Download Emerson FIELDVUEDVC6200 Instruction Manual
Transcript
Instruction Manual Supplement D103858X012 DVC6200 SIS March 2014 Control Schematics for FIELDVUE™ DVC6200 SIS Digital Valve Controller The below drawings are guidelines ONLY, and should be modified/changed for site specific conditions. The guidelines are not specific to individual user needs, applications, process conditions, environmental conditions, or safe state functions and should be finalized in consultation with your local business partner before implementation. References to the make and model number of specified third party vendor products is not to be construed as an endorsement from Emerson Process Management—Fisher Controls International LLC. For clarification or consultation, please contact your Local Business Partner who will consult Fisher Global Industry Sales. The attached schematics provide examples of a DVC6200 SIS in different modes (point-to-point mode or multidrop mode). The DVC6200 SIS can operate through a command signal from either a DCS (basic process control system, BPCS) or logic solver (safety instrumented system, SIS). These are basic schematics that have been developed to provide details of the connections between the control system and user interface. Drawings indicated as “PST Only” depict the use of a DVC6200 SIS with a reverse acting relay (relay B). These drawings are for reference ONLY and it may be possible to have many different combinations or permutations of such schematics. www.Fisher.com Instruction Manual Supplement DVC6200 SIS D103858X012 March 2014 DISPLAY ALARMS ESDV STATUS IN PROGRESS Valve Stuck (PST Unsuccessful) Options Available: LCP100 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation Notes: Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve Trigger diagnostics or capture of demand/reset strokes unavailable since power to DVC6200 SIS is interrupted during a demand AI or DI* SERIAL IN Benefits: SIL 3 Capable digital valve controller Valve Shutdown and PST capability PST with DVC6200 SIS provides diagnostic coverage OUT OUT IN Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) DO IN ValveLink™ Software 024V DC + HART LC340 OUT HART MULTIPLEXER** Optional LCP100 or External Pushbutton PST BPCS SIS FIELD Scenario 1: SIS with DO to DETT FIELDVUE DVC6200 SIS Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer 2 Instrument Air Supply Instruction Manual Supplement DVC6200 SIS D103858X012 March 2014 DISPLAY ALARMS IN PROGRESS ESDV STATUS Options Available: LCP100 Local Control Panel or Valve Stuck (PST Unsuccessful) external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation AI or DI* SERIAL IN Notes: Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve Benefits: SIL 3 Capable digital valve controller Valve Shutdown and PST capability PST with DVC6200 SIS provides diagnostic coverage OUT OUT IN Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) Non-HART AO IN ValveLink Software 4-20 mA + HART Instrument Air Supply HF341/ HF340*** OUT HART MULTIPLEXER** Optional LCP100 or External Pushbutton PST BPCS SIS FIELD Scenario 2: SIS with AO to DETT DVC6200 SIS Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer ***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HARTr communication 3 Instruction Manual Supplement DVC6200 SIS D103858X012 March 2014 DISPLAY ALARMS IN PROGRESS ESDV STATUS Valve Stuck (PST Unsuccessful) Options Available: LCP100 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation Benefits: SIL 3 Capable digital valve controller Valve Shutdown and PST capability PST with DVC6200 SIS provides diagnostic coverage Trigger diagnostics capture shutdown event and reset Notes: Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve AI or DI* OUT IN Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) HART AO IN OUT Instrument Air Supply 4-20 mA + HART HART Pass Through ValveLink Software BPCS Asset Management System Optional LCP100 or External Pushbutton PST SIS FIELD Scenario 3: SIS with HART I/O to DETT DVC6200 SIS Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS 4 Instruction Manual Supplement DVC6200 SIS D103858X012 March 2014 DISPLAY ALARMS IN PROGRESS ESDV STATUS Options Available: LCP100 Local Control Panel or Valve Stuck (PST Unsuccessful) external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation Benefits: Prevents spurious trips on loss of electrical power to DVC6200 SIS PST with DVC6200 SIS provides diagnostic coverage Trigger diagnostics captures safety demand and reset ‐Solenoid health monitoring Notes: ‐ DVC6200 SIS with Relay B in ETT configuration for PST diagnostic only Loss of pneumatic supply to DVC6200 SIS exhausts air to valve DO SERIAL 0-24 V DC IN IN OUT AI or DI* Non-HART AO IN OUT OUT 4-20 mA HF341/ HF340*** OUT Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) S IN Y HART Instrument Air Supply 4-20 mA + HART MULTIPLEXER** ValveLink Software BPCS Optional LCP100 or External Pushbutton PST SIS FIELD Scenario 4: SIS with DO to DETT Solenoid X BPCS with AO to DVC6200 SIS (PST Only) Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer ***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HART communication 5 Instruction Manual Supplement DVC6200 SIS D103858X012 March 2014 DISPLAY ALARMS Valve Stuck (PST Unsuccessful) ESDV STATUS IN PROGRESS Options Available: LCP100 Local Control Panel or external pushbutton Integral 4-20 mA position transmitter or discrete switch Benefits: Prevents spurious trip on loss of electrical power to DVC6200 SIS Trigger diagnostics captures safety demand and reset PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid health monitoring Notes: ‐ DVC6200 SIS with Relay B in ETT configuration for PST diagnostic only Loss of pneumatic supply to DVC6200 SIS exhausts air to valve DO 0-24 V DC IN OUT AI or DI* OUT Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) S IN HART AO IN Y 4-20 mA + HART OUT Instrument Air Supply ValveLink Software BPCS Asset Management System Optional LCP100 or External Pushbutton PST SIS FIELD Scenario 5: SIS with DO to SOV X BPCS with HART I/O to DVC6200 SIS (PST Only) Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS 6 Instruction Manual Supplement DVC6200 SIS D103858X012 DISPLAY March 2014 IN PROGRESS ESDV STATUS Options Available: LCP100 Local Control Panel or external pushbutton Valve Stuck (PST Unsuccessful) SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation Benefits: SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV Trigger diagnostics captures safety demand and reset PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid health monitoring ALARMS Notes: Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve DO IN 0-24 V DC OUT Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) AI or DI* OUT S IN Instrument Air Supply HART AO ValveLink Software BPCS Asset Management System HART Pass Through IN SIS OUT 4-20 mA + HART Optional LCP100 or External Pushbutton PST FIELD Scenario 6: SIS with HART I/O to DETT DVC6200 SIS X SIS DO to DETT Solenoid Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS 7 Instruction Manual Supplement DVC6200 SIS D103858X012 March 2014 DISPLAY IN PROGRESS ESDV STATUS OUT OUT Notes: Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve ‐ Single DO is a common cause failure point Trigger diagnostics or capture of demand/reset strokes unavailable since power to DVC6200 SIS is interrupted during a demand Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) AI or DI* SERIAL IN Benefits: SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV Wiring to both SOV and DVC6200 SIS saves I/O PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid health monitoring Options Available: LCP100 Local Control Panel or Valve Stuck (PST Unsuccessful) external pushbutton SIL 2 Capable 420 mA position transmitter or discrete switch Discrete switch can be configured for position or alert annunciation ALARMS IN S DO IN ValveLink Software LC340 OUT HART MULTIPLEXER** BPCS Instrument Air Supply 0-24 V DC SIS Optional LCP100 or External Pushbutton PST FIELD Scenario 7: SIS with single DO to DETT DVC6200 SIS and DETT SOV Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer 8 Instruction Manual Supplement DVC6200 SIS D103858X012 March 2014 Options Available: LCP100 Local Control Panel or external pushbutton SIL 2 Capable 420 mA position Valve Stuck (PST Unsuccessful) transmitter or discrete switch Discrete switch can be configured for position or alert annunciation DISPLAY ESDV STATUS IN PROGRESS Benefits: SIL3 Capable digital valve controller ‐Redundant DVC6200 SIS and SOV PST with DVC6200 SIS provides diagnostic coverage ‐Solenoid health monitoring ALARMS Notes: Loss of electrical power or pneumatic supply to DVC6200 SIS exhausts air to valve Trigger diagnostics or capture of demand/reset strokes unavailable since power to DVC6200 SIS is interrupted during a demand DO SERIAL 0-24 V DC IN IN OUT OUT Optional Position Feedback (420 mA Analog or 1 A Discrete Switch) AI or DI* OUT IN 0-24 V DC + HART Instrument Air Supply DO IN ValveLink Software LC340 OUT HART Optional LCP100 or External Pushbutton PST MULTIPLEXER** BPCS S SIS FIELD Scenario 8: SIS with separate DO to DETT DVC6200 SIS and DETT SOV Example Drawing Only, may require modifications to meet site specific requirements *Position Monitor AI or DI may reside in SIS or BPCS **PC with ValveLink Software or 475 Field Communicator can be used in lieu of multiplexer 9 DVC6200 SIS March 2014 Instruction Manual Supplement D103858X012 Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher, FIELDVUE, and ValveLink are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a mark owned by the HART Communication Foundation. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Emerson Process Management Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore www.Fisher.com 10 E 2014 Fisher Controls International LLC. All rights reserved.