Download Amana GUSA Technical information
Transcript
Technical Information Model and Manufacturing numbers listed in this manual. MODEL M/N GUSA070BX35 P1233902F GUSA090BX40 P1233904F GUSA090BX50 P1233905F 40" 90% Gas Furnaces GUSA___BX__ • Refer to Service Manual RS6600001 Rev. 2 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. GUSA115BX50 P1233906F GUSA070BX35 P1239502F GUSA090BX40 P1239504F GUSA090BX50 P1239505F GUSA115BX50 P1239506F GUSA070BX35 P1242002F GUSA090BX40 P1242004F GUSA090BX50 P1242005F GUSA115BX50 P1242006F DESI GN This manual replaces RT6612003 Rev. 1 October 2001. CE RTI FI E D CE R T I FI E D REV. 2 - New models added to manual (standardized White-Rodgers Sini Igniter). Heating&Air Conditioning ® Comfort. Quality. Trust. This manual is to be used by qualified HVAC technicians only. Amana does not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person. RT6612003 Revision 2 February 2002 PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. When engineering and manufacturing changes take place where interchangeability of components are affected, the manufacturing number will change. It is very important to use the model and manufacturing numbers at all times when requesting service or parts information. G U S A 070 B X 35 Product Type Airflow Capability 35: 1.5 - 3.5 Tons G: Gas Furnace 40: 1.5 - 4.0 Tons 50: 2.0 - 5.0 Tons Supply Type U: Upflow/Horizontal Additional Features X: NOx Models Furnace Type S: 2-Stage Condensing (90%) Design Series B: Initial Design Series (Silicon Nitride Ignition System) Model Family A: Air Command 90 (40" Height) WARNING Nominal Input 070: 70,000 Btuh 090: 90,000 Btuh 115: 115,000 Btuh IF REPAIRS ARE ATTEMPTED BY UNQUALIFIED PERSONS, DANGEROUS CONDITIONS (SUCH AS EXPOSURE TO ELECTRICAL SHOCK) MAY RESULT. THIS MAY CAUSE SERIOUS INJURY OR DEATH. AMANA WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU PERFORM SERVICE ON YOUR OWN PRODUCT, YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY RESULT. CAUTION 2 Rev. 2 PRODUCT DIMENSIONS GUSA___BX__ AIR DISCHARGE A 28 3/4 B (DISCHARGE AIR) 3/4 3/4 2 1/2 20 3/16 C AIR INTAKE PIPE 2" PVC ALTERNATE GAS SUPPLY HOLE 1 1/2 14 2 1/16 VENT/FLUE PIPE 2" PVC LEFT SIDE DRAIN LINE HOLES 23 DRAIN TRAP CL LOW VOLTAGE ELECTRICAL HOLE 1 3/4 SIDE CUT-OUT ALTERNATE AIR INTAKE LOCATION STANDARD GAS SUPPLY HOLE 2 11/16 7 3/8 HIGH VOLTAGE ELECTRICAL HOLE AIR DISCHARGE 3/4 CONDENSATE DRAIN TRAP w/ 3/4" PVC DISCHARGE (RIGHT OR LEFT SIDE) 1 3/4 30 1/4 40 24 9/16 27 1/8 2 5/8 21 1/4 ALTERNATE VENT/FLUE LOCATION 4 1/8 30 1/4 2 5/8 19 3/16 11 3/4 16 5/8 11 3/4 RIGHT SIDE DRAIN LINE HOLES DRAIN TRAP CL 2 19 3/16 HIGH VOLTAGE ELECTRICAL HOLE 6 1/8 LOW VOLTAGE ELECTRICAL HOLE 32 13/16 1 3/4 SIDE CUT-OUT 1 5/8 1 D BOTTOM KNOCK-OUT 23 9/16 BOTTOM KNOCK-OUT LEFT SIDE VIEW RIGHT SIDE VIEW FRONT VIEW Cabinet Size Units A B C D Small 070__35 16-1/2 15 12-3/8 12-5/8 Medium 090__40 20-1/2 19 16-3/8 14-5/8 Large 090__50 115__50 24-1/2 23 20-3/8 18-5/8 All dimensions are in inches. GUSA___BX__ (Manufacturing Numbers P1239502-06F and P1242002-06F) 3 Rev. 2 PRODUCT DIMENSIONS GUSA___BX__ AIR DISCHARGE A 28 3/4 3/4 2 1/2 20 3/16 AIR INTAKE PIPE 2" PVC ALTERNATE GAS SUPPLY HOLE LEFT SIDE DRAIN LINE HOLES 1 1/2 2 1/16 DRAIN TRAP CL 30 1/4 CONDENSATE DRAIN TRAP w/ 3/4" PVC DISCHARGE (RIGHT OR LEFT SIDE) 40 27 1/8 6 1/8 SIDE CUT-OUT 19 3/16 2 5/8 19 3/16 2 1 3/4 ALTERNATE VENT/FLUE LOCATION 4 1/8 30 1/4 LOW VOLTAGE ELECTRICAL HOLE HIGH VOLTAGE ELECTRICAL HOLE ALTERNATE AIR INTAKE LOCATION STANDARD GAS SUPPLY HOLE 2 11/16 23 14 VENT/FLUE PIPE 2" PVC 7 3/8 2 5/8 AIR DISCHARGE 3/4 B (DISCHARGE) C 3/4 HIGH VOLTAGE ELECTRICAL HOLE 11 3/4 16 5/8 11 3/4 9 3/8 RIGHT SIDE DRAIN LINE DRAIN HOLES TRAP CL LOW VOLTAGE ELECTRICAL HOLE 32 13/16 7 7/8 1 3/4 SIDE CUT-OUT 1 5/8 1 D BOTTOM KNOCK-OUT 23 9/16 BOTTOM KNOCK-OUT LEFT SIDE VIEW RIGHT SIDE VIEW FRONT VIEW Cabinet Size Units A B C D Small 070__35 16-1/2 15 12-3/8 12-5/8 Medium 090__40 20-1/2 19 16-3/8 14-5/8 Large 090__50 115__50 24-1/2 23 20-3/8 18-5/8 All dimensions are in inches. GUSA___BX__ (Manufacturing Numbers P1233902-06F) 4 Rev. 2 COMPONENT IDENTIFICATION 6 5 7 8 7 9 10 BLOWER COMPARTMENT BURNER COMPARTMENT 11 4 3 13 3 12 2 14 1 15 16 17 18 32 31 18 30 20 19 20 21 21 29 22 23 24 24 Volt Thermostat Connections Fuse (3A) 12 Circuit Connector Intell-Ignition Thermostat Selection Jumper (Single vs. Two -Stage) Low to High Stage Delay DIP Switch Heat OFF Delay DIP Switches 5 Circuit Connector 28 25 27 Diagnostic Red LED Circulator Blower, Transformer and Accessory Quick Connects 26 Upflow/Horizontal Integrated Control Module 1 Two-Stage Gas Valve 17 Two-Speed Induced Draft Blower 2 Gas Line Entrance (Alternate) 18 Electrical Connection Inlet (Alternate) 3 Pressure Switch(es) 19 Coil Front Cover Pressure Tap 4 Gas Manifold 20 Coil Front Cover Drain Tap 5 Combustion Air Intake Connection 21 Drain Line Penetrations 6 Hot Surface Igniter 22 Drain Trap 7 Rollout Limit 23 Blower Door Interlock Switch 8 Burners 24 Capacitor 9 Flame Sensor 25 Two-Stage Integrated Control Module 10 Flue Pipe Connection (with fuse and diagnostic LED) 11 Flue Pipe 26 Transformer (40 VA) 12 Combustion Air Intake (Alternate) 27 Circulator Blower 13 Primary Limit 28 Bottom Return Filter Retainer 14 Gas Line Entrance 29 Auxiliary Limit 15 Flue Pipe Connection (Alternate) 30 Junction Box 16 Rubber Elbow 31 Electrical Connection Inlet 32 Coil Front Cover GUSA___BX__ (Manufacturing Numbers P1239502-06F and P1242002-06F) 5 Rev. 2 COMPONENT IDENTIFICATION 6 BLOWER COMPARTMENT BURNER COMPARTMENT 5 7 8 7 4 9 10 11 3 3 12 13 14 15 16 17 18 19 20 2 1 32 18 19 20 21 31 22 30 29 23 24 Volt Thermostat Connections Fuse (3A) 12 Circuit Connector Intell-Ignition Thermostat Selection Jumper (Single vs. Two -Stage) Low to High Stage Delay DIP Switch Heat OFF Delay DIP Switches 5 Circuit Connector 28 27 Diagnostic Red LED 24 26 Circulator Blower, Transformer and Accessory Quick Connects 25 Upflow/Horizontal Integrated Control Module 1 Two-Stage Gas Valve 17 Two-Speed Induced Draft Blower 2 Gas Line Entrance (Alternate) 18 Coil Front Cover Pressure Tap 3 Pressure Switch(es) 19 Coil Front Cover Drain Tap 4 Gas Manifold 20 Drain Line Penetrations 5 Combustion Air Intake Connection 21 Drain Trap 6 Hot Surface Igniter 22 Capacitor 7 Rollout Limit 23 Electrical Connection Inlets (Alternate) 8 Burners 24 Two-Stage Integrated Control Module 9 Flame Sensor (with fuse and diagnostic LED) 10 Flue Pipe Connection 25 Transformer (40 VA) 11 Flue Pipe (Internal) 26 Circulator Blower 12 Combustion Air Intake (Alternate) 27 Bottom Return Filter Retainer 13 Primary Limit 28 Blower Door Interlock Switch 14 Gas Line Entrance 29 Junction Box 15 Flue Pipe Connection (Alternate) 30 Electrical Connection Inlets 16 Rubber Elbow 31 Auxiliary Limit 32 Coil Front Cover GUSA___BX__ (Manufacturing Numbers P1233902-06F) 6 Rev. 2 PRODUCT DESIGN General Operation This GUSA furnace is equipped with an electronic ignition device used to light the burners and an induced draft blower to exhaust combustion products. An interlock switch prevents furnace operation if the blower door is not in place. Keep the blower access door in place except for inspection and maintenance. This furnace is also equipped with a self-diagnosing electronic control module. In the event a furnace component is not operating properly, the control module LED will flash on and off in a factory-programmed sequence, depending on the problem encountered. This light can be viewed through the observation window in the blower access door. Refer to the Troubleshooting Chart for further explanation of the LED codes and Abnormal Operation - Integrated Ignition Control section in the Service Instructions for an explanation of the possible problem. The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Contractors of America. *Obtain from: American National Standards Institute 1430 Broadway New York, NY 10018 Location Considerations • The furnace should be as centralized as is practical with respect to the air distribution system. • Do not install the furnace directly on carpeting, tile, or combustible material other than wood flooring. • When suspending the furnace from rafters or joists, use 3/8" threaded rod and 2” x 2” x 3/8” angle as shown in the Installation and Service Instructions. The length of the rod will depend on the application and clearance necessary. • When installed in a residential garage, the furnace must be positioned so the burners and ignition source are located not less than 18 inches (457 mm) above the floor and protected from physical damage by vehicles. Notes: 1. Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2” or 3” in diameter, depending upon furnace input, number of elbows, length of run and installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. 3. Conversion kits for high altitude natural or propane gas operation are available. See High Altitude Derate chart for details. 4. Installer must supply the following gas line fittings, depending on which entrance is used: Left -- Two 90º Elbows, one close nipple, straight pipe. Right -- Straight pipe to reach gas valve. Accessibility Clearances (Minimum) MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS (INCHES) POSITION* FRONT SIDES REAR TOP FLUE FLOOR Upflow Horizontal 1 Alcove 0 6 0 0 1 4 0 0 C C * = All positioning is determined as installed unit is viewed from the front. C = If placed on combustible floor, floor MUST be wood ONLY. 36" at front is required for servicing or cleaning. Note: In all cases accessibility clearance shall take precedence over clearances from the enclosure where accessibility clearances are greater. All dimensions are given in inches. High Altitude Derate When this furnace is installed at high altitude, the appropriate High Altitude orifice kit must be installed. This is required due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range. PROPANE AND HIGH ALTITUDE KITS MODEL NUMBER GUSA***BX** 0 to 7,000 ft. 7,001 to 11,000 ft. HANG16 LPTK09 High Altitude Propane Conversion Kit Natural Gas Kit (#55 Orifices) (#44 Orifices) 7,001 to 11,000 ft. 7,001 to 11,000 ft. HALP13 High Altitude LP Gas Kit (#56 Orifices) HAPS30 High Altitude Pressure Switch Kit High altitude kits are purchased according to the installation altitude and usage of either natural or propane gas. Refer to the chart above for a tabular listing of appropriate altitude ranges and corresponding manufacturer’s high altitude Natural Gas and Propane Gas kits. For a tabular listing of appropriate altitude ranges and corresponding manufacturer's High Altitude Pressure Switch kits, refer to either the Pressure Switch Trip Points & Usage Chart in this manual or the Accessory Charts in Service Instructions. 2. Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace. 7 Rev. 2 PRODUCT DESIGN PRESSURE SWITCH TRIP POINTS AND USAGE CHART MODEL GUSA070BX35 GUSA090BX40 GUSA090BX50 GUSA115BX50 NEGATIVE PRESSURE ID BLOWER WITH FLUE NOT FIRING TYPICAL SEA LEVEL DATA LOW HIGH FIRE FIRE NEGATIVE PRESSURE ID BLOWER WITH FLUE FIRING TYPICAL SEA LEVEL DATA LOW HIGH FIRE FIRE NEGATIVE PRESSURE COIL COVER WITH FLUE NOT FIRING TYPICAL SEA LEVEL DATA LOW HIGH FIRE FIRE NEGATIVE PRESSURE COIL COVER WITH FLUE FIRING TYPICAL SEA LEVEL DATA LOW HIGH FIRE FIRE -0.35 -0.35 -0.55 -0.55 -0.70 -0.70 -0.65 -0.65 PRESSURE SWITCH TRIP POINTS AND USAGE CHART 0 to 7,000 ft. TRIP POINT COIL COVER PRESSURE SWITCH LOW HIGH FIRE FIRE MODEL GUSA070BX35 GUSA090BX40 GUSA090BX50 GUSA115BX50 -0.37 -0.37 COIL COVER PRESSURE SWITCH PART # 20197305 7,001 ft. to 11,000 ft. TRIP POINT ID BLOWER PRESSURE SWITCH LOW HIGH FIRE FIRE -0.20 ID BLOWER PS1 PRESSURE LABEL SWITCH COLOR PART # -0.55 11177117 GREEN PS2 LABEL COLOR TRIP POINT COIL COVER PRESSURE SWITCH LOW HIGH FIRE FIRE TRIP POINT ID BLOWER PRESSURE SWITCH LOW HIGH FIRE FIRE HIGH ALTITUDE KIT PS1 LABEL COLOR PS2 LABEL COLOR PURPLE -0.37 -0.15 HAPS30 11177119 YELLOW PINK -0.37 -0.46 Note: All installations above 7,000 ft. require a pressure switch change. For installations in Canada the GUSA furnace is certified only to 4500 feet. Note: Replacement pressure switch number is listed below high altitude kit number. Note: All negative pressure readings are in inches of water column (" w.c.). T.O.D. PRIMARY LIMIT ROLLOUT LIMIT SWITCHES PART NUMBER 20162904 20162907 PART NUMBER OPEN SETTING (°F) 150 155 OPEN SETTING (°F) 200 220 190 COLOR CODE(S) BROWN ORANGE COLOR CODE(S) GUSA070BX35 YELLOW ORANGE GRAY GUSA070BX35 1 10123534 1 GUSA090BX40 GUSA090BX50 1 1 GUSA090BX50 2 GUSA115BX50 2 AUXILIARY LIMIT SWITCHES PART NUMBER 10123535 OPEN SETTING (°F) 150 COLOR CODE(S) GUSA070BX35 RED GUSA090BX40 1 GUSA090BX50 1 GUSA115BX50 1 1 10123537 2 GUSA090BX40 GUSA115BX50 8 Rev. 2 10123533 2 PRODUCT DESIGN Coil Matches: A large array of Amana coils are available for use with the new GUSA furnaces, in either upflow or horizontal applications. These coils are available in both cased and uncased models, with or without a TXV expansion device. These new 90%+ furnaces match up with the existing Amana coils as shown in the chart below. Btuh Input GUSA070BX35 CCA_F*C Cased A-Coils CCA_FSC Uncased A-Coils CHA_TCC Cased TXV A-Coils 2 - 3 1/2 CCA18FCC CCA24FCC CCA30FCC CCA36FCC CCA42FCC CCA18FSC CCA24FSC CCA30FSC CCA36FSC CCA42FSC CHA18TCC CHA24TCC CHA30TCC CHA36TCC CCA30FDC CCA36FDC CCA42FDC CCA48FCC CCA48FSC CCA36FKC CCA48FDC CCA54FCC CCA57FCC CCA60FCC CCA54FSC CCA57FSC CCA60FSC Cabinet Air Flow Width (tons) 16 1/2" GUSA090BX40 20 1/2" 2 1/2 - 4 GUSA090BX50 24 1/2" 3-5 GUSA115BX50 24 1/2" 3-5 CHA_TSC Uncased TXV A-Coils CCF_F*C Horiz. A-Coils CHF_TCC Horiz. A-Coils CHA18TSC CHA24TSC CHA30TSC CHA36TSC CCF24FCC CHF18TCC CCF30FCC CHF24TCC CCF36FCC CHF30TCC CHA42TCC CHA42TSC CCF24FDC CCF36FDC CHF36TCC CCF42FCC CHF42TCC CCF48FCC CHA48TCC CHA54TCC CHA57TCC CHA60TCC CHA48TSC CHA54TSC CHA57TSC CHA60TSC CCF48FDC CHF48TCC CCF60FCC CHF60TCC CCF61FCC Coil Matches (for the Amana RSD units using R-410A): Cabinet Air Flow Width (tons) CA_FCA Cased A-Coils CF_FCA Horizontal A-Coils GUSA070BX35 16-1/2" 1-1/2 - 3 CA36FCA CF30FCA GUSA090BX40 20-1/2" 2-1/2 - 4 CA42FCA CF36FCA GUSA090BX50 24-1/2" 3-5 CA48FCA CA57FCA CF48FCA CF60FCA Btuh Input GUSA115BX50 24-1/2" 3-5 9 Rev. 2 PRODUCT DESIGN Thermostats: The following Amana Thermostats are suggested for use with the GUSA Furnace Models: Thermostats Thermostat Man/Auto Programmable Cool Heat Batt. Powered Batt. Bkup* Shape Color 1213411 Man. Changeover No 1 2 No No Rectangular White 1213407 Man. Changeover Yes 2 2 No No Rectangular White 1213406* Man. Or Auto Yes 2 3 No Yes Rectangular White *1213406 is the recommended model for the GUSA furnace when used with a heat pump in a fossil fuel application. It is NOT for use with the GUSA as a sole heating source. 1213406 thermstats are 24V powered with battery backup. Filters: Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty. This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will accommodate the following filter sizes depending on cabinet size: Side Return(s) Bottom Return Cabinet Width (in.) Nominal Filter Size (in.) Approx. Flow Area 2 (in ) All 16 x 25 x 1 400 Approx. Cabinet N o m i n a l Width Filter Size Flow Area 2 (in.) (in.) (in ) 16-1/2 14 x 25 x 1 20-1/2 16 x 25 x 1 24-1/2 20 x 25 x 1 350 400 500 Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return. Cooling Airflow Requirement (CFM) Cooling Airflow Requirement (CFM) 800 1000 1200 1400 1600 2000 070__35 564* 564* 564* GUSA___BX__ Model (Input__Airflow) 672 --- --- 752* 752* 752* 768 --- 090__40 --- 090__50 --- --- 752* 752* 768 960 115__50 --- --- 940* 940* 940* 960 *Minimum filter area dictated by heating airflow requirement. 2 800 1000 1200 1400 1600 2000 070__35 282* 282* 282* 336 GUSA___BX__ Model (Input__Airflow) --- 376* 376* 376* 384 --- 090__40 --- --- 090__50 --- --- 376* 376* 384 480 115__50 --- --- 470* 470* 470* 480 *Minimum filter area dictated by heating airflow requirement. Disposable Minimum Filter Area (in ) Permanent Minimum Filter Area (in 2) [Based on a 300 ft/min filter face velocity] [Based on 600 ft/min filter face velocity] 10 Rev. 2 FURNACE SPECIFICATIONS MODEL GUSA070BX35 GUSA090BX40 GUSA090BX50 GUSA115BX50 Btuh Input (US) High Fire 69,000 92,000 92,000 115,000 Output (US) High Fire 65,200 87,300 86,000 109,100 Btuh Input (US) Low Fire 48,000 64,000 64,000 80,000 Output (US) Low Fire 45,200 60,000 59,800 76,100 A.F.U.E. 92.0% 92.0% 92.0% 92.0% Rated External Static (" w.c.) .10 - .50 .10 - .50 .10 - .50 .10 - .50 Temperature Rise (°F) 35 - 65 35 - 65 35 - 65 35 - 65 High Stage Pressure Switch Trip Point (" w.c.) -0.55 -0.55 -0.55 -0.55 Low Stage Pressure Switch Trip Point (" w.c.) -0.20 -0.20 -0.20 -0.20 Front Cover Pressure Switch Trip Point (" w.c) -0.37 -0.37 -0.37 -0.37 Blower Wheel (D" x W") 11 x 7 11 x 9 11 x 10 11 x 10 1/2 1/2 3/4 1/2 Blower Horsepower Blower Speeds 4 4 4 4 1407 1544 2017 1976 115-60-1 115-60-1 115-60-1 115-60-1 Minimum Circuit Ampacity (MCA) 8.7 6.4 11.1 9.8 Maximum Overcurrent Device 15.0 15.0 15.0 15.0 Transformer (VA) 40 40 40 40 Heat Anticipator (Amps) 0.7 0.7 0.7 0.7 Primary Limit Setting (°F) 155 150 150 150 Auxiliary Limit Setting (°F) 150 150 150 150 Rollout Limit Setting (°F) 200 190 220 220 30 secs. 30 secs. 30 secs. 30 secs. 90 secs. 90 secs. 90 secs. 90 secs. 5 sec. 5 sec. 5 sec. 5 sec. 45 secs. 45 secs. 45 secs. 45 secs. 7 /11 7 / 11 7 / 11 7 / 11 3.5 / 10 3.5 / 10 3.5 / 10 3.5 / 10 #43 / #55 #43 / #55 #43 / #55 #43 / #55 Number of Burners 3 4 4 5 Vent Connector Diameter (inches) 2 2 2 2 Combustion Air Connector Diameter (inches) 2 2 2 2 145 167 175 188 Max CFM @ 0.5 E.S.P. Power Supply Fan Delay On Heating Off Heating * Fan Delay On Cooling Off Cooling Gas Supply Pressure (Natural/Propane) (" w.c.) Manifold Pressure (Natural/Propane) (" w.c.) Orifice Size (Natural/Propane) Shipping Weight (lbs.) * Off Heating - This fan delay timing is adjustable (60, 90, 120 or 180 seconds), 90 seconds as shipped. 1. These furnaces are manufactured for natural gas operation. Optional kits are available for conversion to propane operation. 2. For elevations above 2000 feet the rating should be reduced by 4% for each 1000 feet above sea level. The furnace must not be derated, orifice changes should only be made if necessary for altitude. 3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufacturers method or in accordance with the "A.S.H.R.A.E. GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total heat loss calculated should be equal to or less than the heating capacity. Output based on D.O.E. test procedures, steady state efficiency times output. 4. Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps. 11 Rev. 2 BLOWER PERFORMANCE SPECIFICATIONS GUSA***BX** Blower Performance (CFM & Temperature Rise vs. External Static Pressure) External Static Pressure, (Inches Water Column) Tons AC at 0.5" ESP CFM Low Fire Rise High Fire Rise CFM Low Fire Rise High Fire Rise CFM Low Fire Rise HIGH 3.5 1621 --- 37 1572 --- 38 1521 --- 39 1469 MED 3.0 1402 --- 42 1366 --- 43 1329 --- 45 1290 MED-LOW 2.5 1144 36 52 1122 37 53 1086 38 55 LOW 2.0 868 48 --- 831 50 --- 805 51 --- Model ( Heating Speed As Shipped ) GUSA070BX35 ( ) HIGH FIRE: MED-LO LOW FIRE: LOW 0.3 0.4 High Low Fire CFM Fire Rise Rise 0.5 0.6 0.7 0.8 High Fire Rise CFM Low Fire Rise --- 40 1407 --- 42 1343 1276 1205 --- 46 1243 --- 48 1185 1133 1060 1063 39 56 1024 40 58 981 940 875 782 53 --- 745 55 --- 703 667 619 High Fire CFM CFM CFM Rise 4.0 1821 30 44 1768 31 45 1699 32 47 1624 34 49 1544 36 51 1439 1354 1227 3.5 1624 34 49 1561 35 51 1520 36 52 1461 38 54 1381 40 57 1297 1217 1109 HIGH FIRE: MED MED-LOW 3.0 1395 40 57 1363 40 58 1311 42 60 1258 44 63 1201 46 --- 1120 1045 957 LOW FIRE: LOW LOW 2.5 1212 45 65 1164 47 --- 1126 49 --- 1080 51 --- 1014 54 --- 957 815 HIGH 5.0 2090 --- 38 2076 --- 38 2061 --- 38 2054 --- 39 2017 --- 39 1963 1901 1820 1523 1473 1410 ) ) HIGH FIRE: MED-LO LOW FIRE: LOW GUSA115BX50 ( 0.2 HIGH GUSA090BX50 ( 0.1 MED GUSA090BX40 ( Motor Speed 882 MED 4.5 1615 --- 49 1610 --- 49 1600 --- 50 1591 --- 50 1562 35 51 MED-LOW 3.5 1367 40 58 1367 40 58 1356 41 58 1351 41 59 1345 41 59 1298 1252 1177 LOW 3.0 1191 46 --- 1182 47 --- 1166 47 --- 1141 48 --- 1115 49 --- 1061 1014 HIGH 5.0 2181 --- 45 2117 --- 47 2073 --- 48 2021 --- 49 1976 --- 50 1913 1831 1746 965 MED 4.5 1693 41 58 1666 41 59 1647 42 60 1600 43 62 1562 44 63 1522 1471 1408 HIGH FIRE: MED MED-LOW 3.5 1489 46 --- 1454 47 --- 1428 48 --- 1397 49 --- 1365 50 --- 1328 1270 1214 LOW FIRE: LOW LOW 3.0 1299 53 --- 1275 54 --- 1250 55 --- 1224 56 --- 1188 58 --- 1161 1105 1059 ) 1. Blower speeds for each firing rate are set independently of each other. 2. CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart assumes both filters are installed. 3. All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed. 4. For most jobs, about 400 CFM per ton when cooling is desirable. 5. INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE. 6. The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded area indicates ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for air conditioning purposes only. 7 The dashed (---) areas indicate a temperature rise not recommended for this model. 8. The above chart is for U.S. furnaces installed at 0-4000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise at a particular CFM, while the ESP at that CFM will be lower. 12 Rev. 2 TEMPERATURE RISE 10 20 30 40 50 60 70 30 80 90 100 40 50 60 700 600 CFM 90 100 2000 2200 2400 CFM 1800 1600 1400 OUTPUT BTU/HR x 1000 80 1200 1100 1000 900 70 800 FORMULAS 110 120 130 140 BTU OUTPUT = CFM x 1.08 x RISE BTU OUTPUT RISE = ÷ CFM 1.08 BTU OUTPUT vs TEMPERATURE RISE CHART 150 BLOWER PERFORMANCE SPECIFICATIONS 13 Rev. 2 WIRING DIAGRAMS HI VT-25 RD-2 WH-33 3 C 2 TWO STAGE GAS VALVE C PM 1 FLAME SENSOR GY -12 GY-47 NO NO LOW FIRE PRESS. SWITCH BU-12 OR-15 BU-36 PK -17 L AUTO RESET PRIMARY LIMIT CONTROL VT-28 VT-25 1 JUNCTION BOX GN 2 GND LINE-H LINE-N EAC-H HI HEAT-H VT-28 BLOWER COMPARTMENT PK-30 11 12 7 8 9 4 5 6 BU-12 GY-12 2 COOL-H IND HI HUM-H GY-8 BU-36 IGN-N HOT SURFACE IGNITER FP (3) VT-25 YL-20 HUM-N IGN-H OR-15 3 IND-N ID BLWR IND LO HUMIDIFIER BR-13 1 CIR-N CIRCULATOR BLWR PK-30 10 INTEGRATED CONTROL MODULE TWIN/ DEHUM W2 W1 R B/C G Y YLO O RD-2 WH-33 BK-3 RD-15 WH-7 BR-13 24 V THERMOSTAT CONNECTIONS 24 V 3A LO HEAT -H INTEGRATED CONTROL MODULE PK-30 VT-28 YL-20 MANUAL RESET AUXILIARY LIMIT CONTROL EAC-N ELECTRONIC AIR CLEANER BURNER COMPARTMENT FUSE N DISCONNECT INDUCED DRAFT BLOWER WH RD BK GND WARNING: DISCONNECT POWER BEFORE SERVICING. WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED. CHASSIS GROUND RD -18 MANUAL RESET ROLLOUT LIMIT CONTROLS 3 WARNING:DISCONNECT POWER BEFORE SERVICING.WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED. TO 115VAC/ 1Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE C FRONT COVER PRESSURE SWITCH BU -27 JUCTION BOX BR-13 FLAME SENSOR 115 VAC XFMR-H GN XFMR-N OR-10 VT-28 T-STAT SELECTOR 2 HEAT OFF DELAY DIP SWITCHES PK-30 RD-2 BK-3 2 3 5 DIAGNOSTIC LED 4 OR10 GY -8 3 24 VAC 115 VAC BK-31 LINE XFMR EAC CIRC HUM HUM XFMR LINE PARK COOL EAC HI HEAT LO HEAT HOT HLO (11) W1 40 VA TRANSFORMER 24V THERMOSTAT CONNECTIONS 4 WH-33 NEUTRAL WH-32 BK-4 WH WH-5 WH-33 CIRCULATOR BLOWER 3 4 4 FLASHES = THERMAL PROTECTIVE DEVICE OPEN 6 6 FLASHES = 115 VOLT AC POWER REVERSED 7 FLASHES = LOW FLAME SENSE SIGNAL 1 2 7 9 8 FLASHES = CHECK IGNITER OR IMPROPER GROUNDING 9 FLASHES = HIGH FIRE PRESSURE SWITCH STUCK OPEN C CONTINUOUS FLASHES = UNANTICIPATED FLAME PRESENT 8 COLOR CODES: YL YELLOW OR ORANGE VT VIOLET GN GREEN BK BLACK PK BR WH BU GY RD PINK BROWN WHITE BLUE GRAY RED 20339801 REV.00 PS1 (12) C NO FRONT COVER PRESSURE SWITCH C MVL(7) LOW FIRE PRESSURE SWITCH NO PM C 5 PS2 (2) BLOWER COMPARTMENT DOOR SWITCH (OPEN WHEN DOOR OPEN) STEADY ON = REPLACE CONTROL 1 FLASH = SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED) 2 FLASHES = LOW FIRE PRESSURE SWITCH STUCK CLOSED 3 FLASHES = LOW FIRE PRESSURE SWITCH STUCK OPEN 0 TO MICRO G MVH (1) NO HI C BK-4 CHASSIS GROUND Y BK-1 RD (LOW) W2 7 BU (MED) OR (MED-LO) MANUAL RESET ROLLOUT LIMIT CONTROL(S) HL1 (6) 6 BK (HI) CAPACITOR AUTO RESET PRIMARY LIMIT MANUAL RESETCONTROL AUXILIARY LIMIT CONTROL 24 VAC FUSE 3 A 9 CIRCUIT CONNECTOR RD-15 WH-7 TWO-STAGE INTEGRATED CONTROL MODULE 5 CIRCUIT CONNNECTOR 1 TH (5) R 1 40 VA TRANSFORMER MVC (8) HIGH FIRE PRESSURE SWITCH GND (10) TR (9) GND C GAS VALVE INTEGRATED CONTROL MODULE LOW VOLTAGE (24V) LOW VOLTAGE FIELD HI VOLTAGE (115V) EQUIPMENT GND FIELD GND FIELD SPLICE HI VOLTAGE FIELD SWITCH (TEMP.) JUNCTION TERMINAL INTERNAL TO INTEGRATED CONTROL PLUG CONNECTION IGNITER SWITCH (PRESS.) OVERCURRENT PROT. DEVICE NOTES: 1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS. 2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY. 4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES. GUSA___BX__ (Manufacturing Numbers P1239502-06F and P1242002-06F) 14 Rev. 2 TO AVOID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCONNECT THE POWER BEFORE SERVICING. 1 C NO OR-22 2 CIRCUIT CONNECTOR YL-20 2 HIGH FIRE PRESS. SWITCH ! WARNING HOT SURFACE IGNITER TO 115VAC/ 1Ø / 60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE ID BLOWER TWO-STAGE PRESSURE SWITCH ASSEMBLY WIRING DIAGRAMS ID BLOWER TWO-STAGE PRESSURE SWITCH ASSEMBLY NO OR-22 2 CIRCUIT CONNECTOR HI RD-2 WH-33 C TWO STAGE GAS VALVE 3 VT-25 2 BR-13 C PM 1 NO N DISCONNECT FLAME SENSOR GY -12 GY-47 GND WARNING: DISCONNECT POWER BEFORE SERVICING. WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED. C YL-20 1 L HIGH FIRE PRESS. SWITCH HOT SURFACE IGNITER 2 TO 115VAC/ 1Ø /60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE C NO OR-15 1 BK GN WH RD HI HEAT-H INDUCED DRAFT BLOWER VT-25 2 GND BURNER COMPARTMENT LO HEAT -H INDOOR AIR CIRCULATOR BLWR CIR-N COOL-H IND HI IND-N ID BLWR IND LO HUM-N HUM-H HUMIDIFIER VT-28 BLOWER COMPARTMENT EAC-N ELECTRONIC AIR CLEANER IGN-N IGN-H PK-30 TWIN/ DEHUM W2 R W1 G FLAME SENSOR PK-30 10 11 12 7 8 9 4 5 6 GY-8 OR-15 2 BU-36 3 VT-25 YL-20 GN OR-10 VT-28 T-STAT SELECTOR HEAT OFF DELAY DIP SWITCHES PK-30 1 BK-3 2 3 WH-7 4 WH-33 5 DIAGNOSTIC LED 4 GY -8 OR10 24 VAC 115 VAC BK-31 LINE XFMR EAC CIRC HUM HUM XFMR LINE PARK COOL EAC HI HEAT LO HEAT HOT 3 9 CIRCUIT CONNECTOR RD-15 5 CIRCUIT CONNNECTOR RD-2 2 1 40 VA TRANSFORMER HLO (11) W1 24V THERMOSTAT CONNECTIONS 1 AUTO RESET 24 VAC PRIMARY LIMIT MANUAL RESETCONTROL AUXILIARY LIMIT CONTROL FUSE 3 A BR-13 MANUAL RESET ROLLOUT LIMIT CONTROL(S) HL1 (6) W2 TO MICRO Y PS1 (12) G WH-32 LOW FIRE PRESSURE SWITCH NO MVL(7) C PM C MVH (1) NO HI C PS2 (2) MVC (8) HIGH FIRE PRESSURE SWITCH GND (10) C GAS VALVE GND TR (9) INTEGRATED CONTROL MODULE WH WH-5 CIRCULATOR BLOWER C NO FRONT COVER PRESSURE SWITCH NEUTRAL BK-4 XFMR-N 40 VA TRANSFORMER TH (5) R BU-12 GY-12 115 VAC XFMR-H PK-30 RD-2 WH-33 BK-3 RD-15 B/C Y YLO O WH-7 24 V 3A TWO-STAGE INTEGRATED CONTROL MODULE FP (3) BR-13 24 V THERMOSTAT CONNECTIONS HOT SURFACE IGNITER VT-28 YL-20 MANUAL RESET AUXILIARY LIMIT CONTROL FUSE INTEGRATED CONTROL MODULE 3 VT-28 LINE-N EAC-H INTEGRATED CONTROL MODULE AUTO RESET PRIMARY LIMIT CONTROL BU-36 PK -17 BU-12 BU -27 JUNCTION BOX WITH BLOWER COMPARTMENT DOOR SWITCH LINE-H LOW FIRE PRESS. SWITCH WH-33 WARNING:DISCONNECT POWER BEFORE SERVICING.WIRING TO UNIT MUST BE PROPERLY POLARIZED AND GROUNDED. WH-5 7 6 BK-4 N BU (MED) OR (MED-LO) RD (LOW) CAPACITOR STEADY ON = REPLACE CONTROL 1 1 FLASH = 2 2 FLASHES = LOW FIRE PRESSURE SWITCH STUCK CLOSED 3 3 FLASHES = LOW FIRE PRESSURE SWITCH STUCK OPEN 4 4 FLASHES = THERMAL PROTECTIVE DEVICE OPEN 6 6 FLASHES = 115 VOLT AC POWER REVERSED 7 7 FLASHES = LOW FLAME SENSE SIGNAL 8 8 FLASHES = CHECK IGNITER OR IMPROPER GROUNDING 9 9 FLASHES = HIGH FIRE PRESSURE SWITCH STUCK OPEN C CONTINUOUS FLASHES = UNANTICIPATED FLAME PRESENT PK PINK BR BROWN WH WHITE BU BLUE GY GRAY RD RED 20299701 REV.00 L DISCONNECT LOW VOLTAGE (24V) SYSTEM LOCKOUT (RETRIES/RECYCLES EXCEEDED) GND BK -1 CHASSIS GROUND 0 COLOR CODES: YL YELLOW OR ORANGE VT VIOLET GN GREEN BK BLACK JUNCTION BOX WITH BLOWER COMPARTMENT DOOR SWITCH (OPEN WHEN DOOR IS OPEN) EQUIPMENT GND LOW VOLTAGE FIELD HI VOLTAGE (115V) FIELD GND FIELD SPLICE HI VOLTAGE FIELD SWITCH (TEMP.) JUNCTION TERMINAL INTERNAL TO INTEGRATED CONTROL PLUG CONNECTION TO 115 VAC/ 1Ø / 60 HZ POWER SUPPLY WITH OVERCURRENT PROTECTION DEVICE 5 BK (HI) TO AVOID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCONNECT THE POWER BEFORE SERVICING. MANUAL RESET ROLLOUT LIMIT CONTROLS CHASSIS GROUND RD -18 IGNITER SWITCH (PRESS.) OVERCURRENT PROT. DEVICE NOTES: 1. SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0.7 AMPS. 2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY. 4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C. AND LOCAL CODES. ! WARNING FRONT COVER PRESSURE SWITCH GUSA___BX__ (Manufacturing Numbers P1233902-06F) 15 Rev. 2 16 Rev. 2 TYPICAL SCHEMATIC GUSA___BX__ MODEL FURNACES WR 50M61-288 INTEGRATED IGNITION CONTROL This schematic is for reference only. Not all wiring is as shown above, refer to the appropriate wiring diagram for the unit being serviced. ! WARNING IGNN 1M .0005 IGN K1 C PARK K6 W8 H1 P M MV MVL COM COOL 2 STAGE GAS VALVE GND Q22 K2 HIGH HEAT HLO HIGH LIMIT PS1 2ND STAGE PRESSURE SWITCH PS2 CIRC. NEU EAC NEU 1ST STAGE PRESSURE SWITCH ROLLOUT SWITCH EAC ELECTRONIC AIR CLEANER TO AVOID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DISCONNECT THE POWER BEFORE SERVICING. IGNITOR FP FLAME SENSOR PROBE LINE NEU 120 VAC LINE HOT K7 LOW HEAT CIRCULATOR BLOWER K3 IND HI AUX LIMIT K8a IND LO HLI HUMIDIFIER MVH K8b IND NEU HUM INDUCER FUSE HUMN Y G W2 W1 B/C TR XFMRN XFMR TH R Y G W2 W1 R THERMOSTAT 24 V.A.C. SCHEMATICS