Download Mitsubishi PEN-2.5 Service manual
Transcript
OC129A-1.qxp 01.10.1 7:33 PM Page 1 1997 SPLIT-TYPE,AIR CONDITIONERS No. OC129 REVISED EDITION-A TECHNICAL & SERVICE MANUAL Series PK Wall Mounted Indoor unit [ Model names ] [ Service Ref. ] 1997, 1999, 2001 PK-2.5FLA 1997 1999 PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2 PK-3FLA PK-3FLA2 PK-4FLSA PK-4FLSA2 PK-1.6FLA PK-2FLA PK-3FLA3 2001 PK-2.5FLA3 PK-2.5FLA4 PK-3FLA4 PK-3FLA5 PK-4FLSA3 PK-4FLSA4 CONTENTS Indoor unit ˚C AM PM AM PM NOT AVAILABLE ON / OFF TEMP PK-1.6FLA3 PK-2.5FLA4 PK-2FLA3 PK-3FLA5 PK-2.5FLA2/3 PK-4FLSA4 PK-3FLA2/3/4 PK-4FLSA2/3 REMOTE CONTROLLER • PK-2.5FLA3, PK-2.5FLA4, PK-3FLA3, PK-3FLA4, PK-3FLA5, PK-4FLA3 and PK-4FLA4 are added in REVISED EDITION-A. • Please void OC129 and OC200. • This manual does not cover outdoor units. When servicing them, please refer to the service manual No.OC127 REVISED EDITION-A, OC187, OC217 REVISED EDITION-A and this manual in a set. 1. TECHNICAL CHANGES ·······························3 2. COMBINATION OF INDOOR AND OUTDOOR UNITS ··············3 3. PART NAMES AND FUNCTIONS ················3 4. SPECIFICATIONS ·········································6 5. DATA ···························································13 6. OUTLINES AND DIMENSIONS ··················16 7. WIRING DIAGRAM ·····································20 8. REFRIGERANT SYSTEM DIAGRAM···············22 9. OPERATION FLOW-CHART ······················24 10. MICROPROCESSOR CONTROL ···············27 11. TROUBLESHOOTING·································36 12. DISASSEMBLY PROCEDURE ···················39 13. PARTS LIST ················································42 14. OPTIONAL PARTS ·····································54 OC129A-1.qxp 01.10.1 7:33 PM Page 2 OC129A-1.qxp 01.10.1 7:33 PM 1 Page 3 TECHNICAL CHANGES PK-3FLA2 ➔ PK-3FLA3 PK-2.5FLA3 ➔ PK-2.5FLA4 PK-3FLA4 ➔ PK-3FLA5 PK-4FLSA3 ➔ PK-4FLSA4 ● Outdoor units has changed. ● The parts No. of REMOTE CONTROLLER has changed. (The following parts numbers are interchangeable.) PK-2.5FLA2 ➔ PK-2.5FLA3 PK-3FLA3 ➔ PK-3FLA4 PK-4FLSA2 ➔ PK-4FLSA3 ● ● ● ● NOSE has changed by changing its shape. UNDER PLATE has changed. BOX ASSEMBLY has changed by changing its shape. DRAIN PAN has changed by changing its shape. ˚C AM PM AM PM NOT AVAILABLE ON / OFF TEMP [ T7W 570 200 ] 2 COMBINATION OF INDOOR AND OUTDOOR UNITS Indoor unit PU-1.6 PU-2 PU-2.5 PU-3 PU-4 PU-3 PU-3 VLJSA2 VJA2 NJA1 VJA2 NJA1 VJA2 YJA2 YJA3 NJA1 VLJSA2 YJSA2 YJSA3 TJSA2 VJC YJC VJB YJB — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — PK-2FLA3 — PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4 — — — PK-3FLA2 — — — — — — — — — — — — — — — — — — — — — PK-3FLA3 PK-3FLA4 PK-3FLA5 PK-4FLSA2 PK-4FLSA3 PK-4FLSA4 Outdoor unit Outdoor unit (OC187) (OC217 REVISED EDITION-A) Outdoor unit (OC127 REVISED EDITION-A) PK-1.6FLA3 3 [ T7W E06 714 ] — PART NAMES AND FUNCTIONS ● Indoor Unit Air intake Room air is suctioned in here. Filter Air intake grille (Removes dust and dirt from the intake air.) Guide vane Swing louvers Air flow can be changed to horizontally by moving the Guide vane to the left or right. Disperses airflow up and down as well as adjusts the angle of air flow direction. Air outlet Air outlet 3 OC129A-1.qxp 01.10.1 7:33 PM Page 4 ●Remote controller ● When cover is closed. display PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2, PK-2.5FLA3 PK-3FLA2, PK-3FLA3, PK-3FLA4 PK-4FLSA2, PK-4FLSA3 Part No. [ T7W 570 200 ] display SET TEMP. display indicates desired temperature set. OPERATION MODE display Operation mode display indicates which operation mode is in effect. • CHECK • TEST RUN display CHECK&TEST RUN display indicates that the unit is being checked or test-run. CLOCK display ˚C display DIsplays the current time. AM PM “ AM PM Displays when batteries are dead. ”display NOT AVAILABLE Flashes when the current time is displayed. display ON / OFF TIMER display Displays when setting timer. Displays when in timer operation or when setting timer. display ➡ ” display Displays the order of timer operation. TEMP display “ The vertical direction of airflow is indicated in marks. ”“ ” display “ FAN SPEED display indicates which fan speed has been selected. ▼ ”“ ▼ ▼ Displays whether timer is on or off. display ” display Displays when the current time and the timer time can be changed. button button SET TEMPERATURE button sets any desired room temperature. Push to start operation. Push again to stop operation. SET CLOCK button ● When cover is open. Button used to set the current time. MODE SELECT button MODE SELECT button is used to change cooling. dry (dehumidify) and fan (ventilation) operation modes. ”“ ➡ “ Lights when signal is sent from the remote controller to the indoor unit. ON / OFF TIMER CONTROL buttons MODE CLOCK FAN FAN SPEED SELECT button VANE STOP START HR MIN. FAN SPEED SELECT button selects low or high fan speed. STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time. START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time. VANE CONTROL button HR. and MIN.buttons VANE CONTROL button regulates the vertical distribution of airflow. Buttons used to set the “hour and minute” of the current time and timer time. 4 OC129A-1.qxp 01.10.1 7:33 PM Page 5 ●Wireless remote controller ● When cover is open. PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 Part No. [ T7W E06 714 ] CHECK TEST RUN display CHECK&TEST RUN display indicates that the unit is being checked or test-run. MODEL SELECT display display Blinks when model is selected. Lights up while transmission to the indoor unit is mode using switches. display SET TEMP. display indicates desired temperature set. CLOCK display display Displays the current time. OPERATION MODE display Operation mode display indicates which operation mode is in effect. TIMER display CHECK TEST RUN MODEL SELECT ˚C AMPM Displays when in timer operation or when setting timer. “ AMPM NOT AVAILABLE display The vertical direction of air flow is indicated. ON/OFF “ TEMP ”“ ” display Displays the order of timer operation. ”“ ” display Displays whether timer is on or off. display button FAN SPEED display indicates which fan speed has been selected. FAN AUTO STOP VANE AUTO START SET TEMPERATURE button sets any desired room temperature. ON/OFF button The unit is turned ON and OFF alternately each time the button is pressed. MODE CHECK LOUVER h FAN SPEED SELECT button Used to change the fan speed. MODE SELECT button TEST RUN SET min RESET Used to switch the operation mode between cooling, drying, fan. TIMER CONTROL buttons AUTO STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time. AUTO START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time. CLOCK h and min buttons Buttons used to set the “hour and minute” of the current time and timer settings. LOUVER button CHECK-TEST RUN button This switch the horizontal fan motion ON and OFF. Only press this button to perform an inspection check or test operation. Do not use it for normal operation. (Not available for this model.) CLOCK button VANE CONTROL button RESET button Used to change the air flow direction. SET button 5 OC129A-1.qxp 01.10.1 7:33 PM 4 Page 6 SPECIFICATIONS 1. STANDARD SPECIFICATION Service Ref. Item Indoor, Outdoor D.B./W.B.°C Condition Capacity w1 Btu/h W kW REFRIGERANT PIPING OUTDOOR UNIT INDOOR UNIT Total input w1 Service Ref. Power supply(phase, cycle,voltage) Input kW Running current (Power factor) A (%) Starting current A External finish Heat exchanger Fan(drive) o No. Fan motor output kW Airflow (Low-High) m3/min(CFM) Pa(mmAq) External static pressure kW Booster heater Operation control & Thermostat dB Noise level (Low-High) w2 mm(in.) Cond. drain conn. O.D. W mm(in.) D mm(in.) Dimensions H mm(in.) kg(lbs) Weight Service Ref. Power supply (phase, cycle, voltage) kW Input A(%) Running current (Power factor) A Starting current External finish Refrigerant control Compressor Model kW Motor output Starter type Protection devices Heat exchanger Fan(drive) o No. kW Fan motor output m3/min(CFM) Airflow Defrost method dB Noise level w2 mm(in.) W mm(in.) Dimensions D mm(in.) H kg(lbs) Weight W Crankcase heater kg(lbs) Refrigerant Charge mm(in.) Liquid Pipe size O.D. mm(in.) Gas Indoor side Connection method Outdoor side Between the indoor & Height difference outdoor units Piping length w1 w2 w3 w4 w5 w6 w7 PK-1.6FLA3 PK-2FLA3 27/19.0°C, 35/24°C w6 27/19.0°C, 35/24°C Cooling (JIS B8616) w7 Cooling (JIS B8616) 19,000 19,100 16,000 13,300 5,450 5,600 4,600 3,900 2.54 2.52/2.56 3.06 1.49/1.59 PK-2FLA3 PK-1.6FLA3 Single, 50Hz, 220/240V Single, 50Hz, 220/240V Single, 60Hz, 220V 0.07 0.08 0.09 0.32(99/91) 0.37(98/90) 0.42(97) 0.5 0.5 0.4 0.4 Munsell 3.4Y 7.7/0.8(White) Munsell 3.4Y 7.7/0.8(White) Plate fin coil Plate fin coil Line flow (direct) o 1 Line flow (direct) o 1 0.030 0.030 10-13 (353-459) 10-14 (353-459) 0 (direct blow) 0 (direct blow) — — Wireless remote controller & Built-in Wireless remote controller & Built-in 36 - 43 38 - 45 20 (13/16) 20 (13/16) 1,250 (49-3/16) 1,250 (49-3/16) 200 (7-7/8) 200 (7-7/8) 300 (11-13/16) 300 (11-13/16) 17 (37) 17 (37) PU-1.6VLJA2 PU-2VJA2 PU-2NJA1 Single, 50Hz, 220/240V Single, 50Hz, 220/240V Single, 60Hz, 220V 2.45 2.97 1.42 / 1.52 2.44 / 2.48 11.4(98) 13.6(99) 6.7 / 6.9 (97/92) 11.3 / 10.8(98/96) 54 54 30 /33 48 / 52 Munsell 5Y 7/1 Munsell 5Y 7/1 Capillary tube Capillary tube Hermetic Hermetic RH247VFC NHJ41VMD NHJ33NBD 1.2 2.0 1.5 Line start Line start w4 Inner thermostat, HP/LP switch Plate fin coil Plate fin coil Propeller (direct ) o 1 Propeller (direct) o 1 0.065 0.065 45 (1588) 45 (1588) — — 49 49 50 870 (34-1/4) 870 (34-1/4) 295 (11-5/8) 295 (11-5/8) 650 (25-5/8) 650 (25-5/8) 45 (99) 60 (132) — 32 / 38 — R-22 1.78 (3.9) R-22 1.9 (4.2) R-22 1.3 (2.9) 9.52 (3/8) 9.52 (3/8) 15.88 (5/8) 15.88 (5/8) Flared Flared Flared Flared w3 Max. 15m w3 Max. 20m w3 Max. 20m w3 Max. 30m Refrigerant piping length (one way) : 5m (16ft) Noise level is measured in an unacoustic room based on JIS conditions. Up to 20m it is unnecessary to charge additional refrigerant. Inner thermostat, HP/LP switch. Motor protector, Thermal switch, HP/LP switch. Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C Cooling SSA385, 386 6 OC129A-1.qxp 01.10.1 7:33 PM Page 7 Service Ref. PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4 Item 27/19.0°C, 35/24°C Cooling (JIS B8616) Indoor, Outdoor D.B./W.B.°C Condition Capacity w1 Btu/h W kW OUTDOOR UNIT INDOOR UNIT Total input w1 Service Ref. Power supply(phase, cycle,voltage) Input kW Running current (Power factor) A(%) Starting current A External finish Heat exchanger Fan(drive) o No. kW Fan motor output m3/min(CFM) Airflow (Low-High) Pa(mmAq) External static pressure kW Booster heater Operation control & Thermostat dB Noise level (Low-High) w2 mm(in.) Cond. drain conn. O.D. W mm(in.) D mm(in.) Dimensions H mm(in.) kg(lbs) Weight Service Ref. Power supply (phase, cycle, voltage) kW Input A(%) Running current (Power factor) A Starting current External finish Refrigerant control Compressor Model kW Motor output Starter type Protection devices Heat exchanger Fan(drive) o No. kW Fan motor output m3/min(CFM) Airflow Defrost method dB Noise level w2 mm(in.) W mm(in.) Dimensions D mm(in.) H kg(lbs) Weight W Crankcase heater kg(lbs) Refrigerant Charge mm(in.) Liquid Pipe size O.D. mm(in.) Gas Indoor side Connection method Outdoor side Between the indoor & Height difference outdoor units Piping length 24,400 23,900 7,150 7,000 3.01 2.56 / 2.62 PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4 Single, 60Hz, 220V Single, 50Hz, 220/240V 0.095 0.095 / 0.095 0.44 (98) 0.44 / 0.44 (98/90) 0.7 0.7 / 0.8 Munsell 3.4Y 7.7/0.8(White) Plate fin coil Line flow (direct) o 2 0.04 15 - 20(530-706) 0 (direct blow) — Wireless remote controller & Built-in 39 - 45 20 (13/16) 1,400 (55-1/8) 235 (9-1/4) 340 (13-3/8) 24 (53) PU-2.5NJA1 PU-2.5VJA2 Single, 60Hz, 220V Single, 50Hz, 220/240V 2.91 2.46 / 2.52 13.4 (99) 11.4 / 10.7 (98/98) 58 45 / 49 Munsell 5Y 7/1 Capillary tube Hermetic NHJ41VMD 2.0 Line start Inner thermostat, HP/LP switch Plate fin coil Propeller (direct) o 1 0.085 50 (1765) — 52 53 870 (34-1/4) 295 (+24) (11-5/8 (add 1)) 850 (33-7/16) 71 (157) 32 / 38 R-22 2.4 (5.3) REFRIGERANT PIPING w1 w2 w3 w4 w5 NHJ38NBD 1.7 — R-22 2.4 (5.3) 9.52 (3/8) 15.88 (5/8) Flared Flared w3 Max. 20m w3 Max. 30m Refrigerant piping length (one way) : 5m (16ft) Noise level is measured in an unacoustic room based on JIS conditions. Up to 20m it is unnecessary to charge additional refrigerant. Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C. Cooling SSA385, 386 7 w4 w5 22,700 6,650 3.54 3.44 15.8(99) 58 OC129A-1.qxp 01.10.1 7:33 PM Page 8 Service Ref. PK-3FLA2 Item Indoor, Outdoor D.B./W.B.°C 27/19.0°C, 35/24°C Cooling (JIS B8616) Condition Capacity w1 Btu/h W kW 24,600 7,200 27,300 8,000 3.54 REFRIGERANT PIPING OUTDOOR UNIT INDOOR UNIT 3.28 / 3.30 3.28 / 3.30 Total input w1 PK-3FLA2 Service Ref. Single, 50Hz, 220/240V Single, 60Hz, 220V Power supply(phase, cycle,voltage) 0.095 / 0.095 0.095 kW Input 0.44 / 0.44 (98/90) 0.44 (98) A(%) Running current (Power factor) 0.7 / 0.8 0.7 A Starting current External finish Munsell 3.4Y 7.7/0.8(White) Heat exchanger Plate fin coil Fan(drive) o No. Line flow (direct) o 2 kW Fan motor output 0.04 m3/min(CFM) Airflow (Low-High) 15 - 20 (530-706) Pa(mmAq) External static pressure 0 (direct blow) kW Booster heater — Operation control & Thermostat Wireless remote controller & Built-in dB Noise level (Low-High) w2 39 - 45 mm(in.) Cond. drain conn. O.D. 20 (13/16) W mm(in.) 1,400 (55-1/8) D mm(in.) Dimensions 235 (9-1/4) H mm(in.) 340 (13-3/8) kg(lbs) Weight 24 (53) PU-3YJA2 PU-3YJA3 PU-3NJA1 PU-3VJA2 Service Ref. Single, 60Hz, 220V Single, 50Hz, 220/240V Three, 50Hz, 380/415V Power supply (phase, cycle, voltage) 3.44 3.18 / 3.20 3.18 / 3.20 kW Input 17.6(89) 15.1/13.9(96/96) 5.7/5.3(85/84) A(%) Running current (Power factor) 80 68 / 68 36 / 36 A Starting current Munsell 5Y 7/1 External finish Capillary tube Refrigerant control Hermetic Compressor Model NHJ52YDA NHJ52YDE NHJ47NAD NHJ52VND kW Motor output 2.2 2.2 2.2 Line start Starter type w6 w7 w6 Protection devices Plate fin coil Heat exchanger Propeller (direct) o 1 Fan(drive) o No. 0.085 kW Fan motor output 50 (1765) m3/min(CFM) Airflow — Defrost method 53 53 dB Noise level w2 870 (34-1/4) mm(in.) W 295 (+24) (11-5/8 (add 1)) mm(in.) Dimensions D 850 (33-7/16) mm(in.) H 73 (161) kg(lbs) Weight W Crankcase heater 32 / 38 32 / 38 38 kg(lbs) Refrigerant Charge R-22 3.08 (6.8) R-22 2.88 (6.3) R-22 3.5 (7.7) mm(in.) Liquid 9.52 (3/8) Pipe size O.D. mm(in.) Gas 15.88 (5/8) Indoor side Flared Connection method Outdoor side Flared Between the indoor & Height difference w3 Max. 20m outdoor units Piping length w3 Max. 30m w4 w5 23,500 6,900 4.19 w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay. 8 4.09 20.9(89) 80 OC129A-1.qxp 01.10.1 7:33 PM Page 9 Service Ref. PK-3FLA3 PK-3FLA4 PK-3FLA5 Item Indoor, Outdoor D.B./W.B.°C 27/19°C , 35/24°C Cooling (JIS B8616) Condition 27,300 8,000 3.28 / 3.30 3.28 / 3.30 3.54 Total input w1 PK-3FLA3 PK-3FLA4 PK-3FLA5 Service Ref. Single, 50Hz, 220/240V Single, 60Hz, 220V Power supply(phase, cycle,voltage) 0.095 / 0.095 0.095 Input kW 0.44 / 0.44 (98/90) 0.44 (98) Running current (Power factor) A(%) 0.7 / 0.8 0.7 Starting current A External finish Munsell 3.4Y 7.7/0.8(White) Heat exchanger Plate fin coil Fan(drive) o No. Line flow (direct) o 2 Fan motor output kW 0.04 Airflow (Low-High) m3/min(CFM) 15 - 20 (530-706) Pa,mmAq External static pressure 0 (direct blow) kW Booster heater — Operation control & Thermostat Wireless remote controller & Built-in dB Noise level (Low-High) w2 39 - 45 mm(in.) Unit drain pipe O.D. 20 (13/16) W mm(in.) 1,400 (55-1/8) D mm(in.) Dimensions 235 (9-1/4) H mm(in.) 340 (13-3/8) kg(lbs) Weight 24 (53) PU-3YJC PU-3NJA1 PU-3VJC Service Ref. Single, 50Hz, 220/240V Three, 50Hz, 380/415V Single, 60Hz, 220V Power supply (phase, cycle, voltage) 3.44 3.18 / 3.20 3.18 / 3.20 kW Input 17.6(89) 15.1/13.9(96/96) 5.7/5.3(85/84) A(%) Running current (Power factor) 80 54 / 58 34 / 37 A Starting current Munsell 5Y 7/1 External finish Capillary tube Refrigerant control Hermetic Compressor Model NHJ47NAD NH52VND NH52YDE kW Motor output 2.2 2.2 2.4 Line start Starter type w6 w7 w6 Protection devices Plate fin coil Heat exchanger Propeller (direct) o 1 Fan(drive) o No. 0.085 kW Fan motor output 50 (1765) m3/min(CFM) Airflow — Defrost method 52 53 dB Noise level w2 870 (34-1/4) mm(in.) W 295 (+24) (11-5/8 (add 1)) mm(in.) Dimensions D 850 (33-7/16) mm(in.) H 73 (161) kg(lbs) Weight W Crankcase heater 32 / 38 32 / 38 38 R-22 2.8(6.2) kg(lbs) Refrigerant Charge R-22 3.5 (7.7) mm(in.) Liquid 9.52 (3/8) Pipe size O.D. mm(in.) Gas 15.88 (5/8) Indoor side Flared Connection method Outdoor side Flared Between the indoor & Height difference w3 Max. 20m outdoor units Piping length w3 Max. 30m 27,000 7,900 Btu/h W kW REFRIGERANT PIPING OUTDOOR UNIT INDOOR UNIT Capacity w1 w4 w5 23,500 6,900 4.19 w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay. 9 4.09 20.9(89) 80 OC129A-1.qxp 01.10.1 7:33 PM Page 10 Service Ref. Item Indoor, Outdoor D.B./W.B.°C Condition Capacity w1 Btu/h W kW 27/19°C , 35/24°C Cooling (JIS B8616) 25,600 7,500 2.75 PK-3FLA2 PK-3FLA3 PK-3FLA4 PK-3FLA5 Single, 50Hz, 220V 0.095 0.44 (98) 0.7 Munsell 3.4Y 7.7/0.8(White) Plate fin coil Line flow (direct) o 2 0.04 15 - 20 (530-706) 0 (direct blow) — Wireless remote controller & Built-in 39 - 45 20 (13/16) 1,400 (55-1/8) 235 (9-1/4) 340 (13-3/8) 24 (53) PU-3YJB PU-3VJB Single, 50Hz, 220V Three, 50Hz, 380V 2.65 2.65 12.4(97) 4.2(97) 54 34 Munsell 5Y 7/1 Capillary tube Hermetic NH47VNHT NH47YDNT 2.2 2.2 Line start w6 w7 Plate fin coil Propeller (direct) o 1 0.085 50 (1765) — 52 870 (34-1/4) 295 (+24) (11-5/8 (add 1)) 850 (33-7/16) 73 (161) 32 32 R-22 3.0(6.6) 9.52 (3/8) 15.88 (5/8) Flared Flared w3 Max. 20m w3 Max. 30m REFRIGERANT PIPING OUTDOOR UNIT INDOOR UNIT Total input w1 Service Ref. Power supply(phase, cycle,voltage) Input kW Running current (Power factor) A(%) Starting current A External finish Heat exchanger Fan(drive) o No. kW Fan motor output m3/min(CFM) Airflow (Low-High) Pa,mmAq External static pressure kW Booster heater Operation control & Thermostat dB Noise level (Low-High) w2 mm(in.) Unit drain pipe O.D. W mm(in.) D mm(in.) Dimensions H mm(in.) kg(lbs) Weight Service Ref. Power supply (phase, cycle, voltage) kW Input A(%) Running current /Power factor A Starting current External finish Refrigerant control Compressor Model kW Motor output Starter type Protection devices Heat exchanger Fan(drive) o No. kW Fan motor output m3/min(CFM) Airflow Defrost method dB Noise level w2 mm(in.) W mm(in.) Dimensions D mm(in.) H kg(lbs) Weight W Crankcase heater kg(lbs) Refrigerant Charge mm(in.) Liquid Pipe size O.D. mm(in.) Gas Indoor side Connection method Outdoor side Between the indoor & Height difference outdoor units Piping length PK-3FLA2 PK-3FLA3 PK-3FLA4 PK-3FLA5 w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay. 10 OC129A-1.qxp 01.10.1 7:33 PM Page 11 Service Ref. PK-4FLSA2 PK-4FLSA3 PK-4FLSA4 Item 27/19.0°C, 35/24°C Cooling (JIS B8616) Indoor, Outdoor DB/WB°C Condition 37,500 11,000 3.46 / 3.63 3.40 / 3.47 4.38 Total input w1 PK-4FLSA2 PK-4FLSA3 PK-4FLSA4 Service Ref. Single, 50Hz, 220/240V Single, 60Hz, 220V Power supply(phase, cycle,voltage) 0.114 / 0.114 0.114 kW Input 0.53 / 0.53 (98/90) 0.53 (98) A(%) Running current (Power factor) 0.8 / 0.9 0.8 A Starting current Munsell 3.4Y 7.7/0.8(White) External finish Plate fin coil Heat exchanger Line flow (direct) o 2 Fan(drive) o No. 0.07 kW Fan motor output 22 - 28 (777 - 989) m3/min(CFM) Airflow (Low-High) 0 (direct blow) Pa(mmAq) External static pressure — kW Booster heater Wireless remote controller & Built-in Operation control & Thermostat 41 - 46 dB Noise level (Low-High) w2 20 (13/16) mm(in.) Cond. drain conn. O.D. 1,680 (66-1/8) W mm(in.) 235 (9-1/4) D mm(in.) Dimensions 340 (13-3/8) H mm(in.) 28 (62) kg(lbs) Weight PU-4YJSA2 PU-4YJSA3 PU-4VLJSA2 PU-4TJSA2 Service Ref. Single, 50Hz, 220/240V Three, 50Hz, 380/415V 3, 60Hz, 220V Power supply (phase, cycle, voltage) 4.27 3.35 / 3.52 3.29 / 3.36 kW Input 12.2 (92) 16.9 / 16.3 (90/90) 5.7 / 5.5 (87/85) A(%) Running current (Power factor) 69 79 / 79 38 / 38 A Starting current Munsell 5Y 7/1 External finish Capillary tube Refrigerant control Hermetic Compressor NH56VND NHJ56YDA NHJ56YDE NHJ56TKA Model 2.7 2.7 2.7 kW Motor output Line start Starter type w6 w7 w7 Protection devices Plate fin coil Heat exchanger Propeller (direct) o 2 Fan(drive) o No. 0.065 + 0.065 kW Fan motor output 95 (3352) m3/min(CFM) Airflow — Defrost method 54 55 55 dB Noise level w2 mm(in.) W 870 (34-1/4) mm(in.) Dimensions D 295 (+24) (11-5/8 (add 1)) mm(in.) H 1258 (49-1/2) kg(lbs) Weight 94 (207) W Crankcase heater 32 / 38 38 32 / 38 kg(lbs) Refrigerant Charge R-22 3.8 (8.4) R-22 4.6 (10.1) R-22 4.6 (10.1) 9.52 (3/8) mm(in.) Liquid Pipe size O.D. 19.05 (4/3) mm(in.) Gas Flared Indoor side Connection method Flared Outdoor side w3 Max. 30m Between the indoor & Height difference w3 Max. 40m outdoor units Piping length 33,400 9,800 Btu/h W kW REFRIGERANT PIPING OUTDOOR UNIT INDOOR UNIT Capacity w1 w4 w5 33,800 9,900 5.08 w1 Refrigerant piping length (one way) : 5m (16ft) w2 Noise level is measured in an unacoustic room based on JIS conditions. w3 Up to 20m it is unnecessary to charge additional refrigerant. w4 Indoor, Outdoor D.B./W.B. : 29/19°C, 46/24°C w5 Cooling SSA385, 386 w6 Inner thermostat, HP switch, LP switch. w7 Thermal switch, Reversed-phase protector, HP switch, LP switch, Thermal relay. 11 4.97 14.0(93) 69 OC129A-1.qxp 01.10.1 7:33 PM Page 12 2. POWER SUPPLY & MODEL NAMES Power supply 1ph 50Hz 60Hz Service Ref. (Outdoor unit) Service Ref. (Indoor unit) PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2 PK-3FLA2 PK-3FLA3 PK-2.5FLA3 PK-3FLA4 PK-2.5FLA4 PK-3FLA5 PU-3VJA2 PU-3VJC PU-1.6VLJA2 PU-2VJA2 PU-2.5VJA2 220,230,240V PU-3VJB PU-3VJB 3ph 380/220,400/230,415/240V — — 1ph 220V — PU-2NJA1 3ph 220V — — — (1) Rating conditions JIS B8615, 8616 Series PK Indoor Unit (Single Phase) PU-3YJC PU-3YJB PU-3YJB PU-2.5NJA1 PU-3NJA1 — Notes : 1. Power supply key N …… 1ph, 220V, 60Hz V(L) … 1ph, 220, 230 240V, 50Hz T …… 3ph, 220V, 60Hz 2. Primary power supplies for all indoor units are single-phase. 3. ELECTRICAL SPECIFICATION PU-3YJA3 — PK-4FLSA2 PK-4FLSA3 PK-4FLSA4 PU-4VLJSA2 PU-4YJSA3 PU-3NJA1 — — PU-4TJSA2 Y … 3ph, 380/220, 400/230, 415/240V, 50Hz, 4 wires Indoor : D.B. 27°C (80°F), W.B. 19°C(66°F) Outdoor : D.B. 35°C (95°F) Power supply (1 Phase) Service Ref. Current Input V : 220V 50Hz V : 230V 50Hz PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2 PK-3FLA2 PK-3FLA3 PK-4FLSA2 PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2 PK-3FLA2 PK-3FLA3 PK-4FLSA2 PK-2.5FLA3 PK-2.5FLA3 PK-3FLA4 PK-4FLSA3 PK-3FLA4 PK-4FLSA3 PK-2.5FLA4 PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 PK-3FLA5 PK-4FLSA4 A 0.32 0.37 0.44 0.44 0.44 0.53 0.32 0.37 0.44 0.44 0.44 0.53 kW Starting current A Outdoor unit 0.07 0.08 0.095 0.095 0.095 0.114 0.07 0.08 0.095 0.095 0.095 0.114 0.4 0.4 0.7 0.7 0.7 0.8 0.4 0.4 0.8 0.8 0.8 0.8 PU-1.6 PU-2 PU-2.5 PU-3 PU-3 PU-4 PU-1.6 PU-2 PU-2.5 PU-3 PU-3 PU-4 Power supply (1 Phase) Service Ref. Current Input V : 240V 50Hz N : 220V 50Hz PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2 PK-3FLA2 PK-3FLA3 PK-4FLSA2 PK-2FLA3 PK-2.5FLA2 PK-3FLA2 PK-3FLA3 PK-4FLSA2 PK-2.5FLA3 PK-2.5FLA3 PK-3FLA4 PK-4FLSA3 PK-3FLA4 PK-4FLSA3 PK-2.5FLA4 PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 PK-3FLA5 PK-4FLSA4 A 0.32 0.37 0.44 0.44 0.44 0.53 0.43 0.44 0.44 0.44 0.53 kW Starting current A Outdoor unit 0.07 0.08 0.095 0.095 0.095 0.114 0.09 0.095 0.095 0.095 0.114 0.4 0.4 0.8 0.8 0.8 0.8 0.5 0.7 0.7 0.7 0.8 PU-1.6 PU-2 PU-2.5 PU-3 PU-3 PU-4 PU-2 PU-2.5 PU-3 PU-3 PU-4 12 OC129A-1.qxp 01.10.1 7:33 PM 5 Page 13 DATA 1. PERFORMANS DATA W Outdoor unit PU-3JB COOLING CAPACITY 50Hz Service Ref. Temperature Outdoor D.B. Indoor W.B. 16˚C (60.8˚ F) 18˚C (64.4˚ F) 21˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (69.8˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 25˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (77˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 30˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (86˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 32.2˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (90˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 35˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (95˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 40˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (104˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 40.6˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (105˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 45˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (113˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 46˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (115˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 50˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (69.8˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 52˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (125.5˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) Evaporator airflow (CMM) Bypass factors S.H.F. at rating conditions PK-2FLA3 T.C. C.F. (T.I.) 5.6 0.81 6.0 0.82 6.2 0.83 6.2 0.83 6.4 0.84 6.7 0.86 5.5 0.84 5.9 0.85 6.0 0.86 6.1 0.86 6.2 0.87 6.6 0.89 5.3 0.90 5.6 0.92 5.8 0.93 5.9 0.93 6.0 0.94 6.4 0.96 5.2 0.93 5.5 0.95 5.7 0.96 5.8 0.97 5.9 0.97 6.3 0.99 5.1 0.96 5.4 0.99 5.6 1.00 5.7 1.00 5.8 1.01 6.2 1.04 4.9 1.03 5.2 1.06 5.4 1.07 5.4 1.08 5.5 1.08 5.9 1.11 4.8 1.04 5.2 1.06 5.3 1.08 5.4 1.08 5.5 1.09 5.9 1.12 4.6 1.10 4.9 1.12 5.1 1.14 5.2 1.15 5.3 1.16 5.7 1.20 4.6 1.11 4.9 1.14 5.1 1.15 5.1 1.16 5.2 1.17 5.6 1.21 4.4 1.16 4.7 1.19 4.9 1.21 4.9 1.22 5.0 1.23 5.4 1.28 4.3 1.19 4.6 1.22 4.7 1.24 4.8 1.25 4.9 1.26 5.3 1.31 14 0.16 0.73 PK-1.6FLA3 C.F. T.C. (T.I.) 3.9 0.81 4.2 0.82 4.3 0.83 4.4 0.83 4.4 0.84 4.7 0.86 3.8 0.84 4.1 0.85 4.2 0.86 4.3 0.86 4.3 0.87 4.6 0.89 3.7 0.90 3.9 0.92 4.1 0.93 4.1 0.93 4.2 0.94 4.5 0.96 3.6 0.93 3.9 0.95 4.0 0.96 4.0 0.97 4.1 0.97 4.4 0.99 3.5 0.96 3.8 0.99 3.9 1.00 4.0 1.00 4.0 1.01 4.3 1.04 3.4 1.03 3.6 1.06 3.7 1.07 3.8 1.08 3.9 1.08 4.1 1.11 3.4 1.04 3.6 1.06 3.7 1.08 3.8 1.08 3.8 1.09 4.1 1.12 3.2 1.10 3.4 1.12 3.6 1.14 3.6 1.15 3.7 1.16 3.9 1.20 3.2 1.11 3.4 1.14 3.5 1.15 3.6 1.16 3.6 1.17 3.9 1.21 13 0.18 0.81 PK-2.5FLA3/4 T.C. C.F. (T.I.) 7.0 0.81 7.5 0.82 7.7 0.83 7.8 0.83 7.9 0.84 8.4 0.86 6.9 0.84 7.3 0.85 7.6 0.86 7.7 0.86 7.8 0.87 8.3 0.89 6.6 0.90 7.1 0.92 7.3 0.93 7.4 0.93 7.5 0.94 8.0 0.96 6.5 0.93 6.9 0.95 7.2 0.96 7.3 0.97 7.4 0.97 7.9 0.99 6.3 0.96 6.8 0.99 7.0 1.00 7.1 1.00 7.2 1.01 7.7 1.04 6.1 1.03 6.5 1.06 6.7 1.07 6.8 1.08 6.9 1.08 7.4 1.11 6.0 1.04 6.4 1.06 6.7 1.08 6.8 1.08 6.9 1.09 7.4 1.12 5.8 1.10 6.2 1.12 6.4 1.14 6.5 1.15 6.6 1.16 7.1 1.20 5.7 1.11 6.1 1.14 6.3 1.15 6.4 1.16 6.5 1.17 7.0 1.21 5.5 1.16 5.9 1.19 6.1 1.21 6.2 1.22 6.3 1.23 6.7 1.28 5.3 1.19 5.7 1.22 5.9 1.24 6.0 1.25 6.1 1.26 6.6 1.31 20 0.11 0.81 PK-3FLA2 T.C. C.F. (T.I.) 7.2 0.81 7.7 0.82 7.9 0.83 8.0 0.83 8.2 0.84 8.7 0.86 7.1 0.84 7.5 0.85 7.8 0.86 7.9 0.86 8.0 0.87 8.5 0.89 6.8 0.90 7.3 0.92 7.5 0.93 7.6 0.93 7.7 0.94 8.2 0.96 6.7 0.93 7.1 0.95 7.4 0.96 7.5 0.97 7.6 0.97 8.1 0.99 6.5 0.96 7.0 0.99 7.2 1.00 7.3 1.00 7.4 1.01 7.9 1.04 6.2 1.03 6.7 1.06 6.9 1.07 7.0 1.08 7.1 1.08 7.6 1.11 6.2 1.04 6.6 1.06 6.9 1.08 6.9 1.08 7.1 1.09 7.6 1.12 5.9 1.10 6.4 1.12 6.6 1.14 6.7 1.15 6.8 1.16 7.3 1.20 5.9 1.11 6.3 1.14 6.5 1.15 6.6 1.16 6.7 1.17 7.2 1.21 5.6 1.16 6.0 1.19 6.2 1.21 6.3 1.22 6.5 1.23 6.9 1.28 5.5 1.19 5.9 1.22 6.1 1.24 6.2 1.25 6.3 1.26 6.8 1.31 20 0.12 0.76 PK-3FLA3/4/5 T.C. C.F. (T.I.) 0.81 7.9 0.82 8.4 0.83 8.7 0.83 8.8 0.84 9.0 0.86 9.5 0.84 7.8 0.85 8.3 0.86 8.5 0.86 8.6 0.87 8.8 0.89 9.4 0.90 7.5 0.92 8.0 0.93 8.2 0.93 8.3 0.94 8.5 0.96 9.0 0.93 7.3 0.95 7.8 0.96 8.1 0.97 8.2 0.97 8.3 0.99 8.9 0.96 7.2 0.99 7.6 1.00 7.9 1.00 8.0 1.01 8.2 1.04 8.7 1.03 6.8 1.06 7.3 1.07 7.6 1.08 7.7 1.08 7.8 1.11 8.3 1.04 6.8 1.06 7.3 1.08 7.5 1.08 7.6 1.09 7.8 1.12 8.3 1.10 6.5 1.12 7.0 1.14 7.2 1.15 7.3 1.16 7.5 1.20 8.0 1.11 6.4 1.14 6.9 1.15 7.1 1.16 7.2 1.17 7.4 1.21 7.9 1.16 6.2 1.19 6.6 1.21 6.9 1.22 6.9 1.23 7.1 1.28 7.6 1.19 6.0 1.22 6.5 1.24 6.7 1.25 6.8 1.26 6.9 1.31 7.4 20 0.12 0.73 PK-3FLA2/3/4/5 W T.C. C.F. (T.I.) 0.81 7.5 0.82 8.0 0.83 8.3 0.83 8.4 0.84 8.5 0.86 9.0 0.84 7.4 0.85 7.8 0.86 8.1 0.86 8.2 0.87 8.4 0.89 8.9 0.90 7.1 0.92 7.6 0.93 7.8 0.93 7.9 0.94 8.1 0.96 8.6 0.93 7.0 0.95 7.4 0.96 7.7 0.97 7.8 0.97 7.9 0.99 8.4 0.96 6.8 0.99 7.3 1.00 7.5 1.00 7.6 1.01 7.7 1.04 8.3 1.03 6.5 1.06 6.9 1.07 7.2 1.08 7.3 1.08 7.4 1.11 7.9 1.04 6.5 1.06 6.9 1.08 7.1 1.08 7.2 1.09 7.4 1.12 7.9 1.10 6.2 1.12 6.6 1.14 6.8 1.15 6.9 1.16 7.1 1.20 7.6 1.11 6.1 1.14 6.5 1.15 6.8 1.16 6.9 1.17 7.0 1.21 7.5 20 0.12 0.75 PK-4FLSA2/3/4 T.C. C.F. (T.I.) 0.81 9.8 0.82 10.5 0.83 10.8 0.83 10.9 0.84 11.1 0.86 11.8 0.84 9.6 0.85 10.2 0.86 10.6 0.86 10.7 0.87 10.9 0.89 11.6 0.90 9.3 0.92 9.9 0.93 10.2 0.93 10.3 0.94 10.5 0.96 11.2 0.93 9.1 0.95 9.7 0.96 10.0 0.97 10.2 0.97 10.3 0.99 11.0 0.96 8.9 0.99 9.5 1.00 9.8 1.00 9.9 1.01 10.1 1.04 10.8 1.03 8.5 1.06 9.1 1.07 9.4 1.08 9.5 1.08 9.7 1.11 10.3 1.04 8.4 1.06 9.0 1.08 9.3 1.08 9.5 1.09 9.6 1.12 10.3 1.10 8.1 1.12 8.6 1.14 8.9 1.15 9.1 1.16 9.3 1.20 9.9 1.11 8.0 1.14 8.6 1.15 8.9 1.16 9.0 1.17 9.2 1.21 9.8 1.16 7.6 1.19 8.2 1.21 8.5 1.22 8.6 1.23 8.8 1.28 9.4 1.19 7.4 1.22 8.0 1.24 8.3 1.25 8.4 1.26 8.6 1.31 9.2 28 0.12 0.73 Notes: 1. T.C.: Total capacity (kW) … (kcal/h)=(kW)x860, (Btu/h)=4x(kW)x860 C.F.(T.I.) : Correction factors of Total input(Indoor unit input + Outdoor unit input) 2. (°F)=32+9/5(°C) Lower limit … Indoor : D.B. 21°C(70°F), W.B. 15.5°C(60°F), Outdoor : D.B. 21°C(70°F). 3. Guaranteed operating range(cooling) Upper limit … Indoor : D.B. 35°C(95°F), W.B. 22.5°C(72.5°F), Outdoor : D.B. 46°C(115°F)…VLJ, VJB, YJB. W W Outdoor : D.B. 52°C(125.5°F)…VJA, YJA. { COOLING CAPACITY correction factors 50Hz Service Ref. PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3/4 PK-3FLA2/3/4/5 PK-4FLSA2/3/4 Refrigerant piping length (one way) 5m (16ft) 1.0 1.0 1.0 1.0 1.0 10m (33ft) 0.992 0.985 0.983 0.978 0.984 15m (49ft) 0.987 0.975 0.972 0.962 0.974 20m (66ft) 0.982 0.964 0.961 0.948 0.964 13 25m (82ft) — 0.954 0.951 0.934 0.954 30m (98ft) — 0.944 0.940 0.921 0.944 35m (115ft) — — — — 0.914 40m (13ft) — — — — 0.902 OC129A-1.qxp 01.10.1 7:33 PM Page 14 COOLING CAPACITY 60Hz Service Ref. Temperature Outdoor D.B. PK-2.5FLA3/4 T.C. C.F. (T.I.) 7.2 0.81 7.6 0.82 7.9 0.83 8.0 0.83 8.1 0.84 8.6 0.86 7.0 0.84 7.5 0.85 7.7 0.86 7.8 0.86 8.0 0.87 8.5 0.89 6.8 0.90 7.2 0.92 7.4 0.93 7.5 0.93 7.7 0.94 8.2 0.96 6.6 0.93 7.1 0.95 7.3 0.96 7.4 0.97 7.5 0.97 8.0 0.99 6.5 0.96 6.9 0.99 7.2 1.00 7.2 1.00 7.4 1.01 7.9 1.04 6.2 1.03 6.6 1.06 6.8 1.07 6.9 1.08 7.1 1.08 7.5 1.11 6.2 1.04 6.6 1.06 6.8 1.08 6.9 1.08 7.0 1.09 7.5 1.12 5.9 1.10 6.3 1.12 6.5 1.14 6.6 1.15 6.8 1.16 7.2 1.20 5.8 1.11 6.2 1.14 6.5 1.15 6.6 1.16 6.7 1.17 7.2 1.21 5.6 1.16 6.0 1.19 6.2 1.21 6.3 1.22 6.4 1.23 6.9 1.28 5.4 1.19 5.8 1.22 6.1 1.24 6.2 1.25 6.3 1.26 6.7 1.31 20 0.12 0.78 PK-2FLA3 T.C. Indoor W.B. 16˚C (60.8˚ F) 18˚C (64.4˚ F) 21˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (69.8˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 25˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (77˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 30˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (86˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 32.2˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (90˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 35˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (95˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 40˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (104˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 40.6˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (105˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 45˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (113˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 46˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (115˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 50˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (69.8˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) 16˚C (60.8˚ F) 18˚C (64.4˚ F) 52˚C 19˚C (66.2˚ F) 19.4˚C (67˚ F) (125.5˚ F) 20˚C (68˚ F) 22˚C (71.6˚ F) Evaporator airflow (CMM) Bypass factors S.H.F. at rating conditions C.F. (T.I.) 0.81 0.82 0.83 0.83 0.84 0.86 0.84 0.85 0.86 0.86 0.87 0.89 0.90 0.92 0.93 0.93 0.94 0.96 0.93 0.95 0.96 0.97 0.97 0.99 0.96 0.99 1.00 1.00 1.01 1.04 1.03 1.06 1.07 1.08 1.08 1.11 1.04 1.06 1.08 1.08 1.09 1.12 1.10 1.12 1.14 1.15 1.16 1.20 1.11 1.14 1.15 1.16 1.17 1.21 1.16 1.19 1.21 1.22 1.23 1.28 1.19 1.22 1.24 1.25 1.26 1.31 5.5 5.8 6.0 6.1 6.2 6.6 5.3 5.7 5.9 6.0 6.1 6.5 5.2 5.5 5.7 5.7 5.9 6.2 5.1 5.4 5.6 5.6 5.8 6.1 4.9 5.3 5.5 5.5 5.6 6.0 4.7 5.0 5.2 5.3 5.4 5.8 4.7 5.0 5.2 5.3 5.4 5.7 4.5 4.8 5.0 5.0 5.1 5.5 4.4 4.8 4.9 5.0 5.1 5.5 4.2 4.6 4.7 4.8 4.9 5.2 4.1 4.5 4.6 4.7 4.8 5.1 14 0.16 0.73 PK-3FLA2/3/4/5 T.C. C.F. (T.I.) 8.0 0.81 8.6 0.82 8.8 0.83 8.9 0.83 9.1 0.84 9.6 0.86 7.8 0.84 8.4 0.85 8.6 0.86 8.7 0.86 8.9 0.87 9.5 0.89 7.6 0.90 8.1 0.92 8.3 0.93 8.4 0.93 8.6 0.94 9.1 0.96 7.4 0.93 7.9 0.95 8.2 0.96 8.3 0.97 8.4 0.97 9.0 0.99 7.3 0.96 7.7 0.99 8.0 1.00 8.1 1.00 8.3 1.01 8.8 1.04 6.9 1.03 7.4 1.06 7.7 1.07 7.8 1.08 7.9 1.08 8.4 1.11 6.9 1.04 7.4 1.06 7.6 1.08 7.7 1.08 7.9 1.09 8.4 1.12 6.6 1.10 7.1 1.12 7.3 1.14 7.4 1.15 7.6 1.16 8.1 1.20 6.5 1.11 7.0 1.14 7.2 1.15 7.3 1.16 7.5 1.17 8.0 1.21 6.2 1.16 6.7 1.19 6.9 1.21 7.0 1.22 7.2 1.23 7.7 1.28 6.1 1.19 6.5 1.22 6.8 1.24 6.9 1.25 7.0 1.26 7.5 1.31 20 0.13 0.78 PK-4FLSA2/3/4 T.C. C.F. (T.I.) 11.0 0.81 11.8 0.82 12.1 0.83 12.3 0.83 12.5 0.84 13.2 0.86 10.8 0.84 11.5 0.85 11.9 0.86 12.0 0.86 12.2 0.87 13.0 0.89 10.4 0.90 11.1 0.92 11.4 0.93 11.6 0.93 11.8 0.94 12.6 0.96 10.2 0.93 10.9 0.95 11.3 0.96 11.4 0.97 11.6 0.97 12.4 0.99 10.0 0.96 10.6 0.99 11.0 1.00 11.1 1.00 11.4 1.01 12.1 1.04 9.5 1.03 10.2 1.06 10.5 1.07 10.7 1.08 10.9 1.08 11.6 1.11 9.5 1.04 10.1 1.06 10.5 1.08 10.6 1.08 10.8 1.09 11.6 1.12 9.1 1.10 9.7 1.12 10.0 1.14 10.2 1.15 10.4 1.16 11.1 1.20 9.0 1.11 9.6 1.14 9.9 1.15 10.1 1.16 10.3 1.17 11.0 1.21 8.6 1.16 9.2 1.19 9.5 1.21 9.7 1.22 9.9 1.23 10.6 1.28 8.4 1.19 9.0 1.22 9.3 1.24 9.5 1.25 9.7 1.26 10.4 1.31 28 0.14 0.73 Notes: 1. T.C.: Total capacity (kW) … (kcal/h)=(kW)x860, (Btu/h)=4x(kW)x860 C.F.(T.I.) : Correction factors of Total input(Indoor unit input + Outdoor unit input) 2. (°F)=32+9/5(°C) Lower limit … Indoor : D.B. 21°C(70°F), W.B. 15.5°C(60°F), Outdoor : D.B. 21°C(70°F). 3. Guaranteed operating range(cooling) Upper limit … Indoor : D.B. 35°C(95°F), W.B. 22.5°C(72.5°F), Outdoor : D.B. 52°C(125.5°F). { COOLING CAPACITY correction factors 60Hz Service Ref. PK-2FLA3 PK-2.5FLA2/3/4 PK-3FLA2/3/4/5 PK-4FLSA2/3/4 Refrigerant piping length (one way) 5m (16ft) 1.0 1.0 1.0 1.0 10m (33ft) 0.985 0.978 0.971 0.980 15m (49ft) 0.975 0.963 0.950 0.966 20m (66ft) 0.964 0.948 0.931 0.952 14 25m (82ft) 0.954 0.934 0.913 0.939 30m (98ft) 0.944 0.921 0.896 0.926 35m (115ft) — — — 0.941 40m (131ft) — — — 0.902 OC129A-1.qxp 01.10.1 7:33 PM Page 15 2. STANDARD OPERATION DATA PK-1.6 FLA3 Service Ref. Outdoor Indoor side side Refrigerant circuit Electrical circuit Total MODE Capacity Input Indoor unit Service Ref. Cooling Cooling Cooling 3900 5600 4600 1.49 2.52 2.60 PK-1.6 PK-2FLA3 FLA3 W kW Phase , Hz Volts Amperes Outdoor unit Service Ref. Phase , Hz Volts Amperes Discharge pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Refrigerant pipe length Intake air temperature Discharge air temperature Intake air temperature PK-2FLA3 Mpa (o/f) Mpa (o/f) ˚C ˚C ˚C m D.B.˚C W.B.˚C D.B.˚C D.B.˚C W.B.˚C 1 , 50 220 0.32 PU-1.6 VLJA2 1 , 50 220 6.7 1.89 (19.3) 0.5 (5.1) 84 50 9 5 27 19 15.4 35 24 1 , 50 220 0.37 PU-2 VJA2 1 , 50 220 11.3 1.98 (20.2) 0.46 (4.69) 66 52 3 5 27 19 13.4 35 24 1 , 60 220 0.42 PU-2 NJA1 1 , 60 220 13.6 1.96 (20.0) 0.47 (4.79) 66 52 5 5 29 19 13.5 46 24 PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4 Cooling Cooling 7000 6650 2.56 3.54 PK-2.5FLA2 PK-2.5FLA3 PK-2.5FLA4 1 , 50 1 , 60 220 220 0.44 0.44 PU-2.5 PU-2.5 VJA2 NJA1 1 , 50 1 , 60 220 220 11.4 15.8 2.05 2.13 (20.9) (21.7) 0.47 0.44 (4.79) (4.49) 74.3 87 52 54 10.3 10 5 5 27 29 19 19 14.1 14.1 35 46 24 24 PK-3FLA2 Cooling Cooling 7200 6900 3.28 4.19 PK-3FLA2 1 , 50 220 0.44 PU-3 VJA2 1 , 50 220 15.1 1.99 (20.3) 0.47 (4.79) 62 51 6 5 27 19 13.7 35 24 1 , 60 220 0.44 PU-3 NJA1 1 , 60 220 20.9 2.07 (21.1) 0.44 (4.49) 70 53 4 5 29 19 13.2 46 24 PK-3FLA3 PK-3FLA4 PK-3FLA5 Cooling Cooling 7900 6900 3.28 4.19 PK-3FLA3 PK-3FLA4 PK-3FLA5 1 , 50 1 , 60 220 220 0.44 0.44 PU-3 PU-3 VJC NJA1 1 , 50 1 , 60 220 220 15.1 20.9 1.99 2.07 (20.3) (21.1) 0.47 0.44 (4.79) (4.49) 86 70 51 53 6 4 5 5 27 29 19 19 13.0 13.2 35 46 24 24 PK-3FLA2 PK-4FLSA2 PK-3FLA3 PK-4FLSA3 PK-3FLA4 PK-3FLA5 PK-4FLSA4 Cooling Cooling Cooling 7500 9800 9900 3.28 3.46 5.08 PK-3FLA2 PK-4FLSA2 PK-3FLA3 PK-4FLSA3 PK-3FLA4 PK-3FLA5 PK-4FLSA4 1 , 50 1 , 60 1 , 50 220 220 220 0.53 0.53 0.44 PU-4 PU-4 PU-3 YJSA3 TJSA3 VJB 1 , 50 3 , 50 3 , 60 220 220 220 12.4 5.7 14.0 1.94 1.80 1.93 (19.8) (18.4) (19.7) 0.48 0.48 0.45 (4.85) (4.89) (4.59) 76 65 74 51.4 49 52 5 6 5 5 5 5 27 27 29 19 19 19 13.4 13.9 13.2 35 35 46 24 24 24 Total Electrical circuit Refrigerant circuit Indoor side Outdoor side The unit of pressure has been changed to Mpa on the international system of unit(SI unit system). The converted score against the traditional unit system can be gotten according to the formula below. 1(Mpa)=10.2(O/F·G) 3. ADDITIONAL REFRIGERANT CHARGE (R-22…kg(lbs)) Service Ref. PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3/4 PK-3FLA2 PK-3FLA3/4/5 PK-4FLSA2/3/4 Outdoor unit precharged (kg) (up to 20m) VL---1.3, V---1.79, N---1.9 V---2.4, N---2.4 V---3.08, Y---2.88, N---3.5 V---2.8, Y---2.8, N---3.5 VL---3.8, Y---4.6, T---4.6 20m (66ft) 0 0 0 0 0 0 Refrigerant 25m (82ft) — 0.06(0.13) 0.06(0.13) 0.06(0.13) 0.06(0.13) 0.15(0.33) piping length (one way) 30m (98ft) 35m (115ft) — — 0.12(0.26) — 0.12(0.26) — 0.12(0.26) — 0.12(0.26) — 0.30(0.66) 0.45(0.99) 40m (131ft) — — — — — 0.6(1.32) 60Hz 50Hz Frequency 4. OUTLET AIR SPEED AND COVERAGE RANGE Configuration Wall mounted Model Airflow Air speed Coverage rangew Airflow Air speed Coverage rangew m /min m/sec. m(ft) m3/min m/sec. m(ft) 3 PK-1.6FLA PK-2FLA PK-2.5FLA PK-3FLA PK-4FLSA 13 4.0 9.1(30) — — — 14 4.3 9.8(32) 14 4.3 9.8(32) 20 4.9 12.4(41) 20 4.9 12.4(41) 20 4.9 12.4(41) 20 4.9 12.4(41) 28 5.4 15.3(50) 28 5.4 15.3(50) w The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from the unit at the Hi notch position/ The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture inside the room. 15 OC129A-1.qxp 6 01.10.1 7:33 PM Page 16 OUTLINES AND DIMENSIONS Unit : mm 1. REMOTE CONTROLLER 57 18 3 58 19 CHECK TEST RUN MODEL SELECT ˚C AMPM ˚C AM PM AMPM NOT AVAILABLE AM PM ON/OFF NOT AVAILABLE TEMP 162 153 ON / OFF TEMP 55 PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2, PK-2.5FLA3 PK-3FLA2, PK-3FLA3, PK-3FLA4 PK-4FLSA2, PK-4FLSA3 PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 16 Front (Height ut unit) 68- 5 hole 53 491 476 450 405 Gas pipe position Liquid pipe position 2 X5 - 2.9 hole for tapping screw Knock out hole for left-rear piping Tapping screw 277 300 0 45 85 80 5 2. 323 276 229 R5 179 150 330 1250 60 24 0 190 Knock out hole for left-rear piping 447 (375) (178) 300 286X 2 227 2 Bass pipe 1 Liquid pipe Drainage 50 2 tapping screws for installation plate 0 35 53 80 130 177 Rear piping hole 13- 14 hole (Necessary clearance for Unit installation) 130 or less Right side Left side 60 (100 for left-hand side piping) 150 or more 70 73 (Width of unit) .5 35 Ref.pipes & drain pipe Knock out hole for left-hand side piping 150 174 224 Sleeve Through hole 90 90~ 100 Details of installation plate w 1 Sleeves are available on the market. w 2 This size shows the lower end of through hole. 2-unit hangers Unit cennter 50 or more Service space required around indoor unit Gas pipe Drain pipe Lequid pipe 70 R5 2 215 80 271 47 70 25 318 3/8F 5/8F 2 1 976 479 Air outlet Knock out hole for piping 1100 Drainage(Flexible hole: length 1200) 685 635 Terminal block & pipe position Lower side 500 (manual) 236 227 553 A 26 200 190 60 Installation bolt position Right side 15 or less bolt A B Knock out hole for piping 70 20 8 Knock out hole for under-piping (2:1) 60 8 Knock-out hole for night-hand side piping (2:1) Knock out hole for right piping B Knock out hole for piping Terminal block for control 170 200 Right side Terminal block Air intake Terminal block for power supply 222 143 173 223 Service panel for power supply connection 449 Air intake Auto vanes Lower side 48 16 -louvers 479 Air outlet 449 Air intake 168 1250 91 968 Air intake 213 4 Front 8 Pipe position Left side 625 30 or more 180 or more 374 405 450 476 486 9 17 8 65 2. INDOOR UNIT PK-1.6FLA3 PK-2FLA3 20 01.10.1 7:33 PM 70 OC129A-1.qxp Page 17 Unit : mm 37 74 A 30 32-ø12 hole for bolt 66-ø6 hole for tapping screw Wall fixture 100 4 39 225 18 39 990 180 12-ø6 hole for tapping screw 240 on left-hand side C 30 455 39 610 91 314 285 19 245 90 25 Drain hose for left-hand side piping Knock out hole for left piping Left side Range for left rear piping opening 280 Drainage range on right-hand side 37 74 Unit center 10 91=(910) 900 18 Drainage range 98 32 B 37 65 Knock out hole for piping A 100 4 340 30 10 184 30 30 80 29 280 18 45 45 Front 235 552 Air outlet Liquid pipe 235 Refrigerant pipe. Drain pipe Change vane (manual) Under panel Removable at left-hand side piping Knock out hole for under-piping 1120 Auto vane Lower side 1110 Drain hose 45 62.5 13 Top 1400 1090 Air intake 235 552 Air outlet 235 Rear piping opening 60 183 240 235 Right side Terminal block for control 197 B Terminal block for power supply Gas pipe Drain hose Bolt 15 C Knock out hole for right piping Refrigerant pipe. Drain pipe Liquid pipe 9.52(3/8F) Gas pipe 15.88(5/8F) (Liquid pipe) 55 (Gas pipe) 107 120 111 42 01.10.1 7:33 PM 58 OC129A-1.qxp Page 18 PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA5 Unit : mm 19 295 225 39 180 314 285 19 245 90 Range for left rear piping opening 280 750 Drainage range 91 on right-hand side 595 12-ø6 hole for tapping screw 240 25 Knock out hole for left piping 340 Drain hose for left-hand side piping 37 74 C 30 13 91=(1183) 900 Drainage range on left-hand side 18 Range for left rear piping opening 41-ø12 hole for bolt 18 1270 Unit center 98 32 Wall fixture 39 B 37 65 Knock out hole for wiring Unit out line 37 74 A 30 84-ø6 hole for tapping screw 100 4 39 A 100 4 Left side 235 10 184 30 30 80 29 280 30 Rear piping opening Auto vane 45 1680 Front 235 Drain hose 235 694 Air outlet 183 Under panel (Removable at left-hand side piping) Refrigerant pipe. Drain pipe Knock out hole for under-piping 235 Right side 240 (Liquid pipe) B 55 (Gas pipe) 102 120 111 Terminal block for power supply Gas pipe C Gas pipe 19.05(3/4F) Liquid pipe 9.52(3/8F) Bolt Terminal block for control 15 Change vane (manual) Lower side 1400 45 Knock out hole for right piping 235 Liquid pipe 1370 Air intake 45 1110 Drain hose 235 694 Air outlet 45 62.5 13 Top 42 PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 58 01.10.1 7:33 PM 60 197 OC129A-1.qxp Page 19 Unit : mm OC129A-1.qxp 01.10.1 7:33 PM 7 Page 20 WIRING DIAGRAM L N PK-1.6FLA3 PK-2FLA3 POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz GRN/YLW 10.6VAC 220V TB2 YLW RED 240V 14.5VAC T MV 7 W.B SW1 LS ORN 230V 7 MF LD1 CNB W.R 1 3 5 FAN CNV VANE POWER 12345678 12345 CN28 1 2 3 4 5 6 WHT 2 1 ON OFF L.TEST CN70 WIRELESS TO OUTDOOR UNIT CONNECTING WIRES DC12V RT1 VANE TWIN.1 SW2 CN2 TWIN.2 SW1 JR TIMER CN2A INTAKE 2 1 RT2 CN23 123 CN2B 1 3 2 1 7 ON OFF YLW 2 1 CN20 SW3 TB4 ORN 2 1 PIPE CN30 CN21 ZNR OUTDOOR CN51 MULTIPLE F1 X4 X4 BRN BRN WHT RED RED 4 3 2 1 CN4T TRANS 1 3 CNT TRANS 1 3 F2 YLW RED CND 1 3 BLU BLK 1 3 5 BLK BLK WHT RED I.B Ru C REMORT CONTROLLER RED PK-1.6FLA3 PK-2FLA3 SW1 ON OFF 1 2 3 4 5 6 7 8 SYMBOL C CN2<I.B> CN2A<I.B> CN2B<I.B> CN23<I.B> CN28<I.B> CN51<I.B> F1,2<I.B> I.B JR NAME SYMBOL NAME FAN MOTOR CAPACITOR LD1<W.B> RUN INDICATOR LED TIMER ADAPTOR CONNECTOR MF FAN MOTOR TRANSMISSION WIRES No.1 CONNECTOR MV VANE MOTOR TRANSMISSION WIRES No.2 CONNECTOR ROOM TEMPERATURE THERMISTOR RT1 VANE POSITION CONNECTOR (0%/15k",25°C/5.4k" DETECT) TIME SHORTENING CONNECTOR PIPE TEMPERATURE THERMISTOR RT2 MULTIPLE CONNECTOR (0%/15k". 25°C/5.4k" DETECT FUSE(6.3A 250V) Ru<W.B> RECEIVING UNIT INDOOR CONTROLLER BOARD SW1<I.B> FUNCTION SWITCH FUNCTION SELECTOR JUMPER RESISTORS SW2<I.B> UNIT SELECTOR SWITCH SYMBOL SW3<I.B> SW1<W.B> T TB2 TB4 X4<I.B> ZNR W.B W.R SW1 ON OFF 1 2 3 4 5 6 7 8 NAME EMERGENCY OPERATION SWITCH ON/OFF SWITCH TRANSFORMER POWER SUPPLY TERMINAL BLOCK INDOOR/OUTDOOR CONNECTING WIRE TERMINAL BLOCK FAN MOTOR RELAY VARISTOR WIRELESS REMOTE CONTROLLER BOARD WIRELESS REMOTE CONTROLLER NOTES: 1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the indoor controller board as shown is fig:w1. SW1 SW1 fig w1 Indoor fan motor (MF) for 230,240V. ON OFF ON OFF 12345678 12345678 2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing. 3. Since the indoor transformer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig * : 2. fig w2 When power supply is 230V 220V 220V YELLOW 230V ORANGE 240V RED 4. Symbols used in wiring diagram above are, : Connector, : Terminal block. 5. Emergency operation If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board. [Check items] (1) Compressor and fan. (2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is functioning emergency operation is not possible unless the cause is removed. Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible). [Emergency operation procedure] (1) Set the dip switch (SW3<I.B>) on the indoor controller board to 1 • 2 on and 3 off for cooling. (2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation indoor fan runs at high speed but automatic vane remains stop. If vane is closed open the vane by hands/ (4) Thermostat will not function. (5) Emergency cooling should be limited to 10 hours maximum. (The indoor unit heat exchanger may freeze). 20 OC129A-1.qxp 01.10.1 7:33 PM Page 21 PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 PK-3FLA2, PK-3FLA3, PK-3FLA4 , PK-3FLA5 PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 L N POWER SUPPLY ~(1 PHASE) AC220-240V 50Hz AC220V 60Hz GRN/YLW 10.6VAC 220V MF TB2 RED ORN YLW 230V C 14.5VAC BRN RED BRN RED LD1 SW1 7 FAN1 CND 1 3 1 3 5 F2 4 3 2 1 CN4T TRANS 1 3 CNT TRANS POWER F1 6 X4 6 1 SW3 7 MODELS PK-2.5FLA PK-3FLA ON OFF NAME FAN MOTOR CAPACITOR TIMER ADAPTOR CONNECTOR TRANSMISSION WIRES No.1 CONNECTOR TRANSMISSION WIRES No.2 CONNECTOR DRAIN LEFT-UP MECHANISM VANE POSITION CONNECTOR TIME SHORTENING CONNECTOR MULTIPLE CONNECTOR FUSE(6.3A 250V) INDOOR CONTROLLER BOARD FUNCTION SELECTOR JUMPER RESISTORS 2 1 TO OUTDOOR UNIT CONNECTING WIRES DC12V RT2 RT1 PK-4FLSA ON OFF 12345678 SYMBOL C CN2<I.B> CN2A<I.B> CN2B<I.B> CN23<I.B> CN27<I.B> CN28<I.B> CN51<I.B> F1,2<I.B> I.B JR TB4 REMOTE CONTROLLER CN28 12345678 12345 SW1 CN20 INTAKE W.R MV L.TEST 1 2 3 4 5 6 CN70 SW2 WIRELESS ORN YLW 2 1 TWIN-1 ON OFF CN2 TWIN-2 SW1 JR PIPE TIMER CN2A CN21 DRAIN CN27 123 CN2B CN50 1 D.U.M ON OFF 3 2 1 1 2 3 4 5 CN30 VANE ZNR X4 OUTDOOR 2 1 CN51 MULTIPLE CN6V W.B CNB Ru YLW RED BLU WHT T RED WHT BLK I.B 7 240V 12345678 SYMBOL NAME MF FAN MOTOR MV VANE MOTOR ROOM TEMPERATURE THERMISTOR RT1 (0%/15k",25°C/5.4k" DETECT) PIPE TEMPERATURE THERMISTOR RT2 (0%/15k". 25%/5.4k" DETECT Ru<W.B> RECEIVING UNIT SW1<I.B> FUNCTION SWITCH SW2<I.B> UNIT SELECTOR SWITCH SW3<I.B> EMERGENCY OPERATION SWITCH TRANSFORMER T SYMBOL NAME TB2 POWER SUPPLY TERMINAL BLOCK INDOOR/OUTDOOR CONNECTING WIRE TB4 TERMINAL BLOCK X4<I.B> FAN MOTOR RELAY VARISTOR ZNR SW1<W.B> ON/OFF SWITCH LD1<W.B> RUN INDICATOR LED WIRELESS REMOTE CONTROLLER BOARD W.B WIRELESS REMOTE CONTROLLER W.R NOTES: 1. Since the indoor fan motor (MF) is connected with 220V power, using 230, 240V power will require a setting change of the dip switch (SW1<I.B>) on the indoor controller board as shown is fig:w1. SW1 SW1 fig w1 Indoor fan motor (MF) for 230,240V. ON OFF 12345678 ON OFF 12345678 2. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing. 3. Since the indoor transformer (T) is connected with 220V power, if 230,240V power is used. Change the wiring connection showing fig * : 2. fig w2 When power supply is 230V 220V 220V YELLOW 230V ORANGE 240V RED 4. Symbols used in wiring diagram above are, : Connector, : Terminal block. 5. Emergency operation If remote controller of microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board. [Check items] (1) Compressor and fan. (2) Check the trouble position using self diagnostic function. If the result of self diagnosis indicates protective device such as freeze protection is functioning emergency operation is not possible unless the cause is removed. Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with remote controller is not possible). [Emergency operation procedure] (1) Set the dip switch (SW3<I.B>) on the indoor controller board to 1 • 2 on and 3 off for cooling. (2) Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker in this order. (3) During emergency operation indoor fan runs at high speed but automatic vane remains stop. (4) Thermostat will not function. (5) Emergency cooling should be limited to 10 hours maximum. (The indoor unit heat exchanger may freeze). 21 OC129A-1.qxp 8 01.10.1 7:33 PM Page 22 REFRIGERANT SYSTEM DIAGRAM PK-1.6FLA3 / PU-1.6VLJA2 PK-2FLA3 / PU-2VJA2, PU-2NJA1 INDOOR UNIT PK-1.6 PK-2 Low pressure switch Refrigerant pipe [15.88(5/8) (with insulator) option Charge pIug Flexible tube Ball valve Distributor Indoor heat exchanger Check plug OUTDOOR UNIT PU-1.6/2J series High pressure switch Outdoor heat exchanger Flared connection Flared connection Indoor coil thermistor RT2 Strainer Accumulator Compressor Capillary tube for injection (Only PU-2VJA2) PU-2NJA1 Capillary tube Ball valve (with service port) Refrigerant pipe [9.52(3/8) (with insulator) option PU-1.6 (O.D.3.2 I.D.1.8 L900) PU-2 (O.D.4.0 I.D.2.0 L430) flow of refrigerant PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4, / PU-2.5VJA2, PU-2.5NJA1 PK-3FLA2 / PU-3VJA2, PU-3YJA3, PU-3NJA1 PK-3FLA3, PK-3FLA4, PK-3FLA5 / PU-3NJA1 PK-4FLSA2, PK-4FLSA3, PK-4FLSA4, / PU-4VLJSA2, PU-4YJSA3, PU-4TJSA2 INDOOR UNIT PK-2.5 PK-3 PK-4 PK-2.5 / PK-3 Refrigerant pipe [15.88(5/8) (with insulator) option PK-4 Refrigerant pipe [19.05(3/4) (with insulator) option Low pressure switch Flexible tube Charge Ball valve pIug Distributor Indoor heat exchanger High pressure switch OUTDOOR UNIT PU-2.5/3J series PU-4J series Check pIug Flared connection Strainer Flared connection Indoor coil thermistor RT2 Outdoor heat exchanger Accumulator Compressor Capillary tube Capillary tube for injection Only PU-2.5NJA1 PU-3YJA2 PU-2.5VJA2 PU-3YJA3 PU-3NJA1 PU-4YJSA2 PU-3VJA2 PU-4YJSA3 PU-4TJSA2 Refrigerant pipe [ 9.52(3/8) (with insulator) option Ball valve (with service port) flow of refrigerant Capillary tube size PU-2.5 (O.D.3.2 I.D.1.6 L760) 2pcs PU-3 (O.D.3.2 I.D.1.8 L800) 2pcs PU-4 (O.D.3.2 I.D.2.0 L840) 2pcs 22 OC129A-1.qxp 01.10.1 7:33 PM Page 23 PK-3FLA3, PK-3FLA4, PK-3FLA5 / PU-3VJC , PU-3YJC Refrigerant pipe [15.88(5/8") (with insulator) option Low pressure Flexible tube strainer switch Indoor heat exchanger Ball valve strainer Charge pIug High pressure switch Outdoor heat exchanger Check pIug Flared connection strainer Flared connection Indoor coil thermistor RT2 Accumulator Compressor Capillary tube Distributor with strainer (O.D.3.2 o I.D.1.8 o L800) o2pcs Ball valve (with service port) D.P.R. (Discharge pressure regulator) Refrigerant pipe [ 9.52(3/8") (with heat insulator) option flow of refrigerant PK-3FLA3, PK-3FLA4, PK-3FLA5 / PU-3VJB , PU-3YJB Refrigerant pipe [15.88(5/8") (with insulator) option Low pressure Flexible tube strainer switch Indoor heat exchanger Ball valve strainer Charge pIug High pressure switch Outdoor heat exchanger Check pIug Flared connection strainer Flared connection Indoor coil thermistor RT2 Accumulator Compressor Capillary tube Distributor with strainer (O.D.3.2 oI.D.1.8 oL800) o2pcs Ball valve (with service port) Refrigerant pipe [ 9.52(3/8") (with heat insulator) option 23 flow of refrigerant OC129A-1.qxp 9 01.10.1 7:33 PM Page 24 OPERATION FLOW-CHART 1. Main operation START 1 NO POWER SUPPLY Live YES NO NO ON/OFF button ON YES Protection device Self hold reset STOP YES Abnormal operation mode Protection device Self hold NO POWER lamp ON Self-diagnostic function Indicate & Memory EMERGENCY ALL STOP <Note 4> <Note 5> MODE SELECT button DRY COOL COOL OPERATION DRY OPERATION Note1. The unit starts operation by pressing the ON/OFF switch when unit is OFF. During operation, the unit stops operation by pressing the ON/OFF switch. In addition, operation can be turned ON/OFF with the centralized remote controller or the remote switch. Note2. The factors which cause “abnormal operation mode” are as follows. ● Outdoor unit abnormal operation. ● Fault of room temperature thermistor(RT1). ● Fault of indoor coil thermistor(RT2). ● Indoor coil frost protection mode. ● Fault of drain sensor(DS). ● Drain water overflow prevention mode. Refer to page 30 for abnormal operation, mode details. Note3. The indoor fan runs on the low speed for 1 minute to eliminate remaining heat. Note4. The compressor will not start for 3 minutes after the stop. Note5. The thermostat is continuously ON during the test run. Note6. Refer to page 31 for coil frost protection. Note7. Range A : Indoor coil temperature is more than 5 degrees above room temperature. Range B : Indoor coil temperature is within 5 degrees either way of room temperature. Range C : Indoor coil temperature is more than 5 degrees below room temperature. 24 OC129A-1.qxp 01.10.1 7:33 PM Page 25 2. COOL operation YES COOL operation 3 min. delay NO YES 6-minute time delay Allowance NO NO NO YES Compressor start 3 minutes elapse Coil frost protection check mode 6-minute time delay <Note 7> Coil frost protection <Note 8> Allowance set NO Range C NO YES NO Compressor start 10 minutes elapse Allowance release Indoor coil temperature 10°C or bellow Coil frost prevention NO <Note 6> Compressor themostat ON YES NO NO YES Continue 1 minute YES Fan speed LOW 3-minute time delay Compressor start 16 minutes elapse YES NO Allowance release NO Coil frost prevention release NO Fan speed LOW 5 minutes elapse YES Indoor coil temperature 1°C or below Outdoor unit abnormality check mode NO Compressor ON Coil frost prevention set Compressor ON Compressor OFF 1 25 OC129A-1.qxp 01.10.1 7:33 PM Page 26 3. DRY operation Dry operation <Note 8> YES Room temperature 18°C or below NO Compressor ON NO YES Compressor ON 3 min. elapse NO NO Compressor ON 3 min. delay NO YES <Note 6> Compressor thermostat ON <Note 6> YES YES Compressor ON time completed YES Compressor thermostat ON NO NO Compressor OFF 10 minutes completed YES YES Compressor OFF 10-minute timer start <Note 9> Compressor ON time set YES Compressor OFF Compressor ON <Note 10> <Note 10> Fan stop Fan speed LOW 1 Note8. When room temperature is 18°C or below, the compressor can not turn ON. When the room temperature rises to 18°C or above, the compressor will start operation after a 3-minute time delay. Note9. Refer to page 30 for the compressor operation time. Note10. In DRY operation, the indoor fan runs on the low speed during the compressor ON and stops during the compressor OFF. 26 OC129A-1.qxp 01.10.1 7:33 PM 10 Page 27 MICROPROCESSOR CONTROL 1. OUTLINE OF MICROPROCESSOR CONTROL REMOTE CONTROLLER INPUT to remote controller ●Processes and transmits orders. OUTPUT to remote controller ● Indication LCD lights. ● OFF-ON switching. ● COOL • DRY • FAN selector switching. ● HIGH-LOW fan speed switching. ● TIMER mode selector-switching ● Timer setting. ● Self diagnostic troubleshooting. ● TEST RUN switching. ● CHECK mode switching. ● AUTO Vane setting. ˚C AM PM AM PM NOT AVAILABLE ON / OFF TEMP Indoor unit PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3 PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 INPUT from indoor unit ● Room temperature thermistor. ● Indoor coil thermistor. OUTPUT to indoor unit INDOOR CONTROLLER BOARD ● Receives orders from remote controller and temperature data from indoor unit. ● Processes orders and data. ● Controls indoor and outdoor operation. ● Self diagnostic function w System control operation.<Optional> w Emergency operation ● Fan: ON-OFF. ● Fan speed: HIGH-LOW. ● AUTO vane’s angle setting. ● Emergency stop. Non-polar, two (2) - core cable INPUT from outdoor unit ● Compressor protection device working. 12VDC Independent Control of Outdoor Unit OUTPUT UNIT ● Receives orders from indoor controller. ● Emergency stop. OUTPUT from outdoor unit ● Compressor motor and outdoor fan motor : ON-OFF. 27 Outdoor unit OC129A-1.qxp 01.10.1 7:33 PM Page 28 2. INDOOR UNIT CONTROL 2-1COOL operation <How to operate> 1 Press [ ON/OFF button. 2 Press MODE button to set operation mode to COOL ˚C . / / 3 Set desired temperature with or button. button. NOTE: 1. Set temperature changes by 1 °C in the range 19-30 °C AM PM AM PM NOT AVAILABLE ON / OFF / / each TEMP or button is pressed. 2. Set temperature is displayed on the LCD. TEMP PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3 PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 <COOL operation time chart> Operation starts by POWER button ON. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. Operation stops by POWER button OFF. ON Thermostat OFF LOW or HIGH ON Indoor fan OFF Depends on remote controller setting ON Auto vane LOW or HIGH OFF CLOSE CLOSE ON Compressor OFF MIN. 3 minutes w1 w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended. (1)Compressor control 1 3-minute time delay To prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when the room temperature is higher than the set temperature. The compressor stops when the room temperature is equal to or lower than the set temperature. 3 The compressor stops in check mode or during protective functions. 4 Coil frost prevention To prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 1°C or below after the compressor has been continuously operated for 16 minutes or more. The coil frost prevention is released under any of the following conditions. ● The indoor coil thermistor rises to 10°C or above. ● The room temperature becomes equal to or lower than the set temperature. ● COOL mode is stopped or changed to another mode. NOTE : By cutting the jumper wire JR02 on the indoor controller board, the temperature to start coil frost prevention changes from 1°C to - 3°C 28 OC129A-1.qxp 01.10.1 7:33 PM Page 29 5 Coil frost protection When the indoor coil temperature becomes - 15°C or below, coil frost protection will proceed as follows. <Start condition> After the compressor has been continuously operated for 3 minutes or more, and the indoor coil temperature has been 15°C or below for 3 minutes, the coil frost protection will start. <Coil frost protection> Compressor stops for 6 minutes, and then restarts. If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor units stop, and the remote controller displays this occurrence. <Termination conditions> Coil frost protection released when the start condition is not satisfied again during the allowance, or when the COOL mode stops changes another mode. (2)Indoor fan control Indoor fan speed depends on the remote controller setting. However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller setting. (3)Auto vane control Auto vane position depends on the remote controller setting. (4)Detecting abnormalities in the outdoor unit After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and the room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of RANGE C, the outdoor unit is functioning abnormally. Thus, the compressor will stop and the remote controller will display this occurrence. RANGE A : Indoor coil temperature is more than 5 degrees above room temperature. RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature. RANGE C : Indoor coil temperature is more than 5 degrees below room temperature. (5)AUTO VANE CONTROL 1 Frequency judgement When the unit operates for the first time after the circuit breaker turned to ON, the frequency, 50Hz or 60Hz, is judged by the horizontality sensing switch. If The frequency cannot be judged immediately for some reason, the sensing operation continues for 3 minutes with the vane motor at ON. If the frequency cannot be judged yet after 3-minute sensing, the vane motor turns to OFF. But the AIR DISCHARGE DIRECTION display continues to be indicated. 2 During cooling operation When the cooling operation starts, the vane is automatically set to the horizontal However, the desired direction among four below-listed can be selected with the vane button on the remote controller. a) 10° b) 30° downward c) 60° downward (PK-2.5, 3, 4FL(S)A) / 50° downward (PK-1.6, 2FLA) d) 70° downward (PK-2.5, 3, 4FL(S)A) / 60° downward (PK-1.6, 2FLA) 10° e) Automatic swing (only PK-2.5, 3, 4FL(S)A) NOTE : 30° is available only when the fan speed is HIGH. <AUTO RETURN> When discharge 50°, 60° or 70° continues for 1 hour with the fan speed at LOW, the discharge direction turns to the horizontal discharge automatically. NOTE1 : After that, 50°, 60° or 70° is available by setting with the remote controller, and it continues for 1 hour. NOTE2 : If the discharge direction changes from 50°, 60° or 70° , the direction returns to the horizontal discharge when 1 hour has passed since the discharge 60° started. NOTE3 : If the discharge direction changes from 50° or 60° (or 70° ) to the horizontal discharge, the 1-hour timer to return the horizontal discharge is cancelled. 3 During the operation OFF, the auto vane is in the airflow shut-off position. 4 When the vane motor is out of order or the connector is badly connected, the remote controller display of the remote controller does not change. 29 30° 60° (PK-2.5/3/4) 50° (PK-1.6/2) 70° (PK-2.5/3/4) 60° (PK-1.6/2) Automatic swing (PK-2.5/3/4) OC129A-1.qxp 01.10.1 7:33 PM Page 30 2-2 DRY operation <How to operate> 1 Press [ ON/OFF button. ˚C 2 Press MODE button to set operation mode to DRY AM PM . / / 3 Set desired temperature with or button. NOTE: 1. Set temperature changes by 1 °C in the range 19-30 °C AM PM NOT AVAILABLE ON / OFF / / each TEMP or button is pressed. 2. Set temperature is displayed on the LCD. TEMP PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3 PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 Operation starts by POWER button ON. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. Operation stops by POWER button OFF. ON Thermostat OFF LOW speed ON Indoor fan OFF Depends on remote controller setting ON Auto vane LOW speed OFF CLOSE CLOSE ON Compressor OFF MIN. 3 minutes w2 w2 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended. (1)Compressor control 1 3-minute time delay To prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when the room temperature is higher than the set temperature. The compressor stops when the room temperature is equal to or lower than the set temperature. 3 The compressor stops in check mode or during protective functions. 4 The compressor will not start when the room temperature is below 18 °C. The compressor starts intermittent operation when the power is turned ON with room temperature above 18 °C. The compressor ON/OFF time depends on the thermostat ON/OFF and the room temperature as follows. After 3-minute compressor operation, ● If the room temperature thermistor reads above 28 °C with thermostat ON, the compressor will operate will operate for 6 more minutes and then stop for 3 minutes. ● If the room temperature thermistor reads 26 °C ~ 28 °C with thermostat 0N, the compressor will operate for 4 more minutes and then stop for 3 minutes. ● If the room temperature thermistor reads 24 °C ~ 26 °C with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes. ● If the room temperature thermistor reads below 24 °C with thermostat ON, the compressor will stop for 3 minutes. ●If the thermostat is OFF, regardless of room temperature, the compressor will stop for 10 minutes. 5 Coil frost protection Coil frost protection in DRY operation is the same as in COOL operation. 6 Coil frost prevention Coil frost prevention does not operate in DRY operation. 30 OC129A-2.qxp 01.10.1 7:33 PM Page 31 (2) Indoor fan control The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote controller. Also, the indoor fan does not run during compressor OFF. (3)Auto vane control Same as in COOL operation. (4)Detecting abnormalities in the outdoor unit An abnormality in the outdoor unit can not be detected in DRY operation. 2-3 FAN operation <How to operate> 1 Press POWER ON/OFF button. CHECK TEST RUN MODEL SELECT ˚C AMPM ˚C AM PM AMPM NOT AVAILABLE AM PM NOT AVAILABLE ON/OFF TEMP ON / OFF FAN AUTO STOP VANE AUTO START MODE 2 Press MODE button to set operation mode to Fan . (1) Indoor fan control The indoor fan speed depends on the remote controller setting. (2) Auto vane control The auto vane position depends on the remote controller setting. CLOCK MODE FAN VANE STOP START HR MIN. CHECK LOUVER SET PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3 h TEST RUN min RESET CLOCK PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 2-4 TIMER operation CHECK TEST RUN MODEL SELECT ˚C AMPM ˚C AM PM AMPM NOT AVAILABLE AM PM NOT AVAILABLE ON/OFF TEMP <How to operate> 1 Push POWER ON/OFF button. 2 Check if or not the current time is correct. AUTO STOP AUTO START 3 Push the STOP / or START / button and select the desired time. min h 4 Set the timer time using HR / and MIN. / buttons. ON / OFF MODE FAN AUTO STOP VANE AUTO START CLOCK MODE FAN VANE STOP START HR MIN. CHECK LOUVER TEST RUN SET PK-1.6FLA3 PK-2FLA3 PK-2.5FLA2/3 PK-3FLA2/3/4 PK-4FLSA2/3 h min RESET CLOCK PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 31 OC129A-2.qxp 01.10.1 7:33 PM Page 32 Measure an impedance between the power supply terminal block and ground with a 500V Megger and check that it is equal to or greater than 1.0M". 2-5 Test run PK-1.6FLA3, PK-2FLA3 PK-2.5FLA2/3, PK-3FLA2/3/4 PK-4FLSA2/3 (1) Turn on the main power of unit. (2) Turn the adjusting switch on the back of the wireless remote controller to “SET” CHECK and TEST RUN will start flashing. Wireless remote controller with backside battery cover removed Display will start finishing. ˚C ★(3) Push the MIN button TEST RUN and the operating mode will be displayed (Refer to the illustrated sample display at left) AM PM AM PM Turn the adjusting switch to "SET" Display will start flashing NOT AVAILABLE Nrm Set 23 901 CLOCK 45 MODE Reset After refiling batteries. Press the reset button. 8 67 ★(4) Push the MODE button, change the mode to “FAN” and make sure that there will be blowout of air. ON / OFF FAN VANE STOP START HR MIN. ★(5) Push the MODE button, change the mode to COOL and make sure that there will be blowout of cool air. ★(6) Push the FAN button and make sure that there will be strong (or weak) blowout of air. ON / OFF For operations marked "★", point the transmitter to the wireless receiver, and make sure that you will hear a short beep from the receiver. ★(7) Push the VANE button and verify the operation of the auto vane. ★(8) Push the POWER ON/OFF button and cancel the test run. (9) After completing a test run, be sure to turn the adjusting switch back to “Nrm”. ● The test run automatically stops in 2 hours. ● Set temperature is not displayed during test run. Test run PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 A TEST RUN TEMP ON/OFF 6 FAN AUTO STOP VANE AUTO START 4 MODE 3 5 CHECK LOUVER Measure an impedance between the power supply terminal block and ground with a 500V Megger and check that it is equal to or greater than 1.0M". 1 Turn on the main power to the unit. TEST RUN 2 Press the button twice continuously. (Start this operation from the status of remote controller display turned off.) A TEST RUN and current operation mode are displayed. MODE 3 Press the ( ) button to activate COOL mode, then check whether cool air is blown out from the unit. FAN 4 Press the button and check whether strong air is blown out from the unit. VANE 5 Press the button and check whether the auto vane operates properly. 6 Press the ON/OFF button to stop the test run. Note: • Point the remote controller towards the indoor unit receiver while following steps 2 to 6. • It is not possible to run the in FAN, DRY mode. h min TEST RUN 2 SET RESET CLOCK 32 OC129A-2.qxp 01.10.1 7:33 PM Page 33 2-6 Emergency operation When the remote controller or microprocessor malfunctions and no other trouble exists, emergency operation is available by setting the dip switch on the controller board. [Check items] (1) Make sure the compressor and the fans are running normally. (2) Locate the trouble with the self-diagnostic function. If the self-diagnostic function indicates that the protection device (such as coil frost protection) is functioning, the sources must be removed before attempting emergency operation. Emergency operation ON/OFF is activated not with the remote controller but with the circuit breaker. [Emergency operation produce] (1)Cooling operation is available by setting the dip switch SW3 1and 2 ON and 3 OFF on the indoor controller board. (2)To start emergency operation, turn the outdoor side circuit breaker ON first, and then the indoor side circuit breaker ON. (3)During emergency operation, the indooor fan runs on HIGH speed, the compressor runs continuously, and the louver stops. (4)Thermostat will not function. (5)Do not use emergency cooling operation for more than 10 hours, as the indoor coil may freeze. SW3 SW3 INDOOR CONTROLLER BOARD ON OFF 1 2 3 COOLING 2-7 Function of jumper wire and dip switch on indoor controller board 1. Jumper wire 1 JR01:Jumper wire for the auto vanes Cut JR01 for the unit WITHOUT auto vanes. 2 JR02:Jumper wire for the temperature to start coil frost prevention Cutting JR02 changes the temperature from +1°C to -3°C. 3 JR03:Jumper wire for set temperature adjustment in HEAT mode In HEAT operation, heated air stagnates in the upper part of the room. The indoor unit installed in the upper part of the room will detect the air temperature higher than the actual temperature in the living space. This difference is about 4 degrees. Therefore, the temperature detected by the room temperature thermistor should be corrected 4 degrees down. The unit with JR04 attached will make this adjustment. 4 JR04:Jumper wire for the indoor fan speed during thermostat OFF in HEAT mode Cutting JR04 Changes the speed from Extra-Low to Low. 5 JR05:Jumper wire for detecting abnormalities in the outdoor unit Cutting JR05 makes this detection unavailable. (Occurrence of abnormality can not be detected.) 6 JR06:Jumper wire for auto restart function Cutting JR06 makes the auto restart function available. 2.Dip switch 1 SW1 (Function switch) ON OFF 1 2 3 4 5 6 7 8 SW1-1) Switch for power supply ON:220V OFF:230V, 240V SW1-2) Switch for single or twin control ON:Twin control OFF:Single control SW1-3) Switch for unit number in twin control (This switch is valid when SW1-2 is ON.) ON:Unit No.2 OFF:Unit No.1 33 OC129A-2.qxp 01.10.1 7:33 PM Page 34 SW1-4 ~ SW1-6) Switch for capacity of each model PK-1.6 PK-2.5 PK-3 PK-2 ON OFF PK-4 ON OFF 4 5 6 ON OFF 4 5 6 4 5 6 SW1-7 ~ SW1-8) Switch for the pair number of wireless remote controller 0 1 ON OFF 2 ON OFF 7 8 ON OFF 7 8 3 ON OFF 7 8 7 8 The pair number setting of the wireless remote controller is needed. (Refer to the next page for the details.) 2 SW2 (Unit switch) ON OFF 1 2 3 4 5 SW2-1) Switch for air conditioner with or without electric heater ON:Unit with electric heater OFF:Unit without electric heater SW2-2) Switch for air conditioner with or without heat pump ON:Unit with heat pump OFF:Unit without heat pump SW2-3, SW2-4, SW2-5) Switch for function code ON:Unit with electric heater OFF:Unit without electric heater PK-2.5 PK-3 PK-4 PK-1.6 PK-2 ON OFF ON OFF 3 4 5 3 4 5 3 SW3 (Emergency operation switch) Normal operation For emergency cooling 1 2 3 ON OFF 1 2 3 ON OFF 34 OC129A-2.qxp 01.10.1 7:33 PM Page 35 2-8 Wireless remote controller pair number setting operation PK-1.6FLA3, PK-2FLA3 PK-2.5FLA2/3, PK-3FLA2/3/4 PK-4FLSA2/3 Switches are located on the indoor unit PC board and inside the remote controller as shown. • Setting the SW1 (PC board inside indoor unit) Sub-switches 7 or 8 of SW1 can be used as follows to assign a pair No. Pair Number SW1 0 ON OFF 1 ON OFF Pair Number 12 34 5 6 78 12 34 5 6 78 SW1 2 ON OFF 3 ON OFF 12 34 5 6 78 12 34 5 6 78 • The pair No. SW of the remote controller has been set to ‹‹0›› at the time of ship-ment. Reset After refiling batteries. Press the reset button. Nrm Set 8 67 901 45 23 Note: Make sure that the pair No. A of the remote controller matches that of the indoor unit PC board. A PK-2.5FLA4 PK-3FLA5 PK-4FLSA4 A MODEL SELECT Model No. TEMP ON/OFF 4 MODE 1 Turn on the main power to the unit. 2 Press the SET button with the point of a ball-point pen or the like. Start this operation from the status of remote controller display turned off. MODEL SELECT blinks and Model No. is lighted. min 3 Press the button twice continuously. A Pair No. “0” blinks. 4 Press the temp button to set the pair number you want to set. 5 Press the SET button with the point of a ball-point pen or the like. Set pair number is lighted for three seconds then turned off. FAN AUTO STOP A Pair No. of wireless remote controller VANE AUTO START 0 Indoor PC board < SW1 > ON OFF 12 34 5 6 78 CHECK LOUVER h 1 min TEST RUN 12 34 5 6 78 5 1,4 SET RESET ON OFF 2 CLOCK ON OFF 12 34 5 6 78 3~9 ON OFF 12 34 5 6 78 35 OC129A-2.qxp 01.10.1 7:33 PM 11 Page 36 TROUBLESHOOTING 1. Self-diagnostic function [for PK-1.6FLA3, PK-2FLA3, PK-2.5FLD2/3, PK-3FLD2/3/4, PK-4FLSD2/3 ] (1) Turn on the main power of the unit. (2) Set the adjusting switch on the back of the wireless remote controller to “Set” CHECK and TEST RUN will start lighting. Remove the battery cover on the back side of the wireless remote controller, display will start flashing when the “Set” switch is turned on. For operations marked “★”, point the transmitter to the wireless receiver, and make sure that you will hear a short beep from the receiver. ★(3) Push the HR button, CHECK will start blinking. ★(4) Send the signal from the remote controller to the unit with pressing HR button. If the buzzer sound is heard and the ON/OFF lamp (unit display) blinks, refer to following table. ˚C AM PM Reset After refiling batteries. Press the reset button. AM PM NOT AVAILABLE 1 second (0.5 second interval) Beep This corresponds to the number of buzzer sound 45 23 901 Nrm Set 8 67 Buzzer sound The number of ON/OFF lamp (Unit display) blinking Turn the adjusting switch to "SET" ON / OFF MODE CLOCK The number of ON/OFF lamp (Unit display) blinking and buzzer sound Irregular point 1 Irregular intake sensor 2 Irregular piping sensor 4 Irregular drain sensor 5 Irregular drain pump 6 Freezing protected 8 Irregular outdoor unit 9 NO irregular FAN VANE STOP START HR MIN. Display will start flashing (Refer to next page in detail) ON / OFF ★(5) Push the POWER ON/OFF button and cancel the test run. (6) After completing a test run, be sure to turn the adjusting switch back to “Nrm”. For operations marked "★", point the transmitter to the wireless receiver, and make sure that you will hear a short beep from the receiver. 36 OC129A-2.qxp 01.10.1 7:33 PM Page 37 1. Self-diagnostic function [for PK-2.5FLA4, PK-3FLA5, PK-4FLSA4] 1 Turn on the main power to the unit. CHECK 2 Press the button twice continuously. • begins to light and refrigerant address display “00” begins to blink. • Start this operation from the status of remote controller display turned off h 3 While pointing the remote controller toward the unit’s receiver, press the button • If the buzzer sound is heard and the ON/OFF lamp (unit display) blinks, refer to following table. 4 While pointing the remote controller toward the unit’s receiver, press the ON/OFF button. • Self-check mode is cancelled. ON/OFF Alarm Check Code Suction sensor alarm Single beep ✕ 1 2 Plpe sensor alarm Single beep ✕ 2 3 Transmission alarm Single beep ✕ 3 4 Drain sensor alarm Single beep ✕ 4 Drain pump alarm Single beep ✕ 5 Anti-freezing on Single beep ✕ 6 Anti-overheat on Single beep ✕ 6 7 System error Single beep ✕ 7 8 Outdoor unit alarm Single beep ✕ 8 9 No alarm (no error) Receiving signal only (no error alarm) 6 4 Buzzer sound 1 5 TEMP ON/OFF MODE FAN AUTO STOP VANE AUTO START CHECK LOUVER h 3 2 min TEST RUN SET RESET CLOCK 2. OTHER TROUBLES AND CAUSES Auto vanes do not work. Power ON/OFF button is not available. Auto vane motor does not work. Connector is poorly connected. Auto vane motor is poorly assembled. Indoor controller board is damaged. Indoor/outdoor connecting wire is connected incorrectly. Indoor/outdoor connecting wire shorts. Compressor protector is damaged. Outdoor controller board is defective. Remote controller is damaged. Transmission wire is poorly connected 37 Auto vane motor is damaged. Auto vane motor relay is damaged. Transmission wire is damaged. Connector is poorly connected. OC129A-2.qxp 01.10.1 7:33 PM Page 38 3. How to check the parts PK-1.6FLA3, PK-2FLA3, PK-2.5FLA2/3/4, PK-3FLA2/3/4/5, PK-4FLSA2/3/4 Parts name Check points Room temperature thermistor (RT1) Pipe temperature thermistor (RT2) Disconnect the connector, then measure the resistance using a tester. (Surrounding temperature 10°C~30°C) Transformer Disconnect the connector and measure the resistance using a tester. Normal 4.3k'~9.6k' CNT T CN4T BRN WHT 1 2 3 4 1 2 3 YLW CNT(1)-(3) CN4T(1)-(2) CN4T(3)-(4) RED Abnormal Open or short Normal WHT. Approx. 135' Abnormal BRN. Approx. 0.5~2.0' RED. Approx. 1.0~2.0' Open or short Measure the resistance between the terminals using a tester. Fan motor Relay connector 1 Red 1 3 White 5 Black 3 5 Protector Normal PK- Motor terminal or Relay connector 1.6FLA3, 2FLA3 2.5FLD2/3/4, 3FLD2/3/4/5 4FLSA2/3/4 Red-White White-Black 114.5'i10% 118.2'i10% 99.5'i10% 103.5'i10% 62.6'i10% 74.0'i10% Thermal protector OFF : 125i5˚C ON : 125i5˚C Abnormal Open or short OFF : 130i5˚C ON : 80i20˚C Measure the resistance between the terminals using a tester. (Surrounding temperature 20°C~30°C) Vane motor Normal Orange Red M Connector Brown-Yellow Brown-Blue Red-Orange Red-Pink Blue Brown Pink Yellow 4 5 2 3 6 1 PK-1.6FLA3 PK-2FLA3 PK-2.5FLD2/3/4, PK-3FLD2/3/4/5, PK-4FLSA2/3/4 Abnormal 15k' 186~214' Open or short <Thermistor Characteristic graph> Thermistor for lower temperature < Thermistor for lower temperature > 50 Room temperature thermistor(RT1) Pipe temperature thermistor(RT2) Resistance (K") 40 Thermistor R0=15k' ± 3% Fixed number of B=3480k' ± 2% Rt=15exp { 3480( 0: 10: 20: 25: 30: 40: 1 273+t 1 )} 273 15k' 9.6k' 6.3k' 5.4k' 4.3k' 3.0k' 30 20 10 0 38 -20 -10 0 10 20 30 40 Temperature (:) 50 OC129A-2.qxp 01.10.1 7:33 PM 12 Page 39 DISASSEMBLY PROCEDURE PK-1.6FLA3, PK-2FLA3, PK-2.5FLA2/3/4, PK-3FLA2/3/4/5, PK-4FLSA2/3/4 OPERATING PROCEDURE PHOTOS&ILLUSTRATION 1. Removing the lower side of the indoor unit from the installation plate (1) Remove the 2 screws. Hang the indoor unit hangers to the catches on the installation plate. Figure 1 Hanger of indoor unit Catch of installation plate Metal fixture Screws 2. Removing the right side panel (1) Remove the 2 screws of the right side panel:one on the bottom and the other on the upper right-hand side. (2) Disconnect the connector from the adapter case. (3) Sliding the right side panel to the right, pull it out toward you. Figure 2 Connector Indoor controller board Right side panel Terminal cover Connector Electrical parts box cover 3. Removing the indoor controller board (1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and remove the cover. (3) Disconnect the connectors on the indoor controller board. (4) To unhook the catches on the right-hand side of the indoor controller board, pull the left-hand side toward you and lift up the cover to the right. Then the indoor controller board can be removed. 4. Removing the electrical parts box (1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and remove the cover. (3) Remove the room temperature thermistor and the indoor coil thermistor. (4) Disconnect the vane motor connector on the indoor controller board. (5) Remove the 2 screws of the electrical parts box. (6) Disconnect the connector of the heater lead wire connector. (7) Disconnect the connector of the fan motor lead wire. (8) Remove the electrical parts box. Photo 1 Indoor controller board Electrical parts box cover Catches Photo 2 Room temperature thermistor Indoor coil thermistor Screws Electrical parts box 39 OC129A-2.qxp 01.10.1 7:33 PM Page 40 OPERATING PROCEDURE PHOTOS&ILLUSTRATION (9) Remove the screws of the indoor controller board case, and pull out the indoor controller board case. Then the transformer and the capacitor and relay can be serviced. Photo 3 Relay Transformer Capacitor Indoor controller board case 5. Removing the vane motor (1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover, and remove the cover. (3) Remove the 2 screws of the vane motor, and remove the motor from the shaft. (4) Disconnect the vane motor connector on the indoor controller board. Photo 4 Electrical parts box Screws Vane motor Indoor controller board 6 Removing the intake grills (1) Remove the right side panel. (2) To remove the left side panel, remove the screw on the bottom and the screw on the upper left-hand side. (See Figure 3.) 1. Press up this side of the left side panel to unhook the catch on the panel from the catch on the unit. 2. Slide the left side panel to the left to remove the panel. Note: Fix the unit to the metal fixture securely (3) Remove the air filters. (4) Hold and press the centre cover to remove. (5) Remove the screws of the grills. (6) Pull the lower side of the grill toward you and slide the upper to the right to remove the grills. Figure 3 Catch on the left side panel Catch on the unit Photo 5 Left side panel Slide to the right Grills Screws for grills 7. Removing the drain pan (1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box cover. (4) Loosen the drain hose band to remove. (5) Remove the 3 screws of the drain pan, and slide the drain pan toward you to remove. Photo 6 Drain pan Drain hose band Screws Drain hose 40 OC129A-2.qxp 01.10.1 7:33 PM Page 41 OPERATING PROCEDURE PHOTOS 8. Removing the lineflow fan and the fan motor (1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box. (4) Remove the drain pan. (5) Loosen the screw that fixes the lineflow fan to the fan motor. (See Photo 7. ) (6) Remove the 4 screws of the motor fixture, and remove the fan motor and the motor fixture at a time (See Photo 8.) (7) Remove the screws of the left and right motor supports, and remove the motor supports and the fan motor. (See Photo 9.) (8) Remove the screw of the centre support, and remove the support. (See Photo 10. ) (9) Remove the 2 screws on the left and right sides of the heat exchanger, and pull the bearing support toward you. (See Photo 11.) (10) Pull the left-hand side of the heat exchanger toward you, and remove the lineflow fan. Photo 7 Screw Lineflow fan Fan motor Photo 8 Screw Fan motor Motor fixture Photo 11 Photo 9 Fan motor Screw Screw Heat exchanger Bearing support Motor support Motor support Photo 10 Lineflow fan Lineflow fan Centre support 41 Screw OC129A-2.qxp 13 01.10.1 7:33 PM Page 42 PARTS LIST STRUCTURAL PARTS PK-1.6FLA, PK-1.6FLA1, PK-1.6FLA2, PK-1.6FLA3 PK-2FLA, PK-2FLA1, PK-2FLA2, PK-2FLA3 Q'ty/set No. 1 Part No. Part name R01 KV5 651 FRONT PANEL Specification PK-1.6,PK-2 FLA1 FLA2 FLA FLA3 1 R01 47J 651 FRONT PANEL 2 R01 KV5 096 SCREW CAP 1 4 4 2 2 4 R01 A20 054 FILTER CATCH 2 2 R01 KV5 500 AIR FILTER 2 3 5 — CATCH HOLDER R01 47J 500 AIR FILTER 1 1 7 T7W 570 317 WIRELESS ADAPTER 1 1 PANEL CATCH 2 2 9 R01 KV5 623 UNDER COVER 1 1 10 R01 KV5 658 CORNER COVER 1 1 11 R01 KV5 635 BOX ASSEMBLY 1 1 12 R01 KV5 808 BACK PLATE 1 1 — (BG25R572H06) 2 6 T7W 570 058 SERVICE PANEL 8 Price Wiring RecomRemarks. Diagram mended (Drawing No.) Unit Amount Symbol Q'ty 42 W.B (BG25G057H07) OC129A-2.qxp 01.10.1 7:33 PM Page 43 STRUCTURAL PARTS PK-2.5FLA, PK-2.5FLA1, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 9 10 8 1 12 2 3 7 6 4 5 Part number that is circled is not shown in the figure. Q'ty/set No. Part No. Part name Specification PK-2.5 PK-2.5 FLA FLA1 FLA2 FLA3 FLA4 1 R01 12G 662 LEFT SIDE PANEL 1 1 R01 12G 812 UNDER PLATE 1 2 3 1 R01 E01 812 UNDER PLATE 1 R01 12G 811 NOSE 1 R01 E00 811 NOSE 4 R01 A17 500 AIR FILTER 4 4 5 T7W 570 317 WIRELESS ADAPTER 1 1 6 R01 12G 661 RIGHT SIDE PANEL 1 1 7 R01 12G 691 INTAKE GRILLE 2 2 8 R01 12G 808 BACK PLATE 1 1 9 R01 E01 641 TOP PLATE 1 1 10 — BOX ASSEMBLY — BOX ASSEMBLY Price Wiring RecomRemarks. Diagram mended (Drawing No.) Unit Amount Symbol Q'ty (BG00A593G89) 1 1 11 R01 12G 523 DRAIN SOCKET 1 1 12 R01 24K 658 RECEIVER 1 1 43 W.B (RG00A734G61) OC129A-2.qxp 01.10.1 7:34 PM Page 44 STRUCTURAL PARTS PK-3FLA, PK-3FLA1, PK-3FLA2, PK-3FLA3, PK-3FLA4 , PK-3FLA5 10 9 8 1 12 2 3 7 6 4 5 Part number that is circled is not shown in the figure. Q'ty/set PK-3 PK-3 PK-3 FLA FLA1 FLA2 FLA3 FLA4 FLA5 1 R01 12G 662 LEFT SIDE PANEL 1 1 1 R01 12G 812 UNDER PLATE 1 1 No. 2 3 Part No. Part name Specification 1 R01 E01 812 UNDER PLATE R01 12G 811 NOSE 1 1 1 R01 E00 811 NOSE 4 R01 A17 500 AIR FILTER 4 4 4 5 T7W 570 317 WIRELESS ADAPTER 1 1 1 6 R01 12G 661 RIGHT SIDE PANEL 1 1 1 7 R01 12G 691 INTAKE GRILLE 2 2 2 8 R01 12G 808 BACK PLATE 1 1 1 9 R01 E01 641 TOP PLATE 1 1 1 1 1 10 — BOX ASSEMBLY — BOX ASSEMBLY Price Wiring RecomRemarks. Diagram mended (Drawing No.) Symbol Q'ty Unit Amount (BG00A593G89) 1 11 R01 12G 523 DRAIN SOCKET 1 1 1 12 R01 24K 658 RECEIVER 1 1 1 44 W.B (RG00A734G61) OC129A-2.qxp 01.10.1 7:34 PM Page 45 STRUCTURAL PARTS PK-4FLSA, PK-4FLSA1, PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 10 9 8 1 12 2 3 7 6 4 5 Part number that is circled is not shown in the figure. Q'ty/set No. Part No. Part name Specification PK-4 FLSA FLSA3 FLSA1 FLSA4 FLSA2 1 R01 12G 662 LEFT SIDE PANEL 1 R01 16G 812 UNDER PLATE 1 2 3 PK-4 1 1 R01 E00 812 UNDER PLATE 1 R01 16G 811 NOSE 1 R01 E01 811 NOSE 4 R01 A17 500 AIR FILTER 5 5 5 T7W 570 317 WIRELESS ADAPTER 1 1 6 R01 12G 661 RIGHT SIDE PANEL 1 1 7 R01 12G 691 INTAKE GRILLE 2 2 8 R01 16G 808 BACK PLATE 1 1 9 R01 E00 641 TOP PLATE 1 1 10 — BOX ASSEMBLY — BOX ASSEMBLY Price Wiring RecomRemarks. Diagram mended (Drawing No.) Unit Amount Symbol Q'ty (BG00A593G89) 1 1 11 R01 12G 523 DRAIN SOCKET 1 1 12 R01 24K 658 RECEIVER 1 1 13 R01 16G 692 INTAKE GRILLE 1 1 45 W.B (RG00A734G62) OC129A-2.qxp 01.10.1 7:34 PM Page 46 ELECTRICAL PARTS PK-1.6FLA, PK-1.6FLA1, PK-1.6FLA2, PK-1.6FLA3 PK-2FLA, PK-2FLA1, PK-2FLA2, PK-2FLA3 1 3 2 4 5 8 6 25 27 9 28 7 26 24 31 32 30 10 29 11 12 15 16 17 19 13 14 18 34 33 35 36 46 20 21 22 23 OC129A-2.qxp 01.10.1 7:34 PM Page 47 Parts number that is circled is not shown in the figure. Q'ty/set No. Part No. Part name Specification PK-1.6 PK-2 FLA FLA1 FLA2 FLA FLA1 FLA2 FLA3 FLA3 1 1 1 1 1 1 2 R01 KV5 114 LINEFLOW FAN 1 1 1 1 1 1 3 R01 KV5 106 BEARING SUPPORT 1 1 1 1 1 1 4 R01 566 103 SLEEVE BEARING 1 1 1 1 1 1 5 R01 KV5 102 BEARING MOUNT 1 1 1 1 1 1 1 T7W 570 480 HEAT EXCHANGER R01 21A 480 HEAT EXCHANGER 6 T7W 52J 675 FAN GUARD 1 1 7 T7W 51J 675 FAN GUARD 1 1 Price Wiring RecomRemarks. Diagram mended Unit Amount (Drawing No.) Symbol Q'ty 8 R01 KV5 223 VANE MOTOR 1 1 1 1 1 1 9 R01 KV5 530 NOZZLE ASSEMBLY 1 1 1 1 1 1 10 R01 KV5 038 GUIDE VANE 16 16 16 16 16 16 11 R01 KW1 002 LEFT ROTARY VANE 1 1 1 1 1 1 12 R01 KV5 048 CENTER SUPPORT 1 1 1 1 1 1 1 1 1 1 1 1 (BG25M017H06) 14 R01 71G 527 DRAIN HOSE 1 1 1 1 1 1 15 R01 KV5 059 ARM 2 2 2 2 2 2 16 R01 KW2 002 RIGHT ROTARY VANE 1 1 1 1 1 1 13 — VANE SLEEVE 17 — CONTROL BOX COVER 1 1 1 1 1 1 (BG02A326G06) 18 — TERMINAL COVER 1 1 1 1 1 1 (BG02B718H05) 1 1 1 1 19 T7W 520 310 CONTROLLER BOARD I.B 1 1 T7W 27K 310 CONTROLLER BOARD MV I.B 1 1 1 1 1 1 (BG25B573H05) 21 R01 520 239 FUSE 250V 6.3A 2 2 2 2 2 2 F1,2<I.B> 22 T7W 514 716 TERMINAL BLOCK 3P(L,N,;) 1 1 1 1 1 1 TB2 23 T7W 512 716 TERMINAL BLOCK 2P(1/2) 1 1 1 1 1 1 TB5 1 1 1 1 20 24 — CONTROLLER CASE T7W 552 799 TRANSFORMER 1 T7W 52J 799 TRANSFORMER T 1 T 2.0+ 440V 1 1 1 1 1 1 C1 26 R01 KN7 202 INDOOR COIL THERMISTOR 1 1 1 1 1 1 RT2 R01 J07 202 ROOM TEMPERATURE THERMISTOR 1 25 R01 588 255 RUN CAPACITOR 27 1 RT1 1 1 1 1 1 (BG25B846H11) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 33 R01 58A 049 REMOTE CONTROLLER DOOR 1 1 1 1 1 1 T7W 570 200 REMOTE CONTROLLER 1 1 1 1 1 1 1 1 1 1 1 1 PK4V30-KA 1 1 31 R01 KV5 105 RUBBER MOUNT 1 32 R01 KV5 135 MOTOR COVER 28 R01 06A 202 ROOM TEMPERATURE THERMISTOR — WATER SHIELD 29 R01 KV5 130 MOTOR SUPPORT 30 T7W 570 762 FAN MOTOR 34 35 R01 58A 050 BATTERY COVER 1 1 1 1 1 1 36 R01 18G 075 REMOTE CONTROLLER HOLDER 1 1 1 1 1 1 37 R01 12G 523 DRAIN SOCKET 1 1 1 1 1 1 47 MF W.R 1 1 T7W 56J 200 REMOTE CONTROLLER RT1 W.R OC129A-2.qxp 01.10.1 7:34 PM Page 48 ELECTRICAL PARTS PK-2.5FLA, PK-2.5FLA1, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4 PK-2.5FLA PK-2.5FLA1 PK-2.5FLA2 PK-2.5FLA3 37 1 32 2 35 38 36 34 3 33 4 PK-2.5FLA4 32 31 26 5 30 29 25 28 24 27 6 23 22 7 8 21 20 9 11 19 16 10 12 17 13 14 Q'ty/set No. Part No. Part name Price Wiring RecomPK-2.5 Remarks. Diagram mended Specification (Drawing No.) FLA1 FLA3 FLA4 Symbol Q'ty Unit Amount FLA FLA 2 1 R01 005 103 SLEEVE BEARING 1 1 1 1 2 R01 Z61 102 BEARING MOUNT 1 1 1 1 3 R01 13G 114 LEFT LINEFLOW FAN 1 1 1 1 4 T7W 572 480 HEAT EXCHANGER 1 1 1 1 1 1 1 1 5 R01 12G 529 DRAIN PAN T7W E13 529 DRAIN PAN — 3 3 3 3 7 R01 12G 063 JOINT SHAFT 1 1 1 1 8 R01 12G 621 CENTER COVER 1 1 1 1 6 ARM 18 15 48 (BG25H301H02) OC129A-2.qxp 01.10.1 7:34 PM Page 49 Q'ty/set No. Part No. Part name Price Wiring RecomRemarks. Diagram mended Specification (Drawing No.) 1 Symbol Q'ty Unit Amount FLA FLA FLA 3 FLA4 FLA2 PK-2.5 9 R01 12G 002 AUTO VANE 2 2 2 2 10 R01 KV5 527 DRAIN HOSE 1 1 1 1 — GUIDE VANE 20 20 20 20 (BG25J821H01) — GUIDE VANE (WITH HANDLE) 4 4 4 4 12 R01 12G 223 VANE MOTOR 1 1 1 1 MV 13 R01 06A 202 ROOM TEMPERATURE THERMISTOR 1 1 1 1 RT1 14 R01 KL5 202 INDOOR COIL THERMISTOR 1 1 1 1 RT2 1 1 1 1 1 1 1 1 11 15 — TERMINAL COVER 16 R01 588 255 RUN CAPACITOR 17 2.0+ 440V T7W 560 310 CONTROLLER BOARD (BG02J608H07) C 1 T7W 27K 310 CONTROLLER BOARD 18 T7W 520 239 FUSE (BG25J821H02) 250V 6.3A I.B 1 1 1 I.B 2 2 2 2 F1,2<I.B> 19 — CONTROLLER COVER 1 1 1 1 (BG02A648G02) 20 — CONTROLLER CASE 1 1 1 1 (BG25B573H06) 21 T7W 552 799 TRANSFORMER 1 T7W 51J 799 TRANSFORMER T 1 1 1 T 22 T7W 512 716 TERMINAL BLOCK 2P(1/2) 1 1 1 1 TB4 23 T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 1 1 TB2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 24 — MOTOR BAND 25 R01 12G 220 FAN MOTOR 26 — MOTOR LEG 27 R01 12G 105 RUBBER MOUNT 28 — MOTOR BAND 29 R01 13G 115 RIGHT LINEFLOW FAN (BG02H065H01) MF (BG02A534H16) (BG02H178H01) 30 — CENTER SUPPORT 1 1 1 1 (BG00R259G07) 31 — BEARING BAND 1 1 1 1 (BG02L462H02) 2 2 2 32 T7W 53J 675 FAN GUARD 33 R01 12G 103 SLEEVE BEARING 1 1 1 1 34 R01 KV5 102 BEARING MOUNT 1 1 1 1 1 1 1 35 R01 58A 049 REMOTE CONTROLLER DOOR R01 E01 049 REMOTE CONTROLLER DOOR 36 T7W 570 200 REMOTE CONTROLLER 1 1 1 1 1 1 1 1 1 1 T7W E06 714 REMOTE CONTROLLER 37 R01 58A 050 BATTERY COVER 38 R01 18G 075 REMOTE CONTROLLER HOLDER W.R 1 R01 E00 075 REMOTE CONTROLLER HOLDER 1 49 W.R OC129A-2.qxp 01.10.1 7:34 PM Page 50 ELECTRICAL PARTS PK-3FLA, PK-3FLA1, PK-3FLA2, PK-3FLA3, PK-3FLA4 , PK-3FLA5 PK-3FLA PK-3FLA1 PK-3FLA2 PK-3FLA3 PK-3FLA4 37 1 32 2 35 38 36 34 3 33 4 PK-3FLA5 32 31 26 5 30 29 25 28 24 27 6 23 22 7 8 21 20 9 11 19 16 10 12 17 13 14 Q'ty/set No. Part No. Part name Price Wiring RecomPK-3 Remarks. Diagram mended Specification (Drawing No.) FLA1 Symbol Q'ty Unit Amount FLA FLA2 FLA4 FLA5 FLA3 1 R01 005 103 SLEEVE BEARING 1 1 1 1 2 R01 Z61 102 BEARING MOUNT 1 1 1 1 3 R01 13G 114 LEFT LINEFLOW FAN 1 1 1 1 4 T7W 573 480 HEAT EXCHANGER 1 1 1 1 1 1 1 1 5 R01 12G 529 DRAIN PAN T7W E13 529 DRAIN PAN — 3 3 3 3 7 R01 12G 063 JOINT SHAFT 1 1 1 1 8 R01 12G 621 CENTER COVER 1 1 1 1 6 ARM 18 15 50 (BG25H301H02) OC129A-2.qxp 01.10.1 7:34 PM Page 51 Q'ty/set No. Part No. Part name Price Wiring RecomRemarks. Diagram mended Specification (Drawing No.) FLA1 Symbol Q'ty Unit Amount FLA FLA2 FLA4 FLA5 FLA3 PK-3 9 R01 12G 002 AUTO VANE 2 2 2 2 10 R01 KV5 527 DRAIN HOSE 1 1 1 1 — GUIDE VANE 20 20 20 20 (BG25J821H01) — GUIDE VANE (WITH HANDLE) 4 4 4 4 12 R01 12G 223 VANE MOTOR 1 1 1 1 MV 13 R01 06A 202 ROOM TEMPERATURE THERMISTOR 1 1 1 1 RT1 14 R01 KL5 202 INDOOR COIL THERMISTOR 1 1 1 1 RT2 1 1 1 1 1 1 1 1 11 15 — TERMINAL COVER 16 R01 588 255 RUN CAPACITOR 17 2.0+ 440V T7W 560 310 CONTROLLER BOARD (BG02J608H07) C 1 T7W 27K 310 CONTROLLER BOARD 18 T7W 520 239 FUSE (BG25J821H02) 250V 6.3A I.B 1 1 1 I.B 2 2 2 2 F1,2<I.B> 19 — CONTROLLER COVER 1 1 1 1 (BG02A648G02) 20 — CONTROLLER CASE 1 1 1 1 (BG25B573H06) 21 T7W 552 799 TRANSFORMER 1 T7W 51J 799 TRANSFORMER T 1 1 1 T 22 T7W 512 716 TERMINAL BLOCK 2P(1/2) 1 1 1 1 TB4 23 T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 1 1 TB2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 24 — MOTOR BAND 25 R01 12G 220 FAN MOTOR 26 — MOTOR LEG 27 R01 12G 105 RUBBER MOUNT 28 — MOTOR BAND 29 R01 13G 115 RIGHT LINEFLOW FAN (BG02H065H01) MF (BG02A534H16) (BG02H178H01) 30 — CENTER SUPPORT 1 1 1 1 (BG00R259G07) 31 — BEARING BAND 1 1 1 1 (BG02L462H02) 2 2 2 32 T7W 53J 675 FAN GUARD 33 R01 12G 103 SLEEVE BEARING 1 1 1 1 34 R01 KV5 102 BEARING MOUNT 1 1 1 1 1 1 1 35 R01 58A 049 REMOTE CONTROLLER DOOR R01 E01 049 REMOTE CONTROLLER DOOR 36 T7W 570 200 REMOTE CONTROLLER 1 1 1 1 1 1 1 1 1 1 T7W E06 714 REMOTE CONTROLLER 37 R01 58A 050 BATTERY COVER 38 R01 18G 075 REMOTE CONTROLLER HOLDER W.R 1 R01 E00 075 REMOTE CONTROLLER HOLDER 1 51 W.R OC129A-2.qxp 01.10.1 7:34 PM Page 52 ELECTRICAL PARTS PK-4FLSA, PK-4FLSA1, PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 PK-4FLSA PK-4FLSA1 PK-4FLSA2 PK-4FLSA3 37 1 32 2 35 38 36 34 3 33 4 PK-4FLSA4 32 31 26 5 30 29 25 28 24 27 6 23 22 7 8 21 20 9 11 19 16 10 12 17 13 14 Q'ty/set No. Part No. Part name Price Wiring RecomPK-4 Remarks. Diagram mended Specification (Drawing No.) 1 Symbol Q'ty Unit Amount FLSA FLSA FLSA 3 FLSA4 FLSA2 1 R01 005 103 SLEEVE BEARING 1 1 1 1 2 R01 Z61 102 BEARING MOUNT 1 1 1 1 3 R01 17G 114 LEFT LINEFLOW FAN 1 1 1 1 T7W 574 480 HEAT EXCHANGER 1 1 1 1 1 1 4 R01 46G 480 HEAT EXCHANGER 5 R01 16G 529 DRAIN PAN 1 1 T7W E14 529 DRAIN PAN — 4 4 4 4 7 R01 12G 063 JOINT SHAFT 1 1 1 1 8 R01 12G 621 CENTER COVER 1 1 1 1 6 ARM 18 15 52 (BG25H301H02) OC129A-2.qxp 01.10.1 7:34 PM Page 53 Q'ty/set No. Part No. Part name Price Wiring RecomPK-4 Remarks. Diagram mended Specification (Drawing No.) 1 Symbol Q'ty Unit Amount FLSA FLSA FLSA 3 FLSA4 FLSA2 9 R01 16G 002 AUTO VANE 2 2 2 2 10 R01 KV5 527 DRAIN HOSE 1 1 1 1 — GUIDE VANE 26 26 26 26 (BG25J821H01) — GUIDE VANE (WITH HANDLE) 4 4 4 4 12 R01 12G 223 VANE MOTOR 1 1 1 1 MV 13 R01 06A 202 ROOM TEMPERATURE THERMISTOR 1 1 1 1 RT1 14 R01 KL5 202 INDOOR COIL THERMISTOR 1 1 1 1 RT2 1 1 1 1 1 1 1 1 11 15 — TERMINAL COVER 16 R01 576 255 RUN CAPACITOR 17 3.0+ 440V T7W 560 310 CONTROLLER BOARD (BG02J608H07) C 1 T7W 27K 310 CONTROLLER BOARD 18 T7W 520 239 FUSE (BG25J821H02) 250V 6.3A I.B 1 1 1 I.B 2 2 2 2 F1,2<I.B> 19 — CONTROLLER COVER 1 1 1 1 (BG02A648G02) 20 — CONTROLLER CASE 1 1 1 1 (BG25B573H06) 21 T7W 552 799 TRANSFORMER 1 T7W 51J 799 TRANSFORMER T 1 1 1 T 22 T7W 512 716 TERMINAL BLOCK 2P(1/2) 1 1 1 1 TB4 23 T7W 509 716 TERMINAL BLOCK 3P(L,N,;) 1 1 1 1 TB2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 24 — MOTOR BAND 25 T7W 571 762 FAN MOTOR 26 — MOTOR LEG 27 R01 16G 105 RUBBER MOUNT 28 — MOTOR BAND 29 R01 17G 115 RIGHT LINEFLOW FAN (BG02H065H01) MF (BG02A534H17) (BG02H178H01) 30 — CENTER SUPPORT 1 1 1 1 (BG00R259G07) 31 — BEARING BAND 1 1 1 1 (BG02L462H02) 2 2 2 32 T7W 71J 675 FAN GUARD 33 R01 12G 103 SLEEVE BEARING 1 1 1 1 34 R01 KV5 102 BEARING MOUNT 1 1 1 1 1 1 1 35 R01 58A 049 REMOTE CONTROLLER DOOR R01 E01 049 REMOTE CONTROLLER DOOR 36 T7W 570 200 REMOTE CONTROLLER 1 1 1 1 1 1 1 1 1 1 T7W E06 714 REMOTE CONTROLLER 37 R01 58A 050 BATTERY COVER 38 R01 18G 075 REMOTE CONTROLLER HOLDER W.R 1 R01 E00 075 REMOTE CONTROLLER HOLDER 1 53 W.R OC129A-2.qxp 14 01.10.1 7:34 PM Page 54 OPTIONAL PARTS 1. REFRIGERANT PIPES Service Ref. : PK-1.6FLA3, PK-2FLA3, PK-2.5FLA2, PK-2.5FLA3, PK-2.5FLA4, PK-3FLA2, PK-3FLA3, PK-3FLA4, PK-3FLA5, Part No. Pipe lenght PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E 5m 7m 10m 15m Liquid:{9.52 Gas:{15.88 Pipe size O.D. Indoor unit:Flared Outdoor unit:Flared Pipe size O.D. Service Ref. : PK-4FLSA2, PK-4FLSA3, PK-4FLSA4 PAC-SC51PI-E Part No. PAC-SC52PI-E PAC-SC53PI-E PAC-SC54PI-E 7m 10m 15m 5m Pipe lenght Liquid:{9.52 Gas:{19.05 Pipe size O.D. Indoor unit:Flared Outdoor unit:Flared Connection methed Note 1. How to connect refrigerant pipes. Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow. If piping length exceeds 5m,an additional charge of refrigerant is needed. Note 2. The following main parts are contained in the optional refrigerant piping kit. Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole),connecting cables. 2. TIMER ADAPTER This adapter is needed for system control and for operation via external contacts. Part No. PAC-SA89TA-E ORN 1 BRN 2 RED 3 3. MULTIPLE REMOTE CONTROLLER ADAPTER This adapter is needed for remote indication (operation/check). Part No. PAC-SA88HA-E 1 2 3 4 5 BRN RED ORN YLW GRN 54 OC129A-2.qxp 01.10.1 7:34 PM Page 55 4. CENTRALIZED REMOTE CONTROLLER Allows individual or combined control of up to 16 units. PAC-805RC Part No. Unit : mm 4-1. Dimensions 113 56.3 12 23.5 POWER ON/OFF ENGAGED GROUP DUAL CENTRAL CONTROLLER OPERATION 1 2 3 4 5 6 7 8 9 10 AHEAD ACTIVE BYPASS DUAL CENTRAL GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION BACK AHEAD ACTIVE BYPASS 113 ACTIVE BYPASS PROGRAM TIMER BACK 8 GROUP SELECTION 117 1 2 3 4 5 6 7 8 9 10 POWER ON/OFF ENGAGED GROUP 11 DUAL CENTRAL MITSUBISHI ELECTRIC 10 9 8 7 6 5 4 3 2 1 117 4-2. Names and Functions POWER ON/OFF switch Operation ON/OFF switch. "ENGAGED" indicator When this indicator is lit, transmission is in progress and all switches are inoperative. DUAL/CENTRAL switch This change-over switch governs the operation of the accessory remote controller. POWER ON/OFF ENGAGED GROUP 1 2 3 4 5 6 7 8 9 10 "DUAL" Instructions from both the accessory remote controller and the centralized remote controller are valid. (Priority given to the last instruction received.) GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION "CENTRAL" ON/OFF switching by the accessory remote controller is invalidated. Operation is controlled by the centralized remote controller only. Initial setting is "DUAL". BACK AHEAD ACTIVE BYPASS DUAL CENTRAL MITSUBISHI ELECTRIC ▲BACK ▼AHEAD buttons These buttons are used to designate the attached unit(s). (They designate the unit to be centrally controlled.) ●When group “00” is designated; collective ON/OFF instruction is sent to all units. ●When group “01”-“16“ is designated; ON/OFF instruction is sent only to the designated units. ACTIVE/BYPASS switch This is a change-over switch for the program timer. Use “BYPASS” when a program timer is not connected. LCD Matrix Display This display indicates the operational status of all connected units either by steady lighting or by flashing. Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is possible. When the power supply to the centralized remote controller is cut due to power failure, all settings will return to original “DUAL” and “BYPASS”. 55 OC129A-2.qxp 01.10.1 7:34 PM Page 56 4-3 Connection method (1) Connections in the power supply cord. 1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V AV (220, 230, 240V) to A N . As E is the GND terminal, be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a Ω1.6 (AWG 14) or above two-wire cable for the transmission line. CAUTION : Never connect the power supply cord to the transmission terminal-block. TERMINAL-BLOCK FOR TRANSMISSION TERMINAL-BLOCK OF POWER SUPPLY Transmission A T N 240 (Y) (O) 230 (R) 220 Tie-wrap 200 E (W) (BR) 5A TRANSFORMER A Fuse(5A) POWER SUPPLY N Tie-wrap E Wiring has to be changed when a 200,230 or 240V power is used. (2) Connection method of centralized remote controller and power supply board. 1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable. Power supply board box To adaptor's terminal-block POWER ON/OFF ENGAGED GROUP 1 2 3 4 5 6 7 8 9 10 GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION BACK AHEAD ACTIVE BYPASS DUAL CENTRAL 10 9 8 7 6 5 4 3 2 1 Centralized remote controller To adaptor's terminal-block Non-polar, two-wire cable 2. Wiring diagram 3. Be sure to set the maximum address number with the dip switch SW17 on the centralized remote controller. POWER ON/OFF ENGAGED GROUP 1 2 3 4 5 6 7 8 9 10 Centralized remote controller GROUP SELECTION ACTIVE BYPASS PROGRAM TIMER DUAL CENTRAL CONTROLLER OPERATION BACK AHEAD ACTIVE BYPASS DUAL CENTRAL Power supply board 10 9 8 7 6 5 4 3 2 1 56 Dip switch SW17 OC129A-2.qxp 01.10.1 7:34 PM Page 57 5. PROGRAM TIMER ADAPTER This adapter is needed when a program timer(PAC-815PT)or a centralized remote controller(PAC-805RC)is used. PAC-825AD Part No 5-1 Parts included 1 ADAPTER··························1P 2 3-core cable···························1P 3 3-core cable···························1P Length : 2m(6' 7") Length : 2m(6' 7") 4 4-core cable···························1P 5 5-core cable···························1P Length : 2m(6' 7") Length : 2m(6' 7") 5-2 Connection method Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work. (1) Connections in the adapter box 1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap. Connect a single phase 200V (220, 230, 240V) AV to A N . As E is the GND terminal, be sure to ground the earth wire. 2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a centralized remote controller is being used). CAUTION : Never connect the power supply cord to the transmission terminal-block Fig-1 CN22 SW1 TRANS Dip switch (AG) CN1 CN21 CN51 CN30 CN42 CN50 CN40 A N Tie-wrap TERMINAL-BLOCK FOR POWER SUPPLY Tr ans m i s s i on T (W) (B) (Y) 220 240 TRANS SW1 200 CN22 TERMINAL-BLOCK FOR TRANSMISSION Fig-2 E 5A A POWER SUPPLY N Tie-wrap Transmission cord Fuse(5A) E POWER SUPPLY CORD TRANSFORMER Wiring has to be changed when 200V power supply is used. 57 OC129A-2.qxp 01.10.1 7:34 PM Page 58 2. Set the address number (from SW1-1 to SW1-6) in the dip switch when a centralized remote controller is being used. The address is the control number of each unit in the centralized control system. As the address serves as a time-delay device as well, sequential starts (all units are triggered collectively by one single ON instruction) must be set with different address numbers (greater than O) for each adapter. SW1 10 9 8 8 7 6 5 4 5 4 3 2 1 Levers No. 1-6 can set the following address respectively with binary notations Toggle No.6ON No.5ON No.4ON No.3ON No.2ON No.1ON (Ex. 1) 3=2+1 9 6 ON Address 10 7 32 16 8 4 2 (Ex. 3) 15=8+4+2+1 (Ex. 2) 9=8+1 3 2 1 10 9 8 7 6 5 4 3 1 2 ON 10 1 9 8 7 6 5 4 3 80 40 27 18 65 CN30 CN50 Fixing screw hole 4- 5.5 12 120 CN51 35 8 7 74 Indoor unit Max. Length of each cable is 10m. 58 2 2- 2.9 30 200 ho 15 le 35 15 CN2 27 22 5-core cable ƒ 22 3-core cable ¡ 86 70 240V AC 220 200 230 Adaptor 95 To program timer or centralized remote controller 40 15 (2) Connection from adaptor Fig.4 1 ON ON Fig.3 2 OC129A-2.qxp 01.10.1 7:34 PM Page 59 6. TIMER Model Name Product Name PAC-SK65PT Program timer (The PAC-SK65PT can only be used together with the PAC-825AD) 6-1 Program timer specifications Program Timer PAC-SK65PT Wall mount Quarts clock +50 second/month Liquid crystal display Liquid crystal display 24 hours 30 minutes 48/day — — 5V DC Not provided Product name Model name. Mounting method Clock system Clock accuracy Time Week Display Program cycle Timer setting unit Number. of set point Minimum ON/OFF interval Power failure safeguard Rated power supply Set back function 6-2 Feature of program timer (1) Daily timer function Daily timer can be set in 30 minutes units for up to 24 hours. Each unit can be set for unit ON, unit OFF, or setback operation. (2) Setback operation (PAC-SK65PT) Set back operation is useful for reducing running costs e.g. At a hotel with a 24-hour system 8:00~23:00 Cooling operation with set temperature at 26°C 23:00~8:00 Setback operation with 2 degrees of setback As shown in the chart on the night, the set temperature rises 2 degrees automatically during the setback operation. When the setback operation ends, normal operation will begin. (3) Weekly timer function Daily timer function can apply to each day of the week. 28˚C 26˚C 8:00 Normal operation 23:00 Setback operation 8:00 Normal operation 6-3. How to connect program timer (PAC-SK65PT) (1) Install the program timer next to the remote controller the same way as the remote controller is installed. (2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below 2-wire cable To indoor unit Centraized Remote controller Connector CN1 6-wire cable NOTE:While the program timer is connected to the remote controller, the 24hour ON/OFF timer on the remote controller will not work. Program timer Connector CN1 59 OC129A-2.qxp 01.10.1 7:34 PM Page 60 6-4. Name and functions (PAC-SK65PT) MODE selector button : Used to select \MONITOR" or "SET" mode. "MONITOR" : Indicates the current timer setting. All buttons except SET/MONITOR will not work.This is the normal status. "SET" : "SET" is used to set the time, change the day of the week, and program the daily and weekly timer. Mode display Current time display Current day display Weekly timer display Clock adjustment button : Used to adjust the current time.Press AHEAD button to advance the time. Each time the button is pressed the time advances by 1 minute. Pressing continuously advances 1 minute in a 0.5 secSET MONITOR ond interval. When the lower digit of minute becomes 0 the indication advances in 10 minutes unit. BACK button is used for reversing the time. Each time the button is pressed the time reverses by 1 minute. Pressing continuously reverses the time by 1 minute in a 0.5 second interval. MITSUBISHI ELECTRIC When the lower digit of minute becomes 0 the indication reverses in 10 minutes unit. Weekday setting button : Used to set the day of week. Pressing button changes the day. SET/MOTOR CLOCK WEEKLY TIMER AHEAD ON OFF DAILY TIMER BACK ON Day timer display BACK TODAY S M T W T F S SETBACK AHEAD OFF ▲ Weekly timer button : Used to set the weekly timer. NOTE : Display above is only an example. Daily timer button : Used to set the timer settings in units of 30 minutes. 7. Drain pump (for PK-2.5FLA, PK-3FLA, PK-4FLSA) Model Name PAC-SE89DM-E HEAD OFFICE : MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI,CHIYODA-KU TOKYO 100-8310, JAPAN © Copyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD. Distributed in Sep.2001. No. OC129 REVISED EDITION-A 870 Reprinted in May.2001. No. OC129 5 Issued in Nov.1999. No. OC129 300 Issued in Aug.1999. No. OC129 50 Issued in Mar.1999. No. OC129 50 Issued in Jun.1997. No. OC129 2420 Made in Japan New publication, effective Sep. 2001 Specifications subject to change without notice