Appendix B
Parameter Information
Table 131 - Parameter 19…42
Number
Name
Units
19
Time to OL Trip
Secs
20
Time to OL
Reset
21
Min./Max.
[Default]
Read/Write
Access
Enum Text
Description
0/1000
[0]
NA
Displays the estimated time before an overload trip will occur if the present
operating conditions persist. If operating below ultimate trip current the value will
display the max value.
R
Secs
0/1000
[0]
NA
Displays the estimated time until the motor overload fault can be reset. The MTU
reset level is set by the OL reset parameter (80).
R
Time to PM
Hrs
0/1000
[0]
NA
Displays the estimated time to a preventive maintenance event if enabled. The
scheduled time for a PM event is set by the user via the PM Hours parameter
(126).This value can be reset by the user after an event via the meter reset parameter
(16).
R
22
Starts to PM
—
0/50000
[0]
NA
Displays the estimated number of starts to a PM event if enabled. The scheduled
number of starts for a PM event is set by the user via the PM Starts parameter
(127).This value can be reset by the user after an event via the meter reset parameter
(16).
R
23
Total Starts
—
0/30000
[0]
NA
Displays the total number of SMC starts. The SMC keeps a Start Counter which will
be incremented each time the SMC is started. This parameter cannot be reset by the
customer and leaves the factory with a value of 0.
R
24
1
25
2
26
Start Time
3
Displays the measured start time of the previous start.
Displays the measured start time of the 2nd previous start.
Secs
0/1000
[0]
NA
Displays the measured start time of the 3rd previous start.
27
4
28
5
Displays the measured start time of the 5th previous start.
29
1
Displays the measured peak current of the previous start.
30
31
Peak
Current
32
4
33
5
34
Motor Speed
Displays the measured start time of the 4th previous start.
2
3
Amps
0/150000
[0]
Displays the measured peak current of the 2nd previous start.
NA
Displays the measured peak current of the 3rd previous start.
R
Displays the measured peak current of the 4th previous start.
Displays the measured peak current of the 5th previous start.
%
0/100
[0]
NA
Displays the estimated motor speed during starting and stopping. This parameter is
only valid when using the linear speed starting or linear speed stopping modes.
35
THD ➊ Va
Measures the THD of the applied Phase A line voltage.
36
THD Vb
Measures the THD of the applied Phase B line voltage.
37
THD Vc
38
THD Vave
39
THD ➊ Ia
40
THD Ib
41
THD Ic
42
THD Iave
%
0/1000.0
[0]
NA
Measures the THD of the applied Phase C line voltage.
R
R
Displays the calculated average of the three voltage THD measurements.
Measures the THD of the applied Phase A current.
%
0/1000.0
[0]
NA
Measures the THD of the applied Phase B current.
Measures the THD of the applied Phase C current.
Displays the calculated average of the three current THD measurements.
➊ THD = A Power Quality measurement that provides the ability to measure total harmonic distortion levels.
254
R
Rockwell Automation Publication 150-UM011C-EN-P - March 2014
R