Download Emerson 644 User's Manual

Transcript
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644 Temperature Transmitter
with FOUNDATION™ fieldbus
www.rosemount.com
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table of Contents
SECTION 1
Introduction
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Product Recycling/Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
SECTION 2
Installation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Typical European Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Typical North American Installation . . . . . . . . . . . . . . . . . . . . . . . . 2-5
LCD Display Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Sensor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Ground the Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
SECTION 3
Configuration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
General Block Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Device Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Node Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Link Active Scheduler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Block Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Foundation fieldbus function blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
LCD Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Troubleshooting Guides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
LCD Transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
TOC-1
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
APPENDIX A
Specifications and
Reference Data
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Functional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-2
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-3
Foundation Fieldbus Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .A-4
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-9
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-12
Tagging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-14
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-14
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-15
APPENDIX B
Product
Certifications
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1
European Union Directive Information . . . . . . . . . . . . . . . . . . . . . . . . .B-1
Hazardous Locations Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
Rosemount 644 with Foundation fieldbus. . . . . . . . . . . . . . . . . . . .B-2
North American Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
European Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-3
IECEx Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-4
Japanese Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Combination Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Russian GOST Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Kazakhstan GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Ukraine GOST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-6
Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-7
APPENDIX C
Foundation
fieldbus Block
Information
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2
Sensor Transducer Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-5
Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-5
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-8
AI Parameter Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-9
LCD Transducer Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-11
PID Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-12
TOC-2
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Rosemount 644
Temperature Transmitters
Rosemount 644 Hardware Revision
FOUNDATION™ Fieldbus Device Revision
Device Descriptor Revision
9
2
1
NOTICE
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure to thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 p.m. CST)
National Response Center
1-800-654-7768 (24 hours a day)
Equipment service needs
International
1-(952)-906-8888
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware
or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact a Emerson Process
Management Sales Representative.
www.rosemount.com
Reference Manual
00809-0400-4728, Rev AA
June 2011
Section 1
Rosemount 644
Introduction
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-3
Return of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-4
SAFETY MESSAGES
Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
•
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
•
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
•
Before connecting FOUNDATION fieldbus in an explosive atmosphere, make sure
the instruments in the loop are installed in accordance with intrinsically safe or
non-intrinsic field wiring practices.
•
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
•
All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
•
Do not remove the thermowell while in operation.
•
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
•
www.rosemount.com
Use extreme caution when making contact with the leads and terminals.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
OVERVIEW
Manual
This manual is designed to assist in the installation, operation, and
maintenance of Rosemount 644 head mount and 644 rail mount.
Section 1: Introduction
•
Transmitter and Manual Overview
•
Considerations
•
Return of Material
Section 2: Installation
•
Mounting
•
Installation
•
Wiring
•
Power Supply
•
Commissioning
Section 3: Configuration
•
Calibration
•
Hardware Maintenance
•
Diagnostic Messaging
Appendix A: Specifications and Reference Data
•
Specifications
•
Dimensional Drawings
•
Ordering Information
•
Biotechnology, Pharmaceutical Industries, and Sanitary Applications
Appendix B: Product Certifications
•
Product Certifications
•
Installation Drawings
Appendix C: Foundation fieldbus Block Information
•
Transmitter
1-2
Information regarding the Function Blocks
Features of the Rosemount 644 include:
•
Accepts inputs from a wide variety of sensors
•
Configuration using FOUNDATION fieldbus
•
Electronics that are completely encapsulated in epoxy and enclosed in
a metal housing, making the transmitter extremely durable and
ensuring long-term reliability
•
A compact size and two housing options allowing mounting flexibility for
the control room or the field
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Refer to the following literature for a full range of compatible connection
heads, sensors, and thermowells provided by Emerson Process
Management.
•
Temperature Sensors and Assemblies Product Data Sheet, Volume 1
(document number 00813-0100-2654)
•
Temperature Sensors and Assemblies Product Data Sheet, Volume 2
(document number 00813-0200-2654)
CONSIDERATIONS
General
Electrical temperature sensors such as RTDs and thermocouples produce
low-level signals proportional to their sensed temperature. The 644 converts
the low-level sensor signal to a standard 4–20 mA dc, or digital FOUNDATION
fieldbus signal that is relatively insensitive to lead length and electrical noise.
This signal is then transmitted to the control room via two wires.
Commissioning
The transmitter can be commissioned before or after installation. It may be
useful to commission it on the bench, before installation, to ensure proper
operation and to become familiar with its functionality. Make sure the
instruments in the loop are installed in accordance with intrinsically safe,
FISCO, or non-incendive field wiring practices.
Mechanical
Location
When choosing an installation location and position, take into account the
need for access to the transmitter.
Special Mounting
Special mounting hardware is available for mounting a 644 head mount
transmitter to a DIN rail or assembling a new 644 head mount to an existing
threaded sensor connection head (former option code L1).
Electrical
Proper electrical installation is necessary to prevent errors due to sensor lead
resistance and electrical noise. For best results, shielded cable should be
used in electrically noisy environments.
Make wiring connections through the cable entry in the side of the connection
head. Be sure to provide adequate clearance for cover removal.
Environmental
The transmitter electronics module is permanently sealed within the housing,
resisting moisture and corrosive damage. Verify that the operating
atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Temperature Effects
The transmitter will operate within specifications for ambient temperatures
between –40 and 185 °F (–40 and 85 °C). Heat from the process is
transferred from the thermowell to the transmitter housing. If the expected
process temperature is near or beyond specification limits, consider the use of
additional thermowell lagging, and extension nipple, or a remote mounting
configuration to isolate the transmitter from the process.
Figure 1-1 provides an example of the relationship between transmitter
housing temperature rise and extension length.
1-3
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Figure 1-1. 644 head mount
Transmitter Connection Head
Temperature Rise vs. Extension
Length
Housing Temperature Rise, Above
Ambient °C (°F)
60 (108)
50 (90)
40 (72)
815 °C (1500 °F) Oven Temperature
30 (54)
22
20 (36)
540 °C (1000 °F)
Oven Temperature
10 (18)
250 °C (482 °F) Oven Temperature
0
3
4
3.6
5
6
7
8
Extension Length (in.)
9
Example
The transmitter specification limit is 85 °C. If the ambient temperature is 55 °C
and the process temperature to be measured is 800 °C, the maximum
permissible connection head temperature rise is the transmitter specification
limit minus the ambient temperature (moves 85 to 55 °C), or 30 °C.
In this case, an extension of 100 mm meets this requirement, but 125 mm
provides a margin of 8 °C, thereby reducing any temperature effects in the
transmitter.
RETURN OF MATERIALS
To expedite the return process in North America, call the Emerson Process
Management National Response Center toll-free at 800-654-7768. This
center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for the following information:
•
Product model
•
Serial numbers
•
The last process material to which the product was exposed
The center will provide
•
A Return Material Authorization (RMA) number
•
Instructions and procedures that are necessary to return goods that
were exposed to hazardous substances
For other locations, please contact a Emerson Process Management sales
representative.
NOTE
If a hazardous substance is identified, a Material Safety Data Sheet (MSDS),
required by law to be available to people exposed to specific hazardous
substances, must be included with the returned materials.
PRODUCT
RECYCLING/DISPOSAL
1-4
Recycling of equipment and packaging should be taken into consideration
and disposed of in accordance with local and national legislation/regulations.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Section 2
Rosemount 644
Installation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-7
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-11
SAFETY MESSAGES
Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
•
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
•
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
•
Before connecting a Field Communicator in an explosive atmosphere, make sure
the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
•
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
•
All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
•
Do not remove the thermowell while in operation.
•
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
•
www.rosemount.com
Use extreme caution when making contact with the leads and terminals.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Figure 2-1. Installation Flowchart
START
HERE
Bench
Calibration?
FIELD INSTALL
BASIC SETUP
Set Sensor Type
Set Number of Wires
Set Units
Set Range Values
Set Damping
VERIFY
Simulate Sensor Input
Within
Specifications?
Refer to Section 3: Configuration
2-2
Set Failure Mode
Switch
Mount Transmitter
Wire Transmitter
Power Transmitter
FINISHED
Does not apply to the 644
with FOUNDATION fieldbus
Reference Manual
00809-0400-4728, Rev AA
June 2011
MOUNTING
Rosemount 644
Mount the transmitter at a high point in the conduit run to prevent moisture
from draining into the transmitter housing.
The 644 head mount installs:
•
In a connection head or universal head mounted directly on a sensor
assembly
•
Apart from a sensor assembly using a universal head
•
To a DIN rail using an optional mounting clip.
The 644 rail mount attaches directly to a wall or to a DIN rail.
Mounting a 644H to a DIN Rail
To attach a head mount transmitter to a DIN rail, assemble the appropriate rail
mounting kit (part number 00644-5301-0010) to the transmitter as shown in
Figure 2-2.
Figure 2-2. Assembling Rail Clip
Hardware to a 644H
G-Rail (asymmetric)
Top Hat Rail (symmetric)
Mounting
Hardware
Mounting
Hardware
Transmitter
Transmitter
Rail Clip
Rail Clip
Note: Kit includes Mounting Hardware and both types of Rail Kits.
Retrofitting a 644H for Use in an Existing Threaded Sensor Connection
Head
To mount a 644H in an existing threaded sensor connection head (former
option code L1), order the 644H retrofit kit (part number 00644-5321-0010).
The retrofit kit includes a new mounting bracket and all associated hardware
necessary to facilitate the installation of the 644H in the existing head. See
Figure 2-3.
Figure 2-3. Assembling 644H for
Use in an Existing L1
Connection Head
Existing Threaded Sensor Connection Head
(Former option code L1)
Kit includes
replacement bracket
and screws.
2-3
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
INSTALLATION
Typical European
Installation
Head Mount Transmitter with DIN Plate Style Sensor
1.
Attach the thermowell to the pipe or process container wall. Install
and tighten the thermowell before applying process pressure.
2.
Assemble the transmitter to the sensor. Push the transmitter
mounting screws through the sensor mounting plate and insert the
snap rings (optional) into the transmitter mounting screw groove.
3.
Wire the sensor to the transmitter (see Figure 2-7 on page 2-8).
4.
Insert the transmitter-sensor assembly into the connection head.
Thread the transmitter mounting screw into the connection head
mounting holes. Assemble the extension to the connection head.
Insert the assembly into the thermowell.
5.
Attach a cable gland into the shielded cable.
6.
Insert the shielded cable leads into the connection head through the
cable entry. Connect and tighten the cable gland.
7.
Connect the shielded power cable leads to the transmitter power
terminals. Avoid contact with sensor leads and sensor connections.
8.
Install and tighten the connection head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
B
A
C
D
E
A = 644H Transmitter
B = Connection Head
C = Thermowell
2-4
F
D = Transmitter Mounting Screws
E = Integral Mount Sensor with Flying Leads
F = Extension
Reference Manual
00809-0400-4728, Rev AA
June 2011
Typical North American
Installation
Rosemount 644
Head Mount Transmitter with Threaded Sensor
1.
Attach the thermowell to the pipe or process container wall. Install
and tighten thermowells before applying process pressure.
2.
Attach necessary extension nipples and adapters to the thermowell.
Seal the nipple and adapter threads with silicone tape.
3.
Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
4.
Pull the sensor wiring leads through the universal head and
transmitter. Mount the transmitter in the universal head by threading
the transmitter mounting screws into the universal head mounting
holes.
5.
Mount the transmitter-sensor assembly into the thermowell. Seal
adapter threads with silicone tape.
6.
Install conduit for field wiring to the conduit entry of the universal
head. Seal conduit threads with silicone tape.
7.
Pull the field wiring leads through the conduit into the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact
with other terminals.
8.
Install and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A
D
B
C
E
A = Threaded Thermowell
B = Threaded Style Sensor
C = Standard Extension
D = Universal Head
E = Conduit Entry
2-5
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
LCD Display Installation
The LCD display provides local indication of the transmitter output and
abbreviated diagnostic messages governing transmitter operation.
Transmitters ordered with the LCD display are shipped with the meter
installed. After-market installation of the meter can be performed if the
transmitter has a meter connector (transmitter revision 5.5.2 or later).
After-market installation requires the meter kit (part number
00644-4430-0001), which includes:
•
LCD display assembly (includes LCD display, meter spacer,
and 2 screws)
•
Meter cover with O-ring in place
Figure 2-4. Installing the LCD
Display
Captive Mounting Screws and Springs
Meter Spacer
644H
10 pin Connector
LCD Display
Use the following procedure to install the meter.
1.
If the transmitter is installed in a loop, secure the loop and disconnect
the power. If the transmitter is installed in an enclosure, remove the
cover from the enclosure.
2.
Decide meter orientation (the meter can be rotated in 90°
increments). To change meter orientation, remove the screws located
above and below the display screen. Lift the meter off the meter
spacer. Remove the 8-pin plug and re-insert it in the location that will
result in the desired viewing orientation.
3.
Reattach the meter to the meter spacer using the screws. If the meter
was rotated 90° from its original position, it will be necessary to
remove the screws from their original holes and re-insert them in the
adjacent screw’s holes.
4.
Line up the 10-pin connector with the 10-pin socket and push the
meter into the transmitter until it snaps into place.
5.
Attach the meter cover; tighten at least one-third turn after the O-ring
contacts the transmitter housing. The cover must be fully engaged to
meet explosion-proof requirements.
6.
Use a Field Communicator, AMS software, or a FOUNDATION fieldbus
Communication tool to configure the meter to the desired display.
NOTE
Observe the following LCD display temperature limits:
Operating: –4 to 185 °F (–20 to 85 °C)
Storage: –50 to 185 °F (–45 to 85 °C)
2-6
Reference Manual
00809-0400-4728, Rev AA
June 2011
WIRING
Rosemount 644
All power to the transmitter is supplied over the signal wiring. Use ordinary
copper wire of sufficient size to ensure that the voltage across the transmitter
power terminals does not drop below 9 Vdc.
If the sensor is installed in a high-voltage environment and a fault condition or
installation error occurs, the sensor leads and transmitter terminals could
carry lethal voltages. Use extreme caution when making contact with the
leads and terminals.
NOTE
Do not apply high voltage (e.g., ac line voltage) to the transmitter terminals.
Abnormally high voltage can damage the unit. (Sensor and transmitter power
terminals are rated to 42.4 Vdc. A constant 42.4 volts across the sensor
terminals may damage the unit.)
The transmitters will accept inputs from a variety of RTD and thermocouple
types. Refer to Figure 2-5 on page 2-7 when making sensor connections.
Refer to Figure 2-6 on page 2-8 for FOUNDATION fieldbus installations.
Use the following steps to wire the power and sensor to the transmitter:
1.
Remove the terminal block cover (if applicable).
2.
Connect the positive power lead to the “+” terminal. Connect the
negative power lead to the “–” terminal (see Figure 2-7).
3.
Tighten the terminal screws. When tightening the sensor and power
wires, the max torque is 6-in.-lbs (0.7 N-m).
4.
Reattach and tighten the cover (if applicable).
5.
Apply power (see “Power Supply”).
Figure 2-5. Transmitter Power,
Communication, and Sensor
Terminals
644H
Sensor
Terminals
Communication
Terminals
1
2
3
4
Power Terminals
2-7
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Figure 2-6. Connecting a
FOUNDATION fieldbus Host
System to a Transmitter Loop
6234 ft (1900 m) max
(depending upon cable characteristics)
Terminators
Integrated Power
Conditioner and Filter
Power
Supply
(The power supply,
filter, first
terminator, and
configuration
tool are typically
located in the
control room.)
(Spur)
(Spur)
(Trunk)
FOUNDATION
fieldbus
Configuration
Tool
Devices 1
through 16
Sensor Connections
Figure 2-7. Sensor Wiring
Diagrams
Power/
Signal
Wiring
The 644 is compatible with a number of RTD and thermocouple sensor types.
Figure 2-7 shows the correct input connections to the sensor terminals on the
transmitter. To ensure a proper sensor connection, anchor the sensor lead
wires into the appropriate compression terminals and tighten the screws.
644 Sensor Connections Diagram
1234
2-wire
RTD and 1234
3-wire RTD*
and 1234
4-wire RTD
and 1234
T/C
and mV
* Emerson Process Management provides 4-wire sensors for all single element RTDs. Use these
RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical
tape.
Thermocouple or Millivolt Inputs
The thermocouple can be connected directly to the transmitter. Use
appropriate thermocouple extension wire if mounting the transmitter remotely
from the sensor. Make millivolt inputs connections with copper wire. Use
shielding for long runs of wire.
2-8
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
RTD or Ohm Inputs
The transmitters will accept a variety of RTD configurations, including 2-wire,
3-wire, or 4-wire. If the transmitter is mounted remotely from a 3-wire or 4-wire
RTD, it will operate within specifications, without recalibration, for lead wire
resistances of up to 60 ohms per lead (equivalent to 6,000 feet of 20 AWG
wire). In this case, the leads between the RTD and transmitter should be
shielded. If using only two leads, both RTD leads are in series with the sensor
element, so significant errors can occur if the lead lengths exceed three feet
of 20 AWG wire (approximately 0.05 °C/ft). For longer runs, attach a third or
fourth lead as described above.
Sensor Lead Wire Resistance Effect– RTD Input
When using a 4-wire RTD, the effect of lead resistance is eliminated and
has no impact on accuracy. However, a 3-wire sensor will not fully cancel
lead resistance error because it cannot compensate for imbalances in
resistance between the lead wires. Using the same type of wire on all
three lead wires will make a 3-wire RTD installation as accurate as
possible. A 2-wire sensor will produce the largest error because it directly
adds the lead wire resistance to the sensor resistance. For 2- and 3-wire
RTDs, an additional lead wire resistance error is induced with ambient
temperature variations. The table and the examples shown below help
quantify these errors.
Table 2-1. Examples of
Approximate Basic Error
Sensor Input
Approximate Basic Error
4-wire RTD
3-wire RTD
None (independent of lead wire resistance)
± 1.0  in reading per ohm of unbalanced lead wire resistance
(Unbalanced lead wire resistance = maximum imbalance between
any two leads.)
1.0  in reading per ohm of lead wire resistance
2-wire RTD
Examples of Approximate Lead Wire Resistance Effect Calculations
Given:
Total cable length:
Imbalance of the lead wires at 20 °C:
Resistance/length (18 AWG Cu):
Temperature coefficient of Cu (Cu):
Temperature coefficient of Pt(Pt):
Change in Ambient Temperature (Tamb):
RTD Resistance at 0 °C (Ro):
150 m
1.5 
0.025 /m °C
0.039 / °C
0.00385 / °C
25 °C
100  (for Pt 100 RTD)
•
Pt100 4-wire RTD: No lead wire resistance effect.
•
Pt100 3-wire RTD:
Imbalance of Lead Wires
Basic Error = -----------------------------------------------------------------  Pt  R o 
  Cu    T amb    Imbalance of Lead Wires 
Error due to amb. temp. variation = -----------------------------------------------------------------------------------------------------------------------  Pt    R o 
2-9
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Lead wire imbalance seen by the transmitter = 0.5 
0.5 
Basic error = --------------------------------------------------------------------------------- = 1.3 C
 0.00385  /  C    100  
Error due to amb. temp. var. of  25 °C
 0.0039  /  C    25 C    0.5  
= ------------------------------------------------------------------------------------------------------- =  0.1266C
 0.00385  /  C    100 
•
Pt100 2-wire RTD:
Lead Wire Resistance
Basic Error = --------------------------------------------------------  Pt  R o 
  Cu    T amb    Lead Wire Resistance 
Error due to amb. temp. variation = ---------------------------------------------------------------------------------------------------------------  Pt    R o 
Lead wire resistance seen by the transmitter = 150 m × 2 wires ×
0.025 /m = 7.5 
7.5 
Basic error = --------------------------------------------------------------------------------- = 19.5 C
 0.00385  /  C    100  
Error due to amb. temp. var. of  25 °C
 0.0039  /  C    25 C    7.5  
= ------------------------------------------------------------------------------------------------------- =  1.9 C
 0.00385  /  C    100 
2-10
Reference Manual
00809-0400-4728, Rev AA
June 2011
POWER SUPPLY
Rosemount 644
FOUNDATION fieldbus Installation
Powered over FOUNDATION fieldbus with standard fieldbus power supplies.
The transmitter operates between 9.0 and 32.0 Vdc, 11 mA maximum.
Transmitter power terminals are rated to 42.4 Vdc.
The power terminals on the 644 with FOUNDATION fieldbus are polarity
insensitive.
Ground the Transmitter
The transmitter will operate with the current signal loop either floating or
grounded. However, the extra noise in floating systems affects many types of
readout devices. If the signal appears noisy or erratic, grounding the current
signal loop at a single point may solve the problem. The best place to ground
the loop is at the negative terminal of the power supply. Do not ground the
current signal loop at more than one point.
The transmitter is electrically isolated to 500 Vdc/ac rms (707 Vdc), so the
input circuit may also be grounded at any single point. When using a
grounded thermocouple, the grounded junction serves as this point.
Neither side of the loop should be grounded on FOUNDATION fieldbus devices.
Only the shield wire should be grounded.
NOTE
Do not ground the signal wire at both ends.
Ungrounded Thermocouple, mV, and RTD/Ohm Inputs
Each process installation has different requirements for grounding. Use the
grounding options recommended by the facility for the specific sensor type or
begin with grounding Option 1 (the most common).
Option 1:
1.
Connect signal wiring shield to the sensor wiring shield.
2.
Ensure the two shields are tied together and electrically isolated from
the transmitter housing.
3.
Ground shield at the power supply end only.
4.
Ensure that the sensor shield is electrically isolated from the
surrounding grounded fixtures.
Sensor Wires
Transmitter
Shield ground point
FOUNDATION Fieldbus segment
Connect shields together, electrically isolated from the transmitter
2-11
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Option 2:
1.
Connect sensor wiring shield to the transmitter housing (only if the
housing is grounded).
2.
Ensure the sensor shield is electrically isolated from surrounding
fixtures that may be grounded.
3.
Ground signal wiring shield at the power supply end.
Sensor Wires
Transmitter
Shield ground point
FOUNDATION Fieldbus segment
Option 3:
1.
Ground sensor wiring shield at the sensor, if possible.
2.
Ensure that the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3.
Do not connect the signal wiring shield to the sensor wiring shield.
4.
Ground signal wiring shield at the power supply end.
Sensor Wires
Transmitter
Shield ground point
FOUNDATION Fieldbus segment
Grounded Thermocouple Inputs
1.
Ground sensor wiring shield at the sensor.
2.
Ensure that the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing.
3.
Do not connect the signal wiring shield to the sensor wiring shield.
4.
Ground signal wiring shield at the power supply end.
Sensor Wires
Transmitter
Shield ground point
FOUNDATION Fieldbus segment
2-12
Reference Manual
00809-0400-4728, Rev AA
June 2011
Section 3
Rosemount 644
Configuration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
General Block Information . . . . . . . . . . . . . . . . . . . . . . . . . page 3-2
FOUNDATION fieldbus function blocks . . . . . . . . . . . . . . . . page 3-4
Operation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . page 3-15
OVERVIEW
This section provides information on configuring, troubleshooting, operating,
and maintaining the Rosemount 644 Temperature transmitter using
FOUNDATION fieldbus protocol.
SAFETY MESSAGES
Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or
serious injury.
•
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
•
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
•
Before powering a FOUNDATION fieldbus segment in an explosive atmosphere,
make sure the instruments in the loop are installed in accordance with intrinsically
safe or non-incendive field wiring practices.
•
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
•
All connection head covers must be fully engaged to meet
explosion-proof requirements.
Process leaks could result in death or serious injury.
•
Do not remove the thermowell while in operation.
•
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
•
www.rosemount.com
Use extreme caution when making contact with the leads and terminals.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
GENERAL BLOCK
INFORMATION
Device Description
Before configuring the device, ensure the host has the appropriate Device
Description file revision for this device. The device descriptor can be found on
www.rosemount.com. The initial release of the Rosemount 644 with
FOUNDATION fieldbus protocol is device revision 1.
Node Address
The transmitter is shipped at a temporary (248) address. This will enable
FOUNDATION fieldbus host systems to automatically recognize the device and
move it to a permanent address.
Modes
The Resource, Transducer, and all function blocks in the device have modes
of operation. These modes govern the operation of the block. Every block
supports both automatic (AUTO) and out of service (OOS) modes. Other
modes may also be supported.
Changing Modes
To change the operating mode, set the MODE_BLK.TARGET to the desired
mode. After a short delay, the parameter MODE_BLOCK.ACTUAL should
reflect the mode change if the block is operating properly.
Permitted Modes
It is possible to prevent unauthorized changes to the operating mode of a
block. To do this, configure MODE_BLOCK.PERMITTED to allow only the
desired operating modes. It is recommended to always select OOS as one of
the permitted modes.
Types of Modes
For the procedures described in this manual, it will be helpful to understand
the following modes:
AUTO
The functions performed by the block will execute. If the block has any
outputs, these will continue to update. This is typically the normal
operating mode.
Out of Service (OOS)
The functions performed by the block will not execute. If the block has any
outputs, these will typically not update and the status of any values passed
to downstream blocks will be “BAD.” To make some changes to the
configuration of the block, change the mode of the block to OOS. When
the changes are complete, change the mode back to AUTO.
MAN
In this mode, variables that are passed out of the block can be manually
set for testing or override purposes.
Other Types of Modes
Other types of modes are Cas, RCas, ROut, IMan, and LO. Some of these
may be supported by different function blocks in the 644. For more
information, see the Function Block manual (document number
00809-0100-4783).
3-2
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
NOTE
When an upstream block is set to OOS, this will impact the output status of all
downstream blocks. The figure below depicts the hierarchy of blocks:
Resource
Block
Link Active Scheduler
Transducer
Block
Analog Input
(AI Block)
Other
Function
Blocks
The 644 can be designated to act as the backup Link Active Scheduler (LAS)
in the event that the designated LAS is disconnected from the segment. As
the backup LAS, the 644 will take over the management of communications
until the host is restored.
The host system may provide a configuration tool specifically designed to
designate a particular device as a backup LAS. Otherwise, this can be
configured manually as follows:
1.
2.
Block Installation
Access the Management Information Base (MIB) for the 644.
To activate the LAS capability, write 0x02 to the
BOOT_OPERAT_FUNCTIONAL_CLASS object (Index 605). To
deactivate, write 0x01.
Restart the device.
Rosemount devices are pre-configured with function blocks at the factory, the
default permanent configuration for the 644 is listed below. The 644 can have
up to ten additional instantiated function blocks.
•
2 Analog Input Blocks (tag names AI 1300, AI 1400)
•
1 Proportional/Integral/Derivative Block (tag name PID 1500)
The 644 supports the use of Function Block Instantiation. When a device
supports block instantiation, the number of blocks and block types can be
defined to match specific application needs.The number of blocks that can be
instantiated is only limited by the amount of memory within the device and the
block types that are supported by the device. Instantiation does not apply to
standard device blocks like the Resource, Sensor Transducer, LCD
Transducer, and Advanced Diagnostics Blocks.
By reading the parameter “FREE_SPACE” in the Resource block you can
determine how many blocks you can instantiate. Each block that you
instantiate takes up 4.5% of the “FREE_SPACE.”
Block instantiation is done by the host control system or configuration tool, but
not all hosts are required to implement this functionality. Please refer to your
specific host or configuration tool manual for more information.
3-3
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Capabilities
Virtual Communication Relationship (VCRs)
There are a total of 12 VCRs. One is permanent and 11 are fully configurable
by the host system. Sixteen link objects are available.
Network Parameter
Value
Slot Time
Maximum Response Delay
Maximum Inactivity to Claim LAS Delay
Minimum Inter DLPDU Delay
Time Sync class
Maximum Scheduling Overhead
Per CLPDU PhL Overhead
Maximum Inter-channel Signal Skew
Required Number of Post-transmission-gab-ext Units
Required Number of Preamble-extension Units
8
2
32
8
4 (1ms)
21
4
0
0
1
Block Execution times
Analog Input = 45 ms
PID = 60 ms
FOUNDATION FIELDBUS
FUNCTION BLOCKS
For reference information on the Resource, Sensor Transducer, AI, LCD
Transducer blocks refer to FOUNDATION fieldbus Block Information on
page A-1. Reference information on the PID block can be found in the
Function Block manual document number 00809-0100-4783.
Resource Block (index number 1000)
The Resource Function Block (RB) contains diagnostic, hardware, and
electronics information. There are no linkable inputs or outputs to the
Resource Block.
Sensor Transducer Block (index number 1100)
The Sensor Transducer Function Block (STB) temperature measurement
data includes sensor and terminal temperature. The STB also includes
information about sensor type, engineering units, linearization, reranging,
damping, temperature compensation, and diagnostics.
LCD Transducer Block (index number 1200)
The LCD Transducer Block is used to configure the LCD meter.
Analog Input Block (index number 1300 and 1400)
The Analog Input Function Block (AI) processes the measurements from the
sensor and makes them available to other function blocks. The output value
from the AI block is in engineering units and contains a status indicating the
quality of the measurement. The AI block is widely used for scaling
functionality.
PID Block (index number 1500)
The PID Function Block combines all of the necessary logic to perform
proportional/integral/derivative (PID) control. The block supports mode
control, signal scaling and limiting, feed forward control, override tracking,
alarm limit detection, and signal status propagation.
3-4
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
The block supports two forms of the PID equation: Standard and Series. You
can choose the appropriate equation using the MATHFORM parameter. The
Standard ISA PID equation is the default selection.
Resource Block
FEATURES and FEATURES_SEL
The parameters FEATURES and FEATURE_SEL determine optional
behavior of the 644.
FEATURES
The FEATURES parameter is read only and defines which features are
supported by the 644. Below is a list of the FEATURES the 644 supports.
UNICODE
All configurable string variables in the 644, except tag names, are octet
strings. Either ASCII or Unicode may be used. If the configuration device is
generating Unicode octet strings, you must set the Unicode option bit.
REPORTS
The 644 supports alert reports. The Reports option bit must be set in the
features bit string to use this feature. If it is not set, the host must poll for
alerts.
SOFT W LOCK
Inputs to the security and write lock functions include the software write
lock bits of the FEATURE_SEL parameter, the WRITE_LOCK parameter,
and the DEFINE_WRITE_LOCK parameter.
The WRITE_LOCK parameter prevents modification of parameters within
the device except to clear the WRITE_LOCK parameter. During this time,
the block will function normally updating inputs and outputs and executing
algorithms. When the WRITE_LOCK condition is cleared, a WRITE_ALM
alert is generated with a priority that corresponds to the WRITE_PRI
parameter.
The FEATURE_SEL parameter enables the user to select the software
write lock or no write lock capability. In order to enable the software write
lock, the SOFT_W_LOCK bit must be set in the FEATURE_SEL
parameter. Once this bit is set, the WRITE_LOCK parameter may be set to
“Locked” or “Unlocked.” Once the WRITE_LOCK parameter is set to
“Locked” by the software, all user requested writes as determined by the
DEFINE_WRITE_LOCK parameter shall be rejected.
The DEFINE_WRITE_LOCK parameter allows the user to configure
whether the write lock function will control writing to all blocks, or only to
the resource and transducer blocks. Internally updated data such as
process variables and diagnostics will not be restricted.
N/A = No blocks are blocked
Physical = Locks resource and transducer block
Everything = Locks every block.
3-5
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
The following table displays all possible configurations of the
WRITE_LOCK parameter.
FEATURE_SEL
SW_SEL bit
WRITE_LOCK
WRITE_LOCK
Read/Write
Write access
DEFINE_WRITE_LOCK to blocks
0 (off)
1 (on)
1 (on)
1 (unlocked)
1 (unlocked)
2 (locked)
Read only
Read/Write
Read/Write
NA
NA
Physical
1 (on)
2 (locked)
Read/Write
Everything
All
All
Function
Blocks only
None
FEATURES_SEL
FEATURES_SEL is used to turn on any of the supported features. The
default setting of the 644 does not select any of these features. Choose
one of the supported features if any.
MAX_NOTIFY
The MAX_NOTIFY parameter value is the maximum number of alert reports
that the resource can have sent without getting a confirmation, corresponding
to the amount of buffer space available for alert messages. The number can
be set lower, to control alert flooding, by adjusting the LIM_NOTIFY
parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
PlantWeb™ Alerts
The alerts and recommended actions should be used in conjunction with
“Operation and Maintenance” on page 3-15.
The Resource Block will act as a coordinator for PlantWeb alerts. There will
be three alarm parameters (FAILED_ALARM, MAINT_ALARM, and
ADVISE_ALARM) which will contain information regarding some of the device
errors which are detected by the transmitter software. There will be a
RECOMMENDED_ACTION parameter which will be used to display the
recommended action text for the highest priority alarm and a HEALTH_INDEX
parameters (0 - 100) indicating the overall health of the transmitter.
FAILED_ALARM will have the highest priority followed by MAINT_ALARM
and ADVISE_ALARM will be the lowest priority.
FAILED_ALARMS
A failure alarm indicates a failure within a device that will make the device
or some part of the device non-operational. This implies that the device is
in need of repair and must be fixed immediately. There are five parameters
associated with FAILED_ALARMS specifically, they are described below.
FAILED_ENABLED
This parameter contains a list of failures in the device which makes the
device non-operational that will cause an alert to be sent. Below is a list of
the failures with the highest priority first.
1.
2.
3.
4.
5.
3-6
Electronics
NV Memory
HW / SW Incompatible
Primary Value
Secondary Value
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
FAILED_MASK
This parameter will mask any of the failed conditions listed in
FAILED_ENABLED. A bit on means that the condition is masked out from
alarming and will not be reported.
FAILED_PRI
Designates the alerting priority of the FAILED_ALM, see “Alarm Priority”
on page 3-13. The default is 0 and the recommended value are between 8
and 15.
FAILED_ACTIVE
This parameter displays which of the alarms is active. Only the alarm with
the highest priority will be displayed. This priority is not the same as the
FAILED_PRI parameter described above. This priority is hard coded within
the device and is not user configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device
non-operational.
MAINT_ALARMS
A maintenance alarm indicates the device or some part of the device
needs maintenance soon. If the condition is ignored, the device will
eventually fail. There are five parameters associated with
MAINT_ALARMS, they are described below.
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating
the device or some part of the device needs maintenance soon.
Below is a list of the conditions with the highest priority first.
1.
2.
3.
4.
5.
Primary Value Degraded
Secondary Value Degraded
Diagnostic
Configuration Error
Calibration Error
MAINT_MASK
The MAINT_MASK parameter will mask any of the failed conditions listed
in MAINT_ENABLED. A bit on means that the condition is masked out
from alarming and will not be reported.
MAINT_PRI
MAINT_PRI designates the alarming priority of the MAINT_ALM, “Process
Alarms” on page 3-12. The default is 0 and the recommended values is 3
to 7.
MAINT_ACTIVE
The MAINT_ACTIVE parameter displays which of the alarms is active.
Only the condition with the highest priority will be displayed. This priority is
not the same as the MAINT_PRI parameter described above. This priority
is hard coded within the device and is not user configurable.
MAINT_ALM
An alarm indicating the device needs maintenance soon. If the condition is
ignored, the device will eventually fail.
3-7
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Advisory Alarms
An advisory alarm indicates informative conditions that do not have a
direct impact on the device's primary functions. There are five parameters
associated with ADVISE_ALARMS. They are described below.
ADVISE_ENABLED
The ADVISE_ENABLED parameter contains a list of informative
conditions that do not have a direct impact on the device's primary
functions. Below is a list of the advisories with the highest priority first.
1.
2.
NV Writes Deferred
SPM Process Anomaly detected
ADVISE_MASK
The ADVISE_MASK parameter will mask any of the failed conditions listed
in ADVISE_ENABLED. A bit on means the condition is masked out from
alarming and will not be reported.
ADVISE_PRI
ADVISE_PRI designates the alarming priority of the ADVISE_ALM, see
“Process Alarms” on page 3-12. The default is 0 and the recommended
values are 1 or 2.
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays which of the advisories is
active. Only the advisory with the highest priority will be displayed. This
priority is not the same as the ADVISE_PRI parameter described above.
This priority is hard coded within the device and is not user configurable.
ADVISE_ALM
ADVISE_ALM is an alarm indicating advisory alarms. These conditions do
not have a direct impact on the process or device integrity.
Recommended Actions for PlantWeb Alerts
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will
give a recommended course of action to take based on which type and
which specific event of the PlantWeb alerts are active.
3-8
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table 3-1.
RB.RECOMMENDED_ACTION
Alarm Type
None
Failed/Maint/Advise
Active Event
Recommended Action
Text String
None
NV Writes Deferred
No action required
Non-volatile writes have been deferred, leave
the device powered until the advisory goes
away
Re-write the Sensor Configuration
Confirm the operating range of the applied
sensor and/or verify the sensor connection and
device environment
Retrim the device
Verify the ambient temperature is within
operating limits
Replace the Device
Verify the Hardware Revision is compatible with
the Software Revision
Reset the device then download the Device
Configuration
Verify the instrument process is within the
Sensor range and / or confirm sensor
configuration and wiring.
Verify the ambient temperature is within
operating limits
Advisory
PlantWeb Alerts
Configuration Error
Primary Value
Degraded
Maintenance
Calibration Error
Secondary Value
Degraded
Electronics Failure
HW / SW Incompatible
NV Memory Failure
Failed
Primary Value Failure
Secondary Value
Failure
Sensor Transducer Block
NOTE
When the engineering units of the XD_SCALE are selected, the engineering
units in the Transducer Block change to the same units. THIS IS THE ONLY
WAY TO CHANGE THE ENGINEERING UNITS IN THE SENSOR
TRANSDUCER BLOCK.
Damping
The damping parameter in the Transducer Block may be used to filter
measurement noise. By increasing the damping time, the transmitter will have
a slower response time, but will decrease the amount of process noise that is
translated to the Transducer Block Primary Value. Because both the LCD and
AI Block get input from the Transducer Block, adjusting the damping
parameter will effect both blocks.
NOTE
The AI Block has it's own filtering parameter called PV_FTIME. For simplicity,
it is better to do filtering in the Transducer Block as damping will be applied to
primary value on every sensor update. If filtering is done in AI block, damping
will be applied to output every macrocycle. The LCD will display value from
Transducer block.
Analog Input (AI)
Function Block
Configure the AI block
A minimum of four parameters are required to configure the AI Block. The
parameters are described below with example configurations shown at the
end of this section.
CHANNEL
Select the channel that corresponds to the desired sensor measurement.
The 644 measures both sensor temperature (channel 1) and terminal
temperature (channel 2).
3-9
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
L_TYPE
The L_TYPE parameter defines the relationship of the sensor
measurement (sensor temperature) to the desired output temperature of
the AI Block. The relationship can be direct or indirect.
Direct
Select direct when the desired output will be the same as the sensor
measurement (sensor temperature).
Indirect
Select indirect when the desired output is a calculated measurement
based on the sensor measurement (e.g. ohm or mV). The relationship
between the sensor measurement and the calculated measurement will be
linear.
XD_SCALE and OUT_SCALE
The XD_SCALE and OUT_SCALE each include four parameters: 0%,
100%, engineering units, and precision (decimal point). Set these based
on the L_TYPE:
L_TYPE is Direct
When the desired output is the measured variable, set the XD_SCALE to
represent the operating range of the process. Set OUT_SCALE to match
XD_SCALE.
L_TYPE is Indirect
When an inferred measurement is made based on the sensor
measurement, set the XD_SCALE to represent the operating range that
the sensor will see in the process. Determine the inferred measurement
values that correspond to the XD_SCALE 0 and 100% points and set
these for the OUT_SCALE.
NOTE
To avoid configuration errors, only select Engineering Units for XD_SCALE
and OUT_SCALE that are supported by the device. The supported units
are:
Pressure (Channel 1)
Temperature (Channel 2)
°C
°F
K
R

mV
°C
°F
K
R

mV
When the engineering units of the XD_SCALE are selected, this causes
the engineering units of the PRIMARY_VALUE_RANGE in the Transducer
Block to change to the same units. THIS IS THE ONLY WAY TO CHANGE
THE ENGINEERING UNITS IN THE SENSOR TRANSDUCER BLOCK,
PRIMARY_VALUE_RANGE parameter.
3-10
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Configuration Examples
4-wire, Pt 100  = 385
AI1 = Process Temperature
AI2 = Terminal Temperature
Transducer Block
If Host System Supports Methods:
1. Click on Methods
2. Choose Sensor Connections
3. Follow on-screen instruction.
If Host System Doesn’t Not Support Methods:
1. Put transducer block into OOS mode.
a. Go to MODE_BLK.TARGET
b. Choose OOS (0x80)
2.
Go to SENSOR_CONNECTION.
a. Choose 4-wire (0x4)
3.
Go to SENSOR_TYPE.
a. Choose PT100A385
4.
Put the transducer block back into Auto mode.
AI Blocks (Basic Configuration)(1)
AI1 as Process Temperature
1. Put the AI Block into OOS mode.
a. Go to MODE_BLK.TARGET
b. Choose OOS (0x80)
2.
Go to CHANNEL
a. Choose Sensor 1
3.
Go to L_TYPE
a. Choose Direct
4.
Go to XD_Scale
a. Choose UNITS_INDEX to be °C
5.
Go to OUT_SCALE
a. Choose UNITS_INDEX to be °C
b. Set the 0 and 100 scale to be the same as the
PRIMARY_VALUE_RANGE
6.
7.
(1)
Put the AI Block back into Auto mode.
Follow Host Procedure Download Schedule into Block.
Configure a minimum of four parameters to get a value out of the AI Block.
3-11
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
AI2 as Terminal Temperature
1. Put the AI Block into OOS mode.
a. Go to MODE_BLK.TARGET
b. Choose OOS (0x80)
2.
Go to CHANNEL
a. Choose Body Temperature
3.
Go to L_TYPE
a. Choose Direct
4.
Go to XD_Scale
a. Choose UNITS_INDEX to be °C
5.
Go to OUT_SCALE
a. Choose UNITS_INDEX to be °C
b. Set the 0 and 100 scale to be the same as the
SECONDARY_VALUE_RANGE
6.
7.
Put the AI Block back into Auto mode.
Follow Host Procedure Download Schedule into Block.
Filtering
The filtering feature changes the response time of the device to smooth
variations in output readings caused by rapid changes in input. Adjust the
filter time constant (in seconds) using the PV_FTIME parameter. Set the filter
time constant to zero to disable the filter feature.
Process Alarms
Process Alarm detection is based on the OUT value. Configure the alarm
limits of the following standard alarms:
•
High (HI_LIM)
•
High high (HI_HI_LIM)
•
Low (LO_LIM)
•
Low low (LO_LO_LIM)
In order to avoid alarm chattering when the variable is oscillating around the
alarm limit, an alarm hysteresis in percent of the PV span can be set using the
ALARM_HYS parameter. The priority of each alarm is set in the following
parameters:
3-12
•
HI_PRI
•
HI_HI_PRI
•
LO_PRI
•
LO_LO_PRI
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Alarm Priority
Alarms are grouped into five levels of priority:
Priority
Number
0
1
2
3-7
8-15
Priority Description
The alarm condition is not used.
An alarm condition with a priority of 1 is recognized by the system, but is not
reported to the operator.
An alarm condition with a priority of 2 is reported to the operator.
Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
Status Options
Status Options (STATUS_OPTS) supported by the AI block are shown below:
Propagate Fault Forward
If the status from the sensor is Bad, Device failure or Bad, Sensor failure,
propagate it to OUT without generating an alarm. The use of these
sub-status in OUT is determined by this option. Through this option, the
user may determine whether alarming (sending of an alert) will be done by
the block or propagated downstream for alarming.
Uncertain if Limited
Set the output status of the Analog Input block to uncertain if the measured
or calculated value is limited.
BAD if Limited
Set the output status to Bad if the sensor is violating a high or low limit.
Uncertain if Man Mode
Set the output status of the Analog Input block to uncertain if the actual
mode of the block is Man.
NOTE
The instrument must be in Out of Service mode to set the status option.
Advanced Features
The AI Function Block provides added capability through the addition of the
following parameters:
ALARM_TYPE
ALARM_TYPE allows one or more of the process alarm conditions
detected by the AI function block to be used in setting its OUT_D
parameter.
OUT_D
OUT_D is the discrete output of the AI function block based on the
detection of process alarm condition(s). This parameter may be linked to
other function blocks that require a discrete input based on the detected
alarm condition.
3-13
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
LCD Transducer Block
The LCD meter connects directly to the 644 electronics FOUNDATION fieldbus
output board. The meter indicates output and abbreviated diagnostic
messages.
The first line of five characters displays the sensor being measured.
If the measurement is in error, “Error” appears on the first line. The second
line indicates if the device or the sensor is causing the error.
Each parameter configured for display will appear on the LCD for a brief
period before the next parameter is displayed. If the status of the parameter
goes bad, the LCD will also cycle diagnostics following the displayed variable.
Custom Meter Configuration
Shipped from the factory, Parameter #1 is configured to display the Primary
Variable (temperature) from the LCD Transducer Block. Parameters 2 – 4 are
not configured. To change the configuration of Parameter #1 or to configure
additional parameters 2 – 4, use the configuration parameters below.
The LCD Transducer Block can be configured to sequence four different
process variables as long as the parameters are sourced from a function
block that is scheduled to execute within the 644 temperature transmitter. If a
function block is scheduled in the 644 that links a process variable from
another device on the segment, that process variable can be displayed on the
LCD.
DISPLAY_PARAM_SEL
The DISPLAY_PARAM_SEL parameter specifies how many process
variables will be displayed. Select up to four display parameters.
BLK_TAG_#(1)
Enter the Block Tag of the function block that contains the parameter to be
displayed. The default function block tags from the factory are:
TRANSDUCER
AI 1300
AI 1400
PID 1500
BLK_TYPE_#(1)
Enter the Block Type of the function block that contains the parameter to
be displayed. This parameter is generally selected via a drop-down menu
with a list of possible function block types. (e.g. Transducer, PID, AI, etc.)
PARAM_INDEX_#(1)
The PARAM_INDEX_# parameter is generally selected via a drop-down
menu with a list of possible parameter names based upon what is
available in the function block type selected. Choose the parameter to be
displayed.
CUSTOM_TAG_#(1)
The CUSTOM_TAG_# is an optional user-specified tag identifier that can
be configured to be displayed with the parameter in place of the block tag.
Enter a tag of up to five characters.
(1)
3-14
# represents the specified parameter number.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
UNITS_TYPE_#(1)
The UNITS_TYPE_# parameter is generally selected via a drop-down
menu with three options: AUTO, CUSTOM, or NONE. Select AUTO only
when the parameter to be displayed is pressure, temperature, or percent.
For other parameters, select CUSTOM and be sure to configure the
CUSTOM_UNITS_# parameter. Select NONE if the parameter is to be
displayed without associated units.
CUSTOM_UNITS_#(1)
Specify custom units to be displayed with the parameter. Enter up to six
characters. To display Custom Units the UNITS_TYPE_# must be set to
CUSTOM.
OPERATION AND MAINTENANCE
Overview
This section contains information on operation and maintenance procedures.
METHODS AND MANUAL OPERATION
Each FOUNDATION fieldbus host or configuration tool has different ways of
displaying and performing operations. Some hosts will use Device
Descriptions (DD) and DD Methods to complete device configuration and will
display data consistently across platforms. The DD can found on
www.rosemount.com. There is no requirement that a host or configuration tool
support these features.
The information in this section will describe how to use methods in a general
fashion. In addition, if your host or configuration tool does not support
methods this section will cover manually configuring the parameters involved
with each method operation. For more detailed information on the use of
methods, see your host or configuration tool manual.
3-15
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Troubleshooting Guides
Figure 3-1. 644 troubleshooting flowchart
PROBLEMS WITH COMMUNICATIONS
Device does not
stay on segment.
Device does not
appear on segment.
1. Check wiring to device.
2. Recycle power to device.
3. Electronic failure.
Refer to “Device does not show up on
segment” in Table 3-2 for more
information.
Problem Identified?
Check Segment, see “Device
does not stay on segment” in
Table 3-2 for more information.
No
Yes
Problem Identified?
Perform Recommended
Action, see Table 3-2.
Yes
Perform Recommended
Action, see page 3-6.
No
If the problem persists
contact your local
Rosemount representative.
Table 3-2. Troubleshooting guide.
Symptom(1)
Cause
Recommended Actions
Device does not show up on segment
Unknown
No power to device
Recycle power to device
1. Ensure the device is connected to the segment.
2. Check voltage at terminals. There should be 9–32Vdc.
3. Check to ensure the device is drawing current. There
should be approximately 10.5 mA nominal (11 mA max.)
Segment problems
Electronics failing
Incompatible network settings
Device does not stay on segment(2)
Incorrect signal levels.
Refer to host documentation for
procedure.
Excess noise on segment.
Refer to host documentation for
procedure.
Electronics failing
Other
(1)
(2)
3-16
1. Replace device.
Change host network parameters.
Refer to host documentation for procedure.
1. Check for two terminators.
2. Excess cable length.
3. Bad Power supply or conditioner
1. Check for incorrect grounding.
2. Check for correct shielded wire.
3. Tighten wire connections.
4. Check for corrosion or moisture on terminals.
5. Check for Bad power supply.
1. Replace device.
1. Check for water around the transmitter.
The corrective actions should be done with consultation of your system integrator.
Wiring and installation 31.25 kbit/s, voltage mode, wire medium application guide AG-140 available from the Fieldbus Foundation.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Figure 3-2. Problems with
communications flowchart
COMMUNICATIONS ESTABLISHED BUT HAVE
“BLOCK_ERR” OR AN “ALARM” CONDITION.
See “PlantWeb™ Alerts” on page 3-6
Problem Identified?
Perform Recommended
Action, see Table 3-1.
Yes
No
Read the following parameters in the
Resource Block to determine the
recommended action.
BLOCK_ERR (see Table 3-8)
SUMMARY_STATUS (see Table 3-9)
DETAILED_STATUS (see Table 3-10)
Problem Identified?
Yes
If error condition does not exist
in the Resource Block then it is a
configuration problem, see “AI
BLOCK_ERR Conditions.” in
Table 3-6
No
Perform Recommended
Action, see Table 3-10.
For more detailed
information
Problem Identified?
Perform the following steps in the Sensor
Transducer Block to determine the
recommended action.
BLOCK_ERR (see Table 3-3)
XD_ERR (see Table 3-4)
DETAILED_STATUS (see Table 3-5)
RECOMMENDED_ACTION (see Table 3-5)
SENSOR_DETAILED STATUS (see Table 3-5)
Yes
No
Perform Recommended
Action, see Table 3-7.
Problem Identified?
Yes
No
If the problem persists
contact your local
Rosemount representative.
Perform Recommended
Action, see Table 3-5.
3-17
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Sensor Transducer Block
Sensor Calibration, Lower and Upper Trim Methods
In order to calibrate the transmitter, run the Lower and Upper Trim Methods. If
your system does not support methods, manually configure the Transducer
Block parameters listed below.
1.
2.
3.
4.
5.
6.
7.
8.
Set MODE_BLK.TARGET to OOS.
Set SENSOR_CAL_METHOD to User Trim.
Set CAL_UNIT to supported engineering units in the
Transducer Block.
Apply temperature that corresponds to the lower calibration point and
allow the temperature to stabilize. The temperature must be
between the range limits defined in PRIMRY_VALUE_RANGE.
Set values of CAL_POINT_LO to correspond to the temperature
applied by the sensor.
Apply temperature, temperature corresponding to the upper
calibration.
Allow temperature to stabilize.
Set CAL_POINT_HI.
NOTE
CAL_POINT_HI must be within PRIMARY_VALUE_RANGE and greater than
CAL_POINT_LO + CAL_MIN_SPAN
9. Set SENSOR_CAL_DATE to the current date.
10. Set SENSOR_CAL_WHO to the person responsible for the
calibration.
11. Set SENSOR _CAL_LOC to the calibration location.
12. Set MODE_BLK.TARGET to AUTO.
NOTE
If trim fails, the transmitter will automatically revert to factory trim.
Excessive correction or sensor failure could cause device status to read
“calibration error.” To clear this, trim the transmitter.
3-18
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Recall Factory Trim
To recall a factory trim on the transmitter, run the Recall Factory Trim. If your
system does not support methods, manually configure the Transducer Block
parameters listed below.
1.
2.
3.
4.
5.
6.
7.
Set MODE_BLK.TARGET to OOS.
Set SENSOR_CAL_METHOD to Factory Trim.
Set SET_FACTORY_TRIM to Recall.
Set SENSOR_CAL_DATE to the current date.
Set SENSOR_CAL_WHO to the person responsible for the
calibration.
Set SENSOR _CAL_LOC to the calibration location.
Set MODE_BLK.TARGET to AUTO.
NOTE
When sensor type is changed, the transmitter reverts to the factory trim.
Changing sensor type causes you to loose any trim performed on the
transmitter.
Table 3-3. Sensor Transducer
Block BLOCK_ERR messages
Condition Name and Description
Other
Out of Service: The actual mode is out of service.
Table 3-4. Sensor Transducer
Block XD_ERR messages
Condition Name and Description
Electronics Failure: An electrical component failed.
I/O Failure: An I/O failure occurred.
Software Error: The software has detected an internal error.
Calibration Error: An error occurred during calibration of the device.
Algorithm Error: The algorithm used in the transducer block produced an error due to
overflow, data reasonableness failure, etc.
Diagnostics
Table 3-5 lists the potential errors and the possible corrective actions for the
given values. The corrective actions are in order of increasing system level
compromises. The first step should always be to reset the transmitter and
then if the error persists, try the steps in Table 3-5. Start with the first
corrective action and then try the second.
3-19
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table 3-5. Sensor Transducer
Block STB.SENSOR_
DETAILED_ STATUS messages
STB.SENSOR_DETAILED_STATUS
Description
Invalid Configuration
Wrong sensor connection with wrong sensor
type
The micro detected a chksum or start/stop bit
failure with ASIC communication
The A/D ASIC detected a communication error
ASIC interrupts are too fast or slow
Reference resistors are greater than 25% of
known value
Citadel registers were not written correctly. (Also
CALIBRATION_ERR)
Open sensor detected
Shorted sensor detected
Open PRT detected
Sensor readings have gone beyond
PRIMRY_VALUE_RANGE values
Sensor readings have gone below 2% of lower
range or above 6% of upper range of sensor.
PRT readings have gone beyond
SECONDARY_VALUE_RANGE values
PRT readings have gone below 2% of lower
range or above 6% of upper range of PRT.
(These ranges are calculated and are not the
actual range of the PRT which is a PT100 A385)
For RTDs, this is excessive EMF detected. This
is thermocouple degradation for thermocouples.
The user trim has failed due to excessive
correction or sensor failure during the trim
method
ASIC RCV Error
ASIC TX Error
ASIC Interrupt Error
Reference Error
ASIC Configuration Error
Sensor Open
Sensor Shorted
Terminal Temperature Failure
Sensor Out of Operating Range
Sensor beyond operating limits
Terminal Temperature Out of Operating
Range
Terminal Temperature Beyond Operating
Limits
Sensor Degraded
Sensor Error
3-20
Reference Manual
00809-0400-4728, Rev AA
June 2011
Analog Input (AI)
Function Block
Rosemount 644
Status
Along with the measured or calculated PV value, every FOUNDATION fieldbus
block passes an additional parameter called STATUS. The PV and STATUS
are passed from the Transducer Block to the Analog Input Block. The
STATUS can be one of the following: GOOD, BAD, or UNCERTAIN. When
there are no problems detected by the self-diagnostics of the block, the
STATUS will be GOOD. If a problem occurs with the hardware in the device or
the quality of the process variable is compromised for some reason, the
STATUS will become either BAD or UNCERTAIN depending upon the nature
of the problem. It is important that the Control Strategy that makes use of the
Analog Input Block is configured to monitor the STATUS and take action
where appropriate when the STATUS is no longer GOOD.
Simulation
Simulate replaces the channel value coming from the Sensor Transducer
Block. For testing purposes, it is possible to manually drive the output of the
Analog Input Block to a desired value. There are two ways to do this.
Manual Mode
To change only the OUT_VALUE and not the OUT_STATUS of the AI
Block, place the TARGET MODE of the block to MANUAL. Then, change
the OUT_VALUE to the desired value.
Simulate
1.
If the SIMULATE switch is in the OFF position, move it to the ON
position. If the SIMULATE jumper is already in the ON position, you
must move it to off and place it back in the ON position.
NOTE
As a safety measure, the switch must be reset every time power is
interrupted to the device in order to enable SIMULATE. This prevents a
device that is tested on the bench from getting installed in the process with
SIMULATE still active.
2.
3.
4.
To change both the OUT_VALUE and OUT_STATUS of the AI Block,
set the TARGET MODE to AUTO.
Set SIMULATE_ENABLE_DISABLE to ‘Active.’
Enter the desired SIMULATE_VALUE to change the OUT_VALUE
and SIMULATE_STATUS_QUALITY to change the OUT_STATUS.
If errors occur when performing the above steps, be sure that the
SIMULATE jumper has been reset after powering up the device.
3-21
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table 3-6. AI BLOCK_ERR
Conditions.
Condition
Number
0
1
3
7
14
15
Condition Name and Description
Other
Block Configuration Error: the selected channel carries a measurement that
is incompatible with the engineering units selected in XD_SCALE, the L_TYPE
parameter is not configured, or CHANNEL = zero.
Simulate Active: Simulation is enabled and the block is using a simulated
value in its execution.
Input Failure/Process Variable has Bad Status: The hardware is bad, or a
bad status is being simulated.
Power Up
Out of Service: The actual mode is out of service.
Table 3-7. Troubleshooting the
AI block
Symptom
Bad or no temperature readings
(Read the AI “BLOCK_ERR”
parameter)
OUT parameter status reads
UNCERTAIN and substatus reads
EngUnitRangViolation.
3-22
Possible Causes
Recommended Actions
BLOCK_ERR reads OUT OF
SERVICE (OOS)
BLOCK_ERR reads
CONFIGURATION ERROR
1. AI Block target mode target mode set to OOS.
2. Resource Block OUT OF SERVICE.
1. Check CHANNEL parameter (see “CHANNEL” on page 3-9)
2. Check L_TYPE parameter (see “L_TYPE” on page 3-10)
3. Check XD_SCALE engineering units. (see “XD_SCALE and
OUT_SCALE” on page 2-10
Download Schedule into block. Refer to host for downloading
procedure.
1. Sensor Transducer Block Out Of Service (OOS)
2. Resource Block Out of Service (OOS)
1. Check XD_SCALE parameter.
2. Check OUT_SCALE parameter.
(see “XD_SCALE and OUT_SCALE” on page 3-10)
See Section 3: Operation and Maintenance to determine the
appropriate trimming or calibration procedure.
See “XD_SCALE and OUT_SCALE” on page 3-10.
BLOCK_ERR reads POWERUP
BLOCK_ERR reads BAD INPUT
No BLOCK_ERR but readings are
not correct. If using Indirect mode,
scaling could be wrong.
No BLOCK_ERR. Sensor needs to
be calibrated or Zero trimmed.
Out_ScaleEU_0 and EU_100
settings are incorrect.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Resource Block
This section describes error conditions found in the Resource block. Read
Table 3-8 through Table 3-10 to determine the appropriate corrective action.
Table 3-8. Resource Block
BLOCK_ERR messages
Block Errors
Table 3-8 lists conditions reported in the BLOCK_ERR parameter.
Condition Name and Description
Other
Device Needs Maintenance Now
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory.
Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost.
Device Needs Maintenance Now.
Out of Service: The actual mode is out of service.
Table 3-9. Resource Block
SUMMARY_STATUS messages
Condition Name
No repair needed
Repairable
Call Service Center
Table 3-10. Resource Block
RB.DETAILED_STATUS
RB.DETAILED_STATUS
Description
Sensor Transducer block error.
Manufacturing Block integrity error
Active when any SENSOR_DETAILED_STAUS bit is on.
The manufacturing block size, revision, or checksum is
wrong.
Verify the manufacturing block revision and the hardware
revision are correct/compatible with the software
revision.
Invalid checksum on a block of NV data.
Invalid application code checksum.
Device has been power-cycled while non-volatile writes
were being deferred to prevent premature memory
failure, the write operations have been deferred.
A high number of writes has been detected to
non-volatile memory. To prevent premature failure, the
write operations have been deferred.
Hardware/software incompatible
Non-volatile memory integrity error
ROM integrity error
Lost deferred NV data
NV Writes Deferred
3-23
Reference Manual
00809-0400-4728, Rev AA
June 2011
LCD Transducer block
Rosemount 644
This section describes error conditions found in the LCD Transducer Block.
Read Table 3-11 and to determine the appropriate corrective action.
Self Test Procedure for the LCD
The SELF_TEST parameter in the Resource block will test LCD segments.
When running, the segments of the display should light up for about five
seconds.
If your host system supports methods refer to your host documentation on
how to run the “Self Test” method. If your host system does not support
methods, then you can run this test manually be following the steps below.
1.
2.
3.
4.
Table 3-11. LCD Transducer
Block BLOCK_ERR messages
Put Resource block into “OOS” (Out of Service).
Go to the parameter called “SELF_TEST” and write the value Self
test (0x2).
Observe the LCD screen when you are doing this. All of the segments
should light up.
Put the Resource block back into “AUTO.”
Condition Name and Description
Other
Out of Service: The actual mode is out of service.
Symptom
Possible Causes
Recommended Action
The LCD displays “DSPLY#INVLID.” Read the
BLOCK_ERR and if it says “BLOCK
CONFIGURATION” perform the Recommended Action
The AI.OUT readings do not match.
One or more of the display parameters are
not configured properly.
See “LCD Transducer Block” on
page 3-14.
The OUT_SCALE of the AI block is not
configured properly.
The LCD block parameter
“DISPLAY_PARAMETER_SELECT is not
properly configured.
The resource and or the LCD Transducer
block are OOS.
Some of the LCD segments may have
gone bad.
Device is out o the temperature limit for the
LCD. (-20 to 80 °C)
See “Analog Input (AI) Function
Block” on page 3-21.
See “LCD Transducer Block (index
number 1200)” on page 3-4.
“644” is being displayed or not all of the values are
being displayed.
The display reads OOS.
The display is hard to read.
Verify that both blocks are in
“AUTO.”
See XXXX (Self Test). If some of the
segment is bad, replace the LCD.
Check ambient temperature of the
device.
3-24
Reference Manual
00809-0400-4728, Rev AA
June 2011
Appendix A
Rosemount 644
Specifications and
Reference Data
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1
Foundation Fieldbus Specifications . . . . . . . . . . . . . . . . . page A-4
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-6
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-9
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-17
SPECIFICATIONS
Functional
Inputs
User-selectable; sensor terminals rated to 42.4 Vdc. See “Accuracy” on
page A-6 for sensor options.
Output
Single 2-wired device with a completely digital output with FOUNDATION
fieldbus communication (ITK 5.1 compliant).
Isolation
Input/output isolation tested to 500 Vdc/ac rms (707 Vdc) at 50/60 Hz
Local Display
The optional five-digit integral LCD Display includes a floating or fixed decimal
point. It can also display engineering units (°F, °C, °R, K, , and millivolts),
milliampere, and percent of span. The display can be configured to alternate
between selected display options. Display settings are preconfigured at the
factory according to the standard transmitter configuration. They can be
reconfigured in the field using FOUNDATION fieldbus communications.
Humidity Limits
0–99% relative humidity
Update Time
 0.5 seconds
Accuracy (default configuration) PT 100
FOUNDATION fieldbus: ±0.15 °C
www.rosemount.com
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Physical
Electrical Connections
Model
Power and Sensor Terminals
644H
Compression screws permanently fixed to terminal block
WAGO® Spring clamp terminals are optional (option code G5)
Field Communicator Connections
Communication Terminals
644H
Clips permanently fixed to terminal block
Materials of Construction
Electronics Housing and Terminal Block
Noryl® glass reinforced
644H
Enclosure (Option code J5 or J6)
Housing
Paint
Cover O-ring
Low-copper aluminum
Polyurethane
Buna-N
Materials of Constructions (Stainless Steel Housing for Biotechnology,
Pharmaceutical Industries, and Sanitary Applications)
Housing and Standard Meter Cover
• 316 SST
Cover O-Ring
• Buna-N
Mounting
The 644R attaches directly to a wall or a DIN rail. The 644H installs in a
connection head or universal head mounted directly on a sensor assembly,
apart from a sensor assembly using a universal head, or to a DIN rail using an
optional mounting clip.
Weight
Code
644H
M5
J5, J6
J5, J6
Options
Head Mount Transmitter
LCD Display
Universal Head, Standard Cover
Universal Head, Meter Cover
Weight
92 g (3.25 oz)
38 g (1.34 oz)
577 g (20.35 oz)
667 g (23.53 oz)
Weight (Stainless Steel Housing for Biotechnology, Pharmaceutical
Industries, and Sanitary Applications)
Option Code
Standard Cover
Meter Cover
S1
S2
S3
S4
840 g (27 oz)
840 g (27 oz)
840 g (27 oz)
840 g (27 oz)
995 g (32 oz)
995 g (32 oz)
995 g (32 oz)
995 g (32 oz)
Enclosure Ratings (644H)
All option codes (S1, S2, S3, S4, J5 and J6, J7 and J8) are NEMA 4X, IP66,
and IP68. Option code J6 is CSA Enclosure Type 4X.
Sanitary Housing Surface
Surface finish is polished to 32 RMA. Laser etched product marking on
housing and standard covers.
A-2
Reference Manual
00809-0400-4728, Rev AA
June 2011
Performance
Rosemount 644
EMC (ElectroMagnetic Compatibility)
NAMUR NE 21 Standard
The 644H HART meets the requirements for NAMUR NE 21 Rating.
CE Mark
The 644 is compliant with Directive 2004/108/EC. Meets the criteria under
IEC 61326:2006.
Power Supply Effect
Less than ±0.005% of span per volt
Stability
RTDs and thermocouples have a stability of ±0.15% of output reading or 0.15
°C (whichever is greater) for 24 months.
Self Calibration
The analog-to-digital measurement circuitry automatically self-calibrates for
each temperature update by comparing the dynamic measurement to
extremely stable and accurate internal reference elements
Vibration Effect
The 644 is tested to the following specifications with no effect on performance
per IEC 60770-1, 1999:
Frequency
Vibration
10 to 60 Hz
60 to 2000 Hz
0.21 mm displacement
3 g peak acceleration
Sensor Connections
644244EH Sensor Connections Diagram
1234
2-wire
RTD and 12 34
3-wire RTD
and *
1234
4-wire RTD
and 1234
T/C
and mV
* Rosemount Inc. provides 4-wire sensors for all single element RTDs. You can use these RTDs in 3-wire
configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
A-3
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Rosemount Conformance to Specifications
A Rosemount product not only meets its published specifications, but most likely exceeds
them. Advanced manufacturing techniques and the use of Statistical Process Control provide
specification conformance to at least ± 3(1). Our commitment to continual improvement
ensures that product design, reliability, and performance will improve annually.
Lower
Specification
Limit
For example, the Reference Accuracy distribution for the 644 is shown to the right. Our
Specification Limits are ± 0.15 °C, but, as the shaded area shows, approximately 68% of the
units perform three times better than the limits. Therefore, it is very likely that you will receive
a device that performs much better than our published specifications.
–3
Conversely, a vendor who “grades” product without using Process Control, or who is not
committed to ± 3 performance, will ship a higher percentage of units that are barely within
advertised specification limits.
–2
Upper
Specification
Limit
–1
1
2
3
Accuracy distribution shown is for the 644, Pt
100 RTD sensor, Range 0 to 100 °C
(1) Sigma () is a statistical symbol to designate the standard deviation from the mean value of a normal distribution.
FOUNDATION FIELDBUS
SPECIFICATIONS
A-4
Function Blocks
Resource Block
• The resource block contains physical transmitter information including
available memory, manufacture identification, device type, software tag,
and unique identification.
Transducer Block
• The transducer block contains the actual temperature measurement data,
including sensor 1 and terminal temperature. It includes information about
sensor type and configuration, engineering units, linearization, reranging,
damping, temperature correction, and diagnostics.
LCD Block
• The LCD block is used to configure the local display, if an LCD Display is
being used.
Analog Input (AI)
• Processes the measurement and makes it available on the fieldbus
segment.
• Allows filtering, alarming, and engineering unit changes.
PID Block
• The transmitter provides control functionality with one PID function block in
the transmitter. The PID block can be used to perform single loop,
cascade, or feedforward control in the field.
Instantiable Function Blocks
• All the function blocks used by the transmitter are instantiable, meaning
the total number of function blocks is only limited by the physical memory
available in the transmitter. Since only the instantiable blocks can use
physical memory, any combination of function blocks can be used at any
given time as long as the physical memory size is not violated.
Block
Execution Time (milliseconds)
Resource
Transducer
LCD Block
Analog Input 1
Analog Input 2
PID 1
–
–
–
45
45
60
3144-GRAPH
Typical Accuracy
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Turn-on Time
Performance within specifications in less than 20 seconds after power is
applied, when damping value is set to 0 seconds.
Status
If self-diagnostics detect a sensor burnout or a transmitter failure, the status of
the measurement will be updated accordingly. Status may also send the PID
output to a safe value.
Power Supply
Powered over FOUNDATION fieldbus with standard fieldbus power supplies.
The transmitter operates between 9.0 and 32.0 Vdc, 11 mA maximum. The
power terminals are rated to 42.4 Vdc max.
Alarms
The AI function block allows the user to configure the alarms to HI-HI, HI, LO,
or LO-LO with a variety of priority levels and hysteresis settings.
Backup Link Active Scheduler (LAS)
The transmitter is classified as a device link master, which means it can
function as a Link Active Scheduler (LAS) if the current link master device fails
or is removed from the segment.
The host or other configuration tool is used to download the schedule for the
application to the link master device. In the absence of a primary link master,
the transmitter will claim the LAS and provide permanent control for the H1
segment.
FOUNDATION fieldbus Parameters
Schedule Entries
Links
Virtual Communications Relationships (VCR)
25(1)
16(1)
12(1)
(1) Minimum quantity.
Software Upgrade in the Field
Software for the 644 with FOUNDATION fieldbus will be easy to upgrade in the
field. Users will be able to take advantage of software enhancements by
loading new application software into the device memory.
A-5
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Accuracy
Table A-1. Rosemount 644 Input Options and Accuracy
Sensor
Options
Sensor
Reference
2-, 3-, 4-wire RTDs
Pt 100 ( = 0.00385)
IEC 751
Pt 200 ( = 0.00385)
IEC 751
Pt 500 ( = 0.00385)
IEC 751
Pt 1000 ( = 0.00385)
IEC 751
Pt 100 ( = 0.003916)
JIS 1604
Pt 200 ( = 0.003916)
JIS 1604
Ni 120
Edison Curve No. 7
Cu 10
Edison Copper Winding No. 15
Pt 50 ( = 0.00391)
GOST 6651-94
Pt 100 ( = 0.00391)
GOST 6651-94
Cu 50 ( = 0.00426)
GOST 6651-94
Cu 50 ( = 0.00428)
GOST 6651-94
Cu 100 ( = 0.00426)
GOST 6651-94
Cu 100 ( = 0.00428)
GOST 6651-94
Thermocouples(4)
Type B(5)
NIST Monograph 175, IEC 584
Type E
NIST Monograph 175, IEC 584
Type J
NIST Monograph 175, IEC 584
Type K(6)
NIST Monograph 175, IEC 584
Type N
NIST Monograph 175, IEC 584
Type R
NIST Monograph 175, IEC 584
Type S
NIST Monograph 175, IEC 584
Type T
NIST Monograph 175, IEC 584
DIN Type L
DIN 43710
DIN Type U
DIN 43710
Type W5Re/W26Re
ASTM E 988-96
GOST Type L
GOST R 8.585-2001
Other Input Types
Millivolt Input
2-, 3-, 4-wire Ohm Input
Input
Ranges
Recommended
Min. Span(1)
Digital
Accuracy(2)
D/A
Accuracy(3)
°C
–200 to 850
–200 to 850
–200 to 850
–200 to 300
–200 to 645
–200 to 645
–70 to 300
–50 to 250
–200 to 550
–200 to 550
–50 to 200
–185 to 200
–50 to 200
–185 to 200
°F
–328 to 1562
–328 to 1562
–328 to 1562
–328 to 572
–328 to 1193
–328 to 1193
–94 to 572
–58 to 482
–328 to 1022
–328 to 1022
–58 to 392
–301 to 392
–58 to 392
–301 to 392
°C
10
10
10
10
10
10
10
10
10
10
10
10
10
10
°F
18
18
18
18
18
18
18
18
18
18
18
18
18
18
°C
± 0.15
± 0.15
± 0.19
± 0.19
± 0.15
± 0.27
± 0.15
±1.40
± 0.30
± 0.15
±1.34
±1.34
±0.67
±0.67
°F
± 0.27
± 0.27
± 0.34
± 0.34
± 0.27
± 0.49
± 0.27
± 2.52
± 0.54
± 0.27
± 2.41
± 2.41
± 1.20
± 1.20
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
100 to 1820
–50 to 1000
–180 to 760
–180 to 1372
–200 to 1300
0 to 1768
0 to 1768
–200 to 400
–200 to 900
–200 to 900
0 to 2000
–200 to 800
212 to 3308
–58 to 1832
–292 to 1400
–292 to 2501
–328 to 2372
32 to 3214
32 to 3214
–328 to 752
–328 to 1652
–328 to 1112
32 to 3632
–328 to 1472
25
25
25
25
25
25
25
25
25
25
25
25
45
45
45
45
45
45
45
45
45
45
45
45
± 0.77
± 0.20
± 0.35
± 0.50
± 0.50
± 0.75
± 0.70
± 0.35
± 0.35
± 0.35
± 0.70
± 1.00
± 1.39
± 0.36
± 0.63
± 0.90
± 0.90
± 1.35
± 1.26
± 0.63
± 0.63
± 0.63
± 1.26
± 1.26
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
±0.03% of span
–10 to 100 mV
0 to 2000 ohms
±0.015 mV
±0.45 ohm
±0.03% of span
±0.03% of span
(1) No minimum or maximum span restrictions within the input ranges. Recommended minimum span will hold noise within accuracy specification with damping at
zero seconds.
(2) The published digital accuracy applies over the entire sensor input range. Digital output can be accessed by HART or FOUNDATION fieldbus Communications or
Rosemount control system.
(3) Total Analog accuracy is the sum of digital and D/A accuracies. This is not applicable for FOUNDATION fieldbus.
(4) Total digital accuracy for thermocouple measurement: sum of digital accuracy +0.5 °C. (cold junction accuracy).
(5) Digital accuracy for NIST Type B T/C is ±3.0 °C (±5.4 °F) from 100 to 300 °C (212 to 572 °F).
(6) Digital accuracy for NIST Type K T/C is ±0.70 °C (±1.26 °F) from –180 to –90 °C (–292 to –130 °F).
Accuracy Example
When using a Pt 100 ( = 0.00385) sensor input:
• Total accuracy = ±0.15 °C.
• No D/A accuracy effects apply
A-6
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Ambient Temperature Effect
Table A-2. Ambient Temperature Effect
Sensor Options
2-, 3-, 4-wire RTDs
Pt 100 ( = 0.00385)
Pt 200 ( = 0.00385)
Pt 500 ( = 0.00385)
Pt 1000 ( = 0.00385)
Pt 100 ( = 0.003916)
Pt 200 ( = 0.003916)
Ni 120
Cu 10
Pt 50 ( = 0.00391)
Pt 100 ( = 0.00391)
Cu 50 ( = 0.00426)
Cu 50 ( = 0.00428)
Cu 100 ( = 0.00426)
Cu 100 ( = 0.00428)
Thermocouples
Sensor Reference
IEC 751
IEC 751
IEC 751
IEC 751
JIS 1604
JIS 1604
Edison Curve No. 7
Edison Copper
Winding No. 15
GOST 6651-94
GOST 6651-94
GOST 6651-94
GOST 6651-94
GOST 6651-94
GOST 6651-94
Temperature Effects per 1.0 °C
(1.8 °F) Change in Ambient
Temperature(1)
Range
D/A Effect(2)
-200 to 850
-200 to 850
-200 to 850
-200 to 300
-200 to 645
-200 to 645
-70 to 300
-50 to 250
0.003 °C (0.0054 °F)
0.004 °C (0.0072 °F)
0.003 °C (0.0054 °F)
0.003 °C (0.0054 °F)
0.003 °C (0.0054 °F)
0.004 °C (0.0072 °F)
0.003 °C (0.0054 °F)
0.03 °C (0.054 °F)
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
-200 to 550
-200 to 550
-50 to 200
-185 to 200
-50 to 200
-185 to 200
0.004 °C (0.0072 °F)
0.003 °C (0.0054 °F)
0.008 °C (0.0144 °F)
0.008 °C (0.0144 °F)
0.004 °C (0.0072 °F)
0.004 °C (0.0072 °F)
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
Entire Sensor Input Range
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.014 °C
0.032 °C – (0.0025% of (T –
300))
0.054 °C – (0.011% of (T – 100))
0.005 °C + (0.0043% of T)
T 1000 °C
300 °C  T < 1000 °C
0.001% of span
0.001% of span
100 °C  T < 300 °C
All
0.001% of span
0.001% of span
0.0054 °C + (0.00029%of T)
0.0054 °C + (0.0025% of
absolute value T)
0.0061 °C + (0.0054% of T)
0.0061 °C + (0.0025% of
absolute value T)
0.0068 °C + (0.00036% of T)
T 0 °C
T < 0 °C
0.001% of span
0.001% of span
T  0 °C
T < 0 °C
0.001% of span
0.001% of span
All
0.001% of span
0.016 °C
0.023 °C – (0.0036% of T)
0.016 °C
0.023 °C – (0.0036% of T)
0.0064 °C
0.0064 °C +(0.0043% of
absolute value T)
0.0054 °C + (0.00029% of T)
0.0054 °C + (0.0025% of
absolute value T)
0.0064 °C
0.0064 °C + (0.0043% of
absolute value T)
0.016 °C
0.023 °C – (0.0036% of T)
0.007 °C
0.007 °C – (0.003% of absolute
value T)
T 200 °C
T < 200 °C
T 200 °C
T < 200 °C
T 0 °C
T < 0 °C
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
0.001% of span
T 0 °C
T < 0 °C
0.001% of span
0.001% of span
T 0 °C
T < 0 °C
0.001% of span
0.001% of span
T 200 °C
T < 200 °C
T 0 °C
T < 0 °C
0.001% of span
0.001% of span
0.001% of span
0.001% of span
Input Range
(°C)
Type B
NIST Monograph 175,
IEC 584
Type E
NIST Monograph 175,
IEC 584
-50 to 1000
Type J
NIST Monograph 175,
IEC 584
-180 to 760
Type K
NIST Monograph 175,
IEC 584
-180 to 1372
Type N
NIST Monograph 175,
IEC 584
-200 to 1300
Type R
NIST Monograph 175,
IEC 584
0 to 1768
Type S
NIST Monograph 175,
IEC 584
0 to 1768
Type T
NIST Monograph 175,
IEC 584
-200 to 400
DIN Type L
DIN 43710
-200 to 900
DIN Type U
DIN 43710
-200 to 900
ASTM E 988-96
0 to 2000
GOST R 8.585-2001
-200 to 800
Type W5Re/W26Re
GOST Type L
100 to 1820
A-7
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table A-2. Ambient Temperature Effect
Sensor Options
Other Input Types
Millivolt Input
2-, 3-, 4-wire Ohm
Sensor Reference
Input Range
(°C)
Temperature Effects per 1.0 °C
(1.8 °F) Change in Ambient
Temperature(1)
Range
D/A Effect(2)
-10 to 100 mV
0 to 2000 
0.0005 mV
0.0084 
Entire Sensor Input Range
Entire Sensor Input Range
0.001% of span
0.001% of span
(1) Change in ambient is with reference to the calibration temperature of the transmitter 68 °F (20 °C) from factory.
(2) Does not apply to FOUNDATION fieldbus.
Transmitters can be installed in locations where the ambient temperature is between –40 and 85 °C (–40 and 185
°F). In order to maintain excellent accuracy performance, each transmitter is individually characterized over this
ambient temperature range at the factory.
Temperature Effects Examples
When using a Pt 100 ( = 0.00385) sensor input at 30 °C span at 30 °C ambient temperature:
• Digital Temperature Effects: 0.003 °C x (30 - 20) = 0.03 °C
• D/A Effects: No D/A effects apply
• Worst Case Error: Digital + Digital Temperature Effects = 0.15 °C + 0.03 °C = 0.18 °C
• Total Probable Error:
0.15 2 + 0.03 2 = 0.153C
A-8
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
DIMENSIONAL DRAWINGS
644H (DIN A Head Mount)
Shown with Standard Compression Screw Terminals
Standard
Sensor
Terminals
60 (2.4)
WAGO Spring
Clamp Sensor
Terminals
33
(1.3)
Meter
Connector
24 (1.0)
Communication
Terminals
Shown with WAGO
Simulation Switch
®
Spring Clamp Terminals
60 (2.4)
33
(1.3)
Meter
Connector
24 (1.0)
Communication
Terminals
Simulation Switch
Power
Terminals
Power
Terminals
34 (1.33)
33 (1.30)
Threaded-Sensor Universal Head
(Option code J5 or J6)
Integral DIN Style Sensor
Connection Head
112 (4.41)
Label
96 (3.76)
104
(4.09)
95 (3.74)
LCD
Display
Meter Cover
Standard
Cover
78 (3.07)
128 (5.04)
with LCD
Display
75 103 (4.03) with LCD
(2.93) Display
316 SST “U”
Bolt Mounting,
2-inch Pipe
100
(3.93)
Note: A “U” Bolt is shipped with each universal head unless assembly
Note: The DIN Style Integral sensor connection head is only available
option X1, X2, or X3 is ordered. Since the head is integrally mounted to the through Volume 2 of the Rosemount Temperature Sensors and
sensor, it may not need to be used.
Accessories Product Data Sheet (document number 00810-0101-2654).
Dimensions are in millimeters (inches)
A-9
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
LCD Display
Head Mount Transmitter
Captive Mounting
Screws and Springs
Meter Spacer
644H
10 pin Connector
LCD Display
Mounting
G-Rail (asymmetric)
Mounting
Hardware
Top Hat Rail (symmetric)
Universal Clip for Mounting to a Wall or a Rail
(part number 03044-4103-0001)
Mounting
Hardware
G-Rail
Grooves
Transmitter
Screw Holes
for Mounting
to a Wall
Transmitter
Top Hat Rail
Grooves
Rail Clip
Rail Clip
644H Retrofit Kit
Existing Threaded Sensor
Connection Head
(former option code L1)
Kit includes replacement
bracket and screws.
Note: Kit (part number 00644-5301-0010) includes mounting
hardware and both types of rail kits.
A-10
Note: Kit (part number 00644-5321-0010) includes a new mounting
bracket and the hardware necessary to facilitate the installation.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Sanitary Housing Covers
Standard Cover
Housing
Standard Cover
O-Ring
76.2 (3.0)
33 (1.3)
79.8 (3.14)
27.9 (1.1)
25.4 (1.0)
44.5 (1.75)
24.4
(0.96)
70.0 (2.76)
LCD Display Cover
LCD Display Cover
Housing
O-Ring
47 (1.85)
33 (1.3)
61 (2.4)
76.2 (3.0)
74.4 (2.93)
27.9 (1.1)
25.4 (1.0)
44.5 (1.75)
70.0 (2.76)
Dimensions are in millimeters (inches)
A-11
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
ORDERING INFORMATION
Table A-3. Rosemount 644 Smart Temperature Transmitter Ordering Information
★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
● = Available
– = Not Available
Model
Product Description
644
Temperature Transmitter
Transmitter Type
Standard
H
DIN A Head Mount (suitable for mounting in the field with enclosure options below)
R
Rail Mount
Standard
★
★
Output
Standard
A
4–20 mA with digital signal based on HART protocol
F
FOUNDATION fieldbus digital signal (includes 2 AI function blocks and Backup Link
Active Scheduler)
W
Profibus PA digital signal
Head
Rail
●
●
●
–
Standard
★
★
●
–
★
Product Certifications
Hazardous Locations Certificates (consult factory for availability)
Standard
NA
E5(1)
I5(2)
K5(2)(1)
KC
I6(2)
K6(1)(3)
E1(1)
I1(2)
N1(1)
NC
ND(1)
E7(1)
I7(2)
N7(1)
NG
E2(1)
E4(1)(3)
E3(1)
I3
No approval
FM Explosion–Proof
FM Intrinsically Safe
FM Intrinsically Safe, Explosion-Proof Combination
FM/CSA Intrinsically Safe and Non-incendive Approval
CSA Intrinsically Safe
CSA Intrinsically Safe, Explosion-Proof Combination
ATEX Flameproof
ATEX Intrinsically Safe
ATEX Type n
ATEX Type n Component
ATEX Dust Ignition–Proof
IECEx Flameproof and Dust
IECEx Intrinsically Safe
IECEx Type n
IECEx Type n Component
INMETRO Flameproof
TIIS Explosion–Proof
China Flameproof
China Intrinsic Safety
A
F
W
A
●
●
●
●
●
●
●
–
●
●
●
●
●
●
●
–
–
–
–
●
●
●
●
–
●
●
●
–
●
●
●
–
●
●
●
●
●
●
●
–
●
●
●
●
●
●
●
–
●
●
●
–
●
●
●
●
●
●
●
–
●
●
●
●
●
●
●
–
●
●
●
●
●
●
●
–
●
●
●
–
A
F
W
A
–
●
–
–
Standard
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
Options
PlantWeb Control Functionality
Standard
A01
FOUNDATION fieldbus Advanced Control Function Block Suite
A-12
Standard
★
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table A-3. Rosemount 644 Smart Temperature Transmitter Ordering Information
★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
● = Available
– = Not Available
Assemble To Options
Standard
XA
Sensor Specified Separately and Assembled To Transmitter
●
●
●
Head
Enclosure Options
Standard
J5(4)(5)
Universal Head (junction box), aluminum alloy with 50.8 mm (2-in.) SST pipe bracket
(M20 entries)
J6(4)
Universal Head (junction box), aluminum alloy with 50.8 mm (2-in.) SST pipe bracket
(1/2–14 NPT entries)
J7(4)(5)
Universal Head (junction box), cast SST with 50.8 mm (2-in.) SST pipe bracket (M20
entries)
J8(4)
Universal Head (junction box), cast SST with 50.8 mm (2-in.) SST pipe bracket (1/2–
14 NPT entries)
Expanded
S1
Connection Head, Polished Stainless Steel (1/2–14 NPT entries)
S2
Connection Head, Polished Stainless Steel (1/2–14 NPSM entries)
S3
Connection Head, Polished Stainless Steel (M20 x 1.5 conduit and entries)
S4
Connection Head, Polished Stainless Steel (M20 x 1.5 conduit entries, M24 x 1.5
head entry)
Display
Standard
M5
LCD Display
Expanded
M6
LCD Display with Polycarbonate Meter Face
Software Configuration
Standard
C1
Custom Configuration of Date, Descriptor and Message (Requires CDS with order)
Alarm Level Configuration
Standard
A1
NAMUR alarm and saturation levels, high alarm
CN
NAMUR alarm and saturation levels, low alarm
C8
Low Alarm (Standard Rosemount Alarm and Saturation Values)
Line Filter
Standard
F6
60 Hz Line Voltage Filter
Sensor Trim
Standard
C2
Transmitter-Sensor Matching - Trim to Specific Rosemount RTD Calibration
Schedule (CVD constants)
5-Point Calibration Option
Standard
C4
5-point calibration. Use option code Q4 to generate a calibration certificate
Calibration Certificate
Standard
Q4
Calibration certificate. 3-Point calibration with certificate
External Ground
Standard
G1
External ground lug assembly (see “External Ground Screw Assembly” on
page A-15)
–
Standard
★
Rail
A
F
W
A
●
●
●
–
Standard
★
●
●
●
–
★
●
●
●
–
★
●
●
●
–
★
●
●
●
–
●
●
●
–
●
●
●
–
●
●
●
–
●
●
●
–
●
●
●
–
●
●
●
●
●
–
–
●
●
–
–
●
●
–
–
●
Standard
★
★
★
●
●
●
●
Standard
★
●
●
●
●
Standard
★
●
●
●
●
Standard
★
●
●
●
●
Standard
★
●
●
●
–
Standard
★
Standard
★
Standard
★
A-13
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table A-3. Rosemount 644 Smart Temperature Transmitter Ordering Information
★ The Standard offering represents the most common models and options. These options should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
● = Available
– = Not Available
Cable Gland Option
Standard
G2
Cable gland(6) (7.5 mm - 11.99 mm)
G7
Cable gland, M20x1.5, Ex e, Blue Polyamide (5 mm - 9 mm)
Cover Chain Option
Standard
G3
Cover chain
Terminal
Standard
G5
WAGO spring clamp terminals
Conduit Electrical Connector
Standard
GE(7)
M12, 4-pin, Male Connector (eurofast®)
GM(7)
A size Mini, 4-pin, Male Connector (minifast®)
External Label
Standard
EL
External label for ATEX Intrinsic Safety
Typical Rail Mount Model Number: 644 R A I5
Typical Head Mount Model Number: 644 H F I5
(1)
(2)
(3)
(4)
(5)
(6)
(7)
●
●
●
–
●
●
●
–
Standard
★
★
●
●
●
–
Standard
★
●
●
–
Standard
★
●
●
●
–
●
●
●
–
Standard
★
★
●
●
●
–
Standard
★
M5 J5 C1
Requires enclosure option J5, J6, J7, or J8.
When IS approval is ordered on a FOUNDATION fieldbus, both standard IS and FISCO IS approvals apply. The device label is marked appropriately.
Consult factory for availability.
Suitable for remote mount configuration.
When ordered with XA, 1/2-in. NPT enclosure will come equipped with an M20 adapter with the sensor installed as process ready.
Only available with Enclosure option code J5.
Available with Intrinsically Safe approvals only. For FM Intrinsically Safe or non-incendive approval (option code I5), install in accordance with Rosemount
drawing 03151-1009 to maintain NEMA 4X rating.
NOTE
For additional options (e.g. “K” codes), please contact your local Emerson Process Management representative.
Tagging
Hardware
• 13 characters total
• Tags are adhesive labels
• Permanently attached to transmitter
• Character height is 1/16-in (1.6 mm)
Software
• The transmitter can store up to 13 characters for FOUNDATION fieldbus and Profibus PA. If no
characters are specified, the first 8 characters of the hardware tag are the default.
Considerations
Special Mounting Considerations
See “Mounting” on page A-10 for the special hardware that is available to:
• Mount a 644H to a DIN rail. (see Table 1 on page A-15)
• Retrofit a new 644H to replace an existing 644H transmitter in an existing threaded sensor
connection head (see Table 1 on page A-15).
A-14
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
External Ground Screw Assembly
The external ground screw assembly can be ordered by specifying code G1 when an enclosure is
specified. However, some approvals include the ground screw assembly in the transmitter
shipment, hence it is not necessary to order code G1. The table below identifies which approval
options include the external ground screw assembly and which do not.
Approval Type
E5, I1, I2, I5, I6, I7, K5,
K6, NA, I4
E1, E2, E3, E4, E7, K7,
N1, N7, ND
External Ground Screw
Assembly Included?
No–Order option code G1
Yes
TABLE 1. Transmitter Accessories
Part Description
Part Number
Aluminum alloy Universal Head, standard cover—M20 entries
Aluminum alloy Universal Head, meter cover—M20 entries
Aluminum alloy Universal Head, standard cover—1/2-14 NPT entries
Aluminum alloy Universal Head, meter cover—1/2-14 NPT entries
LCD Display (includes meter and meter spacer assembly)
LCD Display kit (includes meter and meter spacer assembly, and meter cover)
Ground screw assembly kit
Kit, Hardware for mounting a 644H to a DIN rail (includes clips for symmetrical and asymmetrical rails)
Kit, Hardware for retrofitting a 644H in an existing threaded sensor connection head (former option code L1)
Kit, 316 U-Bolt for Universal Housing
Universal clip for rail or wall mount
24 Inches of symmetric (top hat) rail
24 Inches of asymmetric (G) Rail
Ground clamp for symmetric or asymmetric rail
End clamp for symmetric or asymmetric rail
Snap rings kit (used for assembly to a DIN sensor – quantity 12)
SST Universal Head, standard cover—M20 entries
SST Universal Head, meter cover—M20 entries
SST Universal Head, standard cover—1/2 -14 NPT entries
SST Universal Head, meter cover—1/2-14 NPT entries
Polished SST Connection Head, standard cover—1/2-14 NPT entries
Polished SST Connection Head, meter cover—1/2-14 NPT entries
Polished SST Connection Head, standard cover—1/2-14 NPSM entries
Polished SST Connection Head, meter cover—1/2-14 NPSM entries
Polished SST Connection Head, standard cover—M20 x 1.5 entries
Polished SST Connection Head, meter cover—M20 x 1.5 entries
Polished SST Connection Head, standard cover—M20 x 1.5 / M24 x 1.5 entries
Polished SST Connection Head, meter cover—M20 x 1.5 / M24 x 1.5 entries
Configuration
00644-4420-0002
00644-4420-0102
00644-4420-0001
00644-4420-0101
00644-4430-0002
00644-4430-0001
00644-4431-0001
00644-5301-0010
00644-5321-0010
00644-4423-0001
03044-4103-0001
03044-4200-0001
03044-4201-0001
03044-4202-0001
03044-4203-0001
00644-4432-0001
00644-4433-0002
00644-4433-0102
00644-4433-0001
00644-4433-0101
00079-0312-0011
00079-0312-0111
00079-0312-0022
00079-0312-0122
00079-0312-0033
00079-0312-0133
00079-0312-0034
00079-0312-0134
Transmitter Configuration
The transmitter is available with standard configuration setting for
FOUNDATION fieldbus (see “Custom configurations are to be specified when
ordering. This configuration must be the same for all sensors. The following
table lists the necessary requirements to specify a custom configuration.”).
The configuration settings and block configuration may be changed in the field
with DeltaV®, with AMS, or other FOUNDATION fieldbus host or
configuration tool.
A-15
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Standard FOUNDATION fieldbus Configuration
Unless otherwise specified, the transmitter will be shipped as follows for all
sensors:
Sensor Type: 4-wire Pt 100 ( = 0.00385) RTD
Damping: 5 seconds
Units of Measurement: °C
Line Voltage Filter: 50 Hz
Software Tag: See “Tagging” on page A-14
Function Blocks Tags:
• Resource Block: RB
• Transducer Block: TB
• LCD Block: LCD
• Analog Input Blocks: AI1, AI2
Alarm Range: 0
Alarm Limits of AI1 and AI2:
• HI-HI: 100 °C (212 °F)
• HI: 95 °C (203 °F)
• LO: 5 °C (41 °F)
• LO-LO: 0 °C (32 °F)
Local Display (when installed): Engineering Units of Temperature
Custom Configuration
Custom configurations are to be specified when ordering. This configuration
must be the same for all sensors. The following table lists the necessary
requirements to specify a custom configuration.
Option Code
C1: Factory
Configuration Data
(CDS required)
C2:Transmitter –
Sensor Matching
C4: Five Point
Calibration
F6: 60 Hz Line Filter
Requirements/
Specification
Date: day/month/year
Descriptor: 16 alphanumeric characters
Message: 32 alphanumeric character
Analog Output: Alarm and saturation levels
The transmitters are designed to accept Callendar-Van Dusen
constants from a calibrated RTD. Using these constants, the
transmitter generates a custom curve to match the
sensor-specific curve. Specify a Series 65, 65, or 78 RTD sensor
on the order with a special characterization curve (V or X8Q4
option). These constants will be programmed into the transmitter
with this option.
Will include 5-point calibration at 0, 25, 50, 75, and 100% analog
and digital output points.
Use with Calibration Certificate Q4.
Calibrated to a 60 Hz line voltage filter instead of 50 Hz filter
Standard Block Configuration
T1
AI 1300
Tb
AI 1400
Note:
T1 = Sensor Temperature
Tb = Terminal Temperature
Final Station
AI Blocks are scheduled for 1 second. AI Blocks are linked as shown above.
A-16
Reference Manual
00809-0100-4728, Rev AA
June 2011
Appendix B
Rosemount 644
Product Certifications
Approved Manufacturing Locations . . . . . . . . . . . . . . . . . page B-1
European Union Directive Information . . . . . . . . . . . . . . . page B-1
Hazardous Locations Certificates . . . . . . . . . . . . . . . . . . . page B-2
Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page B-7
APPROVED
MANUFACTURING
LOCATIONS
Emerson Process Management Rosemount Division. – Chanhassen,
Minnesota, USA
Rosemount Temperature GmbH – Germany
Emerson Process Management Asia Pacific – Singapore
EUROPEAN UNION
DIRECTIVE
INFORMATION
The EC declaration of conformity for all applicable European directives for this
product can be found on the Rosemount website at www.rosemount.com. A
hard copy may be obtained by contacting our local sales representative.
ATEX Directive (94/9/EC)
Rosemount Inc. complies with the ATEX Directive.
CE Electromagnetic Compatibility Compliance Testing
The 644 meets the criteria under IEC 61326:2006
www.rosemount.com
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
HAZARDOUS LOCATIONS CERTIFICATES
Rosemount 644 with
FOUNDATION fieldbus
North American
Certifications
Factory Mutual (FM) Approvals
I5
FM Intrinsically Safe and Non-incendive
Intrinsically Safe FISCO for use in Class I, II, III, Division 1, Groups A, B,
C, D, E, F, and G; when installed per control drawing 00644-2075.
Temperature Code: T4A (Tamb = – 50 °C to 60 °C).
Nonincendive for use in Class I, Division 2, Groups A, B, C, and D.
Temperature Code: T5 (Tamb = – 50 °C to 85 °C);
T6 (Tamb = – 50 °C to 70 ° C)
When installed per Rosemount control drawing 00644-2075
E5 FM Explosion Proof
Explosion Proof for Class I, Division 1, Groups B, C, and D.
Nonincendive for use in Class 1, Division 2, Groups A, B, C, and D.
Temperature Code: T5 (Tamb = – 50 °C to 85 °C)
When installed per Rosemount control drawing 00644-1049
Dust Ignition Proof for Class II/III, Division 1, Groups E, F, G.
Temperature Code: T5 (Ta = – 50 °C to 85 ° C)
When installed per Rosemount drawing 00644-1049.
(J5, J6 and J8 options only.)
Canadian Standards Association (CSA) Approvals
I6
CSA Intrinsically Safe
Intrinsically Safe and FISCO for Class I, Division 1, groups A, B, C, and
D when connected per Rosemount drawing 00644-2076.
Temperature code: T4 (Tamb = – 50 °C to 60 °C);
Suitable for Class I, Division 2, groups A, B, C, and D (must be installed
in a suitable enclosure)
K6 CSA Intrinsically Safe, Explosion-proof
Includes Intrinsically Safe “I6” and Explosion-Proof for Class I, Division 1,
groups B, C, and D.
Dust-Ignition Proof for Class II, Division 1, Groups E, F, and G.
Dust-Ignition Proof for Class III, Division 1
Seal not required.
CSA Enclosure Type 4X
Temperature Code: T4 (Tamb = – 50 °C to 60 °C);
T5 (Tamb = – 50 °C to 85 ° C)
NOTE:
(For J5 and J6 enclosure options only)
B-2
Reference Manual
00809-0100-4728, Rev AA
June 2011
European Certifications
Rosemount 644
E1 ATEX Flame-Proof
Certificate Number: KEMA99ATEX8715X
ATEX Marking:
II 2 G
1180
Ex d IIC T6 (–50 °C  Tamb  65 °C)
U = 32 Vdc
Special Conditions for Safe Use (X):
For information on the dimensions of the flameproof joints the
manufacturer shall be contacted.
I1
ATEX Intrinsic Safety
Certificate Number: Baseefa03ATEX0499X
ATEX Marking:
II 1 G
1180
Ex ia IIC T4 (-50 °C  Tamb  60 °C)
I.S. Loop/Power Terminals
Ui = 30 V
Ii = 300 mA
Pi = 1.3 W
Ci = 2.1 nF
Li = 0
FISCO Loop/Power Terminals
Ui = 17.5 V
Ii = 380 mA
Pi = 5.32 W
Ci = 2.1 nF
Li = 0
Sensor Terminals
Uo = 13.9 V
Io = 23 mA
Po = 79 mW
Ci = 7.7 nF
Li = 0
Special Conditions for Safe Use (X):
The apparatus must be installed in an enclosure which affords it a
degree of protection of at least IP20. Non-metallic enclosures must have
a surface resistance of less than 1G, light alloy or zirconium enclosures
must be protected from impact and friction when installed.
N1 ATEX Type n
Certificate Number: BAS00ATEX3145
ATEX Marking:
II 3 G
Ex nL IIC T5 (-40 °C  Tamb  70 °C)
Ui = 32 V
B-3
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
NC ATEX Type n Component
Certificate Number: BAS99ATEX3084U
ATEX Marking:
II 3 G
Ex nL IIC T5 (-40 °C Tamb 70 °C)
Max Input Voltage: Ui = 42.4 Vdc
NOTE:
The equipment must be installed in an enclosure meeting the requirements of
IP54 and the requirements of the impact tests described in EN50021.
ND ATEX Dust Ignition-Proof
Certificate Number: KEMA99ATEX8715X
ATEX Marking:
II 1 D
tD A20 T95°C (-50 °C Tamb 85 °C)
1180
IP66
Special Conditions for Safe Use (X):
For information on the dimensions of the flameproof joints the
manufacturer shall be contacted.
IECEx Certifications
E7 IECEx Flameproof and Dust
Certificate Number: IECEx KEM 09.0015X
Ex d IIC T6 (Flameproof)
Ex tD A20 IP 66 T 95 °C (Dust)
Vmax = 42.4 V
Special Conditions for Safe Use (X):
For information on the dimensions of the flameproof joints the
manufacturer shall be contacted.
Table B-1. Electrical Data
Transmitter
Vmax = 32 Vdc
Imax = 12.0 mA
I7
Sensor
Umax = 5 Vdc
Imax = 2.0 mA
IECEx Intrinsic Safety
Certificate Number: IECEx BAS 07.0053X
Ex ia IIC T4/T5/T6
Table B-2. Temperature Classification
Pi (W)
Temperature Class
1.3
T4
5.32 (FISCO Group IIC)
T4
Tamb
-50 °C to 60 °C
-60 °C to 80 °C
Special Conditions for Safe Use (X):
The apparatus must be installed in an enclosure which affords it a degree
of protection of at least IP20.
Non-metallic enclosures must have a surface resistance of less than 1
G; light alloy or zirconium enclosures must be protected from impact
and friction when installed.
B-4
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
Table B-3. Entity Parameters
Transmitter (I.S.) Transmitter (FISCO)
Sensor
Ui = 30 Vdc
Ii = 300 mA
Pi = 1.3 W
Ci = 2.1 nF
Li = 0 mH
Uo = 13.9 Vdc
Io = 23 mA
Po = 79 mW
Ci = 7.7 nF
Li = 0 mH
Ui = 17.5 Vdc
Ii = 380 mA
Pi = 5.32 W
Ci = 2.1 nF
Li = 0 mH
N7 IECEx Type n
Certificate Number: IECEx BAS 07.0055
Ex nA nL IIC T5 (-40 °C  Tamb  70 °C)
Table B-4. Electrical Data
Transmitter
Ui = 32 V
Sensor
RTD
Ui = 5 V
Thermocouple
Ui = 0
NG IECEx Type n Component
Certificate Number: IECEx BAS 07.0054U
Ex nA nL IIC T5 (-40 °C  Tamb  75 °C)
Schedule of Limitations:
The component must be housed in a suitably certified enclosure that
provides a degree of protection of at least IP54.
B-5
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
Japanese Certifications
Japanese Industrial Standard (JIS) Approvals
I4
JIS Intrinsic Safety
E4 JIS Explosion Proof
Table B-5. Certificate and Description
Certificate Description
C15744 644H with meter
and no sensor
C15745 644H without
meter and no
sensor
C15749 644H without
meter and with
RTD
C15750 644H without
meter and with
thermocouple
C15751 644H with meter
and thermocouple
C15752 644H with meter
and RTD
C15910 644H without
meter and with
thermocouple
C15911 644H with meter
and thermocouple
C15912 644H without
meter and with
RTD
C15913 644H with meter
and RTD
Approval
Group
Temp
Code
Ex d II C
T6
Ex d II C
T6
Ex d II B
T4
Ex d II B
T4
Ex d II B
T4
Ex d II B
T4
Ex d II B +
H2
T4
Ex d II B +
H2
Ex d II B +
H2
T4
Ex d II B +
H2
T4
T4
Combination Approvals
K5 Combination of I5 and E5.
Russian GOST
Certifications
PPC BA-13006:
Kazakhstan GOST
Pattern approval Certificate for Measuring Instruments
0 Ex ia IIC T4/T5/T6
See Certificate
Ukraine GOST
Pattern Approval for Measuring Instruments
See Certificate
B-6
Reference Manual
00809-0100-4728, Rev AA
June 2011
INSTALLATION
DRAWINGS
Rosemount 644
The installation guidelines presented by the drawings must be followed in
order to maintain certified ratings for installed transmitters.
Rosemount Drawing 00644-1064, 1 Sheet,
Canadian Standards Association Intrinsic Safety Installation Drawing
Rosemount Drawing 00644-1059, 1 Sheet;
Canadian Standards Association Explosion-Proof Installation Drawing
Rosemount Drawing 00644-2076, 3 Sheets;
Canadian Standards Association 644 Fieldbus Intrinsic Safety/FISCO
Installation Drawing
Rosemount Drawing 00644-0009, 2 Sheet
Factory Mutual Intrinsic Safety Installation Drawing
Rosemount Drawing 00644-1049, 1 Sheet;
Factory Mutual Explosion-proof Installation Drawing
Rosemount Drawing 00644-2075, 3 Sheets;
Factory Mutual 644 Fieldbus Intrinsic Safety/FISCO Installation Drawing
IMPORTANT
Once a device labeled with multiple approval types is installed, it should not
be reinstalled using any of the other labeled approval types. To ensure this,
the approval label should be permanently marked to distinguish the used from
the unused approval type(s).
B-7
Reference Manual
Rosemount 644
Figure B-1. CSA Intrinsic Safety Installation Drawing 00644-1064, Rev. AB
B-8
00809-0100-4728, Rev AA
June 2011
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
Figure B-2. CSA Explosion-Proof Installation Drawing 00644-1059, Rev. AH
B-9
Reference Manual
Rosemount 644
00809-0100-4728, Rev AA
June 2011
Figure B-3. CSA 644 Fieldbus Intrinsic Safety, FISCO Installation Drawing 00644-2076, Rev. AC Sheet 1 of 3
B-10
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
Sheet 2 of 3
B-11
Reference Manual
Rosemount 644
Sheet 3 of 3
B-12
00809-0100-4728, Rev AA
June 2011
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
Figure B-4. FM Explosion-Proof Installation Drawing 00644-1049, Rev. AE Sheet 1of 2
B-13
Reference Manual
Rosemount 644
Sheet 2 of 2
B-14
00809-0100-4728, Rev AA
June 2011
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
Figure B-5. FM Explosion-Proof Installation Drawing 00644-1049, Rev. AE
B-15
Reference Manual
Rosemount 644
00809-0100-4728, Rev AA
June 2011
Figure B-6. FM 644 Fieldbus Intrinsic Safety and FISCO Installation Drawing 00644-2075, Rev. AG Sheet 1 of 3
B-16
Reference Manual
00809-0100-4728, Rev AA
June 2011
Rosemount 644
Sheet 2 of 3
B-17
Reference Manual
Rosemount 644
Sheet 3 of 3
B-18
00809-0100-4728, Rev AA
June 2011
Reference Manual
00809-0400-4728, Rev AA
June 2011
Appendix C
Rosemount 644
FOUNDATION fieldbus Block
Information
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-1
Sensor Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . page C-5
Analog Input (AI) Function Block . . . . . . . . . . . . . . . . . . . page C-8
LCD Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-11
PID Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-12
BASIC SETUP
RESOURCE BLOCK
This section contains information on the 644 Resource Block. Descriptions of
all Resource Block Parameters, errors, and diagnostics are included. Also the
modes, alarm detection, status handling, and troubleshooting are discussed.
Definition
The resource block defines the physical resources of the device. The
resource block also handles functionality that is common across multiple
blocks. The block has no linkable inputs or outputs.
www.rosemount.com
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Parameters and
Descriptions
The table below lists all of the configurable parameters of the Resource Block,
including the descriptions and index numbers for each.
Table C-1. Resource Block Parameters and Descriptions
C-2
Parameter
Index
Number
ACK_OPTION
38
ADVISE_ACTIVE
ADVISE_ALM
82
83
ADVISE_ENABLE
80
ADVISE_MASK
81
ADVISE_PRI
ALARM_SUM
79
37
ALERT_KEY
BLOCK_ALM
04
36
BLOCK_ERR
06
CLR_FSTATE
30
CONFIRM_TIME
33
CYCLE_SEL
20
CYCLE_TYPE
DD_RESOURCE
19
09
DD_REV
13
DEFINE_WRITE_LOCK
60
DETAILED_STATUS
DEV_REV
55
12
DEV_STRING
43
DEV_TYPE
11
DIAG_OPTIONS
DISTRIBUTOR
DOWNLOAD_MODE
46
42
67
Description
Selection of whether alarms associated with the function block will be
automatically acknowledged.
Enumerated list of advisory conditions within a device.
Alarm indicating advisory alarms. These conditions do not have a direct impact on the
process or device integrity.
Enabled ADVISE_ALM alarm conditions. Corresponds bit for bit to the ADVISE_ACTIVE.
A bit on means that the corresponding alarm condition is enabled and will be detected. A
bit off means the corresponding alarm condition is disabled and will not be detected.
Mask of ADVISE_ALM. Corresponds bit of bit to ADVISE_ACTIVE. A bit on means that
the condition is masked out from alarming.
Designates the alarming priority of the ADVISE_ALM
The current alert status, unacknowledged states, unreported states, and disabled states
of the alarms associated with the function block.
The identification number of the plant unit.
The block alarm is used for all configuration, hardware, connection failure or system
problems in the block. The cause of the alert is entered in the subcode field. The first alert
to become active will set the Active status in the Status parameter. As soon as the
Unreported status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active status, if the subcode has changed.
This parameter reflects the error status associated with the hardware or software
components associated with a block. It is a bit string, so that multiple errors may be
shown.
Writing a Clear to this parameter will clear the device FAIL_SAFE if the field condition has
cleared.
The time the resource will wait for confirmation of receipt of a report before trying again.
Retry will not happen when CONFIRM_TIME=0.
Used to select the block execution method for this resource. The 644 supports the
following:
Scheduled: Blocks are only executed based on the function block schedule.
Block Execution: A block may be executed by linking to another blocks completion.
Identifies the block execution methods available for this resource.
String identifying the tag of the resource which contains the Device Description for
this resource.
Revision of the DD associated with the resource - used by an interface device to locate
the DD file for the resource.
Allows the operator to select how WRITE_LOCK behaves. The initial value is “lock
everything”. If the value is set to “lock only physical device” then the resource and
transducer blocks of the device will be locked but changes to function blocks will be
allowed.
Indicateds the state of the transmitter. See Resource Block detailed status codes.
Manufacturer revision number associated with the resource - used by an interface device
to locate the DD file for the resource.
This is used to load new licensing into the device. The value can be written but will always
read back with a value of 0.
Manufacturer’s model number associated with the resource - used by interface devices to
locate the DD file for the resource.
Indicates which diagnostics licensing options are enabled.
Reserved for use as distributor ID. No Foundation enumerations defined at this time.
Gives access to the boot block code for over-the-wire downloads.
0 = Uninitialized
1 = Run mode
2 = Download mode
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table C-1. Resource Block Parameters and Descriptions
Parameter
Index
Number
FAULT_STATE
28
FAILED_ACTIVE
FAILED_ALM
FAILED_ENABLE
72
73
70
FAILED_MASK
71
FAILED_PRI
FB_OPTIONS
FEATURES
69
45
17
FEATURE_SEL
FINAL_ASSY_NUM
FREE_SPACE
FREE_TIME
GRANT_DENY
18
54
24
25
14
HARD_TYPES
HARDWARE_REV
ITK_VER
15
52
41
LIM_NOTIFY
MAINT_ACTIVE
MAINT_ALM
32
77
78
MAINT_ENABLE
75
MAINT_MASK
76
MAINT_PRI
MANUFAC_ID
74
10
MAX_NOTIFY
MEMORY_SIZE
31
22
MESSAGE_DATE
MESSAGE_TEXT
57
58
MIN_CYCLE_T
MISC_OPTIONS
MODE_BLK
21
47
05
NV_CYCLE_T
23
OUTPUT_BOARD_SN
53
Description
Condition set by loss of communication to an output block, fault promoted to an output
block or physical contact. When FAIL_SAFE condition is set, then output function blocks
will perform their FAIL_SAFE actions.
Enumerated list of failure conditions within a device.
Alarm indicating a failure within a device which makes the device non-operational.
Enabled FAILED_ALM alarm conditions. Corresponds bit for bit to the FAILED_ACTIVE.
A bit on means that the corresponding alarm condition is enabled and will be detected. A
bit off means the corresponding alarm condition is disabled and will not be detected.
Mask of FAILED_ALM. Corresponds bit of bit to FAILED_ACTIVE. A bit on means that the
condition is masked out from alarming.
Designates the alarming priority of the FAILED_ALM.
Indicates which function block licensing options are enabled.
Used to show supported resource block options. See Error! Reference source not found.
The supported features are: SOFT_WRITE_LOCK_SUPPORT,
HARD_WRITE_LOCK_SUPPORT, REPORTS, and UNICODE
Used to select resource block options.
The same final assembly number placed on the neck label.
Percent of memory available for further configuration. Zero in a preconfigured device.
Percent of the block processing time that is free to process additional blocks.
Options for controlling access of host computers and local control panels to operating,
tuning, and alarm parameters of the block. Not used by device.
The types of hardware available as channel numbers.
Hardware revision of the hardware that has the resource block in it.
Major revision number of the inter operability test case used in certifying this device as
interoperable. The format and range are controlled by the Fieldbus Foundation.
Maximum number of unconfirmed alert notify messages allowed.
Enumerated list of maintenance conditions within a device.
Alarm indicating the device needs maintenance soon. If the condition is ignored, the
device will eventually fail.
Enabled MAINT_ALM alarm conditions. Corresponds bit for bit to the MAINT_ACTIVE. A
bit on means that the corresponding alarm condition is enabled and will be detected. A bit
off means the corresponding alarm condition is disabled and will not be detected.
Mask of MAINT_ALM. Corresponds bit of bit to MAINT_ACTIVE. A bit on means that the
condition is masked out from alarming.
Designates the alarming priority of the MAINT_ALM
Manufacturer identification number – used by an interface device to locate the DD file for
the resource.
Maximum number of unconfirmed notify messages possible.
Available configuration memory in the empty resource. To be checked before
attempting a download.
Date associated with the MESSAGE_TEXT parameter.
Used to indicate changes made by the user to the device's installation, configuration,
or calibration.
Time duration of the shortest cycle interval of which the resource is capable.
Indicates which miscellaneous licensing options are enabled.
The actual, target, permitted, and normal modes of the block:
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for actual
Minimum time interval specified by the manufacturer for writing copies of NV parameters
to non-volatile memory. Zero means it will never be automatically copied. At the end of
NV_CYCLE_T, only those parameters which have changed need to be updated in
NVRAM.
Output board serial number.
C-3
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table C-1. Resource Block Parameters and Descriptions
C-4
Parameter
Index
Number
RB_SFTWR_REV_ALL
51
RB_SFTWR_REV_BUILD
RB_SFTWR_REV_MAJOR
RB_SFTWR_REV_MINOR
RECOMMENDED_ACTION
RESTART
50
48
49
68
16
RS_STATE
SAVE_CONFIG_BLOCKS
07
62
SAVE_CONFIG_NOW
SECURITY_IO
SELF_TEST
SET_FSTATE
SHED_RCAS
61
65
59
29
26
SHED_ROUT
27
SIMULATE_IO
SIMULATE_STATE
64
66
ST_REV
START_WITH_DEFAULTS
01
63
STRATEGY
SUMMARY_STATUS
TAG_DESC
TEST_RW
UPDATE_EVT
WRITE_ALM
WRITE_LOCK
03
56
02
08
35
40
34
WRITE_PRI
XD_OPTIONS
39
44
Description
The string will contains the following fields:
Major rev: 1-3 characters, decimal number 0-255
Minor rev: 1-3 characters, decimal number 0-255
Build rev: 1-5 characters, decimal number 0-255
Time of build: 8 characters, xx:xx:xx, military time
Day of week of build: 3 characters, Sun, Mon,...
Month of build: 3 characters, Jan, Feb.
Day of month of build: 1-2 characters, decimal number 1-31
Year of build: 4 characters, decimal
Builder: 7 characters, login name of builder
Build of software that the resource block was created with.
Major revision of software that the resource block was created with.
Minor revision of software that the resource block was created with.
Enumerated list of recommended actions displayed with a device alert.
Allows a manual restart to be initiated. Several degrees of restart are possible. They are
the following:
1 Run – nominal state when not restarting
2 Restart resource – not used
3 Restart with defaults – set parameters to default values. See
START_WITH_DEFAULTS below for which parameters are set.
4 Restart processor – does a warm start of CPU.
State of the function block application state machine.
Number of EEPROM blocks that have been modified since last burn. This value will count
down to zero when the configuration is saved.
Allows the user to optionally save all non-volatile information immediately.
Status of security switch.
Instructs resource block to perform self-test. Tests are device specific.
Allows the FAIL_SAFE condition to be manually initiated by selecting Set.
Time duration at which to give up on computer writes to function block RCas locations.
Shed from RCas shall never happen when SHED_ROUT = 0
Time duration at which to give up on computer writes to function block ROut locations.
Shed from ROut shall never happen when SHED_ROUT = 0
Status of simulate switch.
The state of the simulate switch:
0 = Uninitialized
1 = Switch off, simulation not allowed
2 = Switch on, simulation not allowed (need to cycle jumper/switch)
3 = Switch on, simulation allowed
The revision level of the static data associated with the function block.
0 = Uninitialized
1 = do not power-up with NV defaults
2 = power-up with default node address
3 = power-up with default pd_tag and node address
4 = power-up with default data for the entire communications stack (no application data)
The strategy field can be used to identify grouping of blocks.
An enumerated value of repair analysis.
The user description of the intended application of the block.
Read/write test parameter - used only for conformance testing.
This alert is generated by any change to the static data.
This alert is generated if the write lock parameter is cleared.
If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block inputs
will continue to be updated.
Priority of the alarm generated by clearing the write lock.
Indicates which transducer block licensing options are enabled.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
SENSOR TRANSDUCER
BLOCK
The transducer block contains the actual measurement data, including a
pressure and temperature reading. The transducer block includes information
about sensor type, engineering units, linearization, reranging, temperature
compensation, and diagnostics.
Parameters and
Descriptions
Table C-2. Sensor Transducer Block Parameters and Descriptions
Parameter
Index
Number Description
ALERT_KEY
04
The identification number of the plant unit.
BLOCK_ALM
08
BLOCK_ERR
06
CAL_MIN_SPAN
18
CAL_POINT_HI
CAL_POINT_LO
CAL_UNIT
16
17
19
COLLECTION_DIRECTORY
12
ASIC_REJECTION
42
FACTORY_CAL_RECALL
USER_2W_OFFSET
32
36
INTER_DETECT_THRESH
35
MODE_BLK
05
CALIBRATOR_MODE
PRIMARY_VALUE
33
14
The block alarm is used for all configuration,
hardware, connection failure or system
problems in the block. The cause of the alert is
entered in the subcode field. The first alert to
become active will set the Active status in the
Status parameter. As soon as the Unreported
status is cleared by the alert reporting task,
another block alert may be reported without
clearing the Active status, if the subcode has
changed.
This parameter reflects the error status
associated with the hardware or software
components associated with a block. It is a bit
string, so that multiple errors may be shown.
The minimum calibration span value allowed.
This minimum span information is necessary to
ensure when calibration is done, the two
calibrated points are not too close together.
The highest calibrated value.
The lowest calibrated value.
The device description engineering units code
index for the calibration values.
A directory that specifies the number, starting
indices, and DD Item ID's of the data collections
in each transducer.
Indicates the type of material that the drain
vents on the flange are made of. See Drain Vent
Material Codes.
Recalls the sensor calibration set at the factory.
Indicates the type of material that the flange is
made of. See Flange Material Codes.
Indicates the type of flange that is attached to
the device. See Flange Type Codes.
The actual, target, permitted, and normal modes
of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take
on
Normal: Most common mode for target
Indicates the type of sensor module.
The measured value and status available to the
function block.
Notes on how changing this parameter
effects transmitter operation.
No effect on operation of transmitter but may
affect the way alerts are sorted on the host end.
No effect.
No effect.
No effect.
Assigns a value to the calibration high point.
Assigns a value to the calibration low point.
Device must be calibrated using the appropriate
engineering units.
No effect.
Assigns the device mode.
No effect.
C-5
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table C-2. Sensor Transducer Block Parameters and Descriptions
Parameter
Index
Number Description
PRIMARY_VALUE_RANGE
15
PRIMARY_VALUE_TYPE
13
SENSR_DETAILED_STATUS
37
CAL_VAN_DUSEN_COEFF
38
SECONDARY_VALUE_RANG
SECONDARY_VALUE_UNIT
30
29
SENSOR_CAL_DATE
25
SENSOR_CAL_LOC
24
SENSOR_CAL_METHOD
OPEN_SNSR_HOLDOFF
SENSOR_CAL_WHO
23
34
26
SECONDARY_VALUE
SENSOR_CONNECTION
28
27
SENSOR_RANGE
21
SENSOR_SN
SENSOR_TYPE
22
20
ST_REV
01
C-6
The high and low range limit values, the
engineering unit code, and the number of digits
to the right of the decimal point to be used to
display the final value.
Valid engineering units are the following:
1130 = Pa
1133 = kPa
1137 = bar
1138 = mbar
1139 = torr
1140 = atm
1141 = psi
1144 = g/cm2
1145 = kg/cm2
1148 = inH2O @ 68 °F
1151 = mmH2O @ 68 °F
1154 = ftH2O @ 68 °F
1156 = inHg @ 0 °C
1158 = mmHg @ 0 °C
Type of measurement represented by the
primary value.
107 = Differential pressure
108 = Gage pressure
109 = Absolute pressure
Indicates the number of remote seals that are
attached to the device. See Remote Seal
Number Codes.
Indicates the type of remote seals that are
attached to the device. See Remote Seal Type
Codes.
The secondary value, related to the sensor.
Engineering units to be used with
SECONDARY_VALUE.
1001 °C
1002 °F
The last date on which the calibration was
performed.This is intended to reflect the
calibration of that part of the sensor that is
usually wetted by the process.
The last location of the sensor calibration. This
describes the physical location at which the
calibration was performed.
The method of last sensor calibration.
The type of last sensor calibration.
The name of the person responsible for the last
sensor calibration.
Defines the type of fill fluid used in the sensor.
Defines the construction material of the isolating
diaphragms.
The high and low range limit values, the
engineering units code, and the number of digits
to the right of the decimal point for the sensor.
Serial number of the sensor.
Type of sensor connected with the transducer
block.
The revision level of the static data associated
with the function block.
Notes on how changing this parameter
effects transmitter operation.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table C-2. Sensor Transducer Block Parameters and Descriptions
Parameter
Index
Number Description
STRATEGY
03
TAG_DESC
02
SESNOR_1_DAMPING
31
TRANSDUCER_DIRECTORY
09
TRANSDUCER_TYPE
UPDATE_EVT
10
07
XD_ERROR
11
The strategy field can be used to identify
grouping of blocks.
The user description of the intended application
of the block.
Indicates the state of the transmitter. The
parameter contains specific codes relating to
the transducer block and the pressure sensor
specifically.
Directory that specifies the number and starting
indices of the transducers in the transducer
block.
Identifies the transducer that follows.
This alert is generated by any change to the
static data.
Provides additional error codes related to
transducer blocks.
Notes on how changing this parameter
effects transmitter operation.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
No effect.
C-7
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
ANALOG INPUT (AI)
FUNCTION BLOCK
The Analog Input (AI) function block processes field device measurements
and makes them available to other function blocks. The output value from the
AI block is in engineering units and contains a status indicating the quality of
the measurement. The measuring device may have several measurements or
derived values available in different channels. Use the channel number to
define the variable that the AI block processes.
The AI block supports alarming, signal scaling, signal filtering, signal status
calculation, mode control, and simulation. In Automatic mode, the block’s
output parameter (OUT) reflects the process variable (PV) value and status.
In Manual mode, OUT may be set manually. The Manual mode is reflected on
the output status. A discrete output (OUT_D) is provided to indicate whether a
selected alarm condition is active. Alarm detection is based on the OUT value
and user specified alarm limits. Figure C-1 illustrates the internal components
of the AI function block, and Table C-3 lists the AI block parameters and their
units of measure, descriptions, and index numbers.
Figure C-1. AI Function Block
Analog
Measurement
ALARM_TYPE
Access
Analog
Meas.
HI_HI_LIM
HI_LIM
LO_LO_LIM
LO_LIM
CHANNEL
Alarm
Detection
OUT_D
ALARM_HYS
LOW_CUT
Cutoff
PV
Filter
Convert
Status
Calc.
PV_FTIME
SIMULATE
L_TYPE
MODE
FIELD_VAL
IO_OPTS
STATUS_OPTS
OUT_SCALE
XD_SCALE
NOTES:
OUT = block output value and status.
OUT_D = discrete output that signals a selected alarm condition.
C-8
OUT
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
AI Parameter Table
Table C-3. Definitions of Analog Input Function Block System Parameters
Parameter
Index
No.
ACK_OPTION
23
ALARM_HYS
Available Values
Units
Default
Read/Write
Description
None
0 all Disabled
Read and Write
Used to set auto acknowledgment of alarms.
24
0 = Auto Ack Disabled
1 = Auto Ack Enabled
0 – 50
Percent
0.5
Read and Write
ALM_SEL
38
HI_HI, HI, LO, LO_LO
None
Non selected
Read and Write
ALARM_SUM
22
Enable/Disable
None
Enable
Read and Write
ALERT_KEY
04
1 – 255
None
0
Read and Write
BLOCK_ALM
21
Not applicable
None
Not applicable
Read only
BLOCK_ERR
06
Not applicable
None
Not applicable
Read only
CAP_STDDEV
40
>=0
Seconds
0
Read and Write
CHANNEL
15
1 = Pressure
2 = Housing
temperature
None
AI(1): Channel = 1
AI2: Channel = 2
Read and Write
FIELD_VAL
19
0 – 100
Percent
Not applicable
Read only
GRANT_DENY
12
None
Not applicable
Read and Write
HI_ALM
34
Program
Tune
Alarm
Local
Not applicable
None
Not applicable
Read only
HI_HI_ALM
33
Not applicable
None
Not applicable
Read only
HI_HI_LIM
26
Out_Scale(2)
Out_Scale(2)
Not applicable
Read and Write
HI_HI_PRI
HI_LIM
25
28
0 – 15
Out_Scale(2)
None
Out_Scale(2)
1
Not applicable
Read and Write
Read and Write
HI_PRI
IO_OPTS
27
13
0 – 15
Low Cutoff
Enable/Disable
None
None
1
Disable
Read and Write
Read and Write
L_TYPE
16
Direct
Indirect
Indirect Square Root
None
Direct
Read and Write
The amount the alarm value must return within
the alarm limit before the associated active alarm
condition clears.
Used to select the process alarm conditions that
will cause the OUT_D parameter to be set.
The summary alarm is used for all process
alarms in the block. The cause of the alert is
entered in the subcode field. The first alert to
become active will set the Active status in the
Status parameter. As soon as the Unreported
status is cleared by the alert reporting task,
another block alert may be reported without
clearing the Active status, if the subcode
has changed.
The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
The block alarm is used for all configuration,
hardware, connection failure or system problems
in the block. The cause of the alert is entered in
the subcode field. The first alert to become active
will set the Active status in the Status parameter.
As soon as the Unreported status is cleared by
the alert reporting task, another block alert may
be reported without clearing the Active status, if
the subcode has changed.
This parameter reflects the error status
associated with the hardware or software
components associated with a block. It is a bit
string, so that multiple errors may be shown.
The time over which the VAR_INDEX is
evaluated.
The CHANNEL value is used to select the
measurement value. Refer to the appropriate
device manual for information about the specific
channels available in each device.
You must configure the CHANNEL parameter
before you can configure the XD_SCALE
parameter.
The value and status from the transducer block
or from the simulated input when simulation is
enabled.
Normally the operator has permission to write to
parameter values, but Program or Local remove
that permission and give it to the host controller
or a local control panel.
The HI alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state
of the alarm.
The HI HI alarm data, which includes a value of
the alarm, a timestamp of occurrence and the
state of the alarm.
The setting for the alarm limit used to detect the
HI HI alarm condition.
The priority of the HI HI alarm.
The setting for the alarm limit used to detect the
HI alarm condition.
The priority of the HI alarm.
Allows the selection of input/output options used
to alter the PV. Low cutoff enabled is the only
selectable option.
Linearization type. Determines whether the field
value is used directly (Direct), is converted
linearly (Indirect), or is converted with the square
root (Indirect Square Root).
C-9
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
Table C-3. Definitions of Analog Input Function Block System Parameters
Parameter
Index
No.
Available Values
Units
Default
Read/Write
Description
LO_ALM
35
Not applicable
None
Not applicable
Read only
LO_LIM
30
Out_Scale(2)
Out_Scale(2)
Not applicable
Read and Write
LO_LO_ALM
36
Not applicable
None
Not applicable
Read only
LO_LO_LIM
32
Out_Scale(2)
Out_Scale(2)
Not applicable
Read and Write
LO_LO_PRI
LO_PRI
LOW_CUT
31
29
17
0 – 15
0 – 15
>=0
None
None
Out_Scale(2)
1
1
0
Read and Write
Read and Write
Read and Write
MODE_BLK
05
Auto
Manual
Out of Service
None
Not applicable
Read and Write
OUT
OUT_D
08
37
Out_Scale(2) ± 10%
Discrete_State 1 – 16
Out_Scale(2)
None
Not applicable
Disabled
Read and Write
Read and Write
OUT_SCALE
11
Any output range
All available
none
Read and Write
PV
PV_FTIME
07
18
Not applicable
>=0
Out_Scale(2)
Seconds
Not applicable
0
Read only
Read and Write
SIMULATE
09
Not applicable
None
Disable
Read and Write
ST_REV
01
Not applicable
None
0
Read only
The LO alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state
of the alarm.
The setting for the alarm limit used to detect the
LO alarm condition.
The LO LO alarm data, which includes a value of
the alarm, a timestamp of occurrence and the
state of the alarm.
The setting for the alarm limit used to detect the
LO LO alarm condition.
The priority of the LO LO alarm.
The priority of the LO alarm.
If percentage value of transducer input fails
below this, PV = 0.
The actual, target, permitted, and normal modes
of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take
on
Normal: Most common mode for target
The block output value and status.
Discrete output to indicate a selected alarm
condition.
The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point associated with OUT.
The process variable used in block execution.
The time constant of the first-order PV filter. It is
the time required for a 63% change in the IN
value.
A group of data that contains the current
transducer value and status, the simulated
transducer value and status, and the
enable/disable bit.
The revision level of the static data associated
with the function block. The revision value will be
incremented each time a static parameter value
in the block is changed.
STATUS_OPTS
14
0
Read and Write
STDDEV
39
Propagate fault forward
Uncertain if Limited
Bad if Limited
Uncertain if Man Mode
0 – 100
Percent
0
Read and Write
STRATEGY
03
0 – 65535
None
0
Read and Write
TAG_DESC
02
32 text characters
None
none
Read and Write
UPDATE_EVT
20
Not applicable
None
Not applicable
Read only
XD_SCALE
10
Any sensor range
inH2O (68 °F)
inHg (0 °C)
ftH2O (68 °F)
mmH2O (68 °F)
mmHg (0 °C)
psi
bar
mbar
g/cm2
kg/cm2
Pa
kPa
torr
atm
deg C
deg F
(1)
AI1 : Customer
specification
or
inH2O (68 °F) for
DP/GP rng 1, 2, 3)
or
psi for DP/GP rng
4, 5 AP/644 all rng
AI2 deg C
(1) The host system may write over default values pre-configured by Rosemount Inc.
(2) Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale
C-10
The average absolute error between the PV and
its previous mean value over that evaluation time
defined by VAR_SCAN.
The strategy field can be used to identify
grouping of blocks. This data is not checked or
processed by the block.
The user description of the intended application
of the block.
This alert is generated by any change to the
static data.
In all Rosemount devices the units of the
transducer block is forced to match the unit code.
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
LCD TRANSDUCER
BLOCK
Table C-4. LCD Transducer Block Parameters and Descriptions
Parameter
Index
Description
ALERT_KEY
BLK_TAG_1
BLK_TAG_2
BLK_TAG_3
BLK_TAG_4
BLK_TYPE_1
BLK_TYPE_2
BLK_TYPE_3
BLK_TYPE_4
BLOCK_ALM
4
15
21
27
33
14
20
26
32
8
BLOCK_ERR
6
COLLECTION_DIRECTORY
12
CUSTOM_TAG_1
CUSTOM_TAG _2
CUSTOM_TAG _3
CUSTOM_TAG _4
CUSTOM_UNITS_1
CUSTOM_UNITS _2
CUSTOM_UNITS _3
CUSTOM_UNITS _4
DISPLAY_PARAM_SEL
17
23
29
35
19
25
31
37
13
MODE_BLK
PARAM_INDEX_1
PARAM_INDEX_2
PARAM_INDEX_3
PARAM_INDEX_4
ST_REV
STRATEGY
TAG_DESC
TRANSDUCER_DIRCTORY
5
16
22
28
34
1
3
2
9
TRANSDUCER_TYPE
UNITS_TYPE_1
UNITS_TYPE_2
UNITS_TYPE_3
UNITS_TYPE_4
UPDATE_EVT
XD_ERROR
10
18
24
30
36
7
11
The identification number of the plant unit.
The tag of the block containing DP1.
The tag of the block containing DP2.
The tag of the block containing DP3.
The tag of the block containing DP4.
The enumerated block type for DP1's block.
The enumerated block type for DP2's block.
The enumerated block type for DP3's block.
The enumerated block type for DP4's block.
The BLOCK_ALM is used for all configuration, hardware, connection failure or system problems
in the block. The cause of the alert is entered in the subcode field. The first alert to become active
will set the Active status in the Status attribute. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported without clearing the Active status, if the
subcode has changed.
This parameter reflects the error status associated with the hardware or software components
associated with a block. it is a bit string, so that multiple errors may be shown.
A directory that specifies the number, starting indicies, and DD Item ID's of the data collections in
each transducer block.
The block description that is displayed for DP1.
The block description that is displayed for DP2.
The block description that is displayed for DP3.
The block description that is displayed for DP4.
This is the user entered units that are displayed when UNITS_TYPE_1=Custom.
This is the user entered units that are displayed when UNITS_TYPE_2=Custom.
This is the user entered units that are displayed when UNITS_TYPE_3=Custom.
This is the user entered units that are displayed when UNITS_TYPE_4=Custom.
This will determine which Display Parameters are active.
Bit 0 = DP1
Bit 1 = DP2
Bit 2 = DP3
Bit 3 = DP4
Bit 4 = Bar Graph enable
The actual, target, permitted, and normal modes of the block.
The relative index of DP1 within its block.
The relative index of DP2 within its block.
The relative index of DP3 within its block.
The relative index of DP4 within its block.
The revision level of the static data associated with the function block.
The strategy field can be used to identify grouping of blocks.
The user description of the intended application of the block.
A directory that specifies the number and starting indicies of the transducers in the transducer
block.
Identifies the transducer that follows.
This parameter determines where the units for the display parameter come from.
This parameter determines where the units for the display parameter come from.
This parameter determines where the units for the display parameter come from.
This parameter determines where the units for the display parameter come from.
This alert is generated by any change to the staic data.
Provides additional error codes related to transducer blocks.
C-11
Reference Manual
00809-0400-4728, Rev AA
June 2011
Rosemount 644
PID BLOCK
Table C-5. PID Block Parameters and Descriptions
Parameter
Index
Parameter
Index
Parameter
Index
ACK_OPTIONS
ALARM_HYS
ALARM_SUM
ALERT_KEY
BAL_TIME
BETA
BIAS
BKCAL_HYS
BKCAL_IN
BKCAL_OUT
BLOCK_ALARM
BLOCK_ERR
BYPASS
CAP_STDDEV
CAS_IN
CONTROL_OPS
DV_HI_ALM
DV_HI_LIM
DV_HI_PRI
DV_LO_ALM
DV_LO_LIM
DV_LO_PRI
ERROR
FF_GAIN
FF_SCALE
FF_VAL
GAIN
GAMMA
GRANT_DENY
HI_ALM
HI_HI_ALM
46
47
45
4
25
73
66
30
27
31
44
6
17
76
18
13
64
57
56
65
59
58
67
42
41
40
23
72
12
61
60
HI_HI_LIM
HI_HI_PRI
HI_LIM
HI_PRI
IDEADBAND
IN
LO_ALM
LO_LIM
LO_LO_ALM
LO_LO_LIM
LO_LO_PRI
LO_PRI
MATHFORM
MODE_BLK
OUT
OUT_HI_LIM
OUT_LO_LIM
OUT_SCALE
PV
PV_FTIME
PV_SCALE
RATE
RCAS_IN
RCAS_OUT
RESET
ROUT_IN
ROUT_OUT
SHED_OPT
SP
SP_FTIME
SP_HI_LIM
49
48
51
50
74
15
62
53
63
55
54
52
70
5
9
28
29
11
7
16
10
26
32
35
24
33
36
34
8
69
21
SP_LO_LIM
SP_RATE_DN
SP_RATE_UP
SP_WORK
ST_REV
STATUS_OPTS
STDDEV
STRATEGY
STRUCTURECONFIG
T_AOPERIODS
T_AUTO_EXTRA_DT
T_AUTO_HYSTERESIS
T_GAIN_MAGNIFIER
T_HYSTER
T_IPGAIN
T_PDTIME
T_PSGAIN
T_PTIMEC
T_RELAYSS
T_REQUEST
T_STATE
T_STATUS
T_TARGETOP
T_UGAIN
T_UPERIOD
TAG_DESC
TRK_IN_D
TRK_SCALE
TRK_VAL
UPDATE_EVT
22
19
20
68
1
14
75
3
71
92
90
91
89
87
80
85
83
84
88
77
78
79
86
81
82
2
38
37
39
43
C-12
Reference Manual
00809-0100-4728, Rev KA
June 2011
Rosemount 644
Index
A
B
Address . . . . . . . . . . . . . . . . . . 3-2
Temporary Node . . . . . . . . . . 3-2
Advanced Diagnostics Transducer
Block (ADB) . . . . . . . . . . . . . . . 3-4
Advanced Features . . . . . . . . . 3-13
ADVISE_ACTIVE . . . . . . . . . . . . 3-8
ADVISE_ALM . . . . . . . . . . . . . . 3-8
ADVISE_ENABLED . . . . . . . . . . 3-8
ADVISE_MASK . . . . . . . . . . . . . 3-8
ADVISE_PRI . . . . . . . . . . . . . . . 3-8
Advisory Alarms . . . . . . . . . . . . . 3-8
ADVISE_ACTIVE . . . . . . . . . . 3-8
ADVISE_ALM . . . . . . . . . . . . 3-8
ADVISE_MASK . . . . . . . . . . . 3-8
ADVISE_PRI . . . . . . . . . . . . . 3-8
AI Block.See Analog Input (AI) Function
Block
Alarm Priority . . . . . . . . . . . . . . 3-13
ALARM_TYPE . . . . . . . . . . . . . 3-13
Alarms
ADVISE_ACTIVE . . . . . . . . . . 3-8
ADVISE_ALM . . . . . . . . . . . . 3-8
ADVISE_MASKParameter
ADVISE_MASK . . . . . . . . . 3-8
ADVISE_PRI . . . . . . . . . . . . . 3-8
Advisory . . . . . . . . . . . . . . . . 3-8
ALARM_TYPE . . . . . . . . . . . 3-13
FAILED_ACTIVE . . . . . . . . . . 3-7
FAILED_ALARMS . . . . . . . . . 3-6
FAILED_ALM . . . . . . . . . . . . . 3-7
FAILED_ENABLED . . . . . . . . 3-6
FAILED_MASK . . . . . . . . . . . 3-7
FAILED_PRI . . . . . . . . . . . . . 3-7
MAINT_ACTIVE . . . . . . . . . . . 3-7
MAINT_ALARMS . . . . . . . . . . 3-7
MAINT_ALM . . . . . . . . . . . . . 3-7
MAINT_ENABLED . . . . . . . . . 3-7
MAINT_MASK . . . . . . . . . . . . 3-7
MAINT_PRI . . . . . . . . . . . . . . 3-7
PlantWeb . . . . . . . . . . . . 3-6, 3-8
Priorety . . . . . . . . . . . . . . . . 3-13
Process . . . . . . . . . . . . . . . . 3-12
Analog Input (AI) block . . . . . . . .C-8
Analog Input (AI) Function Block 3-4,
BAD if Limited . . .
BLK_TAG_# . . . .
BLK_TYPE_# . . .
BLOCK_ERR
AI Block . . . . .
Resource Block
3-9, . . . . . . . . . . . . . . . . . . . . . C-8
ALARM_TYPE . . . . . . . . . . . 3-13
Block Information . . . . . . . . . . C-8
BLOCK_ERR . . . . . . . . . . . . 3-22
Configuration . . . . . . . . . . . . . 3-9
OUT_D . . . . . . . . . . . . . . . . 3-13
Parameters . . . . . . . . . . . . . . C-9
PV_FTIME . . . . . . . . . . . . . . 3-12
Status . . . . . . . . . . . . . . . . . 3-13
F
. . . . . . . . . . 3-13
. . . . . . . . . . 3-14
. . . . . . . . . . 3-14
. . . . . . . . . . 3-22
. . . . . . . . . . 3-23
C
Capabilities . . . . . . . . . . . . . . . . 3-4
Block Execution Times . . . . . . 3-4
Host Timer . . . . . . . . . . . . . . 3-4
VCRs . . . . . . . . . . . . . . . . . . 3-4
Changing Modes . . . . . . . . . . . . 3-2
Channel . . . . . . . . . . . . . .3-9, 3-10
Configuration
Analog Input (AI) Function Block 3-9
XD_SCALE, OUT_SCALE 3-10
Channel . . . . . . . . . . . . . . . . 3-9
Custom Meter . . . . . . . . . . . 3-14
Direct . . . . . . . . . . . . . . . . . 3-10
Examples . . . . . . . . . . . . . . 3-11
L_TYPE . . . . . . . . . . . . . . . 3-10
Direct . . . . . . . . . . . . . . . 3-10
Indirect . . . . . . . . . . . . . . 3-10
LCD Transducer Block . . . . . 3-14
Resource Block . . . . . . . . . . . 3-4
Considerations . . . . . . . . . . . . . 1-3
Commissioning . . . . . . . . . . . 1-3
Electrical . . . . . . . . . . . . . . . . 1-3
Environmental . . . . . . . . . . . . 1-3
Temperature . . . . . . . . . . . 1-3
General . . . . . . . . . . . . . . . . 1-3
Mechanical . . . . . . . . . . . . . . 1-3
Location . . . . . . . . . . . . . . 1-3
Special Mounting . . . . . . . . 1-3
Custom meter configuration . . . 3-14
CUSTOM_TAG_# . . . . . . . . . . 3-14
CUSTOM_UNITS_# . . . . . . . . 3-15
FAILED_ACTIVE alarms . . . . . . .3-7
FAILED_ALARMS . . . . . . . . . . .3-6
FAILED_ACTIVE . . . . . . . . . . .3-7
FAILED_ALM . . . . . . . . . . . . .3-7
FAILED_ENABLED . . . . . . . . .3-6
FAILED_MASK . . . . . . . . . . . .3-7
FAILED_PRI . . . . . . . . . . . . . .3-7
FAILED_ALM . . . . . . . . . . . . . . .3-7
FAILED_ENABLED alarms . . . . .3-6
FAILED_MASK alarms . . . . . . . .3-7
FAILED_PRI alarms . . . . . . . . . .3-7
FEATURES
FEATURES_SEL . . . . . . . . . .3-6
Features . . . . . . . . . . . . . . . . . .3-5
Advanced . . . . . . . . . . . . . . .3-13
FEATURES, FEATURES_SEL . . .3-5
Features . . . . . . . . . . . . . . . . .3-5
Reports . . . . . . . . . . . . . . . . .3-5
Soft W Lock, Hard W Lock . . . .3-5
Unicode . . . . . . . . . . . . . . . . .3-5
Filtering . . . . . . . . . . . . . . . . . .3-12
AI block . . . . . . . . . . . . . . . .3-12
Foundation fieldbus function blocks .
3-4
FREE_SPACE . . . . . . . . . . . . . .3-3
G
General Block Information
Block Instantiation . . . .
Capabilities . . . . . . . . .
Link Active Scheduler .
Modes . . . . . . . . . . . .
Ground the Transmitter
Grounded
Thermocouple . . . .
Ungrounded
Millivolt . . . . . . . . .
RTD/Ohm . . . . . . .
Thermocouple . . . .
. . . . . .3-2
. . . . . .3-2
. . . . . .3-2
. . . . . .3-2
. . . . .2-12
. . . . . 2-11
. . . . . 2-11
. . . . . 2-11
D
Damping . . . . . . . . . .
Diagram
Sensor Wiring . . . . .
Direct . . . . . . . . . . . . .
DISPLAY_PARAM_SEL
. . . . . . . 3-9
. . . . . . . 2-8
. . . . . . 3-10
. . . . . 3-14
E
H
Hazardous Locations Installations
Installation drawings . . . . . . . B-7
HI_HI_LIM . . . . . . . . . . . . . . . .3-12
HI_HI_PRI . . . . . . . . . . . . . . . .3-12
HI_LIM . . . . . . . . . . . . . . . . . .3-12
HI_PRI . . . . . . . . . . . . . . . . . .3-12
Examples, Configuration . . . . . 3-11
Typical Pressure . . . . . . . . . 3-12
Execution Times . . . . . . . . . . . . 3-4
Index-1
Reference Manual
00809-0100-4728, Rev KA
June 2011
Rosemount 644
I
Indirect . . . . . . . .
Installation . . . . . .
European . . . . .
Head Mount .
Flowchart . . . . .
LCD Display . . .
Multichannel . .
North American
Head Mount .
Rail Mount . .
Instantiation, Block
. . . . . . . . . . 3-10
. . . . . . . . . . . 2-4
. . . . . . . . . . . 2-4
. . . . . . . . . . . 2-4
. . . . . . . . . . . 2-2
. . . . . . . . . . . 2-6
. . . . . . . . . . . 2-7
. . . . . . . . . . . 2-5
. . . . . . . . . . . 2-5
. . . . . . . . . . . 2-6
. . . . . . . . . . . 3-3
L
L_TYPE . . . . . . . . . .
Direct . . . . . . . . . .
Indirect . . . . . . . . .
LCD Display
Installation . . . . . . .
LCD meter . . . . . . . .
LCD Transducer Block
. . . . . . . 3-10
. . . . . . . 3-10
. . . . . . . 3-10
. . . . . . . . 2-6
. . . . . . . 3-14
. . . 3-4, 3-14,
C-11
Messaging . . . . . . .
Parameters . . . . . .
LCD Transducer block
Block Error . . . . . . .
Self Test . . . . . . . .
LIM_NOTIFY . . . . . . .
Limited
Bad . . . . . . . . . . . .
Uncertain . . . . . . . .
Link Active Scheduler .
LO_LIM . . . . . . . . . .
LO_LO_LIM . . . . . . .
LO_LO_PRI . . . . . . .
LO_PRI . . . . . . . . . .
Lower Trim Method . .
. . . . . . . 3-14
. . . . . . . C-11
. . . . . . . 3-24
. . . . . . . 3-24
. . . . . . . 3-24
. . . . . . . . 3-6
. . . . . . . 3-13
. . . . . . . 3-13
. . . . . . . . 3-3
. . . . . . . 3-12
. . . . . . . 3-12
. . . . . . . 3-12
. . . . . . . 3-12
. . . . . . . 3-18
M
MAINT_ACTIVE . . .
MAINT_ALARMS . . .
MAINT_ACTIVE . .
MAINT_ALM . . . .
MAINT_ENABLED
MAINT_MASK . . .
MAINT_PRI . . . . .
MAINT_ALM . . . . . .
MAINT_ENABLED . .
MAINT_MASK . . . . .
MAINT_PRI . . . . . . .
Manual Mode . . . . .
Manual Operation . .
MAX_NOTIFY . . . . .
LIM_NOTIFY . . . .
Methods . . . . . . . . .
Index-2
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . . 3-7
. . . . . . . . 3-21
. . . . . . . . 3-15
. . . . . . . . . 3-6
. . . . . . . . . 3-6
. . . . . . . . 3-15
Millivolt
Ungrounded . . . . . . .
Wiring . . . . . . . . . . . .
MODE_BLK.TARGET . .
MODE_BLOCK.ACTUAL
Modes
Changing Modes . . . .
Permitted Modes . . . .
Types of Modes . . . . .
Auto . . . . . . . . . . .
Man . . . . . . . . . . .
Other . . . . . . . . . .
Out of Service . . . .
Mounting . . . . . . . . . . .
Model 644H
DIN Rail . . . . . . . .
Threaded Sensor . .
Multichannel
Installation . . . . . . . . .
. . . . . 2-11
. . . . . . 2-8
. . . . . . 3-2
. . . . . . 3-2
......
......
......
......
......
......
......
......
3-2
3-2
3-2
3-2
3-2
3-2
3-2
2-3
. . . . . . 2-3
. . . . . . 2-3
. . . . . . 2-7
N
Network Parameters . . . . . . . . . 3-4
Node address . . . . . . . . . . . . . . 3-2
O
Ohm
Ungrounded . . . . . . . . . . . .
Wiring . . . . . . . . . . . . . . . . .
Operation and Maintenance
Sensor Transducer Block . . .
OUT_D . . . . . . . . . . . . . . . . .
AI block . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . .
Manual . . . . . . . . . . . . . . . .
Transmitter . . . . . . . . . . . . .
2-11
. 2-9
3-18
3-13
3-13
. 1-2
. 1-2
. 1-2
P
PARAM_INDEX_# . . . . . . . . . . 3-14
Parameter
ADVISE_ACTIVE . . . . . . . . . . 3-8
ADVISE_ALM . . . . . . . . . . . . 3-8
ADVISE_ENABLED . . . . . . . . 3-8
ADVISE_PRI . . . . . . . . . . . . . 3-8
ALARM_TYPE . . . . . . . . . . . 3-13
Analog Input (AI) Function Block . .
C-9
BLK_TAG_# . . . . . . . . . . . . 3-14
BLK_TYPE_# . . . . . . . . . . . 3-14
BLOCK_ERR . . . . . . .3-22, 3-23
CHANNEL . . . . . . . . . . . . . . . 3-9
CUSTOM_TAG_# . . . . . . . . 3-14
CUSTOM_UNITS_# . . . . . . . 3-15
DEFINE_WRITE_LOCK . . . . . 3-5
DISPLAY_PARAM_SEL . . . . 3-14
FAILED_ACTIVE . . . . . . . . . . 3-7
FAILED_ALARMS . . . . . . . . . 3-6
FAILED_ALM . . . . . . . . . . . . .3-7
FAILED_ENABLED . . . . . . . . .3-6
FAILED_MASK . . . . . . . . . . . .3-7
FAILED_PRI . . . . . . . . . . . . . .3-7
FEATURES . . . . . . . . . . . . . .3-5
FEATURES_SEL . . . . . . . . . .3-6
FREE_SPACE . . . . . . . . . . . .3-3
HI_HI_LIM . . . . . . . . . . . . . .3-12
HI_HI_PRI . . . . . . . . . . . . . .3-12
HI_LIM . . . . . . . . . . . . . . . . .3-12
HI_PRI . . . . . . . . . . . . . . . . .3-12
L_TYPE . . . . . . . . . . . . . . . .3-10
LCD Transducer Block . . . . . C-11
LIM_NOTIFY . . . . . . . . . . . . .3-6
LO_LIM . . . . . . . . . . . . . . . .3-12
LO_LO_LIM . . . . . . . . . . . . .3-12
LO_LO_PRI . . . . . . . . . . . . .3-12
LO_PRI . . . . . . . . . . . . . . . .3-12
MAINT_ACTIVE . . . . . . . . . . .3-7
MAINT_ALARMS . . . . . . . . . .3-7
MAINT_ALM . . . . . . . . . . . . . .3-7
MAINT_ENABLED . . . . . . . . .3-7
MAINT_MASK . . . . . . . . . . . .3-7
MAINT_PRI . . . . . . . . . . . . . .3-7
MAX_NOTIFY . . . . . . . . . . . . .3-6
MODE_BLK.TARGET . . . . . . .3-2
MODE_BLOCK_ACTUAL . . . .3-2
Network . . . . . . . . . . . . . . . . .3-4
OUT_D . . . . . . . . . . . . . . . .3-13
OUT_SCALE . . . . . . . . . . . .3-10
PARAM_INDEX_# . . . . . . . . .3-14
PV_FTIME . . . . . . . . . . 3-9, 3-12
RECOMMENDED_ACTION . . .3-8
REPORTS . . . . . . . . . . . . . . .3-5
Resource Block . . . . . . . . . . . C-2
Sensor Transducer Block . . . . C-5
STATUS_OPTIONS . . . . . . .3-13
UNICODE . . . . . . . . . . . . . . .3-5
UNITS_TYPE_# . . . . . . . . . .3-15
WRITE_LOCK . . . . . . . . . . . .3-5
XD_SCALE . . . . . . . . . 3-9, 3-10
Performance specifications . . . . A-3
Permitted Modes . . . . . . . . . . . .3-2
PID Block . . . . . . . . . . . . . . . . . .3-4
PID block . . . . . . . . . . . . . . . . . .3-4
PlantWeb Alarms . . . . . . . . 3-6, 3-8
Advisory . . . . . . . . . . . . . . . . .3-8
FAILED_ALARMS . . . . . . . . . .3-6
MAINT_ALARMS . . . . . . . . . .3-7
Power Supply . . . . . . . . . . . . . . 2-11
Process Alarms . . . . . . . . . . . .3-12
Propagate Fault Forward . . . . . .3-13
Proportional/Integral/Derivative (PID)
function block . . . . . . . . . . . . . . .3-4
PV_FTIME . . . . . . . . . . . . . . . . .3-9
AI block . . . . . . . . . . . . . . . .3-12
Reference Manual
00809-0100-4728, Rev KA
June 2011
R
Recommended Actions . . . . . . . . 3-8
PlantWeb Alarms . . . . . . . . . . 3-8
RECOMMENDED_ACTION . . . . 3-8
Reference data . . . . . . . . . . . . . A-8
Reports . . . . . . . . . . . . . . . . . . . 3-5
Resource Block . . . . 3-4, 3-23, C-1
Block Errors . . . . . . . . . . . . . 3-23
Block Information . . . . . . . . . . C-1
Configuration . . . . . . . . . . . . . 3-4
Detailed Status . . . . . . . . . . . 3-23
FEATURES, FEATURES_SEL 3-5
Parameters . . . . . . . . . . . . . . C-2
BLOCK_ERR . . . . . . . . . . 3-23
Summary Status . . . . . . . . . . 3-23
Resource block . . . . . . . . . . . . . C-1
Return of Materials . . . . . . . . . . . 1-4
RTD
Ungrounded . . . . . . . . . . . . . 2-11
Wiring . . . . . . . . . . . . . . . . . . 2-9
S
Security . . . . . . . . . . . .
Self Test . . . . . . . . . . . .
Sensor
Connection
Diagram . . . . . . . .
Millivolt . . . . . . . . . . .
Ohm . . . . . . . . . . . . .
RTD . . . . . . . . . . . . .
Thermocouple . . . . . .
Wiring . . . . . . . . . . . .
Sensor Calibration . . . . .
Sensor Transducer Block
. . . . . . 3-5
. . . . . 3-24
. . . . . . 2-8
. . . . . . 2-8
. . . . . . 2-9
. . . . . . 2-9
. . . . . . 2-8
. . . . . . 2-8
. . . . . 3-18
. . 3-4, 3-9,
3-18, . . . . . . . . . . . . . . . . . . . . C-5
Block Information . . . . . . . . . . C-5
Configuration . . . . . . . . . . . . . 3-9
Operation and Maintenance . . 3-18
Parameters . . . . . . . . . . . . . . C-5
Simulate . . . . . . . . . . . . . . . . . 3-21
Simulation . . . . . . . . . . . . . . . . 3-21
Manual Mode . . . . . . . . . . . . 3-21
Soft W Lock, Hard W Lock . . . . . 3-5
Specifications
Performance . . .
Status . . . . . . . . . .
AI block . . . . . . .
STATUS_OPTIONS
Supported Units . . .
Switches
Simulate . . . . . .
. . . . . . . . . . A-3
. . . . . . . . . 3-21
. . . . . . . . . 3-13
. . . . . . . . . 3-13
. . . . . . . . . 3-10
Rosemount 644
Trim
Zero . . . . . . . . . . . . .
Troubleshooting . . . . . .
Flowchart . . . . . . . . .
LCD Transducer block
Reference table . . . . .
Resource Block . . . . .
Types of Modes
Auto . . . . . . . . . . . . .
Man . . . . . . . . . . . . .
Other Types of Modes
Out of Service . . . . . .
. . . . . . 3-9
. . . . . 3-16
. . . . . 3-16
. . . . . 3-24
. . . . . 3-16
. . . . . 3-23
......
......
......
......
3-2
3-2
3-2
3-2
U
Uncertain
Limited . . . . . . . .
Man Mode . . . . . .
Unicode . . . . . . . . .
UNITS_TYPE_# . . .
Upper Trim Method .
. . . . . . . . 3-13
. . . . . . . . 3-13
. . . . . . . . . 3-5
. . . . . . . . 3-15
. . . . . . . . 3-18
V
Virtual Communication Relationship
(VCRs) . . . . . . . . . . . . . . . . . . . 3-4
Network Parameters . . . . . . . . 3-4
W
Wiring . . . . . . . . . .
Sensor Connection
Diagram . . . . .
Millivolt . . . . . .
Ohm . . . . . . . .
RTD . . . . . . . .
Thermocouple .
.........
........
.........
.........
.........
.........
.........
2-7
2-8
2-8
2-8
2-9
2-9
2-8
X
XD_SCALE . . . . . . . . . . . . . . . 3-9
XD_SCALE, OUT_SCALE . . . . 3-10
L_TYPE
Direct . . . . . . . . . . . . . . . 3-10
Z
Zero Trim . . . . . . . . . . . . . . . . . 3-9
. . . . . . . . . 3-21
T
Thermocouple
Grounded . . . . . . . . . . . . . . 2-12
Ungrounded . . . . . . . . . . . . . 2-11
Wiring . . . . . . . . . . . . . . . . . . 2-8
Index-3
Reference Manual
Rosemount 644
Index-4
00809-0100-4728, Rev KA
June 2011
Reference Manual
00809-0400-4728, Rev AA
June 2011
Standard Terms and Conditions of Sale can be found at www.rosemount.com/terms_of_sale
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc.
PlantWeb is a registered trademark of one of the Emerson Process Management group of companies.
FOUNDATION is a trademark of the Fieldbus Foundation.
HART is a registered trademark of the HART Communication Foundation.
Lexan and Noryl are registered trademark of General Electric.
WAGO is a registered trademark of Kontakttechnik GmbH, Germany.
All other marks are the property of their respective owners.
© 2011 Rosemount Inc. All rights reserved.
Emerson Process Management
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN 55317 USA
T (U.S.) 1-800-999-9307
T (International) (952) 906-8888
F (952) 906-8889
www.rosemount.com
00809-0400-4728 Rev AA, 6/11
Emerson Process Management
Temperature GmbH
Frankenstrasse 21
63791 Karlstein
Germany
T 49 (6188) 992 0
F 49 (6188) 992 112
Emerson Process Management Asia
Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947
[email protected]