Download Samson 1400 Operating instructions

Transcript
Series 3731
Type 3731-3
Electropneumatic Ex d Positioner
with HART® communication
Fig. 1 · Type 3731-3
Mounting and
Operating Instructions
EB 8387-3 EN
Firmware version 1.53
Edition February 2015
EB + CD
Definitions of the signal words used in these instructions
DANGER!
indicates a hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING!
indicates a hazardous situation which, if not
avoided, could result in death or serious
injury.
2
EB 8387-3 EN
NOTICE
indicates a property damage message.
Note: Supplementary explanations,
information and tips
Contents
Contents
1
Important safety instructions . . . . . . . . . . . . . . . . . . . . . . 6
2
Article code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3
3.1
3.2
3.2.1
3.3
Design and principle of operation. . . . . . . . . . . . . . . . . . . . 8
Additional equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Configuration using TROVIS-VIEW software . . . . . . . . . . . . . . 10
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4
4.1
4.1.1
4.1.2
4.2
4.3
4.4
4.5
4.5.1
4.6
Attachment to the control valve – Mounting parts and accessories
Direct attachment . . . . . . . . . . . . . . . . . . . . . . . .
Type 3277-5 Actuator . . . . . . . . . . . . . . . . . . . . . .
Type 3277 Actuator . . . . . . . . . . . . . . . . . . . . . . .
Attachment according to IEC 60534-6 (NAMUR) . . . . . . . . .
Attachment to Type 3510 Micro-flow Valve . . . . . . . . . . . .
Attachment to rotary actuators . . . . . . . . . . . . . . . . . .
Reversing amplifier for double-acting actuators . . . . . . . . . .
Reversing amplifier (1079-1118 or 1079-1119) . . . . . . . . .
Required mounting parts and accessories . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
15
17
17
20
22
24
26
28
28
30
5
5.1
5.1.1
5.1.2
5.1.3
5.2
5.2.1
Connections . . . . . . . .
Pneumatic connections . . .
Signal pressure gauges . .
Supply pressure . . . . . .
Signal pressure (output) . .
Electrical connections . . .
Establishing communication
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
34
34
35
35
35
36
40
6
6.1
6.2
6.3
6.4
6.4.1
Operator controls and readings
Rotary pushbutton . . . . . . .
Serial interface . . . . . . . .
Readings on display . . . . . .
HART® communication . . . .
Dynamic HART® variables . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
42
42
42
42
45
45
7
7.1
7.2
7.3
7.4
7.5
Start-up – Settings. . . . . . . . . . . . . .
Adapting the display. . . . . . . . . . . . .
Limiting the signal pressure. . . . . . . . . .
Checking the operating range of the positioner
Allocating the closed position . . . . . . . .
Positioner initialization. . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
46
47
47
48
49
49
.
.
.
.
.
.
.
EB 8387-3 EN
3
Contents
7.5.1
7.5.2
7.5.3
7.5.4
7.6
7.7
Initialization based on MAX maximum range . . . .
Initialization based on NOM nominal range . . . . .
Initialization based on MAN manually selected range
SUB substitute calibration . . . . . . . . . . . . . .
Zero calibration . . . . . . . . . . . . . . . . . . .
Reset to default values . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
51
52
53
55
58
59
8
8.1
8.2
8.2.1
8.2.2
8.3
8.3.1
Operation. . . . . . . . . . . . . . . . . .
Enabling and selecting parameters . . . . .
Operating modes . . . . . . . . . . . . . .
Automatic (AUTO) and manual (MAN) modes
Fail-safe position (SAFE) . . . . . . . . . . .
Malfunction/maintenance alarm . . . . . . .
Confirming error messages . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
60
60
61
61
62
62
63
9
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
10
Servicing explosion- protected devices. . . . . . . . . . . . . . . . . 64
11
Code list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
12
12.1
Dimensions in mm. . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Fixing levels according to VDI/VDE 3845 (September 2010) . . . . . . 86
13
13.1
Appendix . . . . . . . . . . .
Selecting the valve characteristic
Test certificates . . . . . . . .
Index . . . . . . . . . . . . .
4
EB 8387-3 EN
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
87
87
89
98
Modifications to positioner firmware
Modifications to positioner firmware compared to the previous version
1.41 (old)
1.42 (new)
After performing a reset to default values, the allocation of the closing position AIR
TO OPEN (AtO) /AIR TO CLOSE (AtC) is not reset to the default setting. The setting is
kept.
1.42 (old)
1.51 (new)
All EXPERTplus diagnostic functions are available in the positioner without having to
activate them first (refer to EB 8389 EN on EXPERTplus valve diagnostics)
Optional binary input with following actions:
– Transfer switching state
– Set local operation write protection
– Switch between AUTO/MAN
– Various diagnostic functions (refer to EB 8389 EN on EXPERTplus valve diagnostics).
The pressure limit (Code 16) is no longer automatically set during initialization.
1.51 (old)
1.52 (new)
Internal modifications
1.52 (old)
1.53 (new)
Internal modifications
Note:
The functions of EXPERTplus valve diagnostics are described in the Mounting and Operating
Instructions EB 8389 EN.
EB 8387-3 EN
5
Important safety instructions
1
Important safety instructions
For your own safety, follow these instructions concerning the mounting, start up and operation of the positioner:
4 The positioner is to be mounted, started up or operated only by trained and
experienced personnel familiar with the product.
According to these Mounting and Operating Instructions, trained personnel refers to
individuals who are able to judge the work they are assigned to and recognize
possible dangers due to their specialized training, their knowledge and experience as
well as their knowledge of the relevant standards.
4 Explosion-protected versions of this positioner may only be operated by personnel
who have undergone special training or instructions or who are authorized to work
on explosion-protected devices in hazardous areas. Refer to section 10.
4 Any hazards that could be caused by the process medium, the operating pressure, the
signal pressure or by moving parts of the control valve are to be prevented by means
of the appropriate measures.
4 If inadmissible motions or forces are produced in the actuator as a result of the supply
pressure, the supply pressure must be restricted by means of a suitable supply
pressure reducing station.
To avoid damage to any equipment, the following also applies:
4 Do not operate the positioner with the back of the positioner/vent opening facing
upwards.
The vent opening must not be sealed when the positioner is installed on site.
Vent opening
4 Proper shipping and appropriate storage are assumed.
4 Do not ground electric welding equipment near to the positioner.
Note: The device with a CE marking fulfills the requirements of the Directives 94/9/EC and
2004/108/EC.
The Declaration of Conformity is available on request.
6
EB 8387-3 EN
Article code
2
Article code
Positioner
Type 3731 - 3
x x x x x x x 00x 1x 000
With LCD, autotune, HART® communication
Explosion protection
ATEX: II 2G Ex db IIC T6; II 2G Ex db eb IIC T6;
II 2G Ex db [ia] IIC T6; II 2G Ex ia IIC T6; II 2D Ex tb IIIC T80°C IP66
21
FM:
Class I, Div. 1+2, Groups B, C, D; Class I, Zone 1, Groups IIB+H2;
Class I, Div. 1+2 Groups E, F, G; Class III
23
CSA:
Class I, Zone 1, Group IIB+H2 T4...T6; Class I, Div. 1+2, Groups B, C, D T4...T6;
Class II, Div. 1, Groups E, F, G
JIS: Ex d IIC T6
27
Options (additional equipment)
Without
00
Position transmitter
01
Binary input
03
Forced venting
05
Binary output (NAMUR/PLC)
06
Diagnostics
EXPERTplus for control valves
4
Electrical connections
2x M20 x 1.5
1
2x ½ NPT
2
Emergency shutdown
Emergency shutdown with the reference variable of 0 mA*
0
Emergency shutdown when the reference variable is smaller than 3.85 mA
1
Explosion-protection certificates
As specified in Explosion protection
0
NEPSI: Ex d IIC T6~T4; Ex de IIC T6~T4
21
1
IECEx: Ex d IIC T6, T5, T4 Gb; Ex d e IIC T6, T5, T4 Gb; Ex tb IIIC T80°C Db IP66
21
2
GOST: 1Ex d IIC T6/T5/T4 Gb X; 1Ex d e IIC T6/T5/T4 Gb X; Ex tb IIIC T 80°C Db X
21
3
Special applications
None
0
Positioner compatible with paint (IP 41/NEMA 1)
1
Special version
Without
000
* Version no longer available
EB 8387-3 EN
7
Design and principle of operation
3
variable y) is produced for the pneumatic
actuator.
Design and principle of
operation
The electropneumatic Ex d positioner is
mounted on pneumatic control valves. It is
used to assign the valve stem position (controlled variable x) to the control signal (reference variable w). The electric control signal received from a control system is compared to the travel or rotational angle of the
control valve, and a signal pressure (output
The positioner basically consists of an electrical travel sensor system (2), an analog i/p
converter (6) with downstream air capacity
booster (7) and the electronic unit with a
microcontroller (5).
In case of a system deviation, the actuator is
either vented or filled with more air. The signal pressure supplied to the actuator can be
limited to 1.4 bar, 2.4 bar or 3.7 bar by
22
Ex d enclosure
20
Serial
Interface
16
BE
%
FSK
mm
mm
21
23
%
S
4
5
w
13
19
w
PD
17
x
3
G
6
9
8
y
7
1
x
1 Control valve
2 Travel sensor
3 PD controller
4 A/D converter
5 Microcontroller
6 i/p converter
7 Air capacity booster
8 Pressure regulator
9 Flow regulator
13* Analog position
transmitter
16 LCD
17* Control of forced venting
19 D/A converter
20 Serial interface (SSP)
®
21* HART modulation
22 Rotary pushbutton
23* Binary input
* Optional
Fig. 2 · Functional diagram
8
EB 8387-3 EN
Design and principle of operation
software or on site at the positioner. A constant air stream to the atmosphere is created
by the flow regulator (9) with a fixed set
point. The air stream is used to purge the inside of the housing as well as to optimize
the air capacity booster (7). The i/p converter (6) is supplied with a constant upstream pressure by the pressure regulator
(8) to make it independent of the supply
pressure.
All parts are enclosed in an Ex d housing.
The electrical wires are connected over a
separate terminal compartment which is also
designed with Ex d protection.
The extended EXPERTplus diagnostics are integrated into the positioner. It provides information on the positioner and generates diagnostic and status messages, which allow
faults to be pinpointed quickly.
The positioner is suitable for the following
types of attachment using the corresponding
accessories:
Direct attachment to SAMSON
Type 3277 Actuator: section 4.1
Attachment to actuators acc. to
IEC 60534-6 (NAMUR): section 4.2
Attachment to Type 3510 Micro-flow
Valve: section 4.3
Attachment to rotary actuators acc. to
VDI/VDE 3845: section 4.4
4
4
4
4
3.1
Additional equipment
Forced venting
The i/p converter stops working if the operating voltage supply to the relevant terminals
is interrupted. The positioner can no longer
operate and the control valve moves to the
fail-safe position (SAFE) determined by the
actuator, independent of the reference variable.
Binary contact
The positioner has three internal binary signals which can be analyzed over terminals
A/B/C. Two of these signals are intended
for the valve end positions and one signal
for a collective fault alarm. The assignment
of these signals to the A/B/C terminals is
determined over Code 25.
Position transmitter
The position transmitter (13) is a two-wire
transmitter and issues the travel sensor signal as a 4 to 20 mA signal processed by the
microcontroller. Since this signal is issued independent of the positioner’s input signal
(min. current 3.8 mA), the actual travel/angle of rotation is controlled in real-time. Additionally, the position transmitter provides
the possibility of signaling a positioner fault
over a signal current of 2.4 mA or
21.6 mA.
EB 8387-3 EN
9
Design and principle of operation
Binary input
3.2
The positioner has an optional binary input.
The following actions can be performed over
the binary input:
The positioner is equipped with an interface
for HART® protocol (Highway Addressable
Remote Transducer) for communication purposes. Data are transmitted in a superimposed frequency (FSK = Frequency Shift
Keying) on the existing signal loop for the 4
to 20 mA reference variable.
Either a HART® capable handheld communicator or a computer with FSK modem can
be used to establish communication and operate the positioner.
4 Transfer switching state [default]
4
4
4
The switching state of the binary input is
logged.
Set local operation write protection
Settings cannot be changed at the
positioner while the binary input is active. The configuration enabled function
in Code 3 is not active.
Switch between AUTO/MAN
The positioner changes from automatic
mode
(AUTO) mode into manual
mode (MAN) and vice versa.
No action is started if the positioner is in
the fail-safe position (SAFE).
Various diagnostic functions (refer to
EB 8389 EN on EXPERTplus valve diagnostics).
Note: The optional binary output can only
be configured using the TROVIS-VIEW software and over the DD parameters (refer to
EB 8389 EN on EXPERTplus valve diagnostics).
The default switching state is with an open
switch.
Connection to terminals A-B: Binary input
for DC voltage signals
Connection to terminals B-C: Contact input
for an external contact
10
EB 8387-3 EN
Communication
3.2.1 Configuration using
TROVIS-VIEW software
Refer to Table 5 on page 33 for order numbers.
The positioner can be configured using the
TROVIS-VIEW software.
The positioner is equipped for this purpose
with an additional digital SERIAL INTERFACE
to allow a computer to be connected over an
adapter cable from the RS-232 or USB port
of the computer to the positioner.
The TROVIS-VIEW software enables the user
to easily set parameters in the positioner
and view process parameters online.
Note: The TROVIS-VIEW software is a common operator interface for various smart
SAMSON devices. The software together
with a device-specific module allow the configuration and parameterization of the device.
The device-specific module for Type 3731-3
can be downloaded free of charge from the
SAMSON website (Services > Software >
TROVIS-VIEW).
Design and principle of operation
Additional information on TROVIS-VIEW
(e.g. system requirements) can found on the
SAMSON website and in the Data Sheet
T 6661 EN.
EB 8387-3 EN
11
Design and principle of operation
3.3
Technical data
Type 3731-3 Ex d Positioner (technical data in test certificates additionally apply for explosion-protected devices)
Rated travel
Adjustable Direct attachment to Type 3277: 3.6 to 30 mm
Attachment acc. to IEC 60534-6 (NAMUR): 3.6 to 200 mm
Attachment to rotary actuators (VDI/VDE 3845): 24° to 100°
Travel range
Adjustable Adjustable within the initialized travel/angle of rotation;
travel can be restricted to 1 5 at the maximum
Reference variable w
Signal range 4 to 20 mA, 2-wire unit, reverse polarity protection,
min. span 4 mA, static destruction limit 40 V, internal current limit 60 mA
Shutdown action
Type 3731-3xxxxxx000x1x00: Emergency shutdown at 0 mA
Type 3731-3xxxxxx100x1x00: Emergency shutdown at 3.85 mA ± 0.5 mA
Minimum current
3.6 mA for display
Load impedance ≤ 9 V corresponds to 450 Ω at 20 mA
Communication
Local communication SAMSON SSP interface and serial interface adapter
Software requirements TROVIS-VIEW with device-specific module for Type 3731-3
®
HART communication HART® field communication protocol
Impedance in HART® frequency range: Receiving approx. 455 Ω, sending 185 Ω
Software requirements For handheld communicator: device description for Type 3731-3
For PC: DTM file acc. to Specification 1.2, suitable for integrating the positioner in
frame applications that supports the FDT/DTM concept (e.g. PACTware);
integration into AMS™ Suite available.
Supply air
Pressure 1.4 to 6 bar (20 to 90 psi)
Air quality acc. to Max. particle size and density: Class 4 · Oil content: Class 3
ISO 8573-1 Moisture and water: Class 3
edition 2004 Pressure dew point: At least 10 K beneath the lowest ambient temperature to be
expected
Signal pressure (output)
0 bar up to supply pressure · Limitable to 1.4/2.4/3.7 ±0.2 bar via software
Characteristic
Linear/equal percentage/reverse equal percentage
Butterfly valve/Rotary plug valve/Segmented ball valve: linear/equal percentage
User-defined (over operating software and communication)
Deviation from terminal-based conformity ≤ 1 %
Hysteresis
≤ 0.3 %
Sensitivity
≤ 0.1%
Transit time
Separately adjustable up to 240 seconds for supply air and exhaust air
Direction of action
Reversible
Air consumption, steady-state
Independent from supply pressure < 110 ln/h
12
EB 8387-3 EN
Design and principle of operation
Type 3731-3 Ex d Positioner (technical data in test certificates additionally apply for explosion-protected devices)
Air output Pressurized At ∆p = 6 bar: 8.5 mn³/h · At ∆p = 1.4 bar: 3.0 mn³/h · KVmax(20° C) = 0.09
capacity
Vented At ∆p = 6 bar: 14.0 mn³/h · At ∆p = 1.4 bar: 4.5 mn³/h · KVmax(20° C) = 0.15
to actuator
Permissible ambient
temperature
–40 to 80 °C
The limits in the test certificate additionally apply.
Influences
Temperature: ≤ 0.2/10 K · Supply air: None
Vibration: ≤ 0.25 % up to 2000 Hz and 4 g acc. to IEC 770
EMC
Complying with the requirements of EN 61000-6-2, EN 61000-6-3, EN 61326-1 and
NAMUR Recommendation NE 21
Electrical connections
Two threaded connections with ½ NPT thread, optionally with M20 x 1.5
Screw terminals for 2.5 mm² wire cross-section
Explosion ATEX
protection
Type 3731-321: II 2G Ex db IIC T6; II 2G Ex db eb IIC T6;
II 2G Ex db [ia] IIC T6; II 2G Ex ia IIC T6; II 2D Ex tb IIIC T80°C IP66
CSA
Type 3731-323: Class I, Zone 1, Group IIB+H2 T4...T6;
Class I, Div. 1+2, Groups B, C, D T4...T6; Class II, Div. 1, Groups E, F, G
FM
Type 3731-323: Class I, Div. 1+2, Groups B, C, D; Class I, Zone 1, Groups IIB+H2; Class I,
Div. 1+2 Groups E, F, G; Class III
GOST
Type 3731-321: 1Ex d IIC T6/T5/T4 Gb X; 1Ex d e IIC T6/T5/T4 Gb X;
Ex tb IIIC T 80°C Db X
IECEx
Type 3731-321: Ex d IIC T6, T5, T4 Gb; Ex d e IIC T6, T5, T4 Gb; Ex tb IIIC T80°C Db IP66
INMETRO
Type 3731-321: Ex d IIC T* Gb; Ex de IIC T* Gb;
JIS
Type 3731-327: Ex d IIC T6
* See ambient temperature
KCS Korea Type 3731-321: Ex d IIC T6/T5/T4
NEPSI
Type 3731-321: Ex d IIC T6~T4; Ex de IIC T6~T4
STCC
Type 3731-321: 1Ex d IIC T4...T6; 1Ex de IIC T4...T6
Degree of protection
IP 66/NEMA 4 X
Use in safetyinstrumented systems
(SIL)
Observing the requirements of IEC 61508, the systematic capability of the control valve for
emergency venting as a component in safety-instrumented systems is given.
Materials
Die-cast aluminum EN AC-AlSi10Mg(Fe) (EN AC-44300) acc. to DIN EN 1706
chromated and powder paint coating
Housing
External
parts
Weight
Use is possible on observing the requirements of IEC 61511 and the required hardware fault
tolerance in safety-instrumented systems up to SIL 2 (single device/HFT = 0) and SIL 3 (redundant configuration/HFT = 1).
Stainless steel 1.4301/1.4305/1.4310
Approx. 2.5 kg
EB 8387-3 EN
13
Design and principle of operation
Additional equipment
Optional binary output,
software limit switch, galvanically isolated
Connection: Optionally NAMUR EN 60947-5-6 or PLC, configurable as a limit switch or fault alarm output
Signal status
Operating voltage
Terminals B-C
Switching output AC/DC (PLC)
Terminals A-B
Conductive/remaining voltage < 1.7 V
≥ 2.2 mA
Non-conducting/high resist. I < 100 µA
≤ 1.0 mA
Switch. capacity: 40 V DC/28 V/AC 0.3 A
Static destr. limit: 45 V DC/32 V/AC 0.4 A
Only for connection to NAMUR signal
converter acc. to EN 60947-5-6
Optional forced venting, galvanically isolated
Input
0 to 40 V DC/0 to 28 V AC, static destruction limit 45 V DC/32 V AC,
input resistance ≥ 7 kΩ
Signal
Fail-safe position at an input voltage ≤ 3 V
Normal operation at an input voltage > 5.5 V
Optional analog position transmitter, two-wire transmitter
Supply voltage
11 to 35 V DC, reverse polarity protection, static destruction limit 45 V
Output signal
4 to 20 mA
Direction of action
Reversible
Operating range
–1.25 to 103 % of the travel range, corresponding to 3.8 to 20.5 mA, optionally also for
fault alarm over 2.4 or 21.6 mA acc. to NAMUR Recommendation NE 43
Characteristic
Linear
Hysteresis and
HF influence
Same as positioner
Other influences
Same as positioner
Fault alarm
Can be issued with current signal 2.4 mA or 21.6 mA
Optional binary input, galvanically isolated, optionally for detection of an externally applied voltage or for operation
of an external floating contact · Switching behavior configured as required, default setting (see below)
Voltage input function,
polarity insensitive, 0 to 24 V DC voltage to be applied, input resistance 6.5 kΩ
Static destruction limit
40 V
Voltage
> 6 V: Switching state ON · < 4 V: Switching state OFF
Contact input function,
for external switch (floating contact)
Electrical data
Open-circuit voltage when contact is open: 10 V, pulsed DC current, peak value 100 mA
Contact
Closed: Switching state ON · Open: Switching state OFF
14
EB 8387-3 EN
Attachment to the control valve – Mounting parts and accessories
4
Attachment to the control
valve – Mounting parts and
accessories
WARNING!
Attach the positioner, keeping the following
sequence:
1. Mount the positioner on the control valve
2. Connect the supply air
3. Connect the electrical power
4. Perform the start-up settings
The positioner is suitable for the following
types of attachment:
4 Direct attachment to SAMSON
Type 3277 Actuator
4 Attachment to actuators according to
IEC 60534-6 (NAMUR)
4 Attachment to Type 3510 Micro-flow
Valve
4 Attachment to rotary actuators
NOTICE
Attach the positioner to the control valve,
observing the following instructions to avoid
damaging the positioner.
– Use only the mounting parts/accessories
listed in the Tables 1 to 5 (pages 30 to
33) to mount the positioner. Observe the
type of attachment!
– The positioner is fitted with pneumatic
connections with ¼ NPT threads. If you
need G ¼ threads, attach the connecting
plate (6) listed in the accessories.
– Observe the assignment between lever
and pin position (see travel tables on
page 16).
– Fit a signal pressure restriction (Table 5
on page 33) for actuators with diaphragm areas smaller than 240 cm².
Lever and pin position
The positioner is adapted to the actuator
and to the rated travel by the lever on the
back of the positioner and the pin inserted
into the lever.
The travel tables on page 16 show the maximum adjustment range at the positioner. The
travel that can be implemented at the valve
is additionally restricted by the selected
fail-safe position and the required compression of the actuator springs.
The positioner is standard equipped with the
lever M (pin position 35).
Fig. 3 · Lever M with pin position 35 (delivered state)
Note: If the standard mounted lever M is replaced, the newly mounted lever must be
moved once all the way as far as it will go
in both directions to adapt it to the internal
measuring lever.
EB 8387-3 EN
15
Attachment to the control valve – Mounting parts and accessories
Travel tables
Note: The lever M is included in the scope of delivery.
Levers S, L, XL for attachment according to IEC 60534-6 (NAMUR) are available as accessories (see Table 3 on page 32).
Direct attachment to Type 3277-5 and Type 3277 Actuators
Adjustment range at positioner
1)
Actuator size
Rated travel
[cm²]
[mm]
Min.
Travel
Max.
Required
lever
Assigned
pin position
120
7.5
5.0
to
25.0
M
25
120/175/240/350
15
7.0
to
35.0
M
35
355/700/750
30
10.0
to
50.0
M
50
Required
lever
Assigned
pin position
Attachment according to IEC 60534-6 (NAMUR)
SAMSON valves/Type 3271 Actuator
Actuator size
Rated travel
Adjustment range at positioner
Other valves/actuators
1)
[cm²]
[mm]
min.
Travel
60 and 120 with
Type 3510 Valve
max.
7.5
3.6
to
18.0
S
17
5.0
to
25.0
M
25
7.0
to
35.0
M
35
50
120
7.5
120/175/240/350
15
700/750
7.5
355/700/750
15 and 30
10.0
to
50.0
M
1400/2800
30
14.0
to
70.0
L
70
1400/2800
60
20.0
to
100.0
L
100
1400/2800
120
40.0
to
200.0
XL
200
Attachment to rotary actuators according to VDI/VDE 3845
Rotary actuators
Min.
24
1)
16
Opening angle
Max.
Required
lever
Assigned
pin position
to
100°
M
90°
Values are based on the NOM initialization mode
EB 8387-3 EN
Attachment to the control valve – Mounting parts and accessories
4.1
Direct attachment
2.
4.1.1 Type 3277-5 Actuator
Refer to Table 1 on page 30 for required
mounting parts and accessories.
3.
Actuator with 120 cm²
NOTICE
If a solenoid valve or similar is additionally
mounted to the actuator, observe the following instructions which differ from the instructions otherwise described:
– The switchover plate (9) is omitted.
– The signal pressure must be routed from
the signal pressure output over the connecting plate (accessories order no.
1400-6820) to the actuator.
– The hole for the signal pressure output
must be fitted with the screw restriction
(accessories order no. 1400-6964/item
no. 0390-1424).
– Do not remove the screw plug (4) at the
back of the positioner.
Depending on the type of positioner attachment, the signal pressure is routed either left
or right of the yoke through a bore to the
actuator diaphragm.
1.
Refer to Fig. 4 to select the symbol to
match the required fail-safe position
and how the positioner is attached:
Fail-safe position:
Actuator stem extends = Fail-close
Actuator stem retracts = Fail-open
Positioner attachment: Left or right with
view looking onto the switchover plate
4.
5.
6.
7.
8.
Align the marking of the switchover
plate (9) to the corresponding symbol
and mount the plate on the actuator
yoke.
If applicable, mount pressure gauge
bracket (7) with pressure gauges or, in
case G ¼ threaded connections are required, the connecting plate (6), making sure both seal rings (6.1) are
seated properly.
Remove screw plug (4) on the back of
the positioner and seal the signal pressure output "Output 38" on the connecting plate (6) or on the pressure
gauge bracket (7) with the stopper (5)
included in the accessories.
Place follower clamp (3) on the actuator stem, align and screw it tight so that
the mounting screw is located in the
groove of the actuator stem.
Press brass restriction (accessories order no. 1400-6964/item no.
0390-1423) into the seal of the signal
pressure input at the actuator yoke.
Mount cover plate (10) with the narrow
side of the cut-out opening (Fig. 4, left)
pointing towards the signal pressure
connection. Make sure that the bonded
gasket (14) points towards the actuator
yoke.
15 mm travel: Keep the follower pin
(2) at lever M (1) on the back of the
positioner in the pin position 35 (delivered state).
7.5 mm travel: Remove the follower pin
(2) from the pin position 35, reposition
EB 8387-3 EN
17
Attachment to the control valve – Mounting parts and accessories
it in the hole for pin position 25 and
screw tight.
9. Insert formed seal (15) into the groove
of the positioner housing, pressing the
four retaining rings over the housing
screws and both fittings into the housing recesses.
10. Thread the bias spring (17) through the
crosspiece underneath the lever (1) and
push into the hole in the housing. Push
the lever (1) until it engages into place.
Place positioner on the cover plate (10)
and fasten it using the three fixing
screws.
Check to make sure that the follower
pin (2) rest on top of the follower clamp
(3). The lever (1) must rest on the follower clamp with spring force.
Make sure that the seal ring (10.1) is
inserted in the borehole of the cover
plate.
11. Mount cover (11) on the other side.
Make sure that the vent plug (11.1)
points downwards when the control
valve is installed to allow any condensed water that collects to drain off.
18
EB 8387-3 EN
Attachment to the control valve – Mounting parts and accessories
1
1.1
1.2
2
3
4
5
6
6.1
7
8
9
Symbols
Switchover plate (9)
Actuator stem
extends
Left attachment Right attachment
Actuator stem
retracts
A
Signal pressure
input for left
attachment
Marking
Signal pressure input
for right attachment
A-A
15
14
Lever
Nut
Disk spring
Follower pin
Follower clamp
Screw plug
Stopper
Connecting plate for G ¼
Seal rings
Pressure gauge bracket
Press. gauge mounting kit
Switchover plate
for actuator
10
Cover plate
10.1 Seal ring
11
Cover
11.1 Vent plug
14
Gasket
15
Formed seal
17
Bias spring (only with
direct attachment)
11.1
1
2
Cut-out of
cover plate
3
1.1
1.2
17
4
Supply 9
A
5
6
6.1
10.1
10
6
Output 38
11
9
Signal pressure input
with brass restriction
7
8
Fig. 4 · Direct attachment for Type 3277-5 Actuator with 120 cm²
EB 8387-3 EN
19
Attachment to the control valve – Mounting parts and accessories
4.1.2 Type 3277 Actuator
Refer to Table 2 on page 31 for the required
mounting parts and accessories.
Actuators with 175 to 750 cm²
Mount the positioner onto the yoke as shown
in Fig. 5. The signal pressure is routed to the
actuator over the connection block (12), for
actuators with fail-safe action "Actuator
stem extends" internally through a bore in
the valve yoke and for "Actuator stem retracts" through external piping.
1.
2.
3.
4.
5.
20
Place follower clamp (3) on the actuator stem, align and screw it tight so that
the mounting screw is located in the
groove of the actuator stem.
Mount cover plate (10) with the narrow
side of the cut-out (Fig. 5, left) pointing
towards the signal pressure connection.
Make sure that the bonded gasket (14)
points towards the actuator yoke.
Actuators with 355, 700 and 750 cm²:
Remove the follower pin (2) at lever M
(1) on the back of the positioner from
pin position 35, reposition it in the hole
for pin position 50 and screw tight.
Actuators 175 to 350 cm² with 15 mm
travel: The follower pin (2) remains in
pin position 35 (delivered state).
Insert formed seal (15) into the groove
of the positioner housing, pressing the
four retaining rings over the housing
screws and both fittings into the housing recesses.
Thread the bias spring (17) through the
crosspiece underneath the lever (1) and
push into the hole in the housing. Push
EB 8387-3 EN
6.
7.
8.
the lever (1) until it engages into place.
Place positioner on the cover plate (10)
and fasten it using three fixing screws.
Check whether the follower pin (2) rests
on top of the follower clamp (3).
The lever (1) must rest on the follower
clamp with spring force.
Make sure that the tip of the gasket
(16) projecting from the side of the
connection block (12) is positioned
above the actuator symbol that corresponds with the actuator with fail-safe
action "Actuator stem extends" or "Actuator stem retracts." If necessary, remove the three fixing screws and the
cover plate. Then reposition the gasket
(16) turned by 180°. The previous version of the connection block (Fig. 5,
bottom) requires the switch plate (13) to
be turned such that the corresponding
actuator symbol points to the marking.
Actuators with 175 cm²: Unscrew the
filter from the signal pressure input and
first screw the screw restriction (accessories order no. 1400-6964/item no.
0390-1424) into the input and then the
filter.
Place the connection block (12) with the
associated seal rings against the
positioner and the actuator yoke. Screw
it tight using the fixing screw (12.1).
For actuators with fail-safe action "Actuator stem retracts", additionally remove the stopper (12.2) and attach the
external signal pressure line.
Attachment to the control valve – Mounting parts and accessories
1
1.1
1.2
2
3
10
11
11.1
12 Connection block
12.1 Screw
12.2 Stopper or connection for
external piping
13 Switch plate
14 Gasket
15 Formed seal
16 Gasket
17 Bias spring
(only for direct attachment)
Lever
Nut
Disk spring
Follower pin
Follower clamp
Cover plate G ¼
Cover
Vent plug
15
10 14
1
2
3
11
11.1
2
1.1
1.2
Cut-out of
cover plate (10)
17
View AA
Ansicht
16
View CC
Ansicht
16
G
C
G 3/8
SUPPLY
Actuator stem
retracts
extends
16
12
SUPPLY
12.1
12.2
A
Ansicht
View BB
13
12
SUPPLY
Connection block (old)
with switch plate (13)
B
Stem retracts
Stem extends
12
Marking
12.1
12.2
Fig. 5 · Direct attachment – Signal pressure connection for Type 3277 Actuator with 175 to 750 cm²
EB 8387-3 EN
21
Attachment to the control valve – Mounting parts and accessories
9.
4.2
Mount cover (11) on the other side.
Make sure that the vent plug (11.1)
points to the back when the control
valve is installed to allow any condensed water that collects to drain off.
Attachment according to
IEC 60534-6 (NAMUR)
Refer to Table 3 on page 32 for the required
mounting parts and accessories.
The positioner is attached to the control
valve using a NAMUR bracket (10).
1.
2.
22
Actuator with 175 cm²:
Unscrew the filter from the signal pressure input and first screw the screw restriction (accessories order no.
1400-6964/item no. 0390-1424) into
the input and then the filter.
Actuator sizes 120 to 750 cm²:
Screw the two bolts (14) to the bracket
(9.1) of the stem connector (9), place
the follower plate (3) on top and tighten
it using the screws (14.1).
Actuator size 2800 cm² and 1400 cm²
(120 mm travel):
– For a travel of 60 mm or smaller,
screw the longer follower plate (3.1)
directly to the stem connector (9).
– For a travel exceeding 60 mm,
mount the bracket (16) first and then
the follower plate (3) to the bracket
together with the bolts (14) and
screws (14.1).
EB 8387-3 EN
3.
Mount NAMUR bracket (10) to the control valve as follows:
– For attachment to the NAMUR rib,
use an M8 screw (11), washer and
toothed lock washer directly in the
yoke bore.
– For attachment to valves with
rod-type yokes, use two U-bolts (15)
around the yoke. Align the NAMUR
bracket (10) in such a way that the
slot of the follower plate (3/3.1) is
centrally aligned with the NAMUR
bracket at mid valve travel.
4. If applicable, mount pressure gauge
bracket (7) with pressure gauges or, in
case G ¼ threaded connections are required, the connecting plate (6), making sure both seal rings (6.1) are
seated properly.
5. Screw a screw restriction (accessories
order no. 1400-6964/item no.
0390-1424) into the signal pressure
output for actuators with diaphragm areas smaller than 240 cm².
6. Select required lever (1) size M, L or XL
and pin position according to the actuator size and valve travels listed in the
table on page 16.
Lever M with pin position 25 or 50:
6.1 Remove follower pin (2) from pin
position 35 and screw it into the
required hole.
Lever L or XL:
6.1 Unscrew the standard lever M from
the shaft of the positioner.
Attachment to the control valve – Mounting parts and accessories
15
11
10
Attachment to
NAMUR rib
9
9.1
1
1.1
1.2
2
3
3.1
6
Lever
Nut
Disk spring
Follower pin
Follower plate
Follower plate
Connecting plate
(only for G ¼)
6.1 Seal rings
7
8
Pressure gauge bracket
Pressure gauge
mounting kit
9
Stem connector
9.1 Bracket
10 NAMUR bracket
11 Screw
14 Bolt
14.1 Screw
15 U-bolt
16 Bracket
Attachment to rod-type yoke
Rods with 20 to 35 mm Ø
3.1
16
Additional bracket for
actuators with 2800 cm²
and travel ≥ 60 mm
14
XL and L lever
1
3
1
2
1.1
1.2
14.1
Fit screw restriction into output (38)
for actuators smaller than 240 cm²
1
6
6.1
7
8
Fig. 6 · Attachment according to IEC 60534-6 (NAMUR)
EB 8387-3 EN
23
Attachment to the control valve – Mounting parts and accessories
7.
4.3
6.2 Screw the long follower pin (2) included in the mounting kit in the
pin position of the required lever
(1) assigned in the table.
6.3 Place lever (1) on the positioner
shaft and screw tight using the disk
spring (1.2) and nut (1.1).
6.4 Move the lever once all the way as
far as it will go in both directions.
Place positioner on the NAMUR
bracket in such a manner that the follower pin (2) rests in the slot of the follower plate (3/3.1). Adjust the lever (1)
correspondingly. Screw the positioner
to the NAMUR bracket using three fixing screws.
Attachment to Type 3510
Micro-flow Valve
Refer to Table 3 on page 32 for the required
mounting parts and accessories.
The positioner is attached to the valve yoke
using a bracket.
1.
2.
3.
4.
24
Mount the travel indication scale (accessories) onto the outer side of the
yoke using the hex screws (12.1),
ensuring that the scale is aligned with
the stem connector.
Fasten the bracket (9.1) onto the stem
connector.
Fasten the two pins (9.2) to the bracket
(9.1) on the stem connector. Mount the
follower plate (3) and fasten it using the
screws (9.3).
Fasten the hex bar (11) onto the outer
side of yoke by screwing the M8 screws
EB 8387-3 EN
(11.1) directly into the holes on the
yoke.
5. Fasten the bracket (10) to the hex bar
(11) using the hex screw (10.1),
washer and tooth lock washer.
6. If applicable, mount pressure gauge
bracket (7) with pressure gauges or, in
case G ¼ threaded connections are required, the connecting plate (6), making sure both seal rings (6.1) are
seated properly.
7. Screw the restriction (accessories order
no. 1400-6964/item no. 0390-1424)
into the signal pressure output of the
positioner (or output of the pressure
gauge bracket or connecting plate).
8. Unscrew the standard installed lever M
(1) including follower pin (2) from the
positioner shaft.
9. Take lever S (1) and screw follower pin
(2) in the bore for pin position 17.
10. Place lever S on the positioner shaft
and screw tight using the disk spring
(1.2) and nut (1.1).
Move the lever once all the way as far
as it will go in both directions.
11. Place positioner on the bracket (10) in
such a manner that the follower pin
slides into the groove of the clamp (3).
Adjust the lever (1) correspondingly.
Screw the positioner to the bracket (10)
using both its screws.
Attachment to the control valve – Mounting parts and accessories
1
1.1
1.2
2
3
6
6.1
7
8
9
9.1
9.2
9.3
10
10.1
11
11.1
12.1
Lever
Nut
Disk spring
Follower pin
Follower plate
Connecting plate
Seal rings
Pressure gauge bracket
Pressure gauge mounting kit
Stem connector
Bracket
Pin
Screws
Bracket
Screw
Hex bar
Screws
Screws
10.1
11.1
11
9
12.1
9.1
9.2
3
9.3
10
Screw restriction into
signal pressure output (38)
6
6.1
1.1
1.2
1
2
Lever S
7
8
Fig. 7 · Attachment to Type 3510 Micro-flow Valve
EB 8387-3 EN
25
Attachment to the control valve – Mounting parts and accessories
4.4
Attachment to rotary
actuators
6.
Refer to Table 4 on page 33 for the required
mounting parts and accessories.
Both mounting kits contain all the necessary
mounting parts. First select correct actuator
size. Prepare actuator, and mount required
adapter supplied by the actuator manufacturer, if necessary.
1.
2.
3.
4.
5.
26
Mount the housing (10) onto the rotary
actuator. In case of VDI/VDE attachment, place spacers (11) underneath, if
necessary.
For SAMSON Type 3278 and VETEC
S160 Rotary Actuator, screw the
adapter (5) onto the free end of the
shaft or place adapter (5.1) onto the
shaft of the VETEC R Actuator.
Place adapter (3) onto Type 3278,
VETEC S160 and VETEC R Actuator. For
VDI/VDE version, this step depends on
the actuator size.
Stick adhesive label (4.3) onto the coupling wheel in such a manner that the
yellow part of the sticker is visible in the
window of the housing when the valve
is OPEN. Adhesive labels with explanatory symbols are enclosed and can be
stuck on the housing, if required.
Screw tight coupling wheel (4) onto the
slotted actuator shaft or adapter (3) using screw (4.1) and disk spring (4.2).
Undo the standard follower pin (2) on
the lever M (1) of the positioner. Attach
the follower pin (Ø 5) included in the
mounting kit to pin position 90°.
EB 8387-3 EN
7.
8.
If applicable, mount pressure gauge
bracket (7) with pressure gauges or, in
case G ¼ threaded connections are required, the connecting plate (6), making sure both seal rings (6.1) are
seated properly.
For double-acting, springless rotary actuators, a reversing amplifier is required to attach the positioner to the
actuator. Refer to section 4.5.
For actuators with a volume of less than
300 cm³, screw the screw restriction
(accessories order no.1400-6964/item
no. 0390-1424) into the signal pressure output of the positioner (or the output of the pressure gauge bracket or
connecting plate).
Place positioner on housing (10) and
screw it tight. Considering the actuator's direction of rotation, align lever
(1) so that it engages in the correct slot
of the coupling wheel with its follower
pin (Fig. 8).
Counterclockwise
1
10
4
Clockwise
Fig. 8 · Direction of rotation
Attachment to the control valve – Mounting parts and accessories
1
1.1
1.2
2
3
4
4.1
4.2
4.3
5
Lever
Nut
Disk spring
Follower pin
Adapter
Coupling wheel
Screw
Disk spring
Adhesive label
Actuator shaft
or adapter
5.1 Adapter
6
6.1
7
8
10
10.1
11
Connecting plate (only for G ¼)
Seal rings
Pressure gauge bracket
Pressure gauge mounting kit
Adapter housing
Screws
Spacers
Fit screw restriction into signal pressure output for
actuators with < 300 cm³ volume
6
6.1
7
8
1
1.1
1.2
2
4.1
4.2
4
4.3
4.1
4.2
4
4.3
3
3
5.1
10.1
5
10.1
10
11
10
5
SAMSON Type 3278
VETEC S160, VETEC R
Fig. 9 · Attachment to rotary actuators
Attachment acc. to VDI/VDE 3845
(Sept. 2010) level 1, size AA1 to AA4
(see section 12.1)
EB 8387-3 EN
27
Attachment to the control valve – Mounting parts and accessories
4.5
Reversing amplifier for
double-acting actuators
For the use with double-acting actuators, the
positioner must be fitted with a reversing
amplifier, e.g. the SAMSON Type 3710 Reversing Amplifier (see Mounting and Operating Instructions EB 8392 EN).
If a different reversing amplifier (item no.
1079-1118 or 1079-1119) is used, follow
the mounting instructions described in section 4.5.1.
The following applies to all reversing amplifiers:
The output signal pressure of the positioner
is supplied at the output A1 of the reversing
amplifier. An opposing pressure, which
equals the required supply pressure when
added to the pressure at A1, is applied at
output A2.
The rule A1 + A2 = Z applies.
A1: Output A1 leading to the signal pressure
connection at the actuator which opens the
valve when the pressure increases
A2: Output A2 leading to the signal pressure
connection at the actuator which closes the
valve when the pressure increases
4.5.1 Reversing amplifier
(1079-1118 or 1079-1119)
NOTICE
Do not unscrew sealing plug (1.5) out of the
reversing amplifier.
28
EB 8387-3 EN
1.
2.
3.
4.
Thread the special nuts (1.3) from the
accessories of the reversing amplifier
into the boreholes of the positioner.
Remove the rubber seal (1.4).
Insert the gasket (1.2) into the recess of
the reversing amplifier and push both
the hollowed special screws (1.1) into
the connecting boreholes A1 and Z.
Position the reversing amplifier (1) and
screw tight using both the special
screws (1.1).
Use a screwdriver (8 mm wide) to
screw the enclosed filters (1.6) into the
connecting boreholes A1 and Z.
NOTICE
On start up of double-acting actuators, the
following settings as described in section 7
must be made:
– Pressure limit (Code 16) = No
– Fail-safe position (Code 0) = AtO (AIR
TO OPEN)
Pressure gauge attachment
The mounting sequence shown in Fig. 10 remains unchanged. Screw a pressure gauge
bracket onto the connections A1 and Z.
Pressure gauge
bracket:
G¼
¼ NPT
1400-7106
1400-7107
Pressure gauges for supply air Z and output
A1 as listed in Tables 1 to 4.
Attachment to the control valve – Mounting parts and accessories
From the positioner
Output 38
A1
Supply 9
Z
A2
1.3
1.1 1.2
1.4
1.5
1.6
A2
1
1.1
1.2
1.3
1.4
1.5
1.6
Reversing amplifier
Special screws
Gasket
Special nuts
Rubber seal
Sealing plug
Filter
Supply 9
Control signals to
the actuator
Z
Output 38
A1
A1
1.3
1.2
1.1
1
1.6
Fig. 10 · Mounting a reversing amplifier (1079-1118 or 1079-1119)
EB 8387-3 EN
29
Attachment to the control valve – Mounting parts and accessories
4.6
Required mounting parts and accessories
Order no.
Table 1 · Direct attachment to Type 3277-5 (Fig. 4)
Mounting parts For actuators with 120 cm² effective diaphragm area
1400-7452
Version compatible with paint for actuators 120 cm² or smaller
1402-0940
Switchover plate (old) for Actuator Type 3277-5xxxxxx.00 (old)
1400-6819
Switchover plate new for Actuator Type 3277-5xxxxxx.01 (new) 1)
Accessories for
Connecting plate new for Actuator Type 3277-5xxxxxx.01 (new) 1), G
the actuator
Connecting plate old for Actuator Type 3277-5xxxxxx.00 (old): G 18
Connecting plate old for Actuator Type 3277-5xxxxxx.00 (old):
1
8
1400-6822
1
8
Pressure gauge mounting kit (8) up to max. 6 bar (output/supply)
1400-6823
1400-6821
G¼
1400-7461
G¼
1400-7458
¼ NPT
1400-7459
St. st./Brass
1400-6950
St. st./St. st.
1400-6951
Only new switchover and connecting plates can be used with new actuators (Index 01).
Old and new plates are not interchangeable.
EB 8387-3 EN
NPT
1400-6820
Accessories for Pressure gauge bracket (7)
the positioner
30
1
8
NPT
Connecting plate (6)
1)
and
Attachment to the control valve – Mounting parts and accessories
Table 2 · Direct attachment to Type 3277 (Fig. 5)
Mounting
parts
Order no.
Standard version for actuators with 175, 240, 350, 355, 700, 750 cm²
Steel
175 cm²
Stainl.
steel
Steel
240 cm²
Stainl.
steel
Steel
350 cm²
Stainl.
steel
Required piping with screw fitting
– for "Actuator stem retracts"
– with air purging of the top diaphragm
chamber
Accessories
Steel
355 cm²
Stainl.
steel
Steel
700 cm²
Stainl.
steel
Steel
750 cm²
Stainl.
steel
Connection block with seals and screw
Pressure gauge mounting kit (8) up to max. 6 bar
(output/supply)
1400-7453
G
1
4
1
4
3
8
/G
1
4
NPT
1402-0913
3
1400-6447
8
1
4
8
/G
1
4
1
4
NPT
1402-0979
3
1402-0973
8
1
4
3
8
3
1
4
/G
3
8
1402-0915
1400-6449
8
NPT
1402-0916
1402-0974
/ G 38
3
1402-0980
1400-6448
/ G 38
/G
1402-0914
1402-0972
/ G 38
3
1402-0912
1400-6446
/ G 38
NPT /
1402-0981
1402-0975
8
NPT
1402-0982
1
4
1400-8819
NPT
1402-0901
G
1
4
1400-6445
8
NPT / 3 8 NPT
G
1
4
1
4
NPT /
G
1
4
1402-0911
3
NPT / 3 8 NPT
G
1
4
NPT
NPT / 3 8 NPT
G
1
4
8
/G
NPT /
G
1
4
1
4
1402-0978
1400-6444
/ G 38
3
1402-0976
1402-0971
NPT / 3 8 NPT
G
1
4
1
4
NPT /
G
1
4
NPT
NPT / 3 8 NPT
G
1
4
8
/ G 38
NPT /
G
1
4
3
NPT / 3 8 NPT
G
1
4
1
4
1402-0970
/ G 38
NPT /
G
1
4
1
4
Steel/brass
1400-6950
St. steel/St. steel
1400-6951
EB 8387-3 EN
31
Attachment to the control valve – Mounting parts and accessories
Table 3 · Attachment to NAMUR ribs or control valves with rod-type yokes
(20 to 35 mm rod diameter) according to IEC 60534-6 (Figs. 6 and 7)
Order no.
Travel in mm Lever
For actuators
7.5
S
Type 3271-5 Actuator with 60/120 cm² on Type 3510 Valve (Fig. )
5 to 50
M
14 to 100
L
40 to 200
XL
30 or 60
L
1)
1400-7454
Actuators from other manufacturers and Type 3271, versions 1000 and
1400-60
1400-7455
Actuators from other manufacturers and Type 3271, versions 1400-120 and
2800 cm² with 120 mm travel
1400-7456
Type 3271, versions 1400-120 and 2800 cm² (30 or 60 mm travel)
1400-7466
Mounting bracket for Emerson and Masoneilan linear actuators; a mounting
kit acc. to IEC 60534-6 is necessary depending on the travel (see above)
1400-6771
Valtek Type 25/50
1400-9554
Connecting plate (6)
Accessories
Pressure gauge bracket (7)
Pressure gauge mounting kit (8) up to max. 6 bar (output/supply)
32
EB 8387-3 EN
1402-0478
Actuators from other manufacturers and Type 3271with 120 to 750 cm²
G¼
1400-7461
¼ NPT
1400-7462
G¼
1400-7458
¼ NPT
1400-7459
St. st./Brass
1400-6950
St. steel/St. st.
1400-6951
Attachment to the control valve – Mounting parts and accessories
Order no.
Table 4 · Attachment to rotary actuators (Figs. 8 and 9)
Attachment acc. to VDI/VDE 3845 (September 2010), see section 12.1 for details
Mounting
parts
Actuator surface corresponds to level 1
Size AA1 to AA4, heavy-duty version
Size AA5, heavy-duty version (e.g. Air Torque 10 000)
1400-9244
1400-9542
Bracket surface corresponds to level 2, heavy-duty version
1400-9526
Attachment for SAMSON Type 3278 with 160 cm² and for VETEC Type S160, R and
M, heavy-duty version
1400-9245
Attachment for SAMSON Type 3278 with 320 cm² and for VETEC Type S320,
heavy-duty version
1400-5891
and
1400-9526
1400-9120
Attachment to Camflex II
Connecting plate (6)
Accessories
Pressure gauge bracket (7)
Pressure gauge mounting kit up to max. 6 bar (output/supply)
G
1
4
1400-7461
NPT
1400-7462
1
4
1400-7458
G
1
4
1
4
NPT
1400-7459
St. steel/brass
1400-6950
St. steel/st. steel
1400-6951
Table 5 · General accessories
Accessories
Pneumatic reversing amplifier for double-acting actuators
Type 3710
Signal pressure restrictions (screw restriction (item no. 0390-1424) and brass restriction (item no. 0390-1423))
1400-6964
TROVIS-VIEW with device-specific module for Type 3731-3 (refer to section 3.2.1)
Serial interface adapter (SAMSON SSP interface – RS-232 port on computer)
1400-7700
Isolated USB interface adapter (SAMSON SSP interface – USB port on computer)
including TROVIS-VIEW CD-ROM
1400-9740
EB 8387-3 EN
33
Connections
5
Connections
WARNING!
Mount the positioner, keeping the following
sequence:
1. Mount the positioner on the control valve
2. Connect the supply air
3. Connect the electrical power
4. Perform the start-up settings
The connection of the electrical auxiliary
power may cause the actuator stem to move,
depending on the operating mode.
Do not touch the actuator stem or obstruct it
to avoid risk of injury to hands or fingers.
5.1
Pneumatic connections
The maximum input pressure (supply pressure) must not exceed 6 bar.
DANGER!
Danger from the formation of an explosive
atmosphere!
The operator of the apparatus must ensure
that the working medium cannot form an explosive atmosphere, i.e. only such gases
may be used which are free from substances
whose presence in the medium might lead to
the formation of an explosive atmosphere
(e.g. do not use flammable gases, oxygen or
oxygen-enriched gases).
34
EB 8387-3 EN
Follow the instructions below to avoid damaging the positioner.
– The supply pressure at the input must
not exceed 6 bar.
– The screw fittings with ¼ NPT thread can
be screwed directly into the positioner.
In case G ¼ threaded connections are
required, the fittings must be screwed
into the connecting plate (6) or pressure
gauge mounting block or connection
block available from the accessories.
Customary screw-in fittings for metal and
copper pipes or plastic hoses can be
used.
– The supply air must be dry and free from
oil and dust.
The maintenance instructions for upstream pressure reducing stations must be
observed.
Blow through all air pipes and hoses thoroughly prior to connecting them.
If the positioner is attached directly to the
Type 3277 Actuator, the connection of the
positioner's output pressure to the actuator is
fixed. For attachment according to
IEC 60534-6 (NAMUR), the signal pressure
can be routed to either the top or bottom diaphragm chamber of the actuator, depending on the actuator's fail-safe action "Actuator stem extends" or "Actuator stem retracts".
For rotary actuators, the manufacturer's
specifications for connection apply.
Connections
5.1.1 Signal pressure gauges
If there are no specifications, calculate as
follows:
To monitor the supply air (Supply) and signal pressure (Output), we recommend that
pressure gauges be attached (see accessories in Tables 1 to 5).
Required supply pressure =
Upper bench range value + 1 bar
5.1.2 Supply pressure
The required supply pressure (of supply air)
depends on the bench range and the actuator's operating direction (fail-safe action).
The bench range is registered on the nameplate either as spring range or signal pressure range depending on the actuator.
The direction of action is marked FA or FE,
or by a symbol.
5.1.3 Signal pressure (output)
The signal pressure at the output (Output 38) of the positioner can be limited to
1.4, 2.4 or 3.7 bar in Code 16.
The limitation is not activated [No] by default.
Actuator stem extends FA (AIR TO OPEN)
Fail-close (for globe and angle valves):
Required supply pressure = Upper bench
range value + 0.2 bar, minimum 1.4 bar.
Actuator stem retracts FE (AIR TO CLOSE)
Fail-open (for globe and angle valves):
For tight-closing valves, the maximum signal
pressure pstmax is roughly estimated as follows:
d 2 ⋅ π ⋅ ∆p
[bar]
pstmax = F +
4⋅A
d = Seat diameter [cm]
∆p = Differential pressure across the valve
[bar]
A = Actuator diaphragm area [cm²]
F
= Upper bench range of the actuator
[bar]
EB 8387-3 EN
35
Connections
5.2
Electrical connections
DANGER!
Risk of electric shock and/or the formation of an explosive atmosphere!
4 For electrical installation, you are required to observe the relevant
4
electrotechnical regulations and the accident prevention regulations that apply in the country of use.
The following standard applies for assembly and installation in hazardous
areas: EN 60079-14 (VDE 0165 Part 1) Explosive atmospheres - Electrical
installations design, selection and erection.
Connection to conform with the type of protection Ex d (EN 60079-1):
The Type 3731-321 Positioner must be connected over the appropriate cable
glands or conduit systems which meet the requirements of EN 60079-1 (Electrical apparatus for explosive gas atmospheres - Part 1: Flameproof enclosures
"d") Clauses 13.1 and 13.2 and for which a special test certificate exists.
Do not use simple types of cable glands or blanking plugs.
Seal any cable entries that are not used using blanking plugs approved for this
purpose for installations according to the type of protection Ex db.
Install the connecting line rigidly and ensure it is protected adequately from being damaged. In case the temperature exceeds 70 °C at the cable entries, use
appropriate temperature-resistant connecting cables.
Integrate the positioner into the equipotential bonding system on site.
Connection to conform with the type of protection Ex e (EN 60079-7):
The cable and cable entries or blanking plugs must be certified according to the
type of protection Ex e (ATEX) and for which a special test certificate exists.
Devices used at ambient temperatures below –20 °C must have metal cable entries.
In cases where more than one cable core is connected to the same terminal,
make sure that each cable core is clamped adequately.
Two cables with varying cross-sections may only be connected to one terminal,
if this is not explicitly allowed in the documentation related to the electrical apparatus, when the two cables are secured with a common crimp sleeve beforehand.
36
EB 8387-3 EN
Connections
Connection to conform with the type of protection Ex i (EN 60079-11):
For connection to a certified, external instrinsically safe circuit, the terminal compartment of
the positioner may be opened within the hazardous area.
Only the terminal compartment is to be opened within the hazardous area to connect it to a
certified instrinsically safe circuit.
Positioners that are connected to non-intrinsically safe circuits are no longer permitted to
be used as instrinsically safe equipment.
The IP rating of the cable, cable entries and blanking plugs must be the same as the
positioner's degree of protection.
Order no.
Table 6 · Accessories
Cable gland M20 x 1.5; EEx e, black plastic
8808-0178
Blanking plugs; EEx de; stainless steel
(approvals: CENELEC, CSA, GOST, IECEx)
M20 x 1.5
8323-1203
½ NPT
8323-1204
Cable entry for unarmored cables; EEx e, EEx d, EEx tD A21
(approvals: CENELEC, IECEx)
M20 x 1.5
8808-0200
½ NPT
8808-2010
EB 8387-3 EN
37
Connections
Cable entry
mum (reverse polarity protection, see Technical data).
NOTICE
The demanded degree of protection might
not be met because the terminal compartment is not sealed tightly. Only operate the
positioner with sealed cable entries and with
the lid screwed on properly.
Fig. 11 · Location of the terminals
(lid unscrewed)
The threaded connections for the terminal
compartment are designed with ½ NPT or
M20x1.5 threads.
The electrical connections are screw terminals for wire cross-sections of 0.2 to
2.5 mm² using a tightening torque of at least
0.5 Nm.
The wires for the reference variable are to
routed to the enclosure terminals marked
Signal and are polarity insensitive.
4 If the reference variable exceeds 22 mA,
4
OVERLOAD appears on the LC display
as a warning.
If the reference variable falls below
3.7 mA, LOW appears on the LC display
as a warning.
Depending on the version, the positioner is
equipped with an additional binary output,
a forced venting function, a position transmitter or a binary input.
The position transmitter is operated in a
two-wire circuit. The usual supply voltage is
24 V DC. Considering the resistance of the
supply leads, the voltage at the position
transmitter terminals can be between 11 V
at the minimum and 35 V DC at the maxi-
38
EB 8387-3 EN
NOTICE
Loss of explosion protection due to damaged
lid thread and/or connecting thread.
Do not open the flameproof enclosure when
the positioner is in the energized state. Observe explosion protection regulations.
1.
2.
3.
4.
5.
6.
Unscrew lid.
Guide the wires through the side cable
entry to the terminal compartment using
a cable gland or conduit system.
Connect wires to the terminals as
shown in the wiring diagram (Fig. 12).
Check O-ring for damage and replace
it with a new one, if necessary.
Screw on the lid as far as it will go.
Turn it back to first safety position
(notch).
Unscrew the cap screw to lock the lid.
Connections
Signal
Option
A B C
A
4...20 mA
HART®
2-wire transmitter
Supply unit for
position transmitter
+ _
11...35 V DC
Control signal
polarity
insensitive
A B C
Forced venting
L/+ N/_
0...40 V DC
0...28 V AC
A B C
+
Binary output
Signal converter
acc. to EN 60947-5-6
_
A B C
Binary output
PLC
DC/AC
A B C
Binary input
Voltage input, polarity insensitive
0...24 V DC
A B C
Binary input
Contact input for external contact
Fig. 12 · Electrical connections
EB 8387-3 EN
39
Connections
5.2.1 Establishing communication
Communication between PC and the FSK
modem or handheld communicator and
positioner is based on the HART® protocol.
Type Viator FSK modem
RS-232
not ex
Order no. 8812-0130
USB
not ex
Order no. 8812-0132
If the load impedance of the controller or
control station is too low, an isolation amplifier functioning as load converter is to be
connected between controller and
positioner.
via point-to-point or standard bus
(Multidrop).
Point-to-point:
The bus address/polling address must always be set to zero (0).
Standard bus (Multidrop):
In the standard bus (Multidrop) mode, the
positioner follows the analog current signal
(reference variable) as for point-to-point
communication. This operating mode is, for
example, suitable for split-range operation
of positioners (series connection). The bus
address/polling address has to be within a
range of 1 to 15.
Thanks to HART® protocol all control room
and field devices connected in the loop are
individually accessible through their address
Connection in non-hazardous area
Handheld communicator
or second FSK modem
3731-30
4 to 20 mA
Controller/control station
FSK modem
Safe area
Connection in hazardous area
Hazardous area
FSK modem
3731-31
Ex isolating amplifier
Controller/control station
Handheld communicator
or second FSK modem (explosion-protected)
Fig. 13 · Connection with a FSK modem
40
EB 8387-3 EN
Connections
Note:
Communication errors may occur when the
process controller/control station output is
not HART-compatible.
For adaptation, the Z box (order no.
1170-2374) can be installed between output and communication interface.
At the Z box a voltage of 330 mV is released (16.5 Ω at 20 mA).
Alternatively, a 250-Ω resistor can be connected in series and a 22-µF capacitor can
be connected in parallel to the analog output. Note that in this case, the controller output load will increase.
250 Ω
22 µF
Fig. 14 · Adapting the output signal
EB 8387-3 EN
41
Operator controls and readings
6
6.1
Operator controls and
readings
Operating modes:
4
Rotary pushbutton
The rotary pushbutton ( ) is located underneath the front protective cover.
The positioner is operated on site using the
rotary pushbutton:
Turn
to select codes and values.
Press
to confirm setting.
6.2
4
4
Serial interface
The serial interface connection is located underneath the display lid: Unscrew and remove retaining screw and then unscrew display lid.
4
NOTICE
The explosion protection is ineffective as
soon as the display lid is opened!
The positioner needs to be supplied with at
least 4 mA.
To use the TROVIS-VIEW software, connect
the positioner over an adapter (see accessories in Table 5) to the RS-232 or USB port of
the computer.
6.3
Readings on display
Icons appear on the display that are assigned to parameters, codes and functions.
42
EB 8387-3 EN
4
Manual mode (MAN), section 8.2.1
The positioner follows the manual set
point (Code 1) instead of the mA signal
blinks: The positioner has not yet
been initialized. Operation only possible
over manual set point (Code 1).
Automatic mode (AUTO), section 8.2.1
The positioner is in closed-loop operation
and follows the mA signal.
S Fail-safe position, section 8.2.2
The positioner vents the output. The valve
moves to the mechanical fail-safe position.
Bar elements:
In
manual and
automatic modes,
the bars indicate the system deviation
that depends on the sign (+/–) and the
value.
One bar element appears per 1 % system deviation.
If the device has not yet been initialized,
the
icon blinks on the display and the
lever position in degrees in relation to
the longitudinal axis is indicated. One
bar element corresponds to approximately a 5° angle of rotation.
If the fifth bar element blinks (reading
> 30°), the permissible angle of rotation
has been exceeded. Lever and pin position must be checked.
Status messages
: Maintenance alarm
: Maintenance required/Maintenance
demanded
blinking: Out of specification
These icons indicate that an error has occurred.
A classified status can be assigned to
Operator controls and readings
4
each error. Classifications include “No
message”, “Maintenance required”,
“Maintenance demanded”, “Out of specification” and “Maintenance alarm“ (see
section 8.3).
Configuration enabled
This indicates that the codes marked with
an asterisk (*) in the code list (section 11)
are enabled for configuration (see section 8.1).
EB 8387-3 EN
43
Operator controls and readings
Manual mode
Closed-loop operation
Condensed state:
Maintenance alarm
Code
%
mm
mm
Designation
Position
Parameter
%
S
Limit switch
Alarm 1
Bar elements for
system deviation
or lever position
Units
Limit switch
Alarm 2
Configuration
enabled
Condensed state:
Maintenance required
Maintenance demanded
NOM
OVERLOAD
RES
RUN
SAFE
SUB
TunE
YES
ZP
ää
Increasing/increasing
Nominal travel
äæ
Increasing/decreasing
w > 22 mA
Reset
blinking
Emergency mode,
Start
see Code 62
Fail-safe position
blinking
Not initialized
Substitute calibration
Valve in mechanical
Initialization in progress S blinking
fail-safe position
Available/active
Zero calibration
Fail-safe position
active
Readings and their meanings
AUtO
CL
CCL
Err
ESC
HI
LO
LOW
MAN
Automatic mode
Clockwise
Counterclockwise
Error
Escape
ix greater than 21.6 mA
ix smaller than 2.4 mA
w lower than 3.7 mA
Manual mode
Protective cover
Rotary pushbutton
LC display
Serial interface
Retaining
screw
Fig. 15 · Readings and operator controls
44
EB 8387-3 EN
Operator controls and readings
6.4
®
HART communication
The positioner must be supplied with at least
3.8 mA current.
A DTM file (Device Type Manager) conforming to the Specification 1.2 is available for
communication. This allows the device, for
example, to be run with the PACTware operator interface. All the positioner's parameters are then accessible over the DTM and
the operator interface.
Note: In the case, complex functions are
started in the positioner, which require a
long calculation time or lead to a large
quantity of data being stored in the volatile
memory of the positioner, the alert “busy” is
issued by the DTM file.
This alert is not a fault alarm and can simply be confirmed.
®
6.4.1 Dynamic HART variables
The HART® specification defines four dynamic variables consisting of a value and an
engineering unit. These variables can be assigned to device parameters as required.
The universal HART® command 3 (universal
command #3) reads the dynamic variables
out of the device. This allows manufacturer-specific parameters to also be transferred using a universal command.
The dynamic variables of Type 3731-3 can
be assigned as follows in the DD or
TROVIS-VIEW [Settings > Operation unit]:
Write protection
4 The write protection for HART communi-
cation can be disabled over Code 47.
You can only disable or enable this function locally at the positioner.
The write protection is enabled by default.
4 The on-site operation can be locked over
HART communication. HART then blinks
on the display when Code 3 is selected.
This locking function can only be disabled over HART communication.
On-site operation is enabled by default.
EB 8387-3 EN
45
Start-up – Settings
®
Assignment of dynamic HART variables
Variable
Meaning
%
Direction of action set point
%
Set point after transit time specification
%
Valve position
%
Set point deviation e
%
Absolute total valve travel
–
Binary input
status
–
1 = Active
0 = De-energized
Condensed
state
0 = No message
–
1 = Energized
2 = Not installed
–
1 = Maintenance
required
Reading on display after connecting the
electrical auxiliary power:
blinks on the display when the
positioner has not yet been initialized..
The reading indicates the lever position
in degrees in relation to the longitudinal
axis.
Reading when the
positioner has not yet
been initialized
2 = Maintenance
demanded
3 = Failure
4 Code 0 appears on the display when a
4 = Out of
specification
7 = Function check
Temperature
WARNING!
Attach the positioner, keeping the following
sequence:
1. Mount the positioner on the control valve
2. Connect the supply air
3. Connect the electrical power
4. Perform the start-up settings
4 tEStinG runs across the display and then
255 = –/–
Internal
solenoid
valve/forced
venting status
Start-up – Settings
Unit
Set point
0 = Not active
7
°C
positioner has been initialized. The
positioner is in the last active operating
mode.
WARNING!
The actuator stem moves while the start-up
settings are being performed.
Do not touch the actuator stem or obstruct it
to avoid risk of injury to hands or fingers.
46
EB 8387-3 EN
Start-up – Settings
NOTICE
Perform the start-up settings in the same sequence as listed (section 7.1 to section 7.5).
7.1
Adapting the display
Enable configuration at the positioner before
activating the pressure limit function:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
The reading on the display can be turned by
180° to adapt it to how the positioner is attached.
Reading direction for right
attachment of pneumatic
connections
Configuration enabled
Default: No
Turn
Press
Reading direction for left
attachment of pneumatic
connections
→ Code 3, display: No
Code 3 blinks
Turn
→ YES
Press
, display
Pressure limit function:
If the display appears upside down, proceed
as follows:
Turn
→ Code 2
Press
, Code 2 blinks.
Turn
→ Desired reading direction.
Pressure limit
Default: No
Turn
→ Code 16
, Code 16 blinks.
Press
to confirm the reading direction.
Press
7.2
Limiting the signal pressure
Turn
until the required pressure limit
(1.4/2.4/3.7 bar) appears.
If the maximum actuator force may cause
damage to the valve, the signal pressure
must be limited.
Press
ting.
to confirm the pressure limit set-
NOTICE
Do not activate the pressure limit function in
double-acting actuators (with fail-safe action
AIR TO OPEN (AtO) (No = default).
EB 8387-3 EN
47
Start-up – Settings
7.3
Checking the operating
range of the positioner
A horizontal lever (mid-position) is equal to
0°.
To check the mechanical attachment, the
valve should be moved through the operating range of the positioner in the
manual
mode using the manual reference variable
w.
Select manual operating mode (MAN)
:
Mode
Default: MAN
Turn
→ Code 0
Press
, Code 0 blinks.
Turn
→ MAN
Press
mode.
The permissible range has been exceeded
when the displayed angle is greater than
30°, and the outer right or left bar element
blinks.
The positioner changes to the fail-safe position (SAFE).
After canceling the fail-safe position (SAFE)
(see section 8.2.2) it is absolutely necessary
to check the lever and pin position as described in section 4.
to change the positioner to manual
Checking the operating range:
Manual reference variable
(the current opening angle
appears)
Turn
→ Code 1
Press
, Code 1 and
icon blink.
Turn
until the pressure builds up in the
positioner, and the control valve moves to its
end positions to check the travel range/angle of rotation.
The angle of the lever on the back of the
positioner is indicated on the display.
48
To ensure the positioner is working properly, the outer bar elements may not blink
while the valve is moving through the operating range.
The manual mode can be exited by pressing
the rotary pushbutton ( ).
EB 8387-3 EN
WARNING!
To avoid personal injury or property damage caused by the supply air or electrical
auxiliary power, disconnect the supply air
and electrical auxiliary power before exchanging the lever or changing the pin position.
Start-up – Settings
7.4
Allocating the closed
position
Taking into account the type of valve and the
operating direction of the actuator, allocate
the closed position (0 % travel):
Turn
until the required closed position
appears on the display.
Press
Turn
Press
to confirm the closed position.
→ ESC
to exit or:
4 AIR TO OPEN (AtO)
Start initialization as described in section 7.5.
4
For checking purposes: After the positioner
has been initialized successfully, the valve
closed position is indicated on the positioner
display as 0 %, whereas the valve open
position is indicated by 100 %. If this is not
the case, the closing direction has to be
adapted correspondingly and the positioner
needs to be re-initialized.
Signal pressure opens the valve.
Fail-close
AIR TO CLOSE (AtC)
Signal pressure closes the valve.
Fail-open
NOTICE
Double-acting actuators must always be set
to AIR TO OPEN (AtO).
Initialization
7.5
AIR TO OPEN
AIR TO CLOSE
Turn
→ Code 0
Press
, display: MAN
Code 0 blinks.
Turn
Press
→ Init
Positioner initialization
WARNING!
During initialization, the control valve moves
through its entire travel/angle of rotation
range. Therefore, do not start the initialization procedure while a process is running,
but only during start-up when all shut-off
valves are closed.
Before starting initialization, check the maximum permissible signal pressure of the control valve. During initialization, the
positioner issues an output signal pressure
up to the maximum supply pressure supplied. If necessary, limit the signal pressure
by connecting an upstream pressure reducing valve.
EB 8387-3 EN
49
Start-up – Settings
NOTICE
If the positioner is mounted onto another actuator or its mounting position is changed,
reset the positioner to its default settings before re-initializing it. Refer to section 7.7.
During initialization the positioner adapts itself optimally to the friction conditions and
the signal pressure requirements of the control valve.
The type and extent of self-adaptation depends on the initialization mode selected:
MAX maximum range (standard range)
Initialization mode for simple start-up of
valves with two clearly defined mechanical end positions, e.g. three-way valves
(see section 7.5.1)
NOM nominal range
Initialization mode for all globe valves
(see section 7.5.2)
MAN manually selected range
Initialization mode for globe valves with
an unknown nominal range (see section
7.5.3)
SUB substitute calibration (emergency
mode)
This mode allows a positioner to be replaced while the plant is running, with
the least amount of disruption to the
plant (see section 7.5.4)
4
4
4
4
Note: The initialization procedure can be interrupted while running by pressing the rotary pushbutton ( ). StOP appears three
seconds long and the positioner then
changes to the fail-safe position (SAFE). The
fail-safe position can be canceled again
over Code 0 (see section 8.2.2).
50
EB 8387-3 EN
Alternating displays:
Initialization running
Initialization progress
indicated
(MAX, NOM, MAN or SUB
appears, depending on the
initialization mode selected)
Initialization successful
%
Positioner in
mode
automatic
The time required for an initialization process depends on the stroking speed of the
actuator and may take several minutes.
After a successful initialization, the
positioner runs in automatic mode indicated
by the
closed-loop control icon.
A malfunctioning leads to the process being
interrupted. The initialization error appears
on the display according to how it has been
classified by the condensed state. See section 8.3 on page 60).
Note: The setting of Code 48 - h0 = YES
starts the plotting of the reference graphs required for valve diagnostics (drive signal
steady-state d1 and hysteresis d2) after initialization. tESt and d1 and d2 appear on
the display in an alternating sequence.
An unsuccessful plotting of the reference
graphs is indicated on the display by Code
48 - h1 and Code 81 (see error code list).
The positioner still works properly, even
though the reference graph plotting has not
been completed successfully.
Start-up – Settings
7.5.1 Initialization based on MAX
maximum range
Start initialization:
The positioner determines travel/angle of
rotation of the closing member from the
CLOSED position to the opposite side and
adopts this travel/angle of rotation as the
operating range from 0 to 100 %.
Initialization
Fail-safe position setting
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Configuration enabled
Default: No
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
Turn
→ YES
Press
, display:
Select initialization mode:
Initialization mode
Default: MAX
Turn
→ Code 6
Progress indicated until
initialization starts
Turn
→ Code 0
Press
, Code 0 blinks.
Turn
→ Init
Press
. The setting of the fail-safe position
AtO or AtC appears.
Keep
pressed down for 6 seconds.
Initialization starts after the progress indication has stopped.
The nominal travel/angle of rotation is indicated in % after initialization. Code 5 (nominal range) remains locked. The parameters
for travel/angle range start (Code 8) and
travel/angle range end (Code 9) can also
only be displayed and modified in %.
For a reading in mm/°, enter the pin position (Code 4).
Press
Turn
Press
mode.
→ MAX
to confirm the MAX initialization
EB 8387-3 EN
51
Start-up – Settings
Enter pin position:
mm
Enable configuration:
Pin position
Default: No
Turn
→ Code 4
Press
, Code 4 blinks.
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Configuration enabled
Default: No
Turn
→ Pin position on lever (see relevant section on attachment).
Press
. The reading of the nominal range
appears in mm/°.
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
7.5.2 Initialization based on
NOM nominal range
Turn
→ YES
Press
, display:
The calibrated sensor allows the effective
valve travel to be set very accurately. During
the initialization process, the positioner
checks whether the control valve can move
through the indicated nominal range (travel
or angle) without collision.
If this is the case, the indicated nominal
range is adopted with the limits of
travel/angle range start (Code 8) and
travel/angle range end (Code 9) as the operating range.
Enter pin position and nominal travel:
Note: The maximum possible travel must always be greater than the nominal travel entered. If this is not the case, initialization is
interrupted (error message Code 52) because the nominal travel is not achieved.
Turn
→ Code 4
Press
, Code 4 blinks.
52
EB 8387-3 EN
mm
Pin position
Default: No
mm
Nominal range
(locked with Code 4 = No)
Turn
→ Pin position on lever (see relevant section on attachment).
Press
Turn
→ Code 5
Press
, Code 5 blinks.
Turn
→ Nominal valve travel
Start-up – Settings
Press
Select initialization mode:
Initialization mode
Default: MAX
Turn
→ Code 6
Press
, Code 6 blinks.
Turn
→ NOM
Press
mode.
to confirm the NOM initialization
Start initialization:
Initialization
Fail-safe position setting
Keep
pressed down for 6 seconds.
Initialization starts after the progress indication has stopped.
Note: After initialization, check the direction
of action and, if necessary, change it
(Code 7).
7.5.3 Initialization based on MAN
manually selected range
Before starting initialization, move the control valve manually to the OPEN position by
turning
in small steps. The valve must
move to the required valve position with a
monotonically increasing signal pressure.
The positioner calculates the differential
travel/angle using the OPEN and CLOSED
positions and adopts it as the operating
range with limits of travel/angle range start
(Code 8) and travel/angle range end
(Code 9).
Enter OPEN position:
Manual reference variable
(the current angle of rotation
is displayed)
Progress indicated until
initialization starts
Turn
→ Code 0
Turn
→ Code 0
Press
, Code 0 blinks.
Press
, Code 0 blinks.
Turn
→ MAN
Turn
→ Init
Press
Press
. The setting of the fail-safe position
AtO or AtC appears.
Turn
→ Code 1
Press
, Code 1 blinks.
EB 8387-3 EN
53
Start-up – Settings
Turn
until the OPEN position of the valve
is reached.
Press
Select initialization mode:
to confirm the OPEN position.
Initialization mode
Default: MAX
Enable configuration:
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
Turn
Press
, Code 6 blinks.
Turn
→ MAN
Press
mode.
Configuration enabled
Default: No
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
Turn
→ YES
Press
, display:
→ Code 6
to confirm the MAN initialization
Start initialization:
Initialization
Fail-safe position setting
Enter pin position:
mm
Pin position
Default: No
Turn
→ Code 4
Press
, Code 4 blinks.
Turn
→ Pin position on lever (see relevant section on attachment).
Press
Progress indicated until
initialization starts
Turn
→ Code 0
Press
, Code 0 blinks.
Turn
→ Init
Press
. The setting of the fail-safe position
AtO or AtC appears.
Keep
pressed down for 6 seconds.
Initialization starts after the progress indication has stopped.
54
EB 8387-3 EN
Start-up – Settings
7.5.4 SUB substitute calibration
A complete initialization procedure takes
several minutes and requires the valve to
move through its entire travel range several
times. This initialization mode, however, is
an emergency mode, in which the control
parameters are estimated and not determined by an initialization procedure. As a
result, a high level of accuracy cannot be
expected. You should always select a different initialization mode if the plant allows it.
Configuration enabled
Default: No
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
Turn
→ YES
Press
, display:
Enter pin position and nominal travel:
The SUB initialization mode is used to replace a positioner while the process is running. For this purpose, the control valve is
usually fixed mechanically in a certain position, or pneumatically by means of a pressure signal which is routed to the actuator
externally. The blocking position ensures
that the plant continues to operate with this
valve position.
By entering the blocking position (Code 35),
closing direction (Code 34), pin position
(Code 4), nominal range (Code 5) and direction of action (Code 7), the positioner
can calculate the positioner configuration.
NOTICE
Perform a reset before re-initializing the
positioner if the substitute positioner has already been initialized. Refer to section 7.7.
Enable configuration:
mm
Pin position
Default: No
mm
Nominal range
(locked with Code 4 = No)
Turn
→ Code 4
Press
, Code 4 blinks.
Turn
→ Pin position on lever (see relevant section on attachment).
Press
.
Turn
→ Code 5
Press
, Code 5 blinks.
Turn
→ Nominal travel of the valve
Press
Note: If no settings are entered within
120 seconds, the enabled configuration
function becomes invalid.
EB 8387-3 EN
55
Start-up – Settings
Select initialization mode:
Initialization mode
Default: MAX
→ Code 6
Turn
Press
Change pressure limit and control parameters:
Note: Do not change the pressure limit
(Code 16). Only change the control parameters KP (Code 17) and TV (Code 18) if the
settings of the replaced positioner are
known.
→ SUB
Turn
Press
mode.
to confirm the SUB initialization
Pressure limit
Default: No
Enter direction of action:
KP stage
Default: 7
Direction of action
Default: ää
Turn
→ Code 7
Press
, Code 7 blinks.
Turn
→ Direction of action (ää/äæ)
Press
Deactivate travel limit:
Travel limit
Default: 100.0
Turn
→ Code 11
Press
, Code 11 blinks.
Turn
→ No
Press
56
EB 8387-3 EN
TV stage
Default: 2
Turn
→ Code 16/17/18
Press
, Code 16/17/18 blinks.
Turn
eter.
and set the selected control param-
Press
to confirm setting.
Enter closing direction and blocking position:
Closing direction
Direction of rotation causing
the valve to move to the
CLOSED position (view onto
positioner display)
Default: CCL (counterclockwise)
Start-up – Settings
Turn
mm
Blocking position
Default: 0
Press
, Code 0 blinks.
Turn
→ Init
Press
. The setting of the fail-safe position AtO or AtC appears.
Turn
→ Code 34
Press
, Code 34 blinks.
Turn
→ Closing direction (CCL counterclockwise/CL clockwise)
Press
Turn
→ Code 35
Press
, Code 35 blinks.
Turn
→ Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Press
Start initialization:
Initialization
Fail-safe position setting
Progress indicated until
initialization starts
Keep
pressed down for 6 seconds.
Initialization starts after the progress indication has stopped.
The operating mode changes to MAN.
The blocking position appears.
Note: As initialization has not been carried
out completely, the error code 76 (no emergency mode) and possibly also error code
57 (control loop) may appear on the display.
These messages do not influence the
positioner’s readiness for operation.
Cancel the blocking position and change to
automatic mode
(AUTO):
For the positioner to follow its reference
variable again, the blocking position must
be canceled and the positioner must be set
to automatic operating mode.
Turn
→ Code 1
Press
, Code 1 and the
Blocking position
icon blink.
Turn
until the pressure in the positioner
builds up and the valve moves slightly past
the blocking position.
Press
%
→ Code 0
to cancel the blocking position.
Turn
→ Code 0
Press
, Code 0 blinks.
Turn
→ AUtO
EB 8387-3 EN
57
Start-up – Settings
Press
The positioner changes to automatic mode
(AUTO). The current valve position is indicated in % on the display.
Note: If the positioner shows a tendency to
hunt in automatic operating mode, the parameters KP and TV must be slightly corrected. Proceed as follows:
– Set TV (Code 18) to 4.
– Reduce KP (Code 17) until the positioner
shows a stable behavior.
Zero point correction
Finally, if process operations allow it, the
zero point must be calibrated as described
in section 7.6.
7.6
Zero calibration
In case of discrepancies with the closing position of the valve, e.g. with soft-sealed
plugs, it may become necessary to
recalibrate the zero point.
NOTICE
The valve briefly moves from the current
travel/angle of rotation position to the
closed position.
Note: The positioner must be connected to
the supply air to perform the zero calibration.
Enable configuration:
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
Turn
→ YES
Press
, display:
Perform zero calibration:
Initialization mode
Default: MAX
Turn
→ Code 6
Press
, Code 6 blinks.
Turn
→ ZP
Press
Turn
58
EB 8387-3 EN
→ Code 0
Start-up – Settings
Press
display: MAN, Code 0 blinks.
Turn
→ Init
Press
The setting of the fail-safe position AtO or
AtC appears.
Keep
pressed down for 6 seconds.
Zero calibration is started, the positioner
moves the control valve to the CLOSED position and recalibrates the internal electrical
zero point.
7.7
Reset to default values
This function resets all start-up parameters
and diagnosis data to their default values
(see code list in section 11).
Enable configuration:
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
Turn
Press
→ YES
, display:
Reset start-up parameters:
Reset
Default: No
Turn
→ Code 36, display: ••–••–
Press
, Code 36 blinks.
Turn
→ Std
Press
. All start-up parameters and diagnosis data are reset to their default values.
Note: Code 36 - diAG allows just the diagnosis data (EXPERTplus) to be reset. Refer to
EB 8389 EN on EXPERTplus valve diagnostics.
EB 8387-3 EN
59
Operation
8
Operation
WARNING!
The actuator stem moves while the positioner
is being operated.
Do not touch the actuator stem or obstruct it
to avoid risk of injury to hands or fingers.
8.1
Enabling and selecting
parameters
All codes with their meanings and default
settings are listed in the code list in section 11 on page 65 onwards.
The codes which are marked with an asterisk (*) must be enabled with Code 3 before
the associated parameters can be configured as described below.
Code 3
Configuration
not enabled
Configuration
enabled
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
Change the setting of Code 3.
Turn
→ YES
Turn
, display:
The configuration is enabled.
60
EB 8387-3 EN
You can now configure codes one after the
other:
Turn
and select the required code.
Press
to access the selected code. The
code number starts to blink.
Turn
and select the setting.
Press
to confirm the selected setting.
Note: If no settings are entered within 120
seconds, the enabled configuration function
becomes invalid and the display changes to
Code 0.
Canceling the setting
Canceling the setting
To cancel a value before it is confirmed (by
pressing the rotary pushbutton
) without
the value you have just selected being
adopted:
Turn
→ ESC
Press
to confirm the cancelation.
The entry is ended without the value you
have just selected being adopted.
Operation
8.2
Adjust the manual reference variable
Operating modes
8.2.1 Automatic (AUTO) and
manual (MAN) modes
After initialization has been completed successfully, the positioner is in automatic mode
(AUTO).
Automatic mode
%
Switching to manual mode
(MAN)
%
Turn
→ Code 1
Press
, Code 1 blinks.
Turn
until sufficient pressure has been
built up in the positioner and the control
valve moves to the required position.
Note: If no settings are entered within
approx. two minutes, the positioner automatically returns to Code 0, but remains in
manual mode.
Switching to automatic mode
Turn
→ Code 0
Press
, display: AUtO,
Code 0 blinks.
Turn
→ MAN
%
Turn
→ Code 0
Press
, Code 0 blinks.
Turn
→ AUtO
Press
(AUTO):
to switchover to automatic mode.
Press
to switchover to manual mode. The
switchover is smooth since the manual mode
starts up with the set point last used during
automatic mode. The current position is displayed in %.
EB 8387-3 EN
61
Operation
8.2.2 Fail-safe position (SAFE)
If you want to move the valve to fail-safe position determined during start-up (see section 7.4), proceed as follows:
→ Code 0
Turn
Press
, display: current operating mode
(AUtO or MAN), Code 0 blinks.
→ SAFE
Turn
Press
, display: S
The valve moves to the fail-safe position.
If the positioner is initialized, the current
valve position is indicated on the display in
%.
Exit the fail-safe position
Turn
→ Code 0
Press
, Code 0 blinks.
Turn
and select the required operating
mode AUtO or MAN.
Press
The positioner switches to the operating
mode selected.
8.3
All status and fault alarms are assigned to a
classified status in the positioner. The default
settings of the status classification are listed
in the code list.
Note: The status classification can be
changed in TROVIS-VIEW and over the parameters in the DD file. Refer to EB 8389 EN
on EXPERTplus valve diagnostics.
To provide a better overview, the classified
messages are summarized in a condensed
state. The following status messages are
available:
Maintenance alarm
The positioner cannot perform its control
task due to a functional fault in the device or in one of its peripherals or an initialization has not yet been successfully
completed.
Maintenance required
The positioner still performs its control
task (with restrictions). A maintenance
requirement or above average wear has
been determined. The wear tolerance will
soon be exhausted or is reducing at a
faster rate than expected. Maintenance
is necessary in the medium term.
Maintenance demanded
The positioner still performs its control
task (with restrictions). A maintenance
demand or above average wear has
been determined. The wear tolerance will
soon be exhausted or is reducing at a
faster rate than expected. Maintenance
is necessary in the short term.
4
4
4
62
EB 8387-3 EN
Malfunction/maintenance
alarm
Operation
4 Out of specification
Fault alarm output
The positioner is operated outside specified operating conditions.
Note: If an event is assigned to the “No
message” status, this event does not have
any effect on the condensed state.
The condensed state is represented by the
following icons on the positioner display:
Positioner
display
Condensed state
Maintenance alarm
4 The “Function check” condensed state
can also switch the fault alarm contact in
Code 32.
4 The “Maintenance required/demanded”
condensed state can also switch the fault
alarm contact in Code 33.
8.3.1 Confirming error messages
Enable configuration:
Function check
Text e.g.
tESting, tunE or
tESt
Maintenance required/
Maintenance demanded
Out of specification
The “Maintenance alarm” as the condensed
state causes the optional fault alarm output
to be switched.
blinking
If the positioner has not been initialized, the
maintenance alarm icon ( ) appears on
the display as the positioner cannot follow
its reference variable.
If fault alarms exist, the possible source of
error is displayed in Code 49 onwards. In
this case, Err appears on the display.
Turn
→ Code 3, display: No
Press
, Code 3 blinks.
Turn
→ YES
Press
, display:
Confirming error message:
Turn
→ Select error code which you
want to confirm.
Press
.
The error message is confirmed.
Example
Error caused by pin
position
S
The cause and recommended action are
listed in the code list (section 11).
EB 8387-3 EN
63
Maintenance
9
Maintenance
The positioner does not require any maintenance.
There are filters with a 100 µm mesh size in
the pneumatic connections for supply and
output which can be removed and cleaned,
if required.
The maintenance instructions of any upstream supply air pressure reducing stations
must be observed.
64
EB 8387-3 EN
10
Servicing explosionprotected devices
If a part of the positioner on which the explosion protection is based needs to be serviced, the positioner must not be put back
into operation until an expert has inspected
the device according to explosion protection
requirements, has issued a certificate stating
this or given the device a mark of conformity.
Inspection by an expert is not required if the
manufacturer performs a routine test on the
device prior to putting it back into operation. The passing of the routine test must be
documented by attaching a mark of conformity to the device.
Code list
11
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
0
Operating mode
AUtO
[MAN]
MAN
Automatic mode
Manual mode
AUtO · SAFE
SAFE
Fail-safe position
ESC
ESC
Escape
In MAN and AUtO mode, the system deviation is represented by
bar elements on the display.
If the positioner has been initialized, the numerical reading indicates the valve position or the angle of rotation in %, otherwise
the position of the lever in relation to the central axis is displayed
in degrees °.
Switchover from automatic to manual mode is smooth.
In fail-safe position, the S icon appears on the display.
Init · AtO · AtC
Init
Start initialization
Allocate closed position:
AtO: AIR TO OPEN (valve CLOSED in fail-safe position) or
AtC: AIR TO CLOSE (valve OPEN in fail-safe position)
1
Manual reference variable
w
[0] to 100 %
of the nominal range
Setting the manual reference variable w
The current travel/angle is displayed in % when the positioner
has been initialized, otherwise the position of the lever in relation
to the central axis is indicated in degrees °.
Can only be selected when Code 0 = MAN.
2
Reading direction
The reading direction of the display is turned by 180°.
[Normal] or upside down
ESC
3
Enable configuration
[No]
YES
ESC
Enables the option to modify data (automatically deactivated
when the rotary pushbutton has not been operated for 120 s.)
HART blinks on the display when the on-site operation is locked
over HART® communication.
Codes marked with an asterisk (*) can only be read and not
overwritten.
Codes can also only be read over the SSP interface.
EB 8387-3 EN
65
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
4*
[No]
The follower pin must be inserted into the correct pin position according to the valve travel/angle of rotation.
17, 25, 35, 50, 70, 100,
200 mm
The pin position must be entered for initialization using NOM or
SUB.
Pin position
90° with rotary actuators
ESC
Note: If you select a pin
position in Code 4 that is too
small, the positioner switches
to the fail-safe position
mode (SAFE ) for reasons of
safety.
5*
Nominal range
mm or angle °
ESC
Pin position
Code 4
Standard
Code 5
Adjustment range
Code 5
17
25
35
50
70
100
200
90°
7.5
7.5
15.0
30.0
40.0
60.0
120.0
90.0
3.6 to 18.0
5.0 to 25.0
7.0 to 35.0
10.0 to 50.0
14.0 to 70.7
20.0 to 100.0
40.0 to 200.0
24.0 to 100.0
For initialization using NOM or SUB, the nominal travel/angle of
rotation of the valve must be entered.
The permissible adjustment range depends on the pin position
according to the table for Code 4.
Code 5 is generally locked until Code 4 is set to No, i.e. after a
pin position has been entered, Code 5 can be configured.
After initialization has been successfully completed, the maximum nominal travel/angle reached on initialization is displayed.
6*
Initialization mode
Select the initialization mode
[MAX]
MAX:
NOM · MAN · SUB · ZP
ESC
Maximum range of the control valve, the travel/angle of
the closure member from the CLOSED position to the opposite stop in the actuator.
NOM: Nominal range of the control valve, the travel/angle of
the closure member measured from the CLOSED position
to the indicated OPEN position.
MAN: Manually selected range
66
EB 8387-3 EN
SUB:
Substitute calibration (without initialization)
ZP:
Zero calibration
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
7*
Direction of action w/x
[ää]
äæ
ESC
Direction of action of the reference variable w in relation to the
travel/angle of rotation x (increasing/increasing or increasing/decreasing).
Automatic adaptation:
AIR TO OPEN: After initialization, the direction of action remains
increasing/increasing (ää), a globe valve opens as the
reference variable increases.
AIR TO CLOSE: After initialization, the direction of action
changes to increasing/decreasing (äæ), a globe valve
closes as the reference variable increases.
8*
Travel/angle range start
(lower x-range value)
Starting value for the travel/angle of rotation in the nominal or
operating range.
0.0 to 80.0 [0.0] % of the
nominal range
The operating range is the actual travel/angle of the control
valve and is limited by the travel/angle range start (Code 8) and
the travel/angle range end (Code 9).
Usually, the operating range and the nominal range are identical. The nominal range can be limited to the operating range
by the travel/angle range start and end. Value is displayed or
must be entered.
Specified in mm or angle ° provided
Code 4 is set
ESC
The characteristic is adapted.
See also the example in Code 9.
9*
Travel/angle range end
(upper x-range value)
End value for the travel/angle of rotation in the nominal or operating range. Value is displayed or must be entered.
20.0 to 100.0 [100.0] % of
the nominal range
The characteristic is adapted.
Specified in mm or angle ° provided
Code 4 is set
ESC
10*
Example: The operating range is modified, for example, to limit
the range of a control valve which has been sized too large. For
this function, the entire resolution range of the reference variable
is converted to the new limits. 0 % on the display corresponds to
the adjusted lower limit and 100 % to the adjusted upper limit.
Travel/angle lower limit
(lower x-limit)
Limitation of the travel/angle of rotation downwards to the entered value.
[No]
0.0 to 49.9 % of the
operating range
The characteristic is not adapted.
See also example in Code 11.
ESC
EB 8387-3 EN
67
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
11*
Travel/angle upper limit
(upper x-limit)
Limitation of the travel/angle of rotation upwards to the entered
value.
50.0 to 120.0 [100] % of
the operating range
When set to No, the valve can be opened past the nominal travel
with a reference variable outside of the 0 to 100 % range.
No · ESC
The characteristic is not adapted.
Example: In some applications, it is better to limit the valve
travel, e.g. if a certain minimum medium flow is required or a
maximum flow must not be reached.
The lower limit must be adjusted with Code 10, and the upper
limit with Code 11.
If a tight-closing function has been set up, it has priority over the
travel limitation.
12*
Reference variable range
start (w-start)
0.0 to 75.0 % of the
reference variable range
[0.0 %]
ESC
Lower range value of the applicable reference variable range
must be smaller than the final value w-end, 0 % = 4 mA.
The reference variable range is the difference between w-end
and w-start, and must be ∆w ≥ 25 % = 4 mA.
For an adjusted reference variable range of 0 to 100 % = 4 to
20 mA, the control valve must move through its entire operating
range from 0 to 100 % travel/angle of rotation.
In split-range operation, the valves operate with smaller reference variables. The control signal of the control unit to control
two valves is divided such, for instance, that the valves move
through their full travel/angle of rotation at only half the input
signal (first valve set to 0 to 50 % = 4 to 12 mA and the second
valve set to 50 to 100 % =12 to 20 mA reference variable).
13*
Reference variable range
end (w-end)
Upper range value of the applicable reference variable range,
must be greater than w-start.
25.0 to 100.0 % of the
reference variable range
100 % = 20 mA
[100.0 %]
ESC
68
EB 8387-3 EN
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
14*
Setpoint cutoff decrease
(final position w <)
0.0 to 49.9 [1.0] %
No · ESC
If reference variable w reaches the percentage adjusted that
causes the valve to close, the actuator is immediately completely
vented (with AIR TO OPEN) or filled with air (with AIR TO
CLOSE). This action always lead to maximum tight-closing of the
valve.
Codes 14/15 have priority over Codes 8/9/10/11.
Codes 21/22 have priority over Codes 14/15.
15*
Setpoint cutoff increase
(final position w >)
[No]
50.0 to 100.0 %
ESC
If reference variable w reaches the percentage adjusted that
causes the valve to open, the actuator is immediately completely
filled with air (with AIR TO OPEN) or vented (with AIR TO
CLOSE). This action always lead to the valve being completely
opened.
A signal pressure limit is possible over Code 16.
Codes 14/15 have priority over Codes 8/9/10/11.
Codes 21/22 have priority over Codes 14/15.
Example: Set the cutoff to 99 % for three-way valves.
16*
Pressure limit
The signal pressure to the actuator can be limited in stages.
[No]
After changing a pressure limit already set, the actuator must be
vented once (e.g. by selecting the fail-safe position (SAFE) over
Code 0).
P 1.4 · 2.4 · 3.7
ESC
17*
Proportional-action
coefficient KP (step)
0 to 17 [7]
ESC
NOTICE
Do not activate the pressure limit for double-acting actuators with
fail-safe position AIR TO OPEN (AtO).
Displaying or changing the KP and TV steps:
During initialization, the KP and TV values are optimized. Should
the positioner show a tendency for impermissibly high post-pulse
oscillation due to additional interference, the K P and TV steps can
be adapted after initialization. For this, either the TV step can be
increased in increments until the desired response behavior is
reached or, when the maximum value of 4 is reached, the KP
step can be decreased in increments.
Note: Changing the KP step influences the system deviation.
18*
Rate time TV (step)
Changing TV, see Code 17.
[2]
Note: Changing the TV step has no effect on the system deviation.
1 3 4 No
ESC
EB 8387-3 EN
69
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
19*
20*
Tolerance band
Used for error monitoring
0.1 to 10.0 [5] % of the
operating range
ESC
Determination of the tolerance band in relation to the operating
range.
Associated lag time [30] s is a reset criterion.
If a lag time is determined during initialization which is six times
> 30 s, the six-fold lag time is accepted as the lag time.
Characteristic
Select the characteristic:
0 to 9 [0]
0
Linear
ESC
1
Equal percentage
2
Reverse equal percentage
3
SAMSON butterfly valve linear
4
SAMSON butterfly valve equal percentage
5
VETEC rotary plug valve linear
6
VETEC rotary plug valve equal percentage
7
Segmented ball valve linear
8
Segmented ball valve equal percentage
9
User-defined (defined over operating software)
Note: The various characteristics are listed in the Appendix (section 13.1).
21*
Required transit time OPEN The time required to pass through the operating range when the
valve opens.
(w ramp open)
Limitation of the transit time (Code 21 and 22):
0 to 240 s [0]
For some applications it is better to limit the actuating speed of
ESC
the actuator to prevent it from engaging too fast in the running
process.
Code 21 has priority over Code 15.
22*
Required transit time
CLOSED (w ramp closed)
The time required to pass through the operating range when the
valve closes.
0 to 240 s [0]
Code 22 has priority over Code 14.
ESC
23*
Total valve travel
7
0 to 99 · 10 [0]
Totaled double valve travel.
Exponential reading from 9999 travel
cycles onwards
Note: The number of travel cycles (in steps of 1000) is saved in a
non-volatile memory.
RES · ESC
70
EB 8387-3 EN
Can be reset to 0 via RES.
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
24*
Limit of total valve travel
7
1000 to 99 · 10
[1 000 000]
Limit value of total valve travel. If the limit is exceeded, the fault
alarm and the wrench icons appear on the display.
Exponential reading from 9999 travel
cycles onwards
ESC
25*
Binary output
[A1 - / -]
ESC
26*
Limit value A1
No
0.0 to 100.0 [2.0] % of the
operating range
This code allows you to find out on site whether the positioner
has an optional binary output or not. When a binary output
exists, its switching performance can be read and set.
If there is no binary output, - - - - appears on the display of the
positioner.
The binary contacts A1, A2 and the fault alarm output can be
configured at the output as follows:
Alternating display
Meaning
A1
-/ -
A1 functioning as NO contact
A1
----
A1 functioning as NC contact
A2
-/ -
A2 functioning as NO contact
A2
----
A2 functioning as NC contact
FAUL
FAUL
Fault alarm output (always NC contact)
Displaying or changing the software limit value A1 in relation to
the operating range.
ESC
27*
Displaying or changing the software limit value A2 in relation to
the operating range.
No
0.0 to 100.0 [98.0] % of the
operating range
Limit value A2
ESC
EB 8387-3 EN
71
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
28*
Testing the software limit switches alarm A1 and A2 as well as
the fault alarm contact A3.
If the test is activated, the respective limit switches five times.
Alarm test
Reading direction:
29*
30*
Standard
Turned
[No]
[No]
RUN 1
1 RUN
RUN 2
2 RUN
RUN 3
3 RUN
ESC
ESC
Position transmitter x/ix
[ää]
äæ
ESC
RUN1/1 RUN: Software limit switch A1
RUN2/2 RUN: Software limit switch A2
RUN3/3 RUN: Fault alarm contact A3
3)
Fault alarm ix 3)
[No] HI LO
ESC
31*
Position transmitter test 3)
–10.0 to 110.0 [default
value is the last indicated
value of the position
transmitter]
% of the operating range
Operating direction of the position transmitter; indicates how the
travel/angle position is assigned to the output signal i, based on
the closed position.
The operating range (see Code 8) of the valve is represented by
the 4 to 20 mA signal.
When a positioner is not connected (reference variable less than
3.6 mA), the signal is 0.9 mA and when the positioner has not
been initialized 3.8 mA.
Used to select whether faults causing the fault alarm contact to
switch should also be signaled by the position transmitter output
and how they should be signaled
HI ix = 21.6 mA or LO ix = 2.4 mA
Testing the position transmitter. Values can be entered in relation
to the operating range.
The current actual value is used in initialized positioners locally
as the start value (bumpless changeover to the test mode). On
testing over software, the entered simulation value is issued as
the position feedback signal for 30 seconds.
ESC
3)
72
Analog position transmitter: Code 29/30/31 can only be selected if the position transmitter (optional) is installed.
EB 8387-3 EN
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
32*
“Function check” alarm
No · [YES]
ESC
33*
“Maintenance required”
alarm
No · [YES]
ESC
34*
The condensed state can be used for a fault alarm output over
the optional binary contact and the optional position transmitter
(see Code 25).
No
“Function check” condensed state has no affect on
the fault alarm output
YES
“Function check” condensed state switches the fault
alarm output
No
Only the “Maintenance alarm” condensed state
switches the fault alarm output, “Maintenance
required”/”Maintenance demanded”, however, does not
YES
Both the “Maintenance alarm” condensed state and
“Maintenance required”/”Maintenance demanded”
condensed state switch the fault alarm output
[CCL] Counterclockwise
Turning direction of the lever in which the valve is moved to the
CLOSED position (view onto the display of the positioner).
CL
Needs only be entered in SUB initialization mode.
Closing direction
Clockwise
ESC
35*
Blocking position
Distance up to the CLOSED position (0 % position).
[0] mm/° /%
Only needs to be entered in SUB initialization mode.
ESC
36*
Reset
[No]
Std · diAG
ESC
37*
Position transmitter
[No] YES
Std:
Resets all parameters to default (factory setting) as well
as the diagnosis data. After a reset, the positioner must
be re-initialized.
diAG: Resets diagnosis data only. Plotted reference graphs and
logs remain unaffected. The positioner does not need to
be re-initialized.
Display only,
indicates whether the position transmitter option is installed.
ESC
38*
Inductive alarm
Type 3731-3 does not have an optional inductive alarm.
No
39
System deviation e
Deviation from the target position (e = w – x)
–99.9 to 999.9 %
Display only
EB 8387-3 EN
73
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
40
Minimum transit time OPEN Time [s] needed by the system (positioner, actuator and valve) to
move through the nominal travel/angle to open the valve (100 %
0 to 240 s [0 s]
position).
Display only
41
Minimum transit time
CLOSED
0 to 240 s [0 s]
Time [s] needed by the system (positioner, actuator and valve) to
move through the nominal travel/angle to close the valve (0 %
position).
Display only
42
Auto-w/manual-w
Supplied manual and automatic reference variable
0.0 to 100.0 % of the span
Display only
4 to 20 mA
43
Firmware version control
Xxxx
Positioner type and current firmware version (in alternating sequence)
Display only
44
y info
0 to 100 %, [0 %]
45
Control signal y [%] based on the travel range determined on initialization · Display only
MAX:
The positioner builds up its maximum output pressure,
see description in Code 14 and 15.
0 P:
The positioner vents completely, see description in
Code 14 and 15.
– – –:
The positioner has not been initialized.
Forced venting status
Indicates whether the option is installed or not · Display only
No · HIGH/LOW · YES
No
No forced venting installed
YES
Forced venting installed
If a voltage supply is connected at the terminals of the optional
forced venting, YES and HIGH appear on the display in alternating sequence. If a voltage supply is not applied (actuator
vented, fail-safe position indicated on the display by the S icon),
YES and LOW appear on the display in alternating sequence.
46*
74
Polling address
0 to 15/63 [0]
ESC
EB 8387-3 EN
Select bus address
®
0 to 15 for active HART Revision 5 (default setting)
®
0 to 63 for active HART Revision 6.
The address can only be switched over using the operating
software.
Code list
Code Parameter – Display, values
Description
no. [default setting]
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
When the write protection function is activated, device data can
®
only be read, but not overwritten over HART communication.
47*
Write protection HART
[No] · YES
ESC
48*
Diagnostics Refer to EB 8389 EN on EXPERTplus Valve Diagnostics
49*
Note: The error codes listed in following appear in the display corresponding to their status
classification set over the condensed state (Maintenance required/Maintenance demanded:
, Out of specification:
blinking, Maintenance alarm:
). If “No message” is assigned
to the error code as the status classification, the error is not included in the condensed state.
A status classification is assigned to every error code in the default setting. The status classification of error codes can also be changed as required using an operating software (e.g.
TROVIS-VIEW).
EB 8387-3 EN
75
Code list
Initialization errors
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
50
x > range
The value supplied by the measuring signal is either too high or
too low, the measuring sensor is close to its mechanical limit.
• Pin positioned incorrectly.
• Bracket slipped in case of NAMUR attachment or positioner is
not central.
• Follower plate incorrectly attached.
Status classification [Maintenance required]
Recommended action Check attachment and pin position, set operating mode from
SAFE to MAN and re-initialize the positioner.
51
∆x < range
The measuring span of the sensor is too low.
• Pin positioned incorrectly.
• Wrong lever.
A rotational angle smaller than 16° at the positioner shaft creates
just an error message. An angle below 9° leads to the initialization being canceled.
Status classification [Maintenance required]
Recommended action Check attachment and re-initialize the positioner.
52
Attachment
• Positioner attachment incorrect.
• Nominal travel/angle (Code 5) could not be achieved during
initialization under NOM (no tolerance downwards
permissible).
• Mechanical or pneumatic fault, e.g. wrong lever selected or
supply pressure too low to move to the required position.
Status classification [Maintenance required]
Recommended action Check attachment and supply pressure. Re-initialize the
positioner.
Under certain circumstances, it may be possible to check the
maximum travel/angle by entering the actual pin position and
then performing an initialization under MAX.
After initialization has been completed, the Code 5 indicates the
maximum achieved travel or angle.
76
EB 8387-3 EN
Code list
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
53
Initialization time exceeded The initialization routine lasts too long.
(Init time >)
• No pressure on the supply line or there is a leak.
• Supply air failure during initialization.
Status classification [Maintenance required]
Recommended action Check attachment and supply pressure.
Re-initialize the positioner.
54
Initialization/forced venting 1) A solenoid valve is installed (Code 45 = YES) and was
not or not properly connected so that an actuator pressure
could not be built up. The message is generated when you
attempt to initialize the positioner.
2) If you attempt to initialize the device from the fail-safe
position (SAFE).
Status classification [Maintenance required]
Recommended action Re. 1) Check connection and supply voltage of the forced venting
Code 45 HIGH/LOW
Re. 2) Set the MAN operating mode over Code 0. Then initialize
the positioner.
55
Transit time too short
(transit time <)
The actuator positioning rates determined during the initialization are so short that the positioner cannot adapt itself optimally.
Status classification [Maintenance required]
Recommended action Check the volume restriction setting as described in section 4,
re-initialize the positioner.
56
Pin position
Initialization was canceled because you are required to enter the
pin position for the selected initialization modes NOM and SUb.
Status classification [Maintenance required]
Recommended action Enter pin position over Code 4 and nominal travel/angle over
Code 5. Re-initialize the positioner.
EB 8387-3 EN
77
Code list
Operational errors
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
57
Control loop
Additional alarm at the fault
alarm output
Control loop error, the control valve does not react within the tolerable times of the controlled variable (tolerance band alarm
Code 19).
• Actuator mechanically blocked.
• Attachment of the positioner subsequently shifted.
• Supply pressure not sufficient.
Status classification [Maintenance required]
Recommended action Check attachment.
58
Zero point
Zero point incorrect.
Error may arise when the mounting position/linkage of the positioner moves or when the valve seat trim is worn, especially with
soft-sealed plugs.
Status classification [Maintenance required]
Recommended action Check valve and mounting of the positioner. If OK, perform a
zero calibration over Code 6 (see section 7.6 on page 58).
If the lever position on the back of the positioner has been
changed (e.g. while exchanging the lever), move the lever as far
as it will go in both directions to adapt it to the internal measuring lever.
We recommend re-initializing the postioner if the zero point deviates by more than 5 %.
59
Autocorrection
Should an error occur in the data range of the positioner, the
self-monitoring function recognizes it and automatically corrects
it.
Status classification [No message]
Recommended action Automatic
60
Fatal error
An error was detected in the data relevant for safety,
autocorrection is not possible. This may be due to EMC
disturbances.
The positioner changes to the fail-safe position (SAFE).
Status classification Maintenance alarm (cannot be classified)
Recommended action Reset over Code 36.
Re-initialize the positioner (see sections 7.7 and 7.5).
78
EB 8387-3 EN
Code list
Hardware errors
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
62
x signal
Additional alarm at the fault
alarm output
Determination of the measured data for the actuator has failed.
Conductive plastic element is defective.
The positioner continues to run in emergency mode, but should
be replaced as soon as possible.
The emergency mode on the display is indicated by a blinking
closed-loop control icon and 4 dashes instead of the position indication.
Note on the control:
If the measuring system has failed, the positioner is still in a reliable state. The positioner switches to emergency mode where the
position cannot be accurately controlled anymore. However, the
positioner continues operation according to its reference variable
signal so that the process remains in a safe state.
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
63
w too low
The reference variable w is lower than 3.7 mA. This message occurs whenever the power source that drives the positioner does
not comply with the standard.
This condition is indicated on the positioner display by LOW
blinking.
The positioner changes to the fail-safe position (SAFE).
Status classification [No message]
Recommended action Check the reference variable.
If necessary, limit the current source downwards so that no values
below 3.7 mA can be issued.
64
i/p converter
The circuit of the i/p converter has been interrupted.
The positioner changes to the fail-safe position (SAFE).
Status classification Maintenance alarm (cannot be classified)
Recommended action Cannot be remedied.
Return the positioner to SAMSON AG for repair.
EB 8387-3 EN
79
Code list
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
65
Hardware
Initialization key jammed (firmware version 1.51 and higher)
Additional alarm at the fault
alarm output
A hardware error has occurred, the positioner changes to the
fail-safe position (SAFE).
Status classification Maintenance alarm (cannot be classified)
Recommended action Confirm error and return to the automatic operating mode, or
perform a reset and re-initialize the device. If this is not successful, return device to SAMSON AG for repair.
66
Data memory
Additional alarm at the fault
alarm output
The writing of data to the data memory does not work anymore,
e.g. when the written data deviate from the read data.
Valve moves to the fail-safe position.
Status classification Maintenance alarm (cannot be classified)
Recommended action Return the positioner to SAMSON AG for repair.
67
Test calculation
Additional alarm at the fault
alarm output
The hardware controller is monitored by means of a test
calculation.
Status classification Maintenance alarm (cannot be classified)
Recommended action Confirm error. If this is not possible, return the positioner to
SAMSON AG for repair.
80
EB 8387-3 EN
Code list
Data errors
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
68
Control parameter
Control parameter error
Additional alarm at the fault
alarm output
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
69
Poti parameter
Parameter error of the digital potentiometer.
Additional alarm at the fault
alarm output
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
70
Calibration parameter
Additional alarm at the fault
alarm output
Error in the production calibration data. Subsequently, the device
runs on default values.
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
71
General parameters
Parameter errors that are not critical for the control.
Status classification [Maintenance required]
Recommended action Confirm error.
Check and, if necessary, reset required parameters.
72
Start-up parameters
Start-up parameter error
Status classification [Maintenance required]
Recommended action Confirm error, perform reset and re-initialize the positioner.
73
Internal device error 1
Internal device error
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
74
HART parameters
Parameter errors that are not critical for the control.
Status classification [Maintenance required]
Recommended action Confirm error and perform reset.
EB 8387-3 EN
81
Code list
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
75
Info parameters
Info parameter errors that are not critical for the control.
Status classification [Maintenance required]
Recommended action Confirm error.
Check and, if necessary, reset required parameters.
76
No emergency mode
The travel measuring system of the positioner has a
self-monitoring function (see Code 62).
An emergency mode (open-loop control) is not available for
certain actuators, such as double-acting actuators. In this case,
the positioner changes to the fail-safe position (SAFE) when a
measuring error occurs. During the initialization, the positioner
checks whether the actuator has such a function or not.
Status classification [No message]
Recommended action Merely information, confirm, if necessary.
No further action necessary.
77
Program loading error
When the positioner starts operation for the first time after the input signal has been applied, it carries out a self-test (tEStinG runs
across the display).
If the positioner loads the wrong program, the valve moves to the
fail-safe position. It is not possible to make the valve leave this
fail-safe position again.
Status classification Maintenance alarm (cannot be classified)
Recommended action Interrupt current and restart positioner.
Otherwise, return the positioner to SAMSON AG for repair.
78
Options parameter
Errors in options parameters
Status classification [Maintenance required]
Recommended action Return the positioner to SAMSON AG for repair.
82
EB 8387-3 EN
Code list
Diagnosis errors
Error codes – Recommended action Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
79
Diagnostic alarms
Error messages are generated in the extended EXPERTplus diagnostics (refer to EB 8389 EN on EXPERTplus valve diagnostics)
Status classification Maintenance required (cannot be classified)
80
Diagnostic parameters
Errors that are not critical for control.
Status classification Maintenance required (cannot be classified)
81
Reference test canceled
An error occurred during plotting the reference graphs for drive
signal y steady-state or drive signal y hysteresis.
• Reference test was interrupted
• Reference line for drive signal y steady-state or drive signal y
hysteresis was not adopted.
Error messages are saved in EEPROM. They cannot be reset.
Status classification [Maintenance required]
Recommended action Check and, if necessary, perform a new reference test
EB 8387-3 EN
83
Dimensions in mm
12
Dimensions in mm
Pressure
gauge
bracket
or connecting plate
(G ¼ only)
Attachment acc. to
IEC 60534-6 →
Lever in mm
70
15
S = 17
M = 50
L = 100
XL = 200
58
46
Electrical connections:
2 x female thread
½ NPT or
M20 x 1.5
34
34
14
122
Direct
attachment →
NPT ½, ¼
58
236
95
53
Fig. 16a · Attachment to IEC 60534-6 and direct attachment
84
EB 8387-3 EN
28
Output
Supply
¼ NPT
Dimensions in mm
Output Y1
Output Y1
Supply (9)
86
56
80
52
80
130
166
30
86
Ø 101
Output Y2
Output Y2
Type 3710
Reversing
Amplifier
Output A1
Supply (9)
50
Z
76
A1
86
56
A2
Output A2
30
86
Ø 101
80
130
166
Reversing amplifier
Fig. 16b · Attachment to rotary actuators VDI/VDE 3845 (Sept. 2010), level 1, size AA1 to AA4
EB 8387-3 EN
85
Dimensions in mm
12.1
Fixing levels according to VDI/VDE 3845 (September 2010)
Mmin
Level 2 (bracket surface)
25
M6
C
Level 1 (actuator surface)
Actuator
Dimensions in mm
Ød
B
ØD
A
Size
A
B
C
∅d
Mmin
∅D*
AA0
50
25
15
5.5 for M5
66
50
AA1
80
30
20
5.5 for M5
96
50
AA2
80
30
30
5.5 for M5
96
50
AA3
130
30
30
5.5 for M5
146
50
AA4
130
30
50
5.5 for M5
146
50
AA5
200
50
80
6.5 for M6
220
50
* Flange type F05 according to DIN EN ISO 5211
86
EB 8387-3 EN
Appendix
13
Appendix
13.1
Selecting the valve characteristic
The characteristics that can be selected in Code 20 are shown in following in graph form.
Note: A characteristic can only be defined (user-defined characteristic) using a workstation/
operating software (e.g. TROVIS-VIEW).
Linear (select characteristic: 0)
Travel/ angle of rotation [%]
100
50
Reference variable [%]
0
0
50
100
Equal percentage (select characteristic: 1)
Travel/ angle of rotation [%]
Rev. equal percentage (select characteristic: 2)
Travel/ angle of rotation [%]
100
100
50
50
Reference variable [%]
0
0
50
100
Reference variable [%]
0
0
50
100
EB 8387-3 EN
87
SAMSON butterfly valve linear
(select characteristic: 3)
SAMSON butterfly valve equal percentage
(select characteristic: 4)
Travel/ angle of rotation [%]
Travel/ angle of rotation [%]
100
100
50
50
Reference variable [%]
0
0
50
Reference variable [%]
0
0
100
VETEC rotary plug valve linear
(select characteristic: 5)
Travel/ angle of rotation [%]
50
100
VETEC rotary plug valve equal percentage
(select characteristic: 6)
Travel/ angle of rotation [%]
100
100
50
50
Reference variable [%]
0
0
50
100
Segmented valve ball linear
(select characteristic: 7)
Reference variable [%]
0
0
50
100
Segmented ball valve equal percentage
(select characteristic: 8)
Travel/ angle of rotation [%]
Travel/ angle of rotation [%]
100
100
50
50
Reference variable [%]
0
0
50
100
Reference variable [%]
0
0
50
100
EB 8387-3 EN
89
90
EB 8387-3 EN
EB 8387-3 EN
91
92
EB 8387-3 EN
EB 8387-3 EN
93
94
EB 8387-3 EN
EB 8387-3 EN
95
96
EB 8387-3 EN
EB 8387-3 EN
97
Index
Index
A
Accessories. . . . . . . . . . . . . . . . . . . 30, 32
Additional equipment
binary contact . . . . . . . . . . . . . . . . . . 9
binary input. . . . . . . . . . . . . . . . . . . 10
forced venting . . . . . . . . . . . . . . . . . . 9
position transmitter. . . . . . . . . . . . . . . 9
Article code . . . . . . . . . . . . . . . . . . . . . . 7
Attachment
acc. to IEC 60534-6 (NAMUR) . . . . . 22
direct attachment
to Type 3277 Actuator . . . . . 20
to Type 3277-5 Actuator . . . . 17
reversing amplifier . . . . . . . . . . . . . . 28
to Type 3510 Micro-flow Valve. . . . . 24
to rotary actuators . . . . . . . . . . . . . . 26
Automatic mode . . . . . . . . . . . . . . . . . . 61
B
Bar elements . . . . . . . . . . . . . . . . . . . . . 42
Blocking position
canceling . . . . . . . . . . . . . . . . . . . . 57
Connections
electrical . . . . . . . . . . . . . . 36 - 37, 41
pneumatic . . . . . . . . . . . . . . . . . . . . 34
D
Default values . . . . . . . . . . . . . . . . . . . . 59
Design, positioner . . . . . . . . . . . . . . . . . . 8
Dimensions . . . . . . . . . . . . . . . . . . 84 - 86
Display . . . . . . . . . . . . . . . . . . . . . . 42, 44
turned by 180° . . . . . . . . . . . . . . . . 47
E
Electrical connections. . . . . . . . . . . . 36, 39
Enable configuration . . . . . . . . . . . . . . . 60
Error messages
confirming. . . . . . . . . . . . . . . . . . . . 63
data errors . . . . . . . . . . . . . . . . . . . 81
diagnosis errors. . . . . . . . . . . . . . . . 83
hardware errors . . . . . . . . . . . . . . . 79
initialization errors. . . . . . . . . . . . . . 76
operational errors . . . . . . . . . . . . . . 78
Explosion protection . . . . . . . . . . . . . . . 13
F
C
Fail-safe position . . . . . . . . . . . . . . . . . . 62
Cable entry . . . . . . . . . . . . . . . . . . . . . . 38
Characteristic
selecting . . . . . . . . . . . . . . . . . . 70, 87
Closed position of valve . . . . . . . . . . . . . 49
Code list . . . . . . . . . . . . . . . . . . . . 65 - 83
Communication . . . . . . . . . . . . . . . . . . . 12
HART . . . . . . . . . . . . . . . . . 10, 12, 45
Condensed state . . . . . . . . . . . . . . . . . . 63
Configuration
using TROVIS-VIEW. . . . . . . . . . . . . 10
Configuration enabled. . . . . . . . . . . 43, 60
H
98
EB 8387-3 EN
HART® communication . . . . . . . . . . . . . 45
HART® protocol . . . . . . . . . . . . . . . . . . 40
I
Initialization
MAN manually selected range . . 50, 53
MAX maximum range. . . . . . . . 50 - 51
NOM nominal range . . . . . . . . . 50, 52
SUB substitute calibration . . . . . . 50, 55
Index
M
T
Maintenance. . . . . . . . . . . . . . . . . . . . . 64
Malfunction. . . . . . . . . . . . . . . . . . . . . . 62
Manual mode . . . . . . . . . . . . . . . . . . . . 61
Mounting parts . . . . . . . . . . . . 30, 32 - 33
Technical data . . . . . . . . . . . . . . . . 12 - 13
additional equipment . . . . . . . . . . . . 14
Travel tables . . . . . . . . . . . . . . . . . . . . . 16
O
Valve characteristic, selecting. . . . . . . . . 87
Operating modes . . . . . . . . . . . . . . 42, 61
Operating range
MAN manually selected range . . 50, 53
MAX maximum range. . . . . . . . 50 - 51
NOM nominal range . . . . . . . . . 50, 52
checking . . . . . . . . . . . . . . . . . . . . . 48
Operator controls. . . . . . . . . . . . . . 42 - 45
Output
(signal pressure) . . . . . . . . . . . . . . . 35
Z
V
Zero calibration . . . . . . . . . . . . . . . . . . 58
P
Pneumatic connections . . . . . . . . . . 34 - 35
Principle of operation, positioner . . . . . . . 8
R
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Reversing amplifier . . . . . . . . . . . . . . . . 28
Rotary pushbutton . . . . . . . . . . . . . . . . . 42
S
Serial interface . . . . . . . . . . . . . . . . 10, 42
Servicing . . . . . . . . . . . . . . . . . . . . . . . 64
Signal pressure . . . . . . . . . . . . . . . . . . . 35
indicating . . . . . . . . . . . . . . . . . . . . 35
limiting . . . . . . . . . . . . . . . . . . . . . . 47
Start-up . . . . . . . . . . . . . . . . . . . . . 46, 59
Status messages . . . . . . . . . . . . . . . . . . 42
Substitute calibration . . . . . . . . . . . . 50, 55
Supply pressure. . . . . . . . . . . . . . . . . . . 35
EB 8387-3 EN
99
EB 8387-3 EN
2015-02
SAMSON AG · MESS- UND REGELTECHNIK
Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507
Internet: http://www.samson.de