Download SMC-50 Smart Motor Controller
Transcript
Appendix B Parameter Information Table 131 - Parameter 19…42 Number Name Units 19 Time to OL Trip Secs 20 Time to OL Reset 21 Min./Max. [Default] Read/Write Access Enum Text Description 0/1000 [0] NA Displays the estimated time before an overload trip will occur if the present operating conditions persist. If operating below ultimate trip current the value will display the max value. R Secs 0/1000 [0] NA Displays the estimated time until the motor overload fault can be reset. The MTU reset level is set by the OL reset parameter (80). R Time to PM Hrs 0/1000 [0] NA Displays the estimated time to a preventive maintenance event if enabled. The scheduled time for a PM event is set by the user via the PM Hours parameter (126).This value can be reset by the user after an event via the meter reset parameter (16). R 22 Starts to PM — 0/50000 [0] NA Displays the estimated number of starts to a PM event if enabled. The scheduled number of starts for a PM event is set by the user via the PM Starts parameter (127).This value can be reset by the user after an event via the meter reset parameter (16). R 23 Total Starts — 0/30000 [0] NA Displays the total number of SMC starts. The SMC keeps a Start Counter which will be incremented each time the SMC is started. This parameter cannot be reset by the customer and leaves the factory with a value of 0. R 24 1 25 2 26 Start Time 3 Displays the measured start time of the previous start. Displays the measured start time of the 2nd previous start. Secs 0/1000 [0] NA Displays the measured start time of the 3rd previous start. 27 4 28 5 Displays the measured start time of the 5th previous start. 29 1 Displays the measured peak current of the previous start. 30 31 Peak Current 32 4 33 5 34 Motor Speed Displays the measured start time of the 4th previous start. 2 3 Amps 0/150000 [0] Displays the measured peak current of the 2nd previous start. NA Displays the measured peak current of the 3rd previous start. R Displays the measured peak current of the 4th previous start. Displays the measured peak current of the 5th previous start. % 0/100 [0] NA Displays the estimated motor speed during starting and stopping. This parameter is only valid when using the linear speed starting or linear speed stopping modes. 35 THD ➊ Va Measures the THD of the applied Phase A line voltage. 36 THD Vb Measures the THD of the applied Phase B line voltage. 37 THD Vc 38 THD Vave 39 THD ➊ Ia 40 THD Ib 41 THD Ic 42 THD Iave % 0/1000.0 [0] NA Measures the THD of the applied Phase C line voltage. R R Displays the calculated average of the three voltage THD measurements. Measures the THD of the applied Phase A current. % 0/1000.0 [0] NA Measures the THD of the applied Phase B current. Measures the THD of the applied Phase C current. Displays the calculated average of the three current THD measurements. ➊ THD = A Power Quality measurement that provides the ability to measure total harmonic distortion levels. 254 R Rockwell Automation Publication 150-UM011C-EN-P - March 2014 R