Download Black Box IC050C Instruction manual

Transcript
GEH-7275
kV RSX - RS232/RS485 Communications Option
Instruction Manual
March 10, 1999
Notice:
The information contained in this document is subject to change without notice.
GE makes no warranty of any kind with regard to this material, including, but not limited to, the
implied warranties of merchantability and fitness for a particular purpose. GE shall not be liable
for errors contained herein or incidental consequential damages in connection with the furnishing,
performance, or use of this material.
This document contains proprietary information, which is protected by copyright. All rights are
reserved. No part of this document may be photocopied or otherwise reproduced without consent
of GE.
Copyright (c) 1998 by GE
Published in a limited copyright sense, and all rights, including trade secrets, are reserved.
Document Edition - First 10/98
kV™, MeterMate™, and OPTOCOM™ are trademarks of GE.
MS-DOS and Windows are a trademark of Microsoft Corporation.
FCC Notice
FCC Part 15: Preventing Radio and Television Interference
This device complies with part 15 of the FCC rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause
undesirable operation.
Changes or modifications to this equipment not expressly approved by the General Electric
Company could void the user’s authority to operate this equipment.
This instruction book does not cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. The
equipment covered by these instructions should be operated and serviced only by competent
technicians familiar with good safety practices, and these instructions are written for such
personnel and are not intended as a substitute for adequate training and experience in safe
procedures for this type of equipment. Should further information be desired, or should particular
problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should
be referred to GE Meter.
Warning
Any work on or near energized meters, meter sockets, or other metering equipment can
present a danger of electrical shock. All work should be performed only by qualified
industrial electricians and metering specialists in accordance with local utility safety
practices and the procedures outlined in the Handbook for Electricity Metering, Chapter
14 (available from Edison Electric Institute, 1111 19th Street NW, Washington, DC 20036).
The information contained in this instruction book is intended to be an aid to qualified
metering personnel. It is not intended to replace the extensive training necessary to
install or remove meters from service.
Page 2
Related Publications:
GEH-5081
GE kV™ Vector Electricity Meter Installation, Operation, and Maintenance Guide
GEH-5084
MeterMate™ for DOS
Reading and Programming Software for GE Electronic Meters
GEH-5082
MeterMate™ for Windows
Program Creation Software for GE Electronic Meters
GEI-101424
kV RSX Kit Installation Guide
GEI-101421
Telephone Line Surge Protection Devices
Page 3
Table of Contents
INTRODUCTION
6
KV RSX FEATURES, EXTERNAL MODEM MODE
6
Data Rate
Setup Strings
Pulse/Tone
6
6
6
Call Origination
Introduction
Programming Phone Numbers
Retry Algorithm
Call Origination Window
Data Calls
Event Calls
Power Outage Calls (optional)
Power Restoration Calls
Test Calls
7
7
7
7
7
7
8
8
9
9
Call Answer
Answer Window
Number of Rings
Answer Lockout Timer
9
9
9
9
KV RSX FEATURES,
RS-232 SIMPLE SERIAL MODE
Data Rate
KV RSX FEATURES,
9
10
RS-485 SIMPLE SERIAL MODE
Data Rate
10
10
INSTALLING THE KV RSX IN THE KV™ METER
10
kV RSX Installation
10
Installation on S-base Meters
12
Installation on A-base Meters
13
Optional Outage Call-in Battery Installation
14
Option Board Compatibility
Introduction
RG-1 Revenue Guard Option Board
I/O-1 Input/Output Option Board (Obsolete)
I/O-2 Input/Output Option
LP-1 Load Profile Option Board (Obsolete)
LP-2 Load Profile Option Board
kV RSX Option Board
15
15
15
15
16
16
16
16
Page 4
MeterMate Software Compatibility
16
TESTING METER CALIBRATION
17
METER INSTALLATION
17
Test Call
17
RENEWAL PARTS
18
kV RSX Kits
S-Base kV RSX Kits
A-base kV RSX Kits
Call-in On Outage Upgrade Kit
18
18
18
19
Other Renewal Parts:
19
APPENDIX
20
External Modem Mode
kV RSX Setup Strings
Baud Rate
Typical External Modem Setup Strings
Typical Host Modem Setup Strings
20
20
21
22
23
RS-232 Simple Serial Mode
25
RS-485 Simple Serial Mode
26
Determining the Mode of an Installed kV RSX
28
Using MeterMate Version 2.12 with the kV RSX
Default MeterMate Program for kV RSX
External Modem Reset
Programming to use the Optional RJ-11 Cable
29
29
30
31
Page 5
computer using a null modem cable. It also
serves as an RS-232 interface to third party
communications devices. The baud rate for
this mode is fixed at 9600 bps.
Introduction
The kV RSX Communications Board is an
optional factory-supplied addition to the kV™
Meter, or may be ordered in the form of a
retrofit kit to upgrade “Communication
Ready” kV™ Meters. Meters that are capable
of being upgraded may be identified by the
words “Modem Ready” on the upper
nameplate of the meter.
The kV RSX Option Board is used to provide
two-way communication to the kV™ Meter
and may be used on S-base, A-base, and
switchboard meters. It is available on both
TOU and demand versions of the kV™
Meter.
The kV RSX Option Board may be used in
conjunction with other GE option boards,
which provide a three-phase power supply,
load profile recording, and input/output
functions. If required, the flexibility of the
kV™ Meter makes it possible to combine all
of the above option boards in a single meter.
The kV RSX Option Board has three
modes of operation: External Modem
mode, RS-232 Simple Serial mode and
RS-485 Simple Serial mode.
When operating in External Modem Mode,
the kV RSX provides an RS232 interface to
an external telephone or wireless modem to
facilitate remote kV Meter reading and
programming. In this mode the kV RSX
contains AMRA
tables which can be
programmed to provide the following basic
features:
•
300, 1200, 2400, 4800, 9600 baud
support.
•
Supports industry standard
protocol and AMRA Tables
•
Originate call on an event
•
Originate call on a scheduled basis
•
Originate
(optional)
call
on
power
RS-485 Simple Serial Mode provides a halfduplex, 2 -wire, RS-485 interface for remote
reading of the kV Meter. The baud rate is
fixed at 9600 bps. No multidrop capability is
supported.
All kV™ Meters, including those with kV RSX
boards, are programmed using GE’s
MeterMate software program.
kV RSX Features,
External Modem mode
The kV RSX External Modem mode features
can be broken down into those features that
apply only to when the meter originates a call
(call origination), the meter answers a call
(call answer), or standard features that apply
to all call types.
Data Rate
The kV™ RSX Option Board can be
programmed for a DTE baud rate of 300,
1200, 2400, 4800, or 9600. This is the baud
rate at which the option board will
communicate to the attached, external,
modem.
Setup Strings
The kV™ RSX Option Board is shipped with
default external modem setup strings.
However, should it be necessary for you to
change the modem’s setup strings, they may
be changed by using GE’s MeterMate
software program.
PSEM
Pulse/Tone
outage
In RS-232 Simple Serial Mode, the kV RSX
provides a 3-wire, RS-232 interface. This
interface allows the kV Meter to be read by a
The kV™ RSX Option Board can support
both pulse and tone dialing. It can be
configured with the appropriate dialing type
when generating a meter program using
GE’s MeterMate for Windows Program
Creation Software. The type of dialing
method which should be used can be
Page 6
determined by contacting your local
telephone company.
Call Origination
Introduction
The kV™ Meter is capable of originating a
phone call for the following reasons:
• Scheduled data call
• Event (i.e. errors, cautions, diagnostics)
• Power outage (optional)
• Power restoration
• Test call
(1-15 minutes) between each call cycle
(primary/secondary phone numbers). If a
connection cannot be established after the
programmed number of call cycles, the
modem will wait four (4) hours and repeat
the process.
A programmable retry limit is provided that
can limit the total number of times the above
algorithm will be repeated before the meter
no longer attempts to call. The kV Meter will
default to two (2) times through the retry
algorithm unless changed using GE’s
MeterMate Software.
The retry algorithm does not apply to power
outage calls or to test calls.
Programming Phone Numbers
Call Origination Window
The kV™ Meter can store up to three (3)
phone numbers that can be selected by the
meter to place a call to the host software
system. There are five (5) possible ways call
origination can take place. These are
scheduled data calls, event calls, power
restoration calls, test calls, and power outage
calls. Each call type may have both a
primary and secondary phone number. The
primary phone number will be attempted
first, and if no connection can be established,
the meter may then either try the secondary
phone number or go into retry mode (see
below) if no secondary phone number exists.
Phone numbers may be reused (i.e. a single
phone number can be used for all primary
numbers).
A call origination window can be established
that will limit when the kV™ Meter can
originate a call. This window can prevent the
kV™ Meter from making phone calls when a
voice user is likely to need access to the
phone.
Each phone number may be up to 38
characters in length to allow for credit card
calls and other calls requiring long phone
numbers.
Retry Algorithm
If the kV™ Meter attempts to originate a call
using the primary phone number but is
unable to establish a connection for any
reason, it will immediately attempt the
secondary phone number, if supplied. If a
connection cannot be established using this
phone number either, the meter will enter the
following retry algorithm:
The meter will attempt to dial both the
primary and secondary phone number (if
present) up to a programmable five (5) times
each, waiting a random number of minutes
The call origination window is specified as a
start and stop time (HH:MM) on a particular
day of the week, combination days of the
week, or every day of the week. It is not
possible to have different call origination
windows for different days of the week.
Because the kV™ Meter can originate a call
for the purpose of communicating data,
errors/cautions/diagnostics, and reporting
power outages, some control is provided to
customize the kV™ Meter to best meet the
needs of your customer. The kV™ Meter can
be configured to apply the call origination
window to data calls, error/caution/diagnostic
calls, or both types of calls. The call
origination window is not applied to power
outage calls or to test calls.
Note: Demand only kV meters can not
have a call origination window
Data Calls
The kV™ Meter can be configured to
originate a call to report data to the host
software. The meter may be programmed to
originate a call in one of two ways:
1. Call at a specified time and day of the
week - this option enables a call to the host
Page 7
software on a particular day of the week,
combination of days of the week, or every
day of the week at a single specified time.
Using this option, the maximum number of
data calls per day is one.
2. Call on a specific date and time - this
option enables calls to occur on a specified
date at a specified time. Only one date and
time will be stored in the kV™ Meter,
therefore, this field will need to be
reprogrammed during each data call.
The kV™ will attempt to dial the
primary/alternate phone numbers that have
been
programmed
into
the
“Primary/Alternate Data Phone Number” field
using GE’s MeterMate Software.
7.2 Volt Lithium Battery (Safety
Precautions)
•
Do not expose battery to temperatures
above 100 degrees C. Do not incinerate,
puncture, crush, recharge, over
discharge or short circuit the battery
•
The contents are water reactive and the
battery contents can form HCL
(hydrochloric acid), SO2 (sulfur dioxide)
and H2 (hydrogen), upon contact with
water (only when forced open). Do not
expose contents of battery to water. Do
not expose contents to high humidity for
extended periods of time.
•
Dispose of batteries in accordance with
local, state, and federal hazardous waste
regulations. To obtain an MSDS, contact
Manager - Quality and EHS, GE Meter,
130 Main Street, Somersworth, NH
03878-3194, Telephone number (603)
749-8550.
Note: Data calls can not be scheduled on
demand only kV™ Meters
Event Calls
The kV™ Meter can initiate a call to the host
software whenever an error, caution, or
diagnostic is detected by the meter. Using
GE’s MeterMate Software, the kV™ Meter
can be customized to call in on all or
selected events.
The kV™ Meter will attempt to dial the
primary/alternate phone numbers that have
been
programmed
into
the
“Primary/Alternate Event Phone Number”
field using GE’s MeterMate Software.
Power Outage Calls (optional)
The kV™ Meter can be equipped with an
optional dual-cell lithium battery to provide
power outage notification. The life of the
battery will depend on several factors
including the number of outages and the
duration of outages before an outage call is
placed. Under typical use, the battery can be
expected to last for at least fifty (50) phone
calls.
Soft Switch
The optional power outage call feature is
controlled by a Soft Switch. Unless activated,
the power outage feature is not enabled. The
Outage Soft Switch can be purchased by
contacting
your
local
GE
sales
representative. All meters ordered with the
optional power outage call feature will be
supplied with the Outage Soft Switch
enabled.
Outage Definition
The length of time that power must be out
before the kV™ Meter places an outage call
to the host software is programmable from
zero (0) to two hundred fifty-five (255)
seconds. The default time is zero (0), which
means that an outage call will be attempted
as soon as the kV™ Meter goes into power
down mode. This timer should be used for
reference only and is accurate to ± 10%.
Battery Indicator
The kV™ Meter will attempt to dial the
primary/alternate phone number that have
been
programmed
into
the
“Primary/Alternate Outage Phone Number”
field using GE’s MeterMate Software.
It is possible to test the kV™ Meter’s optional
power outage battery. This is a pass/fail test
and is only performed when initiated by the
host software during a communications
session with the meter.
Page 8
Outage Retry Algorithm
If the kV™ Meter outage call to the primary
phone number is unsuccessful the meter will
delay for 2 minutes, then attempt to call the
alternate phone number, if provided.
Alternatively, it will retry the primary number.
If both calls are unsuccessful, the modem
will power down and make no further
attempts to dial the host software.
on a particular day of the week, combination
days of the week, or every day of the week.
It is not possible to have different answer
window for different days of the week.
Note: Demand only kV™ Meter cannot
have an answer window and will behave as
if the answer window is always open.
Number of Rings
Power Outage Delay
A programmable timer is provided with the
optional power outage call feature that can
be used to minimize the number of power
outage calls made by a particular meter for
the same outage.
If enabled, the kV™ Meter will only initiate a
power outage call to the host software after a
programmable timer has expired. The timer
will be initiated after power restoration and
must expire before a power outage call is
initiated. If a power outage occurs before the
timer has expired, no outage call will be
placed and the timer will be reset. This timer
can be configured between zero (0) and two
hundred fifty-five (255) minutes with zero (0)
disabling this feature.
Power Restoration Calls
The kV™ Meter will call the host software
when power has been restored following an
outage if enabled.
Test Calls
Using GE’s MeterMate software and an
optical probe, the kV™ Meter can initiate a
test call to a designated phone number. A
test call may also be initiated over a remote
connection. The call will take place after the
remote session has ended.
The kV™ Meter can be configured to answer
after a programmable number of rings.
Separate limits are provided for the number
of rings before answering for both inside and
outside the answer window.
The number of rings is programmable from
zero (0) to two hundred fifty five (255) where
zero (0) will cause the meter to ignore all
incoming calls.
Answer Lockout Timer
For situations where the kV™ Meter will be
sharing the phone line with a voice user, the
Answer Lockout Timer may be used. This
feature, when enabled using GE’s MeterMate
Software, will cause the kV™ Meter to not
answer incoming phone calls, for a
programmable period of time (0-255
minutes), after it has answered a call but was
unable to establish carrier.
This feature enables a voice user to gain
access to an incoming voice call without
having the meter intercept the call.
Note: GE recommends that the Answer
Lockout Timer be disabled (set to zero)
when the meter is not sharing the phone
line with a voice user.
Call Answer
The kV™ Meter is capable of answering calls
from the host software.
kV RSX Features,
RS-232 Simple Serial
mode
Answer Window
An answer window can be established to
delay or prevent the answering of a call by
the kV™ Meter when it is sharing the phone
line with a voice user. The answer window is
specified as a start and stop time (HH:MM)
The kV RSX Option Board's RS-232 Simple
Serial mode provides a means of remotely
reading and programming the kV Meter over
an electrically isolated RS-232 link. In this
mode the kV RSX contains no
Page 9
programmable features; there are no AMRA
tables in the option board. It simply provides
a pass through communications link to the
kV Meter. In this mode the kV meter can be
communicated with using a 9-pin null
modem cable connected between the kV
RSX communications cable and the RS-232
compatible communications port of the host
device. Refer to the Appendix for
connection details.
Data Rate
The kV RSX Option Board is configured for
8 data bits, 1 stop bit, no parity, and a fixed
baud rate of 9600bps in RS-232 Simple
Serial mode.
kV RSX Features,
RS-485 Simple Serial
mode
The kV RSX Option is configured for 8 data
bits, 1 stop bit, no parity, and a fixed baud
rate of 9600bps in RS-485 Simple Serial
mode.
Warning:
The
kV™
Meter
contains lethal voltages. The
meter
must
be
completely
disconnected from any external
circuits
and the carryover
capacitor completely discharged
before disassembly is attempted.
Failure to observe this practice
can result in serious injury or
death. For more information refer
to the kV™ Meter Installation,
Operation,
and
Maintenance
Guide, GEH 5081A.
kV RSX Installation
The kV RSX Option Board's RS-485 Simple
Serial mode provides a means of remotely
reading and programming the kV Meter over
an electrically isolated, twisted pair, halfduplex, RS-485 link. In this mode the kV
RSX contains no programmable features;
there are no AMRA tables in the option
board. It simply provides a pass through
communications link to the kV Meter. Refer
to the Appendix for connection details.
Data Rate
Installing the kV RSX
in the kV™ Meter
The kV RSX Option Board can only be
installed in “Modem Ready” kV™ Meters.
These meters can be identified by the words
“Modem Ready” which are printed on the left
side of the meter nameplate.
Any combination of the four (4) option
boards may be installed in the kV™ Meter at
one time. These include the I/O-2
Input/Output option board, the LP-2 Load
Profile option board, the kV RSX Option
Board, and the RG-1 Revenue Guard option
board. The I/O-2, LP-2, and kV RSX Option
Board can be combined in an option board
“stack” if necessary.
See Figure 1 for
details.
Page 10
Figure 1: Option board stack
The Revenue Guard option board is not part
of this stack and is not affected by the
presence of other option boards.
Note: The kV RSX Option Board must
always be installed as the inner most option
board (the board closest to the kV™
Meter’s main board).
The kV RSX board is installed as follows:
Figure 4: RS-232 Simple Serial Mode
1.
If the meter is not disassembled, follow
the disassembly instructions described
in the kV™ Meter Installation,
Operation, and Maintenance Guide
(GEH-5081).
2.
Place the bezel face down on a soft,
clean surface to protect the nameplate
and liquid crystal display.
3.
Remove the I/O and LP option boards if
they are present.
4.
The I/O-1 and LP-1 option boards
must not be reused with the kV RSX.
5.
Select the desired mode of operation by
installing the jumper shunts according to
the following:
Figure 5: RS-485 Simple Serial Mode
6.
If the kV RSX Option Board will not be
combined with either the I/O or LP
option boards proceed to step 3. If the
kV RSX Option Board will be installed
with the I/O-2 and/or LP-2 option boards
proceed to the next step.
7.
Place the kV RSX Option Board on a
soft clean surface and install the four (4)
nylon spacers by gently pushing them
into the four (4) holes on the board.
Do not reuse nylon spacers. When
removed, a slight rounding of the
spacer occurs which can greatly
decrease the ability of the spacer to
hold the option board firmly in place.
Figure 2: Location of mode jumpers
8.
If both the LP-2 and I/0-2 option boards
are to be installed, the LP-2 option
board must be installed next. Install it
by engaging the 26 pin connector pins
between the kV RSX Option Board and
the LP-2 option board. Then, after lining
up the nylon spacers on the kV RSX
Option Board with the four (4) holes on
the LP-2 board, snap the option board
into place.
9.
The I/O-2 option board may be installed
directly to the kV RSX Option Board if
the LP-2 option board will not be used
Figure 3: External Modem Mode
Page 11
or, it may be installed directly to the LP2 option board. Either way, the I/O-2
option board is installed in a similar
manner to the LP-2 option board
described in step 6 above.
the slot and up against the base. Make
sure that the cable has been brought up
on the outside of the shroud.
3.
Check the headers on the kV RSX
board to make sure that the pins are not
bent or out of position.
Orient the
smallest black connector such that the
indexed (filled) hole in the black
connector is lined up with the missing
pin in the 4 pin header. Plug the
connector assembly into the header on
the RSX board. Orient the larger black
connector such that the indexed (filled)
hole in the black connector is lined up
with the missing pin in the 6 pin header.
Plug the connector assembly into the
header on the RSX board.
4.
Attach the plastic connector holder as
shown in Figure 7.
The connector
holder snaps should extend through the
holes in the kV RSX board and snap
into place.
10. Depending on whether the installation is
being made to an S-base or A-base
meter, install the appropriate cable
assembly as described below.
For
installation on a switchboard kV Meter,
refer to the switchboard meter
instruction book, GEH-7271.
Installation on S-base Meters
While the meter is unassembled, the S-base
communications cable assembly must be
installed. This cable assembly is installed in
S-base meters as follows:
1.
With the kV™ Meter base facing you,
locate the lower of the two small
knockouts and remove it (see Figure 6:
Locating knockout for cable assembly
on S-Base meters). Enlarge the hole to
a diameter of 0.290 inches. Make sure
the resulting hole is clean.
Figure 6: Locating knockout for cable
assembly on S-Base meters
2.
Locate the end of the cable assembly
with the two small black connectors.
Pass the larger of the black connectors
through the knockout hole from the back
side of the meter base. Next, pass the
smaller black connector through the
same hole and pull until the wire tie is in
Figure 7 : Connector holder placement
5.
Page 12
Check the 30 pin header on the meter
board to make sure that the pins are not
bent or out of position. Adjust any pins
that are out of alignment.
kV™ Meters with 26 pin headers
instead of 30 pin headers cannot be
retrofitted with the kV RSX Option
Board .
6. With the kV RSX Option Board “stack”
in hand, insert the tabs on the kV RSX
Option Board into the slots in the bezel
(see figure 8).
Figure 9 : Check "RS" box
Installation on A-base Meters
While the meter is unassembled, the A-base
communications cable assembly must be
installed. This cable assembly is installed in
A-base meters as follows:
1.
Figure 8: Inserting option boards
With the kV™ Meter base facing you,
locate the knockout on the left side of
the base (see Figure 10) and remove it
by tapping it with a punch. Make sure
the hole is clean and the knockout parts
are removed.
7. Gently lower the board until the 30 pin
connector on the meter and the kV RSX
Option Board are engaged. Make sure
that the two snaps engage the board.
8. Reassemble the meter, except for the
cover, as described in the kV™ Meter
Installation, Operation, and Maintenance
Guide (GEH-5081).
9. Insert and tighten a wire tie around the
cable assembly on the inside of the
meter base to retain the cable assembly.
10. On the right side of the upper nameplate
place an “X” in the box marked “RS” and
replace the cover. See Figure .
11. The meter is now ready to be
programmed using GE’s MeterMate
software.
Figure 10:
Locating knockout for cable
assembly on A-Base meters
2.
Insert the small connectors end of the
cable assembly through the knockout
from the outside of the meter base until
the grommet contacts the knockout.
Make sure that the cable has been
brought up on the outside of the shroud.
3.
Insert the grommet into the knockout
and push until the grommet is fully
seated.
Page 13
4.
5.
Check the headers on the kV RSX
board to make sure that the pins are not
bent or out of position.
Orient the
smallest black connector such that the
indexed (filled) hole in the black
connector is lined up with the missing
pin in the 4 pin header. Plug the
connector assembly into the header on
the RSX board. Orient the larger black
connector such that the indexed (filled)
hole in the black connector is lined up
with the missing pin in the 6 pin header.
Plug the connector assembly into the
header on the RSX board.
Attach the plastic connector holder as
shown in Figure 7.
The connector
holder snaps should extend through the
holes in the kV RSX board and snap
into place.
6.
Follow the steps outlined in the S base
installation for inserting the stack into
the meter. Then, reassemble the meter.
7.
On the right side of the nameplate place
an “X” in the box marked “RS” and
replace the cover. See Figure 9.
8.
The meter is now ready to be
programmed using GE’s MeterMate
software.
Optional
Outage
Battery Installation
Call-in
2.
Place the battery into the battery holder
with the leads extending through the slot
in the battery holder. See Figure 11.
3.
Place the battery and battery holder
behind the communications cable being
careful not to disconnect the cable from
the kV RSX board. Insert the top of the
battery holder under the two top snaps
and press the bottom of the battery
holder until the snaps engage. See
Figure 12 for details.
4.
Place communications cable under
cable holder as shown in Figure 13.
Dress remaining leads by tucking under
bezel.
5.
Replace the cover.
Figure 11: Battery & battery holder assembly
The kV™ Meter can be fitted with an optional
battery pack which will power the kV RSX
Option Board so it can call in during a power
outage. This battery only powers the kV
RSX; the external modem connected to the
kV RSX must be powered by a customer
supplied uninterruptable power source. The
optional battery pack is installed as follows:
1.
Install kV RSX Option Board and cable
per instructions above. Connect the
Lithium battery to the kV RSX Option
Board battery connector, which is next
to where the communications cable
connects. This is a keyed connection
and should not be forced
Figure 12: Battery holder installation
Page 14
I/O-1 Input/Output Option Board
(Obsolete)
The I/O-1 Input/Output option board (GE part
# 9938226002) is now obsolete and has been
replaced by the I/O-2 Input/Output option
board (GE part # 9938226004). The I/O-1
option board cannot be used with the kV™
RSX Option Board. If I/O is needed in a kV™
Meter with a modem, the I/O-2 option board
must be used. See Table 1:
I/O-1
Compatibility for more details.
Figure 13 : Battery cover installation
I/O-1
LP-1
LP-2
kV RSX
√
Option Board Compatibility
√
√
Introduction
√
√
Table 1: I/O-1 Compatibility
The kV™ RSX Option Board may be used in
conjunction with the RG-1 Revenue Guard,
I/O-2 Input/Output, and the LP-2 Load Profile
option boards. In cannot be used with either
the I/O-1 Input/Output, the LP-1 Load Profile
option boards or the kV Internal modem
board. The RSX is used in lieu of the kV
Internal Modem board.
The kV™ RSX Option Board is always
installed directly onto the kV™ Meter. Either
the I/O-2 Input/Output or the LP-2 Load
Profile option board may then connect to the
kV™ RSX Option Board if desired. If all
three option boards are used, the option
boards must be installed in the following
order:
1. kV™ RSX Option Board
2. LP-2 Load Profile option board
3. I/O-2 Input/Output option board
RG-1 Revenue
Board
Guard
Option
The RG-1 Revenue Guard option board may
be used in conjunction with any other kV™
Meter option board including the kV™ RSX
Option Board.
Page 15
I/O-2 Input/Output Option
The I/O-2 Input/Output option board (GE part
# 9938226004) is a direct replacement for
the I/O-1 option board (see above) and was
designed to be compatible with the kV RSX
Option Board. It may be installed directly
onto the kV™ Meter, the kV RSX Option
Board, or to the LP-2, Load Profile option
board. See Table 2: I/O-2 Compatibility for
more details.
The LP-2 Load Profile option board (GE part
# 9938348007) is a direct replacement for
the LP-1 option board (see above) and was
designed to be compatible with the kV RSX
Option Board. It may be installed directly
onto the kV™ Meter or the kV RSX Option
Board. See Table 4: LP-2 Compatibility for
more details.
Option Boards
LP-2
LP-1
LP-2
√
kV RSX
√
√
√
√
√
√
√
Modem
Ready kV
only
Modem
Ready kV
only
The LP-1 Load Profile option board (GE part
# 9938348005) is now obsolete and has been
replaced by the LP-2 Load Profile option
board (GE part # 9938348007). The LP-1
option board cannot be used with the kV
RSX Option Board. If load profile information
is needed in a kV™ Meter with a kV RSX,
the LP-2 option board must be used. See
Table 3: LP-1 Compatibility for more details.
The kV RSX Option Board may be used in
combination with the I/O-2 Input/Output, and
LP-2 Load Profile option boards. See Table
5: kV RSX Compatibility for more details.
Option Boards
KV RSX
(Modem Ready kV
only)
√
√
√
kV RSX
√
√
I/O-2
LP-2
√
√
Option Boards
I/O-2
√
kV RSX Option Board
LP-1 Load Profile Option Board
(Obsolete)
I/O-1
Modem
Ready kV
only
Modem
Ready kV
only
Table 4: LP-2 Compatibility
Table 2: I/O-2 Compatibility
LP-1
√
√
√
kV RSX
√
√
√
√
I/O-2
√
Option Boards
I/O-2
I/O-1
√
√
√
Table 5: kV RSX Compatibility
√
√
Table 3: LP-1 Compatibility
LP-2 Load Profile Option Board
MeterMate Software
Compatibility
The kV RSX Option Board is compatible with
the following software:
1. MeterMate™ Version 2.12 or greater
2. Utility Translation Systems, Inc.’s MV90
Page 16
Testing Meter
Calibration
If the kV RSX is in simple serial mode,
meter calibration can be tested in kV RSX
equipped kV™ Meters as outlined in the
kV™ Meter Installation, Operation, and
Maintenance Guide, GEH 5081B. If the kV
RSX is configured in the external modem
mode, a compatible external modem must
be connected to the kV RSX
communications cable before powering on
the meter to perform calibration. It is
recommended that 20 seconds of settling
time be allowed, after applying voltage,
before making accuracy measurement or
placing the meter into test mode. Users will
see “busy” on the LCD display approximately
17 seconds after voltage has been applied to
the meter. Once the display returns to its
normal scroll, it is safe to begin accuracy
measurements or to place the meter into test
mode.
Meter Installation
The kV™ Meter must be connected to the
external communications device through a
means which will provide both a secure
connection and ease of disconnection for
troubleshooting, meter change out, etc.
Important:
Under no condition should
the communications line be run in a
conduit with power lines or exit the meter
enclosure via the same nipple as the
power lines. Also, for the case where
other optional signal lines are taken from
the kV™ Meter, these other lines should
not be bundled with either the power
lines or the phone line.
For A-base meters, the connection to the
customer
supplied
communications
equipment should be done in a similar
manner. The communications cable for the
A-base terminal block should be taken
immediately to a separate enclosure
dedicated to this specific application.
Test Call
The kV™ Meter equipped with a kV RSX
operating in external modem mode can be
prompted, using GE’s MeterMate Software,
to place a test call to one of the three (3)
phone numbers stored within the meter. The
test call may be initiated using the optical
port or over a remote connection. A red LED
is provided on the kV RSX board that can be
seen from the front of the meter (see Figure
14: kV RSX LED location) and is used to
monitor the progress of the call.
All kV™ Meters with kV RSX option are
supplied with an insulated communications
cable which extends approximately 30
inches out the base on S-base meters and
out of the side of the case on A-base meters.
The communications cable may be
terminated in either an RJ-11 or a DB-9
connector plug.
The communications cable should exit the Sbase meter socket enclosure by the most
direct means and be connected to the
customer
provided
communications
equipment external to the meter enclosure.
Usual practice has a short conduit nipple
extending from the meter enclosure to a
separate, dedicated enclosure where the
external modem is located.
Figure 14: kV RSX LED location
An LED will illuminate when the kV™ Meter’s
external modem
has established a
Page 17
connection
and carrier detected. By
monitoring this LED (as well as any LEDs on
the external modem), correct operation of
the kV RSX, can be verified during meter
installation.
Note: When the kV™ Meter is first
energized at the installation site, the carrier
detect LED will illuminate to indicate that
the kV RSX is properly powered. After the
kV RSX is initialized, the carrier detect LED
will go out. If the LED stays illuminated for
more than 5 seconds, the kV RSX board is
defective and should be replaced.
9938627002. This kit contains the following
material:
Component
kV RSX circuit
board
Cable assembly
Connector holder
PC board
spacers
Wire tie
Instruction sheet
GE Part #
9938498003
Qty
1
9938583002
9938622001
9935026005
1
1
4
9689597010
GEI-101424
1
1
A-base kV RSX Kits
If a communications cable with a DB-9
connector is desired, order GE part number
9938627003. This kit contains the following
material:
Renewal Parts
kV RSX Kits
There are four (4) kV RSX kits that may be
ordered to retrofit a “Modem ready” kV™
Meter. “Modem ready” kV™ Meters will have
“Modem Ready” printed on the meter
nameplate. If the kV™ Meter nameplate
does not have this designation, the meter
can not be retrofitted with a kV RSX board.
GE Part #
9938498003
Qty
1
9938583003
9938622001
9935026005
1
1
4
GEI-101424
1
If a communications cable with an RJ-11
connector is desired, order GE part number
938627004. This kit contains the following
material:
S-Base kV RSX Kits
If a communications cable with a DB-9
connector is desired, order GE part number
9938627001. This kit contains the following
material:
Component
kV RSX circuit
board
Cable assembly
Connector holder
PC board
spacers
Wire tie
Instruction sheet
Component
kV RSX circuit
board
Cable assembly
Connector holder
PC board
spacers
Instruction sheet
GE Part #
9938498003
Qty
1
9938583001
9938622001
9935026005
1
1
4
9689597010
GEI-101424
1
1
Component
kV RSX circuit
board
Cable assembly
Connector holder
PC board
spacers
Instruction sheet
If a communications cable with an RJ-11
connector is desired, order GE part number
Page 18
GE Part #
9938498003
Qty
1
9938583004
9938622001
9935026005
1
1
4
GEI-101424
1
Call-in On Outage Upgrade Kit
Order GE part number 9935143001. This kit
contains the following material:
Component
Outage Battery
Battery Holder
Instruction
Sheet
GE Part #
9938346001
9936888001
GEI-101422
Qty
1
1
1
Other Renewal Parts:
Component
Communications
Cable for SBase Meters,
DB-9 connector
Communications
Cable for SBase Meters,
RJ-11 connector
Communications
Cable for ABase Meters,
DB-9 connector
Communications
Cable for ABase Meters,
RJ-11 connector
Outage Battery
Battery Holder
PC Board
Spacers
GE Part #
9938583001
Qty
1
9938583002
1
9938583003
1
9938583004
1
9938346001
9936888001
9935026105
1
1
100
Page 19
Appendix
External Modem Mode
For correct operation in external modem mode, the kV RSX requires that the operating mode
jumpers be positioned correctly, an external modem be connected to the communications cable
and the setup strings and baud rate be correct for the modem. At the time of power up, the kV
RSX initializes the external modem. If the modem is not present or the set up strings or baud
rate are incorrect, the kV RSX will continue to try to configure the modem. The Modem
Configuration Error bit, in the End Device Mode and Status table of the kV RSX, will be set if the
kV RSX cannot properly configure the external modem.
kV RSX Setup Strings
In External Modem Mode the kV RSX has programmable setup strings which serve to: reset the
external modem device to a known state, initialize it for communications with the kV RSX, setup
call answering and call origination configuration parameters.
External Modem Reset String
The kV RSX is designed to interface with many different external modem devices both domestic
and foreign using telephone or wireless technologies. Because there is no common method of
resetting these various external modems to a known state, the kV RSX provides a programmable
reset string.
Connecting the kV RSX to an external telephone modem will require the use of a 9 pin female to
25 pin male D-sub adapter such as Inmac part #37101 or Global Stock No. THC4496.
Before putting the kV Meter into service it is important to know the reset string and reset state of
the external modem device connected to the kV RSX. The majority of external modem devices
can be reset to their user programmed state by the string "ATZ". This 'z' is the default reset
string value for the kV RSX. Some modems have several user programmed profiles, in which
case the Z is appended with a number to load the desired profile.
Most modems can be reset to their factory default state by "AT&F". If this is the case and the
factory state is desired the 'z' should be reprogrammed with "&F". Some modems have several
factory default profiles, in which case the &F is appended with the number of the desired state.
Some wireless modems only emulate the telephone modem AT command set and do a good job
of resetting themselves on power up. Sending an AT reset command to these modems may
start an undesired, lengthy channel reacquisition process. In these cases it may be best to
program the reset string to all blank characters. This will prevent the kV RSX from sending a
reset string.
In configuring the external modem device to work with the kV RSX it is important to know what
resets the modem and what the reset state is.
Initialization String
The programmable kV RSX initialization string is used to set the external modem to a
configuration required by the kV RSX to control the modem. There are six (6) main functions
that are programmed through the initialization string. These are listed below along with the AT
command that sets the desired configuration in popular telephone modems.
Page 20
Local Echo - Local echo of modem commands must be set to off (E0).
On/Off Hook Control - The external modem is initialized to on hook (H0).
Modem Result Messages - Configure the modem to respond with AT command result
messages (Q0 ).
Format of Result Messages - Configure the modem to respond with text rather than numeric
result messages (V1).
Carrier Detection - Configure the modem to control the carrier detect RS-232 signal line based
on the presence of the carrier signal (&C1 ).
Data Terminal Ready - When using the DB-9 terminated communications cable, configure the
modem to go to go on hook and assume the command mode when DTR is toggled (&D2). If the
RJ-11 communications cable is used, configure the modem to override the DTR state (&D0)
because this cable does not support the DTR signal line.
The default setting for the initialization string is E0H0Q0V1&C1&D2. This should be changed for
cases where the modem in question does not support the default commands. In these cases, the
equivalent command for the modem of interest should be substituted. For external modems
that support error control it is necessary to disable the error control. The AT command to
disable error control should be appended to the initialization string. For external
modems that support data compression and flow control it is necessary to disable both
data compression and flow control. The AT commands to disable data compression and
flow control may be appended to either the initialization string or the Call Answering and
Call Origination Strings. See table 6 for recommendations.
Call Answering Strings
The kV RSX contains two 20 byte strings which can be programmed to accept AT commands
which pertain to configuring the external modem to answer incoming calls. These are initially set
to all spaces.
Call Origination Strings
There are four 20 byte strings which can be programmed to accept AT commands which pertain
to configuring the external modem to originate outbound calls. These are initially set to all
spaces.
CAUTION: The following modem options should NEVER be placed in any meter
modem setup string as you may prevent successful communication with the
meter:
& commands:
S-registers:
Dial modifiers:
E1, H1, Q1
&Sn, &Tn, &Vn, &Wn, &Yn, and &Zn
s3, s4, s5, s14, s16, s21, s23, s24, and s27
s=<n>
Baud Rate
The rate that the kV RSX communicates with the external modem (DTE rate) is configured
through programming of the Answer Baud Rate and the Originate Baud Rate in the kV RSX
AMRA tables. The initial baud rate used to setup the external modem is the Answer Baud Rate,
which is set to 9600 bps at the factory. The Originate Baud Rate also defaults to 9600 bps.
Unless the external modem operates at speeds slower than 9600 bps, these values should
remain at there initial settings. When using slower speed modems it is necessary to reprogram
the Answer and Originate Baud rates to the speed of the modem. For slower DTE speeds it is
necessary to put E0 in the modem reset string following the modem reset command(s).
Page 21
If the answer (and/or originate) connect baud rate is to be other than the DTE rate or if a
particular answer (and/or originate) connect baud rate is desired it must be configured through
the answer (and/or originate) modem string. The RSX will not adjust its DTE rate to that of
the negotiated connection baud rate. This is not a problem for those modems which fix
the DTE rate regardless of the connection rate (DCE rate). For modems that adjust the
DTE rate to the connection rate, the connection rate should be fixed to the DTE rate
through the use of appropriate Call Answering and Call Origination setup strings. See
Table 6 for recommendations.
Typical External Modem Setup Strings
The following table will help configure the most popular external modems for use with the RSX.
In general, modems should be set for error correction disabled, flow control disabled, and data
compression disabled.
USRobotics
Motorola
Hayes
Other (Boca,
Zoom,
Cardinal)
No Flow
Control
Data
Compression
Off
No error
control
Fixed Serial
Port Rate
Setting the
connect rate for
fixed 9600
See external
modem mfr. manual
for other connect
baud rates.
&H0
&K0
&M0
&B1
&N6
&K0 \Q0
%C0
\N1
Not
available
N0 S37=9
&Q0
Not
available
N0 S37=9
1
Not
available
+MS=9,0,9600,9600
2
&K0
&K0
1
%C0
\N1
Table 6 : External Modem Setup Strings
Page 22
Typical Host Modem Setup Strings
The following table will help configure the most popular host modems using MeterMate for DOS.
In general, modems should be set to factory defaults, with command echo suppressed, modem
signals (CD, DTR, DSR) configured for normal operation, and error correction disabled.
USRobotics
Motorola
Hayes
Other (Boca,
Zoom,
Cardinal)
Load
factory
default
Command
Mode
Echo Off
CD
(Carrier
Detect)
Normal
DTR
(Data
Terminal
Ready)
normal
DSR (Data
Set Ready)
always on
No error
correction
&f (&f1)
e0
&c1
&d2
&S0
&m0
&f
e0
&c1
&d2
&S0
\n1
&f
e0
&c1
&d2
&S0
&q0
&f
e0
&c1
&d2
&S0
\n1
1
2
1
Table 7 : Host Modem Setup Strings
1) May be referred to as “Normal operation (no error correction, buffered data)”
2) May be referred to as “Selects direct asynchronous mode (no error correction or speed
buffer)”
Page 23
Figure 15 External Modem Connections for the DB-9 Cable.
Figure 16 External Modem Connections for the RJ-11 Cable
Page 24
RS-232 Simple Serial Mode
RS-232 is used extensively for communications between computers and peripheral devices such
as the mouse, keyboard and etc. Another example is the use of the RS-232 port on a computer
to communicate with the kV meter using the Smartcoupler. The kV RSX, in RS-232 mode,
provides a straightforward, isolated, connection between the kV Meter and the host device. The
permanent connection of the kV Meter to a personal computer, for continuous data collection, is
an example.
The most convenient way to connect the kV RSX to a computer is to connect the kV RSX DB-9
communications cable to the computer's RS-232 port through a 9 pin null modem cable. It is
important to select a null modem cable that is shielded and that the end device (computer)
provide a path from this shield to ground. The shell of the kV RSX DB-9 connector is connected
to the shield which surrounds the wire in this cable. The RS-232 communications distance is
limited to 50 feet.
Figure 17 RS-232 Connections for the DB-9 Cable.
Figure 18 RS-232 Connections for the RJ-11 Cable.
Page 25
RS-485 Simple Serial Mode
RS-485 communications use differential voltage signals to improve on the noise immunity and
distance limitations of RS-232. When fully implemented, RS-485 enables many devices to
share a single communications bus. The kV RSX implementation of RS485 is point to point, with
no multi-drop capability at this time. It is useful if the communications distance is greater than
the 50 feet provided by an RS-232 link. Also, RS-485 communications are more immune to the
disturbances that are experienced in an electrically noisy environment.
The kV RSX communications cable does not connect directly to a computer port, although some
embedded controllers have a dedicated RS-485 port. Typically, an RS-485 Serial Interface Card
is installed in the host computer to provide the correct RS-485 signals over a twisted pair of
wires. The connection to the kV RSX is half duplex, using two wires. For half-duplex, the signal
lines marked RX+ and TX+ must to be connected together and the signal lines RX- and TX- must
be connected together, as shown in Figure 20. Terminating resistors are not required for this
application and should not be used.
The kV RSX, RS-485 communications, have been tested using a host computer and the
RS422/485 Serial Interface Plus, Part # IC050C. This serial interface card is made by:
Black Box Corporation
P.O. Box 12800
Pittsburgh, PA 15241
Though not yet tested with the kV RSX, other serial interface cards and RS-232 to RS-485 signal
converters are available from:
B & B Electronics Manufacturing Company
P.O. Box 1040
Ottawa, IL 61350
http://www.bb-elec.com
Telebyte Technology, Incorporated
270 Pulaski Road
Greenlawn, NY 11740
http://www.telebyteusa.com
The EIA-485 standard does not specify a standard connector for RS-485 communications.
There are two styles of communications cables available for the kV RSX. One is terminated with
a DB-9 connector and the other with a “telephone type” four conductor RJ-11 connector. If the
environment is electrically noisy, use of the kV RSX DB-9 communications cable is
recommended. The shell of the DB-9 connector is connected to the shield which surrounds the
wire in this cable. Over the run of the cable, the shielding should be continuous to the end
device, where it should be grounded.
Page 26
Figure 19 RS-485 Connections for the DB-9 Cable.
Figure 20 RS-485 Connections for the RJ-11 Cable.
Page 27
Determining the Mode of an Installed kV RSX
The kV RSX option board is not detected by the meter in either RS-232 or RS-485 simple serial
modes. There are no tables in the option board when it is in either of the simple serial modes.
There is no way to read the meter and find out what mode the option board is in. The mode can
be determined by observing the LED at the time of power up, one (1) blink for external modem
mode, two (2) blinks for RS-232 simple serial mode, and four (4) blinks for RS-485 simple serial
mode.
If it is not possible to cycle the power to observe this LED and the mode is not known, the mode
can be determined through process of elimination. First, read the kV meter using the
Smartcoupler and determine whether the kV RSX is detected by the meter through reading the
GE Device Table, installed options field. If using MeterMate, the presence of the kV RSX will be
reported if the board is in external modem mode. If the meter is detecting the kV RSX, then the
option board is in external modem mode. Otherwise, the kV RSX is in one of the two (2) simple
serial modes. To determine if the kV RSX is in RS-232 simple serial mode, try reading the meter
using a null modem cable connected between a PC and the communications option board. If the
meter can be read this way, it is in RS232 simple serial mode. If this fails, the kV RSX option
board is in the RS-485 simple serial mode.
Page 28
Using MeterMate Version 2.12 with the kV RSX
MeterMate 2.12 can be used to build programs for both the kV Modem and the kV RSX option
boards. The following instructions pertain to building MeterMate programs for the kV RSX option
board operating in the external modem mode of operation.
Default MeterMate Program for kV RSX
Begin by creating a basic kV RSX default program from which all kV RSX programs will be built.
This process assumes that the default MeterMate programs have not been modified since
MeterMate was installed.
Begin by starting the MeterMate Windows program builder. Select Editors, Modem Option
Editor, Table Name “Default”. After the Modem Option: Default screen opens, edit the Modem
Configuration form so that it appears as follows:
Save this modified table with the table name “RSXdef”. Whenever building a new kV RSX
MeterMate program, select the “RSXdef” Modem Option Table as a starting point.
Page 29
External Modem Reset
Under the Call Answering options, the RSX Reset setup string defaults to z. This sends an ATZ
to the external modem to set the external modem to its stored profile. If the factory, rather than
the stored profile, is desired change the RSX Reset string to &F. In this case the Modem
Configuration form will be:
Page 30
Programming to use the Optional RJ-11 Cable
If the program is being built for a kV RSX that uses a communications cable with the RJ-11
(telephone jack) rather than the DB-9 (9 pin) connector, change the RSX Init setup string in the
Modem Configuration form as follows:
Page 31
Index
A
A-base kV RSX kit, 18
A-base meters, 6, 12, 13, 17
Appendix, 20
B
retry algorithm, 7
Revenue Guard option board, 10, 15
S
S-base kV RSX kit, 18
S-base meters, 6, 12, 17
scheduled data call, 7
setup strings, 6
battery, 8, 9, 14, 15
battery holder, 14, 15
battery test, 9
T
C
test call, 7, 9, 17
test mode, 17
tone dialing, 6
calibration, 17
E
event call, 7
F
FCC, 2
I
I/O option board, 10, 11, 12, 15, 16
K
knockout, 12, 13, 14
L
Light Emitting Diodes, 17, 18
Load profile option board, 10, 11, 12, 15, 16
M
MeterMate, 2, 3, 6, 7, 8, 9, 16, 17
O
option boards, 6, 10, 11, 12, 13, 15, 16
P
PC board spacers, 19
phone number, 7, 8, 9, 17
power outage, 6, 7, 8, 9, 14
pulse dialing, 6
R
restoration calls, 7
Page 32
Page 33