Download Sharp AE-X30EJ Service manual

Transcript
TopPage
AEXM30GR
SERVICE MANUAL
S9619AEXM30GR
MULITI SPLIT TYPE
ROOM AIR CONDITIONERS
MODEL
OUTDOOR UNIT
AE-XM30GR
In the interests of user-safety (Required by safety regulations in some countries)
the set should be restored to its original condition and only parts identical to those
specified should be used.
CONTENTS
CHAPTER 1. SPECIFICATION
[1] SPECIFICATION ...........................................1-1
[2] EXTERNAL DIMENSION ..............................1-2
[3] CAPACITY TABLE.........................................1-2
[4] ELECTRICAL PARTS....................................1-4
[5] WIRING DIAGRAMS .....................................1-4
CHAPTER 2. EXPLANATION OF CIRCUIT AND OPERATION
[1] BLOCK DIAGARM.........................................2-1
[2] FUNCTIONS..................................................2-2
CHAPTER 4. REFRIGERATION CYCLE
[1] REFRIGERATION SYCLE ............................. 4-1
[2] REFRIGERANT PIPE INSTALLATION
WORKS.......................................................... 4-3
CHAPTER 5. DISASSEMBLING PROCEDURE
[1] OUTDOOR UNIT ........................................... 5-1
Parts Guide
CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
[1] PROTECTIVE FUNCTIONS AND OPERATIONS............................................................3-1
[2] TROUBLESHOOTING GUIDE ......................3-2
Parts marked with "
" are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining the
safety and performance of the set.
This document has been published to be used for
after sales service only.
The contents are subject to change without notice.
AE-XM30GR
CHAPTER 1. SPECIFICATION
AE-XM30GR
Service Manual
[1] SPECIFICATION
MODEL
ITEMS
Cooling capacity
4-INDOOR OPERTION
Heating capacity
4-INDOOR OPERTION
Moisture removal (at cooling)✩
Electrical data
Phase
Rated frequency
Rated voltage
Rated current
Rated input ✩
(Min. - Max.)
Power factor ✩
Compressor
Refrigerant system
Noise level (at cooling)
kW
9K&7K&7K&7K
kW
9K&7K&7K&7K
Liters/h
Hz
V
Cool
A
Heat
A
Cool
W
Heat
W
Cool
%
Heat
%
Type
Model
Oil charge
Evaporator
Condenser
Control
Name of refrigerant
Refrigerant volume
dB(A)
Fan system
Drive
Air flow quantity
(at cooling)
Fan
Connections
Refrigerant coupling
Refrigerant tube size Gas, Liquid
Maximum length (per unit)
Maximum length (total)
Maximum charge-less length
Maximum height difference
Drain joint
Others
Safety device
Net dimensions
Net weight
INDOOR UNIT
AY-XPM7FR/9FR/12FR
OUTDOOR UNIT
AE-XM30GR
8.4(4.3–9.0)*
9.0(4.4–10.6)*
1.0&0.8X3*
Single
50
230V
13.7(4.9– 16.0)*
11.0 (4.3 – 14.0)*
2990 (1070– 3490)*
2400 (940 – 3060)*
95
95
Hermetically sealed DC twin rotary
DA220A2F-20L
Ester oil VG74
Silt Fin and Grooved tube type
Corrugate Fin and Grooved tube type
Expansion valve
R410A
2400g
High/Med/Low
7FR: 37/34/28
57
9FR: 39/36/28
12FR: 40/37/29
Direct drive
.
m3/min.
m
m
m
m
mm
High/Med/Low
7FR: 8.0/7.4/5.4
9FR: 8.6/7.9/5.6
12FR: 9.8/8.6/8.6
Cross flow fan
52
Propeller fan
Flare type
1/2”, 1/4”(18class only),3/8”,1/4”
20
50
50
10
O.D18
Compressor: Thermistor
Fan motors: Thermal fuse (indoor unit).
Thermal protector (Out door unit)
Fuse, Micro computer control
Anti-mold polypropylene net of injection type
(Washable)
Width
mm
790
940
Height
mm
278
800
Depth
mm
198
357
kg
10
70
NOTE: The condition of star “✩“marked item are ‘ISO5151’: *: Representative connection
1–1
AE-XM30GR
[2] EXTERNAL DIMENSION
150
150
590
75
51.3
16
361
383
¿4.5
940
890
50
37
320
[3] CAPACITY TABLE
Recommended Combination
Outdoor Units
AE-XM30FR
Indoor Units
AY-XPM7/9/12FR,GS-XPM9/12/18FGR,GS-XPM7/9/12FR
18
12
7
18
9
9
18
9
7
18
7
7
12
12
7
7
12
9
9
7
9
9
9
9
12
9
7
7
9
9
9
7
12
7
7
7
9
9
7
7
9
7
7
7
7
7
7
7
1–2
52
52
284
389
52
151
26
210
800
52
26
AE-XM30GR
COOLING CAPACITY TABLE
Operating
Status
4-Room
3-Room
2-Room
1-Room
Combination of Indoor
Units
A
B
C
D
12
12
07
07
12
09
09
07
09
09
09
09
12
09
07
07
09
09
09
07
12
07
07
07
09
09
07
07
09
07
07
07
07
07
07
07
18
12
07
18
09
09
18
09
07
18
07
07
12
12
07
OFF
12
09
09
OFF
09
09
09
OFF
12
09
07
OFF
12
07
07
OFF
09
09
07
OFF
09
07
07
OFF
07
07
07
OFF
18
12
OFF
18
9
OFF
18
7
OFF
12
12
OFF OFF
12
09
OFF OFF
12
07
OFF OFF
09
09
OFF OFF
09
07
OFF OFF
07
07
OFF OFF
18
OFF OFF OFF
12
OFF OFF OFF
09
OFF OFF OFF
07
OFF OFF OFF
Cooling Capacity (kW)
A
2.65
2.73
2.10
2.88
2.22
3.06
2.36
2.52
2.00
4.04
4.15
4.39
4.67
3.0
3.2
2.5
3.3
3.4
2.5
2.6
2.0
4.56
4.80
4.90
3.1
3.2
3.3
2.5
2.6
2.0
5.0
3.4
2.6
2.0
B
2.65
2.04
2.10
2.16
2.22
1.78
2.36
1.96
2.00
2.69
2.08
2.20
1.82
3.0
2.3
2.5
2.4
1.9
2.5
2.0
2.0
3.04
2.40
1.90
3.1
2.4
2.0
2.5
2.0
2.0
OFF
OFF
OFF
OFF
C
1.55
2.04
2.10
1.68
2.22
1.78
1.84
1.96
2.00
1.57
2.08
1.71
1.8
1.8
2.3
2.5
1.9
1.9
2.0
2.0
2.0
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
D
1.55
1.59
2.10
1.68
1.74
1.78
1.84
1.96
2.00
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
RATING (Min.-Max.)
8.4 (4.3-9.0)
8.4 (4.3-9.0)
8.4 (4.3-9.0)
8.4 (4.3-9.0)
8.4 (4.3-9.0)
8.4 (4.3-9.0)
8.4 (4.3-9.0)
8.4 (4.3-9.0)
8.0 (4.3-9.0)
8.3 (4.3-8.9)
8.3 (4.3-8.9)
8.3 (4.3-8.9)
8.3 (4.3-8.9)
7.8 (3.6-8.4)
7.8 (3.6-8.4)
7.4(3.6-8.4)
7.6 (3.6-8.4)
7.2 (3.6-8.4)
7.0 (3.6-8.4)
6.6 (3.6-8.2)
6.0(3.6-7.8)
7.6 (3.6-8.0j
7.2 (3.6-8.0j
6.8 (3.6-8.0j
6.2 (2.6-7.5j
5.6 (2.6-7.1j
5.3 (2.6-6.8)
5.0 (2.6-6.3)
4.6 (2.6-5.9)
4.0 (2.6-5.3)
5.0 (2.6-5.7)
3.4 (1.8-4.0)
2.6 (1.8-3.3)
2.0 (1.8-2.7)
Running Current (A)
RATING (Min.-Max.)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
12.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-16.0)
13.7 (4.9-6.0)
13.7 (4.9-16.0)
13.7 (4.0-15.1)
13.7 (4.0-15.1)
12.1 (4.0-15.1)
12.8 (4.0-5.1)
11.7 (4.0-15.1)
11.0 (4.0-15.1)
9.9 (4.0-14.6)
8.8 (4.0-14.2)
13.7 (4.0-15.6)
11.9 (4.0-15.6)
10.8 (4.0-15.6)
10.3 (3.2-16.9)
8.9 (3.2-14.6)
7.9 (3.2-12.7)
7.5 (3.2-11.9)
6.4 (3.2-10.3)
5.5 (3.2-8.7)
7.3 (3.2-11.0)
5.0 (2.9-6.6)
3.6 (2.9-4.9)
3.4 (2.9-3.9)
Power Consumption
(W)
RATING (Min.-Max.)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2780(1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (1070-3490)
2990 (880-3300)
2990 (880-3300)
2650 (880-3300)
2800 (880-3300)
2550 (880-3300)
2400 (880-3300)
2160 (880-3200)
1920 (880-3100)
2990 (880-3400)
2600 (880-3400)
2350 (880-3400)
2250 (700-3700)
1950 (700-3200)
1720(700-2770)
1630 (700-2600)
1400 (700-2250)
1200 (700-1900)
1600 (700-2400)
1100 (630-450)
790 (630-1080)
750 (630-850)
HEATING CAPACITY TABLE
Operating Status
4-Room
3-Room
Combination of Indoor
Units
A
B
C
D
12
12
07
07
12
09
09
07
09
09
09
09
12
09
07
07
09
09
09
07
12
07
07
07
09
09
07
07
09
07
07
07
07
07
07
07
18
12
07
18
09
09
18
09
07
18
07
07
12
12
07
OFF
12
09
09
OFF
09
09
09
OFF
12
09
07
OFF
12
07
07
OFF
09
09
07
OFF
09
07
07
OFF
07
07
07
OFF
Heating Capacity (kW)
A
2.84
2.92
2.25
3.09
2.38
3.27
2.53
2.70
2.13
4.33
4.45
4.71
5.01
3.4
3.6
2.9
3.8
3.9
3.0
3.0
2.4
B
2.84
2.19
2.25
2.31
2.38
1.91
2.53
2.10
2.13
2.89
2.33
2.36
1.95
3.4
2.6
2.9
2.8
2.3
3.0
2.4
2.4
C
1.66
2.19
2.25
1.80
2.38
1.91
1.97
2.10
2.13
1.68
2.23
1.83
1.95
2.0
2.6
2.9
2.2
2.3
2.2
2.4
2.4
D
1.66
1.70
2.25
1.80
1.85
1.91
1.97
2.10
2.13
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
RATING (Min.-Max.)
9.0 (4.4-10.6)
9.0 (4.4-10.6)
9.0 (4.4-10.6)
9.0 (4.4-10.6)
9.0 (4.4-10.6)
9.0 (4.4-10.6)
9.0 (4.4-10.6)
9.0 (4.4-10.6)
8.5 (4.4-9.8)
8.9 (4.4-10.5)
8.9 (4.4-10.5)
8.9 (4.4-10.5)
8.9 (4.4-10.5)
8.8 (3.6-10.0)
8.8 (3.6-10.0)
8.8 (3.6`10.0)
8.8 (3.6-10.0)
8.5 (3.6-10.0)
8.2 (3.6-10.0)
7.8 (3.6-9.4)
7.1(3.6-8.8)
1–3
Running Current (A)
RATING (Min.-Max.)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
10.2 (4.3-13.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
11.0 (4.3-14.0)
12.1(3.8-14.4)
12.1(3.8-14.4)
12.1(3.8-14.4)
12.1(3.8-14.4)
11.4 (3.8-14.4)
11.0 (3.8-14.4)
9.8 (3.8-13.7)
8.6 (3.8-12.2)
Power Consumption
(W)
RATING (Min.-Max.)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2230(940-2850)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2400 (940-3060)
2650(830-3150)
2650(830-3150)
2650(830-3150)
2650(830-3150)
2500 (830-3150)
2400 (830-3150)
2150 (830-2990)
1870 (830-2660)
AE-XM30GR
Operating Status
2-Room
1-Room
Combination of Indoor
Units
A
B
C
D
18
12
OFF
18
9
OFF
18
7
OFF
12
12
OFF OFF
12
09
OFF OFF
12
07
OFF OFF
09
09
OFF OFF
09
07
OFF OFF
07
07
OFF OFF
18
OFF OFF OFF
12
OFF OFF OFF
09
OFF OFF OFF
07
OFF OFF OFF
Heating Capacity (kW)
A
4.86
5.40
5.54
3.8
3.8
3.9
2.9
3.0
2.4
5.0
3.8
2.9
2.4
B
3.24
2.70
2.16
3.8
2.9
2.2
2.9
2.3
2.4
OFF
OFF
OFF
OFF
C
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
D
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
RATING (Min.-Max.)
8.1 (3.6-9.0j
8.1 (3.6-9.0j
7.7 (3.6-9.0j
7.6 (2.6-8.0j
6.7 (2.6-8.0j
6.1 (2.6-8.0)
5.8 (2.6-8.0)
5.3(2.6-7.3)
4.8(2.6-6.4)
6.2 (2.6-7.4)
3.8 (1.8-5.2)
2.9 (1.8-4.0)
2.4 (1.8-3.4)
[4] ELECTRICAL PARTS
Compressor
Outdoor fan motor
Outdoor fan motor capacitor
Fuse 1,2
Fuse 6
Fuse 3,4
DA220A2F-20L
MLB051
—
—
—
—
Hermetically sealed DC twin rotary
230V, 50Hz
500V, 3F
QFS-GA065JBZZ(20A,250V)
QFS-GA064JBZZ(1A,250V)
QFS-GA062JBZZ(3.15A,250V)
[5] WIRING DIAGRAMS
CC298
1–4
Running Current (A)
RATING (Min.-Max.)
11.2 (3.8-15.1)
11.2 (3.8-15.1)
10.1 (3.8-15.1)
11.9 (3.3-13.3)
10.3 (3.3-13.3)
8.7 (3.3-13.3)
8.5 (3.3-13.3)
6.9 (3.3-11.0)
6.2 (3.3-9.2)
10.1 (3.3-13.7)
7.3(2.9-10.1)
5.2 (2.9-8.0)
4.0 (2.9-6.2)
Power Consumption
(W)
RATING (Min.-Max.)
2450 (830-3300)
2450 (830-3300)
2200 (830-3300)
2600 (730-2900)
2250 (730-2900)
1900(730-2900)
1850 (730-2900)
1510 (730-2400)
1350 (730-2000)
2200 (730-3000)
1600 (640-2200)
1130 (640-1750)
870 (640-1350)
CONTROL P.W.B and DISPLAY P.W.B
1–5
to IPM PWB CN102
from IPM PWB CN114
from DC FAN MOTOR
from EXPANSION VALVE D
from TERMINAL BOARD "1"
from TERMINAL BOARD "N"
from CONTROL BOX
from TERMINAL BOARD
"N" and "2"
from THERMISTOR
COMP. TENP.
HEAT EXCHANGER TEMP.
from THERMISTOR
OUT DOOR TEMP.
(SUCTION)
SUCTION TEMP.
from EXPANSION VALVE A
from EXPANSION VALVE B
from EXPANSION VALVE C
to ACTIVE FILTER MODULE
to IPM PWB CN101
from IPM PWB
"U", "V", "W"
from 4 WAY VALVE
from DIODE BRIDGE
DB1 "~"
from HEAT-SINK
THERMISTOR
AE-XM30GR
AE-XM30GR
from ELECTROLTIC
CAPACITOR C10 "-"
from CONTROL PWB
CN14
from ELECTROLTIC CAPACITOR C10 "+"
from COMPRESSOR CORD
W "ORANGE"
from COMPRESSOR CORD
V "WHITE"
from COMPRESSOR CORD
U "RED"
from CONTROL PWB
BCN2
from CONTROL PWB BCN1
IPM P.W.B.
1–6
1
2
1
N
2
1
(TERMINAL BOARD)
UNIT D
UNIT C
UNIT B
UNIT A
WIRE CHECK SW
PUMP DOWN SW
WINTER COOL
BLUE
ORANGE
CN11
LED4
LED3
LED2
LED1
SW2
SW1
JP2
8
7
6
5
4
3
2
1
CN6 BLACK
(terminal board)
(DISPLAY PWB)
2
1
GREEN/YELLOW
GREEN/YELLOW
(POWER SUPPLY)
(UNIT D)
(UNIT C)
(TERMINAL BOARD)
(TERMINAL BOARD)
2
N
(UNIT B)
(TERMINAL BOARD)
GREEN/YELLOW
BLUE
BLACK
BROWN
BROWN
RED
1
N
(UNIT A)
(TERMINAL BOARD)
PURPLE
8
7
6
5
4
3
2
1
R147
10k
5V
1
3
5
7
9
R156
2.2k
2.2k
2.2k
2.2k
T4
BCN11
N
A
B
C
D
T1
D32
D2
250V
20A
8
PC81716
10k
R144
10k
R145
R150
R149
R148
R146
10k
R142
10k
CN3A
2A
250V
FUSE5
2
1
1000p
50V
C66
R143
10k
GND
1000p
50V
C67
C68
0.01μ
16V
5
Fan
Motor
C65
0.1μ
630V
3
GND
PC1
4
5V
C12, C14 :
C16, C18 :
10000pF
250V
C11, C13 :
C15, C17 :
4700pF
250V
3
2
1
TH9
2
R78
6.8k
3
TH8
(SUCTION C)
C80
0.1μ
50V
1
+
-
(thermistor)
(compressor)
TH1
TH2
(haet exchange)
TH3
(outdoor)
TH4
(suction )
(SUCTION A)
TH6
TH7
(SUCTION B)
CN4
4
3
CN8A
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
CN8C
3
250V
3.15A
FUSE3
4 - WAY
Valve
1
Q13
KRA106M
(SUCTION D)
R171
10K
4
2
1
C2
C12
C11
275V 1μF
C14
C13
4
3
NR2
C3
275V 1μF
SA1
NR1
D33
1/2W
150K
R5
1/2W
150K
R4
N
R9
R3
1/4W
47K
1/2W
150K
R168
D30
1/2W
R169
150K
C21
0.01μF
50V
5.6K
BLUE
BLUE
BROWN
BLUE
BROWN
BLUE
BROWN
R15
C4
2
JP3
C16
C15
RY3
C64
GREEN/YELLOW
GREEN/YELLOW
0.033μF
275V
275V 1μF
R1
1/4W
510K
C18
1W
100
C17
C1
R2
1/4W
510K
R73
5.6k
R72
5.6k
R74
10k
4
2
1
2
1
3
3
R64 -
5V
4
15V
GND
1A
250V
FUSE6
R10
C22 2KV
330pF
IC4
5
5V
PC11
PC10
51K
R20
3
7
3
4
R71 : 6.8kF
1
4
ZD3
GND
R18
2W
1.0K
R127
C70
4700P
250V
2W
1.0K
R134
3
C63
0.01μ
50V
GND
2
C62
0.1μ
50V
2W
1.0K
R118
C82
0.1μ
50V
D14
2W
1.0K
R121
C72
0.1μ
50V
D17
2W
1.0K
R128
C73
0.1μ
50V
D16
2W
1.0K
R135
C74
0.1μ
50V
2
6
D5
7
4
3
PC817X3
1
PTC1
FUSE4
250V
3.15A
6V
+
-
R24
1/4W
PC15
PC14
3 Pc853H
PC19
2
4 PC18
1
PC817X3
3 Pc853H
PC13
2
4 PC12
1
PC817X3
3 Pc853H
2
4
2
3 Pc853H
PC16
1
PC817X3
R105
2.7k
2
3
1
4
2
3
1
4
2
3
1
4
3
1
2
4
1
PC17
PC817X3
C27
4.7K
4
18V
+
-
+
-
FC6
FC5
C55 - 61, C94 : 10μ16V
R164
R163
R162
R161
R159
R167
R166
AC2
AC1
5V
7805
IC8
4.7K
R137
C93
C33
100μF
25V
-
+
15V
BCN2
GND
50V
1000P
C83
GND
50V
1000P
C75
GND
50V
1000P
C76
R139
2.7k
GND
50V
1000P
C77
1
2
L1
-
AF1
ACT (PFC)
SACT32420C
+
FC8
ORANGE
C86 - C92, C95 : 0.01μ50V
R104
56K
4.7K
R103
R125
2.7k
R124
56K
4.7K
R123
R132
2.7k
R131
56K
4.7K
R130
R138
56K
13V
5V
C79, C93 :
250V
4700pF
C79
D31
50V
0.1μF
7815
KIA7815API
IC10
100μF
25V
GND
KIA7805API
R159, R161 - R167 : 10K
R165
2W
1.0K
R119
3.3K
R102
2W
1.0K
R122
3.3K
R126
2W
1.0K
R129
3.3K
R133
D9
D8
50V
0.01μF
2W
1.0K
R136
3.3K
R140
D7
C28
220μF
35V
R23 560
12
11
12
13
16
TR1 17
BROWN
IC9
MM1431
D15
PC81716
PC817X3
2W
1.0K
R117
C81
4700P
250V
2W
1.0K
R120
250V
C69
4700P
D6
100μF
25V
18K
C26
R19
D4
C26 :
100pF
50V
NR3
HZ15 - 1
4 PC2
C71
4700P
250V
R79
3.3k
T6
R17
33
-
+
+ 2.2K
100μF
25V
+
-
GND
PC8 :
PC10, 11 :
R76
1.5k
R75
1.5k
C23
4700pF
50V
3
R77
3.3k
4
2
1
1
2
R11
1.0K F
R17, 18, 19 :
R20, 21, 23 :
1/4W
MR2920
6
2
PC8
PC9
D1
L5
C8
R71
1
R69
10V
47μF
D3
05NU42
R16
5W
1
R68
R12
6.49K F
R21
1.0K F
R70
27K
T8
R64
C25
R66
1K
C20
C8, 20 :
275V 2.2μF
R67
C24
R65
C19
10V 220μF
C59
R22
C94
BLACK
FUSE1
C55
BLUE
C60
C61
25V
820μF
C31
C56
0.1μF
50V
C32
R27
15KF
R26
1.8KF
WHITE
L1
GND
C87
GRAY
C29
C58
+
C88
P
BLUE
8
d
a
c
Q
5V
IC5
R177
R176
40
P24
P25
MD1
MD2
P40
P37
P36
P35
P34
P33
P32
P31
P30
P27
P26
26
27
28
29
30
31
32
33
34
35
36
37
38
39
MD0
25
R107
270
R106
270
R152
4.7K
5V
12
R153
R151
4.7K
R175 - R177
: 10K
S
3
KIA339P
5 +
18V
BCN13
CN13
C98
0.1μ
50V
4MHz
OSC1
4
3
2
1
CNE
R175
GND
b
1
7
6
2
5
4
3
IC6
(EEPROM)
S24CS02
R30
560 F
1 2 3 4 5 6
YELLOW
C10
1500μF
420V
BLUE
-
4 -
YELLOW
FC2
C9
1500μF
420V
1 2 3 4 5 6
Io
WHITE
34.8K F
15.8K F
FC4
C91
R35
R34
BROWN
C86
1/2W 270KF
270KF
R32
R33
1/2W
R31
6.8K F
C89
C34
D39
C35
0.01μF
50V
DB1
2
1
3
4
5V
3 PC3
4
2 PC4
CN14
f
PST993D
C47
IC2
1μ 50V
R101
R100
ZD101
5V
R174
2
10K
PC817X3
PC817X3
1
17
22
1000pF
50V
C119
16
50V
C120
0.022μF
FUSE2
20A 250V
N
GND
26
P
R173
IC1
6
7
8
Q7
5
4
4
3
2
3
KRC106M
monitor
1
(CN)
GND
2
1
O
Y
W
C78
1000p
50V
m
GND
C85
0.01μ
50V
GND
R160
10K
+
7
flash
writer
CND
+
11
10
-
8
-
+
9
6
-
10V
C43
100μ
D38
79
78
77
76
75
74
73
72
71
70
69
68
67
66
P86
P87
(W)
(Z)
T
GND
5V
GND
1
3
CN8B
R155
1K
R63
6.8kF
C53
50V
0.01μF
C45
50V
0.1μF
65
80
P71
P72
P73
P74
P75
P76
(U) P77
(V) P80
(W) P81
(U) P82
(X) P83
(V) P84
(Y) P85
JPF
R172
10K
5V
9
8
7
6
5
4
3
2
1
23
W 25
V 24
U
KIA339P
IC5
P70
C54
10μ
16V
P
3
12
R
S
T
Q
GND
41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
B
13
14
1
18V
GND
C44
0.1μ
50V
P
R44
3.3K
1/4W
m
R45
1 3.3K
1/4W
3 PC7 2
4
R46
3.3K
1 1/4W
3 PC6 2
4
PC5, PC6, PC7 :
PC817X3
1
3 PC5 2
4
QM101 (IPM)
10K
GND
GND
24 23 222 21 20 19 18 17 16 15 14 13 12 11 10 9
R
4 3 2 1
CN114
e
4 3 2 1
GND
R154
C46
0.1μ
50V
1K
1K
R37
TN
3.3K
1/4W
R36
1M
BLUE
-
+
X0
VCC
MRY1
P42
L4
VSS
(O)
P22
L3
P41
(Y)
P21
RST
(T2)
(W)
P20
P43
P17
R29
10K
C92
C36
R113
: 130K 1/4W
R113, 114,
116, 192
R192
R116
R112
0.01μF
50V
C37
P44
P15
P16
FC3
FC7
L2
P45
P14
0.1μF
50V
630V
0.33μF
R38
10K
C121
P46
P13
50V C36
R100, R101 :
5W 0.018
R39
390
1/4W
P47
P12
R25
2.7KF
C90
50V
0.1μF
X1
(B)
P23
P50
P11
R49
100
R50
100
R48
100
1/4W
R47
100
1/4W
TW
TV
1/4W
1/4W
TH5
(HEATSINK)
FC1
R62
R61
10K
JP5
JP4
a
b
c
d
GND
Z
Y
X
W
V
U
R80
10K
1
1/4W
1
7
8
9
9
10
5
Z 6
4
3
2
1/4W
2SA1020Y
1/4W
2SA1020Y
8
10
13V
1/4W
2SA1020Y
6
Y
X
W
V
U
CN101
Q1
Q2
Q3
Q4
CN16
7
5
4
3
2
BCN1
5V
KRC245M
KRC245M
KRC245M
KRC245M
R82 - R87 :
1/4W
390
R87
R86
R85
R84
R83
R82
R81
R
S
1 2 4 6
R57, R59, R61 :
1/2W 196K F
R58, R60, R62 :
1/2W 180K F
R60
R59
R57
R58
ORANGE
C
RED
R55, 56 :
1/2W 196K F
R55
R56
WHITE
TU2
C40
330pF50V
T5
P51
P10
R28
10K
C95
R108
P60
P07
C41
330pF50V
1.8K F
P61
P06
P02
C42
330pF50V
R43
1.5K
P62
P66
P01
R51
7.5K F
R42
1.5K
P63
P67
P00
R52
14.7K F
R41
1.5K
P64
P05
AVSS
VCC
0.1μF
AVR
R40
1.5K
P65
P03
P04
AVCC
VSS
50V C39
0.1μF
C
R53
R54
C48
14.7K F
14.7K F
R157 10K
R141 10K
50V
1000pF
(CONTROL PWB)
C49
50V
1000pF
IPM PWB
TP
C50
50V
1000pF
YELLOW
C52
50V
0.1μF
C30
C57
10K
C84
C51
50V
0.01μF
4
3
5
8
5
8
2 PC102
6
7
1 PC942
2 PC103
6
7
1 PC942
1 PC942
PC107
PC81716
2
1
2 PC106
6
7
1 PC942
2 PC105
6
7
5
8
5
8
5
8
1 PC942
2 PC104
6
7
8
5
Y
B
1 PC942
W
O
R95
2.2K
1/4W
R93
2.2K
1/4W
Q9
R91
2.2K
1/4W
Q10
R89
2.2K
1/4W
Q11
GND
R99
10K
R98
10K
R97
10K
R96
10K
R109
6.8k
2SA1020Y
Q12
2 PC101
6
7
R94
1K
1/4W
1/4W
R92
1K
R90
1K
1/4W
R88
1K
1/4W
0.1μF
0.1μF
0.1μF
0.1μF
0.1μF
C122
0.1μF
-
4
6
7
8
VUFS
5 VPI
VP VVFB
VVFS
2
D101
3
KID65004AP
1
VPI
UP VUFB
C129
10μF50v
+
JP1
IC3
19
FO
18
WN
21
VN
20
UN
14
IPM
VPC 11
VNC 15
VNI
VWFS 13
VPI 10
9
WP VWFB 12
C109
0.1μF
Y
RY3
D25
D24
D23
D22
-
+
C103
100μF
25V
-
+
C111
0.1μF
-
+
C110
0.1μF
-
+
D104
-
D21
D20
D19
D18
D105
D106
IPM PWB
e
Z100
HZ24 - 2
CN102
D103
W
Y
O
BL
R
GR
W
Y
O
BL
R
GR
Y
W
O
D28
MRY1
+
R
BL
D29
D27
D26
GR
W
O
D37
D35
BL
R
GR
D36
D34
C105
100μF
25V
C101
100μF
25V
CT1
R115
47K
C113
C114
C115
C116
C123
1000pF
C124
1000pF
C125
1000pF
C126
1000pF
C127
1000pF
C128
1000pF
C117
0.1μF
C118
R114
47K
C106
0.1μF
C107
0.1μF
C108
0.1μF
C112
0.1μF
R110, R111, 190, 191 :
1/2W 33
R111
R191
C102
100μF
25V
R110
R190
N
1–7
C104
330μF
25V
T7
2
1
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
(valve A)
(valve B)
CN12C
(valve C)
CN12D
(valve D)
CN12A
CN12B
AE-XM30GR
AE-XM30GR
Manual
CHAPTER 2. EXPLANATION OF CIRCUITService
AND OPERATION
AE-XM30GR
[1] BLOCK DIAGARM
Power supply
circuit
1A
Fuse
Smoothing
circuit
Active filter
circuit
20 A
Fuse
Filter
circuit
AC power
CPU oscillator circuit
DC over voltage
detection circuit
CPU
DC power
supply circuit
Expansion valve A
drive circuit
Expansion valve A
Expansion valve B
drive circuit
Expansion valve B
Expansion valve C
drive circuit
Expansion valve C
Expersion valve D drive circuit
Expansion valve D
4-way valve relay
drive circuit
4-way
valve
Outdoor fan motor relay
drive circuit
Outdoor fan
motor
Power transistor module
drive circuit
Power
transistor module
Serial I/O circuit
CPU reset circuit
3.15 A
Fuse
2A
Fuse
20 A
Fuse
Unit - unit
wiring
(AC power and
serial signals)
Compressor
DC overcurrent detection
circuit / Power transistor
module overheat
AC overcurrent detection
circuit
Current transformer
Compressor thermo circuit
Compressor thermistor
(RE)
CN8A
Heat exchanger pipe
thermo circuit
Heat exchanger pipe
thermistor
(OR)
CN8A
Outdoor temp. thermo.
circuit
Outdoor temperature
thermistor
(N)
CN8A
Suction pipe thermo circuit
Suction pipe thermistor
(BK)
CN8A
Heat sink thermo circuit
Heat sink thermistor
(BK)
CN8B
Unit A thermo. circuit
Thermistor unit A
(BL)
Unit B thermo. circuit
Thermistor unit B
(WH)
Unit C thermo. circuit
Thermistor unit C
(BR)
Unit D thermo. circuit
Thermistor unit D
(YE)
LED drive circuit
LED
Pump down switch circuit
Wire check switch circuit
Position detection circuit
Compressor
2–1
Suction thermistor
CN8C
AE-XM30GR
[2] FUNCTIONS
1. FREQUENCY CONTROL
2. OVER CURRENT PROTECTION
1) AC current peak control
DC over current detection, AC over current detection To protect
against over current due to sudden change in load, the compressor is
stopped if 55A DC is exceeded in the DC section. If the set value of
AC current is exceeded in the AC section, the compressor is stopped.
90 seconds after the compressor has been stopped, another starting
try will be made. Three retries are allowed. On the fourth retry, a complete stop request signal is sent to the indoor unit, and the outdoor unit
will remain stopped until the indoor operation is stopped. DC over current is detected by the power module. AC over current is detected by
CT1, on the outdoor PWB.
Cooling mode
16.5A
Heating mode
16.5A
2) Prevention control of outdoor heat exchanger overheating
If the temperature of the outdoor heat exchanger exceeds the overheating prevention line 1or 2 during cooling, the operating frequency is lowered by approximately 5 to 15Hz. After that, the
frequency is lowered approximately 5Hz once every 60 seconds or
approximately 15Hz once every 120 seconds. When the temperature of the outdoor heat exchanger goes below the overheating
prevention clear line, the frequency is raised by approximately 5Hz
once every 60 seconds, and normal operation is restored. If the frequency is lowered to minimum frequency without the temperature
of the outdoor heat exchanger decreasing and this condition lasts
for 1 minute, the compressor will be stopped.
Overheating Prevention line 1
55C
Overheating Prevention line 2
57C
Overheating Prevention clear line
54C
Cooling mode
19.3A
3. COMPRESSOR PROTECTION CONTROL
If the temperature of the compressor exceeds 113C, the compressor
is stopped. In this case, the outdoor fan is not stopped until the temperature of compressor drops below 99C. In 90 seconds after the
compressor is stopped, if the temperature is below 90C, another
starting try will be made. Three retries are allowed. On the fourth retry,
a complete stop request signal is sent to the indoor unit, and the outdoor unit will remain stopped until the indoor operation is stopped.
Lower 5Hz once every
60 seconds
Lower 15Hz once
every 120 seconds
4. POWER TRANSISTOR MODULE PROTECTION
3) Prevention control of compressor overheating
If the temperature of the compressor exceeds approximately 108
C, the operating frequency is lowered approximately 5Hz. After
that, the frequency is lowered approximately 5Hz once every 60
seconds. When the compressor temperature drops below approximately 108C, the frequency is raised approximately 5Hz once
every 60 seconds, and normal operation is restored. If the frequency is lowered to minimum frequency without the temperature
of the compressor decreasing, and this condition lasts for 1 minute,
the compressor will be stopped.
If the temperature of the chips in the power transistor module exceeds
100C, the compressor is stopped. In this case, the outdoor fan is not
stopped until the temperature of power module drops below 85C. In
90 seconds after the compressor is stopped, if the temperature is
below 85C, another starting try will be made. Three retries are
allowed. On the fourth retry, a complete stop request signal is sent to
the indoor unit, and the outdoor unit will remain stopped until the
indoor operation is stopped.
5. SERIAL SIGNALS
4) Prevention control of indoor heat exchanger overheating
Serial signals consist of all 96-bit signals. If the condition as outdoor
unit unable to receive a serial signal from the indoor unit continues for
30 seconds, it closes the expansion valve which corresponds to the
room which can not be communicated. If all indoor units can not communicate with the outdoor unit, the compressor is stopped.
Two minutes after room several decrease If the temperature of any
of indoor heat exchangers exceeds the overheating prevention line
1 or 2 during heating, the operating frequency is lowered to minimum frequency. When the temperature of all of indoor heat
exchangers go below the overheating prevention line 1, the frequency is raised by approximately 5Hz once every 60 seconds,
and normal operation is restored. If the condition that the frequency
is minimum lasts for 2 minutes, the compressor will be stopped.
6. THERMISTOR OPEN OR SHORT
When compressor, heat exchanger, outdoor thermistor, suction thermistor (CN8A) are in OPEN or SHORT condition, even if they are in
the condition which an operation signal is transmitted from indoors, the
compressor will not start. If any suction thermistors (CN8C) become
OPEN or SHORT resistance, the protective procedure will work only
for the cycle corresponding to the malfunctioning suction thermistor.
<when normal >
If the temperature of any of indoor heat exchangers exceeds the overheating prevention line 1 or 2 during heating, the operating frequency
is lowered by approximately 5 to 15Hz. After that, the frequency is lowered approximately 5Hz once every 60 seconds or approximately
15Hz once every 90 seconds. When the temperature of all of indoor
heat exchangers go below the overheating prevention line 1, the frequency is raised by approximately 5Hz once every 60 seconds, and
normal operation is restored. If the condition that the frequency is minimum lasts for 2 minutes, the compressor will be stopped.
44ºC
(57ºC) Overheating
prevention
line 1
900
2100
“Mis-wiring check” is conducted by detecting the indoor heat
exchanger temp. For example, when the expansion valve for only
room A is open, and the wiring is correct, the indoor heat exchanger
temp for room A will reduce. If the wiring is incorrect, the indoor heat
exchanger temp for a different room will reduce.
8. SAFETY TIME
54ºC
(59ºC)
47ºC
(60ºC)
7. MISWIRING CHECK
Overheating
prevention line 2
57ºC
(62ºC)
Heating mode
19.3A
When the unit is operated by the remote control after the breaker is
turned on, the safety device of the compressor will work and the compressor will not operate for 90 seconds.
51ºC
(57ºC)
48ºC
(54ºC)
When ON
(When OFF)
5200
7200
2–2
AE-XM30GR
9. PUMP DOWN SWITCH
When the PUMP DOWN SWITCH (SW1) is pressed for 5 seconds or
more, the total A/C system will start its TEST RUN automatically and
the compressor frequency will be 55 Hz. When operating only the outdoor unit (cooling 55 Hz fixed mode) To make only the outdoor unit run
in cooling mode, and apply a voltage of 230 V AC to N and 1 on the
terminal board and push the pump down switch. (SW1) (Avoid operating the outdoor unit alone for long periods of time.)
More than
20 min.
Heating
operation
start
10. CONTROL OF COMPRESSOR OR AND EXPANSION VALVE
For 90 seconds after turning on the AC power, the compressor will not
be activated even if indoor units request the compressor to do so. If
the compressor receives a request from one or more indoor units after
90 seconds have passed, it will be turned on and the expansion valve
corresponding to the requesting indoor unit will be opened. When the
indoor unit of a room requests for the cooling operation to the outdoor
unit and it runs responding to the request, requests for the heating
can't be accepted if the indoor units in other rooms send individual
requests. If the indoor unit in another room sends a request for the
heating operation, the operation lamp and timer lamp of the indoor unit
in that room start flashing in turn to inform that the unit is in the standby
mode. If the operation in one room is stopped while the indoor unit in
another room is in the stand-by mode, the operation mode requested
by the indoor unit which is now in the stand-by mode will be accepted.
At this time, the compressor will be temporarily stopped to switch the
four- way valve and restart after 90 seconds. During the cooling or dry
operation, the expansion valve corresponding to the indoor unit that is
not running is closed. Therefore, the refrigerant will not flow into those
units.However,if the heating operation is in progress, it is possible that
it flows into indoor units which are out of operation depending on the
cycle conditions. As a result, the indoor exchanger may be heated up
even if it is not activated. This is not abnormal. When the operations in
all rooms are stopped, the compressor is off and the expansion valves
in all rooms are fully opened.
The outdoor fan is s topped
The operating frequency is as shown in the table below.
The indoor fan is s topped.
All expansion valve are open.
for 5 minutes 3900 rpm
after that 3700 rpm
4) Defrost stop
When defrosting time exceeds 10 minutes When the temperature
of the outdoor heat exchanger rises above approximately 15C
Defrost stop is determined by either of the above conditions, and
the compressor is s topped. At the same time, the outdoor fan go
ON. The compressor is reactivated in the heating cycle 1 minutes
after it was stopped, and normal control resumes.
Defrosting begins during heating if the conditions for compressor
operation time and outdoor heat exchanger temperature are met.
When defrosting begins, the indoor and outdoor fans stop. Defrosting stops when the temperature of the outdoor heat exchanger
goes above approximately 15C or defrosting time exceeds 10 minutes.
Defrost
mask time
Heating
begins
Defrosting
Max. 10 min.
Defrosting
Defrosting
Max. 10 min. Max. 10 min.
When defrosting begins, the compressor stops. Approximately 1
minutes later, the compressor reactivates in the refrigeration cycle,
and the outdoor heat exchanger is defrosted. Each mode is as follows:
1) Overview
Defrost
mask time
More than
20 min.
3) During defrosting
11. DEFROST OPERATION
Defrost
mask time
More than
20 min.
Defrosting
Max. 10 min.
2) Defrosting
If the compressor operation time is more than 20 minutes in the
heating mode and the outdoor air temperature and outdoor heat
exchange temperature satisfy the defrosting conditions, the
defrosting operation is started. When the defrosting operation is
started, the indoor fan s tarts to run intermittently. When the outdoor
heat exchanger temperature reaches approx. 15C or above or
when the defrosting time exceeds 10minutes, the defrosting operation is quit.
2–3
CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES
[1] PROTECTIVE FUNCTIONS AND OPERATIONS
NO.
Function
Description
Compressor is stopped if a current approximately 25A or more flows in the power transistor module.
Lowers the operating frequency if the compressor AC current exceeds set value(19.3).
Stops the compressor if the current exceeds
at minimum frequency.
Lowers the operating frequency if the temperature of the compressor thermistor (TH1)
rises above 108C. Compressor is stopped if
the thermistor stays above 108C for 2 minutes at minimum frequency.
Operation
Detection time
Restart condition
During compressor operation
Automatically restarts after
safety time (180 seconds)
4 times
Yes
Yes
During compressor operation
Automatically restarts after
safety time (180 seconds)
4 times
Yes
Yes
During compressor operation
Automatically restarts after
safety time (180 seconds)
No limit
No
No
1
DC over current
2
AC over current
3
Compressor overheat prevention control
4
Compressor high
temperature error
Compressor is stopped if the compressor
thermistor is above 113C (Or when TH1
shorts)
During compressor operation
Automatically restarts when
thermistor (TH1) temperature falls below 99C
(approximately 30 minutes)
4 times
Yes
Yes
5
Outdoor heat
exchanger overheat
prevention control
Lowers the operating frequency if the temperature of the outdoor heat exchanger rises
above 57C during cooling. Stops the compressor if thetemperature stays above 57C
for 2 minutes at minimum frequency
During compressor operation
Automatically restarts after
safety time (180 seconds)
No limit
No
No
Thermistor short
Compressor ia stopped, if heat exchanger or
outdoor thermistor shorts.Close the expansion valve of the corresponding room, if
some suction thermistor shorts.
When the roomis activatedturns ON andthe
compressorstarts.
Operation OFF
1 time
Yes
Yes
When the room
turns ON and the
compressor
starts.
Operation OFF
1 time
Yes
Yes
During compressor operation
Automatically re-starts after
safety time.(180 sec.)
4 times
Yes
Yes
During operation
Automatically re-starts as
soon as the serial communication becomes possible.
No limit
Yes
Yes
6
Compressor is stopped, if compressor or
heat exchanger or outdoor thermistor opens.
Close the expansion valve of the corresponding room, if some suction thermistor
shorts. opens.
Compressor is stopped, if the oper-ating frequency is above 70Hz and the compressor
current is below 0.8A.
INDOOR
If open, while timer LED blinks, op-eration is
continued. If short, operation is continued.
OUTDOORC
loses the expansion valve of the corresponding room if the outdoor unit does not
receive a serial signal from one or more
indoor unit for 30 seconds.
Compressor is stopped, if the out-door unit
does not receive a serial signal from all
indoor units.
7
Thermistor open
8
AC abnormal current
9
Serial signal error
10
Miswiring check
error
Compressor is stopped, and miswiring check
operation ends.
During miswiring
operation
Miswiring check op-eration
will not re-start automatically.
4 times
Yes
Yes
11
Indoor heat
exchanger overheat
prevention control
Lowers the operating frequency if the temperature of any of indoor heat exchanger
rises high temper-ature during heating.
Stops the compressor if the tem-perature
srays high for 2 minutes at minumum frequency.
During compressor operation
Automatically re-starts after
safety time.(180 sec.)
No limit
No
No
12
Power factor module (Active filter)
error
When a power factor module errorinput is
detected.
During compressor operation
Automatically re-starts after
safety time.(180 sec.)
4 times
Yes
Yes
13
DC Compressor
rotatione rror
In the case that the feed back signal from the
compressor is not input orabnormal.
During compresso roperation
Automatically re-starts after
safety time.(180 sec.)
8 times
Yes
Yes
3–1
NO.
14
Function
IPM overheat prevention control.
IPM high temperature error
Description
Lowers the operating frequency if the temperature of IPM rises high temperature.
Stops the compressor if the tem-perature
srays high for 2 minuteS at minumum frequency.
Operation
Detection time
Restart condition
During compressor operation
Automatically restarts after
safety time.(180 sec.)
No limit
No
No
[2] TROUBLESHOOTING GUIDE
1. SELF-DIAGNOS IS FUNCTION AND DIS PLAY MODE
1) To call out the content of the self-diagnosis memory, hold down the emergency operation button for more than five seconds when the indoor unit is
not operating.
a) According to the content of the self-diagnosis memory, the Operation LED (main category) and the Plasmacluster Ion LEDs (sub-category)
flash in sync with the Timer LE D on the indoor unit.
b) In the event a complete shutdown occurs due to a malfunction, the Operation LED (red), Timer LED (yellow), Plasmacluster Ion LED (blue),
and Plasmacluster Ion LED (green) flash to indicate the general information of the generated malfunction.
c) If the power cord is unplugged from the AC outlet or the circuit breaker is turned off, the self-diagnose is memory loses the stored data.
2) Display of detailed self-diagnosis result with main category and sub-category indications When malfunction information is called out, the main category and sub-category of the self-diagnose is result are indicated by the Operation, Timer, and Plasmacluster Ion LEDs on the indoor unit.
Main category
*1: Example of self-diagnosis result displayed on indoor unit: Suction thermistor open-circuit error
Basic flashing cycle due to error
Timer LED [yellow]
1 sec 1 sec 1 sec
Malfunction No.
5 sec
ON
OFF
Figures in ( ) indicate numbers (binary notation) assigned based on the flashing sequence.
Operation LED [red]
ON
OFF
Plasmacluster Ion LED [blue]
Flashing for main category indication
Flashing for sub-category indication
*2: The self-diagnosis display function of the outdoor unit indicates the error information by flashing LED1 on the
outdoor unit according to the content of self-diagnosis.
The self-diagnosis display function of the outdoor unit is active only for about 3 to 10 minutes after self-diagnosis is
performed during operation, and the display returns to normal condition after this display period.
The content of self-diagnosis cannot be called out by the self-diagnosis display function of the outdoor unit.
Example of self-diagnosis display on outdoor unit : Compressor high-temperature abnormality
ON
OFF
0.5 sec 0.5 sec 0.5 sec 0.5 sec 0.5 sec 0.5 sec 0.5 sec 0.5 sec 0.5 sec
3–2
0.5 sec 0.5 sec 0.5 sec 0.5 sec
Sub-category
3–3
5 time
6 time
7 time
8 time
11 time
Indoor/outdoor
units in
complete
shutdown
Indoor/outdoor
units in
complete
shutdown
Indoor/outdoor
units in
complete
shutdown
Indoor/outdoor
units in
complete
shutdown
2 time
1 time
Normal
flashing
-2
-4
-5
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
-2
-3
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
11 -0
8 -0
-1
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
7 -0
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
6 -0
-1
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
-5
5 -0
-2
-3
-4
-1
2 -0
-1
-2
-3
0 -0
1 -0
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
11
8
3
7
6
0
5
0
0
0
0
2
0
1
Main
Wall(Grill)
Outdoor unit
DC Fan
Abnormal wire
check
Outdoor unit
AC Current
Outdoor unit
DC Current
_
Inspection location/method
_
Remedy
(1)Check the outdoor unit air outlet for blockage.
(2)Check if the power supply voltage is 90 V or higher at full power.
(3)Check the pipe connections for refrigerant leaks.
(4)Measure resistance of the outdoor unit compressor thermistor.
(TH1:Approx.53 k at 25 C)
(5)Check the expansion valve for proper operation.
(1)Change the heat-sink thermistor.
Outdoor unit DC fan rotation error
(AE-XM30FR)
Abnormal wire check error
AC current deficiency error
AC maximum current error
AC current error when OFF
AC overcurrent error
DC overcurrent error
Thermistor Unit A - D thermistor opencircuit error
Discharge thermistor open-circuit error
Suction thermistor open circuit error
_
(1)Check connector CN3A of the outdoor unit DC fan motor for secure installation.
(2)Check the outdoor unit fan motor for proper rotation.
(3)Check fuse FUSE3.
(4)Outdoor unit control PCB
(1)Check the expansion valve. (unit A - D)
(2)Are four expansion valves connected by mistake
(3)Check the wiring between units.
(1)Correct the installation.
(2)Replace the outdoor unit fan motor.
(3)Replace the outdoor unit control PCB assembly.
(4)Replace the outdoor unit control PCB assembly.
(1)Replace the outdoor control board assembly.
(2)Reattach
(3)Check the wiring between units.
(3)Correct refrigerant clogs.
(Stop valve,pipe,expansion valve)
(1)Replace the outdoor unit control PCB assembly.
(2)Charge the specified amount of refrigerant.
(1)Ensure unobstructed air flow from the outdoor unit air outlet.
(2)Check the outdoor unit fan motor.
(1)Ensure unobstructed air flow from the outdoor unit air outlet.
(2)Check the outdoor unit fan motor.
(1)Replace the outdoor unit control PCB assembly.
(2)Charge the specified amount of refrigerant.
(3)Correct refrigerant clogs.
(Stop valve,pipe,expansion valve)
(1)Replace the outdoor IPM PWB
(1)Ensure unobstructed air flow from the outdoor unit air outlet.
(2)Check the outdoor unit fan motor.
(1)Replace the outdoor unit control PCB assembly.
(2)Correct the installation (tighten the screws).
Apply silicon grease.
(3)Replace the outdoor unit fan motor.
(4)Replace the outdoor unit control PCB assembly.
(5)Replace the compressor.
(1)IPM continuity check
(1)Ensure unobstructed air flow from the outdoor unit air outlet.
(2)Check the outdoor unit fan motor.
(1)IPM continuity check
(2)Check the IPM and heat sink for secure installation.
(3)Check the outdoor unit fan motor for proper rotation.
(4)No abnormality found in above inspections (1)through (3).
(5)No abnormality found in above inspections (1)through (4).
(1)Check connector CN8A and CN8C of the outdoor unit thermistor for secure (1)Correct the installation.
(2)Replace the outdoor unit thermistor assembly.
(3)Replace the outdoor unit thermistor assembly.
(4)Replace the outdoor unit control PCB assembly.
installation.
(2)Measure resistance of outdoor thermistors TH1~4,6~9.
(3)Check the lead wires of thermistors TH1~4,6~9 on the outdoor unit
control PCB for open-circuit.
(4)No abnormality found in above inspections (1)through (3).
(1)Measure resistance of the heat-sink thermistor.(CN8B)
IPM high temperature error
_
(Temporary stop for parts protection)
Temporary stop due to IPM overheat *3
_
Temporary stop due to indoor unit heat (Temporary stop for cycle protection)
exchanger overheat *3
_
(1)Ensure unobstructed air flow from the outdoor unit air outlet.
(2)Connect power supply of proper voltage.
(3)Charge the specified amount of refrigerant.
(4)Replace the outdoor unit compressor thermistor assembly.
(5)Replace the expansion valve coil,expansion valve or outdoor unit control PCB
assembly.
Temporary stop due to out door unit
heat exchanger overheat *3
(Temporary stop for cycle protection)
Temporary stop due to compressor dis- (Temporary stop for cycle protection)
charge overheat *3
Suction thermistor open circuit error
Compressor high temperature error
Thermistor Unit A - D thermistor shortcircuit error
(1)Replace the outdoor unit thermistor assembly.
Heat exchanger thermistor short circuit (1)Measure resistance of the outdoor unit thermistors.
error
(TH2~4,6~9 : Approx.4.4 k at 25 C)
(2)Replace the outdoor unit thermistor assembly.
Outdoor temperaturethermistor short- (2)Check the lead wire of the outdoor unit thermistor for torn sheath and short- (3)Replace the outdoor unit control PCB assembly.
circuit.
circuit error
(3)No abnormality found in above inspections (1)and (2).
Suction thermistor short-circuit error
Normal
Heat exchanger thermistor open-circuit
Outdoor unit
error
thermistor opencircuit
Outdoor temperature thermistor opencircuit error
Cycle
temperature
Outdoor unit
thermistor
short-circuit
Sub category
Content of diagnosis
Main category
: Flashes 3 times in 0.2-sec intervals
Indication on indoor unit
: 1sec ON / 1sec OFF X : OFF
Indication by
Wall
Floor / ceiling
(Panel)
LED1 on
outdoor unit Lighting pattern at the time of timer lamp lighting
*2
Main Sub
X for 5 seconds
Indoor/outdoor
units in
complete
shutdown
Indoor unit in
operation
Outdoor unit in
temporary stop
Indoor/outdoor
units in
complete
shutdown
Indoor/outdoor
units in
operation
Indoor/outdoor
units
incomplete
shutdown
Status of
indoor/outdoor
units
Flashes in 1-sec intervals (normal)
3–4
X
Indoor/outdoor
units in
operation
Indoor/outdoor
units in
operation
X
X
Indoor/outdoor
units in
complete
shutdown
Indoor unit in
operation
Outdoor unit in
complete
shutdown
X
14 time
Indoor/outdoor
units in
complete
shutdown
Indoor unit in
operation
Outdoor unit in
complete
shutdown
13 time
20 -0 20
30 -0 30
Operation lamp(RED)
Cluster lamp(BLUE)
19 -0 19
-1
18 -0 18
17 -0 17
-1
14 -0 14
-1
13 -0 13
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Operation lamp(RED)
Cluster lamp(BLUE)
Indication by
Wall
Floor / ceiling
(Panel) Wall(Grill)
LED1 on
outdoor unit Lighting pattern at the time of timer lamp lighting
*2
Main Sub
Main
X for 5 seconds
Indoor/outdoor
units in
complete
shutdown
Status of
indoor/outdoor
units
EEPROM data error
(1)Check connector CN2 and CN10.
(1)Check the indoor fan motor for proper rotating operation.
(Check fan lock.)
(2)Check the lead wire of the indoor fan motor for open-circuit.
(3)Check connector of the indoor unit fan motor for secure installation.
(4)No abnormality found in above inspections (1)through (3).
(EEPROM read data error)
(1)Check the wires between units.
Serial erroneous wiring
Indoor unit fan error
(1)Check the wires between units.
Serial short-circuit
Outdoor unit does not turn on due to (1)Check the wires between units.
(2)Check the outdoor unit fuse.
erroneous wiring
(3)Check 15-V,13-V and 5-V voltages on the PCB.
Check resistance between IPM terminals.
(4)Check pins No.5 and 8 of connector CN3A of the outdoor
unit fan motor for short-circuit.
(5)Outdoor unit control PCB
(1)Check the wires between units.
(2)Check voltage between N and 1 the indoor/outdoor unit terminal boards.
(1)Check the clock for proper inputt
Clock error
Serial open-circuit
(1)Check the AC power supply voltage for fluctuation.
(2)No abnormality found in above inspection (1).
(1)Check the colors (red,white,orange)of the compressor cords
for proper connection.(PCB side,compressor side)
(2)Check if the IPM terminal resistance values are uniform.
(3)No abnormality found in above inspections (1)and (2).
(4)No abnormality found in above inspections (1)through (3).
Inspection location/method
Active filter overvoltage error
Drain pump unit Drain pump unit error
Indoor unit
control PCB
Indoor unit fan
Wires between
units
Wires between
units
Outdoor unit
active filter
Compressor rotation error
DC compressor Compressor startup error
Sub category
Content of diagnosis
Main category
: Flashes 3 times in 0.2-sec intervals
Indication on indoor unit
Flashes in 1-sec intervals (normal) : 1sec ON / 1sec OFF X : OFF
(1)Replace the Drain pump unit unit.
(2)Re-insertion of CN2 and CN10.
(1)Replace the indoor unit control PCB.
(1)Replace the indoor fan motor.
(2)Replace the indoor fan motor.
(3)Correct the installation of CN3 of the indoor fan motor.
(4)Replace the indoor unit control PCB.
(1)Correct the wiring.
(1)Correct the wiring.
(1)Correct the wiring.
(2)Replace the fuse/outdoor unit control PCB assembly.
(3)Replace the outdoor unit control PCB assembly.
(4)Replace the outdoor unit fan motor.
(5)Replace the outdoor unit control PCB board.
(1)Connect stable power supply.
(2)Replace the outdoor unit control PCB assembly.
(1)Replace the outdoor unit control PCB assembly.
(1)Connect stable power supply.
(2)Replace the outdoor unit control PCB assembly.
(1)Correct the installation.
(U:Red,V:White,W:Orange)
(2)Replace the outdoor unit control PCB assembly.
(3)Replace the outdoor unit control PCB assembly.
(4)Replace the compressor.
Remedy
Figure 1 Temperature properties of indoor thermistors
k
100
80
Heat exchange thermistor
TH2 (Orange), TH3 (Black)
25ºC resistance 4.431 k
Signal
Room temperature
TH1
Yellow
thermistor TH1 (CN6 3 - 4 )
Heat exchange
TH2
Orange
Heat exchange
Pipe temperature
TH3
Black
Color
thermistor TH2 (CN6 1 - 2 )
Pipe temperature
To measure the resistance, first remove
the soldering as shown at right.
60
Resistance
Room temperature
Thermistor
thermistor TH3 (CN6 5 - 6 )
CN6
Room temperature
thermistor TH1 (Yellow)
25ºC resistance 10 k
40
1
6
20
Tester
0
-10
0
10
20
30
40
CAUTION: when attaching or removing the board
When operating only the outdoor unit (cooling 55 Hz fixed mode) To make only the outdoor unit run in cooling mode, and apply a voltage
of 220 ~ 240V AC to 1 and N on the terminal board and push the pump down switch (SW1).
(Avoid operating the outdoor unit alone for long periods of time.)
Figure 2 Temperature properties of outdoor thermistors
TH2 : Heat exchanger pipe thermistor (CN8A 3 - 4 )
TH3 : Outdoor temp. thermistor (CN8A 5 - 6 )
TH4 : Suction thermistor (CN8A 7 - 8 )
TH6 : Thermistor unit A (CN8C 1 - 2 )
TH7 : Thermistor unit B (CN8C 3 - 4 )
TH8 : Thermistor unit C (CN8C 5 - 6 )
TH9 : Thermistor unit D (CN8C 7 - 8 )
1
1
8
Connector
CN8A
8
Connector
CN8C
(MIH301C)
500k
40k
Resistance (
Resistance (
)
)
TH1 compressor thermistor
(CN8A 1 - 2 )
400k
25ºC resistance
45 k
300k
200k
5.78k
3.06k
4.17k 2.28k
1.72k
100k
0
20
60
20k
10k
0
-20
0ºC resistance
14.5 k
25ºC resistance
4.431 k
TH2 - TH4
TH6 - TH9
30k
0
80 100 120
-20
Temperature (ºC)
Thermistor
Compressor thermistor
Heat exchanger pipe thermistor
No.
TH1
TH2
Connector
CN8A
CN8A
0
20
40
Temperature (ºC)
Color
Red
Orange
Connector pin
No. 1 to 2
No. 3 to 4
3–5
60
Thermistor
Outdoor temp. thermistor
Suction thermistor
Thermistor unit A (suction)
Thermistor unit B (suction)
Thermistor unit C (suction)
Thermistor unit D (suction)
No.
TH3
TH4
TH6
TH7
TH8
TH9
Connector
CN8A
CN8A
CN8C
CN8C
CN8C
CN8C
Color
Green
Black
Blue
White
Brown
Yellow
Connector pin
No. 5 to 6
No. 7 to 8
No. 1 to 2
No. 3 to 4
No. 5 to 6
No. 7 to 8
Figure 3 Temperature properties of heatsink thermistor
500
Resistance (k )
400
Thermistor
Signal
Color
Heatsink
CN8B
Black
To measure the resistance, first remove
the connector as shown at right.
300
1
3
Heatsink thermistor
TH5 (black)
25ºC resistance 50k
200
6.14k
100
Tester
3.25k
12.3k
0
-20
0
20
40
60
Temperature (ºC)
80
100
2. How to distinguish the defective parts
1. When all rooms are not cooled
Are the timer lamps of the indoor units in all rooms flashing ?
Yes
No
Press the OPERATION button
to start operating the air-conditioner. (One-room operation ON)
(Set the cooling mode to 18
͠㧕
Yes
Is the compressor of the outdoor
unit operating ?
No
The cooling cycle is abnormal.
Are the timer lamps of the indoor
units in all rooms flashing ?
Yes
Check the failure symptom with
the failure diagnosis mode.
No
Check the pressure.
Check that the power between
the terminal board " N " and " 1 "
of the indoor unit is AC 230V,
50Hz.
Repair the wiring between the
units.
3–6
TO
A
(Check the failure with
the outdoor unit.)
3–7
Replace the
thermistor.
No
Is the resistance
value of the thermistor for the compressor (TH1), heat Yes
ex-changer (TH2)
or outdoor temperature (TH3) or suction (TH4, TH6-9)
correct?
Open circuit of the
outdoor thermistor
A
No
Check the voltage
(15V).
No
Yes
Replace the fan motor.
Yes
Connect CN3
Inspect the compressor, heat exchanger
and piping.
Is the resistance value
between 5 and 8
of fan motor 0?
Check the FUSE 5
Yes
AC overcurrent
The cycle is abnormal.
Yes
Is CN3A connected ? No
No
Is the outdoor fan
motor operating ?
Overheat of the compressor
Replace the Compressor.
The compressor is abnormal.
Replace the IPM PWB
Yes
Power module PWB
(IPM) abnormality
Replace the IPM PWB.
Yes
No
Connect CN6.
Check the voltage (5V).
Replace the current
transformer
Yes
Is CN6 connected ?
Yes
Are 4 lamps
switched off ?
Open circuit of serial isgnal line
Short circuit of serial ignal
s line
Is the resistance value of the No
winding in the current transformer ? (720 )
Fix the IPM PWB with
screws securely.
Yes
Replace the outdoor control PWB.
No
Abnormal AC current
Is the winding of the current
transformer broken ?
Is each of the resistance values among
the terminals of the
Yes
IPM PWB 0 ?
P - U, N - U
P - V, N - V
P - W, N - W
No
Is the IPM PWB in a
state of floating from
the heat sink ?
Connect CN16
No
Is each of the resistance
values among the terminals of the IPM PWB 0 ?
P - U, N - U
No
P - V, N - V
P - W, N - W
Check the voltage
(18V).
Yes
No
Is CN16 connected ?
Rotation error of
the compressor
Fix the Power factor
module with screws
secuerly
Yes
No
Replace the Power
factor module (AF1)
Is the resistance value among Yes
the terminal of the Power factor module (AF1) 0 ?
No
Is the Power factor module in a
state of flaoting from the heatsink?
Power factor module (AF1) error
Repair the wiring
between the units.
No
3–8
Replace the indoor
control PWB.
Yes
Check that the power
between the terminal
board "N" and "1" of the
indoor unit is AC 230V.
No
Is the timer lamp of the
indoor unit in the room
not cooled flashing ?
Press the OPERATION
button to start operating
the air-conditioner.
(Set the cooling mode
to 18ûC.)
No
Is the timer lamp of the
indoor unit in the room
not cooled flashing ?
Yes
Yes
Replace the thermistor.
No
Replace the outdoor control PWB
or the expansion valve (UNIT A)
or the expansion valve (UNIT B)
or the expansion valve (UNIT C)
or the expansion valve (UNIT D)
Is the resistance value of the thermistor for UNIT A (TH6), UNIT B Yes
(TH7), UNIT C (TH8) or UNIT D
(TH9)
Short circuit of the thermistor error
Open circuit of the thermistor error
Check the failure
symptom with the failure
diagnosis mode.
Yes
No
Repair the wiring between
the units.
Is the wiring between the
units connected by mistake
or broken ?
Open circuit of serial signal line
Short circuit of serial signal line
Replace the indoor control PWB.
Replace the indoor fan motor.
The thermal fuse is blown.
The motor is locked.
Yes
Is the resistance value of the No
winding in the fan motor ?
(Between 1 and 3 of CN1)
Abnormal fan motor of
indoor unit
2. When one room is not cooled (other rooms are cooled)
3. When all rooms are not heated
Does the air get cooler in the Yes
cooling operation mode?
No
Refer to 1 All rooms are
not cooled.
Press the ON switch on the
remote control to run the air
conditioner.
Set the temperature to 32
͠
in the heating mode and
start operation.
No
Yes
Is the outdoor compressor
running?
No
Yes
To A
Check the four-way valve.
Has the cycle been switched?
No
The heating cycle is normal.
Is AC230V applied between
the connector(CN4) 1 and 3
of the 4-way valve ?
Pressure check
Yes
1-2 AE-XM30FR;
Replace the 4-way valve.
3–9
AE-XM30GR
CHAPTER 4. REFRIGERATION CYCLE
AE-XM30GR
Service Manual
[1] REFRIGERATION SYCLE
1. [7 / 9/ 12] class indoor unit is connected UNITA
UNIT D
(3)
Heat exchanger
Expansion valve D
STOP valve (Liquid)
UNIT B
(3)
Heat exchanger
Expansion valve C
Expansion valve B
(4)
Heat exchanger
Heat exchanger
(2)
4-way valve
(3)
Accumulator
UNIT C
Compressor
(1)
Expansion valve A
UNIT A
(3)
Heat exchanger
STOP valve (Gas)
INDOOR UNIT
OUTDOOR UNIT (AE-XM30GR)
2. [18] class indoor unit is connected UNITA
Expansion valve D
STOP valve (Liquid)
UNIT B
(3)
Heat exchanger
Expansion valve C
Expansion valve B
(4)
Expansion valve A
UNIT A
(3)
Heat exchanger
STOP valve (Gas)
INDOOR UNIT
OUTDOOR UNIT (AE-XM30GR)
4–1
Heat exchanger
Heat exchanger
(2)
4-way valve
(3)
Accumulator
UNIT C
Compressor
(1)
AE-XM30GR
UNIT D
UNIT C
UNIT B
UNIT A
INDOOR UNIT
OUTDOOR UNIT (AE-XM30GR)
Cooling
heating
3. Cycle temperature and pressure in stop valve (AE-XM30GR)
Running unit
AY-XPM9FR &
AY-XPM7FR &
AY-XPM7FR &
AY-XPM7FR
(4 units)
GS-XPM18FGR
no operation mode
(1)
(2)
(3)
(4)
stop valve (gas side)
Frequency
(1)
(2)
(3)
(4)
stop valve pressure
Frequency
Frequency
(1)
Cool (MAX)
94
40
11
13
0.92MPa(abs)
80Hz
92
37
9
10
Cool (Test run)
80
36
13
16
1.1MPa(abs)
50Hz
77
36
11
16
Heat (MAX)
77
15
29
-3
2.53MPa(abs)
90Hz
91
19
38
3
Heat (Test run)
55
6
25
6
1.93MPa(abs)
38Hz
70
8
34
6
0.83MPa(abs)
1.03.MPa(abs)
3.58MPa(abs)
2.57MPa(abs)
62Hz
83
35Hz
72Hz
38Hz
76
82
62
(2)
36
35
13
6
(3)
10
13
(4)
11
stop valve pressure Frequency
Frequency
(1)
(2)
(3)
(4)
stop valve pressure Frequency
Frequency
(1)
(2)
(3)
(4)
stop valve pressure Frequency
Frequency
0.86MPa (abs)
41Hz
78
36
9
13
0.94MPa (abs)
31Hz
74
35
9
16
0.99MPa (abs)
24Hz
19
1.07MPa (abs)
43
4
3.15MPa (abs)
7
2.37MPa (abs)
23Hz
69
35
11
19
1.11.MPa (abs)
30Hz
69
35
11
19
1.09.MPa (abs)
17Hz
50Hz
83
12
36
5
3.20MPa (abs)
45Hz
75
10
32
6
3.00MPa (abs)
35Hz
25Hz
58
6
24
7
2.21MPa (abs)
20Hz
59
6
24
7
2.24MPa (abs)
20Hz
AY-XPM12FR
(1 unit)
AY-XPM9FR
(1 unit)
AY-XPM7FR
(1 unit)
7
Standard conditions (AE-XM30GR)
Cooling
Heating
indoor side
Dry-bulb temp. (C)
Relative humidity (%)
27
47
20
–
4–2
Outdoor side
Dry-bulb temp. (C)
Relative humidly (%)
35
40
7
87
AE-XM30GR
4. PERFORMANCE CURVES
At Heating for AY-XPM9FR (for AE-XM30GR)
NOTE: Total cooling capacity and total input with 4 units running.
(Running frequency: 70HZ)
3200
2600
16
2600
16
2400
15
2400
15
14
13
12
13
12
Coolingcapacity(kW)
14
9.0
8.5
8.0
8.5
8.0
7.5
7.0
24
7.5
7 .0
24
9.0
26
26
28
30
32
34
36
38
40
42
44
32
34
36
38
40
42
44
At Cooling for AY-XPM7FR (for AE-XM30GR)
At Cooling for AY-XPM9FR (for AE-XM30GR)
(Running frequency: 75HZ)
2600
Input(W)
(Running frequency: 75HZ)
2600
Input(W)
30
Outside air temp. (ºC)
Outside air temp.(ºC)
2400
2400
2200
2000
2200
42
1800
Outlet air temp.(ºC)
2000
40
38
36
40
38
36
34
Heatingcapacity(kW)
42
1800
34
Heating capacity(kW)
28
10.0
32
9.0
30
8.0
Outlet air temp. (ºC)
Cooling capacity(kW)
2800
2800
Outlet air temp.(ºC)
Input(W)
3000
3000
Outlet air temp. (ºC)
Input(W)
(Running frequency: 70HZ)
3200
28
7.0
10.0
32
9.0
30
8.0
28
7.0
-6
-4
-2
0
2
4
6
8
10
12
Outside air temp. (ºC)
-6
-4
-2
0
2
4
6
8
10
12
At Heating for AY-XPM7FR (for AE-XM30GR)
Outside air temp.(ºC)
[2] REFRIGERANT PIPE INSTALLATION WORKS
1. Piping
Max. piping length A ------------------ 20m
2. Air-removing
Use an adapter for preventing vacuum pump oil from flowing back to
the gauge manifold hose. ON/OFF operation of the vacuum pump
should be made by the adapter switch.
INDOOR UNIT
Max. total piping length of all unit --- 50m
Max. level difference B -------------- 10m
When the outdoor unit is placed at a
higher level than the indoor units, provide
a trap near the hose’s lead-in port.
1) Remove both valve shaft caps of the stop valves.
A
2) Remove the service port cap of the stop valve (gas side).
OUTDOOR
UNIT
3) Connect the gauge manifold hose to the service port and the vacuum pump. Be sure that the hose end to be connected to the service port has a valve core pusher.
B
4) Open the gauge manifold valve and operate the vacuum pump for
10-15 minutes. Make sure the compound gauge reads -0.1MPa (76cmHg).
B
5) Close the gauge manifold valve.
6) Turn off the vacuum pump.
7) Fully open the stop valve (liquid side) with hexagon socket screw
key. Turn all the way up to contact.
TRAP
4–3
AE-XM30GR
4. MISWIRING CHECK
8) Fully open the stop valve (gas side) with hexagon socket screw
key. Turn all the way up to contact.
Miswiring check must be performed after installation, reinstallation and
service. This multi-type air conditioner is designed with a WIRE
CHECK SWITCH on the outdoor unit, and miswiring of unit-to-unit wiring will be self-corrected by microcomputer. Miswiring check may not
be performed when the outdoor temperature is below 5.
9) Disconnect the gauge manifold hose from the service port.
10)Replace the service port cap and both valve shaft caps tightly. Turn
until the torque suddenly increases. Now tighten a 1/6-turn more.
NOTE: *
*
Use a gauge manifold and hoses exclusive for R410A.
1) Complete the unit-to-unit wiring/piping and perform the air removing of the pipes. Turn the electrical circuit breaker ON. Before turning the circuit breaker ON, make sure no one is working on the
indoor units installation. Electrical shock or injury may occur.
After air removal, check the tube connections for gas leak
using a leakage detector or soapy water. Regarding leakage detector, use high-sensitivity type designed specially
for R410A.
2) Check that all LED (LED1, 2, 3, 4) on the display board unit are
flashing synchronously in a slow (one flash per second) cycle. If
either one or more of all LED is/are kept lighted on, check and correct the wrong wirings among, N, 1, 2, terminals so that all LED will
flash slowly, showing normal condition.
Gauge manifold
Compound
gauge
Lo
Hi
Hose
3) Press the WIRE CHECK SWITCH (SW2) on the display board unit
for 5 seconds or more. The flashing of all LED will change. Mis-wiring (mis-piping) check will start and the indoor and outdoor units
will start operating. (The red operation lamp on the indoor unit will
flash, and three BEEP will be emitted.) Miswiring of unit-to-unit wiring will be self-corrected.
Service port
Stop valve
(gas side)
Stop valve
(liquid side)
Service port
Vacuume pump adapter
4) Wrong piping works cannot be corrected, and will be detected as
an error. When an error is detected during checking, all LED will
show triple flash for eight times. The indoor and outdoor operation
will stop. Turn the circuit breaker OFF and check and correct the
miswiring (mispiping)*. After correction, return to step 1 and repeat
the miswiring (mispiping) check again. If error is still detected, or
other types of LED signal should be indicated, please contact a service technician. (Refer to wiring diagram attached inside the outdoor unit cabinet for self diagnosis signal.)
Hexagon socket screw key
4mm
Valve shaft cap
OPEN
5) All LED (LED1, 2, 3, 4) will flash synchronously in a slow (one flash
per second) cycle when miswiring (mispiping) check is completed
with no error detection (3–6 minutes), and the operation of indoor
and outdoor units will stop. (The red operation lamp flashing on the
indoor unit will go off.)
3. Pump down
(Pump down is adopted in the case of unit removal for reinstallation,
abandonment, repair etc.) Pump down is to collect the refrigerant into
the outdoor unit by control of the stop valves and the compressor.
6) Place the control box cover back in the reverse order.
1) Turn the circuit breaker on.
*Correction points on error detection
2) Check that all LED (LED1, 2, 3, 4) on the display board unit are
flashing synchronously in a slow (one flash per second) cycle.
a) Are all piping the total multi air conditioner system connected?
b) Are the stop valves open?
3) Stop the air conditioner operation.
4) Remove both valve shaft caps of the stop valves.
5) Press the PUMP DOWN SWITCH (SW1) on the display board unit
for 5 seconds or more. The indoor/outdoor unit will start operation
in the pump down mode. (the OPERATION lamp on the indoor unit
will flash and three BEEP will be emitted.)
6) After 5 – 10 minutes, fully close the stop valve (liquid side) by turning the hexagon socket screw key clockwise.
7) After 2 – 3 minutes, immediately close the stop valve (gas side)
fully.
9) Replace the service port cap and both valve shaft caps tightly.
NOTE: Wait more than 90 seconds after finishing pump down, and
turn off the circuit breaker off.
UNIT A
LED 2
LED 1
LED 4
LED 3
UNIT D
UNIT C
SW 2
WIRE CHECK
UNIT A
LED 2
LED 1
LED 4
LED 3
UNIT D
UNIT C
SW 2
SW 1
WIRE CHECK
PUMP DOWN
AE-XM30GR
8) Press the PUMP DOWN SWITCH (SW1) on the display board unit
for 5 seconds or more. The operation of indoor/outdoor unit will
stop.
UNIT B
UNIT B
SW 1
PUMP DOWN
AE-XM30GR
4–4
AE-XM30GR
Service
CHAPTER 5. DISASSEMBLING PROCEDURE
AE-XM30GR
Manual
[1] OUTDOOR UNIT
1. PROCEDURE
4. Remove the 6 screws fixing the rear guard.
1. Remove the 5 screws fixing the front panel R and slide the front
panel R down.
5. Remove the 11 screws fixing the side cover R.
2. Remove the 10 screws fixing the top cover.
3. Remove the 6 screws fixing the front panel L.
6. Remove the 6 screws fixing the side cabinet L.
5–1
AE-XM30GR
12.Remove the terminal cover and disconnect 3 terminals.
7. Cut the insulators.
8. Remove the 2 screws fixing the control box cover.
CAUTION: Discharge electrolytic capacitor before touching this capacitor or other components or wirings.
Screws
Cut
NOTE: Caution to the connectors' position when reinstalling.
9. Cut the wire fixing bands (3 points). Disconnect the 7 connectors.
Fan motor / Reverse valve Thermistor/ Expansion valve
White (C)
Thermistor (Red)
Compressor
Red (S)
Orange (R)
13.Remove the 5 screws fixing the control box assembly.
Cut (3 points)
10.Disconnect the 2 terminals.
14.Cut the 2 insulator.
Cut
11.Remove the compressor cover.
Compressor cover
5–2
AE-XM30GR
15..Remove the 3 screws fixing the bulkhead.
17.Remove the 1 nut fixing the propeller fan.
L oos e
18.remove the 2 screws fixing the motor angle.
19.Cut the fixing bands.
16.Remove the 3 screws fixing the active coil.
5–3
AE-XM30GR
20.Remove the 4 screws fixing the fan motor.
B lack
2. Position of the thermistors
NOTE: Caution to the position when reinstalling.
Green
Y ellow
B rown
Orange
White
B lue
5–4
AE-XM30GR
3. How to disassemble the control box assembly
1. Remove the 4 screws fixing the PWB.
2. Unlock the spacer's lock.
FC4
FC9
The position of setting Ferrite core (FC1 – FC12)
FC10
FC12
FC11
FC6
FC8
FC7
FC5
FC1
FC2
FC3
5–5
AE-XM30GR
4. Mounting position of thermistors and expansion valves
Mounting position of thermistors and expansion valves are shown below.
Thermistor
•
Check the cord color of thermistor before mounting.
•
Thermistor Suction, UNIT A, UNIT B, UNIT C and UNIT D are mounted on GAS side pipes.
•
Thermistor Heat exchanger is mounted on LIQUID side pipe.
Expansion valve
•
Check the labels before connecting to the Control Board Unit.
CAUTION: Mismounting and misconnecting will cause error or failure.
5–6
AE-XM30GR
PartsGuide
PARTS GUIDE
MULITI SPLIT TYPE
ROOM AIR CONDITIONERS
MODEL
OUTDOOR UNIT
AE-XM30GR
CONTENTS
[1]
OUTDOOR UNIT PARTS 1
[4]
PACKING PARTS
[2]
OUTDOOR UNIT PARTS 2

INDEX
[3]
OTHER OUTDOOR UNIT
HOW TO ORDER REPLACEMENT PARTS
To have your order filled promptly and correctly, please
furnish the following information.
1. MODEL NUMBER
2. REF. NO.
3. PART NO.
4. DESCRIPTION
This document has been published to be used
for after sales service only.
The contents are subject to change without notice.
AE-XM30GR
[1] OUTDOOR UNIT PARTS 1
2-37
4-10
1-45
2-23
2-40
1-44
4-10
2-24
1-50
1-48 4-11
1-61
1-12
1-66
1-60
2-17
4-3
1-36
4-14
1-2
1-61
1-65
4-1
1-46
1-70
4-15
1-4
4-16
1-62 1-52
2-6
1-5-2
1-5-1
1-59
4-12
2-25
2-28
4-3
2-19
2-20
2-9
1-66
4-13
2-41
1-62
2-20
1-58
1-63
1-11
2-26
1-76
2-38
3-15
2-39
2-31
2-5
1-69
1-4
2-36
1-3
4-8
2-1
2-5
2-7
2-4
2-49
2-2
2-48
2-46
2-21
1-1
4-9
4-7
2-3
2-12
1-71
2-10
2-56
2-52
2-22
2-47
2-61
2-62
4-3
2-9
2-53
2-15
4-3
4-3
2-8
2-13
4-4
4-3
2-57
4-3
2-14
2
2-55
AE-XM30GR
NO.
PARTS CODE
PRICE NEW PART
RANK MARK RANK
DESCRIPTION
[1] OUTDOOR UNIT PARTS 1
1-1
1-2
1-3
1-4
1-5-1
1-5-2
1-11
1-12
1-36
1-44
1-45
1-46
1-48
1-50
1-52
1-58
1-59
1-60
1-61
1-62
1-63
1-65
1-66
1-69
1-70
1-71
1-76
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
2-9
2-10
2-12
2-13
2-14
2-15
2-17
2-19
2-20
2-21
2-22
2-23
2-24
2-25
2-26
2-28
2-31
2-36
2-37
2-38
2-39
2-40
2-41
2-46
2-47
2-48
2-49
2-52
2-53
2-55
2-56
2-57
2-61
2-62
2-70
3-15
4-1
4-3
4-4
4-7
4-8
4-9
4-10
4-11
4-12
4-13
4-14
4-15
4-16
CMOTLB051JBEZ
LANG-A540JBWZ
LHLD-A539JBFA
LHLD-A544JBFA
QTANZA020JBZZ
QTANZA021JBZZ
DBOX-A044JBWZ
DPWBFA513JBKZ
PRDAFA172JBEZ
RH-TXA006JBZZ
VHDD25VB60+-1
DPWBFA436JBKZ
DPWBFA437JBKZ
RH-IZA105JBEO
PRDAFA173JBEZ
RHOG-A169JBEO
LBNDKA113JBWZ
LHLD-A656JBFZ
LHLDWA039JBEZ
LHLDWA040JBEZ
LX-BZA075JBEO
PSPA-A146JBE0
PSPA-A173JBE0
RH-HXA032JBZZ
RC-AZA046JBEO
RTRN-A297JBZZ
PSPA-A082JBEO
LANGKA164JBPZ
LANGKA165JBPZ
LANGKA166JBPZ
LANGKA163JBPZ
LSUB-A029JBPZ
LSUB-A030JBPZ
PSEL-C642JBEZ
GCAB-A303JBTA
JHNDPA016JBFA
PSEL-C637JBEZ
GCAB-A247JBTB
GGADFA028JBTA
CCHS-A856JBKZ
GLEGMA043JBTB
GPLTMA062JBTB
GPLTMA066JBTB
PSEL-C641JBEZ
PSEL-C597JBEZ
PSKR-A329JBWZ
GCAB-A248JBTB
PSEL-C598JBEZ
PSEL-C640JBEZ
PSEL-C702JBEZ
GGADRA001JBTA
LHLD-A574JBFA
NFANPA108JBFA
PCOV-A940JBWZ
PSEL-C281JBEZ
PSEL-C373JBEZ
PSEL-C634JBEZ
PSEL-C635JBEZ
PSPF-A897JBEZ
PSPF-A898JBEZ
PSPF-A899JBEZ
PSPF-A900JBEZ
TLABBA146JBRA
TLABCC298JBRZ
TSPC-F617JBRZ
PSEL-C760JBEZ
PSEL-C761JBEZ
TLAB-C771JBRZ
TLAB-C773JBRZ
TLAB-D081JBEZ
PCON-A553JBPZ
LX-BZA354JBEZ
LX-BZA364JBEZ
LX-BZA380JBEZ
LX-BZA367JBEZ
LX-NZA319JBEZ
LX-BZA363JBEZ
XBPS740P20J00
XTPS730P12XS0
XCPS730P12XS0
XTTUW40P16000
XBPS730P10000
XCPS740P16000
XCTS740P30000
BX
AU
AE
AG
AQ
AN
AT
BT
BA
BS
AN
AU
BY
AQ
BA
AK
AS
AQ
AC
AC
AA
AC
AE
AX
BE
BK
AB
AQ
AN
AQ
AX
AE
AE
AA
BE
AE
AD
BE
AZ
BK
AX
AX
BC
AD
AC
BC
BB
AK
AG
AE
AV
AE
BA
AP
AC
AC
AE
AD
AT
AR
AF
AG
AN
AH
AN
AB
AB
AR
AN
AH
CC
AC
AC
AK
AC
AE
AE
AF
AF
AF
AB
AF
AC
AF
Fan motor
Terminal board angle
Cord holder
Cord clamp holder
Terminal board
Terminal board
Control box ass'y
Control board unit
Haet sink
Active filter(SACT32430D)
Diode
Display board unit
Power transistor
Photo coupler (PC101-106)
Heat sink
Thermistor(HEATSINK)
Capacitor clamp
Heat sink holder
Wire holder
Wire holder
Special screw
Spacer
PWB spacer
Thermistor
Electrolytic capacitor
Active coil
Pwb spacer
Motor base
Motor angle
Motor angle B
Motor angle T
Motor angle sub A
Motor angle sub B
M.ang sub a seal
Front panel R
Handle
Front panel seal A
Front panel L
Fan guard
Base pan sub ass'y
Base stand
Side cabinet L
Side cabinet R
Side cover R seal
Bulkead insulator
Bulkead
Top cover
Top cover seal A
Top cover seal B
Top cover seal C
Rear guard
Thermistor holder
Protector fan
Control box cover
Cushion
Seal
Panel seal A
Panel seal B
Compressor cover A
Compressor cover B
Compressor cover C
Compressor cover D
Badge
Wiring diagram
Name label
Fr.panel l seal A
Base pan seal A
Service label
Label
Eu energy label
Condenser
Special screw
Special screw
Special screw
Special screw
Special nut
Special screw
Machine screw
Tapping screw
Tapping screw
Tapping screw
Machine screw
Tapping screw
Tapping screw
3
AE-XM30GR
[2] OUTDOOR UNIT PARTS 2
3-14
3-21
3-35 3-25
3-8
2-33
1-69
1-54
3-35
3-9
3-24
3-10
3-7
3-17
1-78
1-79
2-35
3-12
3-1-1
3-17
1-73
3-1-1
3-23
3-17
3-1-1
4-6
3-18
3-22
2-67
2-69
3-13
3-1-2
2-68
3-33
3-11
6-7
6-8
3-31
6-9
3-34
3-30
2-30
3-32
3-28
2-66
6-5
2-30
3-32
2-63
3-28
3-2
6-1
3-34
3-30
6-2
3-30
2-30
3-34
3-32
3-29
4-5
6-3
6-6
3-37
2-64
6-10
3-38
3-36
3-5
3-39
3-5-2
3-5-1
2-29
2-16
4
AE-XM30GR
NO.
PARTS CODE
PRICE NEW PART
RANK MARK RANK
DESCRIPTION
[2] OUTDOOR UNIT PARTS 2
1-54
1-69
1-73
1-78
1-79
2-16
2-29
2-30
2-33
2-35
2-63
2-64
2-66
2-67
2-68
2-69
3-1-1
3-1-2
3-2
3-5
3-5-2
3-5-1
3-7
3-8
3-9
3-10
3-11
3-12
3-13
3-14
3-17
3-18
3-21
3-22
3-23
3-24
3-25
3-28
3-29
3-30
3-31
3-32
3-33
3-34
3-35
3-36
3-37
3-38
3-39
4-5
4-6
6-1
6-2
6-3
6-5
6-6
6-7
6-8
6-9
6-10
QW-IZA100JBZZ
RH-HXA032JBZZ
RTHM-A022JBEO
RH-HXA054JBZZ
MSPR-A027JBEO
PDAI-A114JBTB
LSUB-A021JBWZ
LSUB-A020JBWZ
MSPR-A026JBEO
MSPR-A046JBEO
TLAB-C770JBRA
TLAB-B709JBRA
PSEL-C006JBEZ
PGUM-A119JBEZ
PGUM-A120JBEZ
MSPR-A129JBEO
PVLVRA040JBEZ
PVLVRA045JBEZ
DVLV-A668JBKZ
DVLV-A669JBKZ
LX-NZA228JBEZ
LX-NZA227JBEZ
DVLV-A702JBKZ
CCIL-A112JBEZ
LX-BZA268JBEZ
PACU-A043JBEZ
GLEG-A116JBEZ
LBSHCA004JBEO
PCMPRA407JBEZ
PCOV-A014JBEO
RMOTSA024JBZZ
RMOTSA030JBZZ
PVLVXA061JBEZ
PGUMSA319JBEZ
PMUF-A081JBEZ
PGUM-0035JBEO
PGUM-0036JBEO
DVLV-A703JBKZ
DVLV-A704JBKZ
DVLV-A705JBKZ
LX-NZA250JBEZ
LX-NZA251JBEZ
PCAP-A083JBEZ
PCAP-A084JBEZ
PTUB-A196JBEZ
DVLV-A794JBKZ
DVLV-A796JBKZ
PCAP-A103JBEZ
LX-NZA280JBEZ
LX-BZA355JBEZ
LX-NZA313JBEZ
TINS-B048JBRZ
TINS-B049JBRZ
TINS-B050JBRZ
LX-BZA354JBEZ
GFTASA002JBFA
LBND-A046JBEO
LPFT-A134JBFZ
LPFT-A135JBFZ
PTUB-A218JBEZ
AZ
AX
AN
AX
AB
BB
AE
AE
AB
AC
AR
AH
AC
AG
AG
AD
BM
BD
AZ
AN
AD
AF
BF
AX
AB
BW
AK
AD
CT
AG
BC
BC
BD
AF
AY
AG
AG
AZ
AZ
AZ
AE
AG
AC
AC
AK
BM
BM
AF
AG
AE
AE
AH
AH
AH
AC
AM
AE
AF
AH
AB
Compressor cord
Thermistor
Thermistor
Thermistor
Thermistor spring
Flare coupling base
Flare cou. Sub-s
Flare cou. Sub-s
Spring
Protector spring
Unit label
Label
Insulator
Valve rubber
Valve rubber
Cycle spring
Expansion valve
Expansion valve
3Way valve unit
3Way valve unit
Service nut
Bonnet
Reverse valve ass'Y
Coil
Special screw
Accumulator
Compressor cushion
Terminal seal
Compressor
Terminal cover
Coil
Coil
Reverse valve
Damper rubber
Muffer
Dumper rubber (3/8)inch
Dumper rubber (1/2)inch
Flare union unit 3s
Flare union unit 3s
Flare union unit 2s
Fiare nut
Fiare nut
Nut bonnet
Nut bonnet
Pipe insulator
Flare union unit 4s
Flare union unit 2s
Nut bonnet
Flare nut(4)
Special screw
Special nut
Insulator manual
Insulator manual
Insulator manual
Hex screw 10
Cable cover
Wire fixing band
Drain joint
Drain tray
Tube insulator
AP
AP
AU
AK
AF
AF
AF
BA
AF
AE
AF
AH
AB
AU
AP
AU
AP
AP
AP
BK
AW
AH
Lead wire (TBN-T2)
Lead wire (TBL-T1)
Lead wire (TB-CN6)
Lead wire (TBE-BOX)
Ferrite core (FC1-9)
Ferrite core (FC10-12)
Varistor
Fuse 20A AC250V(FUSE1/2)
Fuse 3.15A C250V(FUSE3-4)
Fuse 2A C250V(FUSE5)
Fuse 1A C250V(FUSE6)
Surge absorb(SA1)
Fuse CLIP(Fuse1-2)
Lead wire (IPM 10A LEAD)
Lead wire (IPM 2P LEAD)
Lead wire (DISPLAY LEAD)
Lead wire (AF LEAD)
Lead wire (BLUE)
Lead wire (BROWN)
Micro computer(IC1)
Ptc thermistor (PTC1)
Relay(RY3)
[3] OTHER OUTDOOR UNIT
1-6
1-7
1-8
1-9
1-10-1
1-10-2
1-13
1-14
1-15
1-16
1-17
1-18
1-19
1-20
1-21
1-22
1-23
1-25
1-26
1-27
1-28
1-29
QW-VZE592JBZZ
QW-VZE593JBZZ
QW-VZF079JBZZ
QW-VZF212JBZZ
RFIL-A064JBE0
RNF--A001VBE0
RH-VXA002JBZZ
QFS-GA065JBZZ
QFS-GA062JBZZ
QFS-GA063JBZZ
QFS-GA064JBZZ
QSPGCA003JBZZ
QTAN-0129JBEO
QW-VZF080JBZZ
QW-VZE581JBZZ
QW-VZF081JBZZ
QW-VZE585JBZZ
QW-VZE624JBZZ
QW-VZE625JBZZ
RH-IXA882JBZZ
RH-QXA005JBZZ
RRLYDA008JBZZ
5
AE-XM30GR
NO.
PARTS CODE
PRICE NEW PART
RANK MARK RANK
DESCRIPTION
[3] OTHER OUTDOOR UNIT
1-30
1-31
1-32
1-33
1-34
1-37
1-38
1-39
1-40
1-41
1-42
1-43
1-47
1-49
1-51
1-53
1-55
1-56
1-57
1-64
1-67
1-68
1-72
1-74
1-75
1-81
1-82
1-83
1-84
1-85
1-86
1-89
1-90
1-91
2-34
3-27
4-2
6-11
6-11-1
RRLYDA012JBZZ
VHGPC817X3+1BS
VHGPC81716N1BS
VHIKA7815AP-1
VHGPC853X++-1S
QW-VZE596JBZZ
QW-VZE597JBZZ
QW-VZE598JBZZ
QW-VZE599JBZZ
QW-VZE600JBZZ
QW-VZE601JBZZ
QW-VZE602JBZZ
QSW-PA016DREO
PH-IXA782JBZZ
VHGPC81716N1BS
PSPA-A150JBZZ
QW-VZE605JBZZ
QW-VZF210JBZZ
QW-VZF211JBZZ
PSHE-A218JBEZ
QW-VZD806JBZZ
QW-VZE603JBZZ
QW-VZF172JBZZ
RTRN-A256JBEO
VHIMR2920++-1S
QW-VZF208JBZZ
QW-VZF209JBZZ
QW-VZD798JBZZ
QW-VZD820JBZZ
QW-VZD799JBZZ
TLAB-C832JBRZ
RH-HXA054JBZZ
TLAB-C831JBRZ
LX-BZA354JBEZ
MSPR-A036JBEO
FCMPRA150JBKZ
LX-BZA140JBE0
CPIPCB059JBKZ
LX-NZA251JBEZ
Relay(MRY1)
Photo coupler(PC2-11,13,15,17,19)
Photo coupler(PC1)
15V regurater(IC10)
Photo coupler(PC12,14,16,18)
Lead wire(AF1(L)-COIL)
Lead wire(AF1(Io)-C9(-))
Lead wire(AF1(P)-C9(+))
Lead wire(DB1(-)-AF(-))
Lead wire(DB1(+)-AF(+))
Lead wire(MRY(OUT)-DB1(AC1))
Lead wire(MRY(T6-DB1(AC2))
Tact switch(sw1)
Power module (PS21869)
Photo coupler (PC107)
Pwb spacer
Lead wire (DC VOLTAGE)
Lead wire (C10(+)-TP)
Lead wire (C10(-)-TN)
Protect sheet
Lead wire
Lead wire(C9(+)-C10(+))
Lead wire(T4-BOX)
Transformer(CT1)
Integrated circuit(IC4)
Lead wire
Lead wire
Lead wire
Lead wire
Lead wire
Label
Thermistor
Label
Hex screw 10
Thermistor spring
Compressor ass'y(3-11,3-12,3-13,3-14)
Special screw
JOINT 1/2-3/8 assembly
FLARE NUT
AR
AD
AQ
AE
AN
AP
AP
AP
AP
AP
AP
AP
AB
BV
AQ
AF
AK
AK
AK
AP
AD
AP
AK
AG
AU
AK
AK
AD
AE
AE
AN
AX
AN
AC
AB
CU
AB
BQ
AG
[4] PACKING PARTS
5-2
5-3
5-1
NO.
PARTS CODE
PRICE NEW PART
RANK MARK RANK
DESCRIPTION
[4] PACKING PARTS
5-1
5-2
5-3
CPADBA072JBKZ
CPADBA073JBKZ
SPAKCC226JBEZ
AR
AH
BD
Bottom pad ass'y
Packing pad ass'y
Packing case
6
AE-XM30GR
INDEX
PARTS CODE
[ C
CCHS-A856JBKZ
CCIL-A112JBEZ
CMOTLB051JBEZ
CPADBA072JBKZ
CPADBA073JBKZ
CPIPCB059JBKZ
[ D
DBOX-A044JBWZ
DPWBFA436JBKZ
DPWBFA437JBKZ
DPWBFA513JBKZ
DVLV-A668JBKZ
DVLV-A669JBKZ
DVLV-A702JBKZ
DVLV-A703JBKZ
DVLV-A704JBKZ
DVLV-A705JBKZ
DVLV-A794JBKZ
DVLV-A796JBKZ
[ F
FCMPRA150JBKZ
[ G
GCAB-A247JBTB
GCAB-A248JBTB
GCAB-A303JBTA
GFTASA002JBFA
GGADRA001JBTA
GGADFA028JBTA
GLEG-A116JBEZ
GLEGMA043JBTB
GPLTMA062JBTB
GPLTMA066JBTB
No.
PRICE NEW PART
RANK MARK RANK
PARTS CODE
MSPR-A046JBEO
MSPR-A129JBEO
[ N ]
NFANPA108JBFA
[ P ]
PACU-A043JBEZ
PCAP-A083JBEZ
PCAP-A084JBEZ
PCAP-A103JBEZ
PCMPRA407JBEZ
PCON-A553JBPZ
PCOV-A014JBEO
PCOV-A940JBWZ
PDAI-A114JBTB
PGUM-0035JBEO
PGUM-0036JBEO
PGUM-A119JBEZ
PGUM-A120JBEZ
PGUMSA319JBEZ
PH-IXA782JBZZ
PMUF-A081JBEZ
PRDAFA172JBEZ
PRDAFA173JBEZ
PSEL-C006JBEZ
PSEL-C281JBEZ
PSEL-C373JBEZ
PSEL-C597JBEZ
PSEL-C598JBEZ
PSEL-C634JBEZ
PSEL-C635JBEZ
PSEL-C637JBEZ
PSEL-C640JBEZ
PSEL-C641JBEZ
PSEL-C642JBEZ
PSEL-C702JBEZ
PSEL-C760JBEZ
PSEL-C761JBEZ
PSHE-A218JBEZ
PSKR-A329JBWZ
PSPA-A082JBEO
PSPA-A146JBE0
PSPA-A150JBZZ
PSPA-A173JBE0
PSPF-A897JBEZ
PSPF-A898JBEZ
PSPF-A899JBEZ
PSPF-A900JBEZ
PTUB-A196JBEZ
PTUB-A218JBEZ
PVLVRA040JBEZ
PVLVRA045JBEZ
PVLVXA061JBEZ
[ Q ]
QFS-GA062JBZZ
QFS-GA063JBZZ
QFS-GA064JBZZ
QFS-GA065JBZZ
QSPGCA003JBZZ
QSW-PA016DREO
QTAN-0129JBEO
QTANZA020JBZZ
QTANZA021JBZZ
QW-IZA100JBZZ
QW-VZD798JBZZ
QW-VZD799JBZZ
QW-VZD806JBZZ
QW-VZD820JBZZ
QW-VZE581JBZZ
QW-VZE585JBZZ
QW-VZE592JBZZ
QW-VZE593JBZZ
QW-VZE596JBZZ
QW-VZE597JBZZ
QW-VZE598JBZZ
QW-VZE599JBZZ
QW-VZE600JBZZ
QW-VZE601JBZZ
QW-VZE602JBZZ
QW-VZE603JBZZ
]
1-2-14
2-3-8
1-1-1
4-5-1
4-5-2
3-6-11
BK
AX
BX
AR
AH
BQ
1-1-11
1-1-46
1-1-48
1-1-12
2-3-2
2-3-5
2-3-7
2-3-28
2-3-29
2-3-30
2-3-36
2-3-37
AT
AU
BY
BT
AZ
AN
BF
AZ
AZ
AZ
BM
BM
3-3-27
CU
1-2-12
1-2-23
1-2-8
2-6-6
1-2-28
1-2-13
2-3-11
1-2-15
1-2-17
1-2-19
BE
BB
BE
AM
AV
AZ
AK
AX
AX
BC
1-2-9
AE
1-1-2
1-2-4
1-2-1
1-2-2
1-2-3
2-6-7
1-1-59
2-3-12
1-1-3
1-1-4
1-2-31
1-1-60
1-1-61
1-1-62
2-6-8
2-6-9
2-2-30
2-2-29
1-2-5
1-2-6
1-1-63
3-4-2
2-3-9
1-4-1
2-6-5
3-1-91
2-4-5
1-4-9
1-4-3
1-4-7
1-4-4
2-3-5-1
2-3-5-2
2-3-31
2-3-32
3-6-11-1
2-3-39
2-4-6
1-4-8
AU
AX
AQ
AN
AQ
AE
AS
AD
AE
AG
AE
AQ
AC
AC
AF
AH
AE
AE
AE
AE
AA
AB
AB
AC
AC
AC
AE
AE
AC
AC
AK
AF
AD
AE
AG
AG
AG
AE
AE
2-2-33
2-1-79
3-2-34
AB
AB
AB
]
]
]
[ J ]
JHNDPA016JBFA
[ L ]
LANG-A540JBWZ
LANGKA163JBPZ
LANGKA164JBPZ
LANGKA165JBPZ
LANGKA166JBPZ
LBND-A046JBEO
LBNDKA113JBWZ
LBSHCA004JBEO
LHLD-A539JBFA
LHLD-A544JBFA
LHLD-A574JBFA
LHLD-A656JBFZ
LHLDWA039JBEZ
LHLDWA040JBEZ
LPFT-A134JBFZ
LPFT-A135JBFZ
LSUB-A020JBWZ
LSUB-A021JBWZ
LSUB-A029JBPZ
LSUB-A030JBPZ
LX-BZA075JBEO
LX-BZA140JBE0
LX-BZA268JBEZ
LX-BZA354JBEZ
"
"
LX-BZA355JBEZ
LX-BZA363JBEZ
LX-BZA364JBEZ
LX-BZA367JBEZ
LX-BZA380JBEZ
LX-NZA227JBEZ
LX-NZA228JBEZ
LX-NZA250JBEZ
LX-NZA251JBEZ
"
LX-NZA280JBEZ
LX-NZA313JBEZ
LX-NZA319JBEZ
[ M ]
MSPR-A026JBEO
MSPR-A027JBEO
MSPR-A036JBEO
7
No.
PRICE NEW PART
RANK MARK RANK
2-2-35
2-2-69
AC
AD
1-2-36
BA
2-3-10
2-3-33
2-3-34
2-3-38
2-3-13
1-3-15
2-3-14
1-2-37
2-2-16
2-3-24
2-3-25
2-2-67
2-2-68
2-3-22
3-1-49
2-3-23
1-1-36
1-1-52
2-2-66
1-2-38
1-2-39
1-2-21
1-2-24
1-2-40
1-2-41
1-2-10
1-2-25
1-2-20
1-2-7
1-2-26
1-2-56
1-2-57
3-1-64
1-2-22
1-1-76
1-1-65
3-1-53
1-1-66
1-2-46
1-2-47
1-2-48
1-2-49
2-3-35
2-6-10
2-3-1-1
2-3-1-2
2-3-21
BW
AC
AC
AF
CT
CC
AG
AP
BB
AG
AG
AG
AG
AF
BV
AY
BA
BA
AC
AC
AC
AC
AK
AE
AD
AD
AG
AD
AA
AE
AB
AB
AP
BC
AB
AC
AF
AE
AT
AR
AF
AG
AK
AB
BM
BD
BD
3-1-15
3-1-16
3-1-17
3-1-14
3-1-18
3-1-47
3-1-19
1-1-5-1
1-1-5-2
2-1-54
3-1-83
3-1-85
3-1-67
3-1-84
3-1-21
3-1-23
3-1-6
3-1-7
3-1-37
3-1-38
3-1-39
3-1-40
3-1-41
3-1-42
3-1-43
3-1-68
AF
AE
AF
BA
AH
AB
AB
AQ
AN
AZ
AD
AE
AD
AE
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AE-XM30GR
PARTS CODE
QW-VZE605JBZZ
QW-VZE624JBZZ
QW-VZE625JBZZ
QW-VZF079JBZZ
QW-VZF080JBZZ
QW-VZF081JBZZ
QW-VZF172JBZZ
QW-VZF208JBZZ
QW-VZF209JBZZ
QW-VZF210JBZZ
QW-VZF211JBZZ
QW-VZF212JBZZ
[ R ]
RC-AZA046JBEO
RFIL-A064JBE0
RH-HXA032JBZZ
"
RH-HXA054JBZZ
"
RH-IXA882JBZZ
RH-IZA105JBEO
RHOG-A169JBEO
RH-QXA005JBZZ
RH-TXA006JBZZ
RH-VXA002JBZZ
RMOTSA024JBZZ
RMOTSA030JBZZ
RNF--A001VBE0
RRLYDA008JBZZ
RRLYDA012JBZZ
RTHM-A022JBEO
RTRN-A256JBEO
RTRN-A297JBZZ
[ S ]
SPAKCC226JBEZ
[ T ]
TINS-B048JBRZ
TINS-B049JBRZ
TINS-B050JBRZ
TLAB-B709JBRA
TLABBA146JBRA
TLAB-C770JBRA
TLAB-C771JBRZ
TLAB-C773JBRZ
TLAB-C831JBRZ
TLAB-C832JBRZ
TLABCC298JBRZ
TLAB-D081JBEZ
TSPC-F617JBRZ
[ V ]
VHDD25VB60+-1
VHGPC81716N1BS
"
VHGPC817X3+1BS
VHGPC853X++-1S
VHIKA7815AP-1
VHIMR2920++-1S
[ X ]
XBPS730P10000
XBPS740P20J00
XCPS730P12XS0
XCPS740P16000
XCTS740P30000
XTPS730P12XS0
XTTUW40P16000
No.
PRICE NEW PART
RANK MARK RANK
3-1-55
3-1-25
3-1-26
3-1-8
3-1-20
3-1-22
3-1-72
3-1-81
3-1-82
3-1-56
3-1-57
3-1-9
AK
AP
AP
AU
AU
AU
AK
AK
AK
AK
AK
AK
1-1-70
3-1-10-1
1-1-69
2-1-69
2-1-78
3-1-89
3-1-27
1-1-50
1-1-58
3-1-28
1-1-44
3-1-13
2-3-17
2-3-18
3-1-10-2
3-1-29
3-1-30
2-1-73
3-1-74
1-1-71
BE
AF
AX
AX
AX
AX
BK
AQ
AK
AW
BS
AF
BC
BC
AF
AH
AR
AN
AG
BK
4-5-3
BD
2-6-1
2-6-2
2-6-3
2-2-64
1-2-52
2-2-63
1-2-61
1-2-62
3-1-90
3-1-86
1-2-53
1-2-70
1-2-55
AH
AH
AH
AH
AN
AR
AR
AN
AN
AN
AH
AH
AN
1-1-45
3-1-32
3-1-51
3-1-31
3-1-34
3-1-33
3-1-75
AN
AQ
AQ
AD
AN
AE
AU
1-4-14
1-4-10
1-4-12
1-4-15
1-4-16
1-4-11
1-4-13
AF
AF
AF
AC
AF
AF
AB
8
EndPage
COPYRIGHT © 2006 BY SHARP CORPORATION
ALL RIGHTS RESERVED.
No part of this publication may be reproduced, stored
in retrieval systems, or transmitted in any form or by
any means, electronic, mechanical, photocopying, recording, or other wise, without prior written permission
of the publisher.
P1 / 1
Date: 17/May/2010
Air Conditioner
AE-X24GR , AE-XM30GR , AE-X2M18KR , others
CHANGE COIL FOR EXPANSION VALVE
Ref.No.: EHH - 299
Technical Report
General
The service parts of the coil for expansion valve is changed.
Model
Reason
Interchangeability
Model name
GU-XR18ER , GU-XR24ER , GU-XR27ER ,
GU-XR18FR , GU-XR24FR , GU-XR27FR ,
AE-X24GR , AE-XM18FR , AE-XM24FR ,
AE-XM30FR , AE-XM30GR , AE-XM24HR ,
AE-X3M18JR
AE-X2M18KR
CFI180H , CFI240H , CFI181H , CFI241H ,
CWI241H , MIH181C , MIH241C , MIH301C ,
MIH302C , MIH183C , MIH244C ,
AOM30XM4 , AOM24XM3 , AOM18XM2 ,
AOM18XM3.UE , AOM24XM4.UE ,
GU-PJ80J , GU-PJ80JS , GU-PJ50J
GU-PJ50JS
AE-S70EP2 , AE-S68GP2
AE-X30EJ
No.
Serial number
Destinations
Europe
Europe , Singapore
From Mar.2010
Product
Italy
(AERMEC)
Running Change
France
(ATLANTIC)
Japan
Taiwan
Australia
Cost Down
A.
OLD
NEW
B.
OLD
NEW
C.
OLD
NEW
D.
OLD
×
NEW
Refer to Service Manual (Parts guide)
Parts
※
Ref No.
DESCRIPTION
PART CODE
Old No.
Q'ty
New No.
Effective Intercha Price
Q'ty from ngeability Code
3-17
COIL
RMOTSA017JBZZ
1
RMOTSA040JBZZ
1
Mar.2010
A
AZ
3-17
COIL
RMOTSA024JBZZ
1
RMOTSA041JBZZ
1
Mar.2010
A
AZ
3-20
COIL
RMOTSA031JBZZ
1
RMOTSA038JBZZ
1
Mar.2010
A
BD
※ Ref No. is the representative model's. Please confirm each service manual in case of other models.
(RMOTSA017JBZZ : AE-X24GR , RMOTSA024JBZZ : AE-XM30GR , RMOTSA031JBZZ : AE-X2M18KR)
Note
These changed parts are used in Mar.2010 by running change.
SHARP CORPORATION, Health and Environment Systems Group, CS Promotion Center
Air conditioner
AE-XM30GR,etc.
Date:24/Mar/2009
Ref.No.:EHH-276
Change of Active filter
Technical Report
General
Active filter has been changed as follows.
Model
Model name
Destination
Effective from
AE-XM30GR
Europe
Jun-06
Reason
Interchange
ability
y
Parts
Standardization
A.. OLD
NEW
B.. OLD
NEW
NEW
D
OLD
Part code
Description
Active filter
C.. OLD
Old
RH-TXA006JBZZ
Q'ty
1
New
RH-TXA008JBZZ
Q'ty P/code
1 BR
× NEW
Effective
from
Note
SHARP CORPORATION
Health & Environment Systems Gr,CS Promotion C.
Jun-06