Control System Field Conversion
The unit can be converted to a different control system in the field. Locate the unit’s
current control system in the “From” column and the new control system in the “To”
column that is in the same row as the current control system. Follow the steps outlined in
the “New” column to complete the field conversion.
NOTE: Contact the factory for the BACview Admin password if required and to
have the wiring diagram updated when doing a control system field conversion.
Failure to do so will result in inaccurate documentation that can complicate possible
future troubleshooting efforts.
From
MRT
MDT
To
MDT
1. Order a BACview remote panel from the factory and plug it into the local
access connection on the front of the unit control module.
2. Change the Control System parameter on Unit Modes screen of BACview
to MDT.
MRT-Expert
1. Order a BACview remote panel from the factory and plug it into the local
access connection on the front of the unit control module. Leave the room
sensor connected.
2. Disconnect the unit enable potentiometer from terminals 214, 215, and 216
and place a jumper between terminals 213 and 216 on the main terminal
strip.
MDT-Expert
1. Order a BACview remote panel from the factory and plug it into the local
access connection on the front of the unit control module.
2. Disconnect the unit enable potentiometer from terminals 214, 215, and 216
and place a jumper between terminals 213 and 216 on the main terminal
strip.
3. Change the Control System parameter on Unit Modes screen of BACview
to MDT.
MRT
1. Order a BACview remote panel and a room sensor from the factory.
2. Plug the BACview into the local access connection on the front of the unit
control module.
3. Wire the room sensor into the four-wire Rnet input on the left side of the
unit control module.
4. Change the Control System parameter on Unit Modes screen of BACview
to MRT.
MRT-Expert
1. Order a BACview remote panel and a room sensor from the factory.
2. Disconnect the unit enable potentiometer from terminals 214, 215, and 216
and place a jumper between terminals 213 and 216 on the main terminal
strip.
3. Plug the BACview into the local access connection on the front of the unit
control module.
57