Download Agilent Technologies 6834B User`s guide

Transcript
3 - Language Dictionary
OUTPut:PON:STATe
This command selects the power-on state of the ac source. The following states can be selected:
RST
RCL0
Sets the power-on state to *RST. Refer to the *RST command as described later in this
chapter for more information.
Sets the power-on state to *RCL 0. Refer to the *RCL command as described later in this
chapter for more information.
Command Syntax
Parameters
Examples
Query Syntax
Returned Parameters
Related Commands
OUTPut:PON:STATe <state>
RST | RCL0
OUTP:PON:STAT RST
OUTPut:PON:STATe?
<CRD>
*RST *RCL
OUTPut:PROTection:CLEar
This command clears the latch that disables the output when an overvoltage (OV), overcurrent (OC),
overtemperature (OT), remote inhibit (RI), or power rail fault condition is detected. All conditions that
generated the fault must be removed before the latch can be cleared. The output is then restored to the
state it was in before the fault condition occurred.
Command Syntax
Parameters
Examples
Related Commands
OUTPut:PROTection:CLEar
None
OUTP:PROT:CLE
OUTP:PROT:DEL *SAV *RCL
OUTPut:PROTection:DELay
This command sets the delay time between the programming of an output change that produces a CL or
UNREG status condition and the recording of that condition by the Questionable Status Condition register.
The delay prevents momentary changes in status that can occur during programming from being
registered as events by the status subsystem. In most cases these temporary conditions are not
considered an event, and to record them as such would be a nuisance.
Command Syntax
Parameters
Unit
*RST Value
Examples
Query Syntax
Returned Parameters
Related Commands
58
OUTPut:PROTection:DELay <NRf+>
0 to 100 | MAXimum | MINimum
S seconds)
100 milliseconds
OUTP:PROT:DEL 75E-1
OUTPut:PROTection:DELay?
<NR3>
OUTP:PROT:CLE *SAV *RCL