Download Mitsubishi Mr.Slim PCA-A.KA4 Technical data
Transcript
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS March 2009 No. OCS14 TECHNICAL DATA BOOK R410A INVERTER <Indoor unit> [Model names] PLA-A·BA PKA-A·HA PKA-A·HAL PKA-A·KA PKA-A·KAL PCA-A·KA PEA-A·AA <Outdoor unit> PUZ-A18/24/30/36/42NHA3 PUZ-A18/24/30/36/42NHA3-BS PUY-A12/18/24/30/36/42NHA3 PUY-A12/18/24/30/36/42NHA3-BS [Model names] CONTENTS 1. REFERENCE SERVICE MANUAL ............................................. 2 2. SPECIFICATIONS....................................................................... 3 3. OUTLINES AND DIMENSIONS ................................................ 10 4. WIRING DIAGRAM ................................................................... 21 5. REFRIGERANT SYSTEM DIAGRAM ...................................... 30 6. PERFORMANCE CURVES ...................................................... 33 7. CORRECTION FACTORS ........................................................ 35 8. AIR FLOW DATA ...................................................................... 36 9. NOISE CRITERION CURVES .................................................. 45 10. OPTIONAL PARTS .................................................... Back cover 1 REFERENCE SERVICE MANUAL For information on service, please refer to the service manual as follows. 1-1. INDOOR UNIT Service Manual No. Model name Service Ref. PLA-A12/18/24/30/36/42BA PLA-A12/18/24/30/36/42BA1 OCH420 OCB420 PKA-A12/18HA PKA-A12/18HAL PKA-A12/18HA PKA-A12/18HAL OCH456 OCB456 PKA-A24/30/36KA PKA-A24/30/36KAL PKA-A24/30/36KA.TH PKA-A24/30/36KAL.TH OCH457 OCB457 PCA-A24/30/36/42KA PCA-A24/30/36/42KA OCH455 OCB455 PEA-A12/18AA PEA-A12/18AA.TH HWE08070 BWE0811A 1-2. OUTDOOR UNIT Service Manual No. Model name Service Ref. PUZ-A18/24/30/36/42NHA3 PUZ-A18/24/30/36/42NHA3-BS PUY-A12/18/24/30/36/42NHA3 PUY-A12/18/24/30/36/42NHA3-BS PUZ-A18/24/30/36/42NHA3 PUZ-A18/24/30/36/42NHA3-BS PUY-A12/18/24/30/36/42NHA3 PUY-A12/18/24/30/36/42NHA3-BS 2 OCH458 OCB458 2 SPECIFICATIONS 2-1. CEILING CASSETTE TYPE Model name Cooling Heating Heating at low ambient Power supply Voltage Indoor unit Remote Controller Outdoor unit Indoor unit Outdoor unit Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h *1 SHF Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W *1 HSPF (/) Btu/h/W Rated Capacity Btu/h Total Input W *2 COP W/W Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W CMM Air flow DRY (Lo-M2-M1-Hi) WET CMM Air flow DRY CFM (Lo-M2-M1-Hi) WET CFM External pressure Pa Sound level dB(A) (Lo-M2-M1-Hi) External finish (Panel) Dimension W : mm [inch] Unit (Panel) D : mm [inch] H : mm [inch] Weight kg Unit (Panel) lbs mm [inch] Field drain pipe size O.D. MCA MOCP Fan Motor Fan Motor Output Compressor Air flow Refrigerant Control Defrost Method Sound level at cooling Sound level at heating External finish Dimension Weight Type Charge Oil Refrigerant pipe size Gas side O.D. Liquid side O.D. Refrigerant pipe length Height difference Length Refrigerant Piping Connection Method A A F.L.A. W R.L.A L.R.A. CMM [CFM] dB(A) dB(A) W : mm [inch] D : mm [inch] H : mm [inch] kg [lbs] Refrigerant kg [lbs, oz] L [oz] mm [inch] mm [inch] PLA-A12BA PLA-A18BA PLA-A24BA PLA-A30BA PLA-A36BA PLA-A42BA PUY-A12NHA3 PUY-A18NHA3 PUY-A24NHA3 PUY-A30NHA3 PUY-A36NHA3 PUY-A42NHA3 PUY-A12NHA3-BS PUY-A18NHA3-BS PUY-A24NHA3-BS PUY-A30NHA3-BS PUY-A36NHA3-BS PUY-A42NHA3-BS 12,000 18,000 24,000 30,000 35,000 42,000 12,000 18,000 24,000 30,000 35,000 42,000 6,000 8,000 12,000 12,000 12,000 18,000 1260 1940 2500 4100 4500 4600 9.5 9.3 9.6 7.3 7.8 9.1 13.5 14.2 13.6 13.6 14.2 14.4 1.7 3.0 5.1 7.2 8.1 10.9 0.84 0.81 0.76 0.73 0.74 0.71 1phase, 60Hz, 208/230V 15 25 30 AC 208 / 230V DC24V DC12V 1 2 15 0.51 1.00 50 120 11-12-13-15 12-14-16-18 14-16-18-21 20-23-26-30 22-25-28-31 10-11-12-14 11-13-15-17 13-15-17-20 19-22-25-29 21-24-27-30 390-420-460-530 420-490-570-640 490-570-640-740 710-810-920-1060 780-880-990-1090 350-390-420-490 390-460-530-600 460-530-600-710 670-770-880-1030 740-850-950-1060 0 27-28-29-31 28-29-31-32 28-30-32-34 32-34-37-40 34-36-39-41 White Munsell 6.4Y 8.9 / 0.4 840 (950) [ 33-1/16 (37-3/8) ] 840 (950) [ 33-1/16 (37-3/8) ] 258 (35) [ 10-3/16 (1-3/8) ] 298 (35) [ 11-3/4 (1-3/8) ] 22 (6) 23 (6) 25 (6) 49 (13) 51 (13) 55 (13) 32 [ 1-1/4 ] Attached in Grille 13 18 25 26 15 20 30 40 0.35 0.75 0.4 + 0.4 40 75 86 + 86 SNB130FPBM1 TNB220FLHM ANV33FDPMT 12 20 14 17.5 27.5 100 [3,530] 34 [1,200] 55 [1,940] Linear Expansion Valve 46 48 51 Ivory Munsell 3Y 7.8/1.1 800 [31-1/2] 950 [37-3/8] 330+23 [13 + 7/8] 330+30 [13 + 1-3/16] 600 [23-5/8] 943 [37-1/8] 1350 [53-1/8] 117 [258] 41 [90] 44 [97] 74 [163] R410A 4.5 [10 lbs] 1.3 [2 lbs 14 oz] 1.7 [3 lbs 12 oz] 3.0 [6 lbs 10 oz] 1.4 (FV50S) [45] 0.65 (MEL56) [20] 0.87 (FV50S) [28] 12.7 [1/2] 15.88 [5/8] 6.35 [1/4] 9.52 [3/8] Max. 30m [Max.100ft] Max. 30m [Max.100ft] Max. 50 [Max.165ft] Not Supplied Flared NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) (heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) *2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Operating range Outdoor : D.B. 35(95°F), W.B. 23.9(75°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F) Outdoor intake air temperature Indoor intake air temperature Maximum D.B. 46(115°F) D.B. 35(95°F), W.B. 21.7(71°F) Minimum D.B. -18(0°F)* D.B. 19.4(67°F), W.B. 13.9(57°F) Maximum D.B. 21.1(70°F), W.B. 15(59°F) D.B. 26.7(80°F), W.B. 19.4(67°F) Heating Minimum D.B. -11.1(12°F), W.B. -12.2(10°F) D.B. 21.1(70°F), W.B. 15.6(60°F) * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.) Cooling 3 Model name Cooling Heating Heating at low ambient Power supply Voltage Indoor unit Remote Controller Outdoor unit Indoor unit Outdoor unit Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h *1 SHF Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W *1 HSPF (/) Btu/h/W Rated Capacity Btu/h Total Input W *2 COP W/W Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY CMM (Lo-M2-M1-Hi) WET CMM Air flow DRY CFM (Lo-M2-M1-Hi) WET CFM External pressure Pa Sound level dB(A) (Lo-M2-M1-Hi) External finish (Panel) Dimension W : mm [inch] Unit (Panel) D : mm [inch] H : mm [inch] Weight kg Unit (Panel) lbs mm [inch] Field drain pipe size O.D. MCA MOCP Fan Motor Fan Motor Output Compressor A A F.L.A. W R.L.A L.R.A. CMM [CFM] Air flow Refrigerant Control Defrost Method Sound level at cooling dB(A) Sound level at heating dB(A) External finish W : mm [inch] Dimension D : mm [inch] H : mm [inch] kg [lbs] Weight Refrigerant Type kg [lbs, oz] Charge L [oz] Oil Refrigerant pipe size Gas side O.D. mm [inch] Liquid side O.D. mm [inch] Refrigerant pipe length Height difference Length Refrigerant Piping Connection Method PLA-A18BA PLA-A24BA PLA-A30BA PLA-A36BA PLA-A42BA PUZ-A18NHA3 PUZ-A24NHA3 PUZ-A30NHA3 PUZ-A36NHA3 PUZ-A42NHA3 PUZ-A18NHA3-BS PUZ-A24NHA3-BS PUZ-A30NHA3-BS PUZ-A36NHA3-BS PUZ-A42NHA3-BS 18,000 24,000 30,000 35,000 42,000 18,000 24,000 30,000 35,000 42,000 8,000 12,000 12,000 12,000 18,000 1940 2500 4100 4500 4600 9.3 9.6 7.3 7.8 9.1 14.2 13.6 13.6 14.2 14.4 3.0 5.1 7.2 8.1 10.9 0.81 0.76 0.73 0.74 0.71 20,000 28,000 34,000 38,000 48,000 19,000 26,000 32,000 37,000 45,000 8,000 12,000 12,000 12,000 18,000 1900 2570 3370 3300 4450 2.93 2.96 2.78 3.28 2.96 9.8 / 7.5 8.5 / 6.8 8.7 / 6.9 9.3 / 7.3 9.3 / 7.2 13,000 16,000 23,000 25,000 30,000 1590 2200 3050 3070 4300 2.40 2.14 2.20 2.37 2.05 1phase, 60Hz, 208/230V 15 25 30 AC 208 / 230V DC24V DC12V 1 2 15 0.51 1.00 50 120 12-14-16-18 14-16-18-21 20-23-26-30 22-25-28-31 11-13-15-17 13-15-17-20 19-22-25-29 21-24-27-30 420-490-570-640 490-570-640-740 710-810-920-1060 780-880-990-1090 390-460-530-600 460-530-600-710 670-770-880-1030 740-850-950-1060 0 28-29-31-32 28-30-32-34 32-34-37-40 34-36-39-41 White Munsell 6.4Y 8.9 / 0.4 840 (950) [ 33-1/16 (37-3/8) ] 840 (950) [ 33-1/16 (37-3/8) ] 258 (35) [ 10-3/16 (1-3/8) ] 298 (35) [ 11-3/4 (1-3/8) ] 22 (6) 23 (6) 25 (6) 49 (13) 51 (13) 55 (13) 32 [ 1-1/4 ] Attached in Grille 13 18 25 26 15 30 40 0.35 0.75 0.4 + 0.4 40 75 86 + 86 SNB130FPBM1 TNB220FLHM ANV33FDPMT 12 20 14 17.5 27.5 34 [1,200] 55 [1,940] 100 [3,530] Linear Expansion Valve Reverse Cycle 46 48 51 47 50 55 Ivory Munsell 3Y 7.8/1.1 800 [31-1/2] 950 [37-3/8] 330+23 [13 + 7/8] 330+30 [13 + 1-3/16] 600 [23-5/8] 943 [37-1/8] 1350 [53-1/8] 45 [99] 75 [165] 118 [260] R410A 1.7 [3 lbs 12 oz] 3.0 [6 lbs 10 oz] 4.5 [10 lbs] 0.65 (MEL56) [20] 0.87 (FV50S) [28] 1.4 (FV50S) [45] 12.7 [1/2] 15.88 [5/8] 6.35 [1/4] 9.52 [3/8] Max. 30m [Max.100ft] Max. 30m [Max.100ft] Max. 50 [Max.165ft] Not Supplied Flared NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) (heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) *2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Operating range Outdoor : D.B. 35(95°F), W.B. 23.9(75°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F) Indoor intake air temperature Outdoor intake air temperature Maximum D.B. 35(95°F), W.B. 21.7(71°F) D.B. 46(115°F) Minimum D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. -18(0°F)* Maximum D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15(59°F) Heating Minimum D.B. 21.1(70°F), W.B. 15.6(60°F) D.B. -11.1(12°F), W.B. -12.2(10°F) * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.) Cooling 4 2-2. WALL-MOUNTED TYPE Indoor unit Model name Cooling Heating Heating at low ambient Power supply Voltage Indoor unit Outdoor unit MCA MOCP Fan Motor Fan Motor Output Compressor Air flow Refrigerant Control Defrost Method Sound level at cooling Sound level at heating External finish Dimension Refrigerant Refrigerant pipe size Refrigerant pipe length Weight Type Charge Oil Gas side O.D. Liquid side O.D. Height difference Length PKA-A18HA PKA-A18HAL PKA-A24KA PKA-A24KAL PKA-A30KA PKA-A30KAL PKA-A36KA PKA-A36KAL PUY-A12NHA3 PUY-A18NHA3 PUY-A24NHA3 PUY-A30NHA3 PUY-A36NHA3 PUY-A12NHA3-BS PUY-A18NHA3-BS PUY-A24NHA3-BS PUY-A30NHA3-BS PUY-A36NHA3-BS Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h *1 SHF Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W *1 HSPF (/) Btu/h/W Rated Capacity Btu/h Total Input W *2 COP W/W Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY CMM (Lo-Mid-Hi) WET CMM Air flow DRY CFM (Lo-Mid-Hi) WET CFM External pressure Pa Sound level dB(A) (Lo-Mid-Hi) External finish (Panel) Dimension W : mm [inch] Unit (Panel) D : mm [inch] H : mm [inch] Weight kg Unit (Panel) lbs Field drain pipe size I.D. mm [inch] Remote Controller Outdoor unit Refrigerant Piping Connection Method PKA-A12HA PKA-A12HAL A A F.L.A. W R.L.A L.R.A. CMM [CFM] dB(A) dB(A) W : mm [inch] D : mm [inch] H : mm [inch] kg [lbs] kg [lbs, oz] L [oz] mm [inch] mm [inch] 12,000 12,000 6,000 1190 10.1 15.2 2.0 0.81 - 18,000 18,000 8,000 2240 8.0 15.3 5.2 0.68 15 0.33 30 9-10.5-12 8-9.5-11 320-370-425 290-335-380 24,000 24,000 12,000 2270 10.6 17.0 5.0 0.77 1phase , 60Hz , 208/230V 25 AC 208 / 230V DC24V DC12V : Wired type 1 15 0.36 30,000 30,000 12,000 4130 7.3 15.5 8.1 0.70 - 34,200 34,200 12,000 5030 6.8 14.0 9.2 0.70 30 0.57 56 18-20-22 16-18-20 635-705-775 570-635-700 20-23-26 18-21-23 705-810-920 635-730-830 39-42-45 43-46-49 0 36-40-43 White Munsell 1.0Y 9.2/0.2 1170 [46-1/16] 295 [11-5/8] 365 [14-3/8] 21 46 16 [5/8] Attached in Indoor Unit 13 18 25 15 20 30 40 0.35 0.75 40 75 SNB130FPBM1 TNB220FLHM 12 14 17.5 34 [1,200] 55 [1,940] Linear Expansion Valve 46 48 Ivory Munsell 3Y 7.8/1.1 800 [31-1/2] 950 [37-3/8] 330+23 [13 + 7/8] 330+30 [13 + 1-3/16] 600 [23-5/8] 943 [37-1/8] 41 [90] 44 [97] 74[163] R410A 1.3 [2 lbs 14 oz] 1.7 [3 lbs 12 oz] 3.0 [6 lbs 10 oz] 0.65 (MEL56) [20] 0.87 (FV50S) [28] 12.7 [1/2] 15.88 [5/8] 6.35 [1/4] 9.52 [3/8] Max. 30m [Max. 100ft] Max. 30m [Max. 100ft] Max. 50m [Max. 165ft] Not Supplied Flared 898 [35-3/8] 249 [9-13/16] 295 [11-5/8] 13 29 NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) (heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) *2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Operating range Outdoor : D.B. 35(95°F), W.B. 23.9(75°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F) Indoor intake air temperature Outdoor intake air temperature D.B. 35(95°F), W.B. 21.7(71°F) D.B. 46(115°F) Maximum Cooling D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. -18(0°F)* Minimum D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15(59°F) Maximum Heating D.B. 21.1(70°F), W.B. 15.6(60°F) D.B. -11.1(12°F), W.B. -12.2(10°F) Minimum * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.) 5 Indoor unit Model name Cooling Heating Heating at low ambient Power supply Voltage Indoor unit Remote Controller Outdoor unit Outdoor unit Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h *1 SHF Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W *1 HSPF (/) Btu/h/W Rated Capacity Btu/h Total Input W *2 COP W/W Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY CMM (Lo-Mid-Hi) WET CMM Air flow DRY CFM (Lo-Mid-Hi) WET CFM External pressure Pa Sound level dB(A) (Lo-Mid-Hi) External finish (Panel) Dimension W : mm [inch] Unit (Panel) D : mm [inch] H : mm [inch] Weight kg Unit (Panel) lbs Field drain pipe size I.D. mm [inch] MCA MOCP Fan Motor Fan Motor Output Compressor Air flow Refrigerant Control Defrost Method Sound level at cooling Sound level at heating External finish Dimension Refrigerant Refrigerant pipe size Refrigerant pipe length Refrigerant Piping Connection Method Weight Type Charge Oil Gas side O.D. Liquid side O.D. Height difference Length A A F.L.A. W PKA-A18HA PKA-A18HAL PUZ-A18NHA3 PUZ-A18NHA3-BS 18,000 18,000 8,000 2240 8.0 15.3 5.2 0.68 20,000 19,000 8,000 1970 2.83 9.5 / 7.6 13,000 1670 2.28 PKA-A24KA PKA-A30KA PKA-A36KA PKA-A24KAL PKA-A30KAL PKA-A36KAL PUZ-A24NHA3 PUZ-A30NHA3 PUZ-A36NHA3 PUZ-A24NHA3-BS PUZ-A30NHA3-BS PUZ-A36NHA3-BS 24,000 30,000 34,200 24,000 30,000 34,200 12,000 12,000 12,000 2270 4130 5030 10.6 7.3 6.8 15.5 14.0 17.0 8.1 9.2 5.0 0.77 0.70 0.70 28,000 34,000 38,000 26,000 32,000 37,000 12,000 12,000 12,000 2330 3150 3610 3.27 2.98 3.00 10.8 / 8.6 8.9 / 7.1 9.3 / 7.5 18,000 23,000 25,000 2850 2200 3030 2.37 2.40 2.42 1phase , 60Hz , 208/230V 25 30 AC 208 / 230V DC24V DC12V : Wired type 1 15 0.36 0.57 56 18-20-22 20-23-26 16-18-20 18-21-23 635-705-775 705-810-920 635-730-830 570-635-700 0 15 0.33 30 9-10.5-12 8-9.5-11 320-370-425 290-335-380 36-40-43 39-42-45 43-46-49 White Munsell 1.0Y 9.2/0.2 1170 [46-1/16] 295 [11-5/8] 365 [14-3/8] 898 [35-3/8] 249 [9-13/16] 295 [11-5/8] 13 29 21 46 16 [5/8] Attached in Indoor Unit 18 30 0.75 75 TNB220FLHM 12 13 20 0.35 40 SNB130FPBM1 R.L.A L.R.A. CMM [CFM] 34 [1,200] dB(A) dB(A) 46 47 W : mm [inch] D : mm [inch] H : mm [inch] kg [lbs] 800 [31-1/2] 330+23 [13 + 7/8] 600 [23-5/8] 45 [99] kg [lbs, oz] L [oz] mm [inch] mm [inch] 1.7 [3 lbs 12 oz] 0.65 (MEL56) [20] 12.7 [1/2] 6.35 [1/4] 14 Max. 30m [Max. 100ft] NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) (heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) *2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Operating range 25 40 17.5 55 [1,940] Linear Expansion Valve Reverse Cycle 48 50 Ivory Munsell 3Y 7.8/1.1 950 [37-3/8] 330+30 [13 + 1-3/16] 943 [37-1/8] 75 [165] R410A 3.0 [6 lbs 10 oz] 0.87 (FV50S) [28] 15.88 [5/8] 9.52 [3/8] Max. 30m [Max. 100ft] Max. 50m [Max. 165ft] Not Supplied Flared Outdoor : D.B. 35(95°F), W.B. 23.9(75°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F) Indoor intake air temperature Outdoor intake air temperature Maximum D.B. 35(95°F), W.B. 21.7(71°F) D.B. 46(115°F) Cooling Minimum D.B. 19.4(67°F), W.B. 13.9(57°F) D.B. -18(0°F)* Maximum D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15(59°F) Heating Minimum D.B. 21.1(70°F), W.B. 15.6(60°F) D.B. -11.1(12°F), W.B. -12.2(10°F) * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.) 6 2-3. CEILING-SUSPENDED TYPE Model name Cooling Heating Heating at low ambient Power supply Voltage Indoor unit Remote Controller Outdoor unit Indoor unit Outdoor unit Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h *1 SHF Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W *1 HSPF (/) Btu/h/W Rated Capacity Btu/h Total Input W *2 COP W/W Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY CMM (Lo-M2-M1-Hi) WET CMM Air flow DRY CFM (Lo-M2-M1-Hi) WET CFM External pressure Pa Sound level dB(A) (Lo-M2-M1-Hi) External finish (Panel) Dimension W : mm [inch] Unit (Panel) D : mm [inch] H : mm [inch] Weight kg Unit (Panel) lbs mm [inch] Field drain pipe size O.D. MCA MOCP Fan Motor Fan Motor Output Compressor A A F.L.A. W R.L.A L.R.A. CMM [CFM] Refrigerant Refrigerant pipe size Refrigerant pipe length PCA-A24KA PUY-A24NHA3 PUY-A24NHA3-BS 24,000 24,000 12,000 2340 10.3 16.8 5.8 0.73 - PCA-A30KA PCA-A36KA PUY-A30NHA3 PUY-A36NHA3 PUY-A30NHA3-BS PUY-A36NHA3-BS 30,000 35,000 30,000 35,000 12,000 12,000 3760 4630 8.0 7.6 14.5 14.4 8.3 8.5 0.69 0.73 1phase , 60Hz , 208/230V 30 AC 208 / 230V DC24V DC12V 25 1 PCA-A42KA PUY-A42NHA3 PUY-A42NHA3-BS 42,000 42,000 18,000 4110 10.2 15.8 11.7 0.69 - 2 15 0.54 95 0.97 160 15-16-17-19 14-15-16-18 530-565-600-670 495-530-565-635 16-17-18-20 15-16-17-19 565-600-635-705 530-565-600-670 33-35-37-40 35-37-39-41 22-24-26-28 20-22-24-26 775-850-920-990 705-775-850-920 23-25-27-29 21-23-25-27 810-885-955-1025 740-810-885-955 37-39-41-43 39-41-43-45 0 White Munsell 6.4Y 8.9/0.4 1280 [50-3/8] 1600 [63] 680 [26-3/4] 230 [9-1/16] 32 71 18 30 14 Air flow Refrigerant Control Defrost Method Sound level at cooling dB(A) Sound level at heating dB(A) External finish Dimension W : mm [inch] D : mm [inch] H : mm [inch] Weight kg [lbs] Type kg [lbs] Charge Oil L [oz] Gas side O.D. mm [inch] Liquid side O.D. mm [inch] Height difference Length Refrigerant Piping Connection Method NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) (heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) *2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Operating range 36 79 26 [1-1/32] Attached in Indoor Unit 25 40 0.75 75 TNB220FLHM 12 17.5 55 [1,940] Linear Expansion Valve 48 Ivory Munsell 3Y 7.8/1.1 950 [37-3/8] 330+30 [13 + 1-3/16] 943 [37-1/8] 74[163] R410A 3.0 [6 lbs 10 oz] 0.87 (FV50S) [28] 15.88 [5/8] 9.52 [3/8] Max. 30m [Max. 100ft] Max. 50m [Max. 165ft] Not Supplied Flared Outdoor : D.B. 35(95°F), W.B. 23.9(75°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F) Outdoor intake air temperature Indoor intake air temperature Maximum D.B. 46(115°F) D.B. 35(95°F), W.B. 21.7(71°F) Cooling Minimum D.B. -18(0°F)* D.B. 19.4(67°F), W.B. 13.9(57°F) Maximum D.B. 21.1(70°F), W.B. 15(59°F) D.B. 26.7(80°F), W.B. 19.4(67°F) Heating Minimum D.B. -11.1(12°F), W.B. -12.2(10°F) D.B. 21.1(70°F), W.B. 15.6(60°F) * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.) 7 38 84 26 0.4 + 0.4 86 + 86 ANV33FDPMT 20 27.5 100 [3,530] 51 - 1350 [53-1/8] 117 [258] 4.5 [10 lbs] 1.4 (FV50S) [45] Model name Cooling Heating Heating at low ambient Power supply Voltage Indoor unit Remote Controller Outdoor unit Indoor unit Outdoor unit Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W EER Btu/h/W SEER Btu/h/W Moisture Removal Pints/h *1 SHF Max. Capacity Btu/h Rated Capacity Btu/h Min. Capacity Btu/h Total Input W COP W/W *1 HSPF (/) Btu/h/W Rated Capacity Btu/h Total Input W *2 COP W/W Phase, Cycle, Voltage Breaker size A Indoor - Outdoor S1-S2 Indoor - Outdoor S2-S3 Indoor - Remote Controller MCA A MOCP A Fan Motor F.L.A. Fan Motor Output W Air flow DRY CMM (Lo-M2-M1-Hi) WET CMM Air flow DRY CFM (Lo-M2-M1-Hi) WET CFM External pressure Pa Sound level dB(A) (Lo-M2-M1-Hi) External finish (Panel) Dimension W : mm [inch] Unit (Panel) D : mm [inch] H : mm [inch] Weight kg Unit (Panel) lbs Field drain pipe size O.D. mm [inch] MCA MOCP Fan Motor Fan Motor Output Compressor A A F.L.A. W R.L.A L.R.A. CMM [CFM] Refrigerant Refrigerant pipe size Refrigerant pipe length PCA-A24KA PUZ-A24NHA3 PUZ-A24NHA3-BS 24,000 24,000 12,000 2340 10.3 16.8 5.8 0.73 28,000 26,000 12,000 2310 3.30 10.9 / 8.9 18,000 2220 2.38 PCA-A30KA PCA-A36KA PUZ-A30NHA3 PUZ-A36NHA3 PUZ-A30NHA3-BS PUZ-A36NHA3-BS 30,000 35,000 30,000 35,000 12,000 12,000 3760 4630 8.0 7.6 14.5 14.4 8.3 8.5 0.69 0.73 34,000 38,000 32,000 37,000 12,000 12,000 3210 3190 2.92 3.40 9.2 / 7.1 10.2 / 8.1 23,000 25,000 2940 2800 2.29 2.62 1phase , 60Hz , 208/230V 30 AC 208 / 230V DC24V DC12V 25 1 PCA-A42KA PUZ-A42NHA3 PUZ-A42NHA3-BS 42,000 42,000 18,000 4110 10.2 15.8 11.7 0.69 48,000 45,000 18,000 3830 3.44 10.2 / 8.3 30,000 3820 2.30 2 15 0.54 95 0.97 160 15-16-17-19 14-15-16-18 530-565-600-670 495-530-565-635 16-17-18-20 15-16-17-19 565-600-635-705 530-565-600-670 33-35-37-40 35-37-39-41 22-24-26-28 20-22-24-26 775-850-920-990 705-775-850-920 23-25-27-29 21-23-25-27 810-885-955-1025 740-810-885-955 37-39-41-43 39-41-43-45 0 White Munsell 6.4Y 8.9/0.4 1280 [50-3/8] 1600 [63] 680 [26-3/4] 230 [9-1/16] 32 71 36 79 26 [1-1/32] Attached in Indoor Unit 25 40 0.75 75 TNB220FLHM 12 17.5 55 [1,940] Linear Expansion Valve Reverse Cycle 48 50 Ivory Munsell 3Y 7.8/1.1 950 [37-3/8] 330+30 [13 + 1-3/16] 943 [37-1/8] 75 [165] R410A 3.0 [6 lbs 10 oz] 0.87 (FV50S) [28] 15.88 [5/8] 9.52 [3/8] Max. 30m [Max. 100ft] Max. 50m [Max. 165ft] Not Supplied Flared 18 30 14 Air flow Refrigerant Control Defrost Method Sound level at cooling dB(A) Sound level at heating dB(A) External finish Dimension W : mm [inch] D : mm [inch] H : mm [inch] Weight kg [lbs] Type kg [lbs] Charge Oil L [oz] Gas side O.D. mm [inch] Liquid side O.D. mm [inch] Height difference Length Refrigerant Piping Connection Method NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) (heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) *2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Operating range Outdoor : D.B. 35(95°F), W.B. 23.9(75°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F) Indoor intake air temperature Outdoor intake air temperature Maximum D.B. 35(95°F), W.B. 21.7(71°F) D.B. 46(115°F) Minimum D.B. -18(0°F)* D.B. 19.4(67°F), W.B. 13.9(57°F) Maximum D.B. 26.7(80°F), W.B. 19.4(67°F) D.B. 21.1(70°F), W.B. 15(59°F) Heating Minimum D.B. 21.1(70°F), W.B. 15.6(60°F) D.B. -11.1(12°F), W.B. -12.2(10°F) * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.) Cooling 8 38 84 26 0.4 + 0.4 86 + 86 ANV33FDPMT 20 27.5 100 [3,530] 51 55 1350 [53-1/8] 118 [260] 4.5 [10 lbs] 1.4 (FV50S) [45] 2-4. CEILING CONCEALED TYPE Model name Cooling Heating Heating at low ambient Power supply Voltage Indoor unit indoor unit outdoor unit Max. Capacity Rated Capacity Min. Capacity Total input EER SEER Moisture Removal *1 SHF Max. Capacity Rated Capacity Min. Capacity Total input COP *1 HSPF(IV/V) Rated Capacity Total input *2 COP Phase,Cycle,Voltage Breaker size indoor - outdoor S1-S2 indoor - outdoor S2-S3 indoor - Remote controller MCA MOCP Fan Motor Fan Motor Output Air flow DRY (Lo-Mid-Hi) WET Air flow DRY (Lo-Mid-Hi) WET External pressure Sound level (Lo-Mid-Hi) External finish Dimension Unit (Panel) Weight Unit Field Drain pipe seize O.D. Remote Controller Outdoor unit MCA MOCP Fan Motor Fan Motor Output Compressor Air flow Refrigerant Control Defrost Method Sound level at cooling Sound level at heating External finish Dimension Refrigerant Refrigerant pipe size Refrigerant pipe length Weignt Type Charge Oil Gas side O.D. Liquid side O.D. Height difference Length Btu/h Btu/h Btu/h W Btu/h Btu/h Pints/h Btu/h Btu/h Btu/h W W/W Btu/h/W Btu/h W W/W PEA-A12AA PUY-A12NHA3 PUY-A12NHA3-BS 12,000 12,000 6,000 1240 9.7 13.8 2.47 0.77 - A A A F.L.A W CMM CMM CFM CFM in.WG [Pa] dB(A) PEA-A18AA PUY-A18NHA3 PUY-A18NHA3-BS 18,000 18,000 8,000 2150 8.4 14.3 3.26 0.80 1phase, 60Hz, 208/230V 15 AC208 / 230V DC24V DC12V 1 15 0.57 PEA-A18AA PUZ-A18NHA3 PUZ-A18NHA3-BS 18,000 18,000 8,000 2150 8.4 14.3 3.26 0.80 20,000 19,000 8,000 1540 3.61 10.0 / 8.0 13,000 1520 2.51 2 15 0.74 96 7-9-11 6-8-10 247-317-388 222-285-349 12-15-18 11-14-17 423-529-635 381-476-572 0.02/0.06/0.14/0.20 [5/15/35/50] 23-28-33 30-34-38 Galvanized W:mm[inch] D:mm[inch] H:mm[inch] kg lbs mm[inch] 990[39] 700[27-9/16] 200[7-7/8] 21 48 32 [1-9/32] Attached in indoor Unit 13 A A F.L.A. W 15 R.L.A. L.R.A. CMM[CFM] dB(A) dB(A) - W:mm[inch] D:mm[inch] H:mm[inch] kg[lbs] 41[90] kg[lbs,oz] L[oz] mm[inch] mm[inch] 1190[46-7/8] 700[27-9/16] 200[7-7/8] 27 60 1.3 [2lbs 14oz] Refrigerant Piping Connection Method NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7(80°F), W.B. 19.4(67°F) (heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) *2.Rating conditions(heating)-Indoor : D.B. 21.1(70°F), W.B. 15.6(60°F) Operating range 20 0.35 40 SNB130FPBM1 12 14 34 [1,200] Linear Expansion Valve 46 Ivory Munsell 3Y 7.8/1.1 800 [31-1/2] 330+23 [13+7/8] 600 [23-5/8] 44[97] R410A 1.7 [3lbs 12oz] 0.65 (MEL 56) [20] 12.7 [1/2] 6.35 [1/4] Max. 30m [Max.100ft] Max. 30m [Max.100ft] Not Supplied Flared Outdoor : D.B. 35(95°F), W.B. 23.9(75°F) Outdoor : D.B. 8.3(47°F), W.B. 6.1(43°F) Outdoor : D.B. -8.3(17°F), W.B. -9.4(15°F) Outdoor intake air temperature Indoor intake air temperature Maximum D.B. 46(115°F) D.B. 35(95°F), W.B. 21.7(71°F) Cooling Minimum D.B. -18(0°F)* D.B. 19.4(67°F), W.B. 13.9(57°F) Maximum D.B. 21.1(70°F), W.B. 15(59°F) D.B. 26.7(80°F), W.B. 19.4(67°F) Heating Minimum D.B. -11.1(12°F), W.B. -12.2(10°F) D.B. 21.1(70°F), W.B. 15.6(60°F) * In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5(23°F)DB.) 9 Reverse Cycle 47 45[99] OUTLINES AND DIMENSIONS Unit: inch (mm) 23-1/2 (597) Air intake hole ( Connected the attached flexible pipe or socket. ) (83) (36) Vane motor Air outlet hole 37-3/8 (950) 1-27/64 3-17/64 (83) Indoor unit Ceiling Grille Min.94-1/2(2400) from floor Min.19-11/16(500) Entire periphery Floor (36) 6-9/16(167) 6-3/32 (155) (:150) Burring hole pitch :4-29/32(:125) 120° 6-7/32 120° Keep 25/64(10)to 19/32(15) between unit ceiling and ceiling slab. + Cut out hole :3-15/16(:100) ++ (35) 1-3/8 Burring hole 3-:1/8(3-:2.8) Ceiling In case of standard grille In case of wireless remote controller Emergency operation switch<Cooling> Emergency operation switch<Heating> 23-1/2 (597) Air intake hole Air outlet hole 19-11/16 (500) M Corner pocket Burring hole Receiver M 19-11/16 (500) 14-:1/8 (14-:2.8) (350) Auto vane (Air outlet) Air intake grille 1-27/64 13-25/32 Detail drawing of fresh air intake hole Drain hole Drain pump clean hole and Drain emergency drainage hole M 3-15/16 (100) 5-1/8 (130) 25/32 to (7.5) 1-25/32 (20~45) Ceiling hole Branch duct hole (:175) :6-7/8 Burring hole pitch +3/16 0 (17+5 0 ) (50~70) 1-15/16~2-3/4 Ceiling Grille M 3-17/64 + + + Suspension bolt lower edge 37-3/8 (950) 24-13/32 (620) 25/32 (140) + + 7-15/32 + + 5-1/2 (170) 6-11/16 2 A (377) 14-27/32 (190) 11-3/16 Drain pipe connected to VP-25 4-1/8 (105) (284) 2-3/8 Cut out hole 6-9/64 (156) (60) 1 3-17/32 (90) Cut out hole (160) 33-1/16 (840) 3-15/16 (100) 3-15/16 (100) 3-17/32 (90) :5-29/32 6-5/16 7-3/8 (187.5) Suspension bolt M10 or W3/8 PLA-A42BA Detail connecting of branch duct(Both aspects) (7.5) C D (5/16) 3-17/32 (90) For wiring replacement kit terminal block +35 23-13/16 -3/16 +1-3/8 (605 -5 ) 15/16 (24) 6-5/16 (160) Indoor unit/Outdoor unit connecting terminal block Branch duct hole 5-29/32(150) 33-1/16(840) For MA-Remote controller terminal block Suspension bolt pitch (160) (5/16) (160) to 1-25/32 (20~45) 6-5/16 PLA-A36BA 25/32 to 1-25/32(20~45) 31-7/8(810) Suspension bolt pitch B Fresh air intake hole PLA-A30BA 33-27/32 to 35-13/16 (860~910) 25/32 to 1-25/32(20~45) 6-5/16 PLA-A24BA Ceiling hole 33-27/32 to 35-13/16(860~910) ( 158) INDOOR UNIT PLA-A12BA PLA-A18BA 11/16 3 DEFROST/STAND BY lamp Operation lamp Note1. As for drain pipe, please use VP-25(O.D.1-1/4(32mm) PVC TUBE). Drain pump is included. Max. lifting height is 70-7/18(850mm) from the ceiling. 2. As for suspension bolt, please use M10 or W3/8. (Procured at local site) 3. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection. 4. The height of the indoor unit can be adjusted with the grille attached. 5. For the installation of the optional high efficiency filter or optional multi-functional casement. 1) Add 5-5/16(135mm) to the dimensions + marked on the figure. 2) Optional high efficiency filter must be used jointly with optional multi-functional casement. 6. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.) 7. As for necessary installation/service space, please refer to the left figure. Models 1 PLA-A12BA Refrigerant pipe PLA-A18BA ····:6.35mm Flared connection ····1/4 PLA-A24BA PLA-A30BA Refrigerant pipe ····:9.52mm PLA-A36BA Flared connection PLA-A42BA ····3/8 10 2 A B C D Refrigerant pipe ····:12.7mm Flared connection 9-1/2 10-3/16 3-5/32 2-29/32 ····1/2 (241) (258) (80) (74) Refrigerant pipe ····:15.88mm Flared connection 11-1/16 11-3/4 3-11/32 3-1/32 ····5/8 (281) (298) (85) (77) PKA-A12HA PKA-A12HAL PKA-A18HA PKA-A18HAL 15-3/16(387) 7-1/2(192) Unit: inch (mm) 7-3/4(197) Top side Mount board 23-9/16(599) Front side 11-5/8(295) Right side D Left side A 27-1/16(688) 2-1/8 (55) Knockout hole for left piping 9-13/16(249) 6-1/16(155) 35-3/8(898) Front side(Grille open) Sleeve (purchased locally) :2-1/2~:3-1/8 (:65~:80) 3/16(5) Knock out hole for right piping Through hole :2-1/2~:3-1/8 (:65~:80) Terminal block for indoor/outdoor connecting line Terminal block for power supply (option) Terminal block for MA-remote controller (only PKA-A·HA models) 17-15/16(457)Gas pipe 21-3/16(539)Liquid pipe 24(610)Drain hose 6-5/8(169) 6-3/16(158) Under side Vane(auto) DEFROST/STAND BY lamp Operation lamp 24-1/16(612) 5/16(8) Emergency operation switch (cooling/heating) 7-3/16(184) Refrigerant Liquid pipe Piping Gas pipe 1/4F (:6.35) Drain hose :5/8 (:16) O.D Knock out hole for lower piping Knock out hole for lower piping Louver(manual) C 1/2F (:12.7) Receiver B Center measurement hole :3/32(:2.5) 5/32(3.8) 12-7/8(237.5) 14(356.3) 14-5/8(372.3) 4-7/8(125) Mount board 7-13/16(200) 8-13/16(225) 9-5/16(238) 10-3/8(265) 11-7/16(291.5) 2-1/4(58) 0 5/8(16) 1-1/16(28.5) 1-9/16(41) 3-1/16(78.5) 3-9/16(91) 4-1/16(103.5) 4-9/16(116) 6-1/2(166) 7(178.5) 8(203.5) 9-1/8(232.5) 9-15/16(253.5) 2-3/4(70) 0 2-3/4(70) 9/16(15) 0 9/16(15) 4-7/8(125) 8-13/16(225) 7-13/16(200) 77-:3/16(:5.1) Tapping screw hole 11-7/16(291.5) 10-3/8(265) 14-5/8(372.3) 14(356.3) 12-7/8(327.5) 4-:5/16(:9) Bolt hole Indoor unit outline 13/16(21.8) 0 3/4(20) 1-1/4(32.7) 2-1/16(53.5) 2-9/16(66) 5(128.5) 6(153.5) 11-1/16(281) 7-9/16(193.5) Knockout hole for rear piping 2-3/4×12-3/16(70×310) 4-1/2(115) 5-1/2(140) 6-9/16(167) 7-1/16(180.3) 10-15/16(278.3) 9-5/16(238) 8-3/8(213) 6-13/16(174) 15-1/2(394) Wall hole for left rear piping 17-5/8(449) 0 17-5/8(449) 9-1/16(231.5) 10-3/4(273.2) Wall hole for right rear piping Required space(Indoor unit) D 3/16(6) 1-3/4(46) Min.1/4(7) 2-5/16(59) 1-11/16(43) A 1-11/16(43) 1-11/16(43) B 2-5/16(60) 11 Min.1-31/32(50) 250mm,9-13/16inch or greater with optional drain pump installation. 2-3/16(56) C 1-11/16(43) 2-3/16(56) 1-3/4(46) 2-3/16(56) 7/16(12.5) Air inlet 3/16(6) 2-11/16(69) (mm) Air inlet Air outlet Min.1-31/32(50) Min.8-5/8 (220) Min.5-7/8(150) Min.9-13/16(250) Knockout hole for piping PKA-A24KA PKA-A36KA PKA-A24KAL PKA-A36KAL PKA-A30KA PKA-A30KAL Unit: inch (mm) 5-17/132(140.3) 2-9/16(65.2) Top side 17(431.7) 7/16(11) 16-11/16(423.7) Left side Right side Front side 14-3/8(365) Mount board Knockout hole for left piping C 2-29/32(74) 9-1/2(241) 33-21/32(855) 46-1/16(1170) A 3/16(5) 11-5/8(295) Operation lamp Front side(Grille open) Knock out hole for right piping DEFROST/STAND BY lamp Receiver 2-3/32(53) 1-1/4(32) 23/32(18) Terminal block for Outdoor unit Terminal block for power supply (option) Terminal block for MA-remote controller (only PKA-A·KA models) Emergency operation switch (cooling/heating) Filter hook 1-3/16(30) 1-3/8(35) 17-15/32(444)Gas pipe 2-19/32(66) 4-27/32(123) 18-31/32(482)Liquid pipe 23-1/32(585)Drain hose 6-1/16(154) 5-9/32(134) Under side Piping connection department Vane(auto) Louver(manual) B Liquid pipe B Knock out hole for lower piping Sleeve (purchased locally) :2-15/16 (:75) Through hole Gas pipe :2-15/16~:3-5/32 (:75~:80) Drain hose Refrigerant pipe: 3/8 O.D(:9.52) Flared connection: 3/8F Refrigerant pipe: 5/8 O.D(:15.88) Flared connection: 5/8F 5/8(:16) O.D Required space(Indoor unit) Min.2-27/32(72.4) 13/32(10.7) 2-1/8(54) 1/8(3) 0 5/8(15.5) 31/32(25) 1-31/32(50) 2-15/16(75) 3-15/16(100) 4-19/32(117) 4-29/32(125) 5-19/32(142) 7-9/16(192) 9-17/32(242) 12-3/8(314) 14-11/32(364) 15-1/8(384.5) 16-3/32(408.5) 17-9/32(439) 17-7/8(454) 18-5/16(465.5) 4-11/32(110) 2-3/8(60) 13/32(10) 0 13/32(10) 2-3/8(60) 4-11/32(110) 12-3/8(314) 17-7/8(454) 17-9/32(439) 16-3/32(408.5) 15-1/8(384) 14-11/32(364) 20-3/8(517.4) 4-:11/32(:9) Bolt hole Mount board Indoor unit outline 2-1/8(54) 1-1/4(32) 31/32(25) 1/2(12.5) 0 1/2(12.5) 1-15/32(37.5) 2-15/32(62.5) 3-7/16(87.5) 4-1/8(104.5) 5-3/32(129.5) 0 6-9/16(167) 8-17/32(217) 9-1/32(229.5) 10-13/32(264) 11-1/2(292) 11(279.5) 11-1/2(292) Wall hole for right rear piping 12 23-1/32(585) 17-11/16(449.2) 13-11/32(339) 13-3/4(349.2) 15-1/8(384) 8-17/32(216.5) 0 7-7/16(189) 15-1/8(384) 13-11/32(339) 16-15/16(430.5) Knockout hole for rear piping 2-15/16×18-29/32(75×480) 37.5) /32(R R1-15 23-1/32(585) 12-5/32(308.5) 12-1/4(311) Wall hole for left rear piping 3-1/32(77) 2-5/8(67) 3-1/32(77) 3-7/16(87) 2-9/16(65) Center measurement hole :3/32(:2.5) 75-:3/16(:5.1) Tapping screw hole B A 5/16(7.8) 2-9/16(65) 2-5/8(67) 3-1/32(77) C 5/16(7.8) Min.9-27/32(250) Min.2(50.5) Min.1-7/8(48) Knockout hole for piping Air outlet Min.8-21/32(220) 20-7/8(530.5) Min.9/32(7) Air inlet 2-9/16(65) 7-1/2(190) 1-13/16(46) 1 2 3 4 5 6 7 8 3(76) 4-7/8(124) 5/16(8) 2 8 120° 7 15-1/4(387) 1-1/2(38) 11/16(18) 10-1/4(260) 3-3/8(85) 1-7/8(48) 9-11/16(246) 9-3/16(233) 1/16(2) 1/16(1) Air intake 5-7/16(138) When drain socket is installed Drainage 4 3-3/8(86) In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece. Then put the independent piece back in initial position.(The heat exchanger might be clogged because of dust) 18-1/8(461) 4-3/4(121) Drainage pipe connection(1(26mm)I.D.) Drainage pipe connection(for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection(gas pipe side/flared connection) Refrigerant-pipe connection(liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for fresh air intake Φ3-15/16(Φ100) Knockout hole for wiring arrangement Φ7/8(Φ22) Accessory...Drain socket (1(26mm) I.D.) Electrical box When electrical box is pulled down 2 Ceiling Φ 2-15/16(75) 3 12 5) 4-1 5/1 6(Φ 4-15/16(126) 1-7/16(37) 1 7-1/12(190) 1/16(2) Air outlet 47-3/16(1198) 46-3/16(1173) 50-3/8(1280) 48-11/16(1237) (Suspension bolt pitch) 5-7/8(150) Electrical box 5 7-3/16(182) 5-1/2(140) 2-7/16(62) 1/16(2) 12-5/8(320) 3-3/8(85) 3-5/16(84) 10(254) [FRONT VIEW] 3-1/8(80) 3-7/16(88) 2-1/4(57) 26-3/4(680) 7-11/16(195) 26-3/4(680) 13 18-3/4(476) 6 2(51) 9/16 14 DEFROST/STAND BY lamp Receiver Operation lamp Emergency operation switch <Heating> When drain socket is installed Drainage 9-3/16(233) liquid Φ3/8(Φ9.52) gas Φ5/8(Φ15.88) 9-11/16(246) 7-7/8(200) NOTES. 1.Use M10 or W3/8 screw for anchor bolt. 2.Please be sure when installing the drain lift up mechanism(option parts),refrigerant pipe will be only upward. i-see sensor Emergency operation switch <Cooling> 9-5/16(236) 7-1/16(180) In case of wireless remote controller and i-see sensor(Optional Parts) In case of wireless remote controller and i-see sensor (Optional Parts) 3/16(5) 3/8(10) PCA-A24KA PCA-A30KA Unit: inch (mm) 9-1/16(230) 11/16(18) 2 3 7-1/2(190) 1-13/16(46) Ceiling 18-1/8(461) 4-3/4(121) 3(76) 4-7/8(124) 8 120° 5 7 15-1/4(387) 1-1/2(38) 11/16(18) 10-1/4(260) 3-3/8(85) 5-7/16(138) 1/16(2) 3-3/8(86) 6 7 8 5 1 2 3 4 1-7/8(48) 9-11/16(246) 9-3/16(233) 1/16(1) Drainage When drain socket is installed Electrical box 1/16(2) 7-1/2(190) Drainage pipe connection(1(26mm)I.D.) Drainage pipe connection(for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement Knockout hole for fresh air intake Φ3-15/16(Φ100) Knockout hole for wiring arrangement Φ7/8(Φ22) Accessory...Drain socket (1(26mm)I.D.) 2 5/16(8) Air outlet 59-3/4(1518) 58-3/4(1493) 63(1600) 61-5/16(1557) (Suspension bolt pitch) 11/16(18) 5-7/8(150) 4 In case of the rear pipe arrangement, make sure to remove the shaded portions from the independent piece. Then put the independent piece back in initial position.(The heat exchanger might be clogged because of dust) When electrical box is pulled down 2-15/16(75) Electrical box 12 5) Φ4 -15 /16 (Φ 4-15/16(126) 1-7/16(37) 7-3/16 182 5-1/2 140 NOTES. 1.Use M10 or W3/8 screw for anchor bolt. 2.Please be sure when installing the drain lift up mechanism (option parts),refrigerant pipe will be only upward. 62 2-7/16 6 1/16(2) 3-3/8 85 3-5/16(84) Air intake 10(254) 1 3-1/8 80 12-5/8(320) 3-7/16(88) 18-3/4(476) [FRONT VIEW] 2(51) 9/16 14 liquid Φ3/8(Φ9.52) gas Φ5/8(Φ15.88) When drain socket is installed Drainage 9-3/16(233) 9-11/16(246) 7-7/8(200) 7-1/16(180) 9-5/16(236) Emergency operation switch <Heating> DEFROST/STAND BY lamp Receiver Operation lamp Emergency operation switch <Cooling> In case of wireless remote controller and i-see sensor(Optional Parts) In case of wireless remote controller and i-see sensor (Optional Parts) 3/16(5) 3/8(10) 9-1/16(230) 26-3/4(680) 7-11/16(195) 2-1/4 57 14 26-3/4(680) PCA-A36KA PCA-A42KA Unit: inch (mm) PEA-A18AA Unit: mm (inch) Drain pipe(O.D.ø32(1-1/4)) (Emergency draining) 159(6-9/32) 345(13-19/32) Suspension bolt hole 4-14X30(9/16X1-3/16) Slot (24-5/8) 100 (3-15/16) 150(Duct) (5-29/32) 23(29/32) 25(1) Drain pipe(O.D.ø32(1-1/4)) 700(27-9/16) 677(26-21/32) 23 (29/32) 10 (13/32) Control box 116 (4-19/32) 2X2-ø2.9(1/8) Refrigerant piping flare connection (gas) 70 (2-25/32) 270(10-21/32) 88(3-15/32) 20(13/16) 23(29/32) 57(2-1/4) (1-15/16) 102(4-1/32) 170(6-23/32) 90 (3-9/16) 200(7-7/8) 25 (1) 20(13/16) 30(1-3/16) 10 (13/32) 625 (Suspension bolt pitch) 49 Air filter 12(1/2) A Air inlet Air outlet N B (Suspension bolt pitch) C M L-ø2.9(1/8) 57(2-1/4) D (Duct) 100(3-15/16)X(E-1)=F 100(3-15/16) 2XE-ø2.9(1/8) 20 (13/16) 12(1/2) 37(1-15/32) 100 (3-15/16) 157.5 (6-7/32) 37(1-15/32) H 100(3-15/16)XJ=K 100(3-15/16) 15(19/32) 88(3-15/32) PEA-A12AA Knockout hole ø27(1-3/32) (Indoor/outdoor connecting line) Knockout hole ø27(1-3/32) (Remote controller transmission line) Terminal block (Indoor/outdoor connecting line) Terminal block (Remote controller transmission line) Refrigerant piping flare connection (liquid) Drain pipe(O.D.ø32(1-1/4)) (Spontaneous draining) Note2 2) 7 77 19/3 - Access (30 50 (131 G /32 ) (131 /32 50 ~ ~ 5 150 -29 /32 ) 4 (17 50 -23 /32 ) 175p5(6-29/32p7/32) (Actual length) Less than 550 (21-21/32) ) /32 31 (150 door 0 0 45 2) /3 n 30 16) -23 tha 3/ (17 ore 11-1 ( M More than 10 (13/32) More than 20 (13/16) Less than 300 (11-13/16) Make the access door at the appointed position properly for service maintenance. Drain hose (I.D.ø32(1-1/4)) <accessory> Required space for service and maintenance mm(in.) Model PEA-A12AA PEA-A18AA A B C D E 900 952 998 860 9 (35-7/16) (37-1/2) (39-5/16) (33-7/8) 1100 1152 1198 1060 (43-5/16) (45-3/8) (47-3/16) (41-3/4) 11 F G 800 1000 H J K 860 7 (27-9/16) (31-1/2) (39-3/8) (33-7/8) 1000 1200 1060 (39-3/8) (47-1/4) (41-3/4) 9 700 900 (35-7/16) L M 1039 990 20 (40-29/32) (39) 24 1239 1190 (48-25/32) (46-7/8) Note1.Use M10 screw for the suspension bolt (field supply). 2.Keep the service space for the maintenance at the bottom. 3.This chart indicates for PEA-A12AA model,which has 2 fans. PEA-A18AA models have 4 fans. 4.In case an inlet duct is used,remove the air filter(supply with the unit), then install the filter(field supply) at suction side. * PEA-A12AA Gas pipe: Connect the joint :12.7, 1/2” (supply with the unit). 15 N 1 Gas pipe ø9.52(3/8) * ø12.7(1/2) Ceiling surface Access door 2 Liquid pipe ø6.35(1/4) OUTDOOR UNIT PUY-A12NHA3(-BS) Unit: mm (inch) PUY-A18NHA3(-BS) PUZ-A18NHA3(-BS) 347.5<13-11/16> W33<1-5/16> drain hole 45.4<1-25/32> 4-oval hole Air discharge 40<1-9/16> 18<23/32> 330<13> Air intake 365<14-3/8> 300<11-13/16> 152<6> 155 Air intake 32.5<1-9/32> 43.6<1-23/32> 400<15-25/32> 23<29/32> 22<7/8> Service panel Service panel for charge plug Connection for liquid pipe FLARE W6.35<1/4> 90<3-17/32> 38<1-1/2> 241<9-1/2> 10<3/8> 300<11-13/16> 600<23-5/8> Handle 155<6-3/32> 2-W22.2<7/8> 1/2 conduit hole Connection for gas pipe 144<5-21/32> FLARE W12.7<1/2> 183<7-7/32> Service port 150<5-29/32> 287.5<11-11/32> Installation bolt pitch 500<19-11/16> 69<2-23/32> 800<31-1/2> FOUNDATION BOLTS Basically open Free space around the outdoor unit (basic example) Please secure the unit firmly with 4 foundation M10<W3/8> bolts. (Bolts, washers and nut must be purchased locally.) Min.100mm<3-15/16> as long as no obstacle is placed on the rear and light-and-left sides of the unit Min.100mm<3-15/16> Max. 18mm<23/32> <Foundation bolt height> Min.350mm<13-25/32> *1 *2 *1 Min.500mm<19-11/16> FOUNDATION PIPING-WIRING DIRECTION Min.100mm<3-15/16> Piping and wiring connection can be made from the rear direction only. 2 sides should be open in the right, left and rear side. Minimum installation space for outdoor unit *1 In the place where short cycle tends to occur, cooling and heating capacity and power consumption might get lowered 10%. Air outlet guide (optional PAC-SG58SG-E) will help them improve. *2 If air discharges to the wall, the surface might get stained. 16 Min. 100mm <3-15/16> Service space Front piping hole (Knockout) Front trunking hole (Knockout) 45 <1-25/32> 19<3/4> 75 <2-31/32> Right piping hole (Knockout) 92<3-5/8> 55<2-3/16> :92<3 -5/8> 40<1-9/16> 45<1-25/32> Conduit hole (2-:27<1-1/16>Knockout) Right trunking hole (Knockout) Min. 500mm <19-11/16> 65<2-9/16> 95<3-5/8> 40<1-9/16> Rear piping hole (Knockout) :92<3 -5/8> Rear trunking hole (Knockout) Conduit hole (2-:27<1-1/16>Knockout) 40<1-9/16> 2-:22.2<7/8> 74<2-19/32> 1/2 Conduit attachment When installing the conduit, Set the attachment to the inner side of each panel. Handle Side Air Intake Handle Rear Air Intake FOUNDATION Handle 30 <1-3/16> 220 145 145 145 <8-21/32> <5-23/32> <5-23/32> <5-23/32> Earth terminal 2-U Shaped notched hole (Foundfation Bolt M10<W3/8>) 66 <2-5/8> 175 <6-7/8> 417 <16-13/32> 2 1 Handle Service panel Terminal Block Left···Power supply wiring Reight···Indoor/Outdoor wiring 2-12%36 Oval hole (Foundation Bolt M10<W3/8>) 42 <1-21/32> Drain hole (5-:33<1-5/16>) 71 <2-13/16> Air Discharge 600 <23-5/8> 950 <37-13/32> 322 <12-11/16> 175 <6-7/8> Rear Air Intake Bottom piping hole (Knockout) Rear piping cover Front piping cover PUY-A24NHA3(-BS) PUY-A30NHA3(-BS) PUY-A36NHA3(-BS) 65<2-9/16> 92<3-5/8> :92 > <3-5/8 40 <1-9/16> Conduit hole (2-:27<1-1/16>Knockout) Piping Knockout Hole Details Air Intake Handle ····Refrigerant GAS pipe connction (FLARE):15.88<5/8> ····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8> *1 ····Indication of STOP VALVE connection location. Example of Notes Min. 500mm <19-11/16> Min. 10mm <3/8> <Foundation bolt height> Side Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. 23<29/32> FREE Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.) 73<2-7/8> 63<2-1/2> Min. 10mm <3/8> 55<2-3/16> 27<1-1/16> Min. 500mm <191/16> 55<2-3/16> 27<1-1/16> Min. 10mm <3/8> 63<2-1/2> 73<2-7/8> 23<29/32> 4 PIPING-WIRING DIRECTIONS Max. 300mm<1-3/16> Min. 100mm <3-15/16> 3 FOUNDATION BOLTS 943 <37-1/8> 330 <13> 30 <1-3/16> 23<29/32> The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc. 27<1-1/16> 92<3-5/8> 63<2-1/2> 73<2-7/8> 23<29/32> 71 <2-13/16> Dimensions of space needed for service access are shown in the below diagram. *1 443<17-7/16> 1 FREE SPACE (Around the unit) 2 SERVICE SPACE 31<1-7/32> 473 <18-5/8> 219 <8-5/8> 45 <1-25/32> *1 447<17-19/32> 17 81<3-3/16> 56 <2-7/32> 53 <2-3/32> 19 <3/4> 370 <14-9/16> 28 <1-3/32> 670 <26-3/8> PUZ-A24NHA3(-BS) PUZ-A30NHA3(-BS) PUZ-A36NHA3(-BS) Unit: mm (inch) Min. 150mm <5-29/32> Min. 10mm <3/8> Service space Min. 10mm<3/8> Min. 500mm <19-11/16> :92 8> <3-5/ 92<3-5/8> 65<2-9/16> Front piping hole (Knockout) 45<1-25/32> 55<2-3/16> 63 27<1-1/16> Front trunking hole 40<1-9/16> (Knockout) Conduit hole (2-:27<1-1/16>Knockout) Piping Knockout Hole Details <2-1/2> 73<2-7/8> 23<29/32> Handle 19<3/4> :92 92<3-5/8> 55<2-3/16> > <3-5/8 45<1-25/32> 92<3-5/8> 65<2-9/16> 40<1-9/16> 74<2-19/32> Rear piping hole (Knockout) : <3-592 /8> Handle 1/2 Conduit attachment When installing the conduit. Set the attachment to the inner side of each panel. Handle Handle Side Air Intake Rear Air Intake Side Air Intake Piping and wiring connections can be made from 4 directions: front, right, rear and below. Conduit hole (2-:27<1-1/16>Knockout) 2-:22.2<7/8> Rear trunking hole (Knockout) 40<1-9/16> Right trunking hole (Knockout) FOUNDATION <Foundation bolt height> Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts and washers must be purchased locally.) Conduit hole (2-:27<1-1/16>Knockout) 75 <2-31/32> 40<1-9/16> Right piping hole (Knockout) Air intake *1 ····Indication of STOP VALVE connection location. ····Refrigerant GAS pipe connction (FLARE):15.88<5/8> ····Refrigerant LIQUID pipe connection (FLARE): 9.52<3/8> Example of Notes Min. 1000mm <39-3/8> Min. 10mm <3/8> FREE 27<1-1/16> 92<3-5/8> 63<2-1/2> 73<2-7/8> Min. 30mm <1-3/16> Min. 150mm <5-29/32> Min. 500mm <19-11/16> 73<2-7/8> 63<2-1/2> 23<29/32> 1350<53-5/32> Rear Air Intake 30<1-3/16> 66<2-5/8> 42<1-21/32> 175<6-7/8> 2-U Shaped notched hole (Foundation Bolt M10<W3/8>) 950<37-13/32> 220 145 145 145 <8-21/32> <5-23/32> <5-23/32> <5-23/32> Drain hole 5-:33<1-5/16> 71<2-13/16> 2 1 Handle Service panel Terminal Block Left···Power supply wiring Right····Indoor/Outdoor wiring 2-12%36 Oval hole (Foundation Bolt M10<W3/8>) 600<23-5/8> 322<12-11/16>Earth terminal Air Discharge 175<6-7/8> 330<13> 30<1-3/16> 23<29/32> 3 FOUNDATION BOLTS 4 PIPING-WIRING DIRECTIONS * 1 443<17-7/16> Dimensions of space needed for service access are shown in the below diagram. 31<1-7/32> 28<1-3/32> Bottom piping hole (Knockout) Rear piping cover Front piping cover 1076<42-3/8> The diagram below shows a basic example. Explantion of particular details are given in the installation manuals etc. 55<2-3/16> 27<1-1/16> 635<25> 371<14-19/32> 81<3-3/16> 219<8-5/8> 19<3/4> 45<1-25/32> 56<2-7/32> 370<14-9/16> 417<16-13/32> 53<2-3/32> * 1 447<17-19/32> 1 FREE SPACE (Around the unit) 2 SERVICE SPACE 71<2-13/16> 18 23<29/32> PUZ-A42NHA3(-BS) PUY-A42NHA3(-BS) Unit: mm (inch) Unit: mm (inch) WIRED REMOTE CONTROLLER 48.5<1-15/16> 120<4-3/4> 130<5-1/8> 19 <3/4> 19 Unit: mm (inch) WIRELESS REMOTE CONTROLLER 58<2-9/32> CHECK TEST MODEL RUN SELECT FAN SWING °F °C STOP AMPM START AMPM NOT AVAILABLE 159.3<6-3/8> COOL DRY AUTO FAN HEAT 19<3/4> 55<2-5/32> 20 4 WIRING DIAGRAM PLA-A12BA [LEGEND] SYMBOL I.B CN2L CN24 CN30 CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 ZNR01,02 DP FS PLA-A18BA PLA-A24BA NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR<BACK-UP HEATING> CONNECTOR<LLC> CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1. SWITCH (CAPACITY CODE) +See table 2. CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN PUMP) VARISTOR DRAIN-UP MACHINE DRAIN FLOAT SWITCH PLA-A30BA SYMBOL MF MV TB4 TB5,TB6 PLA-A36BA PLA-A42BA NAME FAN MOTOR VANE MOTOR TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (32˚F/ 15kΩ, 77˚F / 5.4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (32˚F/ 15kΩ, 77˚F/ 5.4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (32˚F/ 15kΩ, 77˚F/ 5.4kΩ DETECT) TH1 TH2 TH5 OPTION PART W.B BZ LED1 LED2 RU SW1 SW2 PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) TB5 2 1 TRANSMISSION WIRES DC12V 2 1 TB6 Refer to tables 1 and 2. R.B I.B VANE CNV(WHT) 20 18 16 14 12 10 8 6 4 2 SW1 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 Pair No. CN32 (WHT) 1 CN51(WHT) 5 CN2L LED3 LED2 LED1 4 SWE DSA INDOOR/OUTDOOR COMMUNICATION CN3C (BLU) 12 REMOCON CN22 1 (BLK) 1 3 2 1 1 CN41(WHT) 2 1 OUTDOOR 1 3 5 CN01 3 CN24(YLW) FUSE ZNR02 U DC280V U ZNR01 RECTIFICATION (BLU) ON OFF 1 3 CN3G (BLK) 1 WIRELESS CN90 (WHT) 9 I-SEE SENSOR CN4Y 1 (WHT) 4 I-SEE SENSOR MOTOR CN6Y 1 (RED) 6 CNAC (WHT) 3 1 FLOAT SW LIQUID/PIPE INTAKE CN4F CN44 CN20 CN30 (WHT) (WHT) (RED) (GRN) 1 4 1 4 1 2 1 3 7 FAN CNMF (WHT) 4 X1 1 3 1 D.U.M CNP (BLU) 5 5 5 5 M M M M MV MV MV MV GRILLE CNB BZ LED2 SW1 LED1 SW2 ON OFF I-SEE SENSOR FS M t˚ t˚ TH2 TH5 t˚ TH1 MS 3~ MF TB4 YLW S1 ORN S2 S3 +1 TO OUTDOOR UNIT ORN BRN M 1~ DP +Be sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in fan motor.) MT I-SEE SENSOR CORNER PANEL (OPTIONAL PART) RU W.B <Table 1>SW1(MODEL SELECTION) SW1 Service 1 2 3 4 5 5 4 9 YLW ORN <Table 2>SW2(CAPACITY CODE) SW2 MODELS Service MODELS PLA-A12BA PLA-A18BA PLA-A24BA 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON PLA-A30BA OFF ON PLA-A36BA OFF ON PLA-A42BA OFF Service 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON OFF ON OFF ON OFF Notes: 1. SymboIs used in wiring diagram above are, : Connector, : Terminal block. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wiring. 3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. +1.Use copper supply wires. [Self-diagnosis] 1.For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc. 2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis, and Check Codes generated in the past appear on the display. 21 PKA-A12HA PKA-A18HA PKA-A12HAL PKA-A18HAL [Explanation of symbols] Symbol I.B CN2L CN30 CN32 CN41 CN51 CN90 CN152 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE ZNR01,02 R.B TB6 Symbol Name M Indoor controller board MS Connector (LOSSNAY) S.W Connector (LLC) Connector ( Remote switch) SWE2 Connector (HA terminal-A) TB2 Connector (Centrally control) TB4 Connector (Remote operation adapter) TB5 Connector (Back-up heating) TH1 Surge absorber FUSE(T3.15AL250V) TH2 Power supply (I.B) Power supply (R.B) TH5 Transmission (Indoor-outdoor) W.B Switch (Model selection) +See table 1 LED1 Switch (Capacity code) +See table 2 LED2 Connector (Emergency operation) Varistor REC1 Wired remote controller Terminal block (Remote controller transmission line) Name Vane motor Fan motor Switch board Emergency operation Terminal block(Indoor unit Power (option)) Terminal block (Indoor/outdoor connecting line) Terminal block (Remote controller transmission line) Room temp. Thermistor (32°F/15ΚΩ, 77°F/5.4ΚΩ Detect) Pipe temp. Thermistor/liquid (32°F/15ΚΩ, 77°F/5.4ΚΩ Detect) Cond./eva. temp. Thermistor (32°F/15ΚΩ, 77°F/5.4ΚΩ Detect) Pcb for wireless remote controller LED (Operation indication: Green) LED (Preparation for heating: Orange) Receiving unit MS 3~ <Table 1> SW1 (MODEL SELECTION) I.B CNMF 6 (WHT) FUSE 1 T11 DB1 ZNR01 U SWE ON OFF LED2 Refer to tables 1and 2 1 2 CN2L (RED) 1 1 CN151 (WHT) 5 1 X1 9 CN90 (WHT) CN41 (WHT) 4 BLK 1 CN32 3 (WHT) 1 CN51 (WHT) 1 CN30 3 (BLK) CN44 CN4F (WHT) (WHT) 1 4 1 4 5 MODELS 3 1 CNP(BLU) CN3C 3 (BLU) 1 ORN BRN CNRU (WHT) 2 1 2 3 4 5 A18 W.B 6 RU LD101(B) REC1 LED1 ON OFF ON OFF R.B BLU CN22 1 (BLU) 2 SETTING 1 2 3 4 5 A12 S.W LDSWE(B) SWE2 LDSWE(A) (BLU) ON OFF <Table 2> SW2(CAPACITY CODE) 10 CN152 (WHT) CN20 (RED) 1 2 1 2 3 4 5 DSA LED3 1 SETTING TB4 <+3> YLW TO S1 ORN OUTDOOR S2 UNIT S3 YLW ORN CN01 (BLK) ZNR02 U LED1 1 3 5 BLU LED2 1 2 TB6 1 2 TB5 For PKA-A.HA M t ○ t ○ TH1 +1(Fig. 1) CN01 I.B (BLK) YLW 1 ORN 3 5 t TH2 TH5 ○ Notes: 1.SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)for correct wirings. 3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal. +1: If indoor and outdoor units have separate power supplies, refer to Fig 1. +2: For power supply system of this unit, refer to the caution label located near this diagram. +3: Use copper supply wires. 22 I.B RED BLU GRN/YLW YLW ORN ORN BRN TB2 L1 L2 GR POWER SUPPLY 208/230V 60Hz TB4 S1 S2 S3 INDOOR/OUTDOOR 1 3 COMMUNICATION CN3C(BLU) TO OUTDOOR UNIT PKA-A24KA PKA-A24KAL PKA-A30KA PKA-A30KAL Notes: 1.SymboIs used in wiring diagram above are, : Connector, : Terminal (block). 2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)for correct wirings. 3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring diagram for servicing. 4.This diagram shows the wiring of indoor and outdoor connecting wires.(specification of 230V), adopting superimposed system for power and signal. +1: If indoor and outdoor units have separate power supplies, refer to Fig 1. +2: For power supply system of this unit, refer to the caution label located near this diagram. +3: Use copper supply wires. 23 PKA-A36KA PKA-A36KAL PCA-A24KA PCA-A30KA PCA-A36KA PCA-A42KA [LEGEND] SYMBOL I.B CN2L CN24 CN30 CN32 CN41 CN51 DSA FUSE LED1 LED2 LED3 SW1 SW2 SWE X1 ZNR01,02 R.B MF MV NAME INDOOR CONTROLLER BOARD CONNECTOR (LOSSNAY) CONNECTOR (BACK-UP HEATING) CONNECTOR (LLC) CONNECTOR (REMOTE SWITCH) CONNECTOR (HA TERMINAL-A) CONNECTOR (CENTRALLY CONTROL) SURGE ABSORBER FUSE (T6.3AL250V) POWER SUPPLY (I.B) POWER SUPPLY (R.B) TRANSMISSION (INDOOR-OUTDOOR) SWITCH (MODEL SELECTION) +See table 1 SWITCH (CAPACITY CODE) +See table 2 CONNECTOR (EMERGENCY OPERATION) RELAY (DRAIN LIFT UP MECHANISM) VARISTOR WIRED REMOTE CONTROLLER BOARD FAN MOTOR VANE MOTOR SYMBOL TB4 TB5,TB6 TH1 TH2 TH5 OPTIONAL PARTS W.B BZ LED1 LED2 RU SW1 SW2 DP FS NAME TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) ROOM TEMP. THERMISTOR (32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT) PIPE TEMP. THERMISTOR/LIQUID (32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT) COND. / EVA. TEMP. THERMISTOR (32ºF / 15kΩ, 77ºF/ 5. 4kΩ DETECT) PCB FOR WIRELESS REMOTE CONTROLLER BUZZER LED (OPERATION INDICATION : GREEN) LED (PREPARATION FOR HEATING : ORANGE) RECEIVING UNIT EMERGENCY OPERATION (HEAT / DOWN) EMERGENCY OPERATION (COOL / UP) DRAIN LIFT UP MECHANISM DRAIN FLOAT SWITCH <Table 1>SW1(MODEL SELECTION) SW1 Service Refer to tables 1 and 2 TB5 2 1 TRANSMISSION WIRES DC12V 2 1 TB6 VANE CNV(WHT) SW1 20 18 16 14 12 10 8 6 4 2 CN32 (WHT) 1 J41 J42 SW2 19 17 15 13 11 9 7 5 3 1 Pair No. CN2L LED3 LED2 2 1 LED1 4 WIRELESS CN90 (WHT) 9 I-SEE SENSOR CN4Y (WHT) 1 4 CNB BZ SW1 M LED2 SW2 MV 1 6 2 1 I-SEE SENSOR DSA ZNR02 (BLU) ON OFF 1 LIQUID/PIPE INTAKE CN44 CN20 CN30 (WHT) (RED) (GRN) 4 4 1 2 t° t° TH2 TH5 t° TH1 1 1 3 7 FAN CNMF (WHT) 4 MS MT I-SEE SENSOR (OPTIONAL PARTS) LED1 RU ZNR01 DC294~325V RECTIFICATION (BLU) FLOAT SW CN4F (WHT) FUSE U REMOCON CN22 1 When attaching When attaching drain lift up drain lift up mechanism mechanism (optional parts), (optional parts) remove the jumper 1 connector CN4F FLOAT SW CN4F and fit the drain FS (WHT) float switch (FS). M U 1 2 5 4 9 I-SEE SENSOR MOTOR CN6Y (RED) (BLK) INDOOR/OUTDOOR COMMUNICATION CN3C (YLW) CN41(WHT) OUTDOOR 1 3 5 CN01 1 3 CN24 1 SWE (RED) 3 CN51(WHT) 5 5 ON OFF R.B I.B 1 1 2 3 4 5 3~ MF X1 1 D.U.M 1 3 CNP (BLU) YLW ORN PCA-A24KA PCA-A30KA 1 2 3 4 5 1 2 3 4 5 ON PCA-A36KA OFF ON PCA-A42KA OFF 1 2 3 4 5 M DP (OPTIONAL PARTS) +Be sure to turn off the source power and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor) 4 ON OFF ON OFF Notes: 1.SymboIs used in wiring diagram above are, : Connector, : Terminal block. 2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3) for correct wirings. 3.Since the outdoor side electric wiring may change, be sure to check the outdoor unit electric wiring for servicing. +1: Use copper supply wire. TO OUTDOOR UNIT 1~ Service 1 2 3 4 5 +1 ORN BRN W.B (OPTIONAL PARTS) <Table 2>SW2(CAPACITY CODE) SW2 MODELS Service MODELS TB4 YLW S1 ORN S2 S3 [Self-diagnosis] 1.For details on how to operate self-diagnosis with the wireless remote control,refer to the technical manuals etc. 2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins selfdiagnosis, and Check Codes generated in the past appear on the display. For Check Codes and Symptoms refer to the table below. 24 PEA-A12AA PEA-A18AA INSIDE SECTION OF CONTROL BOX TO MA REMOTE CONTROLLER TB15 1 2 I. B. SW1 SW2 CN2L CN24 (Yellow) CN51 1 CN32 12 CN22 (Blue) ON OFF 1 3 5 3 1 CNP (Blue) DSA CN41 SWE ZNR02 U DC310~340V Rectify circuit ZNR01 FUSE U LED2 LED3 CN90 CN01 (Black) 3 CN3C (Blue) LED1 CN4F 1234 CN44 1234 CN20 (Red) 12 CNMF 7654 X1 1 TB4 S1 S2 TO OUTDOOR UNIT S3 to FS to to TH2 TH5 M TH1 Fan motor M 1~ Drainpump SYMBOL EXPLANATION SYMBOL NAME INDOOR CONTROLLER BOARD FUSE FUSE AC250V 6.3A LED3 TRANSMISSION(INDOOR-OUTDOOR) ZNR01,02 VARISTOR SW1 SWITCH (FOR MODE SELECTION) DSA ARRESTER SW2 SWITCH (FOR CAPACITY CODE) X1 AUX. RELAY SWE CN2L CONNECTOR (LOSSNAY) TH1 INTAKE AIR TEMP. THERMISTOR CN24 CONNECTOR (BACK-UP HEATING) TH2 PIPE TEMP. THERMISTOR/LIQUID CN32 CONNECTOR (REMOTE SWITCH) TH5 COND./EVA. TEMP. THERMISTOR CN41 CONNECTOR (HA TERMINAL-A) FS CN51 CONNECTOR (CENTRALLY CONTROL) TB4 CN90 CONNECTOR (WIRELESS) LED1 POWER SUPPLY(I.B.) FLOAT SWITCH TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE) TERMINAL BLOCK (REMOTE CONTROLLER TRANSMISSION LINE) I. B. SYMBOL LED2 TB15 NAME POWER SUPPLY(I.B.) CONTROL BOX I. B. CONNECTOR (EMERGENCY OPERATION) Note1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing. 2.Indoor and outdoor connecting wires have poIarities, make sure to match terminal numbers (S1, S2, S3)for correct wirings. 3.Symbols used in wiring diagram above are, :Connector, :Terminal. 4.Use copper supply wire. 25 TB15 TB4 PARTS LOCATION SYMBOL PFC IPM CB1~CB3 N.F. LI/LO NI/NO EI,E2,E3 52C C.B. SW1 NAME Converter Power Module Main Smoothing Capacitor Noise Filter Circuit Board Connection Terminal<L1-Phase> Connection Terminal<L2-Phase> Connection Terminal<Ground> 52C Relay Controller Circuit Board Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup> SW4 SW5 SW6 SW7 SW8 5 5 6 1 1 3 1 TRANS 1 5 1 4 X51 3 X55 F1 1 2 5 F3 CNAC (WHT) 1 X52 F2 3 2 2 1 3 1 SV2 3 1 SS 21S4 3 (GRN) F4 (BLU) 21S4 RED RED WHT WHT CND (WHT) 3 1 3 1 2 1 2 CNDC (PNK) M-NET ADAPTER 2 1 CN31 CN52C (RED) CN4 (WHT) 7 14 CNM (WHT) 63H (YLW) CN2 (WHT) 3 3 CNVMNT CNMNT (WHT) (WHT) LED5 CN2M (WHT) LED1 LED2 LEV-A (WHT) SW6 1 1 2 TH3 (WHT) SW1 4 LED4 CNDM (WHT) 1 +1 CN51 (WHT) 1 2 SW12 LED3 1 CNS (WHT) LED2 +1 TH32 TH7/6 (BLK) (RED) SW11 SW1 1 t° LED1 1 MF1 MS 3~ t° When M-NET adapter is connected 5 3 C. B. t° NAME Switch LED<Operation Inspection Indicators> Fuse<T6.3AL250V> Switch<Pump Down> Connector<Emergency Operation> Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector <Connected to Optional M-NET Adapter Board> CNVMNT Connector <Connected to Optional M-NET Adapter Board> Connector <Connected for Option (Contact Input)> CNDM Connector <Connected for Option (Signal output)> CN51 X51, X52, X55 Relay M TH32 TH7 TH6 TH3 t° SYMBOL SW9 LED1,LED2 F1~F4 SWP CN31 SS CNM CNMNT LEV-A 63H CNF1 7 (WHT) PUY-A12/18NHA3-BS CN5 (WHT) NAME Terminal Block<Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Thermistor<Outdoor Pipe> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Thermistor<Shell> Electronic Expansion Valve Reactor Capacitor Power Circuit Board Connection Terminal<L1/L2-Phase> Connection Terminal<U/V/W-Phase> PUY-A12/18NHA3 SW4 SWP SW8 SW5 [LEGEND] SYMBOL TB1 MC MF1 21S4 63H TH3 TH6 TH7 TH8 TH32 LEV-A ACL CY1,CY2 P.B. TABR/S TABU/V/W PUZ-A18NHA3-BS SW9 SW7 PUZ-A18NHA3 3 A B S 1 TB7 5 M-NET 1 (WHT) PUZ only RED WHT N. F. ACL LO MS MC 3~ U PFC CN4 1 (WHT) 2 2 2 CN52C (BLK) CN5 1 (RED) 2 2 2 1 52C RED BLK P. B. WHT W V M-NET ADAPTER NO E3 IPM TABU 1 3 t° TH8 1 5 CN5 (RED) CN3 1 (WHT) 2 TABV TABW CNAC2 (RED) TABR RED TABS WHT CN2 (WHT) CB2 CB3 1 2 2 7 E2 CB1 1 +1 MODEL SELECT 1 2 3 4 5 6 7 8 +2. SW5-1 to 4 : Function switch CNAC1 (WHT) U 1 2 3 4 5 6 LI BRN ON OFF 1 2 3 4 5 6 ORN ON OFF YLW ON PUY-A18N OFF 1 2 3 4 5 6 7 8 ON OFF +2 U EI 1 2 3 4 5 6 L1 CY1 CY2 GRN ON PUY-A12N OFF 1 2 3 4 5 6 7 8 SW5-5.6 BLU ON PUZ-A18N OFF 3 SW6 RED MODEL L2 GR POWER SUPPLY 208 / 230V 60Hz S1 S2 S3 TB1 INDOOR UNIT +Use copper supply wires. 26 NI SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 NAME Terminal Block<M-net connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1s digit> Switch<Address setting : 10s digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Recelving> LED<Power Supply : DC12V> PUY-A24NHA3 NAME Converter Power Module Main Smoothing Capacitor Noise Filter Circuit Board Connection Terminal<L1-Phase> Connection Terminal<L2-Phase> Connection Terminal<Ground> 52C Relay Controller Circuit Board Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup> Switch SW4 SW5 SW6 SW7 SW8 SW9 5 5 CN2 (WHT) 3 1 TRANS 1 1 3 1 2 1 2 CNDC (PNK) 3 2 2 3 1 21S4 3 (GRN) F4 4 PUZ only 1 3 1 SV2 3 3 3 A B S 1 TB7 5 M-NET 1 1 SS (WHT) (BLU) 21S4 CND (WHT) 3 1 X51 X52 2 X55 5 F3 CNAC (WHT) 1 F1 M-NET ADAPTER 2 1 CN31 CN52C (RED) CN4 (WHT) 7 14 CNM (WHT) 1 F2 5 LED5 CN2M (WHT) LED1 3 SW7 1 CNVMNT CNMNT (WHT) (WHT) CNDM (WHT) LED2 1 6 SW6 LEV-A (WHT) LED4 SW1 1 1 2 TH3 (WHT) SW12 LED3 +1 CN51 (WHT) 4 SW4 SWP SW8 SW5 1 63H (YLW) CNS (WHT) LED2 LED1 1 2 TH32 TH7/6 (BLK) (RED) SW11 SW1 1 t° +1 CNF1 7 (WHT) 1 5 3 C. B. MF1 MS 3~ When M-NET adapter is connected M TH32 TH7 TH6 TH3 t° t° NAME LED<Operation Inspection Indicators> Fuse<T6.3AL250V> Switch<Pump Down> Connector<Emergency Operation> Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector <Connected to Optional M-NET Adapter Board> Connector CNVMNT <Connected to Optional M-NET Adapter Board> Connector <Connected for Option (Contact Input)> CNDM Connector <Connected for Option (Signal output)> CN51 X51,X52,X55 Relay LEV-A 63H t° SYMBOL LED1,LED2 F1~F4 SWP CN31 SS CNM CNMNT CN5 (WHT) SYMBOL PFC IPM CB1~CB3 N.F. LI/LO NI/NO EI,E2,E3 52C C.B. SW1 PUY-A24NHA3-BS SW9 NAME Terminal Block<Power Supply, Indoor/Outdoor> Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Solenoid Valve (Bypass Valve) Thermistor<Outdoor Pipe> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Thermistor<Shell> Electronic Expansion Valve Reactor Capacitor Power Circuit Board Connection Terminal<L1/L2-Phase> Connection Terminal<U/V/W-Phase> SV RED RED WHT WHT RED WHT N. F. ACL LO MS MC 3~ NO U PFC 2 CN4 1 (WHT) 2 2 CN3 1 (WHT) 2 TH8 2 CN52C (BLK) CN5 1 (RED) 2 2 1 52C P. B. RED W V BLK E3 IPM 1 TABV TABW 3 t° 5 1 CN5 (RED) TABR RED TABS WHT CNAC2 (RED) TABU 1 CN2 (WHT) CB2 CB3 2 2 7 E2 CB1 +1 MODEL SELECT 1 2 3 4 5 6 7 8 1 3 1 2 3 4 5 6 CNAC1 (WHT) ON OFF +2 1 2 3 4 5 6 SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 NAME Terminal Block<M-net connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1s digit> Switch<Address setting : 10s digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Recelving> LED<Power Supply : DC12V> L1 CY1 CY2 GRN M-NET ADAPTER BLU +2. SW5-1 to 4 : Function switch L2 GR S1 POWER SUPPLY 208 / 230V 60Hz S2 S3 INDOOR UNIT +Use copper supply wires. 27 U U LI BRN ON PUY-A24N OFF 1 2 3 4 5 6 7 8 SW5-5.6 ON OFF YLW SW6 ORN MODEL ON PUZ-A24N OFF RED [LEGEND] SYMBOL TB1 MC MF1 21S4 63H SV TH3 TH6 TH7 TH8 TH32 LEV-A ACL CY1,CY2 P.B. TABR/S TABU/V/W PUZ-A24NHA3-BS WHT PUZ-A24NHA3 TB1 NI EI PUZ-A30/36NHA3 [LEGEND] SYMBOL TB1 MC MF1 21S4 SV 63H TH3 TH6 TH7 TH8 TH32 LEV-A DCL CY1, CY2 ACTM PUZ-A30/36NHA3-BS NAME Terminal Block<Power Supply, Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) Solenoid Valve (Bypass Valve) High Pressure Switch Thermistor<Outdoor Pipe> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Thermistor<Shell> Electronic Expansion Valve Reactor Capacitor Active Filter Module SYMBOL P.B. TABU/V/W TABS/T TABP1/P2 TABN1/N2 DS2, DS3 IPM N.F. LI/LO NI/NO EI, E2 52C C.B. F1~F4 SW1 PUY-A30/36NHA3 NAME Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal<L1/L2-Phase> Connection Terminal<DC Voltage> Connection Terminal<DC Voltage> Diode Bridge Power Module Noise Filter Circuit Board Connection Lead<L1-Phase> Connection Lead<L2-Phase> Connection Terminal<Ground> 52C Relay Controller Circuit Board Fuse<T6.3AL250V> Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> SYMBOL SW4 SW5 SW6 SW7 SW8 SW9 SWP CN31 LED1,LED2 SS CNM CNMNT CNVMNT CNDM CN51 X51,X52,X55 PUY-A30/36NHA3-BS NAME Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup> Switch Switch<Pump Down> Connector<Emergency Operation> LED<Operation Inspection Indicators> Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector<Connected to Optional M-NET Adapter Board> Connector<Connected to Optional M-NET Adapter Board> Connector< Connected for Option (Contact Input)> Connector< Connected for Option (Signal output)> Relay When M-NET adapter is connected LEV-A 5 M TH32 TH7TH6 TH3 3 C. B. t° 1 TRANS CN52C (RED) 12 SW6 SW1 LED1 LED2 2 3 X51 4 1 21S4 3 (GRN) 1 SV2 3 (BLU) 1 SS (WHT) 21S4 CND (WHT) 3 1 3 X55 3 F4 2 1 CN31 7 F3 CNAC (WHT) 1 2 F1 14 CNM (WHT) 2 F2 1 1 CN4 (WHT) 12 7 CNDC (PNK) CNS (WHT) 3 1 3 1 5 CNVMNT CNMNT (WHT) (WHT) X52 1 CN2 (WHT) 6 +1 CN51 CNDM (WHT) (WHT) 1 5 1 3 3 LEV-A (WHT) SW4SWPSW8 SW5 1 1 3 63H (YLW) 2 LED2 SW12 LED3 LED4 M-NET ADAPTER t° 12 1 4 12 TH32 TH7/6 TH3 (BLK) (RED) (WHT) SW11 SW1 1 LED5 CN2M (WHT) LED1 t° +1 CNF1 7 (WHT) 1 5 5 SW9 SW7 t° MF1 MS 3~ CN5 (WHT) 63H A B S TB7 M-NET SV BLU WHT PUZ only 2 CN52C (BLK) 1 CNAF (WHT) ON PUZ-A36N OFF ON PUY-A30N OFF ON PUY-A36N OFF 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 TABN1 BLK ON OFF ON OFF ON OFF 1 2 3 4 5 6 RED BLK P N1 N2 6 RED CNAC2 (RED) L1 L2 GR S1 S2 CN5 (RED) BRN 1 ORN L2 YLW WHT L1 S3 WHT Io 1 2 3 4 5 6 ACTM INDOOR UNIT 1 2 3 4 5 6 POWER SUPPLY 208 / 230V 60Hz 1 2 3 4 5 6 +Use copper supply wires. +2. SW5-1 to 4 : Function switch M-NET ADAPTER SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 U 4 BLK +2 GRN ON OFF CNAC1 (WHT) LI BLU ON PUZ-A30N OFF 1 V W MS 3~ MC DCL SW5-5.6 1 2 +1 MODEL SELECT SW6 E2 U 3 U MODEL 3 1 RED TABP TABS WHT TABP1 RED TABP2 RED TABN DS2 WHT TABN2 2 TABT BLU TABW 2 7 1 CN3 2(WHT) 1 CN5 2 (RED) 1 CN4 2(WHT) RED TABU WHT TABV BLK TH8 DS3 3 IPM CN2 (WHT) t° CNDC (PNK) 2 1 6 1 7 2 1 P. B. 4 N. F. NO 52C LO NAME Terminal Block<M-net connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1s digit> Switch<Address setting : 10s digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Recelving> LED<Power Supply : DC12V> 28 CY1 CY2 TB1 NI U EI 2 PUZ-A42NHA3 [LEGEND] SYMBOL TB1 MC MF1,MF2 21S4 63H 63L TH3 TH4 TH6 TH7 TH8 LEV-A DCL CY1, CY2 ACTM CB PUZ-A42NHA3-BS NAME Terminal Block<Power Supply, Indoor/Outdoor > Motor for Compressor Fan Motor Solenoid Valve (Four-Way Valve) High Pressure Switch Low Pressure Switch Thermistor<Outdoor Pipe> Thermistor<Discharge> Thermistor<Outdoor 2-Phase Pipe> Thermistor<Outdoor> Thermistor<Heatsink> Electronic Expansion Valve Reactor Capacitor Active Filter Module Main Smoothing Capacitor PUY-A42NHA3 SYMBOL P.B. TABU/V/W TABS/T TABP1/P2/P TABN1/N2/N DS2, DS3 IPM N.F. LI/LO NI/NO EI, E2 52C C.B. F1~F4 SW1 PUY-A42NHA3-BS NAME Power Circuit Board Connection Terminal<U/V/W-Phase> Connection Terminal<L1/L2-Phase> Connection Terminal<DC Voltage> Connection Terminal<DC Voltage> Diode Bridge Power Module Noise Filter Circuit Board Connection Lead<L1-Phase> Connection Lead<L2-Phase> Connection Terminal<Ground> 52C Relay Controller Circuit Board Fuse<T6.3AL250V> Switch<Forced Defrost, Defect History Record Reset, Refrigerant Address> SYMBOL SW4 SW5 SW6 SW7 SW8 SW9 SWP CN31 LED1,LED2 SS CNM CNMNT CNVMNT CNDM CN51 X51,X52 NAME Switch<Test Operation> Switch<Function Switch> Switch<Model Select> Switch<Function Setup> Switch<Function Setup> Switch Switch<Pump Down> Connector<Emergency Operation> LED<Operation Inspection Indicators> Connector<Connection for Option> Connector<A-Control Service Inspection Kit> Connector<Connected to Optional M-NET Adapter Board> Connector<Connected to Optional M-NET Adapter Board> Connector< Connected for Option (Contact Input)> Connector< Connected for Option (Signal output)> Relay When M-NET adapter is connected 63H LEV-A 5 M 3 C. B. 1 CNDC (PNK) 14 CNM (WHT) SW6 5 1 3 1 CNVMNT CNMNT (WHT) (WHT) 6 2 2 3 1 F3 CNAC (WHT) 1 2 F1 3 X52 F2 3 F4 4 CND (WHT) 3 1 3 A B S TB7 M-NET X51 7 CNS (WHT) 2 1 CN31 CN52C (RED) 12 CN4 (WHT) 12 CN2 1 (WHT) 7 TRANS LEV-A (WHT) LED5 CN2M (WHT) LED1 1 3 63H (YLW) 1 3 63L (RED) 2 1 1 SW1 CNF2 7 (WHT) 3 LED2 SW12 LED3 LED4 M-NET ADAPTER +1 CN51 CNDM (WHT) (WHT) 1 5 1 3 1 4 12 21 TH7/6 TH3 TH4 (RED) (WHT)(WHT) SW11 SW1 1 t° SW4SWPSW8 SW5 1 t° LED1 MF2 MS 3~ t° +1 CNF1 7 (WHT) LED2 1 5 5 SW9 SW7 t° MF1 MS 3~ CN5 (WHT) 63L TH7TH6 TH3 TH4 1 21S4 (GRN) 3 1 SS (WHT) 21S4 BLU WHT +2 PUZ only 1 CN52C (BLK) 1 CNAF (WHT) TABN1 ON PUY-A42N OFF 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 BLK ON OFF 1 2 3 4 5 6 RED BLK 6 CN5 (RED) CNAC1 (WHT) L1 YLW GRN L2 GR S1 S2 S3 RED WHT INDOOR UNIT ACTM POWER SUPPLY 208 / 230V 60Hz M-NET ADAPTER SYMBOL TB7 CN5 CND CN2M SW1 SW11 SW12 LED1 LED2 LED3 LED4 LED5 P N1 N2 Io 1 2 3 4 5 6 +2. SW5-1 to 4 : Function switch 1 BRN L2 ORN L1 BLU WHT +2 RED 4 BLK SW5-5.6 ON OFF 1 LI DCL SW6 1 3 V W M 3~ MC +1 MODEL SELECT MODEL CNAC2 (RED) TABP2 RED U ON PUZ-A42N OFF E2 U WHT TABN2 RED TABP 3 1 2 TABV WHT CB TABS WHT TABW 2 DS2 BLU TABP1 RED TABU 2 TABT RED WHT BLK TH8 7 1 CN3 2(WHT) 1 CN5 2 (RED) 1 CN4 2(WHT) TABN DS3 3 IPM CN2 (WHT) t° CNDC (PNK) 2 1 6 1 7 2 2 P. B. 4 N. F. NO 52C LO +Use copper supply wires. NAME Terminal Block<M-net connection> Connector<Transmission> Connector<Power Supply> Connector<M-NET communication> Switch<Status of communication> Switch<Address setting : 1s digit> Switch<Address setting : 10s digit> LED<Power Supply : DC5V> LED<Connection to Outdoor Unit> LED<Transmission : Sending> LED<Transmission : Recelving> LED<Power Supply : DC12V> 29 U CY1 CY2 TB1 NI U EI 2 5 REFRIGERANT SYSTEM DIAGRAM 5-1. INDOOR UNIT PLA-A·BA PCA-A·KA PEA-A·AA Strainer(#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH5 (Cond./Eva. temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Distributor with strainer(#50) Thermistor TH2 Pipe temperature (Liquid) Thermistor TH1 (Room temperature) PKA-A·HA Strainer(#50) PKA-A·HAL PKA-A·KA PKA-A·KAL Strainer (#50) Heat exchanger Refrigerant GAS pipe connection (Flare) Thermistor TH2 Pipe temperature(Liquid) Thermistor TH5 (Cond./ Eva.temperature) Refrigerant flow in cooling Refrigerant flow in heating Refrigerant LIQUID pipe connection (Flare) Thermistor TH1 (Room temperature) Strainer (#50) Distributor with strainer (#50/#50 : HA(L)) (#50/#100 : KA(L)) 30 5-2. OUTDOOR UNIT PUZ-A18NHA3(-BS) Unit: mm (inch) 4-way valve (#50) Strainer Refrigerant GAS pipe 12.7 (W1/2) <4-way valve solenoid coil> Heating : ON Cooling : OFF Service port(check) High pressure protect switch Stop valve (with service port) Outdoor heat exchanger Thermistor (TH6) Muffler Thermistor (TH3) Thermistor (TH32) Distributor Accumulator Compressor Refrigerant LIQUID pipe 6.35 (W1/4) Stop valve Refrigerant flow in cooling Refrigerant flow in heating (#100) Strainer (#100) Strainer Linear expansion valve PUZ-A24NHA3(-BS) PUZ-A30NHA3(-BS) PUZ-A36NHA3(-BS) Bypass valve Ball valve 4-way valve (#50) Refrigerant GAS pipe Strainer 15.88 (W5/8) Service port (check) Service port (check) High pressure protect switch Outdoor heat exchanger Thermistor (TH6) Muffler Thermistor (TH3) Thermistor (TH32) Distributor Accumulator Refrigerant LIQUID pipe 9.52 (W3/8) Compressor Stop valve (with service port) Refrigerant flow in cooling Refrigerant flow in heating (#100) Strainer (#100) Strainer Linear expansion valve PUZ-A42NHA3(-BS) Low pressure protect switch 4-way Ball valve valve (#50) Strainer Refrigerant GAS pipe 15.88 (W5/8) Service port (check) Service port (check) High pressure protect switch Outdoor heat exchanger Thermistor (TH6) Muffler Thermistor (TH4) Strainer (#100) Accumulator Refrigerant LIQUID pipe 9.52 (W3/8) Stop valve (with service port) Distributor Refrigerant flow in cooling Refrigerant flow in heating Compressor Strainer (#100) Thermistor (TH3) Strainer (#100) Linear expansion valve 31 PUY-A12NHA3(-BS) PUY-A18NHA3(-BS) Stop valve (with service port) (#50) Strainer Refrigerant GAS pipe 12.7 (W1/2) Unit: mm (inch) Service port (Check) Outdoor heat exchanger High pressure protect switch Thermistor (TH6) Thermistor (TH3) Thermistor (TH32) Distributor Accumulator Compressor Refrigerant LIQUID pipe 6.35 (W1/4) Stop valve Refrigerant flow in cooling (#100) Strainer (#100) Strainer Linear expansion valve PUY-A24NHA3(-BS) PUY-A30NHA3(-BS) PUY-A36NHA3(-BS) Refrigerant GAS pipe 15.88 (W5/8) Ball valve (#50) Strainer Bypass valve Service port (check) Outdoor heat exchanger Thermistor (TH6) High pressure protect switch Thermistor (TH32) Service port (check) Thermistor (TH3) Distributor Accumulator Refrigerant LIQUID pipe 9.52 (W3/8) Compressor (#100) Strainer Stop valve (with service port) Refrigerant flow in cooling (#100) Strainer Linear expansion valve PUY-A42NHA3(-BS) Low pressure protect switch Service port (#50) Strainer (check) Strainer (#100) Ball valve Refrigerant GAS pipe 15.88 (W5/8) Outdoor heat exchanger Thermistor (TH6) Thermistor (TH3) High pressure protect switch Service port (check) Thermistor (TH4) Accumulator Distributor Refrigerant flow in cooling Compressor Refrigerant LIQUID pipe 9.52 (W3/8) Strainer (#100) Stop valve (with service port) Strainer (#100) Linear expansion valve 32 6 PERFORMANCE CURVES FOR THE COMBINATION OF OUTDOOR UNIT PUZ-A·NHA3(-BS), PUY-A·NHA3(-BS) Cooling performance curve CAPACITY (RATIO) 1.4 1.2 INDOOR W.B.(˚C) 22 (72˚F) 1.0 20 (68˚F) 18 (64˚F) 0.8 16 (61˚F) INDOOR W.B.(˚C) 22 (72˚F) 20 (68˚F) 18 (64˚F) 16 (61˚F) 1.2 TOTAL INPUT (RATIO) 1.0 0.8 0.6 0.4 -5 0 (23˚F) (32˚F) 10 (50˚F) 20 (68˚F) 30 (86˚F) 40 46 (104˚F) (115˚F) OUTDOOR D.B.(˚C) Note : This diagram shows the case where the operation frequency of a compressor is fixed. 33 Heating performance curve Correcting the capacity line influenced by frosting Not correcting the capacity line influenced by frosting INDOOR 1.4 CAPACITY (RATIO) 1.2 D.B.(˚C) In some cases, heating operation cannot be conducted with the maximum frequency in the area below the slanting line. 15 (59˚F) 20 (68˚F) 25 (77˚F) 1.0 0.8 0.6 0.4 1.4 1.2 INDOOR In some cases, heating operation cannot be conducted with the maximum frequency in the area above the slanting line. D.B.(˚C) 25 (77˚F) 20 (68˚F) TOTAL INPUT (RATIO) 15 (59˚F) 1.0 0.8 0.6 0.4 -12 -10 (10˚F) (14˚F) -5 (23˚F) 0 (32˚F) 5 (41˚F) 10 (50˚F) OUTDOOR W.B.(˚C) Note : This diagram shows the case where the operation frequency of a compressor is fixed. 34 15 (59˚F) CORRECTION FACTORS 7 7-1. COOLING CAPACITY CORRECTION FACTORS Outdoor unit PUY-A12/18 PUZ-A18 PUY-A24/30/36 PUZ-A24/30/36 PUY-A42 PUZ-A42 Refrigerant piping length (one way) 30m (100ft) 20m (70ft) 5m (16ft) 10m (33ft) 40m (130ft) 50m (165ft) 1.00 0.985 0.957 0.931 – – 1.00 0.988 0.966 0.946 0.929 0.913 1.00 0.985 0.957 0.931 0.908 0.886 40m (130ft) 50m (165ft) 7-2. HEATING CAPACITY CORRECTION FACTORS Outdoor unit Refrigerant piping length (one way) 30m (100ft) 20m (70ft) 5m (16ft) 10m (33ft) PUZ-A18 1.00 0.997 0.991 0.985 – – PUZ-A24/30/36 1.00 0.997 0.991 0.985 0.979 0.973 PUZ-A42 1.00 0.997 0.991 0.985 0.979 0.973 7-3. CAPACITY CORRECTION Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity curves below. Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m) Cooling Corrected pipe length (ft) = actual pipe length (ft) + number of bends x 1 (ft) Heating 100 Heating A18,24,30,36,42 models (Up to 30m(100ft) for A18 model) 95 Capacity ratio [%] Cooling A24,30,36 model 90 Cooling A12,18,42 models (Up to 30m (100ft) for A12/18 models) 85 80 75 70 5 10 15 20 25 30 35 40 45 <16> <33> <50> <70> <80> <100> <115> <130> <150> Corrected pipe length 35 50 m <165> ft 7-4. ADDITION OF REFRIGERANT • Additional charging is not necessary if the pipe length does not exceed 20 m(70 ft) for A12-A36 or 30 m(100 ft) for A42. • If the pipe length exceeds the specified length above, charge the unit with additional R410A refrigerant according to the permitted pipe lengths in the chart below. * When the unit is stopped, charge the unit with the additional refrigerant through the liquid stop valve after the pipe extensions and indoor unit have been vacuumized. * When the unit is operating, add refrigerant to the gas check valve using a safety charger. Do not add liquid refrigerant directly to the check valve. * After charging the unit with refrigerant, note the added refrigerant amount on the service label (attached to the unit). • Be careful when installing multiple units. Connecting to an incorrect indoor unit can lead to abnormally high pressure and have a serious effect on operation performance. Model Max. pipe length Max. height difference A12, A18 30 m, 100 ft 30 m, 100 ft 0 A24, A30, A36 50 m, 165 ft 30 m, 100 ft 0 A42 50 m, 16 5 ft 30 m, 100 ft 0 8 20 m 70 ft 25 m 80 ft 0.06 kg 2 oz 0.17 kg 6 oz 27 m 90 ft 0.11 kg 4 oz 0.34 kg 12 oz 0 0 Additional refrigerant charging amount (kg/oz) 30 m 33.5 m 36.6 m 40 m 43 m 45.5 m 100 ft 110 ft 120 ft 130 ft 140 ft 150 ft 0.17 kg – – – – – 6 oz 0.51 kg 0.68 kg 0.85 kg 1.02 kg 1.19 kg 1.36 kg 18 oz 24 oz 30 oz 36 oz 42 oz 48 oz 0.17 kg 0.34 kg 0.51 kg 0.68 kg 0.85 kg 0 6 oz 12 oz 18 oz 24 oz 30 oz 48.8 m 160 ft 50 m 165 ft – – 1.53 kg 54 oz 1.02 kg 36 oz 1.70 kg 60 oz 1.19 kg 42 oz AIR FLOW DATA 8-1. OUTLET AIR SPEED AND COVERAGE RANGE Air flow CFM Air speed ft/sec.(m/sec.) Coverage range ft(m) Air flow CFM Air speed ft/sec.(m/sec.) Coverage range ft(m) PLA-A12BA 530 8.5(2.6) 13(4.1) PLA-A18BA 640 10.5(3.2) 15(4.8) PLA-A24BA 640 10.5(3.2) 15(4.8) PKA-A12HA PKA-A12HAL PKA-A18HA PKA-A18HAL 425 20.0(6.1) 35(10.8) 425 20.0(6.1) 35(10.8) PLA-A30BA 740 12.1(3.7) 18(5.6) PLA-A36BA 1060 17.4(5.3) 26(8.0) PLA-A42BA 1090 17.7(5.4) 26(8.2) Air flow CFM Air speed ft/sec.(m/sec.) Coverage range ft(m) PKA-A24KA PKA-A24KAL 775 19.7(6.0) 47(14.3) PKA-A30KA PKA-A30KAL 775 19.7(6.0) 47(14.3) PKA-A36KA PKA-A36KAL 920 22.3(6.8) 53(16.1) PCA-A24KA 670 10.2(3.1) 32(9.6) PCA-A30KA PCA-A36KA PCA-A42KA Air flow CFM Air speed ft/sec.(m/sec.) Coverage range ft(m) 705 10.5(3.2) 33(10.1) 990 11.8(3.6) 41(12.5) 1025 12.1(3.7) 42(12.9) The air coverage range is the distance to which the 0.8 ft/sec. air can reach, when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room. 36 8-2. PLA-A·BA 8-2-1 FRESH AIR INTAKE AND BRANCH DUCT 1. Branch duct hole and fresh air intake hole (Fig. 1) At the time of installation, use the duct holes (cut out) located at the positions shown in Fig.1, as and when required. • A fresh air intake hole for the optional multi function casement can also be made. Note: The figure marked with * in the drawing represent the dimensions of the main unit excluding those of the optional multi function casement. When installing the optional multi function casement, add 5-5/16 to the dimensions marked on the figure. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. Unit : inch(mm) [Fig. 1] Fresh air intake hole diagram Fresh air intake hole 3-:1/8(:2.8) burring hole Indoor unit 6-7/32 (*158) 120 :4-29/32(:125) burring hole pitch 120 Branch duct hole 3-:15/16(:100) cut out hole Ceiling *6-3/32(155) 70 :6-7/8(:175) burring hole pitch 13-25/32(350) *6-9/16(167) 3-17/32 3-15/16 3-15/16 3-17/32 (90) (100) (90) (90) 5-1/8(130) Refrigerant pipe Branch duct hole diagram (view from either side) 3-15/16(100) Drain pipe 14-:1/8(:2.8) burring hole :5-29/32(:150) cut out hole 2. Fresh air intake (Installation at site) By mounting the optional multi-function casement to the indoor unit main body, and mounting the duct flange (option) onto it further, fresh exterior air intake can be accomplished. (The mounting of the multi-function casement increases the height of the ceiling plenum by 5-5/16(135mm).) 37 3. Fresh air intake amount & static pressure characteristics 1 PLA-A12 · A18 · A24 · A30BA Multifunction casement + Standard filter 50(20) Static pressure [Pa(in.W.G.%10-2)] Static pressure [Pa(in.W.G.%10-2)] Multifunction casement + High efficiency filter 0 -50(-20) 2 - inlet -100(-40) -150(-60) 1 - inlet -200(-80) 0 1 2 50 3 4 100 6[CMM] 5 150 200 50(20) 0 -50(-20) 2 - inlet -100(-40) -150(-60) 1 - inlet -200(-80) 0 1 2 [CFM] 3 50 4 100 6[CMM] 5 150 200 [CFM] Air flow rate How to read curves 1 A 2 E C A -100(-40) -150(-60) 0 1 2 3 4 100 Air flow rate 5 3 6[CMM] 150 200 D -200(-80) Q [CFM] Q Qa 2 PLA-A36 · A42BA Multifunction casement + Standard filter Multifunction casement + High efficiency filter 50(20) Static pressure [Pa(in.W.G.%10-2)] Static pressure [Pa(in.W.G.%10-2)] B Q -50(-20) Q…Designed amount of fresh air intake <CMM(CFM)> A…Static pressure loss of fresh air intake duct system with air flow <Pa(in.W.G.o10-2)> amount Q B…Forced static pressure at air conditioner inlet with air flow amount Q <Pa(in.W.G.o10-2)> C…Static pressure of booster fan with air flow amount Q <Pa(in.W.G.o10-2)> D…Static pressure loss increase amount of fresh air intake dust system for air <Pa(in.W.G.o10-2)> flow amount Q E…Static pressure of indoor unit with air <Pa(in.W.G.o10-2)> flow amount Q Qa … Estimated amount of fresh air <CMM(CFM)> intake without D Duct characteristics at site 0 0 50 0 -50(-20) 2 - inlet -100(-40) -150(-60) 1 - inlet -200(-80) 0 2 50 4 100 150 6 200 8 [CMM] 50(20) 0 -50(-20) -100(-40) 2 - inlet -150(-60) -200(-80) [CFM] 250 50(20) 0 -50(-20) -100(-40) -150(-60) 0 2 50 4 100 150 2 4 100 150 Air flow rate Taking air into the unit -200(-80) 1 - inlet 0 50 Air flow rate Static pressure [Pa(in.W.G.%10-2)] Curve in the graphs C 50(20) A Static pressure [Pa(in.W.G.%10-2)] Taking air into the unit 6 200 8 250 [CMM] [CFM] Air flow rate 38 6 200 8 250 [CMM] [CFM] 4. Change of outlet numbers The optional air outlet is necessary. To change the air outlet number to 3-, or 2-way outlet, the outlet number should be closed with the operational air outlet shutter. Indoor unit When the air outlets are closed, close the vane by removing the vane connector. Outlet concave portion Button Vane motor Up/down vanes Connector Air outlet shutter plate (Option) Vane motor Connector Button 5. Branch duct and change of outlet numbers + Branch duct should be connected to one of the branch duct holes on the main unit. <4- way air flow and branch duct> Branch duct Air intake Air outlet + Close the outlet on the side of branch duct and air flows in 3 directions. <3- way air flow and branch duct> Branch duct Air intake Air outlet Air outlet closed position + The outlet on the side of branch duct and one of the other outlets are closed. Air flows in 2 directions. <2- way air flow and branch duct> Branch duct Air Air outlet outlet closed closed position position Air intake Air outlet closed position 39 PLA-A30BA 4-way air flow (horizontal vane) Round duct 4-way air flow (horizontal vane) Rectangular duct 30(12) Static pressure [Pa(in.W.G%10-2)] Static pressure [Pa(in.W.G%10-2)] 30(12) Duct 20(8) 10(4) High Low 0 0 2 0 50 4 100 6 150 200 Air flow rate Low 0 0 [CFM] 0 250 3-way air flow (horizontal vane) Round duct High 2 50 4 100 250 [CFM] 70(28) Static pressure [Pa(in.W.G%10-2)] 60(24) Close 50(20) 40(16) 30(12) 20(8) High Low 10(4) 0 0 2 50 4 100 6 150 8 200 250 Close 50(20) 40(16) 30(12) High 20(8) Low 10(4) 0 10[CMM] 300 Duct 60(24) [CFM] 0 0 2 50 4 100 6 150 Air flow rate 8 200 250 10[CMM] 300 [CFM] Air flow rate 2-way air flow (horizontal vane) Round duct 2-way air flow (horizontal vane) Rectangular duct 80(32) Static pressure [Pa(in.W.G%10-2)] 80(32) Static pressure [Pa(in.W.G%10-2)] Air flow rate 8[CMM] 200 3-way air flow (horizontal vane) Rectangular duct Duct 70(28) Duct 60(24) Close Close 50(20) 40(16) 30(12) High 20(8) Low 10(4) 0 6 150 80(32) 70(28) Static pressure [Pa(in.W.G%10-2)] 10(4) 8[CMM] 80(32) 0 Duct 20(8) 70(28) Duct 60(24) Close Close 50(20) 40(16) 30(12) 20(8) High Low 10(4) 0 0 0 2 50 4 100 150 6 200 8 250 Air flow rate 10 300 350 400 12[CMM] 0 [CFM] 0 2 50 4 100 150 6 200 8 250 10 300 350 12[CMM] 400 [CFM] Air flow rate • Use 1 of the 2 duct holes on the indoor unit. • Air flow rate of PLA-A12~24BA can be calculated from the air flow rate based on the characteristic of the duct for PLA-A30BA. • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow. 40 PLA-A42BA Duct 20(8) 10(4) 0 2 0 50 30(12) Duct 20(8) 10(4) High Low 0 4-way air flow (horizontal vane) Rectangular duct Static pressure [Pa(in.W.G%10-2)] Static pressure [Pa(in.W.G%10-2)] 4-way air flow (horizontal vane) Round duct 30(12) 4 100 6 150 8[CMM] 0 0 [CFM] 0 250 200 Air flow rate 3-way air flow (horizontal vane) Round duct 4 100 8[CMM] 250 200 Air flow rate [CFM] 70(28) Duct Duct Static pressure [Pa(in.W.G%10-2)] Close 60(24) 50(20) 40(16) High 30(12) 20(8) Low 10(4) 0 0 0 2 50 4 100 6 150 8 200 250 Air flow rate Close 60(24) 50(20) 40(16) High 30(12) 20(8) Low 10(4) 10[CMM] 0 0 [CFM] 0 300 2 50 4 100 8 200 10[CMM] 250 300 Air flow rate [CFM] 100(40) 90(36) 90(36) Duct Duct 80(32) 80(32) Close Close Close Close 70(28) Static pressure [Pa(in.W.G%10-2)] 70(28) 60(24) 50(20) 40(16) High 30(12) Low 20(8) 10(4) 0 0 6 150 2-way air flow (horizontal vane) Rectangular duct 2-way air flow (horizontal vane) Round duct 100(40) Static pressure [Pa(in.W.G%10-2)] 6 150 80(32) 70(28) Static pressure [Pa(in.W.G%10-2)] 2 50 3-way air flow (horizontal vane) Rectangular duct 80(32) 0 High Low 2 50 4 100 150 6 200 8 250 300 10 350 12[CMM] 400 [CFM] 60(24) 50(20) High 40(16) Low 30(12) 20(8) 10(4) 0 0 0 2 50 4 100 150 6 200 8 250 300 10 350 Air flow rate Air flow rate • Use 1 of the 2 duct holes on the indoor unit. • Air flow rate of PLA-A36BA can be calculated from the air flow rate based on the characteristic of the duct for PLA-A42BA. • Use the optional air outlet shutter plate (PAC-SH51SP-E) for 3-way and 2-way air flow. 41 12[CMM] 400 [CFM] 8-3. PCA-A·KA FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS Fresh air intake hole At the time of installation, use the duct holes (knock out) located at the positions shown in the left diagram, as and when required. A Indoor unit B Fresh air intake hole (knock out hole) C Filter in. (mm) A C B A B C 10-3/16 (259.5) ø 3-15/16 (ø 100) 4-5/16 (109) How to read curves Curve in the graphs 1 A 0 -100(-40) Duct characteristics at site -150(-60) Q -200(-80) B 0 -50(-20) -250(-100) 2 1 2 50 3 100 4 [CMM] C A -300(-120) 0 [CFM] Airflow rate Q D 3 Static pressure[Pa(in.W.G.×10ˉ²] A ■ PCA-A36, 42KA Q Qa 50(20) 0 -50(-20) -100(-40) -150(-60) -200(-80) -250(-100) -300(-120) 0 1 2 50 3 100 4 [CMM] [CFM] Airflow rate 42 C 50(20) E Static pressure[Pa(in.W.G.×10ˉ²] ■ PCA-A24, 30KA Q…Designed amount of fresh air intake <CMM(CFM)> A…Static pressure loss of fresh air intake duct system with airflow amount Q <Pa(in.W.G.x10-2)> B … Forced static pressure at air conditioner inlet with airflow amount Q <Pa(in.W.G.x10-2)> C…Static pressure of booster fan with airflow amount Q <Pa(in.W.G.x10-2)> D…Static pressure loss increase amount of fresh air intake duct system for airflow amount Q <Pa(in.W.G.x10-2)> E…Static pressure of indoor unit with airflow amount Q <Pa(in.W.G.x10-2)> Qa … Estimated amount of fresh air intake without D <CMM(CFM)> 8-4. PEA-A·AA INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW PEA-A12AA PEA-A12AA (External static pressure 0.020[in.WG](5Pa) 208/230V 60Hz (External static pressure 0.060[in.WG](15Pa) 208/230V 60Hz 50 [0.20] External static pressure [in.WG](Pa) External static pressure [in.WG](Pa) 40 [0.16] 30 [0.12] Limit 20 [0.08] High 10 [0.04] 40 [0.16] Limit 30 [0.12] High 20 [0.08] Middle Rated point 10 [0.04] Middle Rated point Low Low 0 6 [212] 7 [247] 8 [282] 9 [318] 10 [353] 11 [388] 0 12 [424] 6 [212] 7 [247] Airflow rate(m3/min)[CFM] 11 [388] 12 [424] (External static pressure 0.200[in.WG](50Pa) 208/230V 60Hz 80 [0.32] 80 [0.32] 70 [0.28] 70 [0.28] 60 [0.24] External static pressure [in.WG](Pa) External static pressure [in.WG](Pa) 10 [353] PEA-A12AA (External static pressure 0.140[in.WG](35Pa) 208/230V 60Hz Limit 50 [0.20] 40 [0.16] Rated point 30 [0.12] High Middle 20 [0.08] Low Limit 60 [0.24] 50 [0.20] Rated point High 40 [0.16] Middle 30 [0.12] 20 [0.08] Low 10 [0.04] 0 6 [212] 9 [318] Airflow rate(m3/min)[CFM] PEA-A12AA 10 [0.04] 8 [282] 0 7 [247] 8 9 10 [282] [318] [353] 3 Airflow rate(m /min)[CFM] 11 [388] 12 [424] 6 [212] 7 [247] 8 [282] 9 [318] 3 10 [353] Airflow rate(m /min)[CFM] 43 11 [388] 12 [424] PEA-A18AA PEA-A18AA (External static pressure 0.020[in.WG](5Pa) 208/230V 60Hz (External static pressure 0.060[in.WG](15Pa) 208/230V 60Hz 50 [0.20] 40 [0.16] Limit External static pressure [in.WG](Pa) External static pressure [in.WG](Pa) Limit 30 [0.12] 20 [0.08] High Middle 10 [0.04] High 30 [0.12] Middle 20 [0.08] Low Rated point 10 [0.04] Low Rated point 0 9 [318] 40 [0.16] 0 10 11 [353] [388] 12 [424] 13 14 15 16 17 18 19 [459] [494] [530] [565] [600] [636] [671] 9 [318] 10 11 [353] [388] 3 Airflow rate(m /min)[CFM] PEA-A18AA PEA-A18AA (External static pressure 0.140[in.WG](35Pa) 208/230V 60Hz (External static pressure 0.200[in.WG](50Pa) 208/230V 60Hz 80 [0.32] 80 [0.32] Limit 60 [0.24] High 50 [0.20] 40 [0.16] Middle Rated point 30 [0.12] Low 20 [0.08] Limit 70 [0.28] External static pressure [in.WG](Pa) External static pressure [in.WG](Pa) 70 [0.28] High 60 [0.24] 50 [0.20] Middle 40 [0.16] Rated point 30 [0.12] Low 20 [0.08] 10 [0.04] 10 [0.04] 0 9 [318] 12 13 14 15 16 17 18 19 [424] [459] [494] [530] [565] [600] [636] [671] 3 Airflow rate(m /min)[CFM] 0 10 11 [353] [388] 12 13 14 15 16 17 18 19 [424] [459] [494] [530] [565] [600] [636] [671] Airflow rate(m3/min)[CFM] 9 [318] 44 10 11 [353] [388] 12 13 14 15 16 17 18 19 [424] [459] [494] [530] [565] [600] [636] [671] Airflow rate(m3/min)[CFM] 9 NOISE CRITERION CURVES PLA-A12BA NOTCH SPL(dB) High 31 Medium1 29 Medium2 28 Low 27 LINE PLA-A18BA 90 bar) NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 70 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 NC-20 250 500 1000 2000 4000 10 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz PLA-A24BA NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 LINE 500 PLA-A30BA bar) NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 70 10 250 1000 2000 4000 8000 NOTCH SPL(dB) High 34 Medium1 32 Medium2 30 Low 28 LINE 90 80 20 NC-20 BAND CENTER FREQUENCIES, Hz 90 bar) LINE 90 80 10 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 NOTCH SPL(dB) High 32 Medium1 31 Medium2 29 Low 28 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz 45 4000 8000 PLA-A36BA NOTCH SPL(dB) High 40 Medium1 37 Medium2 34 Low 32 LINE PLA-A42BA bar) 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 LINE 90 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 NOTCH SPL(dB) High 41 Medium1 39 Medium2 36 Low 34 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 BAND CENTER FREQUENCIES, Hz APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz UNIT CEILING 5ft MICROPHONE 46 4000 8000 PKA-A12HA PKA-A18HA PKA-A12HAL PKA-A18HAL NOTCH SPL(dB) High 43 36 Low LINE PKA-A24KA PKA-A30KA PKA-A24KAL PKA-A30KAL NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 μbar) 70 80 70 125 250 500 1000 2000 4000 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 63 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 49 Low 43 PKA-A36KA PKA-A36KAL LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB= 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 μbar) 80 10 LINE 90 90 20 NOTCH SPL(dB) High 45 Low 39 UNIT WALL 3.3ft 3.3ft MICROPHONE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 10 63 47 125 250 500 1000 2000 4000 8000 NOTCH SPL(dB) High 40 Medium1 37 Medium2 35 Low 33 PCA-A30KA LINE 90 90 80 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) PCA-A24KA 63 125 70 500 1000 2000 4000 50 NC-50 40 NC-40 30 NC-30 10 8000 NC-70 NC-60 20 250 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 90 80 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 1000 2000 2000 4000 8000 4000 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 BAND CENTER FREQUENCIES, Hz ceiling 3.3ft unit about 4.62ft MICROPHONE 48 LINE NC-60 10 8000 NOTCH SPL(dB) High 45 Medium1 43 Medium2 41 Low 39 NC-70 BAND CENTER FREQUENCIES, Hz 3.3ft 1000 60 20 500 500 70 NC-20 250 250 PCA-A42KA LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) NOTCH SPL(dB) High 43 Medium1 41 Medium2 39 Low 37 90 20 NC-20 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz PCA-A36KA LINE 60 NC-20 10 NOTCH SPL(dB) High 41 Medium1 39 Medium2 37 Low 35 4000 8000 <60Hz> PEA-A12AA NOTCH SPL(dB) High 33 Middle 28 Low 23 External static pressure : 0.020[in.WG](5Pa) LINE NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 20 10 8000 63 NOTCH SPL(dB) High 34 Middle 29 Low 24 External static pressure : 0.140[in.WG](35Pa) LINE 1000 2000 4000 8000 <60Hz> NOTCH SPL(dB) High 35 Middle 31 Low 25 External static pressure : 0.200[in.WG](50Pa) LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 500 PEA-A12AA 90 10 250 BAND CENTER FREQUENCIES, Hz <60Hz> PEA-A12AA NC-20 125 BAND CENTER FREQUENCIES, Hz 20 LINE 90 80 10 NOTCH SPL(dB) High 33 Middle 28 Low 23 External static pressure : 0.060[in.WG](15Pa) 90 20 <60Hz> PEA-A12AA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 20 10 8000 63 BAND CENTER FREQUENCIES, Hz NC-20 125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation. Aux. duct test unit 3.3ft 5ft 6.6ft Measurement location 49 <60Hz> PEA-A18AA NOTCH SPL(dB) High 37 Middle 33 Low 29 External static pressure : 0.020[in.WG](5Pa) LINE NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 70 80 70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 8000 NC-70 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 BAND CENTER FREQUENCIES, Hz NOTCH SPL(dB) High 39 Middle 35 Low 31 External static pressure : 0.140[in.WG](35Pa) LINE 500 1000 2000 4000 8000 <60Hz> NOTCH SPL(dB) High 39 Middle 36 Low 32 External static pressure : 0.200[in.WG](50Pa) LINE 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 μbar) 250 PEA-A18AA 90 10 NC-20 BAND CENTER FREQUENCIES, Hz <60Hz> PEA-A18AA 20 LINE 90 80 10 NOTCH SPL(dB) High 38 Middle 34 Low 30 External static pressure : 0.060[in.WG](15Pa) 90 20 <60Hz> PEA-A18AA 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 BAND CENTER FREQUENCIES, Hz APPROXIMATE TERESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz NOTE: The sound level is measured in an anechoic room where echoes are few, when compressor stops. The sound may be bigger than displayed level under actual installation condition by surrounding echoes. The sound level can be higher by about 2 dB than the displayed level during cooling and heating operation. 50 MICROPHONE 3.3ft UNIT 5ft GROUND PUY-A12NHA3 (-BS) PUY-A18NHA3 (-BS) PUZ-A18NHA3 (-BS) MODE SPL(dB) COOLING 46 HEATING 47 PUY-A24/30/36NHA3(-BS) PUZ-A24/30/36NHA3(-BS) LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 MODE SPL(dB) COOLING 51 HEATING 55 LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz PUY-A42NHA3(-BS) PUZ-A42NHA3(-BS) LINE 90 90 20 MODE SPL(dB) COOLING 48 HEATING 50 8000 BAND CENTER FREQUENCIES, Hz 51 8000 10 OPTIONAL PARTS 10-1. INDOOR UNIT Part Name Model Name Remote sensor (extensible) PAC-SE41TS-E PAC-88HA-E (1pc.) PAC-725AD (10pcs.) PAC-SE55RA-E PAC-SE57RA-E PAC-SE56RA-E PAC-SE59RA-E PAC-SH55HR-E PAC-SG95HR-E PAC-SH98HR-E PLP-42BAMD PLP-40BAU PAC-SH53TM-E PAC-SH65OF-E Connector for CN51 (output for remote display + pulse12V input) Connector for CN32 (remote ON/OFF) Connector for CN30 (LLC) Connector for CN24 (Back up heating) Connector for CN152 (Back up heating) Power supply terminal kit Decoration panel with wired remote controller Decoration panel Multi-function casement Flange for fresh air intake High-efficiency filter element (PAC-SH53TM-E is needed.) i-see sensor corner panel Wireless signal receiver Wireless remote controller kit Space panel Air outlet shutter plate High efficiency filter Drain lift up mechanism i-see Sensor Wireless remote controller kit with i-see Sensor Wireless remote controller kit Wireless remote controller PAC-SH59KF-E PAC-SA1ME-E PAR-SA9FA-E PAR-SW96U-E PAC-SH48AS-E PAC-SH51SP-E PAC-SH89KF-E PAC-SH90KF-E PAC-SH84DM-E PAC-SH91MK-E PAR-SA92MW-E Applicable model All models PLA-A·BA, PKA-A·HA(L)/KA(L), PCA-A·KA PLA-A·BA, PCA-A·KA, PEA-A·AA PKA-A·HA(L)/KA(L) PLA-A·BA PKA-A·HA(L)/KA(L) PCA-A·KA PLA-A·BA PCA-A24/30KA PCA-A36/42KA PCA-A·KA PAR-SL93B-E PAR-FL32MA-E PEA-A·AA Part Name Model Name Applicable model M-NET adapter A-control service tool Drain socket PAC-SF80MA-E PAC-SK52ST PAC-SG61DS-E PAC-SG58SG-E PAC-SG59SG-E PAC-SG56AG-E PAC-SH63AG-E PAC-SG63DP-E PAC-SG64DP-E MSDD-50SR-E 10-2. OUTDOOR UNIT Air outlet guide (A42 needs 2 pieces.) Air protect guide (A42 needs 2 pieces.) Drain pan Distribution pipe for twin use All models A12,18 A24-42 A12,18 A24-42 A12,18 A24-42 A24,36 HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN CCopyright 2009 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Mar. 2009 No.OCS14 PDF6 Made in Japan New publication, effective Mar. 2009 Specifications subject to change without notice