Download Daikin IM-820 Instruction manual
Transcript
Installation and Maintenance Manual IM-820 Group: Unitary Part Number: IM-820 Date: March 2005 Supersedes: New MCM Ceiling/Floor Convertible Split Type Air Conditioner Indoor Unit Wireless Remote Control (Standard) Outdoor Unit Wired Wall Control (Optional) © 2005 Daikin IM 820 Page 1 Table of Contents Model Numbers . . . . . . . . . . . . . . . . . . . . . 2 General Information . . . . . . . . . . . . . . . . . . 3 Safety Precautions ....................................... 3 Unit Dimensions . . . . . . . . . . . . . . . . . . . . 4 Indoor Units .................................................. 4 Outdoor Units ............................................... 4 Installation Guidelines . . . . . . . . . . . . . . . 5 Installation Diagram ..................................... 5 Installation of Outdoor Unit ........................... 5 Installation of the Indoor Unit ....................... 6 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Indoor Unit Clearances . . . . . . . . . . . . . . . . 6 Standard Mounting . . . . . . . . . . . . . . . . . . . 7 Semi-enclosed Mounting . . . . . . . . . . . . . . 7 Refrigerant Tubing . . . . . . . . . . . . . . . . . . 8 Tubing Length & Elevation . . . . . . . . . . . . . 8 Tubing Preparation . . . . . . . . . . . . . . . . . . . 8 Tubing Connection To Units . . . . . . . . . . . . 8 Electrical Connections . . . . . . . . . . . . . . . 9 Wiring Diagrams . . . . . . . . . . . . . . . . . . . 10 Evacuating and Charging . . . . . . . . . . . . 17 Evacuating the tubing and the indoor unit . 17 Additional charge . . . . . . . . . . . . . . . . . . . .17 Charge operation . . . . . . . . . . . . . . . . . . . . 17 Remote Controller Operation Guide . . . .18 Netware 2 - Wired Wall Control (Optional) 19 Special Features . . . . . . . . . . . . . . . . . . . .20 Dry mode . . . . . . . . . . . . . . . . . . . . . . . . . .20 Heat mode (heat pump only) . . . . . . . . . . .20 Overheating protection (heat pump only) . .20 Frost prevention . . . . . . . . . . . . . . . . . . . . .20 Fan speed and rated cooling capacity . . . .20 Operating Conditions ................................. 20 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Overall Checking . . . . . . . . . . . . . . . . . . . .20 Unit Indicator Lights . . . . . . . . . . . . . . . . 21 IR signal receiver . . . . . . . . . . . . . . . . . . . .21 Netware 2 - Wired Wall Control (Optional) .21 Service and Maintenance . . . . . . . . . . . . 22 Electrostatic Filters . . . . . . . . . . . . . . . . . . 22 Filter Replacement . . . . . . . . . . . . . . . . . . .22 Startup After Extended Shutdown . . . . . . .22 Troubleshooting . . . . . . . . . . . . . . . . . . . . .22 Service and Maintenance . . . . . . . . . . . . . .23 Model Numbers Cooling Only Indoor Unit MCM20D MCM25D MCM30D MCM40D MCM50D Outdoor Unit MLC20B MLC25B MLC30C MLC40C MLC50C Nominal Cooling - BTUH 20,000 25,000 30,000 40,000 50,000 Cooling/Heat Pump Indoor Unit MCM20DR MCM25DR MCM30DR MCM40DR MCM50DR Page 2 Outdoor Unit MLC20BR MLC25BR MLC30CR MLC40CR MLC50CR Nominal Cooling - BTUH 20,000 24,000 30,000 40,000 50,000 Nominal Heating - BTUH 21,000 25,000 32,000 41,000 48,000 IM 820 General Information This manual provides the installation procedures so your air conditioner unit operates properly and provides you the service it was designed to provide. Special adjustment may be necessary to suit local requirements. Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. CAUTION Use copper conductors only. Unit terminals are not designed to accept other types of conductors. Failure to do so can cause damage to the equipment. Safety Precautions Before installing the air conditioner unit, please read the following safety precautions carefully.. WARNING • The installer must determine and follow all applicable codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can cause property damage, equipment damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only. • Do not allow flammable fumes near unit or areas sharing ventilation. • Installation and maintenance must be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. • All field wiring must be done in accordance with industry standards and local codes. • Inspect the unit nameplate to be certain the voltage is the same as the voltage that will be delivered to the unit. Improper electrical wiring can cause property damage, sever personal energy or death. • The unit must be GROUNDED. • Make sure wiring does not touch refrigerant piping, compressor, or any moving parts of the fan motors. • Confirm that the power supply is switched OFF before installing or servicing the unit. WARNING Hazardous Voltage! Disconnect all electrical power including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal injury or death. IM 820 CAUTION • Do not install in a laundry room. Humidity and laundry chemicals can corrode unit components. • Do not install the unit where leakage of flammable gas may occur. If gas leaks and accumulates around the unit, it can cause a fire. • Connect drainage piping properly. If drainage piping is not connected properly, water leakage can cause property damage. • Do not overcharge the unit. This unit is factory precharged. Overcharge will cause over-current or damage to the compressor. • Keep panel closed. Unsecured panels will cause the unit to operate noisily. NOTICE This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier, as follows: VISIBLE LOSS OR DAMAGE Any external evidence of loss or damage must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrie’s refusing to honor a damaged claim. The form required to file such a claim will be supplied by the carrier. CONCEALED LOSS OR DAMAGE Concealed loss or damage means loss or damage which does not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’s agent within fifteen (15) days of the delivery date. File a claim with the carrier since such damage is the carrier’s responsibility. Page 3 Unit Dimensions Indoor Units A Two mounting brackets shipped attached to the indoor unit. See page 7 for more detail. B C E D Model MCM A B* C D E F G H 20D/DR 46 1/4" 42 1/2" 47 3/4" 26 1/2" 6 1/4" 2 1/4" 20 1/2" 22" 25D/DR 46 1/4" 42 1/2" 47 3/4" 26 1/2" 6 1/4" 2 1/4" 20 1/2" 22" F G H 30D/DR 46 1/4" 42 1/2" 47 3/4" 26 1/2" 6 1/4" 3 3/4" 20 1/2" 22" 40D/DR 66" 62 1/4" 67 1/2" 26 1/2" 6 1/4" 3 3/4" 20 1/2" 22" 50D/DR 66" 62 1/4" 67 1/2" 26 1/2" 6 1/4" 3 3/4" 20 1/2" 22" *Discharge air opening width. Outdoor Units A E B C D Model MLC A B C D E Page 4 20 & 25 B/BR 16" 33" 25 1/2" 2 1/4" 13 1/4" 30,40 & 50C/CR 19 1/4" 40 1/2" 33 1/2" 3 1/2" 15 3/4" IM 820 Installation Guidelines Installation Diagram INDOOR UNIT Air Discharge Swing Baffle IR Receiver and LED Indicator Lights Air Discharge Grille Air Intake Grille Optional Wired Wall Control Air Filters Refrigerant Tubing and Insulation Wireless IR Remote Control Air Intake Air Intake Air Discharge Nozzle OUTDOOR UNIT Installation of Outdoor Unit Install the outdoor unit in a manner to prevent mixing hot discharged air with return air flow. Also, the unit should be a suitable distance from obstructions See Figure 1 for minimum installation clearances. Double the dimensions shown if surroundings are more than 72" tall, or if there is an obstruction on top. Select the coolest possible place where intake air temperature is not greater than the outside air temperature (maximum 113°F). See Table 1, Page 7 for weight of outdoor unit. Figure 1. Outdoor Unit Minimum Clearances 40" Min. Min. Air Intake Air Discharge 12" 20" Min. Min. Air Intake IM 820 12" Service Access Page 5 Installation of the Indoor Unit Locate the installation for convenient wiring and piping. General Indoor Unit Clearances Electrical supply and installation must conform to local codes and regulations. The indoor unit must be installed in a manner to prevent mixing the cool discharged air with the hot return air. Follow the installation clearances shown in Figure 2. Do not place the indoor unit in direct sunlight. The location must be suitable for piping and drainage, and be away from doors or windows. Voltage supply fluctuation must not exceed ±10% of the rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fluctuation. Figure 2. Indoor Unit Minimum Clearances .1/2" min. 12" min. 19.68" 10" max.* *Appliances, furniture or built-in architectural features must not extend more than 10". CEILING MOUNT 16" min. 40" min. WALL/FLOOR MOUNT Page 6 IM 820 Standard Mounting Semi-enclosed Mounting Make sure the ceiling or wall is strong enough to support the weight of the unit (See Table 1). Remove the mounting brackets from the unit and secure to wall or ceiling as required. In case the unit is to be half-recessed into a false ceiling, make sure the unit is well-aligned with the ceiling. The unit must be level front to back and sloped 1/8" towards condensate drain (See Figure 3). Figure 4. Semi-enclosed Mounting Provide the installation space as shown in Figure 4. 12" min. Table 1: Unit Weight - lbs. Model 20 25 30 40 50 Weight ID Unit 95 99 99 154 154 Weight OD Unit 125 128 209 220 231 48" min. 1/2" min. 23" 12" min. Figure 3. Slope for condensate drainage Top Panel of Unit 1/2" 1/8" Ceiling Mount Slope Wall/Floor Mount Slope IM 820 22" 1/2" Mounting Surface Ceiling Board 6.3/4" 1/2" Page 7 Refrigerant Tubing Tubing Length & Elevation • Copper tubing to connect the indoor and outdoor units is supplied by others or it can be ordered from the factory. See Table 2 and Figure 5 for requirements. Remove burrs from cut ends by holding tubing downwards to prevent metal chips from entering the tubing. • Slide the flare nuts, for both the indoor unit and outdoor unit onto the copper tubing. Table 2: Refrigeration Tubing Requirements • Flare the tubing as shown in Figure 6 and Table 3. • The flare must be even and not cracked or scratched. Model 20 25 30 40 50 Maximum Length, ft. 49’ 49’ 115’ 115’ 115’ Max. elevation, ft, H 26’ 26’ 49’ 49’ 49’ Figure 6. Cutting and Flaring Tube Max. number of bends 10 10 10 10 10 Cutting Copper Tube Liquid tube size - OD 1/4" 3/8" 3/8" 3/8" 3/8" Gas tube size - OD 5/8" 5/8" 5/8" 3/4" 3/4" 1/4 Tube Note: The refrigerant pre-charged in the outdoor unit is for tubing length up to 25 ft. See Table 7 for additional R-22 refrigerant required on runs longer than 25 ft. Figure 5. Tubing length and elevations Copper Tube Indoor Unit See Table 3 Outdoor Unit Tubing Length Flaring Tool X Elevation Table 3: Tube Flaring Dimensions Tube Diameter - OD Outdoor Unit Inch Imperial Rigid 1/4 .051 .028 3/8 .063 .039 5/8 .087 .067 Tubing Connection To Units Tubing Length Elevation X (in.) • Connect the copper tubing to both the indoor and outdoor units (See Figure 7). • Torque each flare nut to specifications (See Table 4). • Cover both tubes individually with 3/8" wall foam insullation. Figure 7 Flared Tube Indoor Unit Tubing Preparation • • • Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs or brass nuts from the valves, fittings, tubings and coils until you are ready to connect suction or liquid line into valves or fittings. If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the brazing work is done. This will eliminate soot formation on the inside wall of the copper tubing. Unit Fitting Flare Nut Table 4: Tube Size (in.) Torque (ft./lb.) 1/4 13.3 3/8 31.0 5/8 48.0 Cut the copper tubing with a tube cutter (See Figure 6). Page 8 IM 820 Electrical Connections WARNING Improper installation can cause severe personal injury o r death . Wi rin g mu st b e d one by a qual ifi ed technician in compliance with local codes. • • • Wiring must be in accordance with all applicable electrical codes. Wires must not touch the refrigerant piping, compressor or any moving part. All electrical field wiring must be clamped at both the indoor unit and the outdoor unit. Note: • • Field install 10A fuse in outdoor unit as shown in wire diagrams for unit sizes 30, 40, and 50. See Table 5, and 6 for the number of wires, wire gage and fuse/circuit breaker size required. NEC requires an approved electrical disconnect within sight of the unit so that anyone working on the unit can turn off the power and see that its not accidently turned back on. This will require two disconnects, one by the outdoor unit and one by the indoor unit. IM 820 Table 5: Wire, Fuse/Breaker Requirements - Cooling Only Unit Size 20 25 Voltage - 60Hz. 1 Ph. Power supply wire size 30 40 50 208/230 12 ga. 10 ga. 8 ga. 8 ga. 6 ga. No. of 12 ga. wires between units 2 + gnd. 2 + gnd 3 + gnd 3 + gnd 3 + gnd Fuse/Breaker size 20 amp. 25 amp. 35 amp. 40 amp. 55 amp. Table 6: Wire, Fuse/Breaker Requirements - Heat Pump Only Unit Size 20 25 Voltage - 60Hz. 1 Ph. Power supply wire size 30 40 50 208/230 12 ga. 10 ga. 8 ga. 8 ga. 6 ga. No. of 12 ga. wires between units* 4 + gnd. 4 + gnd 6 + gnd 6 + gnd 6 + gnd Fuse/Breaker size 20 amp. 25 amp. 35 amp. 40 amp. 55 amp. * Not including the low voltage OD coil sensor cable. Page 9 Wiring Diagrams MODEL MCM20D/25D INDOOR UNIT- COOLING ONLY RETURN AIR SENSOR ROOM JH INDOOR COIL SENSOR ID OD CN4 CN6 TRANSFORMER L WIRELESS REMOTE CONTROLLER COMP. HIGH WIRED WALL CONTROL (OPTIONAL) LOW MED AS BLUE RED WHITE NOTE: DISCONNECT CN6 IF CN4 IS USED N2 LIVE N1 WHITE BLUE YELLOW BLACK RED FH FM FL G/Y RED WHITE BROWN AS BLACK BLACK BLACK AC GREEN/YELLOW IC GREEN/YELLOW MC KEY: ---- - FIELD SUPPLY WIRING AS - AIR SWING MOTOR COMP. L N N FAN MOTOR L2 L1 } 208/230V 1 PHASE 60Hz 12 GA. WIRE COMP N BROWN RED FAN MOTOR CAPACITOR BLUE BLUE GREEN/YELLOW BLUE C COMPRESSOR S R RED BLUE CAPACITOR WHITE MODEL MLC20B/25B OUTDOOR UNIT Page 10 IM 820 MODEL MCM 030D INDOOR UNIT- COOLING ONLY RETURN AIR SENSOR ROOM INDOOR COIL SENSOR ID OD CN4 CN6 TRANSFORMER L WIRELESS REMOTE CONTROLLER COMP. AS N2 HIGH WIRED WALL CONTROL (OPTIONAL) LOW MED N1 LIVE FH WHITE BLUE YELLOW RED FM FL BLACK RED RED WHITE NOTE: DISCONNECT CN6 IF CN4 IS USED BLUE 208-230V 1 PH 60HZ { A.C. GREEN/YELLOW KEY: ---- - FIELD SUPPLIED WIRING AS - AIR SWING MOTOR BROWN BLACK RED BLACK AS BLACK I.C. GREEN/YELLOW MC COMP. L N FAN MOTOR 12 GA. WIRE L2 L1 N CAP. S R COMP. RED G/Y *10A RED *10A HIGH / LOW PRESSURE SWITCH RED REDREDRED A C R/L1S/L2 T/L3 A1 MAGNETIC 1 CONTACTOR 2 U/T1V/T2 W/T3 A2 BLUE REDRED BLACK N L BLUE BLUE RED RED RED BLUE BLUE BLUE BLACK GREEN/YELLOW L WHITE WHITE *NOTE: FIELD INSTALL 10A FUSE IN BLUE AND RED WIRE AS SHOWN WHITE RED WHITE RED R S RED BROWN C FAN G/Y COMPRESSOR CRANKCASE MOTOR HEATER BROWN MODEL MLC30C OUTDOOR UNIT IM 820 Page 11 MODEL MCM40D/50D INDOOR UNIT- COOLING ONLY RETURN AIR SENSOR ROOM INDOOR COIL SENSOR ID CN4 CN6 TRANSFORMER L WIRELESS REMOTE CONTROLLER COMP. N2 HIGH WIRED WALL CONTROL (OPTIONAL) LOW MED AS LIVE N1 FH WHITE BLUE YELLOW RED RED PURPLE NOTE: DISCONNECT CN6 IF CN4 IS USED RED FM FL BLUE WHITE BLACK RED AS BLACK A.C. GREEN/YELLOW KEY: ---- - FIELD SUPPLIED WIRING AS - AIR SWING MOTOR { 208-230V 1 PH 60Hz I.C. GREEN/YELLOW MC COMP. L/L1 N/L2 FAN MOTOR 12 GA. WIRE L2 L1 *NOTE: FIELD INSTALL 10A FUSE IN BLUE AND RED WIRE AS SHOWN COMP. L/L1 N/L2 BLUE GREEN/YELLOW BLACK PURPLE RED *10A FUSE BLUE *10A FUSE RED 8 REDRED RED 1L1 3L2 5L3 1 2T1 4T2 6T3 2 REDRED 7 BLUE A1 RED 6 A2 2 LOCK OUT RELAY RED PURPLE BLUE BLACK HIGH PRESSURE SWITCH LOW PRESSURE SWITCH BLUE RED GREEN/YELLOW L/L1 N/L2 BLUE BLACK WHITE RED RED RED BLUE BROWN C FAN G/Y COMPRESSOR CRANKCASE MOTOR HEATER BROWN R S RED BLUE WHITE MODEL MLC40C/50C OUTDOOR UNIT Page 12 IM 820 MODEL MCM20DR/25DR INDOOR UNIT - HEAT PUMP RETURN AIR SENSOR ROOM JH INDOOR COIL SENSOR RMODE CN3 ID OD CN4 CN6 TRANSFORMER L N1 BLUE FH WHITE BLUE YELLOW RED RED WHITE BROWN BLUE NOTE: DISCONNECT CN6 IF CN4 IS USED N2 LIVE RED AS HIGH WTP 4WV DDH COMP. LOW MED BLACK WIRELESS REMOTE CONTROLLER WIRED WALL CONTROL (OPTIONAL) RED FM FL BLUE G/Y BLACK BLACK BLACK RED WHITE AS A.C. GREEN/YELLOW I.C. GREEN/YELLOW MC 4WV OF COMP. L N N FAN MOTOR KEY: ---- - FIELD SUPPLIED WIRING AS - AIR SWING MOTOR 4WV - 4 WAY VALVE L2 L1 LOW VOLTAGE CABLE TO OUTDOOR COIL SENSOR 208-230V 1 PH 60Hz 12 GA. WIRE 4WV OF COMP. BLACK N BLACK GREEN/YELLOW TH2 BLACK BLUE GREEN/YELLOW BROWN BLUE WHITE BLUE C CONPRESSOR RED MOTOR S BLUE RED FAN MOTOR WHITE BROWN R BLUE BLACK 4V BLACK KEY: ---- - FIELD SUPPLIED WIRING 4V - 4 WAY VALVE TH2 - OUTDOOR THERMISTOR AS - AIR SWING MOTOR MOEL MLC20BR/25BR OUTDOOR UNIT IM 820 Page 13 MODEL MCM 30DR INDOOR UNIT - HEAT PUMP RETURN AIR SENSOR ROOM JH INDOOR COIL SENSOR RMODE CN3 ID OD TO OUTDOOR DEFROST SENSOR CN4 CN6 TRANSFORMER L LOW MED N1 WHITE BLUE YELLOW RED RED WHITE BROWN BLUE LIVE RED FH FM FL BLUE BROWN AS NOTE: DISCONNECT CN6 IF CN4 IS USED: BLACK N2 HIGH 4WV WTP COMP. WIRELESS REMOTE CONTROLLER DDH WIRED WALL CONTROL (OPTIONAL) RED BLACK AS BLACK A.C. KEY: ---- - FIELD SUPPLIED WIRING AS - AIR SWING MOTOR 4WV - 4 WAY VALVE N FAN MOTOR 12 GA. WIRE L2 L1 A BLACK *NOTE: FIELD INSTALL 10A FUSE IN BLUE AND RED WIRE AS SHOWN N RED 4WV WHITE BLACK CRANKCASE HEATER C BLACK WHITE BLUE HIGH PRESSURE SWITCH BROWN A2 L G/Y BROWN A1 COMP. WHITE *10A FUSE WHITE WHITE BLUE 22 T1 T2 T3 14 REDRED WHITE WHITE O/D COIL SENSOR REDREDRED 21 L1 L2 L3 13 OF BLUE GREEN/YELLOW RED 4WV *10A FUSE BLACK BLUE BLUE N RED L BLACK { GREEN/YELLOW MC A 4WV OF COMP. L LOW VOLTAGE CABLE TO OUTDOOR COIL SENSOR 208-230V 1 PH 60Hz I.C. GREEN/YELLOW R S RED BLUE COMPRESSOR FAN MOTOR MODEL MLC30CR - OUTDOOR UNIT Page 14 IM 820 MODEL MCM 40DR/50DR INDOOR UNIT RETURN AIR SENSOR ROOM JH INDOOR COIL SENSOR RMODE CN3 ID OD TO OUTDOOR DEFROST SENSOR CN4 CN6 TRANSFORMER L N2 HIGH WTP AS LIVE N1 WHITE BLUE YELLOW RED RED PURPLE BROWN BLUE 4WV DDH COMP. LOW MED RED FH FM FL BLACK BROWN WIRELESS REMOTE CONTROLLER BLACK AS WHITE KEY: ---- - FIELD SUPPLIED WIRING AS - AIR SWING MOTOR RED WIRED WALL CONTROL (OPTIONAL) BLACK A.C. I.C. GREEN/YELLOW GREEN/YELLOW MC A 4WV OF COMP.L L1 N L2 FAN MOTOR LOW VOLTAGE CABLE TO OUTDOOR COIL SENSOR L2 L1 A RED 4WV PURPLE BLACK HIGH PRESSURE SWITCH WHITE BLUE BROWN BLUE G/Y PURPLE BLACK S RED C COMPRESSOR BLUE WHITE A2 CRANKCASE HEATER R BLACK *10A FUSE A1 WHITE 2T14T2 6T3 2 REDREDRED WHITE BLUE O/D COIL SENSOR REDREDRED 1L1 3L2 5L3 1 OF BLUE GREEN/YELLOW RED 4WV *10A FUSE BLACK RED BLUE *NOTE: FIELD INSTALL 10A FUSE IN BLUE AND RED WIRE AS SHOWN COMP. L L1 N L2 BROWN L L1 N L2 BLUE { 208-230V 1 PH 60Hz 12 GA. WIRE FAN MOTOR MODEL MLC40CR/50CR IM 820 Page 15 MODEL : MLC 20B - 25B OUTDOOR UNIT - COOLING ONLY - OPTIONAL LOW AMBIENT KIT (208/230V - 1 PHASE - 60HZ) WHITE OL C RED S CM CAPACITOR BLUE R GREEN/YELLOW BLUE BLUE CAPACITOR FM YELLOW ORANGE 1 2 OUTDOOR COIL SENSOR 3 4 5 COMP N FSCM KEY CM - COMPRESSOR MOTOR FM - OUTDOOR FAN MOTOR FSCM - FAN SPEED CONTROL MODULE 12 GA. FIELD SUPPLIED WIRING (TO INDOOR UNIT) MODEL : MLC 20BR - 25BR OUTDOOR UNIT - HEAT PUMP - OPTIONAL LOW AMBIENT KIT (208/230V - 1 PHASE - 60HZ) KEY FM - FAN MOTOR CM - COMPRESSOR MOTOR 4V - 4 WAY VALVE TH2 - OUTDOOR THERMISTOR FSCM - FAN SPEED CONTROL MODULE 12 GA. FIELD SUPPLIED WIRING (TO INDOOR UNIT) BLACK BROWN N 4V OF COMP. BLACK E BLUE BLACK BROWN BLACK GREEN/YEL TH2 BLUE 1 BLUE WHITE 2 FSCM ORANGE BROWN YELLOW 3 BLACK E 4 C RED RED S BLUE E BLUE BLACK Page 16 CM WHITE R BLACK FM 4V BLACK IM 820 Evacuating and Charging Evacuating the tubing and the indoor unit The outdoor unit is pre-charged with refrigerant R-22. The indoor unit and the refrigerant connection tubing must be evacuated as follows: 1. Remove the 3 caps from the valves on the outdoor unit. 2. Connect the center of the charging gauge to the vacuum pump. Connect the charging gauge to the service port of the 3-way valve (See Figure 9). Start the pump and evacuate to -760 mm Hg (-29.9" Hg). Close the valve of the changing gauge and stop the vacuum pump. On the outdoor unit, open both valves using a 4 mm Allen wrench (See Figure 8). 3. 4. 5. 6. Table 7: Additional R-22 ounces per foot of tubing (when tubing length is more than 25 ft.) and maximum tubing length. Model Oz. Per ft. Max. Length 20D .16 49’ 25D .40 49’ 30D .53 115’ 40D .55 115’ 50D .55 115’ 20DR .16 49’ 25DR .50 49’ 30DR .53 115’ 40DR .55 115’ 50DR .55 115’ Charge operation Figure 8. 3-way Suction Valve on Outdoor Unit Hex Socket for 4 mm Allen wrench Refrigerant Tubing Flare Nut Service Port This operation must be done by weighing the R-22 being added thru the service port on the 3-way suction valve. See Table 7 and Figure 10. 1. Remove the service port cap. 2. Connect the low pressure side of the charging gauge to the suction service port center of the cylinder tank and close the high pressure side of the gauge. Purge the air from the service hose (See Figure 10). Start the air conditioner unit. Open the gas cylinder and low pressure charging valve. When the required refrigerant quantity is pumped into the unit, close the low pressure side and the gas cylinder valve. Disconnect the service hose from service port. Put back the service port cap. 3. 4. 5. Outdoor Unit 3-way Valve 6. Figure 9 Evacuation Schematic Outdoor Unit Indoor Unit Liquid side Discharge Valve Close Figure 10. Charging Schematic Outdoor Unit Indoor Unit Liquid side Discharge Valve Gas side Suction Valve Gas side Close Vacuum Pump Suction Valve Low Press. High Press. Low Press. High Press. Additional charge The refrigerant is pre-charged in the outdoor unit. If the tubing length between the indoor and outdoor unit is no more than 25 ft., then an additional charge after evacuation is not necessary. If the tubing length is more than 25 ft., use additional R-22 as indicated in Table 7. IM 820 Page 17 Remote Controller Operation Guide Transmission source Signal Transmission Indication • • The source where the signal is transmitted. Blinks to confirm the last setting was sent to the unit. Temperature Setting • Set the desired room temperature by pressing the buttons to increase or decrease the set temperature. On/Off Button • Press once to start the air conditioner. Press again to stop the air conditioner. • The temperature setting range is from 60°F to 86°F. • • Press both buttons simultaneously to toggle the temperature setting between °C and °F. Operation mode Fan Speed Selection • Press the button until the desired fan option displays (auto, low, med. or high). "Auto" automatically selects high fan until room temperature is within 2oF of setting, then switches to low fan. Fan runs continuouse in COOL and cycles in HEAT. Press the SET button will activate the on timer function. • Set the desired on time by pressing the SET button continuously. If the timer is set to 7.30am, the air conditioner will turn on at 7.30 sharp. • Press the CLR button to cancel the on timer setting. Press the MODE button to select the type of operating mode. • For cooling only unit, the available modes are : COOL, DRY & FAN. • For heat pump unit, the available modes are: AUTO, COOL, DRY, FAN & HEAT. OFF Timer Setting ON Timer Setting • • • Press the SET button will activate the off timer function. • Set the desired off time by pressing the SET button continuously. • Press the CLR button to cancel the off timer setting. Sleep mode setting Automatic Air Swing • Press the button to activate sleep mode. This function is available under COOL, HEAT & AUTO mode. • In COOL mode, the set temperature will increase 1.0°F after 30 minutes, 2°F after 1 hour and a total of 4°F after 2 hours. • In HEAT mode, the set temperature will decrease 2°F after 30 minutes, 4°F after 1 hour and a total of 5°F after 2 hours. Clock Time Setting • Press the SWING button to activate the automatic air swing function. • To distribute the air to a specific direction, press the SWING button and wait until the air conditioner baffle swings to the desired direction. Press the button again to hold it. • Press button + or - to increase or decrease the clock time. Symbol Identification Auto Cool Page 18 Dry Fan Heat Sleep Power Timer Auto low med high Fan Speed IM 820 Netware 2 - Wired Wall Control (Optional) Features: 1. Modes - Cool, Heat, Auto, Dry, Fan and Off. AUTO SLEEP DRY AUTO COOL HEAT FAN SET CLOCK MON TUE WED THU FRI SAT SUN ON AM PM OFF TIME ACTIVATE SET TIMER SET CLOCK COOL TEMP. HEAT TEMP. ROOM TEMP. SWING ˚F ˚C ON/OFF FAN SLEEP MODE SET TEMP SWING ON TIMER OFF TIMER DAY HOUR CLOCK HOLD IM 820 MINUTE 2. Temperature Range - 60° F to 86° F. (Press both arrows simultaneously to convert from °C to °F.) 3. Timer - Seven day clock capable of a different On/Off time for each day of the week. Note: Hold button is used to temporarily override timer. 4. Shows time of day. 5. Electronic lockout to prevent tampering. 6. Fan Speeds - Low, medium, high and auto. 7. Sleep - Sets temperature back for sleeping. 8. Swing - Swings or positions air baffle for better air distribution. 9. Display normally shows room temperature. (Momentarily shows set point when a change is made.) 10. Heat symbol (Ã ) blinks while outdoor coil defrosts (heat pump only). 11. Error codes blink on display: E1 - Room sensor loose or defective. E2 - Indoor coil sensor loose or defective. E3 - Outdoor coil sensor loose or defective. E4 - Compressor cycling on overload. E5 - Low refrigerant charge. For more detail, see manual that ships with the Wall Control. Page 19 Special Features Dry mode • Heating (heat pump only) Select this mode when the standard Cool mode does not provide sufficient dehumidification. The compressor and indoor low fan will cycle together and will operate for longer periods of time to provide the increased rate of dehumidification. As a result, the room temperature differential may increase slightly. Heat mode (heat pump only) • • Temperature Ts °F Th °F Minimum Indoor 61 — Maximum Indoor 86 — Minimum Outdoor 16 21 Maximum Outdoor 75 64 Ts = Dry Bulb Temperature, Th = Wet Bulb Temperature When the unit is switched on from cold start or defrosting cycle, the indoor fan will start to operate only after the coil warms up. When the set temperature is achieved, the indoor fan will operate until the coil cools down. Overall Checking Ensure that: 1. The unit has been mounted properly. Overheating protection (heat pump only) 2. Refrigerant tubing connections have been checked for leaks • 3. Proper wiring and circuit breakers have been installed. In case the coil overheats (145°F), the compressor will cut out. Frost prevention • If the indoor coil starts to frost, an LED light will blink to indicate that the unit is in defrost. Fan speed and rated cooling capacity • The rated cooling capacity is provided at high indoor fan speed. • The cooling capacity is slightly lower when the unit is operating at MEDIUM and LOW fan speed. Operating Conditions Cooling Temperature Ts (dry bulb) °F Th (wet bulb) °F Minimum Indoor 61 52 Maximum Indoor 90 73 Minimum Outdoor 66* 24 Maximum Outdoor 114 75 Drainage check: Check condensate drain for leaks and proper flow. Test run: Check the following items: • Are all electrical plugs firmly inserted into there receptcales? • Is there any abnormal sound from the unit? • Is there any abnormal vibration on the unit itself or piping? Confirm that: 1. Condenser fan is running, with warm/cold air blowing off the outdoor unit. (Cooling only/Heat Pump) 2. Evaporator blower is running and discharge cool/warm air. (Cooling only/Heat Pump) Note: The control incorporates a 3 minute randum start delay in the circuit. Thus, it requires about 3 minutes before the outdoor unit will start. * 32°F on size 20 and 25, 23°F on size 30, 40 and 50 with optional Low Ambient Kit. Page 20 IM 820 Unit Indicator Lights IR signal receiver Wireless Remote Control When an infrared remote control operating signal is transmitted, the indoor unit beeps and indicator lights confirm acceptance of the signal transmission. Figure 12. LED Indicator Lights Display Cooling Unit Figure 11. IR Receiver & LED Indicator Lights Location INDOOR UNIT Air Discharge Swing Baffle IR Receiver and LED Indicator Lights Air Discharge Grille Air Filters Air Intake Grille Optional Wired Wall Control Cool Dry Fan Cool Dry Fan Heat Wireless Remote Control Figure 13: Mode and Diagnostic Chart Mode or Fault Cool Dry Fan Heat Cooling mode Dry mode Fan mode Heat mode Auto mode in heating operation. Auto mode in cooling operation. Defrost operation Compressor overload protection Outdoor coil sensor contact loose/short Room air sensor contact loose/short ON Blinking Netware 2 - Wired Wall Control (Optional) Error codes blink on wall control display as follows: E1 - Room sensor loose or defective. E2 - Indoor coil sensor loose or defective. E3 - Outdoor coil sensor loose or defective. E4 - Compressor cycling on overload. E5 - Low refrigerant charge. IM 820 Page 21 Service and Maintenance WARNING Disconnect the electrical power supply before performing any service, maintenance or troubleshooting. Electrostatic Filters Pre-charged electrostatic polypropylene filter removes microscopic dust, smoke and small invisible particles to keep the room air clean. Filter Replacement Startup After Extended Shutdown • Inspect thoroughly and clean indoor and outdoor units. • Clean or replace air filter. • Clean condensate drain line. • Clean clogged indoor and outdoor coils. • Check fan imbalanced before operation. • Tighten all wire connections. • Check for refrigerant leakage. Note: WARNING Disconnect the main power supply before opening the return air grille. DO NOT restore power until the grille is closed. The crankcase heater should be energized for at least 6 hours before starting the unit. Troubleshooting If any malfunction of the unit is noted, immediately switch off the power supply. See Figure 14. Check the following chart for possible causes/treatments. Replace the electrostatic air purifying filters every 6 months or sooner if they turn brown. If the trouble persists, please call your local dealer/serviceman. Replacement filters can be purchased from your sales representative or distributor. Use the new filter immediately once it has been removed from the package. 1. Open the return air grilles and remove the filters. 2. Use a vacuum cleaner or wash with water with a neutral cleaning agent. Rise and dry before installing the filter. 3. Note: Trouble The compressor does not operate. Possible cause/treatment Protection against frequent starting. Wait for 3 to 4 minutes for the compressor to start operating. Power failure. Check fuse or circuit breaker. Fans and compressor do not operate. Never use chemicals such as gasoline or paint thinner to clean the filters. Filters will be damaged. Power supply disconnect off. Delay timer may be set incorrectly. Dirty air filters. Figure 14. Changing the Filters Air flow too low or insufficient cooling/heating capacity. Doors or windows open. Adjust thermostat setting. Discharge air flow has bad odor. Smoke, perfume, etc. may have collected on the indoor coil. Clean coil. Use dry mode. High humidity in conditioned space. Condensation on the return air grille of the indoor unit. Page 22 Set temperature too low. Increase temperature setting and operate unit at high fan speed. Condensate leaking into room. Condensate drain plugged. Hissing sound from the unit during operation. Refrigerant fluid flowing into the evaporator coil. Operate for a while to see if sound goes away. IM 820 Service and Maintenance WARNING Disconnect the main power supply before performing any service, maintenance or troubleshooting. The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention. Item Maintenance Procedures Frequency Indoor Unit Air Filters 1. Remove the filter before cleaning it. 2. Remove the dust adhering on the filter by using a vacuum cleaner or wash with lukewarm water (below 40°C/104°F) with neutral detergent solution. At least once a month. 3. Rinse well and dry the filter before placing it back onto the unit. Note. Do not use gasoline, volatile substances or chemicals to clean the filter. Indoor Unit Clean the grille and panel by wiping it using soft cloth soaked in lukewarm water (below 40°C/104°F) with neutral detergent solution. Note. Do not use gasoline, volatile substances or chemicals to clean the unit. Every year. Check and clean if necessary. Every year. Condense Drain Pan and Pipe Indoor Fan Indoor/Outdoor Coil Power Supply Compressor Compressor Oil Fan Motor Oil IM 820 . Check for abnormal noise. Every year. Clean the louvers and coil. Be careful not to bend or flatten the aluminium fins. DO NOT use cleaning fluids that might corrode the coil. Every year. 1. Check the running current and voltage for indoor and outdoor units. 2. Check the electrical wiring and tighten the terminals. Every year. No maintenance needed if refrigerant circuit remains sealed. However, check for refrigerant leaks at joints and fittings. Every year. Oil is factory charged. Not necessary to add oil if circuit remains sealed. No maintenance required. All motors are pre-lubricated and sealed at factory. No maintenance required. Page 23 This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com. Daikin Applied 800.432.1342 www.DaikinApplied.com © 2004 Daikin