Package Gas-Electric
Installation Instructions
is a trademark of Maytag Corporation and is used under
license to Goodman Company, L.P. All rights reserved.
®
DESIGN
CE RTIF IE D
CE
R TI FI E D
®
This Forced Air Central Unit Design Complies With
Requirements Embodied in The American National
Standard / National Standard of Canada Shown Below.
ANSI Z21.47•CSA-2.3 Central Furnaces
TO THE INSTALLER
Before installing this unit please read this manual to familiarize
yourself on the specific items which must be adhered to such
as maximum external static pressure to unit, air temperature
rise, minimum or maximum CFM and motor speed
connections.
TO THE OWNER
It is important to complete the owner registration card and
mail it immediately. This will assist us in contacting you if any
service or warranty information should change in the future.
When completing the registration card, be sure to include the
Model, Manufacturing and Serial Numbers, plus the installation
date.
The warranty certificate is also supplied with the unit. Read
the warranty carefully and note what is covered. Keep the
warranty certificate in a safe place so you can find it if
necessary.
If additional operating instructions are required, call the dealer
where the purchase was made. Keep this literature in a safe
place for future reference.
Part No. 10692413
Printed in USA
These installation instructions cover the outdoor
installation of single package gas electric heating and
cooling units. See the Product Data Book applicable to
your model* for information regarding accessories.
*NOTE: Please contact your distributor or our
website for the applicable product data
book referred to in this manual.
Goodman Company, L.P.
1810 Wilson Parkway • Fayetteville, Tennessee 37334
www.amana-hac.com
2002-2004 Goodman Company, L.P.
Effective: June 2004
Table of Contents
RECOGNIZE SAFETY SYMBOLS, WORDS, AND LABELS .............................................................................................. 3
Safety Instructions ............................................................................................................................................................. 3
ALL INSTALLATIONS: ........................................................................................................................................... 4
GROUND LEVEL INSTALLATIONS ONLY ................................................................................................................... 4
ROOFTOP INSTALLATIONS ONLY ............................................................................................................................ 4
General Information ........................................................................................................................................................... 4
SHIPPING AND HANDLING ..................................................................................................................................... 5
RIGGING AND HANDLING ...................................................................................................................................... 5
PROPER PIPING PRACTICE .................................................................................................................................. 5
HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY) ............................................................................................. 5
GAS PIPING CHECKS .......................................................................................................................................... 6
Propane Gas Installations ................................................................................................................................................. 6
TANKS AND PIPING ............................................................................................................................................. 7
PROPANE GAS PIPE SIZING ................................................................................................................................. 7
Electrical Connections ....................................................................................................................................................... 7
THERMOSTAT ..................................................................................................................................................... 7
WIRING ............................................................................................................................................................ 7
UNIT VOLTAGE .................................................................................................................................................. 8
Air Circulation and Filters ................................................................................................................................................. 8
AIRFLOW CONVERSION ....................................................................................................................................... 8
DUCTWORK ....................................................................................................................................................... 8
FILTERS ............................................................................................................................................................ 9
FILTER INSTALLATION .......................................................................................................................................... 9
Venting ................................................................................................................................................................................ 9
FLUE HOOD AND AIR INLET HOOD INSTALLATION .................................................................................................... 9
HIGH STATIC OR DOWN-DISCHARGE INSTALLATION .................................................................................................. 9
CONDENSATE DRAIN CONNECTION ........................................................................................................................ 9
Normal Sequences of Operation ..................................................................................................................................... 10
HEATING ......................................................................................................................................................... 10
COOLING ........................................................................................................................................................ 10
FAN ONLY ...................................................................................................................................................... 10
Startup, Adjustments, and Checks ................................................................................................................................. 10
HEATING STARTUP ........................................................................................................................................... 10
COOLING STARTUP ........................................................................................................................................... 14
Troubleshooting ............................................................................................................................................................... 14
ABNORMAL OPERATION - HEATING ...................................................................................................................... 14
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART ................................................................................................ 15
Maintenance ..................................................................................................................................................................... 15
REPLACING OR CLEANING FILTER ...................................................................................................................... 15
MAINTAINING CABINET FINISH ............................................................................................................................ 16
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY) .............................................................................................. 16
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS .................................................................................... 16
FLAME SENSOR (QUALIFIED SERVICER ONLY) ...................................................................................................... 16
FLUE PASSAGES (QUALIFIED SERVICER ONLY) ..................................................................................................... 16
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY) .............................................................................................. 16
Accessories and Functional Parts .................................................................................................................................. 17
SHEET METAL ACCESSORIES ............................................................................................................................. 17
FUNCTIONAL PARTS ......................................................................................................................................... 17
2
SAFETY INSTRUCTIONS
RECOGNIZE SAFETY SYMBOLS, WORDS, AND LABELS
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s
and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to
heed safety information increases the risk of personal injury, property damage, and/or product damage.
WARNING
WARNING - Hazards or unsafe practices which COULD result in severe personal injury or death.
CAUTION
CAUTION - Hazards or unsafe practices which COULD result in minor or moderate personal injury, product damage, property
damage.
WARNING
IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A
FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE.
–
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
–
WHAT TO DO IF YOU SMELL GAS:
• DO NOT TRY TO LIGHT ANY APPLIANCE.
• DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY
CARBON MONOXIDE POISONING HAZARD
Special Warning for Installation of Furnace or Air Handling Units in
Enclosed Areas such as Garages, Utility Rooms or Parking Areas
PHONE IN YOUR BUILDING.
• IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S
PHONE.
FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS.
Carbon monoxide producing devices (such as an automobile, space
heater, gas water heater, etc.) should not be operated in enclosed areas
such as unventilated garages, utility rooms or parking areas because of
the danger of carbon monoxide (CO) poisoning resulting from the exhaust
emissions. If a furnace or air handler is installed in an enclosed area such
as a garage, utility room or parking area and a carbon monoxide producing
device is operated therein, there must be adequate, direct outside
ventilation.
• IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL THE FIRE
DEPARTMENT.
– INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER,
SERVICE AGENCY OR THE GAS SUPPLIER.
WARNING
This ventilation is necessary to avoid the danger of CO poisoning which
can occur if a carbon monoxide producing device continues to operate in
the enclosed area. Carbon monoxide emissions can be (re)circulated
throughout the structure if the furnace or air handler is operating in any
mode.
THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE
STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER
CO can cause serious illness including permanent brain damage or death.
REPRODUCTIVE HARM.
B10259-216
WARNING
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN
OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE
HEATING UNIT SHOULD NOT BE UTILIZED WITHOUT REASONABLE, ROUTINE,
TURNING OFF THE ELECTRICAL SUPPLY.
INSPECTION, MAINTENANCE AND SUPERVISION. IF THE BUILIDNG IN WHICH ANY
SUCH DEVICE IS LOCATED WILL BE VACANT, CARE SHOULD BE TAKEN THAT
WARNING
SUCH DEVICE IS ROUTINELY INSPECTED, MAINTAINED AND MONITORED. IN THE
EVENT THAT THE BUILDING MAYBE EXPOSED TO FREEZING TEMPERATURES
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE
THIS UNIT IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A
AND WILL BE VACANT, ALL WATER-BEARING PIPES SHOULD BE DRAINED, THE
BUILDING SHOULD BE PROPERLY WINTERIZED, AND THE WATER SOURCE
QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE
CLOSED. IN THE EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING
ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN
TEMPERATURES AND WILL BE VACANT, ANY HYDRONIC COIL UNITS SHOULD
UNDER WATER.
BE DRAINED AS WELL AND, IN SUCH CASE, ALTERNATIVE HEAT SOURCES
SHOULD BE UTILIZED.
WARNING
THIS UNIT MUST NOT BE USED AS A "CONSTRUCTION HEATER" DURING THE
THIS TYPE OF
FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE.
USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY
LOW RETURN AIR TERMPERATURES AND EXPOSURE TO CORROSIVE OR VERY
DIRTY ATMOSPHERES.
3
UNIT LOCATION
•
The combustion air inlet and flue outlet hoods on the side of
the unit must never be obstructed. If used, do not allow the
economizer/manual fresh air damper/ motorized fresh air
damper to become blocked by snow or debris. In some
climates or locations, it may be necessary to elevate the
unit to avoid these problems.
•
When the unit is heating, the temperature of the return air
entering the unit must be between 50° F and 100° F.
•
Provisions must be made for adequate combustion and
ventilation air in accordance with Section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code,
NFPA 54/ ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CAN/
CSA B149 Installation Codes, or applicable provisions of
the local building codes.
WARNING
TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
ALL INSTALLATIONS:
•
For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted level.
•
The flue outlet hood must be at least 12 inches from any
opening through which flue gases could enter a building,
and at least three feet above any forced air inlet located
within ten feet. The economizer/manual fresh air intake/
motorized fresh air intake and combustion air inlet mounted
on the unit are not affected by this restriction.
•
GROUND LEVEL INSTALLATIONS ONLY
To avoid possible corrosion of the heat exchanger, do not
locate the unit in an area where the outdoor air (i.e.
combustion air for the unit) will be frequently contaminated
by compounds containing chlorine or fluorine. Common
sources of such compounds include swimming pool
chemicals and chlorine bleaches, paint stripper, adhesives,
paints, varnishes, sealers, waxes (which are not yet dried)
and solvents used during construction and remodeling.
Various commercial and industrial processes may also be
sources of chlorine/fluorine compounds.
•
To avoid possible illness or death of the building occupants,
do NOT locate outside air intake device (economizer, manual
fresh air intake, motorized fresh air intake) too close to an
exhaust outlet, gas vent termination, or plumbing vent outlet.
For specific distances required, consult local codes.
•
Allow clearances from the enclosure as shown for fire
protection, proper operation, and service access. These
clearances must be permanently maintained.
•
The base should also be located where no runoff of water
from higher ground can collect in the unit.
•
To avoid possible personal injury or property damage, the
roof must have sufficient structural strength to carry the
weight of the unit(s) and snow or water loads as required by
local codes.
• The unit may be installed directly on wood floors or on Class
A, Class B, or Class C roof covering material.
• To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
NOTE: Refer to the Product Data Book applicable to your
model* or the unit Rating Plate for approved duct orientation,
before using down discharge openings.
This unit is approved only for an outdoor installation.
GENERAL INFORMATION
To assure that your unit operates safely and efficiently, it must
be installed, operated, and maintained in accordance with these
installation and operating instructions, all local building codes
and ordinances, or in their absence, with the latest edition of
the National Fuel Gas Code NFPA54/ANSI Z223.1 and National
Standard of Canada CAN/CSA-2.3.
The heating and cooling capacities of the unit should be greater
than or equal to the design heating and cooling loads of the
area to be conditioned. The loads should be calculated by an
approved method or in accordance with A.S.H.R.A.E. Guide or
Manual J - Load Calculations published by the Air Conditioning
Contractors of America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE,
CLEARANCES TO COMBUSTIBLE SURFACES LISTED IN THE FIGURE BELOW
MUST BE OBSERVED.
24" Clearance
(Condenser End)
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended.
Prepare a base 47 inches by 49 inches or slightly larger and
3 inches thick.
ROOFTOP INSTALLATIONS ONLY
CAUTION
36" Side
Clearance
for Servicing
Recommended
•
36"
Maximum
Overhang
48" Minimum
Overhang
Vinyl Coated
Canvas
Connections
Insulated
Return
Duct
Minimum 9" Clearance
to Combustibles
36" Clearance for
Service Required
0" Minimum
Clearance to
Combustibles
Insulated
Supply
Duct
Minimum Clearances for Unit
*NOTE: Please contact your distributor or our website for the applicable product data book referred to in this manual.
4
PROPER PIPING PRACTICE
The gas line installation must comply with local codes, or in the
absence of local codes, with the latest edition of the National
Fuel Gas Code NFPA 54/ANSI Z223.1.
IMPORTANT NOTE: This unit is factory set to operate on
natural gas at the altitudes shown on the rating plate. The
plate is stamped with the model number, type of gas and gas
input rating. Make sure the unit is equipped to operate on the
type of gas available.
WARNING
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DUE TO FIRE,
EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELECTRIC SHOCK OR CARBON
MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED,
AND MAINTAINED.
SHIPPING AND HANDLING
Units are securely packed in shipping containers approved by
the International Safe Transit Association. Check the carton
upon arrival for external damage. If damage is found, file a
request in writing for inspection by the carrier agent immediately.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim. The
distributor or manufacturer will not accept claims from dealers
for transportation damage. If no damage is found, carefully
remove all shipping material and properly dispose of it.
Keep the unit as upright as possible. Laying the unit on its side
or top could cause equipment damage.
DO NOT VARY FROM THE MINIMUM SUPPLY PRESSURE
GIVEN IN THE INLET GAS PRESSURE TABLE.
Doing so could create ignition problems.
Inlet Gas Pressure
Natural
Propane
Min. 5.0" W.C., Max. 10.0" W.C.
Min. 11.0" W.C., Max. 13.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in
Table Above.
DO NOT EXCEED THE RATED INPUT SHOWN ON THE
RATING PLATE.
Overfiring of the unit could result in premature heat
exchanger failure.
RIGGING AND HANDLING
WARNING
DO NOT UNDERSIZE THE NATURAL/PROPANE GAS
PIPING FROM THE METER/TANK TO THE UNIT.
Doing so could cause unsatisfactory operation or equipment
damage due to under firing of equipment.
When sizing a trunk line, include all appliances on that line
that could be operated simultaneously.
TO PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT
POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE
LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN
ADEQUATE CABLE SLING.
NOTE: Refer to Product Data Book applicable to your model* or the
unit Rating Plate for approved duct orientation, before using down
discharge openings.
Natural Gas Capacity of Pipe
in Cubic Feet of Gas Per Hour (CFH)
Nominal Black Pipe Size (inches)
Length of
Pipe in Feet
1
1/2
3/4
1 1/4
1 1/2
10
132
278
520
1050
1600
20
92
190
350
730
1100
30
73
152
285
590
980
40
63
130
245
500
760
50
56
115
215
440
670
60
50
105
195
400
610
70
46
96
180
370
560
80
43
90
170
350
530
90
40
84
160
320
490
100
38
79
150
305
460
Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based
on 0.60 Specific Gravity Gas)
Important: If using bottom discharge with roof curb, ductwork
should be attached to the curb prior to installing the unit.
Ductwork dimensions are shown in roof curb installation
instructions.
Refer to the Roof Curb Installation Instructions for proper curb
installation. Curbing must be installed in compliance with the
National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit,
center of gravity will cause condenser end to be lower than
supply air end.
If using a fork lift, see the following figure for location of fork
prongs. Make certain prongs support unit weight.
CFH =
Fork Lift From
Back Of Unit
BTUH Furnace Input
Heating Value of Gas (BTU/Cubic Foot)
WARNING
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN EITHER
USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL
THE PROPER CONVERSION KIT(S).
FAILURE TO DO SO CAN RESULT IN
HIGH ALTITUDE
UNSATISFACTORY OPERATION AND/OR EQUIPMENT DAMAGE.
KITS ARE FOR
IN
U.S. INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE
CANADA.
HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY)
IMPORTANT NOTE: The gas/electric units naturally derate with
altitude. Do not attempt to increase the firing rate by changing
orifices or increasing the manifold pressure. This can cause
poor combustion and equipment failure.
Fork Lift Unit Positioning
5
GAS PIPING CHECKS
At all altitudes, the manifold pressure must be within 0.3 inches
w.c. of that listed in the “Product Data Book applicable to your
model*” for the fuel used. At all altitudes and with either fuel,
the air temperature rise must be within the range listed on the
unit nameplate.
Refer to the following table for kit conversions from natural gas
to propane gas and for altitude adjustments.
CAUTION
TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE
FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS
CONNECTIONS AND PRESSURE TESTING:
•
HIGH ALTITUDE GAS ORIFICE CHART
Altitude
(Ft)
0 - 6000
6001 - 11000
Gas
Kit
Orifice
Natural
Propane
Natural
Propane
None
LPTK09
HANG07
HALP09
#43
#55
#45
#56
Manifold
Pressure
3.5" W.C
10.0" W.C.
3.5" W.C
10.0" W.C.
THE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE
PLACING IN OPERATION. BECAUSE OF THE DANGER OF EXPLOSION OR
FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER
EXCEED SPECIFIED PRESSURES FOR TESTING. HIGHER PRESSURE MAY
DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN
PREMATURE HEAT EXCHANGE FAILURE.
•
THIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM
THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT
•
NOTE: In Canada, gas furanceare are certified to 4500 feet only.
TEST PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA).
THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY
CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE
TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES
Manual
Shut-Off
Valve
EQUAL TO OR LESS THAN 1/2
PSIG (3.48 KPA).
WARNING
Gas
Valve
TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE
SURE THERE IS
NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.
There will be air in the gas supply line after testing for leaks on
a new installation. Therefore the air must be bled from the line.
Follow the steps below to bleed air from the gas line.
1. Ensure there is no open flame in the vicinity.
2. Disconnect power to the unit.
3. Loosen the ground joint union until pure gas expels.
4. Tighten joint union and wait five minutes until gas is
dispersed.
5. Close the main electrical disconnect switch for the unit.
Drip Leg
Ground Joint Union
(Installed Ahead Of Gas Valve)
Reduce coupling 1/2" x 1/8",
with 1/8" pipe plug to measure
line gas pressure.
General Layout at the Unit
Natural Gas Connection
Refer to the above figure for the general layout at the unit. The
following rules apply:
1. Use black iron or steel pipe and fittings for the supply piping.
2. Use pipe joint compound on male threads only. Pipe joint
compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter
the gas valve. The drip leg must be a minimum of three
inches long.
5. Use two pipe wrenches when making connection to the gas
valve to keep it from turning.
6. Install a manual shut-off valve in a convenient location (within
six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
8. The unit must be connected to the building piping by one of
the following methods:
• Rigid metallic pipe and fittings
• Semirigid metallic tubing and metallic fittings (Aluminum
alloy tubing must not be used in exterior locations)
• Listed gas appliance connectors used in accordance with
the terms of their listing that are completely in the same
room as the equipment
• In the prior two methods above the connector or tubing
must be protected from physical and thermal damage.
Aluminum alloy tubing and connectors must be coated to
protect against external corrosion when in contact with
masonry, plaster or insulation or are subject to repeated
wettings by liquids (water - not rain water, detergents or
sewage).
PROPANE GAS INSTALLATIONS
WARNING
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE
OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS
DETECTING WARNING DEVICE. SINCE RUST CAN REDUCE THE LEVEL
OF ODORANT IN PROPANE GAS, A GAS DETECTING WARNING DEVICE
IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK.
CONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A
GAS DETECTING WARNING DEVICE.
IMPORTANT NOTE: Propane gas conversion kits must be
installed to convert units to propane gas. See High Altitude Gas
Orifice chart for kit part number for this model.
All propane gas equipment must conform to the safety standards
of the National Board of Fire Underwriters (See NBFU Manual
58).
For satisfactory operation, propane gas supply pressure must
be 10 inch w.c. at the unit manifold with all gas appliances in
operation. Maintaining proper gas pressure depends on three
main factors:
1. Vaporization rate, which depends on (a) temperature of the
liquid, and (b) wetted surface area of the container or
containers.
2. Proper pressure regulation.
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size required
6
will depend on length of pipe run and total load of all
appliances.
standard commercial compounds, special pipe dope must be
used. Shellac based compounds resistant to the actions of
liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s®
or John Crane® are satisfactory. The figure below shows a typical
propane gas installation.
TANKS AND PIPING
WARNING
5 to 15 PSIG
(20 PSIG Max.)
First Stage
Regulator
TO PREVENT PROPERTY DAMAGE OR SERIOUS PERSONAL INJURY DUE TO
Continuous
11" W.C.
FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS
DETECTING WARNING DEVICE.
IF THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A
200 PSIG
Maximum
CONFINED SPACE, A WARNING DEVICE IS REQUIRED DUE TO:
•
PROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN
•
PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE
Second Stage
Regulator
SETTLE IN ANY LOW AREAS OR CONFINED SPACES.
EXCEPT WITH A WARNING DEVICE.
If the presence of gas is suspected, follow the warnings on Page
2 of this manual.
Typical Propane Gas Installation
ELECTRICAL CONNECTIONS
PROPANE GAS PIPE SIZING
THERMOSTAT
Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10
PSIG Setting. Capacities in 1,000 BTU/HR
PIPE OR
TUBING
LENGTH,
FEET
Movement of air must not be obstructed by furniture, door,
draperies, etc. The thermostat must be located a minimum of
five feet above the floor on a vibration-free inside wall with good
air circulation. The thermostat must not be mounted where it
will be affected by drafts, hot or cold water pipes or air ducts in
walls, radiant heat from fireplace, lamps, the sun, television,
etc. Consult the Instruction Sheet packaged with thermostat for
mounting instructions. Adjust the heat anticipator in the room
thermostat to obtain the proper number of heating cycles per
hour and to prevent the room temperature from overshooting
the room thermostat setting. Heat anticipator must be set at 0.4
amps.
All units have one stage of heating and one stage of mechanical
cooling. NOTE: Units with economizers can use thermostats
with one or two stages of cooling.
NOMINAL PIPE SIZE,
SCHEDULE 40
TUBING SIZE, O.D., TYPE L
30
3/8"
309
1/2"
700
5/8"
1,303
3/4"
2,205
7/8"
3,394
1/2"
1,843
3/4"
3,854
40
265
599
1,115
1,887
2,904
1,577
3,298
50
235
531
988
1,672
2,574
1,398
2,923
60
213
481
896
1,515
2,332
1,267
2,649
70
196
446
824
1,394
2,146
1,165
2,437
80
182
412
767
1,297
1,996
1,084
2,267
90
171
386
719
1,217
1,873
1,017
2,127
100
161
365
679
1,149
1,769
961
2,009
150
130
293
546
923
1,421
772
1,613
200
111
251
467
790
1,216
660
1,381
250
90
222
414
700
1,078
585
1,224
300
89
201
378
634
976
530
1,109
350
82
185
345
584
898
488
1,020
400
76
172
321
543
836
454
949
WARNING
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130
To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at
11" W.C. Setting. Capacities in 1,000 BTU/HR
PIPE OR
TUBING
LENGTH,
FEET
TO AVOID INJURY, ELECTRICAL SHOCK OR DEATH, DISCONNECT ELECTRICAL
POWER BEFORE SERVICING OR CHANGING ANY ELECTRICAL WIRING.
NOMINAL PIPE SIZE,
SCHEDULE 40
TUBING SIZE, O.D., TYPE L
3/8"
1/2"
5/8"
3/4"
7/8"
1/2"
3/4"
1"
1-1/4"
10
49
110
206
348
539
291
608
1,146
2,353
3,525
20
34
76
141
239
368
200
418
788
1,617
2,423
30
27
61
114
192
296
161
336
632
1,299
1,946
40
23
52
97
164
253
137
284
541
1,111
1,665
50
20
46
86
146
224
122
255
480
985
1,476
60
19
42
78
132
203
110
231
436
892
1,337
80
16
36
67
113
174
94
198
372
764
1,144
100
14
32
59
100
154
84
175
330
677
1,014
125
12
28
52
89
137
74
155
292
600
899
150
11
26
48
80
124
67
141
265
544
815
200
10
22
41
69
106
58
120
227
465
697
250
9
19
36
61
94
51
107
201
412
618
WIRING
1-1/2"
All internal wiring in the unit is complete. This unit is designed
for 60 hertz current operation at the voltages shown on the rating
plate. Bring in the contactor power supply per the supplied unit
wiring diagram. Connect the unit control panel to the room
thermostat using 24 volt wiring.
1
4
7
10
2
5
8
11
3
6
9
12
D1
L1
L1
L2
300
8
18
33
55
85
46
97
182
374
560
350
7
16
30
51
78
43
89
167
344
515
400
7
15
28
47
73
40
83
156
320
479
L2
L2
L2
UNUSED
HEAT
COOL
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54
Complete information regarding tank sizing for vaporization,
recommended regulator settings and pipe sizing is available
from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead or most
Low Voltage Terminal Board
Optional Low Voltage Terminal Board Location
7
and review the blower performance charts in the Product Data
Book applicable to your model*. In some installations it will be
necessary to change the blower speed to provide proper air
flow.
If converting to down discharge airflow, be sure to refer to the
unit rating plate for approved duct orientation and proceed as
follows:
G
Y
R
W
R
W
Y
G
From
Unit
•
Cut insulation around bottom openings and remove panels
from the bottom of the unit, saving the screws holding the
panels in place.
•
Install horizontal duct cover kit.
DUCTWORK
Duct systems and register sizes must be properly designed for
the C.F.M. and external static pressure rating of the unit.
Ductwork should be designed in accordance with the
recommended methods of Air Conditioning Contractors of
Proper Thermostat Wiring
Refer to the unit wiring diagram for electrical connections. When
installed, the unit must be electrically grounded in accordance
with local codes or in the absence of local codes, with the
National Electrical Code, ANSI/NFPA No. 70, and/or the CSA
C22.1 Electrical Code, if an external source is utilized.
WARNING
TO AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE
POLARIZED AND GROUNDED.
CAUTION
TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE
ONLY COPPER CONDUCTORS.
CAUTION
TO PREVENT IMPROPER
AND DANGEROUS OPERATION DUE TO WIRING ERRORS,
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.
VERIFY PROPER OPERATION AFTER SERVICING.
The best protection for the wiring is the lowest rated fuse or
circuit breaker which will supply power to the unit during normal
operation without nuisance trips. Such a device will provide
maximum circuit protection. DO NOT EXCEED THE MAXIMUM
OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA
PLATE.
All line voltage connections must be made through weatherproof
fittings. All exterior power supply and ground wiring must be in
approved weatherproof conduit. Low voltage wiring from the
unit control panel to the thermostat requires coded cable. For
ground level and rooftop wiring see figures below.
Electrical Power Directly To Junction Box
UNIT VOLTAGE
The unit transformer is factory connected for 230V operation. If
the unit is to operate on 208V, reconnect the transformer primary
lead and induced draft blower motor leads as shown on the unit
wiring diagram.
AIR CIRCULATION AND FILTERS
AIRFLOW CONVERSION
This package gas unit is shipped from the factory with the
appropriate blower setting for a normal horizontal discharge
installation. Units can easily be converted from horizontal to
vertical airflow delivery. In down-discharge or high static
installations, the installer should measure the total external static
Electrical Power Routed Through Bottom of Unit
8
If using the Over/Under Transition Kit, the filter(s) may be located
in the return air duct(s) or return air filter grille(s). Filters installed
external to the unit should be sized in accordance with their
manufacturer recommendations. A throwaway filter must be
sized for a maximum face velocity of 300 feet per minute.
America Manual D (Residential) or Manual Q (Commercial). All
ductwork exposed to the outdoors must include a weatherproof
barrier and adequate insulation.
A duct system should be installed in accordance with Standards
of the National Board of Fire Underwriters for the Installation of
Air Conditioning, Warm Air Heating and Ventilating Systems.
Pamphlets No. 90A and 90B.
The warm air supply duct from the unit through a wall fabricated
of combustible material may be installed without clearance.
However, minimum clearances for the unit must be observed
as shown in the Minimum Clearances for Unit figure on page 4.
The outlet duct should be provided with an access panel. This
access should be large enough to inspect the air chamber
downstream from the heat exchanger for any smoke or
combustion gas leaks. A cover should be tightly attached to
prevent air leaks.
For horizontal airflow, duct flange dimensions on the unit are
shown in the Product Data Book applicable to your model*.
For vertical airflow, the ductwork should be attached to the roof
curb prior to installing the unit. Ductwork dimensions are shown
in the roof curb installation manual.
If desired, supply and return duct connections to the unit may
be made with flexible connections to reduce possible unit
operating sound transmission.
FILTER INSTALLATION
Important: When installing a filter, the air flow arrows on the
filter must point toward the circulator blower.
VENTING
NOTE: Venting is self-contained. Do not modify or block.
FLUE HOOD AND AIR INLET HOOD INSTALLATION
Install the flue hood and air inlet hood prior to operation of the
unit.
To install the flue hood cover:
1. Remove the flue hood and bug screen from inside the
compressor compartment.
2. Attach the flue hood (enclosed side down) and screen with
the sheet metal screw provided.
To install the air inlet hood:
1. Remove hood from the compressor compartment.
2. Attach hood by using the supplied sheet metal screws.
FILTERS
CAUTION
Flue Hood
TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF
Screen
EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT
BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR
FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Even though a return air filter is not supplied with this unit, there
must be a means of filtering all return air.
Refer to the following table for filter size information.
Model
PGA24C***2(E/F)
PGA30C***2(E/F)
PGA36C***2(E/F)
PGA42C***2(E/F)
Disposable Permanent Rated Cooling
Filter
Filter
Airflow
2*
2**
CFM
ft
ft
3.8
1.9
800
3.8
1.9
1000
4.0
2.0
1200
4.5
2.3
1350
PGA48C***2(E/F)
PGA60C***2(E/F)
5.3
5.8
2.7
2.9
1600
1750
PGB24C***2(E/F)
PGB30C***2(E/F)
PGB36C***2(E/F)
PGC42C***2(E/F)
3.0
3.5
4.0
4.5
1.5
1.8
2.0
2.3
800
1000
1150
1350
PGB42C***2(E/F)
PGB48C***2(E/F)
PGB60C***2(E/F)
5.0
5.5
7.0
2.5
2.8
3.5
1400
1600
2000
PGD24C***2(E/F)
PGD30C***2(E/F)
PGD36C***2(E/F)
PGD42C***2(E/F)
3.0
3.5
4.0
4.5
1.5
1.8
2.0
2.3
800
1000
1150
1350
PGD48C***2(E/F)
PGD60C***2(E/F)
5.0
6.0
2.5
3.0
1500
1750
*Based on a face velocity of 300ft/min.
**Based on a face velocity of 600 ft/min.
Air Intake Hood
Hood Installation
CONDENSATE DRAIN
HIGH STATIC OR DOWN-DISCHARGE INSTALLATION
IMPORTANT: Elevated internal static pressure can cause
condensate to be drawn out of the drain pan and into the return air
plenum. For gas package units and down discharge installations
experiencing total external pressure of 0.30” w.c. or greater, add a
splash baffle. It will prevent condensate from seeping over into the
return air plenum in high static applications. The baffles are factory
installed in all large chassis gas/electric package units. Contact your
distributor for the correct splash baffle for your model.
CONDENSATE DRAIN CONNECTION
These units are equipped with a built-in trap and do not require
an external trap.
To avoid double trapping and an overflowing drain pan, soft
plastic drain lines are not recommended.
9
NORMAL SEQUENCES OF OPERATION
HEATING
This unit is equipped with an ignition control that automatically
lights the main burner. DO NOT attempt to light the main burners
by any other method.
1. Thermostat calls for heat. The induced draft blower energizes
for a 15-second pre-purge.
2. The spark igniter and gas valve energizes for seven seconds.
NOTE: The igniter produces a very intense electrical spark
that ignites the gas.
3. The 30-second HEAT FAN ON delay time begins.
4. The unit delivers heat to the conditioned space until the
thermostat is satisfied.
5. The gas valve deenergizes. The induced draft blower
continues operation for a 29-second post-purge.
6. Ignition control begins timing the HEAT FAN OFF delay. This
allows any additional heat in the heat exchanger to be
transferred to the conditioned space. After the HEAT FAN
OFF delay time has elapsed, the blower will deenergize.
Models with a PSC (Permanent Split Capacitor) circulator blower
motor have an adjustable HEAT FAN OFF delay of 90/120/ 150/
seconds OR 60/90/120/180 seconds. Models with variable
speed motor (ECM) have a fixed HEAT FAN OFF delay of 120
seconds.
HEATING STARTUP
Heat Anticipator Setting
Set the heat anticipator on the room thermostat to 0.4 amps to
obtain the proper number of heating cycles per hour and to
prevent the room temperature from overshooting the room
thermostat setting.
Rollout Protection Control
The rollout protection device opens, cutting power to the gas
valve, if the flames from the burners are not properly drawn into
the heat exchanger. The rollout protection device is located on
the burner bracket (see figure below). The reason for elevated
temperatures at the control should be determined and repaired
prior to resetting this manual reset control.
Rollout Protection
Rollout Protection Device
COOLING
1. Thermostat calls for cooling. The compressor and outdoor
fan are energized.
2. Approximately seven seconds later, the indoor fan starts.
NOTE: Models with a variable speed motor (ECM) do not
have a seven-second COOL FAN ON delay. The motor
“ramps” up to full speed over a 30-second period.
3. The unit will deliver cooling to the conditioned space until
the thermostat is satisfied.
4. The compressor and outdoor fan will be deenergized when
the thermostat opens.
5. The indoor fan continues to run for approximately 30 seconds
after the thermostat is satisfied. This allows additional cooling
from the indoor coil to be transferred to the conditioned
space. Then, the indoor fan stops.
WARNING
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE
OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR
THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING
THE ROLLOUT PROTECTION DEVICE.
Secondary Limit Control
A second limit control is placed on the blower scroll. This control
will open due to elevated temperature caused by the blower
failing. The reason for elevated temperatures at the control
should be determined and repaired prior to resetting. The
secondary limit control is located on the top of the blower scroll
assembly (see figure below).
If the power to the unit is interrupted during the heating cycle, it
may cause the secondary limit to trip. Once the blower
compartment temperature drops below the limit reset
temperature, the limit will automatically reset.
FAN ONLY
1. Thermostat calls for FAN ONLY by energizing “G”.
2. Approximately seven seconds later, the indoor fan starts.
NOTE: Not all models will have a “7-Second ON” indoor
fan start delay or an “OFF” delay in continuous fan mode.
3. The indoor fan continues to run for approximately 30 seconds
after “G” is deenergized.
Secondary
Limit Control
Condenser Coil
STARTUP, ADJUSTMENTS, AND CHECKS
Duct
Opening
This unit is equipped with an electronic ignition device to
automatically light the main burners. It also has a power vent
blower to exhaust combustion products.
On new installations, or if a major component has been replaced,
the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If
any sparking, odors, or unusual sounds are encountered, shut
off electrical power and recheck for wiring errors, or obstructions
in or near the blower motors. Duct covers must be removed
before operating unit.
Blower
Assembly
Blower
Compartment
Access Door
Top View
Secondary LImit Control
10
Heating Timing Chart
On
Circulator
Blower
Off
On
Gas Valve
Off
Igniter
On
Off
Induced
Draft
Blower
On
Off
On
Thermostat
Off
Seconds
0
15
22
52
0
29
90, 120, or 60, 90,
150
120,180
Cooling Timing Chart
Circulator
Blower
ON
OFF
Outdoor Fan
and
Compressor
Thermostat
ON
OFF
ON
OFF
Seconds
0
7
0
11
30
Pre-Operation Checks
Gas Valve
On/Off
Selector
Switch
INLET
Gas
Valve
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
OUTLET
Inlet Pressure Tap
(Side of Valve) Pressure Regulator
Adjustment
(Under Cap Screw)
White-Rodgers Model 36F22
Proper Gas Valve Mounting Location
Close the manual gas valve external to the unit.
Turn off the electrical power supply to the unit.
Set the room thermostat to its lowest possible setting.
Remove the heat exchanger door on the side of the unit by
removing screws.
This unit is equipped with an ignition device which
automatically lights the main burner. DO NOT try to light
burner by any other method.
Move or rotate (depending on your gas valve) the gas control
valve switch to the OFF position. Do not force.
Wait five minutes to clear out any gas.
Smell for gas, including near the ground. This is important
because some types of gas are heavier than air. If you have
waited five minutes and you do smell gas, immediately follow
the warnings on page 2 of this manual. If having waited for
five minutes and no gas smell is noted, move or rotate the
gas control valve switch to the ON position.
Replace the heat exchanger door on the side of the unit.
Open the manual gas valve external to the unit.
Turn on the electrical power supply to the unit.
Set the thermostat to desired setting.
Gas Inlet Pressure Check
INLET
OUTLET
Inlet Pressure
Tap
Gas Valve
On/Off
Selector
Switch
White-Rodgers 36G22
Pressure Regulator
Adjustment
(Under Cap Screw)
O
F
F
INLET
M
1
P
3
C
2
ON
Outlet (Manifold)
Pressure Tap
Honeywell
INLET
OUTLET
ON
OFF
Inlet Pressure Tap
Gas Valve
On/Off
Control Knob
Honeywell Model VR8205
With Power And Gas Off:
Connect a water manometer or adequate gauge to the inlet
pressure tap of the gas valve.
Inlet gas pressure can also be measured by removing the cap
from the dripleg and installing a predrilled cap with a hose fitting.
Gas inlet pressure must be checked and adjusted in accordance
to the type of fuel being consumed.
Gas Valve
On/Off
Selector
Switch
Pressure Regulator
Adjustment
(Under Cap Screw)
Outlet Pressure
Tap
Gas Supply And Manifold Check
Gas supply pressure and manifold pressure with the burners
operating must be as specified on the rating plate.
Outlet (Manifold)
Pressure Tap
Gas Line
Gas
Shutoff
Valve
OUTLET
Gas Line
To Furnace
Inlet Pressure Tap
(Side of Valve)
Pressure Regulator
Adjustment
(Under Cap Screw)
Outlet (Manifold)
Pressure Tap
(Side of Valve)
Open To
Atmosphere
White-Rodgers Model 36E22
Drip Leg Cap
With Fitting
Manometer Hose
Manometer
Gauge Attachment to Inlet Pressure Tap
12
4. Relight all other appliances turned off in step 1. Be sure all
pilot burners are operating.
With Power And Gas On:
Put unit into heating cycle and turn on all other gas consuming
appliances.
Main Burner Flame Check
Flames should be stable, soft and blue (dust may cause orange
tips but they must not be yellow) and extending directly outward
from the burner without curling, floating or lifting off.
Inlet Gas Pressure
Natural
Propane
Min. 5.0" W.C., Max. 10.0" W.C.
Min. 11.0" W.C., Max. 13.0" W.C.
NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value
Shown.
Temperature Rise Check
Check the temperature rise through the unit by placing
thermometers in supply and return air registers as close to the
unit as possible. Thermometers must not be able to sample
temperature directly from the unit heat exchangers, or false
readings could be obtained.
1. All registers must be open; all duct dampers must be in their
final (fully or partially open) position and the unit operated
for 15 minutes before taking readings.
2. The temperature rise must be within the range specified on
the rating plate.
NOTE: Air temperature rise is the temperature difference
between supply and return air.
With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit is
operated at rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may
be necessary to change the blower speed. A higher blower
speed will lower the temperature rise. A slower blower speed
will increase the temperature rise.
NOTE: Blower speed MUST be set to give the correct air
temperature rise through the unit as marked on the rating plate.
If operating pressures differ from above, make necessary
pressure regulator adjustments, check piping size, etc., and/or
consult with local utility.
Manifold Pressure Check
A ”U” Tube manometer having a scale range from 0 to 12 inches
of water should be used for this measurement. The manifold
pressure must be measured with the burners operating.
Honeywell Model VR8205, White-Rodgers Models 36E22/
36F22:
A tapped opening is provided in the gas valve to facilitate
measurement of the manifold pressure.
White Rodgers Model 36G22:
Using a 3/32 inch hex wrench, loosen the outlet pressure tap
screw 1 turn only (DO NOT REMOVE). Attach a length of 5/16
inch hose to the outlet pressure tap boss. Connect the 5/16
inch hose to a water manometer or other adequate gauge.
To adjust the pressure regulator, remove the adjustment screw
or cover on the gas valve. Turn out (counterclockwise) to
decrease pressure, turn in (clockwise) to increase pressure.
Only small variations in gas flow should be made by means of
the pressure regulator adjustment. In no case should the final
manifold pressure vary more than plus or minus 0.3 inches water
column from the specified nominal pressure. Any major changes
in flow should be made by changing the size of the burner
orifices. The measured input rate to the furnace must not exceed
the rating specified on the unit rating plate.
For natural gas, the manifold pressure must be between 3.2
and 3.8 inches water column (3.5 nominal).
For propane gas, the manifold pressure must be between 9.7
and 10.3 inches water column (10.0 nominal).
External Static Pressure Check
The total external static pressure must be checked on this unit
to determine if the airflow is proper.
Limit Check
Check limit control operation after 15 minutes of operation by
blocking the return air grille(s).
1. After several minutes the main burners must go OFF. Blower
will continue to run.
2. Remove air restrictions and main burners will relight after a
cool down period of a few minutes.
Adjust the thermostat setting below room temperature.
1. Main burners must go OFF.
2. Circulating Air Blower will continue to run for selected HEAT
FAN OFF delay.
Gas Input (Natural Gas Only) Check
NOTE: On outdoor equipment, the gas input will vary with the
temperature of the gas. Rated input will be obtained at
approximately 10° F. With warmer ambient and gas
temperatures, the input will decrease. Example: At 70° F the
input will decrease 12%.
To measure the gas input using the gas meter proceed as
follows:
1. Turn off gas supply to all other appliances except the unit.
2. With the unit operating, time the smallest dial on the meter
for one complete revolution. If this is a 2 cubic foot dial,
divide the seconds by 2; if it is a 1 cubic foot dial, use the
seconds as is. This gives the seconds per cubic foot of gas
being delivered to the unit.
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT
Example: Natural gas with a heating value of 1000 BTU per
cubic foot and 34 seconds per cubic foot as determined by
Step 2, then:
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE:
BTU content of the gas should be obtained from the gas
supplier. This measured input must not be greater than
shown on the unit rating plate.
Blower Speed Adjustment
WARNING
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE
ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE
BLOWER MOTOR.
Refer to the wiring diagram on the unit to verify speed tap
settings.
Blower speeds can be adjusted on the ignition control board.
Both heat speed and cool speed terminals are supplied on
the board along with two unused motor lead terminals.
13
1
10
LED. If diagnostic LED indicates a hard lockout, check power
supply to unit for proper voltage, check all fuses, circuit breakers
and wiring. Disconnect electric power for five seconds. If LED
remains off after restoring power, replace control.
11
8
5
2
11
R31
2
9
6
12
3
12
3
9
6
K1
C27
D7
FS
External Lockout
D5
R25
An external lockout occurs if the integrated ignition control
determines that a measurable combustion cannot be established
within three (3) consecutive ignition attempts. If flame is not
established within the seven (7) second trial for ignition, the
gas valve is deenergized, 15 second inter-purge cycle is
completed, and ignition is re-attempted. The control will repeat
this routine three times if a measurable combustion is not
established. The control will then shut off the induced draft
blower and go into a lockout state.
If flame is established but lost, the control will energize the
circulator blower at the heat speed and then begin a new ignition
sequence. If flame is established then lost on subsequent
attempts, the control will recycle for four (4) consecutive ignition
attempts (five attempts total) before locking out.
The diagnostic fault code is 1 flash for a lockout due to failed
ignition attempts or flame dropouts. The integrated control will
automatically reset after one hour, or it can be reset by removing
the thermostat signal or disconnecting the electrical power
supply for five seconds.
Important: If you have to frequently reset your gas/electric
package unit, it means that a problem exists that should be
corrected. Contact a qualified servicer for further information.
R10
R38
D3
C13
R8
K2
R22
D1
D9
R29
Z1
D10
L1
R34
R3
R35
L1
L2
UNUSED
C20
L2
K3
D14
HEAT
R4
L2
K4
R11
R42 D12
COOL
L2
D11
R36
LED
1068-83-400A
Control Board
NOTE: If necessary, adjust HEAT FAN OFF delay settings to obtain
satisfactory comfort level.
COOLING STARTUP
NOTE: Check all manual reset limit controls in heating circuit if cooling
mode does not operate.
Pressure Switch Stuck Open
Compressor Protection Devices
A pressure switch stuck open can be caused by a faulty pressure
switch, faulty wiring, a disconnected or damaged hose, a blocked
or restricted flue, or a faulty induced draft blower.
If the control senses an open pressure switch during the prepurge cycle, the induced draft blower only will be energized. If
the pressure switch opens after ignition has begun the gas valve
is deenergized, the circulator blower heat off cycle begins, and
the induced draft blower remains on. The diagnostic fault code
is two flashes.
The compressor includes components which are designed to
protect the compressor against abnormal operating conditions.
WARNING
TO PREVENT PERSONAL INJURY OR DEATH, ALWAYS DISCONNECT ELECTRICAL
POWER BEFORE INSPECTING OR SERVICING THE UNIT. ALL COMPRESSOR
PROTECTION DEVICES RESET AUTOMATICALLY, ENERGIZING THE CONTACTOR
Pressure Switch Stuck Closed
A stuck closed pressure switch can be caused by a faulty
pressure switch or faulty wiring. If the control encounters a
pressure switch stuck closed, the induced draft blower remains
off. The diagnostic LED code for this fault is three (3) flashes.
AND OUTDOOR FAN.
Operating Instructions (Cooling)
NOTE: Mechanical cooling cannot be reliably provided at
ambient temperatures below 50° F.
1. Turn on the electrical power supply to the unit.
2. Place the room thermostat selector switch in the COOL
position (or AUTO if available, and if automatic changeover
from cooling to heating is desired).
3. Set the room thermostat to the desired temperature.
Open Thermal Protection Device
If a primary, auxiliary, or rollout limit switch opens, the gas valve
is immediately deenergized, the induced draft and air circulating
blowers are energized. The induced draft and air circulator
blowers remain energized until the limit switch recloses. The
diagnostic fault code for an open limit is four (4) flashes.
A primary limit will open due to excessive supply air
temperatures. This can be caused by a dirty filter, excessive
duct static, insufficient air flow, or a faulty limit. Check filters,
total external duct static, blower motor, blower motor speed tap
(see wiring diagram), and limit. This limit will automatically reset
once the temperature falls below a preset level.
An automatic reset auxiliary limit is located on the circulator
blower scroll. A dirty filter, excessive duct static, insufficient air
flow, a faulty limit, or a failed circulator blower can cause this
limit to open. Check filters, total external duct static, circulator
blower motor, blower motor speed tap (see wiring diagram),
and limit. An interruption in electrical power during a heating
cycle may also cause the auxiliary limit to open. The secondary
limit is located on top of the circulator blower assembly (see
TROUBLESHOOTING
ABNORMAL OPERATION - HEATING
The following presents probable causes of questionable unit
operation. Remove the control box access panel and note the
number of diagnostic LED flashes. Refer to Diagnostic Indicator
Chart for an interpretation of the signal and to this section for
an explanation.
Internal Lockout
If the integrated ignition control in this unit encounters an internal
fault, it will go into a “hard” lockout and turn off the diagnostic
14
Secondary Limit Control figure).
If the burner flames are not properly drawn into the heat
exchanger, the flame rollout protection device will open. The
rollout limit is a manual reset limit located on the burner bracket.
The cause of the flame rollout must be determined and corrected
before resetting the limit. Possible causes are restricted or
blocked flue passages, blocked or cracked heat exchanger, a
failed induced draft blower, or insufficient combustion air.
Important: If a limit opens five (5) times within a single
call for heat, the ignition control will go into a 30-minute lockout.
Only the air circulator blower remains on during this lockout.
The diagnostic fault code for this condition is “8” flashes and
the control automatically resets after 30 minutes. A dirty filter is
the most likely cause for the fault.
operation, the ignition control will delay output to the compressor
contactor for three minutes from the time power is restored.
(Compressor is off a total of three minutes). The diagnostic
LED will flash six (6) times to indicate the compressor contactor
output is being delayed.
NOTE: Some electronic thermostats also have a built-in compressor
short cycle timer that may be longer than the three minute delay
given above. If you are using an electronic thermostat and the
compressor has not started after three minutes, wait an additional
five minutes to allow the thermostat to complete its short cycle delay
time.
MAINTENANCE
Flame Detected with Gas Valve Closed
Have the gas heating section of the unit checked at least once
a year before the heating season begins, to be sure that the
combustion air inlet and flue outlet hoods are not blocked by
debris, which would prevent adequate combustion air and a
properly operating vent system.
If flame is sensed with the gas valve deenergized, the
combustion and air circulator blowers are energized. The
diagnostic fault code is five (5) flashes for this condition. The
control can be reset by removing the power supply to the unit or
it will automatically reset after one hour. Miswiring is the probable
cause for this fault.
WARNING
Low Flame Sensor Current
If the flame sense current drops below approximately one
microamp DC, the diagnostic LED will flash seven (7) times.
The control will function normally until it can no longer sense
flame. If this fault code is encountered, have a qualified service
technician remove the sensor and clean it with steel wool.
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK,
DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY MAINTENANCE.
REPLACING OR CLEANING FILTER
A return air filter is not supplied with this unit; however, there
must be a means of filtering all of the return air. The filter(s)
may be located in the return air duct(s), or return air filter grille(s).
Consult with your installing dealer for the actual location of the
return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating
or cooling performance. Filter inspection should be made at
least every two months; more often if necessary because of
local conditions and usage.
Dirty throwaway filters should be discarded and replaced with a
new, clean filter. Dirty permanent filters should be washed with
water, thoroughly dried and sprayed with a filter adhesive before
being reinstalled. (Filter adhesives may be found at many
hardware stores.) Permanent filters should last several years.
However, should one become torn or uncleanable, it should be
replaced.
Gas Valve Energized When It Should Be OFF
Some models utilize an ignition control that recognizes voltage
present at the gas valve when the gas valve should be off. If
the ignition control senses this fault, it will lockout all functions
except continuous fan. This fault is indicated by (9) flashes.
Possible causes are miswiring, shorts in the wire harness, or
corrosion at the burners. Check and correct wiring if required.
Inspect and clean burners if required. Power to the unit must
be removed in order to reset the control from lockout.
ABNORMAL OPERATION - COOLING
Short Cycle Compressor Delay
The automatic ignition control has a built-in feature that prevents
damage to the compressor in short cycling situations. In the
event of intermittent power losses or intermittent thermostat
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART
Light Signal
Off
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
Refer to Abnormal Heating or Cooling Operation Sections of this Manual
Internal Lockout
External Lockout
Pressure Switch Stuck Open
Pressure Switch Stuck Closed
Open Thermal Protection Device
Flame Sensed with Gas Valve Closed
Short Cycle Compressor Delay (Cooling)
Low Flame Sense Current
Thermal Protection Device Open
Gas Valve Energized When It Should Be OFF (DSI-1 Control Only)
15
MAINTAINING CABINET FINISH
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)
Use a fine grade automotive wax on the cabinet finish to maintain
the finish’s original high luster. This is especially important in
installations with extended periods of direct sunlight.
Flames should be stable, soft and blue (dust may cause orange
tips but must not be yellow). The flames must extend directly
outward from the burner without curling, floating or lifting off.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The coil with the outside air flowing over it should be inspected
annually and cleaned as frequently as necessary to keep the
finned areas free of lint, hair and debris.
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS
Bearings on the air circulating blower motor, condenser motor
and the combustion fan motor are permanently lubricated. No
additional oiling is required.
Check the burner flames for:
1. Good adjustment
2. Stable, soft and blue
3. Not curling, floating, or lifting off.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
A drop in the flame sensing signal can be caused by a nearly
invisible coating on the flame sensor. This coating, created by
the fuel or combustion air supply, can be removed by carefully
cleaning the flame sensor with steel wool.
NOTE: After cleaning, the microamp signal should be stable
and in the range of 4 - 6 microamps DC.
Burner Flame
WARNING
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK,
DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY
Flame
Sensor
ADJUSTMENT.
CONTACT A QUALIFIED SERVICER AT ONCE IF AN ABNORMAL
FLAME SHOULD DEVELOP.
At least once a year, prior to or during the heating season, make
a visual check of the burner flames.
NOTE: This will involve removing and reinstalling the heat
exchanger door on the unit, which is held by two screws. If you
are uncertain about your ability to do this, contact a qualified
servicer.
If a strong wind is blowing, it may alter the airflow pattern within
the unit enough that an inspection of the burner flames is not
possible.
Flame Sensor Location
FLUE PASSAGES (QUALIFIED SERVICER ONLY)
At the start of each heating season, inspect and, if necessary,
clean the unit flue passage.
CLEANING BURNERS
1. Shut off electric power and gas supply to the unit.
2. Remove the screws holding the burner retention bracket in
place.
NOTE: On some models it will be necessary to remove the
manifold instead of a burner retention bracket. In such a
case, remove the manifold and rotate each burner
counterclockwise to remove.
Cleaning Flue Passages (Qualified Servicer Only)
1. Shut off electric power and gas supply to the unit.
2. Remove burner assembly by disconnecting the gas line and
removing the manifold bracket from the partition panel.
3. Remove the flue from the induced draft blower and the
collector box from the partition panel.
4. The primary heat exchanger tubes can be cleaned using a
round wire brush attached to a length of high grade stainless
steel cable, such as drain cleanout cable. Attach a variable
speed reversible drill to the other end of the spring cable.
Slowly rotate the cable with the drill and insert it into one of
the primary heat exchanger tubes. While reversing the drill,
work the cable in and out several times to obtain sufficient
cleaning. Use a large cable for the large tube, and then repeat
the operation with a small cable for the smaller tube. Repeat
for each tube.
5. When all heat exchanger tubes have been cleaned, replace
the parts in the reverse order in which they were removed.
6. To reduce the chances of repeated fouling of the heat
exchanger, perform the steps listed in “Startup, Adjustments,
and Checks”.
Burner
Manifold
Burner Bracket and Manifold
16
Burner Bracket
3. Remove the burners.
4. Use a bottle brush to clean burner insert and inside of the
burners.
5. Replace burners and burner retention bracket or manifold,
inspect the burner assembly for proper seating of burners in
retention slots.
6. Reconnect electrical power and gas supply.
ACCESSORIES AND FUNCTIONAL PARTS
SHEET METAL ACCESSORIES
Additional accessories, as described below can be purchased
to fit specific application needs. Parts and instructions are
available from your distributor.
CAUTION
Accessory
Over/Under Duct Cover Kit
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.
WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
Horizontal Duct Covers*
Compressor Sound Blanket
Propane Gas Conversion Kit
CAUTION
High Altitude Kit
Roof Curbs
ALWAYS VERIFY PROPER OPERATION AFTER SERVICING.
For further information on the yearly inspection, consult the User
Manual. It is recommended that a qualified servicer inspect and
service the unit at least once each year.
Turn the unit on at the thermostat. Wait a few minutes, since
any dislodged dust will alter the normal flame appearance.
Flames should be predominantly blue and directed into the
tubes. They should not be yellow. They should extend directly
outward from the burner ports without curling downward, floating
or lifting off the ports.
FUNCTIONAL PARTS
Functional Parts
Auxiliary Limit Switch
Blower Housing
Circulator Blower Motor
Blower Wheel
Burner
Capacitor
Compressor
Condenser Coil
Condenser Fan Blade
Condenser Fan Motor
Contactor
Manifold
Evaporator Coil
Flame Roll-Out Switch
Flame Sensor
Gas Orifice
Gas Valve
Heat Exchanger
High Limit Switch
Ignitor
Ignition Control
Inducted Draft Motor
Pressure Switch
Pressure Switch Hose
Transformer
Although only functional parts are shown, all sheet metal parts,
doors, etc. may be ordered by description. Parts are available
from your distributor. Be sure to provide the unit model,
manufacturing, and serial numbers with the order.
17
18
1
9 7 2
CAP
CC
W
CC
R
1
G
2X
4F
M
VR
OD
C
N
1
COMP
C
NC
T2
N0
L2
PS
C
6
DSI
8
T
1
F
S
3
L
I
M
I
T
A
U
X
L
I
M
I
T
C
M
RL
FS
GV
5
N
4 4
BU-23
BK-26
BK-26
MED HI
HI
HI
4
4
2
PGA36C0702F
PGA36C0902F
PGA42C0902F
BU-23
MED HI
4
PGA30C0702F
BU-23
MED HI
MOTOR TO "HEAT"
4
SPEED
* HEATING BLOWER SPEED
PGA24C0702F
MOTOR
SPEEDS
6
COO L
HEA T
L2
WH
WH
FACTORY WIRED MOTOR CONNECTIONS
WARNING:DISCONNECT POWER BEFORE SERVICING.
S
R
C
O
M
N
2
COMB
BLOWER
2 2
0 3
8 0
D
I
L2
L2
L1
120
60
90
L1
D1
FS
VT-47
COMBUSTION
BLOWER
(CB)
12
9
6
3
2
11
8
5
10
BU-23
BK-26
HI
BU-23
RD-24
YL-27
MOTOR TO "COOL"
MED HI
MED HI
MED LOW
LOW
SPEED
7
4
1
208
5.
7.
6.
BU-36
GY
25
RD
1
6
GY-25
1
OR
YL
4 SPEED
BLOWER
G
C
GN
WH
R
Y
W
NO
COM
6
AMANA SPECIFIED REPLACEMENT PARTS MUST BE
USED WHEN SERVICING.
IFANYORIGINALWIREISREPLACED, 105° CWIREMUST
BEUSED.USECOPPERCONDUCTORSONLY.
EQUIPPED FOR 230 VOLT OR 208 VOLT.
HEAT ON/OFF FAN DELAY FACTORY SETTINGS: 30
SECONDS ON AND 120 SECONDS OFF.
UNUSED BLOWERMOTORLEADS MUSTBEPLACEDON
UNUSED MOTOR TERMINALSOFCONTROLOR TAPED.
IFHEATINGANDCOOLINGBLOWERSPEEDSARENOTTHE
SAMEDISCARDJUMPERBEFORECONNECTINGBLOWERLEADS.
COOLING/FAN ONLY ON/OFF FAN DELAY SETTING:
7 SECONDS ON AND 30 SECONDS OFF.
READ BEFORE OPERATING OR SERVICING THIS
UNIT WARNING: DISCONNECT POWER BEFORE
SERVICING.
2
1
AIR
CIRCULATION
BLOWER
(ACB)
FLAME
SENSOR
AUX LIMIT
CONTROL
OR-19
CAPACITOR
(CAP)
3
4
5
GAS VALVE
(GV)
GY-25
VT-34
BR
RD
13
L1
S
R
C
YL-12
PTCR
(WHEN
REQUIRED)
COMPRESSOR
1Ø WIRING
120
GND
L1
L2
60
VT
BR
90
BK
RD
10
FAN
VT
20
HERM
COM
GN GREEN
HI VOLTAGE FIELD
HI VOLTAGE
LOW VOLTAGE FIELD
LOW VOLTAGE
RD RED
BU BLUE
GY GRAY
VT VIOLET
BK BLACK
BR BROWN
WH WHITE
VT
16
YL YELLOW
OR ORANGE
COLOR CODE
20351601 REV. 2
RD
15
C
A
P
A
C
I
T
O
R
O.D.
FAN
MOTOR
WARNING:DISCONNECT POWER
BEFORE SERVICING.
GND
T1
T2
DETAIL 2
CUSTOM
CONTROLS, INC
180
ADJUSTABLE FAN SETTING
(FACTORY SETTING AS SHOWN)
DETAIL 1
UTEC
FIELDCONNECTION
208/230VAC1Ø
L2
VT
37
BR
8. DIAGNOSTICLIGHT: STEADYON=STANDBYMODE;
STEADYOFF=INTERNALFAULTORNOPOWER;1
FLASH=LOCKOUT; 2FLASHES=PSSTUCKOPEN;
3FLASHES=PSSTUCKCLOSED; 4FLASHES=
OPENHIGHLIMITSWITCH, AUXLIMITSWITCH,
OROPENROLLOUT; 5FLASHES=FLAME
DETECTEDWITHGASVALVECLOSED;6
FLASHES=COMPRESSORDELAYEDONSHORT
CYCLETIMER;7FLASHES=LOWFLAMESENSE
CURRENT; 8FLASHES=5LIMITTRIPS
WITHINASINGLECALLFORHEAT;
9FLASHES=GASVALVESENSEDONINERROR
(CUSTOMCONTROLS, INC. ONLY)
9. COMPRESSORSHORT CYCLEDELAY: 3MIN.
STARTUPDELAY AFTERPOWERLOSS.
10. OPTIONALTHERMOSTATTERMINAL STRIP
ISNOTPRESENTONALLMODELS.
THERMOSTAT
DIRECT SPARK
IGNITOR (DSI)
RD-29
OR-22
LIMIT
YL-27
RD-24
BU-23
BK-26
RD
YL-11
NC
VT-18
PRIMARYROLLOUT
LIMIT(RL)
OR-49
(OPTIONAL,
SEE NOTE 10)
GY-70
2
AIR
CIRCULATION
BLOWER
(ACB)
VT-14
3
4
5
AIR PRESSURE
SWITCH (PS)
BR-21
LOAD
YL-27
BK-26
2 SPEED
BLOWER
IMPORTANT:
3.
4.
2.
1.
T1
DETAIL 1
230
LINE
COM
TRANSFORMER
** COOLING BLOWER SPEED
180
DETAIL 2
UNUSE D
L2
BK
17
VT
(COM)
RD
(230)
BK
(208V)
FOR PROPER OPERATION ON 208 VOLT THE
FOLLOWING CHANGES MUST BE MADE:
MOVE BK17 WIRE FROM TRANSFORMER
230 TERMINAL TO 208 TERMINAL.
UNPLUG RED COMBUSTION BLOWER LEAD
FROM CONTROL BOARD TERMINAL (DI) AND
ATTACH BLACK BLOWER LEAD TO TERMINAL.
TAPE UNUSED RED LEAD.
M 1
ACB
C
A
P
FAN
2
208/230 VAC 1Ø
GND
THERMOSTAT
Y
C
O
M
HERM
MODELS
L1
T1
2
0
8
L
1
H
E
A
T
C 2
2
3
0
FAN
N
3
COM
PTCR
(WHEN REQ'D)
L
11 10
1
C
O
O
L
P 3
208 VOLT INSTALLATION
090
CONTROL BOARD
(TERMINAL ORDER REARRANGED)
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DISCONNECT ELECTRICAL POWER TO THIS FURNACE BEFORE
SERVICING OR PERFORMING MAINTENANCE.
WARNING
120
150
19
1
9 7 2
2
0
8
W
CC
R
1
G
2X
4F
M
VR
2
C
A
P
C
S
R
COMP
C
C
O
M
N
2
N0
NC
L2
T2
PS
COMB
BLOWER
2
3
0
D
I
C
6
DSI
8
T
1
F
S
3
RL
L
I
M
I
T
A
U
X
L
I
M
I
T
FS
GV
C
M
5
N
4 4
COOL
HEAT
L2
WH
WH
6
L2
LOW
MED
LOW
3
3
3
3
PGA48C0902F
PGA48C1152F
PGA60C0902E
PGA60C1152F
MED
SPEED
MODELS
90
D1
FS
11
10
7
12
4
8
9
HI
HI
RD-24
BU-23
BK-26
BK-26
BU-23
BU-23
MED
MED
MOTOR TO "COOL"
** COOLING BLOWER SPEED
120
L1
1
2
5
6
3
T1
DETAIL 1
LINE
208 230
COM
TRANSFORMER
SPEED
180
60
DETAIL 2
L1
BU-23
RD-24
MOTOR TO "HEAT"
* HEATING BLOWER SPEED
L2
BK
17
VT-47
COMBUSTION
BLOWER
(CB)
VT
(COM)
RD
(230)
UNUSED
L2
FACTORY WIRED MOTOR CONNECTIONS
WARNING:DISCONNECT POWER BEFORE SERVICING.
208/230 VAC 1Ø
GND
FAN
OD
N
1
ACB
THERMOSTAT
HERM
CAP
CC
L
1
Y
L
P
S
C
O
M
2
3
0
FAN
N
3
H
E
A
T
MOTOR
SPEEDS
L1
T1
COM
PTCR
(WHEN REQ'D)
L
1 11 10
C
O
O
L
GY
25
OR
BU-36
WH
GN
YL
RD
R
Y
W
G
C
NO
COM
1
FLAME
SENSOR
AUX LIMIT
CONTROL
OR-19
CAPACITOR
(CAP)
2
AIR
CIRCULATION
BLOWER
3
(ACB)
THERMOSTAT
DIRECT SPARK
IGNITOR (DSI)
GAS VALVE
(GV)
6
BR
GY-25
VT-34
BR
L1
PTCR
(WHEN
REQUIRED)
120
60
GND
L1
L2
90
BK
DETAIL 2
CUSTOM
CONTROLS, INC
180
VT
BR
VT
20
RD
15
C
A
P
A
C
I
T
O
R
LOW PRESSURE
SWITCH
(OPTIONAL)
RD
10
FAN
HERM
COM
O.D.
FAN
MOTOR
VT
16
LOW VOLTAGE
LOW VOLTAGE FIELD
HI VOLTAGE
HI VOLTAGE FIELD
COLOR CODE
YL YELLOW
BR BROWN
OR ORANGE
WH WHITE
VT VIOLET
BU BLUE
GN GREEN
GY GRAY
BK BLACK
RD RED
20351501 REV. 0
WARNING:DISCONNECT POWER
BEFORE SERVICING.
YL/BK
GND
T1
T2
ADJUSTABLE FAN SETTING
(FACTORY SETTING AS SHOWN)
DETAIL 1
UTEC
FIELD CONNECTION
208/230 VAC 1Ø
L2
VT
37
RD
13
R
C
COMPRESSOR
1Ø WIRING
S
YL-12
READ BEFORE OPERATING OR SERVICING THIS
8. DIAGNOSTIC LIGHT: STEADY ON= STANDBY MODE;
UNIT WARNING: DISCONNECT POWER BEFORE
STEADY OFF= INTERNAL FAULT OR NO POWER; 1
SERVICING.
FLASH= LOCKOUT; 2 FLASHES= PS STUCK OPEN;
1. AMANA SPECIFIED REPLACEMENT PARTS MUST BE
3 FLASHES= PS STUCK CLOSED; 4 FLASHES=
USED WHEN SERVICING
OPEN HIGH LIMIT SWITCH, AUX LIMIT SWITCH,
2. IF ANY ORIGINAL WIRE IS REPLACED,
105
°C
WIRE
MUST
°
OR OPEN ROLL OUT; 5 FLASHES= FLAME
BE USED.USE COPPER CONDUCTORS ONLY.
DETECTED WITH GAS VALVE CLOSED; 6
3. EQUIPPED FOR 230 VOLT OR 208 VOLT.
FLASHES= COMPRESSOR DELAYED ON SHORT
4. HEAT ON/OFF FAN DELAY FACTORY SETTINGS: 30
CYCLE TIMER;7 FLASHES = LOW FLAME SENSE
SECONDS ON AND 120 SECONDS OFF.
CURRENT; 8 FLASHES = 5 LIMIT TRIPS WITHIN A
5. UNUSED BLOWER MOTOR LEADS MUST BE PLACED ON
SINGLE CALL FOR HEAT.
UNUSED MOTOR TERMINALS OF CONTROL OR TAPED.
9. COMPRESSOR SHORT CYCLE DELAY: 3 MIN.
6. IF HEATING AND COOLING BLOWER SPEEDS ARE NOT THE
STARTUP DELAY AFTER POWER LOSS.
SAME DISCARD JUMPER BEFORE CONNECTING BLOWER LEADS.
10. OPTIONAL THERMOSTAT TERMINAL STRIP
7. COOLING /FAN ONLY ON/OFF FAN DELAY SETTING: 7 SECONDS ON
IS NOT PRESENT ON ALL MODELS.
AND 30 SECONDS OFF.
IMPORTANT:
(OPTIONAL,
SEE NOTE 10)
GY-70
YL-11
NC
VT-18
OR-22
LIMIT
RD-29
PRIMARY ROLLOUT
RD
LIMIT (RL)
1
OR-49
AIR PRESSURE
SWITCH (PS)
BR-21
LOAD
GY-25
VT-14
RD-24
BU-23
BK-26
5
4
M 1
208 VOLT INSTALLATION
P 3
FOR PROPER OPERATION ON 208 VOLT THE
FOLLOWING CHANGES MUST BE MADE:
MOVE BK17 WIRE FROM TRANSFORMER
230 TERMINAL TO 208 TERMINAL.
C 2
CONTROL BOARD
(TERMINAL ORDER REARRANGED)
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DISCONNECT ELECTRICAL POWER TO THIS FURNACE BEFORE
SERVICING OR PERFORMING MAINTENANCE.
WARNING
090
120
150
20
2
0
8
COM
R
G
2X
4F
M
VR
FAN
208/230 VAC 1Ø
GND
C
S
R
ACB
C
A
P
OD
2
N
1
COMP
C
C
O
M
N
2
L2
T2
N0
PS
NC
COMB
BLOWER
2 2
0 3
8 0
D
I
C
6
DSI
8
T
1
F
S
3
RL
L
I
M
I
T
A
U
X
L
I
M
I
T
FS
GV
C
M
5
N
4 4
COOL
HEAT
L2
WH
WH
6
L2
BK-26
BU-23
BK-26
BU-23
BK-26
MED HI
HI
MED HI
HI
MED HI
HI
4
4
4
4
4
4
4
2
PGB24C0902E
PGB30C0702E
PGB30C0902E
PGB36C0702E
PGB36C0902E
PGB42C0902E
HI
LOW
BK-26
BU-23
YL-27
MOTOR TO "HEAT"
PGB24C0702E
SPEED
PGB24C0452E
* HEATING BLOWER SPEED
L2
L1
D1
FS
4
12
11
10
7
1
8
2
5
6
9
3
BU-23
BU-23
MED HI
MED HI
BK-26
RD-24
MED LOW
HI
YL-27
YL-27
LOW
RD-24
YL-27
LOW
MED LOW
MOTOR TO "COOL"
T1
DETAIL 1
SPEED
LOW
COM
LINE
208 230
** COOLING BLOWER SPEED
L1
BK
17
VT-47
COMBUSTION
BLOWER
(CB)
VT
(COM)
RD
(230)
UNUSED
L2
FACTORY WIRED MOTOR CONNECTIONS
WARNING:DISCONNECT POWER BEFORE SERVICING.
HERM
CAP
CC
W
CC
1
THERMOSTAT
Y
C
O
M
L
1
GY
25
RD
1
GY-25
1
OR
GN
RD
YL
WH
R
Y
W
G
C
NO
COM
1
FLAME
SENSOR
AUX LIMIT
CONTROL
OR-19
CAPACITOR
(CAP)
2
THERMOSTAT
DIRECT SPARK
IGNITOR (DSI)
GAS VALVE
(GV)
BR
VT-34
RD
13
L1
R
C
COMPRESSOR
1Ø WIRING
S
VT
16
BR
11
GND
L1
L2
BK
27
RD
10
FAN
VT
20
HERM
COM
RD
15
C
A
P
A
C
I
T
O
R
O.D.
FAN
MOTOR
VT
16
LOW VOLTAGE
LOW VOLTAGE FIELD
HI VOLTAGE
HI VOLTAGE FIELD
COLOR CODE
BR BROWN
YL YELLOW
WH WHITE
OR ORANGE
BU BLUE
VT VIOLET
GY GRAY
GN GREEN
RD RED
BK BLACK
20261301 REV. 1
WARNING:DISCONNECT POWER
BEFORE SERVICING.
GND
T1
T2
ADJUSTABLE FAN SETTING
(FACTORY SETTING AS SHOWN)
DETAIL 1
FIELD CONNECTION
208/230 VAC 1Ø
L2
VT
37
BR
YL-12
8. DIAGNOSTIC LIGHT: STEADY ON= STANDBY MODE;
STEADY OFF= INTERNAL FAULT OR NO POWER; 1
FLASH= LOCKOUT; 2 FLASHES= PS STUCK OPEN;
3 FLASHES= PS STUCK CLOSED; 4 FLASHES=
OPEN HIGH LIMIT SWITCH, AUX LIMIT SWITCH,
OR OPEN ROLL OUT; 5 FLASHES= FLAME
DETECTED WITH GAS VALVE CLOSED; 6
FLASHES= COMPRESSOR DELAYED ON SHORT
CYCLE TIMER;7 FLASHES= LOW FLAME SENSE
CURRENT; 8 FLASHES= 5 LIMIT TRIPS
WITHIN A SINGLE CALL FOR HEAT.
9. COMPRESSOR SHORT CYCLE DELAY: 3 MIN.
STARTUP DELAY AFTER POWER LOSS.
GY-25
6
AIR
5 CIRCULATION
BLOWER
4
(ACB)
3
READ BEFORE OPERATING OR SERVICING THIS
UNIT WARNING: DISCONNECT POWER BEFORE
SERVICING.
1. AMANA SPECIFIED REPLACEMENT PARTS MUST BE
USED WHEN SERVICING.
2. IF ANY ORIGINAL WIRE IS REPLACED, 105 ºC WIRE MUST
BE USED.USE COPPER CONDUCTORS ONLY.
3. EQUIPPED FOR 230 VOLT OR 208 VOLT.
4. HEAT ON/OFF FAN DELAY FACTORY SETTINGS: 30
SECONDS ON AND 120 SECONDS OFF.
5. UNUSED BLOWER MOTOR LEADS MUST BE PLACED ON
UNUSED MOTOR TERMINALS OF CONTROL OR TAPED.
6. IF HEATING AND COOLING BLOWER SPEEDS ARE NOT THE
SAME DISCARD JUMPER BEFORE CONNECTING BLOWER LEADS.
7. COOLING ON/OFF FAN DELAY SETTING: 7 SECONDS ON
AND 30 SECONDS OFF.
IMPORTANT:
GY-70
YL-11
NC
VT-18
RD-29
OR-22
LIMIT
YL-27
RD-24
BU-23
BK-26
4 SPEED
BLOWER
PRIMARY ROLLOUT
LIMIT (RL)
OR-49
VT-14
2
6
AIR
5 CIRCULATION
BLOWER
4
(ACB)
3
AIR PRESSURE
SWITCH (PS)
BR-21
BU-36
LOAD
YL-27
BK-26
2 SPEED
BLOWER
M 1
FOR PROPER OPERATION ON 208 VOLT THE
FOLLOWING CHANGES MUST BE MADE:
MOVE BK17 WIRE FROM TRANSFORMER
230 TERMINAL TO 208 TERMINAL.
UNPLUG RED COMBUSTION BLOWER LEAD
FROM CONTROL BOARD TERMINAL (DI) AND
ATTACH BLACK BLOWER LEAD TO TERMINAL.
TAPE UNUSED RED LEAD.
BK
TRANSFORMER
(208V)
C 2
2
3
0
FAN
N
3
MOTOR
SPEEDS
L1
T1
1
9 7 2
H
E
A
T
MODELS
L
11 10
1
C
O
O
L
P 3
208 VOLT INSTALLATION
090
120
CONTROL BOARD
(TERMINAL ORDER REARRANGED)
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DISCONNECT ELECTRICAL POWER TO THIS FURNACE BEFORE
SERVICING OR PERFORMING MAINTENANCE.
WARNING
150
21
2
0
8
COM
R
G
2X
4F
M
VR
2
C
C
A
P
S
COMP
C
C
O
M
N
2
N0
NC
L2
T2
PS
COMB
BLOWER
2
3
0
D
I
C
6
DSI
8
T
1
F
S
3
RL
L
I
M
I
T
A
U
X
L
I
M
I
T
FS
GV
C
M
5
N
4 4
COOL
HEAT
L2
WH
WH
6
L2
MED
LOW
MED
HI
MED
HI
3
3
3
3
3
3
3
PGB48C0902E
PGB48C1152E
PGB48C1402E
PGB60C0902E
PGB60C1152E
PGB60C1402E
LOW
SPEED
BK-26
BU-23
RD-24
BK-26
BU-23
RD-24
BU-23
MOTOR TO "HEAT"
* HEATING BLOWER SPEED
L2
MED
MED
MED
LOW
SPEED
HI
HI
HI
L1
D1
FS
10
7
9
11
4
8
6
12
1
2
5
3
BK-26
BK-26
BK-26
BU-23
BU-23
BU-23
RD-24
MOTOR TO "COOL"
T1
DETAIL 1
LINE
208 230
COM
TRANSFORMER
** COOLING BLOWER SPEED
L1
BK
17
VT-47
COMBUSTION
BLOWER
(CB)
VT
(COM)
RD
(230)
UNUSED
L2
FACTORY WIRED MOTOR CONNECTIONS
WARNING:DISCONNECT POWER BEFORE SERVICING.
208/230 VAC 1Ø
GND
FAN
OD
R
ACB
N
1
PGB42C1152E
CC
HERM
CAP
W
CC
1
THERMOSTAT
Y
L
P
S
C
O
M
L
1
GY
25
OR
BU-36
WH
GN
YL
RD
R
Y
W
G
C
NO
COM
1
FLAME
SENSOR
AUX LIMIT
CONTROL
OR-19
CAPACITOR
(CAP)
2
AIR
CIRCULATION
BLOWER
3
(ACB)
THERMOSTAT
DIRECT SPARK
IGNITOR (DSI)
GAS VALVE
(GV)
6
BR
GY-25
VT-34
BR
L1
VT
16
BR
11
GND
L1
L2
BK
27
VT
20
RD
15
C
A
P
A
C
I
T
O
R
LOW PRESSURE
SWITCH
RD
10
FAN
HERM
COM
O.D.
FAN
MOTOR
VT
16
LOW VOLTAGE
LOW VOLTAGE FIELD
HI VOLTAGE
HI VOLTAGE FIELD
COLOR CODE
YL YELLOW
BR BROWN
OR ORANGE
WH WHITE
VT VIOLET
BU BLUE
GN GREEN
GY GRAY
BK BLACK
RD RED
20261201 REV. 2
WARNING:DISCONNECT POWER
BEFORE SERVICING.
YL/BK
GND
T1
T2
ADJUSTABLE FAN SETTING
(FACTORY SETTING AS SHOWN)
DETAIL 1
FIELD CONNECTION
208/230 VAC 1Ø
L2
VT
37
RD
13
R
C
COMPRESSOR
1 WIRING
S
YL-12
READ BEFORE OPERATING OR SERVICING THIS
UNIT WARNING: DISCONNECT POWER BEFORE
SERVICING.
8. DIAGNOSTIC LIGHT: STEADY ON= STANDBY MODE;
1. AMANA SPECIFIED REPLACEMENT PARTS MUST BE
STEADY OFF= INTERNAL FAULT OR NO POWER; 1
USED WHEN SERVICING
FLASH= LOCKOUT; 2 FLASHES= PS STUCK OPEN;
2. IF ANY ORIGINAL WIRE IS REPLACED, 105 °C WIRE MUST
3 FLASHES= PS STUCK CLOSED; 4 FLASHES=
BE USED.USE COPPER CONDUCTORS ONLY.
OPEN HIGH LIMIT SWITCH, AUX LIMIT SWITCH,
3. EQUIPPED FOR 230 VOLT OR 208 VOLT.
OR OPEN ROLL OUT; 5 FLASHES= FLAME
4. HEAT ON/OFF FAN DELAY FACTORY SETTINGS: 30
DETECTED WITH GAS VALVE CLOSED; 6
SECONDS ON AND 120 SECONDS OFF.
FLASHES= COMPRESSOR DELAYED ON SHORT
5. UNUSED BLOWER MOTOR LEADS MUST BE PLACED ON
CYCLE TIMER;7 FLASHES = LOW FLAME SENSE
UNUSED MOTOR TERMINALS OF CONTROL OR TAPED.
CURRENT; 8 FLASHES = 5 LIMIT TRIPS WITHIN A
6. IF HEATING AND COOLING BLOWER SPEEDS ARE NOT THE
SINGLE CALL FOR HEAT.
SAME DISCARD JUMPER BEFORE CONNECTING BLOWER LEADS.
9. COMPRESSOR SHORT CYCLE DELAY: 3 MIN.
7. COOLING /FAN ONLY ON/OFF FAN DELAY SETTING: 7 SECONDS ON
STARTUP DELAY AFTER POWER LOSS.
AND 30 SECONDS OFF.
IMPORTANT:
GY-70
YL-11
NC
VT-18
OR-22
LIMIT
RD-29
PRIMARY ROLLOUT
RD
LIMIT (RL)
1
OR-49
AIR PRESSURE
SWITCH (PS)
BR-21
LOAD
GY-25
VT-14
RD-24
BU-23
BK-26
5
4
M 1
2
3
0
FAN
N
3
MODELS
L1
T1
1
9 7 2
H
E
A
T
MOTOR
SPEEDS
L
1 11 10
C
O
O
L
P 3
208 VOLT INSTALLATION
C 2
FOR PROPER OPERATION ON 208 VOLT THE
FOLLOWING CHANGES MUST BE MADE:
MOVE BK17 WIRE FROM TRANSFORMER
230 TERMINAL TO 208 TERMINAL.
090
120
CONTROL BOARD
(TERMINAL ORDER REARRANGED)
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DISCONNECT ELECTRICAL POWER TO THIS FURNACE BEFORE
SERVICING OR PERFORMING MAINTENANCE.
WARNING
150
22
R
G
FAN
208/230 VAC 1Ø
GND
C
S
R
ACB
C
A
P
OD
2
COMP
C
C
O
M
N
2
L2
T2
N0
PS
NC
COMB
BLOWER
2 2
0 3
8 0
D
I
C
6
DSI
8
T
1
F
S
3
RL
L
I
M
I
T
A
U
X
L
I
M
I
T
FS
GV
C
M
5
N
4 4
COOL
HEA T
L2
WH
WH
6
L2
BK-26
BK-26
BK-26
BK-26
BK-26
HI
HI
HI
HI
HI
4
4
4
4
4
2
PGD24C0902E
PGD30C0702E
PGD30C0902E
PGD36C0702E
PGD36C0902E
PGD42C0902E
HI
BK-26
YL-27
BU-23
LOW
4
MED HI
4
MOTOR TO "HEAT"
SPEED
PGD24C0452E
* HEATING BLOWER SPEED
L2
L1
D1
FS
VT-47
COMBUSTION
BLOWER
(CB)
2
12
11
8
5
9
3
6
1
10
7
4
BU-23
MED HI
BK-26
BU-23
MED HI
HI
RD-24
MED LOW
YL-27
LOW
YL-27
YL-27
LOW
RD-24
MOTOR TO "COOL"
MED LOW
230
T1
DETAIL 1
SPEED
LOW
COM
LINE
208
** COOLING BLOWER SPEED
L1
BK
17
VT
(COM)
RD
(230)
UNUSED
L2
FACTORY WIRED MOTOR CONNECTIONS
WARNING:DISCONNECT POWER BEFORE SERVICING.
HERM
CAP
COM
CC
W
CC
2X
4F
M
VR
THERMOSTAT
Y
L
P
S
C
O
M
1
N
1
PGD24C0702E
L1
T1
2
0
8
L
1
GY
25
RD
1
OR
YL
R
G
W
Y
C
THERMOSTAT
DIRECT SPARK
IGNITER (DSI)
GAS VALVE
(GV)
LOW VOLTAGE TERMINAL STRIP
WH
GN
RD
NO
COM
FLAME
SENSOR
AUX LIMIT
CONTROL
OR-19
CAPACITOR
(CAP)
6
AIR
5 CIRCULATION
BLOWER
4
(ACB)
3
2
1
READ BEFORE OPERATING OR SERVICING THIS
UNIT WARNING: DISCONNECT POWER BEFORE
SERVICING.
1. AMANA SPECIFIED REPLACEMENT PARTS MUST BE
USED WHEN SERVICING.
2. IF ANY ORIGINAL WIRE IS REPLACED, 105 C WIRE MUST
BE USED.USE COPPER CONDUCTORS ONLY.
3. EQUIPPED FOR 230 VOLT OR 208 VOLT.
4. HEAT ON/OFF FAN DELAY FACTORY SETTINGS: 30
SECONDS ON AND 120 SECONDS OFF.
5. UNUSED BLOWER MOTOR LEADS MUST BE PLACED ON
UNUSED MOTOR TERMINALS OF CONTROL OR TAPED.
6. IF HEATING AND COOLING BLOWER SPEEDS ARE NOT THE
SAME DISCARD JUMPER BEFORE CONNECTING BLOWER LEADS.
7. COOLING ON/OFF FAN DELAY SETTING: 7 SECONDS ON
AND 30 SECONDS OFF.
IMPORTANT:
GY-70
YL-11
NC
VT-18
RD-29
OR-22
LIMIT
YL-27
RD-24
BU-23
BK-26
4 SPEED
BLOWER
PRIMARY ROLLOUT
LIMIT (RL)
OR-49
GY-25
VT-14
6
AIR
5 CIRCULATION
BLOWER
4
(ACB)
3
2
1
AIR PRESSURE
SWITCH (PS)
BR-21
BU-36
LOAD
YL-27
BK-26
2 SPEED
BLOWER
M 1
FOR PROPER OPERATION ON 208 VOLT THE
FOLLOWING CHANGES MUST BE MADE:
MOVE BK17 WIRE FROM TRANSFORMER
230 TERMINAL TO 208 TERMINAL.
UNPLUG RED COMBUSTION BLOWER LEAD
FROM CONTROL BOARD TERMINAL (DI) AND
ATTACH BLACK BLOWER LEAD TO TERMINAL.
TAPE UNUSED RED LEAD.
BK
TRANSFORMER
(208V)
C 2
2
3
0
FAN
N
3
MODELS
W
R
1
9 7 2
H
E
A
T
MOTOR
SPEEDS
Y
L
1 11 10
C
O
O
L
GY-25
RD
13
L1
R
C
COMPRESSOR
1 WIRING
S
VT
16
BR
11
GND
L1
L2
BK
27
VT
20
RD
15
C
A
P
A
C
I
T
O
R
LOW PRESSURE
SWITCH
RD
10
FAN
HERM
COM
O.D.
FAN
MOTOR
VT
16
LOW VOLTAGE
LOW VOLTAGE FIELD
HI VOLTAGE
HI VOLTAGE FIELD
COLOR CODE
YL YELLOW
BR BROWN
OR ORANGE
WH WHITE
VT VIOLET
BU BLUE
GN GREEN
GY GRAY
BK BLACK
RD RED
20261401 REV. 2
WARNING:DISCONNECT POWER
BEFORE SERVICING.
YL/BK
GND
T1
T2
ADJUSTABLE FAN SETTING
(FACTORY SETTING AS SHOWN)
DETAIL 1
FIELD CONNECTION
208/230 VAC 1Ø
L2
VT
37
BR
VT-34
BR
YL-12
8. DIAGNOSTIC LIGHT: STEADY ON= STANDBY MODE;
STEADY OFF= INTERNAL FAULT OR NO POWER; 1
FLASH= LOCKOUT; 2 FLASHES= PS STUCK OPEN;
3 FLASHES= PS STUCK CLOSED; 4 FLASHES=
OPEN HIGH LIMIT SWITCH, AUX LIMIT SWITCH,
OR OPEN ROLL OUT; 5 FLASHES= FLAME
DETECTED WITH GAS VALVE CLOSED; 6
FLASHES= COMPRESSOR DELAYED ON SHORT
CYCLE TIMER;7 FLASHES= LOW FLAME SENSE
CURRENT; 8 FLASHES= 5 LIMIT TRIPS
WITHIN A SINGLE CALL FOR HEAT.
9. COMPRESSOR SHORT CYCLE DELAY: 3 MIN.
STARTUP DELAY AFTER POWER LOSS.
P 3
208 VOLT INSTALLATION
090
120
CONTROL BOARD
(TERMINAL ORDER REARRANGED)
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DISCONNECT ELECTRICAL POWER TO THIS FURNACE BEFORE
SERVICING OR PERFORMING MAINTENANCE.
WARNING
150
N
2
L1
T1
2
0
8
L1
C
O
M
2
3
0
CC
HE RM
CAP
CO M
FAN
CC
N
10 3
OD
2
FAN
2X
4F
M
VR
GND
1
S
C
RCOMP
L2
T2
N0
PS
NC
C
DSI
COMB
BLOWER
FS
C
O
M
H
E
A F D N
T S I 1
W1
EM/W2
C M
8 6 7 3 5
C
C
C
NORMAL
NORMAL
NORMAL
NORMAL
NORMAL
PGD48C1152E
PGD48C1402E
PGD60C0902E
PGD60C1152E
PGD60C1402E
B
B
B
C
B
A
C
B
A
*
*
*
NORMAL
*****
HEATING
BLOWER
SPEED
RL
L
I
M
I
T
L
I
M
I
T
A
U
X
N
4 4
COOLING
BLOWER
SPEED
PGD48C0902E
ADJUST
SETTING
BLOWER MOTOR SPEED
DETAIL 2
WARNING: DISCONNECT POWER BEFORE SERVICING.
208/230 VAC 1Ø
L
P
S
L
1 11 12
C
O
T O
9 I L
CONTROL BOARD
(TERMINAL ORDER REARRANGED)
BLOWER
INTERFACE
R2
O
R3
C1
C2
HEAT
L2
L2
UNUS ED
L2
L1
L1
D1
FS
8
11
9
12
2
5
3
6
1
10
7
4
T1
GY-70
YL-11
DETAIL 1
RD-13
VT-37
RD-1
COM
LINE
208 230
WH
BR-21
GY-25
LOAD
READ BEFORE OPERATING OR SERVICING THIS UNIT.
WARNING: DISCONNECT POWER BEFORE SERVICING.
1. AMANA SPECIFIED REPLACEMENT PARTS MUST BE
USED WHEN SERVICING.
2. IF ANY ORIGINAL WIRE IS REPLACED, 105ºC WIRE
MUST BE USED.USE COPPER CONDUCTORS ONLY.
3. EQUIPPED FOR 230 VOLT OR 208 VOLT.
4. HEAT ON/OFF FAN DELAY FACTORY
SETTINGS: 30 SECONDS ON AND 120 SECONDS OFF.
5. UNUSED BLOWER MOTOR LEADS MUST BE PLACED ON
UNUSED MOTOR LEADS TERMINALS OF CONTROL OR TAPED.
6. IF HEATING AND COOLING BLOWER SPEEDS ARE NOT THE
SAME DISCARD JUMPER BEFORE CONNECTING BLOWER LEADS.
7. COOLING / FAN ONLY ON/OFF FAN DELAY SETTING:
7 SECONDS ON AND 30 SECONDS OFF.
IMPORTANT:
COOL
L2
VT-47
BK-17
COMBUSTION
BLOWER
(CB)
VT
(COM)
RD
(230V)
RD-31
TRANSFORMER
FOR PROPER OPERATION ON 208 VOLT THE
FOLLOWING CHANGE MUST BE MADE:
MOVE BK17 WIRE FROM TRANSFORMER
230 TERMINAL TO 208 TERMINAL.
OR-49
LIMIT
YL/BK
SEE
DETAIL
2
VT-34
AUX LIMIT
CONTROL
OR-19
AIR
CIRCULATION
BLOWER
(ACB)
R Y W G C
NORM
(+
)
(-)
TEST
A DJUST
CO OL
A
B
C
D
BLOWER
INTERFACE
HEAT
A
B
C
D
CUT TO
E NA BLE
DEHUM IDIFY
VT
20
RD
10
BU-44
RD-23
BR
48
GN-70
YL
27
8. DIAGNOSTIC LIGHT: STEADY ON= STANDBY MODE;
STEAD OFF= INTERNAL FAULT OR NO POWER; 1
FLASH= LOCKOUT; 2 FLASHES= PS STUCK OPEN;
3 FLASHES= PS STUCK CLOSED; 4 FLASHES=
OPEN HIGH LIMIT SWITCH, AUX LIMIT SWITCH,
OR OPEN ROLL OUT; 5 FLASHES= FLAME
DETECTED WITH GAS VALVE CLOSED; 6
FLASHES= COMPRESSOR DELAYED ON SHORT
CYCLE TIMER;7 FLASHES= LOW FLAME SENSE
CURRENT; 8 FLASHES= 5 LIMIT TRIPS WITHIN A
SINGLE CALL FOR HEAT.
9. COMPRESSOR SHORT CYCLE DELAY: 3 MIN.
STARTUP DELAY AFTER POWER LOSS.
THERMOSTAT
GN
RD
AIR PRESSURE
SWITCH (PS)
FLAME
SENSOR
GY-25
RD-29
DIRECT SPARK
IGNITOR (DSI)
VT-18
BU
36
YL
VT-14
PRIMARY ROLLOUT
LIMIT (RL)
OR-22
NO
MODELS
R Y W G C
AIR
CIRCULATION
BLOWER
(ACB)
TEST
( -)
A
B
C
D
A
B
C
D
()+
NORM
ADJUST
COOL
HEAT
G
M 1
208 VOLT INSTALLATION
P 3
Y/Y2
C 2
CUT TO
E NA B LE
W1
EM/W2
O
R2
R3
C1
C2
G
Y/Y2
DEHUM IDI FY
R
C
RD
13
L1
L2
T1
T2
FAN
HERM
COM
DETAIL 1
ADJUSTABLE FAN SETTING
(FACTORY SETTING AS SHOWN)
VT
20
LOW VOLTAGE
LOW VOLTAGE FIELD
HI VOLTAGE
HI VOLTAGE FIELD
COLOR CODE
YL YELLOW
BR BROWN
OR ORANGE
WH WHITE
VT VIOLET
BU BLUE
GN GREEN
GY GRAY
BK BLACK
RD RED
GY
25
VT
16
RD RD
10 15
C
A
P
A
C
I
T
O
R
O.D.
FAN
MOTOR
20290001 REV. 0
LOW PRESSURE
SWITCH (LPS)
GND
GY
25
BR
11
VT BK
16 27
L2 L1 GND
FIELD CONNECTION YL
208/230 VAC 1Ø
BK
VT
37
COMPRESSOR
1Ø WIRING
S
YL-12
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DISCONNECT ELECTRICAL POWER TO THIS FURNACE BEFORE
SERVICING OR PERFORMING MAINTENANCE.
WARNING
COM
090
120
150
23
NC
2002-2004 Goodman Company, L.P.
24
Effective: June 2004