USER MANUAL FOR EXPLOSION PROTECTED LOW
VOLTAGE SWITCHGEAR AND CONTROL GEAR ASSEMBLYES
type SKX 16/.., SKX 18/.., SKX20/..
No: TEPEx.RS.030
Rev : 1
Date: 06.2014
MANUFACTURER
TEP Ex d.o.o. , Medarska 69, HR-10090 Zagreb
tel. 049/222-900, fax 049/426-450, e-mail: tepextepex.hr, www.tepex.hr
PURPOSE
Explosion protected control units type SKX 16 – SKX 20, independently or in combination coupled record (combination),
are intended for the management, distribution and signaling in the power circles::
 in hazardous areas due to the presence of flammable and explosive gases, vapors or mists in Zones 1 and 2
 in hazardous areas due to the presence of flammable and explosive dust in Zones 21, 22
TYPE OF PROTECTION
The explosion protection ensure utilizing types of protection:
-
EN 60079-0:2012,
EN 60079-1:2007,
EN 60079-7:2007,
EN 60079-11:2012,
EN 60079-18:2009,
EN 60079-31:2009.
Apparatus category and marking of explosion-protection:
Certificate:
Marking:
EXA 14 ATEX 029
2465
II 2G Ex d e mb ia/ib IIC T4 - T6 Gb
II 2D Ex tb IIIC T80C Db
Apparatus category and marking of explosion-protection:
Ambient temperature:
-20ºC ≤ Ta ≤ +50ºC
Degree of protection:
IP 66
Resistance to shock:
IK 08
CONSTRUCTION
In and on Ex e enclosure or combination of multiple enclosures, interconnected by bushing, are mounted " Ex e d m ia/ib"
and Ex e built-in components and actuator and indicators.
There are no limitation in orientation of encosure/combination of multiple enclosures, (longer side of enclosure is mounted
horizontally or vertically) and the manner of which the mounting is set to the surface.
In horizontal orientation of enclosure, built-in components and actuator and indicators are mounted in maximum two rows.
In vertical orientation of enclosure , built-in components and actuator and indicators are mounted in maximum:
- SKX 16 - 2 rows
- SKX 18 - 3 rows
- SKX 20 - 5 rows
The actual nuber of mounted rows depends on the device configuration.
Circuit breaker 3p/4p Ith = 40 A, 80 A with its matching actuatuator or block NH 00 main fuse always occupies two hole
rows,
Actuator and indicators – circuit breaker which are not connected with the actuaror, always occupie one and a half row. In
one row there can be maximaly be:
- SKX 16 - 6 pols, horizontal and vertical orientation of the enclosure,
- SKX 18 - 12 pols vertical, 8 pols horizontal orientation of the enclosure,
- SKX 20 - 18 pols vertical, 12 pols horizontal orientation of the enclosure.
Permitted installation and current loading of terminals is determined with table of maximum losses of terminal boxes
SKX16/E. Table is expanded with 50 mm2 and 70 mm2 terminals, and same data is valid as for 35 mm2 terminals.
Possible combinations, number and distribution of actuators and indicators and built-in components are determined by
certification drawings.
1
A
B
80
SKX 20
SKX 18
A
C
C
110
110
D
A
110
110
SKX 18
2,3
250
250
502
±0.5
400
2,3
B
D
K
110
1260
600
SKX 20
110
2,3
D
SKX 16
C
80
255
SKX 16
B
Built-in components are installed in enclosures with screw fitting connection to steel base plate 2 mm, in such way that
they provide clearance according to standards (creepage distances are determined by component construction) minimum 12
mm of clearance between Ex e terminals and minimum 50 mm between Ex e and EX i terminals.
Control units, generally, are not factory-wired. When they are shipped wired, wiring is done with H07V-K type cables with
appropriate cross-section with lug fastons.
Distribution of intrinsic safe and non- intrinsic safe wiring is done separately, without mutual crossings.
Certified Ex e cable glands, chosen according to cable type are used for cable entries. If metal cable glands are used, an
external earthing terminal is mounted next to them. Unused cable entries are closed with EX e plugs.
For intrinsic safe circuits blue (RAL 5012) terminals are used. For cable entry of intrinsic safe circuits into enclosure cable
glands with blue cable glands nut is used.
Device is designed in accordance with EN 60493-1:1991.+A1:2004, EN 60947-7-1,2,3:2002, and all other connected
standards.
Example of design SKX combination
2
TECHNICAL DATA
Rated insulation voltage Ui :
Nominal current Ith :
PE terminals (inside the enclosure):
Cover screw:
Cable glands:
Surface resistance:
Energy shock:
Colour:
Dimensions LxWxH (without cable glands):
Mounting dimensions:
690 V AC
(terminal type SL.. Ui=400V AC)
up to 80A
max. 2x4 mm2+2x2,5 mm2 , 3x4 mm2 , 2x6 mm2 – solid,
stranded, flexible
Screw M6x30 (Z4) - 4.8 A2
Tightening torque 1,5 Nm
Tightening torque of cable gland nut and body, depending on the
size, according to the manufacturer's instructions
< 109 Ω
7J
Black , RAL 9005
SKX 16: 255x250x120/160 mm
SKX 18: 400x250x120/160 mm
SKX 20: 600x250x120/160 mm
With screw through hole 12/7mm
SKX 16: 235 x 200 mm
SKX 18: 380 x 200 mm
SKX 20: 580 x 200 mm
Dimension drawings for moulded plastic enclosures (without cable glands ):
255
120
162
SKX 16/
250
3
162
400
120
SKX 18/
250
600
120
162
SKX 20/
250
4
ACTUATORS AND INDICATOR ELEMENTS:
TYPE
DESCRIPTION
MOUNTING
DIMENSION
42
90
70

0

OTVOR U STIJNCI POKLOPCA
SWITCH ACTUATOR
5
 23
SMO 17/.
- manufacturer: TEP Ex d.o.o.
- explosion protection:
I M2 II 2GD Ex e I/II IP66
- certificate: HREx T 06.025U
,2
±0
I
I
0
II
0
I
III
32±0,5
SMO 17/1
SMO 17/2
0
1
SMO 17/3
1
2
I
III
3
SMO 17/6
SMO 17/4
1
2
II
SMO 17/5
2
3
3
4
4
SMO 17/7
5
SMO 17/8
1
2
5
4
3
6
SMO 17/9
64,5±0,1
76
- manufacturer: TEP Ex d.o.o.
- explosion protection:
II 2GD Ex e II IP66
- certificate: HREx T 06.026U
56 -0,2
+0,5
12
FRONT ELEMENT OF
MEASURING
INSTRUMENTS
SAM 72
II
I
II
 3,5
76
34
38
PUSCHBUTTON ACTUATOR
2,8 +0,2
0
Type SPO 01/.
0
16 +0,2
SPO 01/.
- manufacturer: TEP Ex d.o.o.
- explosion protection:
- II 2GD EEx e II T80°C
IP66
- certificate: HREx T 04.020U
SPO 01/01
SPO 01/02
30 +0,2
0
SPO 01/03
SPO 01/04
SPO 01/05
SPO 01/06
SPO 01/07
SPO 01/08
SPO 01/09
SPO 01/10
0
I
II
red
green
white
START
STOP
ON
OFF
38
0
16 +0,2
SPO 02/.
20
2,8 +0,2
0
- manufacturer: TEP Ex d.o.o.
- explosion protection:
II 2GD EEx e II T80°C
IP66
- certificate:
HREx T 04.020U
38
18
FRONT ELEMENT OF
SIGNAL LAMP
Type SPO 02/.
30 +0,2
0
SPO 02/01
RED TRANSP.
SPO 02/02
GREEN TRANSP.
SPO 02/03
YELLOW TRANSP.
SPO 02/04
KEY-OPERATED
PUSHBUTTON ACTUATOR
56
21
2,8 +0,2
0
0
16 +0,2
GHG
410 1904
R0012
- manufacturer: CEAG GmbH
- explosion protection:
certificirano unutar GHG
41...R... II 2G/D EEx e II
IP66
- certificate:
PBT 00 ATEX 3117
TRANSPARENT
30 +0,2
0
5
MUSHROOM-HEAD
PUSHBUTTON ACTUATOR
(EMERGENCY-STOP)
GHG
410 1905
R0006
- manufacturer: CEAG GmbH
- explosion protection:
II 2G/D EEx e II IP66
- certificate:
PBT 00 ATEX 3117
KEY-OPERATED
MUSHROOM-HEAD
PUSHBUTTON ACTUATOR
(EMERGENCY-STOP)
O38
0
16 +0,2
2,8
30 +0,2
0
21
2,8 +0,2
0
0
16 +0,2
GHG
410 1905
R0005
21
+0,2
0
- manufacturer: CEAG GmbH
- explosion protection:
II 2G/D EEx e II IP66
- certificate:
PBT 00 ATEX 3117
SWITCH ACTUATOR
30 +0,2
0
56
30
21
2,8 +0,2
0
- manufacturer: CEAG GmbH
- explosion protection:
II 2G/D EEx e II IP66
- certificate:
PBT 00 ATEX 3117
CABLE GLAND
30 +0,2
0
30
0
16 +0,2
GHG
410 1944
R0010
33
+0,2
- manufacturer: TEP Ex d.o.o.
- explosion protection:
II 2GD EEx e II IP66
- certificate:
HREx T 00.005X
M25x1.5
SPU 25
(M25)
25,5 -0,4
44
CABLE GLAND
GHG
960 1955
- manufacturer: CEAG GmbH
- explosion protection:
II 2GD EEx e II IP66
- certificate:
PBT 99 ATEX 3101X,
PTB 99 ATEX 3128X
A,5
A,5
+0,2
-0,4
+0,2
-0,4
A
A
A = M16-M40
CABLE GLAND
- manufacturer: ELFIT S.p.A
- explosion protection:
II 2GD EEx d IIC Eex e II
IP66/67
- certificate:
CESI 02 ATEX 081 X
SPC 25
M25
GHG 960
A,5
A
A = M16-M40
OK30
+0,2
A
25,5 -0,4
- manufacturer: TEP Ex d.o.o.
- explosion protection:
II 2GD EEx e II IP66
- certificate: HREx T 04.009
PLUG
- manufacturer: CEAG GmbH
- explosion protection:
II 2GD EEx e II IP66
- certificate:
PBT 99 ATEX 3130
+0,2
-0,4
3
PLUG
A,5
+0,2
-0,4
18
FGA1 –
FGA4
M25x1.5
A
A,5
+0,2
-0,4
A
A,5
+0,2
-0,4
A = M16-M40
6
BUILD-IN COMPONENTS:
TYPE
DESCRIPTION + technical data
WIRING DIAGRAM
DIMENSION
SMS
03/1
SMS
03/4
SMS
03/5
SMS
03/6
SMS 03/.
-
80
35
manufacturer: TEP Ex d.o.o.
explosion protection:
I M2 Ex de I
II 2G Ex de IIC
rated voltage: 660V
rated current: 16A
rated section: 2,5mm2
certificate: HREx T 01.016U
SMS
03/3
SMS
03/2
70
-
SMS
03/12
5
CONTROL SWITCH
4
72
SMS
03/7
80
SMS
03/10
SMS
03/8
SMS
03/9
SMS
03/11
060
062
CONTROL SWITCH
48
72
065
061
063
50
GHG 23.
GHG 29.
manufacturer: CEAG GmbH
explosion protection:
II 2G Ex de IIC
- rated voltage: 690V
- rated current: 10/20A
- rated section: 2,5/6 mm2
- certificate:
GHG 23. - PTB 98 ATEX
1116U
GHG 29. - PTB 98 ATEX
1118U
4,5
-
4
067
62
70
011
034
7
037
049
023
019
033
024
SLP
-
manufacturer: TEP Ex d.o.o.
explosion protection:
I M2 Ex de I
II 2GD Ex de IIC
rated
voltage:
20-250V
AC/DC
Imax: 20mA
rated section: 2,5mm2
certificate: HREx T 06.027U
45
21
13
23
11
21
14
22
14
24
12
22
PBT/02
PBT/03
34
PBT/01
62
68
80
-
13
45
PBT/.
manufacturer: TEP Ex d.o.o.
explosion protection:
I M2 Ex de I
II 2GD Ex de IIC T6
- rated voltage: 690V
- rated current: 16A
- rated section: 2,5mm2
- certificate: HREx T 06.028U
SIGNAL LAMPS
X1 X2
34
-
12
PUSHBUTTON
62
68
POTENTIONMETER
56
32
66
90
AM 45/72,
VM 45/72
- manufacturer: CEAG GmbH
- explosion protection:
II 2G EEx em IIC EEx ib Iic
- measuring range:
AM: n/1A
0-20mA
0-25A direct 4-20mA
VM: n/1A
6-415V
6-660V
- scale: 0-600A, 20 tipova
- connection terminal: 1,54mm2
- certificate:
PBT 99 ATEX 2032U
52
58
70
GHG 41.
manufacturer: CEAG GmbH
explosion protection:
II 2G Ex de IIC
- rated voltage: 250V
- resistance range: 100-10
000Ω
- scale: 0-100%
- connection terminal: 2,5mm2
- certificate:
PBT 97 ATEX1081U
MEASURING INSTRUMENTS
70
-
8
SL 5
-
10
manufacturer: TEP Ex d.o.o.
explosion protection:
I M2 Ex e I
II 2GD Ex e IIC
rated voltage: 400V
connection terminal: 4mm2
certificate: HREx T 05.002U
19
26
-
50
MANTLE TERMINALS
57
96
SL 8
-
manufacturer: TEP Ex d.o.o.
explosion protection:
I M2 Ex e I
II 2GD Ex e IIC
rated voltage: 400V
connection terminal: 4mm2
certificate: HREx T 05.002U
60
-
16
MANTLE TERMINALS
44
84
TERMINALS
EURO 4/35
EURO 1625/35
5 terminals 4 mm2 with rail 357,5 TH
- manufacturer:
MORSETTITALIA
- explosion protection:
II 2GD EEx e II
- certificate:
KEMA 03ATEX2118 U
-
2 terminals 16 mm2 with rail TH
35-7,5
- manufacturer:MORSETTITA
LIA
- explosion protection:
II 2GD EEx e II
- certificate:
KEMA 03ATEX2118 U
NH 00
MAIN FUSE
type: NH0 300XX, NH0 301XX
- manufacturer: CEAG GmbH
- explosion protection:
II2G Ex de IIC
- certificate: PTB 99 ATEX
1066U
HSC 300 40
HSC 300 80
HSC 400 40
HSC 400 80
MAIN CURRENT SWITCH
type: HSC ... ..
- manufacturer: CEAG GmbH
- explosion protection:
II2G Ex de IIC
certificate: PTB 99 ATEX 1031U
9
MAINTANCE, REPAIR AND OVERHAUL
Maintenance is performed in accordance with EN 60079-17:2007, the national rules and user policy. Repair and overhaul
is performed in accordance with EN 60079-19:2007 and applicable national rules. Repairs that affect the explosion
protection, may only be carried out by TEP Ex or a qualified electrician in compliance with the national rules.
Modifications to the control unuts or changes of its design are not permitted. Every improper usage, as well as every
unofficial repair or modification of the product, release the manufacturer of all responsibilities..
MARKING
Explosion protected control units, types SKX 12 - SKX 15, are labeled with:
-
marking labels
HR-10090
1)
SKX ../...
Ui = ...2) V
2465
Zagreb
Ith = ...2) A
IP66
II 2G Ex d e ia/ib mb IIC T4 - T6 Gb 3)
II 2D Ex tb IIIC T80°C Db
EXA 14 ATEX . . . 4).
-
MA/MR ....5)
DAT....6)
warning label:
WARNING
DO NOT OPEN WHEN ENERGIZED
94,5
42
RESPONSIBILITY AND AUTHORIZATION
Responsibility and authorization are defined by the "Regulation on technical supervision over the electrical stations, installations and
equipment intended for usage in potentially explosive atmospheres" . This Manual represents the most relevant information about the
product. Adequate national laws and regulations supplement
it. TheZagreb
person in charge 0722
is required to secure its employment in the
HR - 10090
industrial unit. Every improper usage, as well SKX
as every
repair or restoration of the product, release the
. ./ . . unofficial
.1) . . . V2)restructuring,
. . . A3)
IP66
manufacturer of all responsibilities.
II 2G Ex de IIC T6 Gb
II 2D
Ex t IIIC T80°C Db
6)
CESI 12 ATEX ... 4)
MA/MR .......5)
DATE ......
STORAGE AND TRANSPORT
Transport and storage is only allowed in the original
packaging,
on
the
way
pointed
out
on
the
carton box.
Control units with measuring instruments type AM72, VM72
OR
All rights reserved.
II 2G
II 2D
Ex de mb IIC T6 Gb
Ex t IIIC T80°C Db
Control units with terminals type SL5, SL8, TH 35 5x4mm2
II 2G Ex e II T6 Gb
II 2D Ex t IIIC T80°C Db
Control units with Ex i terminals 5x4mm2
II 2G
Ex ia/ib IIC T6 Ga/Gb
06.2014. / Rev. 01