Series Rating Method
An alterative to the full rating method is the series rating
method, which requires that the main upstream circuit
protection device must have an interrupting rating equal to
or greater than the available fault current of the system, but
subsequent downstream circuit protection devices connected
in series can be rated at lower values.
For example, a building with 42,000 A of available fault
current might have a breaker at the service entrance with an
interruption rating of 42,000 A and additional downstream
breakers rated at a lower level, but “sufficient for the current
that must be interrupted,” 18,000 A in this example.
Main Breaker
Interrupting Rating = 42,000 A
Branch Breakers
Interrupting Rating = 18,000 A
Series Connected
Short Circuit Rating
The series rating method is used when the selected series
combination of circuit protection devices has been tested and
certified by UL. Each series combination of circuit protection
devices has a series connected short circuit rating. For
additional information, refer to the Series Connected Short
Circuit Ratings tables in the SPEEDFAX catalog.
Review 5
1.
A ________ is a condition in which current
unintentionally flows to ground.
2. NEC® Article 110.9 requires circuit protection
equipment to have an ________ rating sufficient for the
circuit voltage and available current.
3. The ________ rating method requires selecting circuit
protection devices with individual interrupting ratings
equal to or greater than the available fault current.
4. Series connected circuit breaker combinations must be
tested and certified by ________.