Download Agilent Technologies 6834B User`s guide

Transcript
3 - Language Dictionary
INSTrument:NSELect
INSTrument:SELect
Agilent 6834B Only
These commands allow the selection of individual outputs in a three-phase model for subsequent
commands or queries. Their operation is dependent on the setting of INSTrument:COUPle. If INST:COUP
NONE is programmed, then the phase selectable commands are sent only to the particular output phase
set by INSTrument:NSELect. If INST:COUP ALL is programmed, then all commands are sent to all three
output phases.
INSTrument:NSELect selects the phase by its number, while INSTrument:SELect references it by name.
These commands also select which output phase returns data when a query is sent.
Command Syntax
Parameters
*RST Value
Examples
Query Syntax
Returned Parameters
Related Commands
36
INSTrument:NSELect <NR1>
INSTrument:SELect <output>
For INST:NSEL 1 | 2 | 3
For INST:SEL OUTPut1 | OUTPut2 | OUTPut3
1 or OUTPut1
INST:NSEL 3
INST:SEL OUTP1
INSTrument:NSELect?
<NR1>
INST:COUP