once the memorised Setpoint is
active, it remains operating also
when it command is not active
anymore.
The previous Local Setpoint
value will be lost.
Remote
Setpoint Ratio
Ratio is the coeff. which defines
the remote Setpoint span with
respect to the input span.
r
# tio
Remote
Setpoint
Bias defines the starting point of
analogue Remote Setpoint in
eng. units corresponding to the
low limit (current or voltage) of
the remote signal.
Remote Setpoint Bias and Ratio
Remote
signal
ab
bias = 20
ratio = 0.1
10V
a´ b´
bias = 100
ratio = –0.1
b
# ias
Range
-200
LR
0
100
20
a (b´ )
b (a´ )
Remote
Setpoint span
PV =
LR =
HR =
SR =
a (a´) =
b (b´) =
600 °C
HR
Process variable
PV low limit
PV high limit
Remote Setpoint
SR starting point
SR ending point
43
4 - Operation
4.5.1 MENÙ SETPOINT
If SR starting point is lower then
the ending point, both
expressed in engineering units:
If SR starting point is higher
then the ending point, both
expressed in engineering units
biaS= starting point = a
biaS= starting point = a´
rtio=
b-a
HR - LR
Example:
biaS= 20
rtio=
100 - 20
80
=
= 0.1
600 - (-200)
800
rtio=
b´ - a´
HR - LR
Example:
biaS= 100
rtio=
20 - 100
- 80
=
= - 0.1
600 - (-200)
800
Working Setpoint (SP) as
combination
of
Local
Setpoint (SL) and remote signal
Setpoint type Loc.t
(table 3, page 27)
SP = SL + (rtio • REM)
+ biaS
Setpoint type reM.t
(table 3, page 27)
SP = REM + (rtio • SL)
+ biaS
SIGN = Remote signal
percentage
SPAN = HR-LR
REM =
44
SIGN * SPAN
100
Examples:
Local Setpoint (SL) with an
external Trim with multiplying
coeff. of 1/10:
Setpoint type = Loc.t
rtio= 0.1
biaS= 0
Remote Setpoint (SR) with an
internal Trim with multiplying
coeff. of 1/5:
Setpoint type = reM.t
rtio= 0.2
biaS= 0
Remote Setpoint range equal to
the Input range:
Setpoint type = Loc.t
rtio = 1
biaS= LR
SL = 0
4 - Operation
4.5.2 ALARM MENU
(see also pages 32 and 33)
Asymmetric
upper alarm
hysteresis
h
# y-u
h
# y-d
Asymmetric
lower alarm
hysteresis
Example with high absolute alarm
Alarm threshold
Alarm
delay
Delay time for alarm activation.
OFF: alarm activated immediately
1...9999: alarm activated only if
the condition persists for the set
time
t
# F1
4.5.3 PID MENU
Not present with On-Off main
output.
Proportional
Band
Cool Proportional
Band
This parameter specifies the proportional band coefficient that
multiplies the error (SP - PV)
p
# b
. .
p
# b
. . C
On
Integral
Time
Cool integral
Time
It is the integral time value, that
specifies the time required by the
integral term to generate an output
equivalent to the proportional term.
When Off the integral term is not
included in the control algorithm.
t
# i
. .
t
# i
. . C
Off
#hy-d = #hy-u
The parameter can be set
between 0 and 5% of the configured Span and set in
Engineering units. e.g.
Range
= -200…600°C
Span
= 800°C
Max Hysteresis = 5% 800°= 40°C
Derivative
Time
Cool Derivative
Time
It is the time required by the proportional term P to reach the level of
D. When Off it is not included.
t
# d
. .
t
# d
. . C
Overshoot
control
(Automatically disabled when the
adaptive tune is running)
This parameter specifies the
span of action of the overshoot
control. Setting lower values
(1.00—>0.01) the overshoot
generated by a Setpoint change
is reduced. The overshoot control doesn’t affect the effectiveness of the PID algorithm.
Setting 1, the overshoot control
is disabled.
O
# C
. .
For symmetrical hysteresis set
=h
# y-u
h
# y-d
45
4 - Operation
4.5.3 PID MENU
4.5.4 TUNING MENU
Manual
reset
This term specifies the value of
the control output when PV = SP,
in a PD only algorithm (lack of
the Integral term).
See page also 57
M
# r
. es
Error
Dead Band
Inside this band for (PV - SP), the control output does not change to protect the actuator (output Stand-by)
d
# e
. rr
(not shown for ON-OFF main control output)
Two tuning method are provided:
• Initial one shoot Fuzzy-Tuning
• Continuous, self learning
Adaptive Tuning
The Fuzzy-Tuning determines
automatically the best PID term with
respect to the process behaviour.
The controller provides 2 types of
“one shot” tuning algorithm, that
are selected automatically according to the process condition when
the operation is started.
STEP response
tuning start
PV variable
End of the tuning
operating and setting
of the new calculated
terms.
Control output
SP
Setpoint change
PV variable
End of the tuning
operating and setting of
the new calculated
terms.
Start of autotune
operation
Control output
This type is selected when, at
the start of the autotune operation, the PV is far from the
Setpoint of more than 5% of the
span. This method has the big
advantage of fast calculation,
with a reasonable accuracy in
the term calculation.
46
Natural frequency
This type is selected when the PV
is close to the SP Setpoint.
This method has the advantage
of a better accuracy in the term
calculation with a reasonable
speed calculation.
The Fuzzy Tuning determines
automatically the best method
to use to calculate the PID
term, according the process
conditions.
4 - Operation
4.5.5 INPUT MENU
The self-learning adaptive autotune is not intrusive. It doesn’t
affect the process, at all, during
the phase of calculation of the
optimal terms parameters.
Continuous adaptive tune
Perturbation
New
parameters
It is particularly suitable for
controlling process whose
control characteristics change
with time or are not linear in
relation to the Setpoint values.
It doesn’t require any operation
by the user. It is simple and
works fine: it samples continuously the process response to
the various perturbations, determining the frequency and the
amplitude of the signals. On the
basis of this data and their statistical values, stored in the
instrument, it modifies automatically the PID term parameters.
It is the ideal for all applications
where it is required to change
continuously the PID terms parameters, in order to adjust the PID
to the changes of the process
dynamic conditions.
In case of power off with the
Adaptive Tune enabled, the
values of the PID terms parameters are stored, in order to
be reused at the next power
on.
At power on the Adaptive Tune
starts automatically.
Input
filter
Time constant, in seconds, of
the RC input filter on the PV
input. When this parameter is
Off the filter is bypassed.
t
# f
. il
Filter response
Sampling
Time
Sampling time, in seconds, of
the instrument. This parameter
is normally used when controlling slow process, increasing the
sampling time from 0.1 to 10
seconds.
t
# S
. aM
100%
63,2%
0 Filter
time
PV
Time
Measure
Bias
This value is added to the measured PV input value. Its effect
is to shift the whole PV scale of
its value (±60 digits).
I
# n.sh
47
4 - Operation
4.5.6 OUTPUT MENU
O
# p.hy
Control output
hysteresis
SP
On
Off
O
# p. l
Control Output
low limit
It specifies the minimum value of
the control output signal.
It is applied in manual mode, too.
Soft start of the
control output
It specifies the value at which
the control output is set during
the start up phase.
Control output
high limit
Cool output
high limit
It specifies the maximum value
the control output can be set. It
is applied in manual mode, too.
Soft start
time
This value specifies the time the
start up phase lasts. The start
up phase starts at power up of
the controller
s
# t.Op
hy
The parameter can be set
between zero and 5% of the
configured Span and set in
Engineering units.
e.g.
Range
= -200…600°C
Span
= 800°C
Max Hysteresis = 5% 800°= 40°C
Control output
cycle time
Cool
cycle time
It’s the cycle time of the logic
control output. The PID control
output is provided by the pulse
width modulation of the waveform.
t
# c
. .
t
# c
. . C
48
O
# p. H
O
# p.CH
.
Heat output
maximum rate
Cool output
maximum rate
This value, specified in %/seconds, with range from 0.01 to
99.99%/sec. provides the maximum rate of change of the output. When set to Off this function is disabled.
O
# p.r
O
# p.rC
s
# t.tM
OP
100%
Soft-Start
phase
Time
Start-up
Travel
time
It provides the time required to
the motor positioner to go from
the 0% position to 100%
M
# U.tM
Heat/Cool
deadband
This parameter specifies the
width of the deadband between
the Cool and the Heat channel
d
# b
. nd
#Op.r
Speed in
%/sec
#st.Op
Minimum
step
It specifies the minimum allowed
time of activation of the output
to a motor positioner that produces a sensible effect. It is
related to the deadband of the
positioner
M
# U.hy
Heat / Cool Algorithm
Heat
100%
Heat
Cool
#OpC.H
#Op.H.
SP
P.b.
d.bnd P.b. / C
0
100%
Heat output
0
100%
Cool output
4 - Operation
4.5.7 SERIAL COMMUNICATION MENU (OPTION)
SLAVE address
communication
- 1…247
SLAVE
Profibus DP
address
- 3…124
Three serial comm.s options
are available:
All the instrument connected to
the same supervisor must have
different addresses.
If set Off the serial comm.s is
not active.
SLAVE
Baud rate
MASTER
Baud rate
It provides the baud rate in the
range from 1200 to 19.200
bit/sec.
Parity
B - Modbus/Jbus MASTER
with Mathematical package
Mathematical package
The transmission and inquiry of
parameters value to all the
devices using Modbus/Jbus
SLAVE (e.g. PLC, etc.) is
allowed.
A
# dd.S
A
# dd.P
b
# dr.S
b
# dr.M
P
# Ar.y
May be set even EVEn or odd
odd.
If None is set, parity will be
excluded.
A - Modbus/Jbus SLAVE
The parameters value can be read
and when possible modified.
X5 45.80
50
45.80
RS485
Modbus/Jbus
X3
C1
Industrial standard for peripheral
devices connection to a machine
in a plant.
45.80
45.80
125.4
The mathematical package can
manipulate the received data by
means the serial comm.s.
MASTER
SLAVE 1
SLAVE 2
SLAVE 3
Example:
The MASTER (X5) reads the
process variable from SLAVE 1
(C1) and SLAVE 2 (X3). It compairs the two values and send the
higher to the SLAVE 3 (PLC).
The available math. operations
are:
+
C - PROFIBUS DP SLAVE
(Process Field bus protocol)
-
*
/
> <
The protocol installed in this controller, offers the following advantages against the standard normally
supplied by other suppliers:
• Communications baudrate
Up to 12 Mb/sec with
electric isolation.
• The list of data transfer (profile
file) is user configurable.
It can be set by means the
configuration software (see
separate manual)
To define the controller operations
of this option, the configuration
software must be used (see separate user manual).
49
4 - Operation
4.6
PARAMETERISATION - ACCESS MENU - PASSWORD - CALIBRATION
274.8
275.8
Operator
mode
Pressing í
go back to the Operator
mode
[1] With the level of access set to full,
all the related parameters are displayed.
Press until
AccS
Menu
fUll
Ac.le
A.pas
Enter password
for access enable
none
EHec
If the password entered corresponds to the one stored in the
A.pas [A] parameter, the
access configuration page is
displayed.
yes
YES
OK
NO
50
Oper
Execute
the following
operations
C.pas
Operator
level Access
Ac.le
Access
menu
from -999 to 9999
(11 default value from factory)
11
Access
to all the levels
[1]
E.AMn
A/M enable
/ nO
EHec
33
C.pas
Change the
Configuration
password
Enter
the Configuration
password
4 - Operation
X5
45.80
50
45.80
Edit
Ac.le
A.pas
EHec
II
A.pas
During the up-download of the data
to/from the Memory chip, the controller
display shows the segment clockwise
rotation of the digits.
Access
to the edit level
Change
the Access password
Enter [A]
the Access
password
load
Load the data
from Memory chip
stor
EHec
EHec
Confirm and return
back to the
Operator mode
Download the data
to Memory chip
C.pot
EHec
O
pot.l
255
pot.H
Calibrate
the potentiometer
(if present)
The valve
go to low scale
When the indication
(the valve) is stopped,
confirm the calibration value using
$ or %
The valve
go to full scale
51
4 - Operation
4.6
PARAMETERISATION - ACCESS MENU - PASSWORD - CALIBRATION
With the access level Edit, the
user defines which groups and
parameters are accessible to
the operator
After selecting and confirming
the access level Edit, enter in the
parameters menu.
The code of the access level is
displayed on the front panel.
Press the $% keys to select
the proper level.
Group of parameters
pId
Menu
Group of parameters
35.0
p.b.
Code
read
Hide
Code
AItr
fast
read
Hide
Access level
Visible
Not visible
The parameters in the access
level fast are recalled on the
front panel through the procedure of fast parameter
access illustrated in par. 5.2
page 53. The maximum number
of fast parameters is 10.
Access level
Visible and changeable
Included in “Fast view”
Visible only
Not visible and not changeable
At the end of the parameter list
of the selected group, the controller quits from the Edit access
level.
Therefore, the Edit level must
be selected for each group of
parameters
The access level of groups and
parameters, is activated through
Oper
Ac.le
Confirm
52
Access
level operator
5 - Displays
5
DISPLAYS
5.1 STANDARD DISPLAY
5.2
FAST VIEW
(fast access to the parameters)
274.8
63
275.0
Manual
mode
274.8
63
275.0
Operator mode
Automatic mode
Fast view
parameter
no
Product
identification
274.8
°C
Engineering
units
00A
rel.
tune
365.8
Software
release
63.0
Op
Main output
(during the program
run only)
3fs.H
One shot
tune start
no/yes
Alarm 3 threshold
(high absolute
alarm)
full scale
A B C D
3150
Hard
Base
product code
(see page 5)
Back to the Operator mode
300.0
t.s.p.
Target
Setpoint value
local mode only
(not displayed if the
Slopes are disabled)
none
s.sel
With this procedure, simple and
fast, up to 10 parameters, selected through the fast view (see par
4.6 page 52) are displayed and
can be modified by the operator without requiring the standard parameter setting procedure.
Press $% in order to modify the parameters
The value is entered by pressing è key
On left side, please find as an
example a list of parameters on
Fast view menu.
Stored Setpoint
selection
none/s.LOC/
s.sp
. I
. /s.sp
. 2
. /
s.sp
. 3
.
Back to the Operator mode
53
6 - Commands
6
COMANDS
COMMANDS TO THE CONTROLLER AND OPERATING PHASES
The commands can be
entered in 3 ways:
6.1 KEYPAD
see page 55
•
•
•
•
•
•
54
Setpoint modification
Manual mode
Local/remote selection
Stored Setpoint display
Tune Run / Stop
Program start/stop
(see page 66)
6.2 DIGITAL INPUTS
see page 58
6.3 SERIAL
COMMUNICATIONS
see the manual on this topic
6 - Commands
6.1 KEYPAD COMMANDS
6.1.1 SETPOINT MODIFICATION
The Setpoint is directly modified with the $% keys.
Once entered, the new value is
checked and becomes operating
after 2 seconds. The end of this
phase is flagged by flashing
momentarily the display with SP.
6.1.2 AUTO/MANUAL MODE
274.8
63
275.0
Operator
mode
Modified
Setpoint value
350.0
after 2 seconds
274.8
350.0
{
led on
Example of
Setpoint modification from 275.0 to
350.0
274.8
Select
manual
green
Flash momentarily
the SP value to
confirm that it has
become operating.
back to the operator mode
274.8
274.8
63
275.0
63
275.0
Modification of control
output value
A
The new value is immediately
working without any confirm.
Modify
the output
value
Back to the
operator mode
274.8
35
275.0
Operator
mode
(automatic)
The bumpless action is present
switching between AUTO, MAN
and vice versa.
AUTO
100%
Setpoint SP
SP (PV)
AUTO
MAN
PV
SP
Op.r
SP = PV
0
100% output OP OPMAN=OPAUTO
change
Y
OP
O
OP
co
OPAUTO=OPMAN
0
AIn case of power failure, the
AUTO/MAN status and the
output value remain stored in
the controller memory.
55
6 - Commands
6.1.3 LOCAL/ REMOTE SELECTION
274.8
6.1.4 STORED SETPOINTS SELECTION (see also pages 42, 43)
S.P.
275.0
The Setpoint is directly modified with the $% keys.
Once entered, the new value is checked and becomes operating
after 2 seconds. The end of this phase is flagged by flashing momentarily the display with SP.
Menu
Stored
Setpoint
displays
Local/remote
selection
Select
remote
Back to the
operator mode
56
s.sel
loc
S.LOC
l=r
s.sel
reM
l=r
The selected
Setpoint becomes
operating pressing the
loc
l=r
1st stored
Setpoint
s.s.p.1
s.sel
è
When in Remote,
the green led
Select
local
none
2nd stored
Setpoint
Ü
is on
3th stored
Setpoint
Back to the operator mode
The selected Setpoint
becomes operating
pressing the
è key.
The three
ú ù û
s.s.p.3
s.sel
leds flag the Setpoint
operating.
6 - Commands
6.1.5 TUNE RUN / STOP
This controller is provided with
2 different Tuning algorithm:
• Fuzzy tune (one shot tune)
for calculating the optimal PID
terms parameters
• Adaptive Tune (continuous tune)
for a continuous calculation of
the PID terms parameters.
274.8
Press until
Fuzzy Tune
start-up
no
no
tune
Adpt
Operator
mode
275.0
Confirm
yes
to start
yes
tune
press until
Confirm
Tune
Menu
Adaptive Tune
start-up
Tuning
menu
no
to stop
no
The command start/stop
is executed pressing the
è key.
When the controller is
calculating the PID parameters, the green Ä
led is ON.
tune
After the execution of the tuning, the
calculated values are automatically
presented in the PID menu.
Confirm
yes
to start
Confirm
no
to stop
yes
Adpt
no
Adpt
The command
start/stop is executed
pressing the
è key.
When the controller is
calculating the PID
parameters, the green
Ä led is flashing
(blinking)
When this function is in progress, the
calculated values are visible in the
Tuning menu but cannot be modified.
57
6 - Commands
6.2
DIGITAL INPUTS
COMMANDS
A function is assigned, through
the configuration procedure to
each IL1, IL3 and IL3 digital
input. (see the parameters setting at tab. 10 at page 30).
The configured function is activated when the digital input (free
voltage contact or open collector output) is in the On state
(closed). It is deactivated by setting the input to the Off state
(open).
The activation of the function
through the digital input has the
highest priority than through the
keypad or through the serial
communication.
6.2.1 DIGITAL INPUTS COMMANDS FOR LOCAL-REMOTE SETPOINT
Function
1st stored
Setpoint
O
# FF
A
# M
. an
k
# eb.I
H
# p
. U
S
# lo.1
F
# O
. ut
s
# p
. . 1
2nd stored
Setpoint
3th stored
Setpoint
None
Set manual mode
Keyboard lock
PV
measure hold
Setpoint slopes
inhibition
Output forcing mode
Set Remote
mode
Reactivation
of blocking
58
Parameter
value
Performed operation
Off
On
—
—
Automatic
Manual
Unlock
Locked
Normal
operation
Rate limiting
is active
Normal
output
PV is hold
Normal
operation
Forced
output
Local
1st SP
s
# p
. . 2
Local
2nd SP
s
# p
. . 3
l
# =r
b
# LcK
Local
3th SP
Local
Remote
—
Notes
Not used
With the keypad locked the commands from
digital inputs and serial communications are
still operating
The value of PV is “frozen” at the time the digital
input goes to the close state
When the input is in the on state, the Setpoint is
changed in steps
With ON command the output is equal to the
forced value ( see page 28)
The permanent closure forces the chosen stored
value. Setpoint modification is not possible.
The impulsive closure, selects the stored value.
Setpoint modification is allowed.
If more than one digital input is selecting a Setpoint,
the last to be activated is the operating one.
(see page 43)
Reactivation of The blocking function is activated on closing
blocking
the command from digital inputs
7 - Programmed Setpoint
7
PROGRAMMED
SETPOINT
INTRODUCTION
When the Setpoint programmer
option (mod. X5-3… 4 ) is present, up to four programs are
available.
MAIN CHARACTERISTICS
• 4 program, 16 segments
max/program
• start, stop, hold etc, commands from the keypad
• time base in seconds, minutes or hours
• continuous or up to 1…9999
time cycling of the program
• two digital outputs (OP3 and
OP4) related to the program.
• setting of the maximum
allowed deviation from the
Setpoint
7.1
PROGRAM STRUCTURE
The program consists of a
sequence of segments.
For each segment, it is specified:
• the Setpoint
to reach
s
# p
. .
alvays
• the duration
present
of the segment
t
# i
. .
The program consists of:
• 1 initial segment named O
• 1 end segment named f
• 1…14 normal segments
Initial segment - 0
Its main purpose is to define the
value the process variable has
to maintain before starting the
program.
Ramp
#s.p.==
#ti.==
Dwell
• the state of the OP3 output
#s.p.==
#ti.==
End segment - F
Its main purpose is to define the
value the process variable has
to maintain at the end of the program and until further changes
of Setpoint.
Normal segments - ===
These segments build up the
profile program. There are 3
types of segments:
#ti.==
#s.p.==
Step
#s.p.==
#ti.== = 0
s.p.
ti.
= Target Setpoint
=Duration
=Previous segment
=Current segmente
=Next segment
59
7 - Programmed Setpoint
EXAMPLE OF SETPOINT PROFILE
°C
#sp. 4
Setpoint
#sp. 3
250
#sp.10
Maximum
allowed deviation
#sp.11
#sp. 2
#sp.12
#sp.13
#sp. I
Program
start
7.2.1 MAXIMUM
ALLOWED
DEVIATION ( band )
#sp. 9
band
350
300
7.2 SETPOINT PROGRAMMER
#sp.14
200
150
100
#sp. f
50
#sp. 0
0
Segment Initial
t0
Time
# Io
C
#Opn
#CIo
OP4 digital
output #Opn
OP3 digital
output
60
30 50
70 80
110
1°
2°
3°
4°
5°
t1
t2
t3
t4
t5
9°
time
190
210 230
250
10°
11°/12° 13° 14°
End
t9
t10
170
t11/t12 t13
t14
If the PV controlled input value
exceeds the band, centred
around the SP, the segment time
is extended of the same time the
PV input stays out of the band.
The band width is defined in a
parameter of the program segment.
The actual segment period is
. = +Ti
calculated as ti.=
7 - Programmed Setpoint
OPERATION
7.2.2 RE-START OF A PROGRAM AFTER A POWER FAILURE
A. Ramp
#band
#band
SP
PV
Ti
#ti.-#ti.-- + Ti
The parameter f
# ail . specifies the behaviour of the programmer at power up (see page
62). Selected between the following 3 choices:
C
# ont
Continue
#res
Reset
r
# aMp
Ramp
If #Cont is selected,
the execution of the program
starts from the point reached at
the power failure time.
All the parameters, like
Setpoint and the remaining
time are restored at the values
they had at power off.
If r
# aMp is selected,
the execution of the program
starts from the point reached at
the power failure time.
In this case, the programs continue with PV reaching SP with
a ramp, whose slope corresponds to the one of the segment running at the power off.
Power off during a dwell
SP
Power Off
Power Off
B. Dwell
PV
SP
#band
ti
Power Off time
#band
PV
Ti
is selected,
If #res
at power on the program ends
and goes back to local mode.
ti
Power off during a ramp
Power Off
#ti.-ti.-- + Ti
ti
61
7 - Programmed Setpoint
7.3
PARAMETERISATION - PROGRAM MENU (OPTION)
274.8
Operator
mode
275.8
Prog
Menu
Pr.no
[1] Two digital outputs are provided to be configured for
program purposes. These
output are usually OP3 and
OP4. If this functionality is not
required, it can be inhibited
by setting Off the corresponding parameter.
62
Program
menu
Program number
1/ 2/ 3/ 4
Program status
= reset
Hold = hold
run = start
n.Seg 1…14 max
Restart
Cyc.
Stat res
a power off
Fail after
Cont = continue
N° of segments
N° of program cycles
Off / 1…9999
res = reset
raMp = continue
with the slope
Time units
Unit p.sec = seconds
p.Min = minutes
p.hr = hours
Allowed deviation
band Off / 0...span/10
7 - Programmed Setpoint
Continue for
all the 14 normal
segments
ti. 0
Segment 0
time
0.1…999.9 Unit
ti. 1
Segment 1
time
0.1…999.9 Unit
s.P. 0
Segment 0
Setpoint
whole range
s.P. 1
Segment 1
Setpoint
whole range
s.P. f segment Setpoint
Segment 0
OP. 3 Digital output [1]
Segment 1
OP. 3 digital output[1]
OP. 3 Digital output [1]
Clo
Opn
Off
OP. 4
Clo
Opn
Off
= closed
= open
= inhibited
Segment 0
Digital output [1]
Clo = closed
Opn = open
Off = inhibited
OP. 4
End
whole range
End segment
Clo
Opn
Off
= closed
= open
= inhibited
Segment 1
Digital output [1]
Clo = closed
Opn = open
Off = inhibited
= closed
= open
= inhibited
End segment
OP. 4 digital output[1]
Back to the 1st parameter
Clo
Opn
Off
= closed
= open
= inhibited
63
7 - Programmed Setpoint
7.4
PROGRAM STATUS DISPLAYING
The function mode of the program as well
its status is displayed clearly by means the
Ö andá; leds as follows:
Function
Status
On program run mode, each 3 sec. the display shows alternatively:
- number of running program;
- number of operating segment as well its
status.
The control output value can be displayed
during the program run using the procedure
at page 53.
Led
Öá
Local
Reset OFF OFF
Program run
Run
ON
OFF
Program hold
Hold
ON
ON
Program hold for
Hold
PV outside Error band back
ON
ON
Program end (reset)
ON
OFF
End
X5
246.9
63
22.05
Number of running Program
(program n° 3)
each 3 sec. Operating segment
and its status
(Segment n°12) - ramp up
(Segment n°12) - ramp down
(Segment n°12) - dwell
(End segment)
Program end
64
7 - Programmed Setpoint
7.5
START/STOP OF A PROGRAM
The various commands, supported by the controller, are different for each of the following
operating phases:
A] when in Local Setpoint mode
B] during the execution of a program
C]when the program is in hold
Type of
operating
setpoint
Phase
Local
Programmed
Programmed
Execution
of a program
Hold
of a program
B
C
Program
start
Program
hold
Program
continuation
Program
stop
in local mode
Program
stop
in local mode
Program
stop
in local mode
Start of a
program
A
Supported
commands
Setting
of Local
setpoint
Commands supported by the
controllers
When the
program is
ended it comes
back to normal
mode
The different phase are displayed in a chained way, just for
easing the understanding of the
functionality.
Two different mode for starting
and stopping a program are provided:
direct mode with the ê key
(see page 66)
through the parameter menu
(see page 67)
65
7 - Programmed Setpoint
7.5.1 START/STOP OF A PROGRAM BY DIRECT MODE WITH ê
Program
selection
274.8
50
275.0
Operator
mode
(local Setpoint)
3
50
pr.no
Program
start
Program number displaying
1
Program
running
Ö led
continuously on
Note:
To reset the program see procedure at page 67
274.8
and
275.0
Program hold
50
Pr.no
274.8
and
Program hold
á
led continuously on
66
alternatively
275.0
Continue up to the
program end
7 - Programmed Setpoint
7.5.2 START/HOLD/STOP OF A PROGRAM THROUGH THE PARAMETER MENU
Program
selection
Reset procedure
274.8
50
275.0
Operator
mode
(local Setpoint)
3
run
Pr.no
Stat
Program start
Press until
Prog
50
Menu
Program
menu
Program
running
Ö led
continuously on
Stat
Program hold
Program hold
á led
continuously on
2
Pr.no
HoLd
N° of program
reS
Stat
Program reset
67
7 - Programmed Setpoint
7.5.3 DIGITAL INPUT COMMANDS FOR SETPOINT PROGRAMMER FUNCTION (OPTION)
Function
None
Set manual mode
Keyboard lock
PV
measure hold
Setpoint slopes
inhibition
Output forcing
1st Program
selection
2nd Program
selection
3rd Program
selection
4th Program
selection
Program
Start/Hold
Program
reset
Reactivation
of blocking
68
Parameter
value
O
# FF
A
# M
. an
k
# eb.I
H
# p
. U
S
# lo.1
F
# O
. ut
P
# rg.1
P
# rg.2
P
# rg.3
P
# rg.4
r
# =
. H.
r
# St
blck
Performed operation
Off
—
—
Automatic
Manual
Unlock
Locked
Normal
operation
Rate limiting
is active
Normal
operation
Local
Local
Local
Local
HOLD
Normal
operation
—
Notes
On
PV is hold
Normal
operation
Forced
output value
1st
program
2nd
program
3rd
program
4th
program
Not used
With the keypad locked the commands from
digital inputs and serial communications are
still operating
The value of PV is “frozen” at the time the digital
input goes to the close state
When the input is in the on state, the Setpoint
is changed in steps
Digital input ON means activation forcing output
value (see page 28)
Program selection by permanent closure
of the digital input
When the input is in the On state, the program is
executed up to the end. When off, the program
is forced in hold.
Program
Digital input ON means program reset and
reset
control switching to Local setpoint
Reactivation The blocking function is activated on closing
of blocking the command from digital inputs
RUN
8 - Technical Specifications
8
TECHNICAL SPECIFICATIONS
Features
at 25°C env. temp.
Total configurability
(see chapter 4.3 page 25)
PV Input
(see pages13,14
and page 26)
Description
From keypad or serial communication the
- the type of Setpoint
user selects:
- the type of control algorithm
- the type of input
- the type of output
A/D converter with resolution of 160.000 points
Update measurement time: 50 ms
Common
Sampling time::0.1…10.0 sec. Configurable
characteristics
Input shift: - 60…+ 60 digit
Input filter with enable/disable: 0.1…99.9 seconds
0.25% ± 1 digits for temperature sensors
Accuracy
0.1% ± 1 digits (for mV and mA)
Resistance
2 or 3 wires
Pt100Ω
a
0°C
thermometer
connection
(IEC 751)
(for∆T: R1+R2
Burnout
°C/°F selectable
must be <320Ω)
(with any combination)
Thermocouple
L,J,T,K,S, R, B, N, E, W3, W5
(IEC 584)
Rj >10MΩ
°C/°F selectable
DC input (current)
4-20mA, 0-20mA
0-50mV, 0-300mV
DC input (voltage)
1-5, 0-5, 0-10V
Frequency (option)
0-2.000 / 0-20.000Hz
Low level ≤2V
High level 4 - 24V
Internal cold junction
compensation con NTC
Error 1°C/20°C ±0.5°C
Burnout
- the type and functionality of the alarms
- control parameter values
- access levels
Between 100…240V~
the error is minimal
Max. wire Res:
20Ω max (3 wires)
Sensitivity: 0.1°C/10° E. T.
<0.1°C / 10Ω Wire Res.
Line: 150Ω max
Input drift:
<2µV/°C.Env. Temp
<5µV / 10Ω Wire Res.
Rj =30Ω
Burnout. Engineering units
position
Rj >10MΩ conf. decimal point
—
with or without √
Rj>10KΩ Init. Scale -999…9999
Full Scale -999…9999
(min. range of 100 digits)
Input drift:
<0.1% / 20°C Env. Temp.
<5µV / 10Ω Wire Res.
69
8 - Technical Specifications
Features
at 25°C env. temp.
Auxiliary inputs
Description
Remote
Setpoint
Not isolated
accuracy 0.1%
Current
0 / 4-20mA
Voltage
1-5, 0-5, 0-10V
Rj = 30Ω
Rj = 30OKΩ
Feedback valve position
Potentiometer from 100Ω to 10KΩ
Digital inputs
3 logic
Operating mode
and Outputs
Bias in engineering units and ± range
Ratio from -9.99…+99.99
Local + Remote Setpoint
The closure of the Auto/Man mode change, Local/Remote Setpoint mode change, 3 Stored Setpoint activation, keyboard lock, measure
external contact
hold, slope inhibit and output forcing
produces any of the
Program hold/run (if option installed)
following actions:
Control output
Alarm
Alarm
Alarm
Alarm
Retransmission
Main
Secondary
AL1
AL2
AL3
AL4
PV / SP
(Heat)
(Cool)
Single
OP1
OP2
OP3
OP4
OP5
OP6
action
Relay/Triac
Relay/Triac
Relay
Relay
Analog./Digital Analog./Digital
1 single or
double action
PID loop or
On/Off with
1, 2,3 or 4
alarms
OP5
Analog./Digital
OP1
Relay/Triac
Double
action
Heat / Cool
OP1
Relay/Triac
OP2
Relay/Triac
OP1
OP5
Relay/Triac Analog./Digital
OP5
OP2
Analog./Digital Relay/Triac
OP2
Relay/Triac
OP1
Relay/Triac
OP5
OP6
OP1
Analog./Digital Analog./Digital Relay/Triac
Valve drive
70
OP1
Relay/Triac
OP2
Relay/Triac
OP2
Relay/Triac
OP2
Relay/Triac
OP3
Relay
OP4
Relay
OP6
Analog./Digital
OP3
Relay
OP4
Relay
OP5
OP6
Analog./Digital Analog./Digital
OP3
Relay
OP4
Relay
OP6
Analog./Digital
OP3
Relay
OP4
Relay
OP6
Analog./Digital
OP3
Relay
OP4
Relay
OP3
Relay
OP4
Relay
OP5
OP6
Analog./Digital Analog./Digital
8 - Technical Specifications
Features
at 25°C env. temp.
Control mode
Description
Algorithm
Proportional band (P)
Integral time (I)
Derivative time (D)
Error dead band
Overshoot control
Manual reset
Cycle time (Time proportional only)
Min./Max output limits
Control output rate limit
Soft-start output value
Output safety value
Control output forcing value
Control output hysteresis
Dead band
Cool proportional band (P)
Cool integral time (I)
Cool derivative time (D)
Cool cycle time (Time proportional only)
Control output high limit
Cool output max. rate
Motor travel time
Motor minimum step
Feedback potentiometer
PID with overshoot control or On-off - PID with valve drive algorithm,for controlling motorised positioners
0.5…999.9%
1…9999 sec
0.1…999.9 sec
0.1…10.0 digit
0.01…1.00
0…100%
0.2…100.0 sec
0…100% separately adjustable
0.01…99.99%/sec
1…100% - Time 1…9999 sec
-100…100%
-100…100%
0…5% Span in engineering units
0.0…5.0%
0.5…999.9%
1…9999 sec
0.1…999.9 sec
0.2…100.0 sec
0…100%
0.01…99.99%/sec
15…600 sec
to 0.1…5.0%
100Ω …10KΩ
OFF = O
Single action
PID algorithm
OFF = O
On-Off algorithm
OFF = O Double action
PID algorithm
(Heat / Cool)
OFF = O
Valve drive PID algorithm
Raise/Stop/Lower
71
8 - Technical Specifications
Features
at 25°C env. temp.
Description
OP1-OP2 outputs
SPST Relay N.O., 2A/250V~ for resistive load
Triac, 1A/250V~ for resistive load
OP3 output
OP4 output
Analogue / digital
OP5 and
OP6 (option) outputs
SPDT relay N.O., 2A/250V~ for resistive load
RSPST relay N.O. 2A/250V~ for resistive load
Galvanic isolation: 500 V~/1 min
Control or PV/SP
Short circuit protected
Resolution 12bit
retransmission
Accuracy: 0.1 %
Hysteresis 0…5% Span in engineering units
Active high
Action type
AL1 - AL2 - AL3 - AL4
alarms
Active low
Action
Analogue: 0/1…5V, 0…10V, 500Ω / 20mA max,
0/4…20mA, 750Ω / 15V max
Digital: 0/24V– ±10%- 30mA max
for solid state relay
Deviation threshold
±range
Band threshold
0…range
Absolute threshold
whole range
Sensor break, heater break alarm
Special functions
Acknowledge (latching), activation inhibit (blocking)
Connected to Timer or program (if options installed) (only OP3-OP4)
Local + 3 memorised
Remote only
Setpoint
Up and down ramps 0.1...999.9 digit/min or digit/hour (OFF=0)
Low limit: from low range to high limit
High limit: from low limit to high range
Local and Remote
Local with trim
Remote with trim
Programmable
72
If option installed
8 - Technical Specifications
Features
at 25°C env. temp.
Programmable Setpoint
(optional)
Tuning
Auto/Man station
Serial comm. (option)
Auxiliary Supply
Operational
safety
General
characteristics
Description
4 programs, 16 segments (1 initial and 1 end)
From 1 to 9999 cycles or continuous cycling (Off)
Time values in seconds, minutes and hours
Start, stop, hold, etc. activated from the keypad, digital input and serial communications
Fuzzy-Tuning type . The controller selects automatically the best Step response
method according to the process conditions
Natural frequency
Adaptive Tune self-learning, not intrusive, analysis of the process response to perturbations and continuously calculation of the PID
parameters
Standard with bumpless function,
by keypad, digital input or serial communications
RS485 isolated, SLAVE Modbus/Jbus protocol, 1200, 2400, 4800, 9600, 19.200 bit/sec, 3 wires
RS485 isolated, MASTER Modbus/Jbus protocol, 1200, 2400, 4800, 9600, 19.200 bit/sec, 3 wires
RS485 asynchronous / isolated, PROFIBUS DP protocol, from 9600 bit/sec at 12MB/sec selectable, max lenght 100m (at 12 Mb/sec.)
+24V– ± 20% 30mA max - for external transmitter supply
Detection of out of range, short circuit or sensor break with automatic activation of the safety strategies and alerts on display
Measure input
Control output
Safety and forcing value -100%...100% separately adjustable
Parameters
Parameter and configuration data are stored in a non volatile memory for an unlimited time
Access protection
Password to access the configuration and parameters data - Fast wiew
Power supply
100 - 240V~ (-15% + 10%) 50/60Hz or
Power consumption 5W max
(fuse protected)
24V~ (-15% + 25%) 50/60Hz e 24V– (-15% + 25%)
Safety
Compliance to EN61010-1 (IEC 1010 – 1), installation class 2 (2500V) pollution class 2, instrument class II
Electromagnetic
Compliance to the CE standards (see page 2)
compatibility
Protection
IP65 front panel
EN60529 (IEC 529)
1/ DIN - 48 x 96, depth 110 mm, weight 380 gr. max
Dimensions
8
73
1
WARRANTY
We warrant that the products will
be free from defects in material
and workmanship for 3 years from
the date of delivery.
The warranty above shall not
apply for any failure caused by the
use of the product not in line with
the instructions reported on this
manual.
74
G.&P. Grafica & Pubblicità • Gazzaniga (BG) • e-mail: G & P @ m a i l - g a t e
. net
Warranty
ASCON’S WORLDWIDE SALES NETWORK
SUBSIDIARY
DISTRIBUTORS
FRANCE
ARGENTINA
GREECE
ASCON FRANCE
Phone
0033 1 64 30 62 62
Fax
0033 1 64 30 84 98
MEDITECNA S.R.L.
Phone
+5411 4585 7005
Fax
+5411 4585 3434
AGENCE SUD-EST
Phone
0033 4 74 27 82 81
Fax
0033 4 74 27 81 71
AUSTRALIA
CONTROL SYSTEM
Phone
+30 31 521 055-6
Fax
+30 31 515 495
BRANCH OFFICE
Phone
+30 1 646 6276
Fax
+30 1 646 6862
IPA INDUSTRIAL PYROMETER
(AUST) PTY.LTD
Phone
+61 8 8352 3688
Fax
+61 8 8352 2873
FINLAND & ESTONIA
TIM-TOOL OY
Phone
+358 50 501 2000
Fax
+358 9 50 55 144
GERMANY
MESA INDUSTRIE ELEKTRONIK GMBH
Phone
+49 2365 915 220
Fax
+49 2365 915 225
HOLLAND
HSD INSTRUMENTS
Phone
+31 78 617 03 55
Fax
+31 78 618 26 68
PORTUGAL
REGIQUIPAMENTOS LDA
Phone
+351 21 989 0738
Fax
+351 21 989 0739
SPAIN
INTERBIL S.L.
Phone
+34 94 453 50 78
Fax
+34 94 453 51 45
BRANCH OFFICE
Phone
+34 93 311 98 11
Fax
+34 93 311 93 65
Phone
+34 91 656 04 71
Fax
+34 91 677 21 26
SWITZERLAND
CONTROLTHERM GMBH
Phone
+41 1 954 37 77
Fax
+41 1 954 37 78
TURKEY
KONTROL SISTEMLERI LTD
Phone
+90 216 302 19 70-71
Fax
+90 216 302 19 72
UNITED KINGDOM
EUKERO CONTROLS LTD
Phone
+44 20 8568 4664
Fax
+44 20 8568 4115
75