Download White Mountain DVP48FP7 Owner`s manual

Transcript
INSTALLATION INSTRUCTIONS
AND OWNER’S MANUAL
GAS-FIRED
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING: If not installed, operated and maintained
in accordance with the manufacturer’s instructions,
this product could expose you to substances in fuel
or from fuel combustion which can cause death or
serious illness.
DIRECT VENT, ZERO CLEARANCE
GAS FIREPLACE HEATER
MILLIVOLT STANDING PILOT
DVP(42,48)FP3(0,1,2,3)(N,P)-4
DIRECT IGNITION
DVP(42,48)FP5(0,1,2,3)N-1
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death or
property damage.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
—Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
INTERMITTENT PILOT
DVP(42,48)FP7(0,1,2,3)(N,P)-5
REMOTE RF
DVP(42,48)FP9(1,3)(N,P)-5
UL FILE NO. MH30033
This appliance may be installed in
an aftermarket, permanently located,
manufactured home (USA only) or mobile
home, where not prohibited by state or local
codes.
This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with other
gases, unless a certified kit is used.
WARNING
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and shall
be installed for the protection of children and other at-risk
individuals.
Note: Barrier required, but may be sold separately.
Page 1
TABLE OF CONTENTS
SECTIONPAGE
IMPORTANT SAFETY INFORMATION............................................................................................................................................. 3
SAFETY INFORMATION FOR USERS OF LP GAS......................................................................................................................... 4
REQUIREMENTS FOR MASSACHUSETTS.................................................................................................................................... 5
INTRODUCTION............................................................................................................................................................................... 6
SPECIFICATIONS............................................................................................................................................................................. 7
VENT SYSTEM IDENTIFICATION.................................................................................................................................................... 8
SPECIAL VENT SYSTEMS............................................................................................................................................................... 9
FIREPLACE DIMENSIONS............................................................................................................................................................... 9
CLEARANCES................................................................................................................................................................................ 10
LOCATING FIREPLACE...................................................................................................................................................................11
GAS SUPPLY.................................................................................................................................................................................. 12
INSTALLATION........................................................................................................................................................................... 13-16
VENTING FIREPLACE - TOP.................................................................................................................................................... 17-19
EXAMPLES - TOP VENT RUN........................................................................................................................................................ 20
VENTING EXAMPLES WHEN USING DVA47 ADAPTOR.............................................................................................................. 21
VENTING FIREPLACE - REAR....................................................................................................................................................... 22
EXAMPLES - REAR VENT RUN..................................................................................................................................................... 23
REAR VENT CONVERSION........................................................................................................................................................... 24
VENT CLEARANCES...................................................................................................................................................................... 25
8” VENTING FRAMING AND FINISHING................................................................................................................................... 26-27
6 ⅝” VENTING FRAMING AND FINISHING............................................................................................................................... 28-29
TERMINATION CLEARANCES....................................................................................................................................................... 30
HORIZONTAL TERMINATION......................................................................................................................................................... 31
VERTICAL TERMINATION......................................................................................................................................................... 32-33
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS........................................................................................................... 34-36
DVVK-5F FLEX VENT INSTRUCTIONS......................................................................................................................................... 37
PROPANE/LP GAS CONVERSION................................................................................................................................................ 38
LOG PLACEMENT (4 LOG SET).................................................................................................................................................... 39
MILLIVOLT SYSTEM OPERATING INSTRUCTIONS................................................................................................................ 40-41
MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM........................................................................................................ 42
MILLIVOLT SYSTEM STANDING PILOT LIGHTING INSTRUCTIONS.......................................................................................... 43
MILLIVOLT SYSTEM STANDING PILOT TROUBLESHOOTING................................................................................................... 44
DIRECT IGNITION LIGHTING INSTRUCTIONS............................................................................................................................. 45
DIRECT IGNITION WIRING DIAGRAM.......................................................................................................................................... 46
OPTIONAL REMOTE CONTROL.................................................................................................................................................... 46
INITIAL START UP GAS LINE PURGE........................................................................................................................................... 47
DIRECT IGNITION TROUBLESHOOTING..................................................................................................................................... 47
DIRECT IGNITION PROPANE/LP GAS CONVERSION................................................................................................................. 48
IPI ELECTRONIC SYSTEM OPERATING INSTRUCTIONS........................................................................................................... 49
IPI ELECTRONIC SYSTEM WIRING DIAGRAM............................................................................................................................ 50
INTERMITTENT PILOT LIGHTING INSTRUCTIONS..................................................................................................................... 51
INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING....................................................................................... 52-54
RF OPERATING INSTRUCTIONS.................................................................................................................................................. 55
RF MAINTENANCE INSTRUCTIONS............................................................................................................................................. 56
RF WIRING DIAGRAM.................................................................................................................................................................... 57
RF STANDING PILOT LIGHTING INSTRUCTIONS....................................................................................................................... 58
MAINTENANCE AND SERVICE...................................................................................................................................................... 59
DVP42FP(3,5,7,9) PARTS LIST................................................................................................................................................. 60-61
DVP48FP(3,5,7,9) PARTS LIST................................................................................................................................................. 62-63
PARTS VIEW................................................................................................................................................................................... 64
MASTER PARTS DISTRIBUTOR LIST........................................................................................................................................... 65
HOW TO ORDER REPAIR PARTS................................................................................................................................................. 65
FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION.............................................................................................. 66-67
JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS.......................................................................................................... 68
OPTIONAL BRICK LINER INSTALLATION INSTRUCTIONS......................................................................................................... 68
ACCESSORIES............................................................................................................................................................................... 69
QUICK REFERENCE GUIDE..................................................................................................................................................... 70-71
WARRANTY..................................................................................................................................................................................... 72
Page 2
31455-8-0415
IMPORTANT SAFETY INFORMATION
Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.
DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED
DANGER: Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
CAUTION: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
WARNING: Indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
NOTICE: Addresses practices not related to personal injury.
•
If this appliance is installed directly on carpeting, tile or
other combustible material other than wood flooring the
appliance shall be installed on a metal or wood panel
extending the full width and depth of the appliance.
The base referred to above does not mean the fireproof
base as used on wood stoves. The protection is for rugs
that are extremely thick and light colored tile.
•
Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to avoid
burns or clothing ignition.
•
Young children should be carefully supervised when they
are in the same room as the appliance.
•
Clothing or other flammable material should not be placed
on or near the appliance.
•
Adequate accessibility clearances for servicing and proper
operation.
•
This appliance must not share or be connected to a flue
serving a separate solid-fuel burning appliance.
•
Keep the area around your appliance clear of combustible
materials, gasoline and other flammable vapor and liquids.
•
Under no circumstances should any solid fuels (wood,
coal, paper or cardboard etc.) be used in this appliance.
•
Due to high temperatures the appliance should be located
out of traffic and away from furniture and draperies.
•
The glass front or any part removed for servicing the
appliance must be replaced prior to operating the
appliance. Work should be done by a qualified service
person.
•
Keep burner and control compartment clean.
•
Vent cap is hot while fireplace is in operation.
•
Installation and repair should be done by a qualified
service person. The appliance should be inspected
before use and at least annually by a qualified service
person. More frequent cleaning may be required due
to excessive lint from carpeting, bedding materials, etc.
It is imperative that control compartments, burners and
circulating air passageways of the appliance be kept
clean.
•
Do not put anything around the fireplace that will obstruct
the flow of ventilation air.
•
Clearance in accordance with local installation codes
and the requirements of the gas supplier.
31455-8-0415
•
The flow of combustion and ventilation air must not be
obstructed in any way.
•
Young children should be carefully supervised when
they are in the same room as the appliance. Toddlers,
young children, and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at-risk individuals in the house. To
restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers young children, and
other at-risk indivicuals out of the room and away from
hot surfaces.
•
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and
shall be installed for the protection of children and other
at-risk individuals. Barrier required, may be sold separately.
•
If the barrier becomes damaged, the barrier shall be
replaced with the manufacturer’s barrier for this appliance.
•
Any safety screen, guard, or barrier removed for servicing an appliance must be replaced prior to operating the
appliance.
•
Do keep the appliance area clear and free from
combustible material, gasoline and other flammable
vapors and liquids.
•
Do examine venting system periodically and replace
damaged parts.
•
Do make a periodic visual check of pilot and burners.
Clean and replace damaged parts.
•
CAUTION: The glass used in your fireplace is
tempered glass. If the glass is cracked or damaged in
any way, it should be replaced only with a complete
glass frame assembly from Empire. See parts list on
Pages 69 to 73 for ordering.
•
Do not use this fireplace if any part has been under
water. Immediately call a qualified service technician to
inspect the heater and to replace any part of the control
system and any gas control which has been under water.
•
Any safety screen or guard removed for servicing
an appliance must be replaced prior to operating the
appliance.
Page 3
SAFETY INFORMATION FOR USERS OF LP GAS
Propane (LP-Gas) is a flammable gas which can cause fires
and explosions. In its natural state, propane is odorless and
colorless. You may not know all the following safety precautions
which can protect both you and your family from an accident.
Read them carefully now, then review them point by point
with the members of your household. Someday when there
may not be a minute to lose, everyone’s safety will depend
on knowing exactly what to do. If, after reading the following
information, you feel you still need more information, please
contact your gas supplier.
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
• Do not operate electric switches, light matches, use your phone.
Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as
basements. When you have reason to suspect a gas leak, keep
out of basements and other low areas. Stay out until firefighters
declare them to be safe.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the fire department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, let the service man and firefighters check for escaped
gas. Have them air out the area before you return. Properly
trained LP-Gas service people should repair the leak, then
check and relight the gas appliance for you.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must find out if you
can smell the odorant in propane. Smoking can decrease your
ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors in
the area mask the gas odor. People may not smell the gas odor
or their minds are on something else. Thinking about smelling a
gas odor can make it easier to smell.
The odorant in LP-Gas is colorless, and it can fade under
some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can filter the odorant.
Odorants in LP-Gas also are subject to oxidation. This fading can
occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That will
take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels. Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of LP-Gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it to
find out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas
Dealer.
• If you are not qualified, do not light pilot lights, perform service,
or make adjustments to appliances on the LP-Gas system. If
you are qualified, consciously think about the odor of LP-Gas
prior to and while lighting pilot lights or performing service or
making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the odor
if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should
be particularly alert and careful when new tanks or cylinders
are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are filled and allowed to set too
Page 4
long before refilling. Cylinders and tanks which have been out
of service for a time may develop internal rust which will cause
odor fade. If such conditions are suspected to exist, a periodic
sniff test of the gas is advisable. If you have any question
about the gas odor, call your LP-Gas dealer. A periodic
sniff test of the LP-Gas is a good safety measure under
any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is under
no vapor pressure), turn the tank valve off immediately. If the
container valve is left on, the container may draw in some air
through openings such as pilot light orifices. If this occurs, some
new internal rusting could occur. If the valve is left open, then
treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container
before it goes completely empty or having it refilled before it is
completely empty.
31455-8-0415
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed
in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination
is less than seven feet above finished grade in the area of the
venting, including but not limited to decks and porches, the
following requirements shall be satisfied:
3. SIGNAGE. A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight feet above grade directly in line with
the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print
size no less than 1/2 inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level where
the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated
or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or
structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property owner
to secure the services of qualified licensed professionals for
the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
floor level.
b. In the event that the requirements of this subdivision
can not be met at the time of completion of installation,
the owner shall have a period of thirty days to comply
with the above requirements; provided, however, that
during said thirty day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a) 1
through 4.
(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board;
and
2. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(d)
MANUFACTURER
REQUIREMENTS
GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not
provide the parts for venting the flue gases, but identifies
“special venting systems”, the following requirements
shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instruction.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the
completion of the installation.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/
UL 2034 listed and IAS certified.
31455-8-0415
Page 5
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner fill out and mail warranty card supplied
with the fireplace.
3. Installer should show owner how to start and operate the fireplace.
This direct vent gas fireplace heater is designed to operate with
all combustion air being siphoned from the outside of the building
and all exhaust gases expelled to the outside of the building. The
information contained in this manual pertains to all models and gas
control systems unless otherwise noted.
WARNING: This unit is not for use with solid fuels.
Appliance Certification
This fireplace is design certified in accordance with American
National Standard/CSA Standard ANSI Z21.88/CSA 2.33 and by
Underwriters Laboratories as a Direct Vent Gas Fireplace Heater
and shall be installed according to these instructions.
Consult your local building code agency, prior to installation, to ensure
compliance with local codes-including permits and inspections.
The fireplace, when installed, must be electrically grounded in
accordance with local codes or, in absence of local codes, with the
National Electric Code ANSI/NFPA 70 or Canadian Electric code,
CSA C22.1, if an external electrical source is utilized.
These models may be installed in a bedroom or bed-sitting room
in the U.S.A. and Canada.
Qualified Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be
performed only by a qualified agency. The term “qualified agency”
means any individual, firm, corporation or company which either in
person or through a representative is engaged in and is responsible for
(a) the installation or replacement of gas piping or (b) the connection,
installation, repair or servicing of equipment, who is experienced in
such work, familiar with all precautions required and has complied
with all the requirements of the authority having jurisdiction.
State of Massachusetts: The installation must be made by
a licensed plumber or gas fitter in the Commonwealth of
Massachusetts.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not
shown on the rating plate is the responsibility of the person
and company making the change.
Important
All correspondence should refer to complete Model Number, Serial
Number and type of gas.
High Altitude
When installing this unit at an elevation above 2000 feet (in the
United States) it may be necessary to decrease the input rating by
changing the existing burner orifice to a smaller size. Generally,
input should be reduced 4 percent for each 1000 feet above sea
level. However, if the heating value of the gas has been reduced,
this general rule may not apply. Check with local gas utility for proper
orifice size identification.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m)
When installing this unit at an elevation above 4500 feet (in Canada),
check with local authorities.
Consult your local gas utility for assistance in determining the proper
orifice for location.
Preparation
This direct vent gas fireplace and its components are tested and
safe when installed in accordance with this Installation Manual.
Report to your dealer any parts damaged in shipment, specifically
check glass condition. Do not install unit with damaged, incomplete,
or substitute parts. Read all instructions before starting installation
and follow these instructions carefully during installation to insure
maximum benefit and safety. Failure to follow them will void your
warranty and may present a fire hazard.
The warranty will be voided by, and the warranter disclaims any
responsibility for the following actions:
• Installation of any damaged fireplace or vent system component.
• Modification of the fireplace or direct vent system.
• Installation other than as instructed by Empire Comfort Systems,
Inc.
• Improper positioning of the logs, glass door or decorative rock.
• Installation and/or use of any component part not manufactured
or approved by manufacturer.
The installation must conform with local codes or, in the absence of
local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA
54* Natural Gas and Propane Installation Code, or CSA B149.1 in
Canada. *Available from the American National Standards Institute,
Inc. 11 West 42nd St., New York, N.Y. 10036.
WARNING: ANY CHANGE TO THIS FIREPLACE OR ITS
CONTROLS CAN BE DANGEROUS.
Improper installation or use of the fireplace can cause
serious injury or death from fire, burns, explosions, or carbon
monoxide poisoning.
Page 6
31455-8-0415
SPECIFICATIONS
DVP42
28,000 (Nat)
28,000 (LP)
19,000 (Nat)
22,000 (LP)
8.2
5.5
DVP48
30,000 (Nat)
30,000 (LP)
20,500 (Nat)
24,000 (LP)
8.8
6.0
#38 (.1015) P-203 - (DVP42FP(3,7,9))
3.25 mm P-306 - (DVP42FP5)
1/8"(3.2mm)
#37 (.1040) P-213 - (DVP48FP(3,7,9))
#34 P-270 - (DVP48FP5)
1/8"(3.2mm)
#52 (.0635") P-185
FULL OPEN
34 3/4"(883mm)
1.65MM P-250
FULL OPEN
34 3/4"(883mm)
43"(1092mm)
49"(1245mm)
19 7/8"(505mm)
1/2 NPT
19 7/8"(505mm)
1/2 NPT
Input Btu/hr Maximum
Btu/hr Minimum (millivolt only)
KWH (Maximum)
(Minimum)
NAT.
Orifice
Air Shutter Opening
LP
Orifice
Air Shutter Opening
Height without standoff
Width
Depth
Gas Inlet Shutoff Valve (Pipe)
NOTE: Air shutter settings are factory minimum settings. Some venting configurations may require minor air shutter adjustments for
optimum performance.
Remote Control Options
& Accessories
FRBC
FRBTC
TMW
TRW
FWS-1
FREC
FBB4
Description
Millivolt/IP Battery Remote ON/OFF
Millivolt/IP Battery Remote T-Stat
Millivolt/IP WIRELESS Wall Thermostat
Millivolt/IP REED SWITCH Wall Thermostat
Direct Ignition/Millivolt/IP Wall Switch
Electric Remote
Blower Assembly
FIREPLACE BARRIER SCREENS
SCREEN MODEL
DESCRIPTION
FIREPLACE MODELS USED ON
DVFB42TBL
Fireplace Barrier Screen, Matte Black
DVP42FP
DVFB48TBL
Fireplace Barrier Screen, Matte Black
DVP48FP
Note: A firescreen is required for operation of the appliance, but are sold separately. Follow the instructions that come with your firescreen
for proper installation.
31455-8-0415
Page 7
VENT SYSTEM IDENTIFICATION
Begin the vent system installation by selecting the type of venting
to be installed and the path that it will take. Verify that clearances
are met throughout the path of the venting system. Determine if the
fireplace is to be vented out the top or out the rear.
NOTICE: Some fireplaces cannot be vented out the rear of the
fireplace.
Determine how the vent system will be terminated out the side of
the house or through the roof. Verify clearances for the termination.
When selecting a vent system for use with the fireplace, refer to
the “Special Vent Systems” section in this manual to determine
what systems are acceptable. Check all clearances and venting
components. Identify if any problems existing in the vent system.
Use Figure 22 on page 17 for top venting, or Figure 35 on page
22 for rear venting to eliminate issues after installation. Check pipe
diameter on vent system and fireplace to verify the size is the same.
NOTICE: All outer connection joints must be sealed with
aluminum tape, screws or silicone sealant rated above
300°F/149°C. The inner flue joints do not require any sealant.
*Note: If using three 90° elbows during horizontal
termination, see Figure 30.
Special Venting Components (Simpson Duravent)
See Empire Comfort Systems Retail Price List for Simpson Duravent part numbers and pricing.
Special DV Vent Kits Available from Empire Comfort Systems, Inc. dealers.
Figure 1
DVVK-4VP
Direct-Vent Fireplace Vent Kit - Vertical, Includes SD46DVA-VCH,
SD46DVA-F6 and SD46DVA-SC
DVVK-4RE
Direct-Vent Fireplace Vent Kit, Thru-the-wall, for 5 to 13-3/4 inch
wall thickness
DVVK-4TP
Direct-Vent Fireplace Vent Kit for Top Vent, Thru-the-wall, 8 to 11
inch wall thickness, Includes SD46DVA-HC, SD46DVA-E90,
SD46DVA-09, SD46DVA-08A and SD46DVAWT
Direct-Vent Fireplace Vent Kit for Top Vent, Thru-the-wall, 5 to 7
DVVK-4TSP inch wall thickness, Includes SD46DVA-HC, SD46DVA-E90,
SD46DVA-06 and SD46DVA-WT
DVVK-5RP
Direct-Vent Fireplace Vent Kit for Rear Vent, 6 to 12 inch wall thickness, Includes SD-58DVA06, SD-58DVAHC, and SD58DVAWTEC
DVVK-5TP
Direct-Vent Fireplace Vent Kit for Top Vent, Thru-the-wall, 4 to
6 inch wall thickness, Includes SD58DVAE90, SD58DVAHC,
SD58DVA06, and SD58DVAWTEC
DVVK-5VP
Direct Vent Fireplace Vent Kit - Vertical, Includes SD58DVAVCH,
SD58DVASC, and SD58DVAF6
DVVK-5F
Horizontal Flex Vent Kit (4’ Flex) (1.22m)
Note: All DVVK-4 Vent Kits require use of the DVA47 adaptor.
Page 8
31455-8-0415
SPECIAL VENT SYSTEMS
The following vent systems are acceptable for use with the
DVP (42,48) series fireplaces:
Simpson Duravent® GS 5" - 8"
American Metal Products 5" - 8"
Selkirk Direct-Temp® 5" - 8"
Security Secure Vent® 5" - 8"
Excel DV Venting 5” - 8”
BDM 5” - 8”
Empire Flexvent Kit DVVK-5F
The following vent systems are acceptable for use with the DVA-47
adaptor vertically off top of fireplace only:
Simpson Duravent® GS 4" - 6⅝"
American Metal Products 4" - 6⅝"
Selkirk Direct-Temp® 4" - 6⅝"
Security Secure Vent® 4" - 6⅝"
Excel DV Venting 4” - 6⅝”
BDM 4” - 6 5/8”
Empire Horizontal Round Termination Kit DVVK-4RE
Note: DVA-47 Not for use with Flex Vent Kits. For use with Simpson
Duravent vents only.
FIREPLACE DIMENSIONS
A
B
DVP42
43”
(1092mm)
40”
(1016mm)
25 1/16”
37 5/8”
(636 mm) (956 mm)
34 3/4”
(883 mm)
19 7/8”
26”
(505 mm) (660 mm)
7 1/8”
(181 mm)
26 1/2”
13 1/4”
(826 mm) (337 mm)
12 3/4”
(324 mm)
DVP48
49”
(1245mm)
46”
(1168mm)
25 1/16”
37 5/8”
(636 mm) (956 mm)
34 3/4”
(883 mm)
19 7/8”
26”
(505 mm) (660 mm)
7 1/8”
(181 mm)
32 1/2”
16 1/4”
(826 mm) (413 mm)
12 3/4”
(324 mm)
31455-8-0415
C
D
E
F
Figure 2
G
H
I
J
K
Page 9
CLEARANCES
Clearance to Combustibles
Back
0" (0 mm)
Side
0" (0 mm)
Floor
0" (0 mm)
Top Stand-off
0" (0 mm)
Top Framing Edge
3" (76 mm)
Mantel Chart
Figure 5
Note A: See Figure 5 for maximum mantel depth.
Note B: See Figure 5 for minimum height above unit.
Figure 3
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the fireplace. The flow of heat can
ignite combustibles.
Clearances
Clearance from top front edge of fireplace to ceiling is 36”
Clearance from side of fireplace to adjacent sidewall is 6”. See
Figure 6.
(914mm)
Figure 6
Figure 4
Page 10
31455-8-0415
LOCATING FIREPLACE
NOTICE: Island and Room Divider installation is possible as long
as the horizontal portion of the vent system does not exceed 20 feet
with a minimum vertical run of 8 feet. See details in Venting Section.
When you install your Direct Vent Fireplace in Room divider or Flat
on wall corner positions, a minimum of 6 inches clearance must
be maintained from the perpendicular wall and the front edge of
the appliance.
CABINET
INSTALLATION
CORNER
INSTALLATION
ISLAND
INSTALLATION
ANGLED CORNER
INSTALLATION
FLUSH WALL
INSTALLATION
ROOM DIVIDER
INSTALLATION
Figure 7
31455-8-0415
Page 11
GAS SUPPLY
The gas pipeline can be brought in through the right or left side of
the appliance. Consult the current National Fuel Gas Code, ANSI
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat.
L.P.
Nat.
L.P.
0-10ft
0-3m
1/2"
12.7mm
3/8"
9.5mm
1/2"
12.7mm
3/8"
9.5mm
11-40ft
4-12m
1/2"
12.7mm
1/2"
12.7mm
5/8"
15.9mm
1/2"
12.7mm
41-100ft
13-30m
1/2"
12.7mm
1/2"
12.7mm
3/4"
19mm
1/2"
12.7mm
101-150ft
31-46m
3/4"
19mm
1/2"
12.7mm
7/8"
22.2mm
3/4"
1.9 mm
Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a
flexible appliance connector cannot exceed three feet in length.
Figure 8
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate,
contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTE: The millivolt gas controls are equipped with a captured screw
type pressure test point, therefore it is not necessary to provide a
1/8” test point up stream of the control.
On direct ignition valves, hex plugs may be replaced with hose fittings
for pressure checks, then reinstalled before operating fireplace.
When using copper or flex connector use only approved fittings.
The appliance and it’s individual shut off valve must be disconnected
from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system
by closing its individual manual shut off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5kPa).
CAUTION: If one of the procedures results in pressures in
excess of 1/2 psig (14” w.c.) (3.5 kPa) on the fireplace gas valve,
it will result in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5” w.c. (.871kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 4.5” w.c.
(1.120kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484kPa). Propane gas models will have a manifold
pressure approximately 10.0” w.c. (2.49kPa) at the valve outlet
with the inlet pressure to the valve from a minimum of 10.8” w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0” w.c. (3.484kPa).
Gas Supply Pressure (inches w.c.)
Minimum
Normal
Maximum
Natural Gas
4.5"
7.0"
*14.0"
LP (Propane)
10.8"
11.0"
*14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas
3.5"
LP (Propane)
10.0"
Figure 9
*NOTE: Remote “RF” Models - 10.5” w.c. maximum
Page 12
31455-8-0415
INSTALLATION
Framing and Finishing
1. Choose unit location.
2. Frame in fireplace with a header across the top. It is important
to allow for finished face when setting the depth of the frame.
See Figure 10B.
3. Attach fireplace to frame using nailing flange. Preset depth to
suit facing material (adjustable to 1/2”, 5/8” or 3/4” depths).
NOTICE: Fireplace must mount flush to facing material. If facing
material requires more depth than 3/4”, mark and drill two 1/8”
holes into fireplace side at appropriate depth. Bend standoff
tabs as needed to move fireplace flush with facing material.
See Figure 10A.
4. Use eight 1/2” hex-head screws supplied in hardware package,
to screw through slotted holes in nailing flange and then screw
into pre-drilled holes on fireplace side. Measure from face of
fireplace to face of nailing flange to determine final depth.
Vent Pipe Clearance
Note: Maintain one inch of clearance around top vent pipe. See
Figure 11. For rear vent, maintain a minimum 1” clearance to the
bottom and sides of the vent, and 3” clearance to combustibles
above the vent pipe. See Figure 12.
Figure 11 - Top Vent
Figure 12 - Rear Vent
Figure 10A
31455-8-0415
Figure 10B
Page 13
INSTALLATION
Flush Mount Mantel Installation
The fireplace must extend 3/4” beyond finished wall surface when
using a flush mount mantel. Refer to Figure 13 to locate nailing
flanges on fireplace sides. Mark and drill two 1/8” holes into fireplace
side to mount each nailing flange. Use eight 1/2” hex-head screws
supplied in hardware package to attach nailing flanges to fireplace
sides.
"A"
DVP42
DVP48
37 3/4"
37 3/4"
"B"
43 3/8"
49 3/8"
"C"
19 7/8"
19 7/8"
Figure 14
Attention: Add 3-3/4” to “A” dimensions when using a flush mantel
base.
Figure 13
Attention: When fireplace is installed in optional full cabinet mantel
or corner mantel the four nailing flanges shown in Figure 10A will
not be installed on the side of outer casing. The fireplace will be
attached to the full cabinet mantel or corner mantel with the two
nailing flanges located on the top of the outer casing assembly.
Framing
Fireplace framing can be built before or after the fireplace is set in
place. Framing should be positioned to accommodate wall covering
and fireplace facing material. The fireplace framing should be
constructed of 2 x 4 lumber or heavier. The framing headers may
rest on the fireplace standoffs. Refer to Figure 14 for minimum
framing dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS, AND WALL COVERING DETAILS
BEFORE FRAMING CONSTRUCTION BEGINS.
Framing dimension "A" includes a three inch clearance for
standoffs on firebox. After installing firebox into framing,
the finished wall surface must cover the three inch opening
above the firebox.
Page 14
WARNING: If a base or mantel is not used and the
appliance is installed directly on carpeting, tile or other
combustible material other than wood flooring, it shall be
installed on a metal or wood panel extending the full width and
depth of the appliance. The vertical dimension in Figure 14
must be adjusted when a metal or wood panel is placed
beneath the appliance.
Finishing
Finish the walls with the material of your choice. Figure 5 on page 10
shows the minimum vertical and corresponding maximum horizontal
dimensions of mantels or other combustible projections above the
top front edge of the fireplace.
Only non-combustible materials may be used to cover the black
fireplace front.
WARNING: When finishing the fireplace never obstruct or
modify the air inlet/outlet louvers in any manner. Provide
adequate clearances around air openings into the combustion
chamber.
CAUTION: If the joints between the finished wall and the
fireplace surround (top and sides) are sealed, a 300°F minimum
sealant material must be used. These joints are not required to
be sealed. Only non-combustible material (using 300°F minimum
adhesive if needed), can be applied as facing to the fireplace
surround.
31455-8-0415
INSTALLATION
Flush Wall Installation
Attention: Cold climate installation recommendation:
When installing this unit against a non-insulated exterior
wall, it is recommended that the outer walls be insulated to
conform to applicable insulation codes.
Vent Runs
In planning the installation for the fireplace, it is necessary to install
certain components before the appliance is completely positioned
and installed. These include the direct vent system, gas piping for
the appliance and the electrical wiring. (If the fan option is used.)
The appliance can be mounted on any of the following surfaces:
1. A flat, hard combustible (burnable) surface.
2. A raised wooden platform.
3. Four corner supports. (Example: Four concrete masonry blocks.)
These supports must be positioned so they contact all four
perimeter edges on the bottom of the unit (if allowed by local
codes).
NOTICE: Discard insulation and retainer when venting from
the top of the fireplace.
TOP, 90° ELBOW WITH HORIZONTAL TERMINATION
Figure 15
Combustible Surround Installation
Figure 17
Figure 16
Note: For mantelshelf requirements, see Figure 5 on page 10.
31455-8-0415
Page 15
INSTALLATION
REAR ONLY, STRAIGHT OUT THE BACK
"A"
"B"
CORNER INSTALLATION TOP, 90° ELBOW TO HORIZONTAL
OUT THE WALL
MODEL
6"(152mm)
5 1/8"(130mm) to 6 /2"(165mm)
DVP 42,48
9"(229mm)
8 1/8"(206mm) to 91/2"(241mm)
DVP 42
12"(305mm) 11 1/8"(283mm) to 12 1/2"
(317mm)
DVP 42
Figure 18
TOP, 90° ELBOW TO HORIZONTAL OUT THE WALL
Dim.
DVP42
DVP48
A
45 3/8"
1152mm
49 5/8"
1260mm
B
32 1/8"
816mm
35 1/8"
892mm
C
13 3/8"
34 mm
15 1/2"
39 mm
D
64 1/8"
1628mm
70 1/8"
1781mm
Figure 20
CORNER INSTALLATION REAR, 45° ELBOW
TO HORIZONTAL OUT THE WALL
"A"
"B"
"C"
6"(152mm)
11 1/4"(286mm) to
12 3/4"(324mm)
4 3/4"(121mm) to
6 1/4"(159mm)
9"(229mm)
14 1/4"(362mm) to
15 3/4"(400mm)
7 3/4"(197mm) to
9 1/4"(235MM)
12"(305mm)
17 1/4"(438mm) to
18 3/4"(476mm)
10 3/4"(273mm) to
12 1/4"(311mm)
Figure 19
DVP42
"A"
"B"
6"(152mm) 4"(102mm) to
5 1/2"(140mm)
9"(229mm) 6"(152mm) to
7 /2"(191mm)
12"(305mm) 9"(229mm) to
10 1/2"(267mm)
DVP48
"B"
4"(102mm) to
5"(127mm)
6"(152mm) to
7 1/2"(191mm)
9"(229mm) to
10 1/2"(267mm)
Figure 21
Page 16
31455-8-0415
VENTING FIREPLACE - TOP
Venting Graph (Dimensions in Feet)
To Use the Vent Graph
1. Determine the height of the center of the horizontal vent
pipe. Using this dimension on the Sidewall Vent Graph,
locate the point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line to
the bottom of the graph.
3. Select the indicated dimension, and position the unit in
accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 35 feet,
the horizontal run to the outer wall flange must not exceed
6.5 feet.
EXAMPLE B:
If the vertical dimension from the floor of the unit is 6.5 feet,
the horizontal run to the outer wall flange must not exceed
14.5 feet.
Special Note: For each 45 degree elbow installed in the
horizontal run, the length of the horizontal run MUST be
reduced by 18" (45cm). This does not apply if the 45 degree
elbows are installed on the vertical part of the vent system.
Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal
vent length is 20' and if two 45 degree elbows are required
in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per
side wall installation is two. These elbows can be installed
in either the vertical or horizontal run.
Note: On vertical venting the first elbow does not get counted.
31455-8-0415
Acceptable vertical and horizontal vent run.
(40' maximum vertical and 20' maximum horizontal)
Unacceptable vertical and horizontal vent run.
Figure 22
Page 17
VENTING FIREPLACE - TOP
Below Grade Installation
When it is not possible to meet the required vent terminal clearances
of 12” (305mm) above grade level, a snorkel kit is recommended.
It allows installation depth down to 7” (178mm) below grade level.
The 7” (178mm) is measured from the center of the horizontal vent
pipe as it penetrates through the wall.
Ensure the sidewall venting clearances are observed. If venting
system is installed below ground, we recommend a window
well with adequate and proper drainage to be installed around
the termination area.
Figure 24
Examples of possible venting systems using two 90° elbows.
V is listed as minimum vertical dimensions and H1 + H2 is listed
as total of maximum horizontal dimensions. The maximum vertical
and horizontal distances for two 90° elbows as shown in Figure
25 is 20 feet.
Attention: Refer to Figure 22 for additional venting requirements.
TYPICAL BASEMENT INSTALLATION
Figure 23
Examples of possible venting systems using one 90° elbow. Eight
feet is listed as minimum vertical vent run with 20 feet of maximum
horizontal vent run. Vertical dimensions are based on centerline to
centerline of pipe. Horizontal dimensions are based on centerline
of pipe to end of termination.
Figure 25
Page 18
31455-8-0415
VENTING FIREPLACE - TOP
SEE FIGURE 22 FOR
PERMISSIBLE “H” AND “V”
DIMENISONS.
Figure 27
Figure 26
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE
WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW
OFF TOP OF FIREPLACE
FIREPLACE
SERIES
DVP42FP
DVP48FP
FIREPLACE
SERIES
DVP42FP
DVP48FP
HARD ELBOW DIMENSIONS
"A"
"B"
"C"
43-1/2"
5"
7"
(1105mm) (127mm)
(178mm)
43-1/2"
5"
7"
(1105mm) (127mm)
(178mm)
FLEX PIPE 90 DEGREE BEND
"A"
"B"
"C"
46"
5"
7" (178mm)
(1143mm) (127mm)
46"
5"
7"
(1143mm) (127mm)
(178mm)
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12” (305mm) high x 10” (254mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination. See Figure 26. When locating the hole it must be noted
that the bottom of the cap must be 12” (305mm) above the ground
level, and top of the cap must be no less than 18” (457mm) below a
combustible projection, and no closer than 9” (229mm) to any wall
running parallel to vent termination. See Figure 27.
31455-8-0415
Figure 28
Page 19
EXAMPLES - TOP VENT RUN
Figure 30
Figure 29
Figure 31
Page 20
31455-8-0415
VENTING EXAMPLES WHEN USING DVA47 ADAPTOR
Vertically Off Top of Fireplace Only
Simpson Duravent® venting only.
Figure 33
Figure 32
DVA47 ADAPTOR
Example
H1 = 2ft
V1 = 20ft
H = 2ft V = 20ft
Figure 34
31455-8-0415
Page 21
VENTING FIREPLACE - REAR
Venting Graph (Dimensions in Feet)
To Use the Vent Graph
1. Determine the height of the center of the horizontal
vent pipe. Using this dimension on the Sidewall
Vent Graph, locate the point it intersects with the
slanted graph line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
unit in accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is
12 feet, 4 inches the horizontal run to the outer wall
flange must not exceed 12 feet, 3 inches.
EXAMPLE B:
If the vertical dimension from the floor of the unit is
6 feet, 9 inches the horizontal run to the outer wall
flange must not exceed 6 feet, 6 inches.
Special Note: For each 45 degree elbow installed
in the horizontal run, the length of the horizontal
run MUST be reduced by 18" (45cm). This does
not apply if the 45 degree elbows are installed on
the vertical part of the vent system. Reduce 3' for
every 90° elbow.
Example: According to the chart the maximum
horizontal vent length is 20' and if two 45 degree
elbows are required in the horizontal vent it must
be reduced to 17'.
The maximum number of 45 degree elbows permitted
per side wall installation is two. These elbows can
be installed in either the vertical or horizontal run.
Page 22
Acceptable vertical and horizontal vent run.
Unacceptable vertical and horizontal vent run.
Figure 35
31455-8-0415
EXAMPLES - REAR VENT RUN
Model
Maximum Pipe
Length H1
DVP42
24"
DVP48
24"
Figure 38
Figure 36
Model
Maximum Pipe
Length H1
DVP42
24"
DVP48
24"
Figure 39
Figure 37
31455-8-0415
Page 23
REAR VENT CONVERSION
Figure 40
Converting flue take-off to rear venting
When switching out the flue and inlet vent collars to run horizontally
off the rear vent, the following steps must be taken.
1. Remove the inlet vent collar (8 screws) and flue collar (4 screws)
from the top of the fireplace, and set to the side.
2. Remove the inlet cover plate and flue cover plate located on
the back of the fireplace. These will be used to close the top
flue and inlet openings.
3. Insert the insulation retainer bracket and insulation into the top
flue pipe before reinstalling the flue cover plate over the top
flue with 4 screws.
Page 24
4. Reinstall the inlet cover plate over the top inlet opening with 4
screws. See illustration above.
5. Install the flue collar assembly to the rear flue with 4 screws.
6. Install the inlet vent collar to the rear of the fireplace with 8
screws.
7. This completes the conversion for a rear vent application.
WARNING: For top vented installations, the insulation and
retainer are to be removed from the flue pipe and discarded.
31455-8-0415
VENT CLEARANCES
Figure 41
A = *Clearance above grade, veranda, porch, deck or balcony
[*12 inches (30cm) minimum]
B = clearance to window or door that may be opened [*12 inches
(30cm) minimum for appliances < 100,000 Btuh (30kW)
C = clearance to permanently closed window [minimum 12
inches (30cm) recommended to prevent condensation on
window]
D = vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24 inches (60 cm)
from the center of the terminal [18 Inches (46 cm) minimum
E = clearance to unventilated soffit [12 inches 30cm) minimum]
F = clearance to outside corner [See Page 30]
G = clearance to inside corner [See Page 30]
H = *not to be installed above a meter/regulator assembly
within 3 feet (90cm) horizontally from the center-line of the
regulator
J = clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance [*12 inches
(30cm) minimum for appliances ≤ 100,000 Btuh (30 kW)
36 inches (90cm) minimum for appliances > 100,000 Btuh
(30kW)]
K = clearance to a mechanical air supply inlet [* 6 feet (1.8m)
minimum]
L = †clearance above paved sidewalk or a paved driveway
located on public property [*7 feet (2.1m) minimum]
M= clearance under veranda, porch, deck, or balcony [*12
inches (30cm) minimum ¥]
† a vent shall not terminate directly above a sidewalk or
paved driveway which is located between two single family
dwellings and serves both dwellings*
¥ only permitted if veranda, porch, deck, or balcony, is fully
open on a minimum of 2 sides beneath the floor*
* as specified in CGA B149 Installations Codes or ANSI
Z223.1. Note: Local Codes or Regulations may require
different clearances.
Distances are to non-combustible surfaces unless otherwise indicated.
I = clearance to service regulator vent outlet [*6 feet (1.8m)
minimum]
31455-8-0415
Page 25
8" VENTING FRAMING AND FINISHING
Installing Support Brackets
A horizontal pipe support MUST BE used for each 3 feet of horizontal
run. The pipe supports should be placed around the pipe and nailed
in place to framing members. There MUST BE a 3 inch clearance
to combustibles above 8 inch diameter pipe and elbows and 1 inch
clearance on both sides and bottom of the 8 inch diameter pipe to
combustibles on all horizontal pipe sections and elbows.
Vertical runs of this vent systems must be supported every 4 feet
above the appliance flue outlet by wall brackets attached to the 8
inch vent pipe and secured with nails or screws to structural framing
members.
Figure 43
Vertical runs of this system which pass through ceilings require
the use of ONE ceiling firestop at the hole in each ceiling through
which the vent passes.
Position a plumb bob directly over the center of the vertical vent
component and mark the ceiling to establish the center point of the
vent. Drill a hole or drive a nail through this center point and check
the floor above for any obstructions such as wiring or plumbing
runs. Reposition the appliance and vent system, if necessary, to
accommodate ceiling joists and/or obstructions.
Figure 42
Installing Firestops
Firestops are required for safety whenever the vent system passes
through an interior wall, an exterior wall, or a ceiling. These firestops
act as a firebreak heat shield and as a means to insure that minimum
clearances are maintained to the vent system.
Cut a 10 1/2 inch x 10 1/2 inch hole through the ceiling, using the
center point previously marked. Frame the hole with framing lumber
the same size as the ceiling joists. See Figure 44. If the area above
the ceiling is NOT an attic, position and secure the ceiling firestop on
the ceiling side of the previously cut and framed hole. See Figure
45. If the area above the ceiling is an attic, position and secure the
firestop on top of the previously framed hole. See Figure 46.
NOTE: Remove insulation from the framed area in the attic before
installing the firestop and/or vent pipes.
Horizontal runs in the vent system which pass through either interior
or exterior walls, require the use of wall firestops on both sides of
the wall through which the vent passes.
Cut an appropriate sized hole in the wall. See Figure 43. Position
the firestop on the interior side of the wall for the hole.
Attention: Wall firestop hole is off-set towards bottom of wall
opening. Secure with nails or screws. Continue the vent run through
the firestop. See Figure 43.
Page 26
31455-8-0415
8" VENTING FRAMING AND FINISHING (continued)
Figure 44
Figure 46
See Horizontal Termination Page 31 and Vertical Termination
Pages 32 and 33.
Figure 45
31455-8-0415
Page 27
6 ⅝" VENTING FRAMING AND FINISHING
Installing Support Brackets
A horizontal pipe support MUST BE used for each 3 feet of horizontal
run. The pipe supports should be placed around the pipe and nailed
in place to framing members. There MUST BE a 3 inch clearance to
combustibles above 6 ⅝ inch diameter pipe and elbows and 1 inch
clearance on both sides and bottom of 6 ⅝ inch pipe to combustibles
on all horizontal pipe sections and elbows.
Vertical runs of this vent systems must be supported every 4 feet
above the appliance flue outlet by wall brackets attached to the
6 ⅝ inch vent pipe and secured with nails or screws to structural
framing members.
Figure 48
Vertical runs of this system which pass through ceilings require the
use of one ceiling firestop at the hole in each ceiling through which
the vent passes.
Position a plumb bob directly over the center of the vertical vent
component and mark the ceiling to establish the center point of the
vent. Drill a hole or drive a nail through this center point and check
the floor above for any obstructions such as wiring or plumbing
runs. Reposition the appliance and vent system, if necessary, to
accommodate ceiling joists and/or obstructions.
Figure 47
Installing Firestops
Firestops are required for safety whenever the vent system passes
through an interior wall, an exterior wall, or a ceiling. These firestops
act as a firebreak heat shield and as a means to insure that minimum
clearances are maintained to the vent system.
Cut a 10 inch x 10 inch hole through the ceiling, using the center
point previously marked. Frame the hole with framing lumber the
same size as the ceiling joists. See Figure 49. If the area above the
ceiling is NOT an attic, position and secure the ceiling firestop on
the ceiling side of the previously cut and framed hole. See Figure
50. If the area above the ceiling is an attic, position and secure the
firestop on top of the previously framed hole. See Figure 51.
NOTE: Remove insulation from the framed area in the attic before
installing the firestop and/or vent pipes.
Horizontal runs in the vent system which pass through either interior
or exterior walls, require the use of wall firestops on both sides of
the wall through which the vent passes.
Position the firestops on both sides of the 10 inch x 11 inch hole,
previously cut. Secure with nails or screws. The heat shields of the
firestops MUST BE placed towards the top of the hole. Continue
the vent run through the firestops. See Figure 48.
Figure 49
Page 28
31455-8-0415
6 ⅝" VENTING FRAMING AND FINISHING (continued)
Figure 50
31455-8-0415
Figure 51
See Horizontal Termination Page 31 and Vertical Termination
on Pages 32 and 33.
Page 29
TERMINATION CLEARANCES
Termination clearance for buildings with combustible and noncombustible exteriors.
Figure 52
Vertical Sidewall Installations
Important! Minimum clearance between vent pipes and combustible materials is 3" (76mm) on top, and 1" (25mm) on bottom and sides.
Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must extend outward so that
the horizontal vent terminal is located flush to, or behond the outcrop siding..
Information on Various Venting Routes and Components
Important: It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain
limitations as to vent configurations apply and must be strictly adhered to.
The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.
The maximum horizontal vent run is 20 feet (457 cm) when the vertical vent rise is 8 feet (244 cm). See Figure 22, page 17.
Venting terminals shall not be recessed into wall or siding.
Page 30
31455-8-0415
HORIZONTAL TERMINATION
NOTE: Termination cap should pass through the wall firestop from
the exterior of the building. Adjust the termination cap to
its final exterior position on the building.
WARNING: Termination cap must be positioned so that
arrow is pointing up.
Attach the termination cap with the four wood screws provided.
Before attachment of the termination, run a bead of silicone sealant
rated above 250°F on its outside edge too, so as to make a seal
to the exterior wall.
NOTE: Wood screws can and should be replaced with appropriate
fasteners for use on stucco, brick, concrete or other types
of siding.
CAUTION: If exterior walls are finished with vinyl siding, (or
materials that could become discolored or warp) it is necessary
to install a vinyl siding standoff.
The vinyl siding standoff will be installed between the vent termination
and the exterior wall. See Figure 53. This horizontal vent termination
bolts onto the flat portion of the vinyl siding standoff, so an air space
will exist between the wall and the termination cap.
Figure 53
31455-8-0415
Page 31
VERTICAL TERMINATION
Locate and mark the center point of the venting pipe. Using a nail
on the underside of the roof and drive this nail through this center
point. Make the outline of the roof hole around this center point.
NOTE: Size of the roof hole dimensions depend on the pitch of
the roof. There must be a 1 inch clearance (25mm) to the
vertical pipe sections. This clearance is to all combustible
material.
Cover the opening of the vent pipe and cut and frame the roof hole.
Use framing lumber the same size as the roof rafters and install the
frame securely. Flashing anchored to frame must withstand high
winds. The storm collar is placed over this joint to make a water-tight
seal. Non-hardening sealant should be used to completely seal this
flashing installation.
Determining Minimum Vent Height Above the Roof.
WARNING: Major U.S. building codes specify minimum
chimney and/or vent height above the roof top. These minimum heights are necessary in the interest of safety. These
specifications are summarized in Figure 54.
Figure 55
ROOF PITCH
H (Min.)
General Maintenance
Conduct an inspection of the venting system semi-annually.
Recommended areas to inspect are as follows:
1. Check areas of the venting system which are exposed to
the elements for corrosion. These will appear as rust spots
or streaks and, in extreme cases, holes. These components
should immediately be replaced.
2. Remove the cap and shine a flashlight down the vent. Remove
any bird nests or other foreign material.
3. Check for evidence of excessive condensate, such as water
droplets forming in the inner liner and subsequently dripping
out at joints. Condensate can cause corrosion of caps, pipe
and fittings. It may be caused by having excessive lateral runs,
too many elbows and exterior portions of the system being
exposed to cold weather.
4. Inspect joints to verify that no pipe sections or fittings have been
disturbed and, consequently, loosened. Also, check mechanical
supports, such as wall straps or plumbers’ tape for rigidity.
Flat to 6/12
12" (305 mm)
Venting terminal shall not be recessed into a wall or siding.
6/12 to 7/12
15" (381 mm)
Over 7/12 to 8/12
18" (457 mm)
A removable panel or other means must be provided in the enclosure
for visual inspection of the flue connection.
Over 8/12 to 16/12
24" (610 mm)
Over 16/12 to 21/12
36" (914 mm)
Figure 54
Note that for steep roof pitches, the vent height must be increased.
In high wind conditions, nearby trees, adjoining roof lines, steep
pitched roofs, and other similar factors can result in poor draft, or
down-drafting. In these cases, increasing the vent height may solve
this problem.
NOTE: This also pertains to vertical vent systems installed on the
outside of the building.
Slide the vertical vent cap over the ends of the vent pipe and secure.
See Figure 56.
When terminating the vent cap near an exterior wall or overhang,
maintain minimum clearances as shown in Figure 55.
Page 32
31455-8-0415
VERTICAL TERMINATION
Installing the Vent System in a Chase
A chase is a vertical box-like structure built to enclose the gas
appliance and/or it’s vent system. Vertical vent runs on the outside of
a building may be, but are not required to be installed inside a chase.
Vertical Through the Roof Applications
Your Gas Fireplace has been approved for:
a) Vertical installations up to 40 feet in height.
b) Two sets of 45 degree elbow offsets within these vertical
installations. From 0 to a maximum of 8 ft. a vent pipe can be
used between elbows.
c) Wall straps must be used to support offset pipe every 4’.
This application will require that you first determine the roof pitch
and use the appropriate venting components.
Figure 56
CAUTION: Treatment of firestop spacers and construction
of the chase may vary with the type of building. These instructions
are not substitutes for the requirements of local building codes.
Therefore, your local building codes must be checked to determine
the requirements for these steps.
NOTE: When installing this vent system in a chase, it is always good
building practice to insulate the chase as you would the outside
walls of your home. This is especially important for cold climate
installations. Upon completion of building your chase framing,
install the vent system by following the instructions in this manual.
Remember to build the chase large enough so that minimum
clearance of combustible materials (including insulation) to the vent
system are maintained.
Figure 57
Reassembly and Resealing Vent Pipe System
Attach vent pipe to inlet and outlet vent adaptor on fireplace in either
the vertical or horizontal position, replace horizontal and vertical pipe
lengths, elbows and horizontal or vertical termination kit.
All vent system components lock into place by sliding the concentric
pipe section with four equally spaced interior beads onto the appliance
collar or previously installed component end with four equally spaced
indented sections. When the internal beads of each starting outer
pipe line up, rotate pipe section clockwise 90° (approximately three
inches). The vent pipe is now locked together.
Continue replacing components per the vent system configuration.
Be certain that each succeeding vent component is securely fitted
and locked into the preceding component in the vent system.
31455-8-0415
Page 33
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS
NOTICE: For top vent installation only: Use of a DVA47 adaptor is required.
CAUTION: Sharp edges, use protective gloves when
installing.
Tools Needed for Installation:
Sheet metal snips
5/16” nut driver
Phillips head screwdriver - #2
High temperature sealant or furnace cement rated for continuous
use at 1,000oF minimum
Measuring tape
Parts Verification
See parts list on page 36 to verify components included in this vent
kit prior to installation.
NOTICE: A DVA47 adaptor must be used in conjunction with the
DVVK4RE (top vent connection only). See Figure 59.
Figure 58
NOTICE: If installing onto wood, lap, or vinyl siding, the vinyl siding
kit should be used (sold separately, part number DV-822).
The vinyl siding vent kit, DV-822, is available from Empire Comfort
Systems, Inc. The depth is 3” (76mm), which enables the vent
cap to be extended away from vinyl siding or projections. The wall
depth plus the additional 3” (76mm) depth of the vinyl siding vent
cap extension should not exceed a total depth of 13 3/4” (349mm).
If wall depth exceeds 13 3/4” (349mm), extend system using
6 5/8” (168mm) x 4” (102mm) rigid venting (See Fireplace Instructions for approved lengths) See Figure 59.
Installing Wall Thimble/Firestop Assembly
1. Fix fireplace to permanent location. If using rigid venting system,
install up to the location where it will exit the building.
2. Cut hole in wall for wall thimble/firestop assembly (Figure 58)
into your combustible wall. Note: On brick or block exterior wall
a 7” (178mm) diameter hole needs to be cut.
Measure the total wall thickness to determine whether or not the
extension thimble is to be used. If the combustible wall depth
is over 5 3/8” (137mm), then the extension thimble should be
used. See Figure 58.
3. Install the wall thimble assembly through the framed opening so
the firestop plate is on the interior wall (Figure 58). Telescope
section should extend all the way through the exterior wall.
Attach with four 10 x 1” screws.
4. When placing the vent cap on an exterior wall covered with
combustibles such as wood, lap, or vinyl siding, install the vinyl
siding kit to the exterior wall sheathing.
Figure 59
Cutting Vent Tubes
This is the most important part of the installation. With the
fireplace (and the rigid venting system if used) fixed to its permanent location, the 6 5/8” (168mm) diameter air inlet tube and the 4”
(102mm) diameter flue outlet tube are to be marked and cut using
the following procedure.
5. Attach the inlet tube to the outside mounting plate. Align
tinnerman clips on the tabs of the air inlet tube to the holes
on outside mounting plate, and fix with two #10 x 1/2” screws.
6. With the vinyl siding kit installed to wall (if necessary), insert
the 6 5/8” (168mm) diameter tube with outside mounting plate
attached through hole in wall. Connect to collar on fireplace or
rigid vent system. Measure between wall or vent cap extension
and outside mounting plate. See Figures 60 and 61.
Page 34
31455-8-0415
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS
Figure 60
Figure 61
7. Remove outside mounting plate with tube attached from wall.
Mark and cut the extra length of the 6 5/8” (168mm) diameter
tube from the opposite end. Do not crimp or enlarge tube.
8. Attach the 4” (102mm) diameter flue outlet tube onto the rigid
venting system or directly to fireplace. Ensure the 4” (102mm)
diameter flue outlet tube is placed as far as possible onto the
rigid venting system. Mark the 4” (102mm) diameter flue outlet
tube 2 1/2” (64mm) beyond the vinyl siding kit or wall. See
Figure 61. Remove the 4” (102mm) diameter flue outlet tube
from rigid venting system. When installing directly to fireplace,
tape gasket needs to be used.
31455-8-0415
9. Mark or wrap tape completely around the tubes at the marked
points to help in making a true cut. Do not crimp or enlarge
tubes.
10. From outside: Push the 6 5/8” (168mm) diameter inlet tube/
mounting plate onto end of rigid venting system to correct
position. Fasten the outside mounting plate to the vinyl siding
kit or wall with four 10 x 1 1/2” screws. (Ensure upward slope).
11. From inside: Attach the inlet tube to the collar on the back of the
fireplace (or the rigid venting system) using three self tapping
screws.
12. Seal the 4” (102mm) diameter flue outlet tube. Follow instructions and diagram. See Figure 62.
13. Fasten 4” (102mm) diameter flue outlet tube in place. Do not
“twist” the flue outlet tube into the fireplace collar (or rigid venting system). Hold the tube by the seam and push in using a
perpendicular “rocking” motion. This ensures the seam on the
tube stay intact.
14. Fasten vent cap end using three 10 x 1/2” screws to mounting
plate.
Sealing 4” (102mm) Diameter Flue Outlet Tube
Figure 62
NOTICE: Tape gasket to be applied prior to installing to fireplace
flue outlet tube only. Tape gasket should not be used when mating
the flue outlet tube to a rigid venting system.
Page 35
DVVK-4RE VENT KIT INSTALLATION INSTRUCTIONS
Follow correct option according to venting method.
Connecting Directly to Fireplace
If the air inlet and flue outlet tubes are to be connected directly to
the unit (no rigid venting system is being used), then the gasket
provided must be used to seal the 4” (102mm) flue outlet tube.
Peel the paper off the self-adhesive gasket and then wrap it around
the end of the tube (if tube was cut, it is recommended to use cut
end) as shown in Figure 62. Pull the gasket tight at all times while
wrapping it around tube. The gasket ends should align, to form a
complete seal. The overlapped section should NOT come in contact with the seam in the tube. Apply high temperature sealant to
the opposite end of the tube (on the inside of the tube). The end
with the gasket will attach to the back of the unit. Continue with
Step 13.
Connecting to Rigid Vent System
If the air inlet and flue outlet tubes are to be connected to a rigid
venting system (and not directly to the back of the unit), then do
not use the gasket provided. High temperature sealant should be
applied to the outside of the 4” diameter (102mm) flue outlet tube
(if tube was cut, it is recommended to use cut end) and to the inside of the tube on the end that connects to the vent cap.
PARTS LIST
INDEX
NUMBER
PART
NUMBER
DESCRIPTION
1
DV769
Vent Cap Assembly
2
19193
Outside Mounting Plate
3
19194
Air Inlet Tube
4
DV524
Flue Outlet Tube
5
19196
Firestop/Thimble Assembly
6
20527
Gasket
Figure 63
Page 36
31455-8-0415
DVVK-5F FLEX VENT INSTRUCTIONS
The DVVK-5F FLEX VENT KIT includes the following components:
• (1) Horizontal Termination Cap
• (1) 4-foot section of Flex vent with spacers (5” flue/8” outer
pipe) with flue adapter collar
• (1) Wall Firestop/Thimble Assembly
• Hardware pack that includes band clamps and screws
Flex venting can be installed either vertically or horizontally
off of the DVP Series fireplaces. When installing a horizontal
vent run from top connections, maintain at least ½” rise for
every 12” of vent run. When venting horizontal off the rear
vent connections, allow a minimum rise of 2”. Refer to the
Figure 53 when mounting termination near vinyl siding.
CAUTION: Always stretch and secure venting with wire or
metal strapping to ensure that the horizontal runs do not sag.
If space permits, it is generally easier to attach venting in the
top vent configuration.
Because of sharp edges, always use gloves when handling
the flex vent components.
Vent connections should overlap a minimum of 1” for proper
sealing.
Always follow the general venting requirements for vent terminal location, vent lengths, and clearance to combustible
materials.
INSTALLATION
1. Unpack vent components and check that all items are
included.
2. Check to see that the vent spacer springs are located around
the flue vent at 8” and 12” intervals along its length. See
Figure 64. If not, stretch the spacer springs to about 15” long
and wrap them around the flue, then interlock the ends of
each spring about 2”. See Figure 65. Maintain equal distance
between spring spacers.
high. The minimum combustible clearance from the horizontal
vent is 1” from sides and bottom, and 3” above the vent pipe.
See Figure 67.
5. In most cases, after determining the length of the vent that
is needed, it may be easier to install the flue and outer vent
pipes to the Termination Cap first, then from the outside, feed
the venting through the wall to the fireplace.
6. If the venting is to long, trim off any excess vent before
attaching the vent end connectors.
7. Attach the Termination Cap to the outside of the house.
CAUTION: Do not use force when installing the Horizontal
Vent Termination into the flex venting. Always stretch venting
out first, then cut off excessive vent material prior to sliding
the vent termination into the flue and inlet venting. Forcing
the termination cap into the flex venting will deform the flue
venting, which will restrict the exhaust gases, and cause
improper operation of the fireplace.
8. Prior to making the vent connections, apply high temperature
sealant (1000 degree F min.) to the vent connections before
securing with the band clamps provided. Note: the flue pipe
end without the adapter is to be installed to the Termination
Cap.
9. Apply sealant to the outside of the flue pipe adapter and
connect to the flex flue pipe. Then insert the adapter into the
fireplace flue. Secure flue adapter to the fireplace flue with a
minimum of two screws provided. See Figure 66.
10. Attach the Outer Vent pipe to the 8” diameter collar on the
fireplace with a large band clamp provided. Sealant may also
be used on the outer vent connections.
11. Check all vent connections for tightness. Make sure horizontal
venting has the proper rise and combustible clearances
required. Refer to venting charts in fireplace instruction
manual.
Figure 64
Figure 66
Figure 65
3. Use existing 8” diameter inlet collar to attach outer vent pipe.
4. Install the Wall Firestop/Thimble assembly as required
through the wall. Refer to the venting charts in the fireplace
manual to determine the proper height and size of the vent
opening. The minimum opening should be 10” wide by 12”
31455-8-0415
Figure 67
Page 37
PROPANE/LP GAS CONVERSION
Maxitrol Valve Conversion (Direct Ignition)
A
Model
AIR SHUTTER
SETTINGS
BURNER ORIFICE
Opening "A"
Propane/LP Orifice
DVP42
Full Open
#52
DVP48
Full Open
#51
Figure 69
Figure 68
Page 38
31455-8-0415
LOG PLACEMENT (4 LOG SET)
Before you begin: If you are installing logs into the DVP42 or DVP48
model then this fireplace is supplied with a set of four ceramic fiber
logs. Do not handle these logs with your bare hands. Always wear
gloves to prevent skin irritation from ceramic fibers. After handling
logs, wash your hands gently with soap and water to remove any
traces of fiber.
The positioning of logs is critical to safe and clean operation of this
fireplace. Sooting and other problems may result if the logs are not
properly and firmly positioned in the fireplace. Please refer to Figure
70, Figure 71, and Figure 72 and corresponding WARNING, when
completing the following log placement steps.
1.
2.
3.
4.
5.
6.
Remove top louver, grasp louver, lift and pull forward.
Lower bottom louver, lift and hinge forward.
Release two glass frame spring clamps at bottom of firebox
Place rear (#1) log onto two pins on rear log support.
Place left, front (#2) log onto two left, front pins on burner pan.
Place right, front (#3) log onto two right, front pins on burner
pan.
7. Place Branch (#4) onto one pin on rear log and one on front
left log (#2).
8. Place decorative rock in front of grates and sides of main burner.
Figure 71
WARNING: Failure to position the parts in accordance with
this diagram or failure to use only parts specifically approved
with this appliance may result in property damage or personal
injury.
ATTENTION: Do not place decorative rock on logs or on burner.
The decorative rock should only be placed on the fireplace floor.
9. After all logs are properly positioned, place small “dime” size
pieces of Rockwool lightly across the front round “blueflame”
ports. Place the ember material (Rockwool pieces) side by side.
Do not stack more than one layer of embers across the burner
ports. See Figure 70.
10. Replace glass door onto firebox.
11. Secure the two glass frame spring clamps at bottom of firebox.
12. Align the tabs on top louver brackets with slots in front posts
to secure top louver.
13. Close bottom louver. Lift slightly to engage the end tabs into
the slots in fireplace sides to close louver panel.
Figure 72
LOG SET PARTS LIST
PART NO.
INDEX
NO.
DVP42
DVP48
1
R10349
R10357
REAR LOG
2
R10350
R10358
FRONT LEFT LOG
3
R10351
R10359
FRONT RIGHT LOG
4
R10352
R10360
TOP BRANCH
DESCIPTION
WARNING: If flame lifts off burner and goes out, verify
insulation and retainer were removed. See page 24.
Figure 70
31455-8-0415
Page 39
MILLIVOLT SYSTEM OPERATING INSTRUCTIONS
750 Millivolt System
The standing pilot (750 millivolt system) is a continuous burning
pilot. The pilot remains ON even when the main burner is OFF.
The OWNER should carefully read and follow these operating
instructions at all times. Lower the door assembly to view the gas
controls for the fireplace.
When you ignite the pilot, the thermopile produces millivolts (electrical
current) which energizes the magnet in the gas valve. After 30
seconds to 1 minute time period you can release the gas control
knob and the pilot will stay ON. Allow your pilot flame to operate
an additional one to two minutes before you turn the gas control
knob from the PILOT position to the ON position. This time period
allows the millivolts (electrical current) to build-up to a sufficient
level allowing the gas control to operate properly.
Initial Lighting
Upon completing the gas line or turning the gas valve on after it has
been in the “OFF” position, a small amount of air will be in the lines.
When first lighting the fireplace, it will take a few minutes for the
lines to purge themselves of this air. Once the purging is complete,
the fireplace will light and operate satisfactorily.
1. Follow the SAFETY and LIGHTING INSTRUCTIONS for
standing pilot controls found in this manual and on labels found
in control compartment behind the door assembly.
CAUTION: During the initial purging and subsequent
lightings, never allow the gas valve control knob to remain
depressed in the “pilot” position without pushing the piezo
ignitor button at least once every second.
Subsequent lightings of the appliance will not require such purging
if the gas valve is not turned to “OFF.”
Pilot Flame
The thermopile/thermocouple (standing pilot) tips should be covered
with flame.
2. During the operating season, leave the control valve knob in
the “ON” position. This will allow the pilot flame to remain lit.
Turn the burner flame on or off with the fireplace Remote/OFF/
ON switch, wall switch or remote controls.
NOTICE: The gas control valve allows you to increase or decrease
the height of the main burner flame. The control valve has a pressure
regulator with a knob as shown in Figure 73. Rotate the knob
clockwise to “HI” to increase the flame height and counterclockwise
to “LO” to decrease the flame height.
3. When the operating season is over, turn the Remote/OFF/ON
switch to “OFF” and the control valve to “OFF”. The system,
including the pilot light, will be shut down.
Figure 74
Figure 73
Page 40
31455-8-0415
MILLIVOLT SYSTEM OPERATING INSTRUCTIONS
STANDING PILOT OPERATING INSTRUCTIONS
Remote/Off/On Switch
The fireplace is equipped with a Remote/OFF/ON switch. A wire
harness is attached to the Remote/OFF/ON switch. The red, black
and green (wires) female push-ons attach to the Remote/OFF/ON
switch. At the opposite end of the wire harness, the black and green
(wires) female push-ons attach to the gas valve. An additional green
wire and the red wire, which are stripped and bare, will attach to one
of the accessories that can be purchased for use with your fireplace.
Operation of REMOTE/OFF/ON Switch with no Accessories
To ignite main burner, turn the control knob on the gas valve from
the PILOT position to the ON position. Turn the Remote/OFF/ON
switch from the OFF position to the ON position. The additional
green wire and red wire, which are stripped and bare are not used.
Wall Switch, FWS-1
Connect the green and red, stripped and bare, wires on the REMOTE/
OFF/ON switch wire harness to the wall switch using wire nuts.
Turn the REMOTE/OFF/ON switch to the Remote position. Pivot
the rocker switch on the FWS-1 to the ON position.
Wall Thermostats (optional)
TRW - Wireless for Millivolt models
TMV - Reed switch for Millivolt models
Battery Operated Remote Controls, FRBC, FBRTC, and TRW
Connect the green and red, stripped and bare, wires on the
REMOTE/OFF/ON switch wire harness to the remote receiver that
is a component in the remote kit using wire nuts. Turn the REMOTE/
OFF/ON switch to the remote position. Follow instructions included
with the remote to complete installation.
Note: If batteries fail in the remote, and immediate heat is desired,
turn the REMOTE/OFF/ON switch from the REMOTE position to
the ON position.
Installation of Remote Receiver
Place remote receiver on the floor of fireplace behind the louver as
far forward as possible.
Attention: The velcro loop and hook are not necessary in this
installation but can be used to secure remote receiver.
Refer to remote control installation and operating instructions for
more details on remote control.
Millivolt Control
The valve regulator controls the burner pressure which should be
checked at the pressure test point. Turn captured screw counter
clockwise 2 or 3 turns and then place tubing to pressure gauge over
test point (Use test point “A” closest to control knob). After taking
pressure reading, be sure and turn captured screw clockwise firmly
to re-seal. Do not over torque. Check for gas leaks.
Millivolt thermopile is self generating. Gas valve does not require
24 volts or 110 volts.
Check System Operation
Millivolt system and all individual components may be checked with
a millivolt meter 0-1000 MV range.
It is important to use wire of a gauge proper for the length of the wire:
Recommended Wire Gauges
Maximum Length
Wire Gauge
1' to 10'
18
10' to 25'
16
25' to 35'
14
Electric (120 volt) Operated Remote Control, FREC
Connect the green and red, stripped and bare, wires on the REMOTE/
OFF/ON switch wire harness to the wires on remote receiver that
is a component in the FREC. Turn the REMOTE/OFF/ON switch to
the REMOTE position. Follow instructions in the FREC to complete
installation.
NOTE: If electric (120 Volt) fails in FREC, and immediate heat
is desired, turn the REMOTE/OFF/ON switch from the REMOTE
position to the ON position.
31455-8-0415
Page 41
MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM
Figure 75
Page 42
31455-8-0415
MILLIVOLT SYSTEM STANDING PILOT LIGHTING INSTRUCTIONS
FOR YOUR SAFETY, READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions exactly.
• If you cannot reach your gas supplier, call the fire
department.
B. Before lighting smell all around the appliance area for gas. Be
sure to smell next to the floor because some gas is heavier
than air and will settle on the floor.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
don't try to repair it; call a qualified service technician. Force
or attempted repair may result in a fire or explosion.
What To Do If You Smell Gas
• Do not try to light any appliance.
• Do not touch any electrical switch;
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
LIGHTING INSTRUCTIONS
1. 2.
3.
4.
5.
Stop! Read the safety information above.
Set REMOTE/OFF/ON switch to OFF.
Turn off all electric power to the appliance (if applicable).
Lower bottom louver assembly.
Push in gas control knob slightly and turn clockwise
to "OFF."
9. Push in control knob all the way and hold in. Repeatedly push
the piezo ignitor button until the pilot is lit. Continue to hold
the control knob in the for about one minute after the pilot is
lit. Release knob, and it will pop back up. Pilot should remain
lit. If it goes out, repeat steps 5 through 9.
• If the control knob does not pop up when released, STOP
and IMMEDIATELY call a qualified service technician or
gas supplier.
• If the pilot will not stay lit after several tries, turn the gas
control knob to "OFF" and call your service technician or
gas supplier.
10. Turn gas control knob counterclockwise
to "ON."
11. Close bottom louver assembly.
12. Turn on all electric power to the appliance (if applicable).
13. Set REMOTE/OFF/ON switch to desired setting.
Note: Knob cannot be turned from "PILOT" to "OFF" unless knob
is pushed in slightly. Do not force.
6. Wait ten minutes to clear out any gas. Then smell for gas,
including near the floor. If you then smell gas, STOP! Follow
"B" in the safety information above. If you do not smell gas,
go to the next step.
7. Find pilot - Follow metal tube from gas
control. The pilot is behind the burner
on the right side.
8. Turn gas control knob counterclockwise
to "PILOT."
TO TURN OFF GAS TO FIREPLACE
1. Set REMOTE/OFF/ON switch to OFF.
2. Turn off all electric power to the appliance if service is to be
performed (if applicable).
3. Lower bottom louver assembly.
31455-8-0415
4. Push in gas control knob slightly and turn clockwise
to "OFF." Do not force.
5. Close bottom louver assembly.
Page 43
MILLIVOLT SYSTEM STANDING PILOT TROUBLESHOOTING
With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you
do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the
diagnosis of problems and the corrective action to be taken.
1. Spark ignitor will not light pilot after repeated triggering of
piezo ignitor button.
a. Defective ignitor (no spark electrode)
—Check for spark at electrode and pilot; if no spark and
electrode wire is properly connected, replace ignitor.
b. No gas or low gas pressure.
—Check remote shut off valves from fireplace. Usually there
is a valve near the main. There can be more than one valve
between the fireplace and main.
—Low pressure can be caused by a variety of situations
such as a bent line, too narrow diameter of pipe, or low line
pressure. Consult with plumber or gas supplier.
c. No LP in tank.
—Check LP (propane) tank. Refill tank.
2. Pilot will not stay lit after carefully following lighting
instructions.
a. Defective thermocouple.
—Check that pilot flame impinges on thermocouple. Clean
and/or adjust pilot for maximum flame impingement.
—Ensure the thermocouple connection at the gas valve
is fully inserted and tight (hand tight plus 1/4 turn). Faulty
thermocouple if reading is below specified minimum of 15
millivolts.
—Disconnect the thermocouple from the valve, place one
millivolt meter lead wire on the end of the thermocouple and
the other millivolt meter lead wire on the thermocouple copper
wire. Start the pilot and hold the valve knob in. If the millivolt
reading is less than 15 millivolt, replace the thermocouple.
b. Defective valve.
—If thermocouple is producing more than 15 millivolts, replace
faulty valve.
3. Pilot burning, no gas to burner, valve knob “ON”, REMOTE/
OFF/ON switch “ON.”
a. REMOTE/OFF/ON switch, wall switch, remote control or
wires defective.
—Check REMOTE/OFF/ON switch and wires for proper
connections. Place jumper wires across terminal at switch.
If burner comes on, replace defective switch. If OK, place
jumper wires across switch wires at gas valve-if burner comes
on, wires are faulty or connections are bad.
b. Thermopile may not be generating sufficient millivolts.
—If the pilot flame is not close enough physically to the
thermopile, adjust the pilot flame.
—Be sure the wire connections from the thermopile at the gas
valve terminals are tight and the thermopile is fully inserted
into the pilot bracket.
—Check the thermopile with a millivolt meter. Take the
reading at TH-TP & TP terminals of the gas valve. The meter
should read 350 millivolts minimum, while holding the valve
knob depressed in the pilot position, with the pilot lit, and
the REMOTE/OFF/ON switch in the OFF position. Replace
the faulty thermopile if the reading is below the specified
minimum.
—With the pilot in the ON position, disconnect the thermopile
leads from the valve. Take a reading at the thermopile leads.
The reading should be 350 millivolts minimum. Replace the
thermopile if the reading is below the minimum.
Page 44
4.
5.
6.
7.
c. Defective valve.
—Turn valve knob to ON. Place REMOTE/OFF/ON switch
to ON. Check with millivolt meter at thermopile terminals.
Millivolt meter should read greater than 200 millivolts. If the
reading is okay and the main burner does not ignite, replace
the gas valve.
d. Plugged main burner orifice.
—Check main burner orifice for blockage and remove.
Frequent pilot outage problem.
a. Pilot flame may be too high or too low, or blowing (high),
causing pilot safety to drop out.
—Clean and adjust flame for maximum flame impingement
on the thermocouple. Follow lighting instructions carefully.
The pilot and main burner extinguish while in operation.
a. No LP (Propane) in tank.
Check LP (Propane) tank. Refill fuel tank.
b. Inner vent pipe leaking exhaust gases back into system
—Check for leaks.
c. Glass too loose, gasket leaks in corners after usage.
—Be certain glass assembly is installed correctly.
d. Horizontal vent improperly pitched.
—The horizontal vent cap should slope down only enough
to prevent any water from entering the unit. The maximum
downwards slope is 1/4 inch.
e. Bad thermopile or thermocouple.
—Replace if necessary.
f. Improper vent cap installation.
—Check for proper installation and freedom from debris or
blockage.
Glass soots.
a. Flame impingement on logs.
—Check and adjust log position. Contact Empire Comfort
Systems, Inc.
b. Debris around throat of main burner.
—Inspect the opening at the base of the main burner. It is
imperative that NO material be placed in this opening.
Flame burns blue and lifts off main burner.
a. Insufficient oxygen being supplied.
—Check to make sure vent cap is installed properly and free
of debris. Make sure that vent system joints are tight and
have no leaks.
—Check to make sure that no material has been placed at
the main burner base.
31455-8-0415
DIRECT IGNITION LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
A. BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electrical switch
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's
phone.
• Follow the gas supplier's instructions.
• If you can not reach your gas supplier, call the fire
department.
B. Use only the wall switch or remote control switch to turn the
gas control on/off. Any attempted repairs or adjustments should
be performed by a qualified service technician. Applying force
or attempted repair may result in a fire or explosion.
C. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
9. Turn on all electric power to the appliance.
2. Set the thermostat, if used, to the lowest setting.
10. Set thermostat to desired setting (if available).
3. Turn off all electric power to the appliance.
11. If the appliance will not operate, follow the instructions “TO
TURN OFF GAS TO APPLIANCE,” and call your service
technician or gas supplier.
4. This appliance is equipped with an ignition device that automatically lights the burner. Do not try to light the burner by
hand.
5. Open bottom louver assembly.
6. Turn gas line valve to “ON.”
7. Wait five minutes to clear out any gas. Then smell for gas,
including near the floor. If you smell gas, STOP! Follow “A” in
the safety information above. If you do not smell gas, go to
the next step.
8. Close bottom louver assembly.
TO TURN OFF GAS TO APPLIANCE
1. STOP! Read the safety information above.
4. Turn gas line valve to "OFF."
2. Turn off all electric power to the appliance.
5. Close bottom louver assembly, or close valve access door.
3. Open bottom louver assembly, or open the valve access door.
31455-8-0415
Page 45
DIRECT IGNITION WIRING DIAGRAM
LED CODES
Steady ON
Normal operation, power ON to control
2 Flashes
3 unsuccessful ignition trials
3 Flashes
Main burner flame failed 4 times during a single heating cycle
4 Flashes
Interrupt power for 5 seconds to reset control
Steady Flash
Flame detected out of sequence
Figure 76
OPTIONAL REMOTE CONTROL
Electric (120 volt) Operated Remote Control (FREC)
1. Disconnect 3-prong power cord from receptacle.
2. Remove wire from 120 VAC hot terminal on control module.
3. Connect female terminal from receiver onto 120 VAC hot
terminal on control module.
Page 46
4. Connect remaining wire from remote control (male terminal)
to (female terminal) on power cord removed from control
module (step 2).
5. Insert electric remote control power cord plug into the
junction box on the right side of fireplace.
6. Connect 3-prong plug into receptacle.
31455-8-0415
INITIAL START UP GAS LINE PURGE
NOTE: UNIT MUST BE PROPERLY GROUNDED FOR ELECTRONIC IGNITION TO FUNCTION.
On initial installation, or after extended periods where the fireplace has not been used, gas lines may require purging.
The installer or qualified service person may use the following purge procedures to prevent the delays that would be caused by waiting
for the lockout periods between tries for ignition.
PURGE PROCEDURE
1. Remove glass door and place away from the fireplace.
2. Turn on gas shut off valve. Follow ignition procedure.
3. If burner does not light after spark sequence has ended, use
an insulated jumper wire between terminal locations 12 and
13 for fast reset function.
4. Interrupt power for 5 seconds. The green indicator light will
blink 4 times repetitively. Then retry for ignition.
5. Allow time for any raw gas to dissipate and repeat steps 3 and
4 until ignition is achieved.
6. Turn burner off and install glass door frame assembly.
7. Test ignition of burner with glass door in place.
INSULATED
JUMPER WIRE
DIRECT IGNITION TROUBLESHOOTING
With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do
experience a problem, refer to the troubleshooting guide below. This guide will assist a qualified service person in the diagnosis of
problems and the corrective action to be taken.
SYMPTOM
CHECK
ACTION
No spark when system is turned to “ON” and Check for 120V between black “hot” line at If 120V not present, check fuse or circuit
reset cycle* has been completed
control module and “white” return at module breaker or repair wiring leading to fireplace.
Main burner will light, but igniter continues Disconnect power to fireplace junction box
to spark for several seconds and then
and check that the "Hot-Black" wire is
locks out (module will show two blinks on
connected to the gold receptacle screw
indicator light).
side, and that the "Neutral - White" wire
is connected to the silver screw side. The
green ground must also be secured for
proper operation.
Prior to rewiring the fireplace junction box,
check operation of the control system by
running a grounded extension cord from
another standard wall receptacle outlet to
the fireplace control system. Follow purge
reset procedure above in order to clear the
light codes.
Spark for six seconds at ignitor, but no a. Check that gas is turned on and system Turn gas on and/or purge system
ignition of burner.
purged
b. Check that tips of ignitor are directly Position electrodes so tips are directly
above ports on main burner. Spark is above burner port ports and about ¼" to
between electrodes and not from one 3/8" above burner.
electrode to burner.
c. Check for 120V at each coil on the gas If 120V present, but gas valve does not click,
valve and listen for click, indicating gas replace gas valve.
valve is opening.
Spark for six seconds, main burner lights, Check for clean ground path between
but goes out when spark stops.
electrode bracket and fireplace chassis.
Check wiring to wiring diagram label. Check
for broken electrode on high-tension lead
attachment to module.
Clean, position according to wiring diagram,
and repair defective electric connections.
If all electrical connections are clean and
correct, replace module.
Main burner lights normally and then goes a. Check thermostat if applicable.
Turn thermostat up to call for heat or replace
out.
b. Check high-tension lead and connector Replace spark electrode assembly
for shorts.
c. Refer to installation instructions Repair as required.
troubleshooting guide for issues such
as venting.
31455-8-0415
Page 47
DIRECT IGNITION PROPANE/LP GAS CONVERSION
The conversion shall be carried out in accordance with the
requirements of the provincial authorities having jurisdiction
and in accordance with the requirements of the CSA B149.2
installation code (Canada) and with the requirements of the
National Fuel Gas Code Z223.1/NFPA 54 (United States).
WARNING: This conversion kit shall be installed by a
qualified service agency in accordance with the manufacturer's
instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in this
instruction is not followed exactly, a fire, explosion, or
production of carbon monoxide may result causing property
damage, personal injury, or loss of life. The qualified service
agency is responsible for the proper installation of this kit. The
installation is not proper and complete until the operation of
the converted appliance is checked as specified in the
manufacturer's instructions supplied with the kit.
Installer notice: Using an ink pen, fill out the required information
on the conversion label. Remove the backing from label and stick
label in a visible position on bottom of fireplace close to gas valve.
Installer notice: These instructions must be left with the appliance.
Instructions for converting your direct ignition fireplace from
natural gas to propane/LP gas.
All direct ignition fireplaces are shipped from the factory equipped
to operate on natural gas. Please see the appropriate parts list for
your model for parts included with the direct ignition fireplace.
Check the items in the kit with the parts list. Notify the supplier of
any items that are missing before installing the conversion kit.
1. Turn off the gas supply.
2. Turn off the electrical supply to the appliance if so equipped.
3. Remove top louver and lower bottom louver.
4. Remove glass frame assembly.
5. Remove logs from burner assembly.
VALVE CONVERSION
6. Remove plastic cap from regulator fitting. Unscrew fitting using
a 11/16" wrench. Turn fitting over so end of fitting marked "LPG"
(red) screws into valve. Tighten fitting (snug only). Replace
plastic cap.
7. Remove 1/4" screw from air shutter.
8. Located to the right of electrodes is a burner hold-down tab.
Using needle-nose pliers, bend burner hold-down tab off the
main burner.
9. Remove main burner by pivoting main burner forward as you
slide main burner from left to right. Be careful as you remove
main burner in order to protect the electrodes from being
damaged.
10. Remove air shutter from orifice fitting.
11. Remove natural gas main burner orifice from orifice fitting.
Page 48
12. Install propane/LP main burner orifice marked #54 for
DVP42FP or marked #51 for DVP48FP.
Important: Failure to install the correct orifice will result in
unit over-firing that could overheat the appliance and result
in a fire.
13. Replace air shutter onto orifice fitting. Air shutter must be
threaded and bottomed-out onto orifice fitting.
14. Replace main burner onto burner assembly. Place main
burner beneath electrodes, slide main burner from right to
left into burner location, and pivot main burner away from
you and into air shutter.
15. Set air shutter opening at 1/4" for DVD32 or DVD36 and 5/16"
for DVD42 or DVD48. Tighten air shutter in place with 1/4"
screw from step 7.
16. Using needle-nose pliers, bend burner hold-down tab over
main burner.
17. Refer to log placement, page 39 to place logs onto burner
assembly.
18. Loosen screw and attach a manometer or pressure gauge to
the outlet pressure tap of the control valve.
19. Turn on the gas supply. Turn on the electrical supply to the
appliance. Check for gas leaks using soap and water solution
or leak detection solution. Bubbles indicate a leak that MUST
be corrected. Do not use an open flame to test for gas leaks.
20. Check the air shutter opening. See chart and illustration below.
21. Relight the main burners and verify proper burner ignition and
operation.
22. With the main burner burning, read the pressure on the
manometer or pressure gauge. The pressure on the gauge
should read between 9.8" and 10.2" w.c.
23. Turn off the gas supply. Turn off the electrical supply to the
appliance.
24. Remove the manometer or pressure gauge. Tighten the screw
in the pressure tap.
25. Turn on the gas supply. Turn on the electrical supply to the
appliance.
26. Immediately test all gas line connections and the control
valve for gas leaks using a soap and water solution or other
gas detection solution. Bubbles indicate a leak that MUST be
corrected. Do not use an open flame to test for gas leaks.
27. Using a ball point pen, fill out the conversion label that is
supplied with the conversion kit. Place the conversion label
adjacent to the rating plate.
28. Replace glass frame assembly.
29. Reinstall top and bottom louvers.
30. Test operation of fireplace once again. Allow the fireplace to
operate for at least 10 minutes and check flame coloration.
Flames on rear of burner should be yellow without any
orange-colored tip. Minor adjustment of the air shutter may
be necessary to "tune in" the proper flame color.
31455-8-0415
IPI ELECTRONIC SYSTEM OPERATING INSTRUCTIONS
5.25 VDC ELECTRONIC CONTROL VALVE
The electronic control valve system includes the ability to switch
the pilot from a standing pilot mode to an intermittent pilot mode.
• IPI Mode - In the Intermittent Pilot mode, when the unit is
turned ON, it will cause spark to the pilot, light the pilot,
then allow the burner to light. When the unit is turned to
OFF, both the burner and pilot will be OFF.
• CPI Mode - In the Continuess Pilot mode, the pilot remains ON continuously even when the burner is turned
OFF.
Note: A small toggle switch is located on the front of the module
tray that is used to switch from IPI (left) to the CPI (right). See
Figure 77.
When the unit is turned to ON, the electrical current will energize
a spark to the pilot igniter. Once the pilot sensor heats up (after a
few seconds), the valve will be energized, allowing gas to flow to
the burner.
OPTIONAL REMOTE CONTROLS
Optional remote controls are available for use with this appliance.
It is recommended that the remote receiver be placed either in a
wall outlet box with extended wiring, on the fireplace hearth, behind the left side surround panel, or in the control compartment
area as far forward in the insert as possible.
The placement options for the remote receiver are given to allow
flexibility, however battery life will be extended when the receiver
is placed in cooler areas.
To connect the remote receiver to the appliance, first disconnect
the ON/OFF switch wires from the white and green wire connectors and connect the wires from the remote receiver to the green
and white wire connectors. See Figure 77.
Follow the instructions included with the remote control for programming and other operational information.
1. Follow the SAFETY and LIGHTING INSTRUCTIONS for Intermittent Pilot controls found in this manual, and on labels
found in the control compartment located in the lower cavity
of the appliance.
2. During the operating season (or in power outage periods), it is
recommended that the pilot remain in the CPI (standing pilot
mode) to reduce cold start issues, and/or conserve battery
backup power during a power outage.
3. The gas valve has inlet and outlet pressure taps as shown in
Figure 77. Refer to page 12 for gas pressure requirements.
Note:
The gas control has a manual HI/LO flame adjustment
knob (regulator) that allows you to increase or decrease
the height of the burner flame. See Figure 77. Rotate
the HI/LO knob counterclockwise to “HI” to increase the
flame height, and clockwise to “LO” to decrease the flame
height.
Figure 77
31455-8-0415
Page 49
IPI ELECTRONIC SYSTEM WIRING DIAGRAM
If any of the original wire as supplied with this unit must be
replaced, it must be replaced with equivalent gauge and temperature rated wire.
This appliance is only for use with the type of gas indicated
on the rating plate and may be installed in an aftermarket,
permanently located, manufactured (mobile) home where not
prohibited by local codes. This appliance is not convertible for
use with other gases, unless a certified kit is used.
CAUTION: Do not operate the appliance with liner(s)
removed, cracked or broken. Replacement of the liner(s)
should be done by a licensed or qualified service person.
WARNING: Improper installation, adjustment, alteration,
service or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be performed
by a qualified installer, service agency or the gas supplier.
Page 50
31455-8-0415
INTERMITTENT PILOT LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
Warning: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which can be lighted with the
manual on/off switch, a remote control, or by switching the
receiver switch to the “ON” position. When lighting the pilot,
follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical
switch. Do not use any phone in your building. Immediately
call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions. If you can not reach your gas
supplier, call the fire department.
C. Use only the remote control or manual remote receiver
switch to operate the gas valve. Never use tools. If valve
does not operate, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a
fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
Lighting Instructions
1. STOP! Read the safety information above.
2. Turn OFF electric power to the appliance.
3. Remove front surround panel assembly or bottom louver if
included.
4. Turn gas cock counterclockwise
to “On” position.
5. Wait ten minutes to clear out any gas. Then smell for gas,
including near the floor. If you smell gas, STOP! Follow “B” in
the safety information above on this page. If you do not smell
gas, go to the next step.
6. Turn ON electric power to the appliance.
7. Find pilot - Follow metal tube from gas control. The pilot is
behind the burner on the right side.
8. Turn main flame to on. If the pilot does not light within 60
seconds, stop and go to Step 5.
9. Refer to remote control instructions for detailed information,
control features, and operation. Note: There is a CPI/IPI
switch that allows for a continuous standing pilot mode or an
intermittent pilot mode. See appliance manual for location
of this switch. If the pilot or burner does not stay lit (in the
standing pilot mode), stop and immediately call a qualified
service technician or gas supplier.
10. If the burner or pilot does not operate properly after several
tries, turn the gas cock clockwise
to “OFF” and call
your service technician or gas supplier.
11. Replace the front surround assembly or close bottom louver
assembly.
12. Operation of the gas valve is controlled by a manual on/
off switch or a hand held remote control. Refer to remote
instructions for detailed operation information.
GAS COCK
To Turn Off Gas To Fireplace
1. Turn off all electric power to the appliance if service is to be
performed (if applicable).
2. Gain access to control compart. Remove surround panel
assembly if necessary.
31455-8-0415
3. Locate On/Off gas cock and turn clockwise to
“OFF”. Do not force.
4. Close bottom louver assembly, if included.
Page 51
INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING
Brief Description of the Components
The gas valve is fitted with a manual HI/LO knob to allow for manual modulation of the gas outlet pressure to the appliance burner.
The controls are designed to be used with either LPG or Natural
Gas and can be converted by use of an OEM supplied conversion
kit.
The Digital Fireplace Control (DFC) is an automatic gas ignition
system based on a single microcontroller core. This control manages all functions related to ignition, flame sensing and supervision for atmospheric applications.
The DFC can be set to provide continuous or intermittent ignition
control sequences and flame monitoring with safety shutdown in
case of failure.
The DFC is set up as a stand alone (AC powered system with
battery back up. See Lighting Instructions on page 51 and Wiring
Diagram on page 50.
Troubleshooting
Before proceeding with the procedures in the following troubleshooting table, verify that the power supply (AC/DC adapter) is
present and that the batteries inside the receiver and/or optional
battery pack are fresh and installed with correct polarity.
Make sure all the connections between the wire harnesses and
system components are proper and positive.
Verify that the static inlet pressure meets the manufacturer’s recommended inlet pressure. If necessary adjust the line pressure
regulator.
If the recommended actions for the following troubleshooting chart
do not help to address the problem consider replacing wiring harnesses.
WARNING:
Any actions performed on the gas valve must be performed
in accordance with this instruction manual. Likewise, any
actions performed on the DFC or other system components
must be done in accordance with the individual component
instructions.
Replacement of components must be performed in accordance with this instructions manual.
Page 52
31455-8-0415
INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING
1
If the DFC giving signal lock out:
The board should be unlocked to
reinitiate a pilot flame ignition (for
the correct unlock sequence refer
to the DFC Use and Installation
Instructions).
NO
Is the DFC board in
lock out?
NO
1.
Verify the electrical connections’ integrity and
make sure they are in accordance with the relevant
system wiring diagram. If necessary replace the
wire harness.
2.
Replace the DFC board.
YES
1. Check the spark electrode positioning - adjust
as necessary.
Was observed spark
at the Pilot Hood
before the DFC
board locked out?
2.
3. Verify the electrical connections’ integrity and
make sure they are in accordance with the
relevant system wiring diagram. If necessary
replace the wire harness.
4.
YES
YES
Replace the pilot assembly.
NO
Replace the DFC board.
1. Verify the electrical connections’ integrity and
make sure they are in accordance with the
relevant system wiring diagram. If necessary
replace the wire harness.
2. If pilot flow adjuster screw is not sealed:
Check if pilot flow adjust screw is set correctly in
accordance with the appliance manufacturer
instructions. If necessary correct it.
3. Replace pilot tube or complete pilot
assembly.
4. Replace the pilot orifice with a new orifice of
correct size, and type, or replace the pilot
assembly. Under all circumstances follow the
appliance manufacturer’s service instructions.
5. Remove the provided wiring harnesses from
Ev1 of gas valve (red base), and verify voltage at
ignition between the Ev1 terminal and the ground
connection on teh valve body. If the voltage is
greater than 0 then Replace Valve. Otherwise
Replace DFC.
Spark continues
while the pilot is ON.
YES
1.
Replace the pilot assembly.
2.
Replace the DFC board.
NO
2
31455-8-0415
Page 53
INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING
Page 54
31455-8-0415
RF OPERATING INSTRUCTIONS
RF VALVE OPERATION (AF-4040 Electronic Gas Valve system
only)
Please refer to the separate instructions for detailed operation and
programming of the Multi-function Remote Control.
The AF-4040 Electronic Gas Control Valve features a Remote
controlled High/Low Variable - 6 Volt DC Motor Drive. This gas
control uses a spark to pilot burner assembly. For use with Propane or natural gas (pre-set at the factory).
This gas control system includes the items identified in Figure 78.
ance will operate from an appliance mounted rocker switch
(#3) or optional wall switch connected to the two BROWN
wires on the Control Module.
3. When the remote/off switch is in the REMOTE position the
appliance will operate from the Remote Control transmitter.
The Control Module must be programmed to the Remote Control.
1. To program, located the learn button on the left side of the
Control Module Note: Press and release the learn button.
There will be a beep sound from the Control Module, then
press any key on the remote transmitter. Once the internal
receiver accepts the transmitter code there will be a series of
confirming beeps.
2. To switch between the NG and LP step motor settings, press
and hold the learn button for 20 seconds. The module should
emit a short beep (less than 1 second) to indicate that the
control was switched from NG (default setting) to LP. When
switching back from LP to NG, the control should emit a long
beep (3 seconds).
SPECIAL FEATURES ON THE CONTROL MODULE
The Control Module has two special pilot mode features built into
the system.
CONTINUOUS PILOT FEATURE: This allows the user to change
from a spark to pilot system to a standing pilot system.
1. There is a switch located on the right side of the Control
Module (#4) that reads CONTINUOUS PILOT ON/OFF. This
switch will allow the user to select the pilot mode of operation.
2. When the continuous pilot switch is in the OFF position and
the appliance turned ON, the pilot will spark and light, then the
main burner will light as well. When the appliance is turned
OFF, the pilot and main burner will shut OFF.
3. When the continuous pilot switch is in the ON position and
the appliance is turned ON, the pilot will spark and light. Then
when the appliance is turned OFF the pilot will remain ON,
but the main burner will shut OFF. Note: The Continuous pilot mode setting is generally recommended on Direct Vent appliances during cold climate seasons to help keep the firebox warm.
POWER SUPPLY SYSTEM
The Gas Control system is powered by a standard 110 volt AC
through a 6.0 volt DC adaptor. The AC adaptor is connected to the
Control Module with two 1/4” female terminals.
This control system also includes a Battery Back-up pack that allows the Gas Control system only to operate in the event of a
power outage.
NOTE: The Accent Light and/or Blower features will not operate
during a power outage.
NOTE: All Batteries should be replaced at least once each year,
preferably at the beginning of the heating season.
REMOTE CONTROL FEATURE: The Control Module has a built
in remote control receiver which allows the user to program the
hand held remote transmitter.
1. There is a switch located on the right side of the Control Module that reads REMOTE/OFF.
2. When the remote/off switch is in the OFF position the appli-
CAUTION: Fire or explosion hazard. Can cause property damage, sever injury or death.
Do not attempt to take apart the gas control or to clean it. Improper
assembly and cleaning can cause unreliable operation.
7
3
6
1
2
4
5
Index No.
Part No.
Description
1
R10418
Battery Back-up
2
R10415
AF Valve, RF
3
R2522
Off/On Switch
4
R11007
AF Control Module
5
R10416
AF Extension Module
6
R10419
AC Adapter
R10423
Pilot Assembly - Nat
R10424
Pilot Assembly - LP
R11006
Remote Control
7
Not Shown
Figure 78
31455-8-0415
Page 55
RF MAINTENANCE INSTRUCTIONS
MAINTENANCE
Maintenance frequency must be determined individually for each
application. Some considerations are:
• Exposure to water, dirt, chemicals and heat can damage the
gas control and shut down the control system.
• Cycling frequency. Appliances that may cycle 20,000 times
annually should be checked monthly.
• Intermittent use. Appliances that are used seasonally should
be checked before shutdown and again before the next use.
• Dusty, wet or corrosive environment. Because these environments can cause the gas control to deteriorate more rapidly,
the system should be checked more often.
• Any control should be replaced if it does not perform properly
on checkout or service. In addition, replace any module if it is
wet or looks like it has been wet.
SERVICE
Do not disassemble the gas control; it contains non-replaceable
components. Attempted disassembly or repair can damage the
control.
Exactly follow the warnings and the lighting instructions.
1. Before lighting, smell around the appliance area for gas. If
the appliance uses LP (bottled) gas, be sure to smell next to
the floor because LP gas is heavier than air. If you smell gas,
immediately shut off the manual valve in the gas piping to the
appliance or on LP at the tank. Do not try to light any appliance. Do not touch any electrical switch or use the phone.
Leave the building and call your gas supplier. If your gas supplier cannot be reached, call the fire department.
2. The gas control must be replaced if it has been flooded with
water. Call a qualified service technician.
3. The gas control is a safety device. It must be replaced in case
of any physical damage such as bent terminals, missing parts,
stripped threads, or evidence of exposure to excessive heat.
TROUBLESHOOTING
IMPORTANT: All service and trouble-shooting procedures should
be performed by an experienced qualified service technician.
If the pilot will not stay lit:
1. Confirm that the “S” wire and the “I” wire are properly connected to the Control Module “S” and “I” terminals.
2. Confirm that the Spark to Pilot burner is properly grounded to
the Gas Control Valve and the Control Module.
3. Check the power source from the 6-volt power adaptor or the
Battery Back-up pack connection and condition of batteries.
4. Check the position of the CONTINUOUS PILOT switch on the
Control Module. If main burner does not come ON when the
manual switch and remote control is turned ON:
a. Confirm that the pilot sparks and lights.
b. Check the two pin plastic connectors that plug into the
face of the Gas Control valve.
c. Confirm that the Gas Control valve is properly grounded
to the Control Module.
OPTIONAL GAS CONVERSION KITS
Please contact your dealer or distributor for the proper Conversion
kit for these fireplace models. Conversion kits will include complete instructions, minimum rate screw, plus the pilot and main
burner orifice for the gas type required. The AF-4040 Electronic
Gas Control Valve is convertible to use either natural or propane
gas by simply turning a small Rotary knob located at the front of
the gas valve. This rotary knob is located under a small rubber cap
and should only be adjusted when converting gas type.
CAUTION: The gas type has been pre-set at the factory and
must not be changed unless a complete conversion is made which
includes changing of the gas pilot injector, minimum rate screw
and main burner orifice.
Follow the operating instructions provided by the manufacturer of
your heating appliance.
Page 56
31455-8-0415
RF WIRING DIAGRAM
Note:
For "RF" Fireplace models with Premium Multi-Function Remote Control, Refer to the separate instructions for operation of the
remote control system.
Figure 79
31455-8-0415
Page 57
RF STANDING PILOT LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR
EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR
LOSS OF LIFE.
A. This appliance has a pilot which must be lighted with
the remote control. When lighting the pilot, follow these
instructions exactly.
B. BEFORE LIGHTING, smell around the appliance area for
gas. Be sure to smell next to the floor because some gas
in heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions. If you can not reach your gas
supplier, call the fire department.
C. Use only the remote control to operate the gas control
knob. Never use tools. If valve does not operate, don't
try to repair it, call a qualified service technician. Force
or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
LIGHTING INSTRUCTIONS
1.
2.
3.
4.
5.
6.
7.
8.
STOP! Read the safety information above.
Turn OFF electric power to the appliance.
Open bottom louver assembly.
to "ON"
Turn gas cock counterclockwise
position.
Wait ten minutes to clear out any gas. Then smell for gas,
including near the floor. If you smell gas, STOP! Follow
"B" in the safety information above on this label. If you
do not smell gas, go to the next step.
Turn ON electric power to the appliance.
Find pilot - Follow metal tube from gas control. The pilot
is behind the burner on the right side.
Using the remote control, turn main flame to "ON." If the
pilot does not light within 60 seconds, stop and go to Step
5.
9.
Refer to remote control instructions for detailed information,
control features, and operation. Note: There is a switch on
the side of the Electronic Control Module that allows for
a continuous standing pilot mode or an intermittent pilot
mode. See appliance manual for location of this switch.
If the pilot or burner does not stay lit (in the standing
pilot mode), stop and immediately call a qualified service
technician or gas supplier.
10. If the burner or pilot does not operate properly after
several tries, turn the gas control knob clockwise
to "OFF" and call your service technician or
gas supplier.
11. Close bottom louver assembly.
12. Operation of the gas valve, blower, and/or optional light
must be controlled by using the hand held remote control.
Refer to remote instructions for detailed operation
information.
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance if service is to
be performed (if applicable).
2. Open bottom louver assembly.
Page 58
3. Locate On/Off gas cock and turn clockwise to
"OFF." Do not force.
4. Close bottom louver assembly.
31455-8-0415
MAINTENANCE AND SERVICE
Please Note
It is normal for appliances fabricated of steel to give off
some expansion and/or contraction noise during the start
up or cool down cycle. Similar noises are found with your
furnace heat exchanger or car engine.
It is not unusual for your gas fireplace to give off some odor the
first time it is burned. This is due to the curing of the paint and any
undetected oil from the manufacturing process.
Please ensure that your room is well ventilated - open all windows.
It is recommended that you burn your fireplace for at least
six hours the first time you use it. If optional fan kit has been
installed, place fan in the “OFF” position during this time.
IMPORTANT: Turn off gas before servicing appliance. It is
recommended that a qualified service person perform these checkups at the beginning of each heating season.
• Clean Burner and Control Compartment
Keep the control compartment, logs, and burner areas surrounding
the logs clean by vacuuming or brushing at least twice a year.
Cleaning Procedure
1. Turn off pilot light at gas valve.
2. Remove glass front. (See Glass Removal)
3. Vacuum burner compartment.
4. Reinstall glass front.
5. Ignite pilot. (See Lighting Instructions)
6. Operate the pilot burner. If it appears abnormal call a service
person.
• Check Vent System
The appliance and venting system should be inspected before
initial use and at least annually by a qualified service person.
Inspect the external vent cap on a regular basis to make sure
that no debris is interfering with the air flow.
Reassembly and Resealing Gas Accumulation Relief System
Glass Frame Assembly and Combustion Chamber
Whenever the glass frame assembly is pivoted open by a delayed
ignition in the main burner, the glass frame assembly gaskets and
combustion chamber must be examined by a qualified service person
for damage. All damaged gaskets on the glass frame assembly and
combustion chamber must be replaced by a qualified service person.
If damage occurs to the combustion chamber, it must be replaced
by a qualified service person. Contact Empire Comfort Systems,
Inc. for replacement parts.
Glass Cleaning
It will be necessary to clean the glass periodically. During start-up
condensation, which is normal, forms on the inside of the glass and
causes lint, dust and other airborne particles to cling to the glass
surface. Also initial paint curing may deposit a slight film on the
glass. It is therefore recommended that the glass be cleaned two or
three times with a non-abrasive household cleaner and warm water
(we recommend gas fireplace glass cleaner). After that the glass
should be cleaned two or three times during each heating season
depending on the circumstances present.
WARNING:
1. The use of substitute glass will void all product warranties.
2. Care must be taken to avoid breakage of the glass.
3. Under no circumstances should this appliance be operated
without the glass front or with a broken glass front.
Replacement of the glass (with gasket) as supplied by the
manufacturer should be done by a qualified service person.
4. Do not abuse the glass by striking or hitting the glass.
WARNING: Do not use abrasive cleaners on glass. Do
not attempt to clean glass when glass is hot.
Glass Door Removal
1. Remove the top louver by grasping the louver, then lift upward
and pull forward.
2. Remove the bottom louver by lifting up and pulling forward.
3. Locate the bottom two glass frame spring clamps. Pull forward
and down to release them from the Glass Door frame.
4. Remove the Glass Door by pulling the bottom of the door
outward several inches, then lift upwards to disengage it from
the firebox upper flange.
Glass Door Installation
1. When installing the Glass Door assembly, make sure that the
door top flange is hooked over the firebox top flange as illustrated
in the “Correct” view in Figure 80.
Important: Do not allow the gasket across the top of the
door to roll up on top of the firebox flange as shown in
“Incorrect” view in Figure 80.
2. To install correctly, the door should be held at an angle outward
from the firebox as shown in the illustration, then carefully engage
the upper flange of the door frame with the top flange of the
firebox. Center the door left to right, then allow the bottom of
the door to swing inward to seal against the firebox front.
3. Once the glass door is placed flat to the firebox front edges,
engage the two spring latches to the bottom flange on the glass
door frame to secure the door assembly.
4. Replace the top and bottom louvers.
GASKET
FIREBOX
TOP
T
EC
RR
CO
FIREBOX
TOP
T
EC
R
OR
General Glass Information
WARNING: Do not operate appliance with the glass front
removed, cracked or broken. Replacement of the glass should
be done by a licensed or qualified service person.
Only glass approved for use by the manufacturer in fireplace may
be used for replacement. The glass replacement should be done
by a licensed or qualified service person.
31455-8-0415
INC
Figure 80
Page 59
DVP42FP(3,5,7,9) PARTS LIST
Index No.
1
Part Number
DVP42FP3
DVP42FP5
DVP42FP7
DVP42FP9
R7654
R7654
R7654
R7654
Description
Insulation, Flue
2
17426
17426
17426
17426
Retainer, 5” Flue
3
R7567
R7567
R7567
R7567
Vent Adapter
4
R7573
R7573
R7573
R7573
Inlet Vent Gasket
5
17363
17363
17363
17363
Flue Outlet Assembly
6
M170
M170
M170
M170
Gasket, Flue Outlet
7
17142
17142
17142
17142
Cover Plate, Vent
8
R7575
R7575
R7575
R7575
Cover Plate Gasket
9
17430
17430
17430
17430
Cover Plate, Flue
10
R7574
R7574
R7574
R7574
Gasket, Flue Outlet
11
17247
17247
17247
17247
Top Standoff (Qty. 2)
12
10554
10554
10554
10554
Nailing Flange (Qty. 4)
13
R3490
R3490
R3490
R3490
Junction Box
14
R3492
R3492
R3492
R3492
3-Prong Receptacle
15
17357
17357
17357
17357
Heat Shield (Junction Box)
(2 Required for DVP42FP7 Models)
16
17445
17445
17445
17445
Top Shield
17
17804
17804
17804
17804
Top Inner Heat Shield
18
17381
17381
17381
17381
Baffle, Flue Vent
19
17187
17187
17187
17187
Louver Assembly - Upper
20
17190
17190
17190
17190
Ceramic Glass Door Assembly
21
17188
17188
17188
17188
Louver Assembly - Lower
22
R7611
-
R10424
R10424
Pilot Assembly (LPG)
22
R7612
-
R10423
R10423
Pilot Assembly (Nat)
23
R7617
R7617
R9189
R9189
Pilot Gasket
24
11269
11269
11269
11269
Gas Line Fitting
25
R7649
R7649
R7649
-
26
P200
P200
P200
P200
Orifice Fitting
27
P185
P185
P185
P185
Orifice (LPG)
Orifice (Nat)
Fan Control Switch
27
P203
P306
P203
P203
28
R5676
R5676
R5676
R5676
Air Shutter
29
11499
11499
11499
11499
Burner Support - Left
30
11377
11377
11377
11377
Burner Support - Right
31
17370
17370
17370
17370
Burner Assembly
32
21533
21533
21533
21533
Burner Base Plate Assembly
33
17369
17369
31458
17369
Tubing Assembly
34
R2423
R2423
R2423
R2423
5/16" Male Connector
36
R7578
R7733
R11126
R10415 &
R10428
Gas Valve (LPG)
36
R7577
R7733
R11125
R10415 &
R10430
Gas Valve (Nat)
37
17161
20707
29400
26307
Gas Valve Bracket
38
16223
16223
16223
16223
Spring Retainer Assembly
39
R10947
R8147
R11034
-
Wire Assembly
40
R2708
-
-
-
Piezo Ignitor
Page 60
31455-8-0415
DVP42FP(3,5,7,9) PARTS LIST
Index No.
Part Number
Description
DVP42FP3
DVP42FP5
DVP42FP7
DVP42FP9
41
R3436
-
R2522
-
Remote/On/Off Switch
43
-
R7615
-
Cord Set
44
-
R8144
-
-
Wire Harness (DI)
45
-
-
R11123
-
Wire Harness (IP)
46
-
-
-
18880
Blower Shield
47
-
-
-
18858
Blower Base
48
FBB4
FBB4
FBB4
R7731
Blower Assembly
49
-
-
-
R7831
Blower Wire Assembly
50
R10352
R10352
R10352
R10352
Twig, Top Branch
51
R10350
R10350
R10350
R10350
Log, Front Left
52
R10351
R10351
R10351
R10351
Log, Front Right
53
R10349
R10349
R10349
R10349
Log, Rear
54
-
-
R11122
R10418
Battery Back-up
55
-
-
R11128
R10419
AC Adapter
56
-
-
-
R10416
120V Extension Module
57
-
R7616
R11127
R11007
Control Module
58
-
-
-
R10499
Extension Wire Harness (5 pin)
59
-
-
-
R10497
Wire Harness (4 Pin )
60
-
-
-
R10498
Wire Harness (8 Pin)
61
Not Used On DVP42FP(3,5,7,9) Models
Insulation, Top Shield
62
Not Used On DVP42FP(3,5,7,9) Models
Heat Shield, (Flue)
63
Not Used On DVP42FP(3,5,7,9) Models
Mounting Brace
64
R7680
R7680
R7680
R7680
Optional Brick Panel, Side (Left)
65
R7681
R7681
R7681
R7681
Optional Brick Panel, Back
66
R7680
R7680
R7680
R7680
Optional Brick Panel, Side (Right)
67
R7682
R7682
R7682
R7682
Optional Brick Panel, Top
68
-
R7613
-
-
Spark Plug Wire
69
-
R7590
-
-
Spark Ignitor, PSE
70
-
R7589
-
-
Gasket, PSE Ignitor
71
-
19545
-
-
Spark Ignitor Shield
72
-
-
R2667
-
Wire Assembly
74
-
-
29382
-
Module Tray
77
-
-
31500
-
Pilot Shield
N/S
-
-
-
R10427
Min. Rate Screw - #47 (LPG)
N/S
-
-
-
R10431
Min. Rate Screw - #0 (NAT)
N/S
R5668
-
-
-
N/S
-
-
-
R11006
N/S
18704
18704
18704
18704
Decorative Rock (1lb)
N/S
15999
15999
15999
15999
Rockwool (0.1 oz)
Ignitor Wire, Piezo
Remote Control, RF
N/S = Not Shown
See Page 39 for ordering logs.
31455-8-0415
Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.
Page 61
DVP48FP(3,5,7,9) PARTS LIST
Part Number
Index
No.
DVP48FP3
DVP48FP5
DVP48FP7
DVP48FP9
1
R7654
R7654
R7654
R7654
Insulation, Flue
Description
2
17426
17426
17426
17426
Retainer, 5” Flue
3
R7567
R7567
R7567
R7567
Vent Adapter
4
R7573
R7573
R7573
R7573
Vent Gasket
5
17363
17363
17363
17363
Flue Outlet Assembly
6
M170
M170
M170
M170
Gasket, Flue Outlet
7
17142
17142
17142
17142
Cover Plate, Vent
8
R7573
R7573
R7573
R7573
Gasket, Inlet Vent
9
17430
17430
17430
17430
Cover Plate, Flue
10
R7574
R7574
R7574
R7574
Gasket, Flue Outlet
11
17247
17247
17247
17247
Top Standoff (Qty. 2)
12
10554
10554
10554
10554
Nailing Flange (Qty. 4)
13
R3490
R3490
R3490
R3490
Junction Box
14
R3492
R3492
R3492
R3492
3-Prong Receptacle
15
17357
17357
17357
17357
Heat Shield (Junction Box)
(2 Required for DVP48FP7 Models)
16
17446
17446
17446
17446
Top Shield
17
17805
17805
17805
17805
Top Inner Heat Shield
18
17447
17447
17447
17447
Baffle, Flue Vent
19
17210
17210
17210
17210
Louver Assembly - Upper
20
17213
17213
17213
17213
Ceramic Glass Door Assembly
21
17211
17211
17211
17211
Louver Assembly - Lower
22
R7611
-
R10424
R10424
Pilot Assembly (LPG)
22
R7612
-
R10423
R10423
Pilot Assembly (Nat)
23
R7617
R7617
R9189
R9189
Pilot Gasket
24
11269
11269
11269
11269
Gas Line Fitting
25
R7649
R7649
R7649
-
26
P200
P200
P200
P200
Orifice Fitting
27
P250
P210
P250
P250
Orifice (LPG)
Fan Control Switch
27
P213
P270
P213
P213
28
R5676
R5676
R5676
R5676
Air Shutter
Orifice (Nat)
29
11499
11499
11499
11499
Burner Support - Left
30
11377
11377
11377
11377
Burner Support - Right
31
17386
17386
17386
17386
Burner Assembly
32
17385
17385
17385
17385
Burner Base Plate Assembly
33
17369
17369
31458
17369
Tubing Assembly
34
R2423
R2423
R2423
R2423
5/16" Male Connector
36
R7578
-
R11126
R10415
Gas Valve (LPG)
36
R7577
R7733
R11125
R10415
Gas Valve (Nat)
37
17161
20707
29400
26307
Gas Valve Bracket
Spring Retainer Assembly
38
16223
16223
16223
16223
39
R10947
R8147
R11034
-
Wire Assembly
40
R2708
-
-
-
Piezo Ignitor
41
R3436
-
R2522
-
Remote/On/Off Switch
43
-
R7615
-
-
Cord Set
Page 62
31455-8-0415
DVP48FP(3,5,7,9) PARTS LIST
Index
No.
DVP48FP3
DVP48FP5
Part Number
44
-
45
-
46
-
Description
DVP48FP7
DVP48FP9
R8144
-
-
Wire Harnes (DI)
-
R11123
-
Wire Harness (IP)
-
-
18880
Blower Shield
47
-
-
-
18858
Blower Base
48
FBB4
FBB4
FBB4
R7731
Blower Assembly
49
-
-
-
R7831
Blower Wire Assembly
50
R10360
R10360
R10360
R10360
Twig, Top Branch
51
R10358
R10358
R10358
R10358
Log, Front Left
52
R10359
R10359
R10359
R10359
Log, Front Right
53
R10357
R10357
R10357
R10357
Log, Rear
54
-
-
R11122
R10418
Battery Back-up
55
-
-
R11128
R10419
AC Adapter
56
-
-
-
R10416
120V Extension Module
57
-
R7616
R11127
R11007
Control Module
58
-
-
-
R10499
Extension Wire Harness (5 pin)
59
-
-
-
R10497
Wire Harness (4 Pin )
60
-
-
-
R10498
Wire Harness (8 Pin)
61
Not Used On DVP48FP(3,5,7,9) Models
Insulation, Top Shield
62
Not Used On DVP48FP(3,5,7,9) Models
Heat Shield, (Flue)
63
Not Used On DVP48FP(3,5,7,9) Models
Mounting Brace
64
R7680
R7680
R7680
R7680
Optional Brick Panel, Side (Left)
65
R7685
R7685
R7685
R7685
Optional Brick Panel, Back
66
R7680
R7680
R7680
R7680
Optional Brick Panel, Side (Right)
67
R7686
R7686
R7686
R7686
Optional Brick Panel, Top
68
-
R7613
-
-
Spark Plug Wire
69
-
R7590
-
-
Spark Ignitor, PSE
70
-
R7589
-
-
Gasket, PSE Ignitor
71
-
19545
-
-
Spark Ignitor Shield
72
-
-
R2667
-
Wire Assembly
74
-
-
29382
-
Module Tray
77
-
-
31500
-
Pilot Shield
N/S
-
-
-
R10427
Min. Rate Screw - #47 (LPG)
N/S
-
-
-
R10431
Min. Rate Screw - #0 (NAT)
N/S
R5668
-
-
-
Ignitor Wire, Piezo
N/S
-
-
-
R11006
N/S
18704
18704
18704
18704
Remote Control, RF
Decorative Rock (1 lb)
N/S
15999
15999
15999
15999
Rockwool (0.1 oz)
N/S = Not Shown
See Page 39 for ordering logs.
Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.
31455-8-0415
Page 63
PARTS VIEW
Page 64
31455-8-0415
MASTER PARTS DISTRIBUTOR LIST
To Order Parts Under Warranty, please contact your local Empire dealer. See the dealer locator at www.empirecomfort.
com. To provide warranty service, your dealer will need your name and address, purchase date and serial number, and the
nature of the problem with the unit.
To Order Parts After the Warranty Period, please contact your dealer or one of the Master Parts Distributors listed below.
This list changes from time to time. For the current list, please click on the Master Parts button at www.empirecomfort.com.
Please note: Master Parts Distributors are independent businesses that stock the most commonly ordered Original
Equipment repair parts for Heaters, Grills, and Fireplaces manufactured by Empire Comfort Systems Inc.
Dey Distributing
1401 Willow Lake Boulevard
Vadnais Heights, MN 55101
Victor Division of F. W. Webb Company
200 Locust Street
Hartford, CT 06114
Phone: 651-490-9191
Toll Free: 800-397-1339
Website: www.deydistributing.com
Parts: Heater, Hearth and Grills
Phone: 860-722-2433
Toll Free: 800-243-9360
Fax: 860-293-0479
Toll Free Fax: 800-274-2004
Websites: www.fwwebb.com & www.victormfg.com
Parts: Heater, Hearth and Grills
East Coast Energy Products
10 East Route 36
West Long Branch, NJ 07764
Able Distributors
2501 North Central Avenue
Chicago, IL 60639
Phone: 732-870-8809
Toll Free: 800-755-8809
Fax: 732-870-8811
Website: www.eastcoastenergy.com
Parts: Heater, Hearth and Grills
Phone: 773-889-5555
Toll Free: 800-880-2253
Fax: 773-466-1118
Website: www. abledistributors.com
Parts: Heater
HOW TO ORDER REPAIR PARTS
Parts Not Under Warranty
Parts can be ordered through your Service Person, Dealer, or a Master Parts Distributor. See this page for the Master Parts Distributors list. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the
service person/dealer.
Warranty Parts
Warranty parts will need a proof of purchase and can be ordered by your Service Person or Dealer. Proof of purchase is required for
warranty parts.
All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number and Serial Number from the
name plate on your equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the following illustration and part list. Be sure to give all this information . . .
Appliance Model Number
Appliance Serial Number
Part Description
Part Number
Type of Gas (Propane or Natural)
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, fires and all causes beyond our control.
31455-8-0415
Page 65
FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION
Attention: Install blower assembly before connecting gas
inlet supply line
Note: Junction box on right side of fireplace must be pre-wired at
time of fireplace installation for use with blower assembly.
It is recommended that an ON/OFF wall switch be installed
that will activate the power supply to the furnace by a
qualified electrician.
1.
2.
3.
4.
If installed, turn OFF gas supply to fireplace.
If applicable, turn OFF electric supply to fireplace.
Lower bottom louver on fireplace.
Refer to page 68, "Junction Box Wiring Installation Instructions"
to complete wiring of junction box.
Attention: If installed, do not damage gas inlet supply line
when blower assembly is inserted into fireplace. If
necessary, remove gas inlet supply line.
5. Insert blower assembly into interior, bottom of fireplace.
Position blower assembly behind gas valve, align notch
on back of blower assembly with center screw on fireplace
back and push blower assembly against fireplace back. The
magnets on the back and bottom of blower assembly will
sufficiently hold blower assembly in place.
6. Position speed control box to the right of gas valve. Attach
speed control box to bottom of fireplace. The magnets on
bottom of speed control box will sufficiently hold speed control
box in place.
7. With base (flush face) of fan control switch facing upward,
insert base of fan control switch under the mounting tabs on
valve bracket. The base (flush face) of fan control switch must
be in contact with bottom of firebox.
8. Insert power cord plug into junction box.
9. Close bottom louver on fireplace.
10.Installation of FBB4 optional variable speed blower assembly
is completed.
Wiring
The appliance, when installed, must be electrically grounded in
accordance with local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA 70, if an external
electrical source is utilized. This appliance is equipped with a
three-prong [grounding] plug for your protection against shock
hazard and should be plugged directly into a properly grounded
three-prong receptacle. Do not cut or remove the grounding prong
from this plug. For an ungrounded receptacle, an adapter, which
has two prongs and a wire for grounding, can be purchased,
plugged into the ungrounded receptacle and its wire connected
to the receptacle mounting screw. With this wire completing the
ground, the appliance cord plug can be plugged into the adapter
and be electrically grounded.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
Blower Motor
The blower motor does not have oiling holes. Do not attempt to
oil the blower motor.
Blower Wheels
The blower wheels will collect lint and could require periodic
cleaning. If the air output decreases or the noise level increases,
it indicates a dirty blower wheel. Remove fan and clean blower
wheels.
WARNING: Unplugging of blower accessory will not stop
the heater from cycling. To turn off gas to the heater (millivolt
model): push in gas control knob slightly and turn clockwise
to "OFF." Do not force. To turn off gas on direct ignition
model, turn gas line valve to "OFF."
Page 66
*Note: Refer to Junction Box wiring instructions on page 68
for proper operation.
Figure 81
31455-8-0415
FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION
31455-8-0415
1
R7731
BLOWER MOTOR
2
31920
SWITCH ASSEMBLY
3
R4192
SPEED CONTROL KNOB
4
R4186
SPEED CONTROL
Page 67
JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS
CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT MAIN POWER
SUPPLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE
WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA 70 (LATEST EDITION).
*
A factory installed junction box is located on the lower right side of
the fireplace. Wiring must be fed to the junction box and attached
to the receptacle that is provided. Leave approximately 6” of wire
in the junction box for connection.
Attach black wire to one side of the receptacle and white wire to
opposite side of receptacle. The ground wire should be attached
to the green (ground) screw.
Install the receptacle into the junction box. Attach cover plate.
Figure 82
OPTIONAL BRICK LINER INSTALLATION INSTRUCTIONS
1. Using gloves, unpack liner components and check for
damaged or missing components.
2. Lower bottom louver and remove upper louver on fireplace.
3. Remove glass frame assembly from fireplace.
4. Remove rear logs from burner assembly.
5. Place brick panel (rear) against rear wall in fireplace.
Note: The top edge will have a half-moon cutout relief to match up
with the rear flue vent hole.
6. While holding finished edge on brick panel (side), place brick
panel (sides) against side walls in fireplace. Move side panels
rearward until the back edge meets the rear brick panel. Slide
side brick panels down so they rest on firebox bottom.
Page 68
7. Align grout lines on top brick panel with the grout lines on the
side brick panels. Place the top brick panel into brick panel
holder. With needle-nose pliers, carefully bend hold-down tabs
on brick panel holder over the edges of the top brick panel.
The hold-down tabs will securely hold the top brick panel in
place.
8. Replace rear logs onto burner assembly. Refer to log
placement, page 39.
9. Attach glass frame assembly onto fireplace.
10. Raise bottom louver and replace top louver onto fireplace.
11. Installation of optional brick liner is complete.
31455-8-0415
ACCESSORIES
The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond
what your dealer can furnish, contact Empire Comfort Systems Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois 62220-2623.
Accessory
Description
Fan Kit
Variable Speed
This fan kit was designed to provide forced air flow.
(Note: For use with Millivolt and intermittent pilot models FBB4
only. "RF" Fireplace models are equipped with blower
assembly.)
Model Number
Simulated Brick Liners
The simulated brick panels were designed to enhance the
appearance of your fireplace, imitating the look of authentic
masonry.
DVP3DH(DVP42)
DVP4DH(DVP48)
HERRINGBONE
Simulated Brick Liners
The simulated brick panels were designed to enhance the
appearance of your fireplace, imitating the look of authentic
masonry.
DVP3DA(DVP42)
DVP4DA(DVP48)
AGED BRICK
DECORATIVE ACCESSORIES
Decorative Louver Mission
Decorative Louver Arch
Decorative Frame Rectangle
with hinges
Window Trim
31455-8-0415
Decorative Louver Leaf
Decorative Door Plain Rectangle
STD Louvers 45 Degree
Outside Frame Kits
Page 69
EMPIRE
Comfort Systems
Empire Comfort Systems
918 Freeburg Avenue
Belleville, Illinois 62220-2623
GAS-FIRED
Web Site www.empirecomfort.com
The Tahoe Direct Vent Zero Clearance Gas
Fireplace Heater
MILLIVOLT STANDING PILOT: DVP(42,48)FP3(0,1,2,3)(N,P)-4
DIRECT IGNITION PILOT: DVP(42,48)FP5(0,1,2,3)-1
INTERMITTENT PILOT: DVP(42,48)FP7(0,1,2,3)(N,P)-5
REMOTE RF: DVP(42,48)FP9(1,3)(N,P)-5
Fireplace requires one of the following fronts:
Arched: DCF42B(FB,CM,HP), DCF42T(FB,CM,HP)
Rectangular: DCF42A(FB,CM,HP)
Fireplace requires one of the following ceramic liners:
DVP3DA, DVP3DH, DVP42DG
All Brick Liners are made from Ceramic Fiber for rich detail and lasting beauty. Aged Brick
Liners have brown bricks with charcoal mortar in running bond courses, plus smoked accents.
Herringbone Liners have burnt umber bricks in a herringbone pattern with light mortar, plus
smoked accents. Stacked Limestone Liners have stones of varying depth and color for a rustic
cabin look.
CLEARANCES to Combustibles
(914mm)
Clearance to Combustibles
Back
0" (0 mm)
Side
0" (0 mm)
Floor
0" (0 mm)
Top Stand-off
0" (0 mm)
Top Framing Edge 3" (76 mm)
Page 70
31455-8-0415
EMPIRE
Comfort Systems
Empire Comfort Systems
918 Freeburg Avenue
Belleville, Illinois 62220-2623
GAS-FIRED
Web Site www.empirecomfort.com
The Tahoe Direct Vent Zero Clearance Gas
Fireplace Heater
MILLIVOLT STANDING PILOT: DVP(42,48)FP3(0,1,2,3)(N,P)-4
DIRECT IGNITION PILOT: DVP(42,48)FP5(0,1,2,3)-1
INTERMITTENT PILOT: DVP(42,48)FP7(0,1,2,3)(N,P)-5
REMOTE RF: DVP(42,48)FP9(1,3)(N,P)-5
Fireplace requires one of the following fronts:
Arched: DCF42B(FB,CM,HP), DCF42T(FB,CM,HP)
Rectangular: DCF42A(FB,CM,HP)
Fireplace requires one of the following ceramic liners:
DVP3DA, DVP3DH, DVP42DG
All Brick Liners are made from Ceramic Fiber for rich detail and lasting beauty. Aged Brick
Liners have brown bricks with charcoal mortar in running bond courses, plus smoked accents.
Herringbone Liners have burnt umber bricks in a herringbone pattern with light mortar, plus
smoked accents. Stacked Limestone Liners have stones of varying depth and color for a rustic
cabin look.
FIREBOX DIMENSIONS
DVP42
DVP48
A
43"
1092mm
49"
1245mm
B
40"
1016mm
46"
1168mm
C
25 1/16"
636 mm
25 1/16"
636 mm
D
37 5/8"
956 mm
37 5/8"
956 mm
E
34 3/4"
883 mm
34 3/4"
883 mm
F
19 7/8" 505
mm
19 7/8"
505 mm
G
26"
660 mm
26"
660 mm
H
7 1/8"
181 mm
7 1/8"
181 mm
I
26 1/2"
826 mm
32 1/2"
826 mm
J
13 1/4"
337 mm
16 1/4"
413 mm
K
12 3/4"
324 mm
12 3/4"
324 mm
FRAMING DIMENSION
31455-8-0415
DVP42
DVP48
"A"
37 3/4"
37 3/4"
"B"
43 3/8"
49 3/8"
"C"
19 7/8"
19 7/8"
Page 71
WARRANTY
Empire Comfort Systems Inc. warranties this hearth product to be free from defects at the time of purchase and for the periods specified below. Hearth products must be installed by a qualified technician and must be maintained and operated safely, in accordance with
the instructions in the owner’s manual. This warranty applies to the original purchaser only and is not transferable. All warranty repairs
must be accomplished by a qualified gas appliance technician.
Limited Lifetime Parts Warranty – Combustion Chamber, Heat Exchanger, and Factory-Installed Glass
If the combustion chamber, heat exchanger (see parts list) or factory-installed glass fails because of defective workmanship or material, Empire will repair or replace at Empire’s option.
Limited Three-Year Parts Warranty – All Other Components
(Except Remote Controls, Thermostats, Accessories and Replacement Parts)
Should any part fail because of defective workmanship or material within three years from the date of purchase, Empire will
repair or replace at Empire’s option..
Limited One-Year Parts Warranty – Remote Controls, Thermostats, Accessories, and Parts
Should any remote control, thermostat, accessory, or other part fail because of defective workmanship within one year from
the date of purchase, Empire will repair or replace at Empire’s option.
Duties Of The Owner
The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the appliance.
A bill of sale, cancelled check, or payment record should be kept to verify purchase date and establish warranty period.
Ready access to the appliance for service.
What Is Not Covered
Damages that might result from the use, misuse, or improper installation of this appliance.
Travel, diagnostic costs and freight charges on warranted parts to and from the factory.
Claims that do not involve defective workmanship or materials.
Unauthorized service or parts replacements.
Removal and reinstallation cost.
Inoperable due to improper or lack of maintenance.
How To Get Service
To make a claim under this warranty, please have your receipt available and contact your installing dealer. Provide the dealer
with the model number, serial number, type of gas, and purchase verification. The installing dealer is responsible for providing service and
will contact the factory to initiate any warranted parts replacements. Empire will make replacement parts available at the factory. Shipping
expenses are not covered.
If, after contacting your Empire dealer, service received has not been satisfactory, contact: Consumer Relations Department,
Empire Comfort Systems Inc., PO Box 529, Belleville, Illinois 62222, or send an e-mail to [email protected] with “Consumer Relations” in the subject line.
Your Rights Under State Law
This warranty gives your specific legal rights, and you may also have other rights, which vary from state to state.
EMPIRE
Comfort Systems
Empire Comfort Systems Inc.
918 Freeburg Ave. Belleville, IL 62220
If you have a general question about our products, please e-mail us at
[email protected].
If you have a service or repair question, please contact your dealer.
www.empirecomfort.com
Page 72