Download Samsung MCM-A100 Installation manual

Transcript
INSTALLATION
MANUAL
Centralized Controller
MCM-A202A
MCM-A202AU
System Air Conditioner
E DB98-29495A(1)
MCM-A202A_IM_E_29495-1.indd
21
2008-02-14
ソタネト 2:58:30
Safety Precautions
This installation manual indicates you to install the centralized controller which is
connected to the indoor unit. For installation of other optional accessories, see an
appropriate installation manual.
WARNING
CAUTION
Read carefully this installation manual before installation
and check whether the centralized controller is installed
correctly after installation.
Do not attempt to install or repair this centralized
controller by yourself.
This centralized controller contains no user-serviceable
parts. Always consult authorized service personnel for
repairs.
When moving, consult authorized service personnel
for disconnection and installation of the centralized
controller.
Ensure that the wall is strong enough to support the
weight of the centralized controller.
The centralized controller must be installed according to
the national electrical rules by an installation specialist.
When you want to disuse the centralized controller,
consult authorized installation center.
Do not use inflammable gases near the centralized
controller.
Do not install the centralized controller in a location
where it will come into contact with the combustible
gases, machine oil, sulphide gas, etc.
Avoid a location where acid/alkali solution or special
spray is used.
Choose a location that is dry and sunny, but not exposed
to direct sunlight. Available temperature is between
0°C(32°F) and 39°C(102°F).
Do not spill water into the centralized controller.
Do not give tensile strength to the cable to avoid
disconnection.
Do not press buttons with a pointed thing.
Do not connect the power cable to the control terminal.
If the centralized controller is installed in a hospital or
other special places, it should not affect other electronic
devices.
E-2
MCM-A202A_IM_E_29495-1.indd
2
2008-02-14
ソタネト 2:57:55
Centralized Controller Installation
Accessories
Centralized
Controller (1)
Note
Cable-tie (2)
Cable Clamp (5)
M4x16 Tapped
Screw (7)
User’s manual (1)
Installation
manual (1)
If you would like to install the centralized controller, you must
install the optional transmitter in the outdoor unit.
Wiring Diagram
Each outdoor unit connected to the same centralized controller must
have its own transmitter.
Centralized
controller
Channel 1
Outdoor unit 1
Indoor unit
Indoor unit
Indoor unit
MAIN 0 RMC(1) 0
RMC(2) 0
MAIN 1 RMC(1) 0
RMC(2) 1
MAIN 2 RMC(1) 0
RMC(2) 2
Transmitter
Channel 1
Transmitter
Channel 1
Outdoor unit 2
Transmitter
Indoor unit
Indoor unit
Indoor unit
MAIN 3 RMC(1) 0
RMC(2) 3
MAIN 4 RMC(1) 0
RMC(2) 4
MAIN 5 RMC(1) 0
RMC(2) 5
E-3
MCM-A202A_IM_E_29495-1.indd
3
2008-02-14
ソタネト 2:57:56
Centralized Controller Installation (Continued)
Transmitter Installation
5V (BLK)
12V
(BLUE)
CN03
(BLUE)
Transmitter 1
Transmitter 2
�� ��
�� ��
CN04
(BLK)
Outdoor unit PCB
Red
Transmitter 3
Blue
Centralized
controller
AC power
supply
E-4
MCM-A202A_IM_E_29495-1.indd
4
2008-02-14
ソタネト 2:57:59
Assigning Address
Turn the arrow of rotary switch on the transmitter to appropriate
position. Transmitters controlled with the same centralized controller
must have different addresses.
Transmitter MAIN PCB
Transmitter SUB PCB
Channel 3
�� �� �� ��
Channel 2
DC 12V supply
DC 5V supply
Transmitter
ADDRESS
rotary switch
�� ��
Channel 1
 Install MAIN PCB only if the
number of indoor units is
below 16.
 Install both of MAIN PCB and
SUB PCB if the number of
indoor units is over 16.
E-5
MCM-A202A_IM_E_29495-1.indd
5
2008-02-14
ソタネト 2:58:01
Centralized Controller Installation (Continued)
Setting up Option Switches (Indoor Unit)
In Case of Installing Centralized Controller Only
K1 K2 K3 K4
SW05

1
Adjust K2 DIP switch(SW05) on the indoor unit PCB to the
'OFF' position. It means use of the centralized controller.
2
Set the RMC(1) and RMC(2) switch among the address setup
switches of indoor unit main PCB as below.
RMC(1)
Setting
Meaning
0
Select transmitter 'channel 0'
1
Select transmitter 'channel 1'
2
Select transmitter 'channel 2'
Indoor unit address setup switch
MAIN(TEN)
MAIN(ONE)
SW01
SW02
RMC(1)
RMC(2)
SW03
SW04
 If the RMC (1) switch is set to other numbers besides 0, 1, and 2,
communication error occurs.
 According to the number of installed indoor units, transmitter connection
setup is changed. For detailed installation structure, refer to the installation
example of central controller + transmitter (pages 7 to 17).

RMC(2)
Note
The number of button on the centralized controller is decided by
the RMC(2) addresses of indoor units.
Refer to the table below.
RMC(2) Address 0 1 2 3 4 5 6 7 8 9 A B C D E F
Button No.
Note
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
 Individual control
means a centralized controller controls only 1 indoor unit. In this case,
you should assign the RMC address to the indoor unit.
 Group control
means a centralized controller controls more than 2 indoor units. In this case,
you should assign the RMC address to each indoor unit to be controlled by the
centralized controller and cannot use a wireless remote controller.
E-6
MCM-A202A_IM_E_29495-1.indd
6
2008-02-14
ソタネト 2:58:02
Different Levels of the Centralized Controller
 Adjust the DIP switch in the centralized controller PCB and set a
level. This will enable the user to control the indoor units
connected to the centralized controller according to the set level.
Switch
SW1 SW2 SW3 SW4
No.
Meaning
LEVEL 0 OFF OFF
-
-
Among the various controllers,
such as the centralized controller,
wired/wireless controller and the
indoor unit button, the air conditioner
will only be able to operate with the
most recently used controller
LEVEL 1 ON OFF
-
-
The wired/wireless controller can
only be used when the centralized
controller is powered on.
LEVEL 2 OFF ON
-
-
The air conditioner can only be
operated with the centralized
controller.
DIP Switch
DS01
Cooling/Heating
switch
Rotary switch
MCM-A202A
 If the 'All ON' button of the
-
LEVEL 3 ON ON
Note
-
centralized controller is pressed
once, the operating lamp turns on,
the indoor unit falls into a standby
state, and the indoor unit can be
turned ON/OFF using the wired/
wireless remote controller and the
indoor unit button. (The indoor
units cannot be operated with the
'All ON/OFF' button)
 If the 'All ON' button of the
centralized controller is pressed
twice, the operating lamp turns off,
and it is not possible to control the
indoor unit with a wired/wireless
remote controller or an indoor unit
button.
 The LEVEL of the centralized controller is ‘0’ when all the
switches are in the 'OFF' position.
 The power is reset when the ADDRESS of the centralized
controller is changed.
 When attempting to change the LEVEL of the centralized
controller, reset the main system’s power or turn off and
then on the power of all the indoor units using the
'All ON/OFF' button.
E-7
MCM-A202A_IM_E_29495-1.indd
7
2008-02-14
ソタネト 2:58:03
Centralized Controller Installation (Continued)
Centralized Controller Communication Option
Setup Method
1
When setting the option by operating the DIP switch (DS01) of
Centralized Controller PCB, the Centralized Controller can be
controlled according to the setup option.
SW1 SW2 SW3 SW4
Contents
-
-
ON
-
ROOM Mode tracking
-
-
OFF
-
GROUP Mode tracking
-
-
-
ON Communication speed of 2400 bps
-
-
-
OFF Communication speed of 9600 bps
 All DIP switches are set to OFF when a Centralized
Controller is delivered.
 If the option of a Centralized Controller is changed, the





changed option is applied only when the power of the
central controller is reset.
When the option is changed, the changed option is applied
only when the indoor unit is controlled at least once by using
the all room ON/OFF button of the Centralized Controller.
Example) If the indoor unit is operated, send the changed
signal to the indoor unit by pressing the all room
ON button. Or press the all room OFF button.
(But, when pressing the all room OFF button, the
operating indoor unit is turned off.) If not using
an indoor unit, send the changed signal to the
indoor unit by pressing the all room OFF button.
The communication option setup is executed without the
relation with the level setup.
If the communication option is wrong, an error mark is
displayed as below.
If transmitters have a different communication speed each
other, the communication speed must be fixed to 2400 bps.
However, the communication speed must be fixed to 2400
bps without relation with transmitter models when
function controller (MCM-A100) is connected to the
Centralized Controller.
Caution
If there are more than one centralized controllers installed,
the communication option settings in the centralized controller
must all be set as same.
E-8
MCM-A202A_IM_E_29495-1.indd
8
2008-02-14
ソタネト 2:58:03
2
Error Display (Displayed on the Centralized Controller front LED)
 Tracking mode setting DIP S/W no. 3 :
Set to GROUP/ROOM mode
 When the upper controller is set to ROOM mode and
the DIP S/W is set to GROUP mode
 When the upper controller is set to GROUP mode and the
DIP S/W is set to ROOM mode
 Communication speed setting DIP S/W no. 4 :
9600 bps/2400 bps
 When the upper controller is set to 2400 bps and
the DIP S/W is set to 9600 bps
 When the upper controller is set to 9600 bps and
the DIP S/W is set to 2400 bps
Error Display Method
Rotated flickering when
error  is occurred
Rotated flickering when
error  is occurred
Rotated flickering when
error  is occurred
Rotated flickering when
error  is occurred
Note
Upper Controller
 This device controls the several Centralized Controllers
through the PC control or Ethernet control.
(SNET-i, SNET-II, SNET-III, SNET-mini, DMS and so on)
 Group mode tracking: Control the indoor units according
to the RMC address.
 Room mode tracking: Control the indoor units
according to the main address of
the indoor units.
(In room mode, the centralized
controller buttons are disabled.)
E-9
MCM-A202A_IM_E_29495-1.indd
9
2008-02-14
ソタネト 2:58:04
Centralized Controller Installation (Continued)
To install 48 Indoor units for 1 Outdoor unit
(Individual control of indoor units)
Centralized
controller
Outdoor unit
Controls 16 indoor units
which have the indoor unit
RMC(1) switch set to '2'.
Channel 3
�� �� �� ��
Centralized
controller
Channel 2
Power cable(DC 12V)
Power cable(DC 5V)
Communication Cable
Transmitter
�� ��
Channel 1
Controls 16 indoor units
which have the indoor unit
RMC(1) switch set to '1'.
Centralized
controller
DIP 1
OFF : 12V, 5V Supply
Controls 16 indoor units
which have the indoor unit
RMC(1) switch set to '0'.
 Transmitter ADDRESS switch
setting should be set respectively.
Caution
When setting the indoor unit address
If the MAIN address is set incorrectly, the communication error
occurs.
E-10
MCM-A202A_IM_E_29495-1.indd
10
2008-02-14
ソタネト 2:58:05
When setting the indoor unit address
MAIN(TEN) MAIN(ONE)
SW01
SW02
RMC(1)
RMC(2)
SW03
SW04
Indoor unit
3~12
Indoor unit
0
Indoor unit
1
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
2
Indoor unit
13
Indoor unit
14
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
15
RMC(1)
SW03
Indoor unit
19~28
Indoor unit
31
Indoor unit
30
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
29
Indoor unit
18
Indoor unit
17
1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3
6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1
1
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
16
RMC(1)
SW03
Indoor unit
35~44
Indoor unit
32
Indoor unit
33
MAIN(TEN)
MAIN(ONE)
Indoor unit
ADDRESS
RMC(1)
RMC(2)
Indoor unit
34
Indoor unit
45
Indoor unit
46
3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4
2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7
2
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
47
RMC(1)
SW03
E-11
MCM-A202A_IM_E_29495-1.indd
11
2008-02-14
ソタネト 2:58:08
Centralized Controller Installation (Continued)
To install 32 indoor units for 1 outdoor unit
(Individual control of indoor units)
Centralized
controller
Outdoor unit
Controls 16 indoor units
which have the indoor unit
RMC(1) switch set to '1'.
Channel 3 �� �� �� �� Channel 2
Centralized
controller
Power cable(DC 12V)
Power cable(DC 5V)
Communication Cable
Transmitter
�� ��
Channel 1
Controls 16 indoor units
which have the indoor unit
RMC(1) switch set to '0'.
DIP 1
OFF : 12V, 5V Supply
 Transmitter ADDRESS switch
setting should be set respectively.
Caution
When setting the indoor unit address
If the MAIN address is set incorrectly, the communication error
occurs.
E-12
MCM-A202A_IM_E_29495-1.indd
12
2008-02-14
ソタネト 2:58:11
When setting the indoor unit address
MAIN(TEN) MAIN(ONE)
SW01
SW02
RMC(1)
RMC(2)
SW03
SW04
Indoor unit
3~12
Indoor unit
0
Indoor unit
1
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
2
Indoor unit
13
Indoor unit
14
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
15
RMC(1)
SW03
Indoor unit
19~28
Indoor unit
31
Indoor unit
30
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
29
Indoor unit
18
Indoor unit
17
1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3
6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1
1
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
16
RMC(1)
SW03
E-13
MCM-A202A_IM_E_29495-1.indd
13
2008-02-14
ソタネト 2:58:14
Centralized Controller Installation (Continued)
To install 16 indoor units for 1 outdoor unit
(Individual control of indoor units)
Outdoor unit
Channel 3
�� �� �� ��
Centralized
controller
Channel 2
Power cable(DC 12V)
Power cable(DC 5V)
Communication Cable
Transmitter
�� ��
Channel 1
Controls 16 indoor units
which have the indoor unit
RMC(1) switch set to '0'.
DIP 1
OFF : 12V, 5V Supply
 Transmitter ADDRESS switch
setting should be set respectively.
Caution
When setting the indoor unit address
If the MAIN address is set incorrectly, the communication error
occurs.
E-14
MCM-A202A_IM_E_29495-1.indd
14
2008-02-14
ソタネト 2:58:16
When setting the indoor unit address
MAIN(TEN) MAIN(ONE)
SW01
SW02
RMC(1)
RMC(2)
SW03
SW04
Indoor unit
3~12
Indoor unit
0
Indoor unit
1
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
2
Indoor unit
13
Indoor unit
14
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
15
RMC(1)
SW03
E-15
MCM-A202A_IM_E_29495-1.indd
15
2008-02-14
ソタネト 2:58:18
Centralized Controller Installation (Continued)
To install 64 indoor units for 1 outdoor unit
(Group control of indoor units)
Outdoor unit
Channel 3 �� �� �� �� Channel 2
Centralized
controller
Power cable(DC 12V)
Power cable(DC 5V)
Communication Cable
Transmitter
�� ��
Channel 1
Controls 64 indoor units
which have the indoor unit
RMC(1) switch set to '0'.
DIP 1
OFF : 12V, 5V Supply
 Transmitter ADDRESS switch
setting should be set respectively.
Caution
When setting the indoor unit address
If the MAIN address is set incorrectly, the communication error
occurs.
E-16
MCM-A202A_IM_E_29495-1.indd
16
2008-02-14
ソタネト 2:58:20
When setting the indoor unit address
MAIN(TEN) MAIN(ONE)
SW01
SW02
RMC(1)
RMC(2)
SW03
SW04
Indoor unit
3~12
Indoor unit
0
Indoor unit
1
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
2
Indoor unit
13
Indoor unit
14
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
15
RMC(1)
SW03
Indoor unit
19~28
Indoor unit
30
Indoor unit
31
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
29
Indoor unit
18
Indoor unit
17
1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3
6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
16
RMC(1)
SW03
Indoor unit
35~44
Indoor unit
33
Indoor unit
32
Outdoor
unit
ADDRESS
MAIN(TEN)
MAIN(ONE)
RMC(1)
RMC(2)
Indoor unit
34
Indoor unit
45
Indoor unit
46
3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4
2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
47
RMC(1)
SW03
Indoor unit
51~60
Indoor unit
63
Outdoor
unit
ADDRESS
Indoor unit
62
MAIN(TEN)
MAIN(ONE)
RMC(1)
RMC(2)
Indoor unit
61
Indoor unit
50
Indoor unit
49
4 4 5 5 5 5 5 5 5 5 5 5 6 6 6 6
8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
48
RMC(1)
SW03
E-17
MCM-A202A_IM_E_29495-1.indd
17
2008-02-14
ソタネト 2:58:22
Centralized Controller Installation (Continued)
To install 19 indoor units for 1 outdoor unit +
13 indoor units for 1 DVM PLUS outdoor unit
Outdoor unit
Power cable(DC 12V)
Power cable(DC 5V)
Communication Cable
Channel 3 �� �� �� ��
Channel 2
Centralized
controller
Transmitter
DIP 1
OFF : 12V, 5V Supply
�� ��
Channel1
 Transmitter ADDRESS switch
setting should be set respectively.
Controls 16 indoor units
which have the indoor unit
RMC(1) switch set to '0'.
DVM PLUS Outdoor unit
Centralized
controller
Transmitter
MIM-B04A
 Controls 13 indoor units connected to DVM PLUS outdoor
unit, which have the indoor unit RMC switch set to '0~C'.
 Controls 3 indoor units connected to outdoor unit, which
have the indoor unit RMC switch set to '1'.
E-18
MCM-A202A_IM_E_29495-1.indd
18
2008-02-14
ソタネト 2:58:25
When setting the indoor unit address
MAIN(TEN) MAIN(ONE)
SW01
SW02
RMC(1)
RMC(2)
SW03
SW04
Indoor unit
3~12
Indoor unit
0
Indoor unit
1
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
2
Indoor unit
13
Indoor unit
14
Indoor unit
15
0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
Indoor unit
18
RMC(1)
SW03
Indoor unit
17
MAIN(TEN)
Indoor unit MAIN(ONE)
ADDRESS
RMC(1)
RMC(2)
Indoor unit
16
1 1 1
6 7 8
1
D E F
RMC(1)
SW03
When setting the indoor
unit address
MAIN
SW01
RMC
SW02
SW03
Indoor unit
3~ 9
Indoor unit
0
Indoor unit
1
Indoor unit
2
Indoor unit
10
Indoor unit
11
Indoor unit
12
Indoor unit
K9 K10
Indoor unit
ADDRESS
MAIN
0 1 2 3 4 5 6 7 8 9 10 11 12
RMC
0 1 2 3 4 5 6 7 8 9 A B C
SW06
K10 : ON
(Transmitter
selecting switch)
E-19
MCM-A202A_IM_E_29495-1.indd
19
2008-02-14
ソタネト 2:58:28
MCM-A202A_IM_E_29495-1.indd
20
2008-02-14
ソタネト 2:58:30