Download Panasonic KW Series Eco Power Meters

Transcript
Compact Power Meter
Eco-POWER METER
KW SERIES
Conforming to EMC Directive
(Excluding KW1M-R)
Recognition
(KW4M only)
Certified
(Some models only)
Get In-depth Support for Saving Energy
by Visualizing Each Power Consumption
Inverter air-conditioning
power consumption
visualization
STO
RE
Refrigerating power
consumption and temperature*
visualization
* When analog input is used
NEW
NEW
Lighting power
consumption and illumination*
visualization
KW2G
Eco-POWER METER
Standard type
KW2G-H
Eco-POWER METER
SD memory card type
KW2G / KW2G-H
* When analog input is used
Eco-POWER METER
Expansion unit (Power measurement and Pulse output)
IP66
KW1M
Eco-POWER METER
Standard type
KW1M-H
Eco-POWER METER
SD memory card type
(Master unit)
(Slave unit)
KW1M-R
Eco-POWER METER
Built-in wireless type
KW7M
Eco-POWER METER
DIN rail
KW4M
Eco-POWER METER
DIN□48
KW8M
Eco-POWER METER
DIN48×96
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Visualizing energy consumption is
the first step toward energy savings.
Install Eco-POWER METERs in lighting equipment, air conditioners, and production equipment to measure power
consumption and check the current status. Then, with specific targets in place, the implementation and management of
an energy savings plan is quick and simple. Visualizing target achievments improves the energy usage cycle and allows
for changes to be made to maximize efficiency.
Inverter air-conditioning
power consumption
visualization
Refrigerating power
consumption and temperature*
STO
RE
visualization
* When analog input is used
Lighting power
consumption and illumination*
visualization
BEFORE
* When analog input is used
AFTER
1
Measurement
2
Use condition
analysis
Energy saving
cycle
4
Implementation
and management
of an energy
saving plan
3
Energy saving
target setting
3 year warranty
Factory Automation
Devices Products
Market Trend
Company direction
To reduce the usage of earth's resources,
Pursue and supply high quality standard
demand for a longer product lifecycle increases.
products which can be safely used in long term.
* Please refer to our website for warranted products and extent of 3 year warranty.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Steps
KW SERIES
TYPICAL APPLICATIONS
S
Schools and
supermarkets,
etc.
Small retailers
e.g. convenience
stores
STORE
Convenience stores
Lighting
100 V
CT
CT
CT
CT
CT
RS485
KW8M
DLL or
DLU
3F
CT
Air-conditioning
CT
Air-conditioning
Lighting
Plants
Schools and supermarkets
Display cases
for freezers
and refrigerator
200 V
Plants with
large equipment
CT
RS485
KW2G
KW1M-R
KW1M-R
RS232C
CT
Manufacturing
equipment
DLL or
DLU
RS485
KW2G
KW2G
CT
CT
2F
CT
CT
Lighting
KW4M
KW7M
RS485
KW2G
CT
CT
CT
KW1M
LAN
CT
LAN
DLL or DLU
CT
CT
RS485
DLL or
DLU
PC
1F
RS485 KW2G
RS232C
KW2G
RS232C
CT
KW1M-R
LAN
PC
You can add only the
required number of units in
a small switchboard. Ideal
for small stores.
Connector-expandable
type
KW2G
Eco-POWER METER
Display cases
for freezers
and refrigerator
DLL or
DLU
Wiring work not required.
Ideal if the layout is
frequently changed.
(Master unit)
Built-in wireless type
KW1M-R
Eco-POWER METER
PC
Mountable on a panel surface.
Applicable to 400 V equipment.
Panel surface mount type
KW8M Eco-POWER METER
Mountable on a panel.
Waterproof (IP66).
Waterproof type
(Slave unit)
KW4M Eco-POWER METER
You can add only the
required number of units,
preventing waste.
Designed for DIN rail mounting,
ideal for installation in a panel.
Panel-mount DIN rail type
Connector-expandable
type
KW7M Eco-POWER METER
KW2G
Eco-POWER METER
Expandable for large equipment
with multiple power supplies.
Connector-expandable type
KW2G Eco-POWER METER
Easy when you want small-scale visualization or for trial runs
Easy to measure. You can
immediately check data on a PC.
Easily measure multiple circuits, immediately view
results on a PC screen.
SD memory card type
SD memory card type
KW1M-H Eco-POWER METER
KW2G-H Eco-POWER METER
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Selection Guide
KW SERIES
Eco-POWER METER SELECTION GUIDE
Needs
■ Need to measure power of general-
purpose CT installed at facility
■ Need to measure high current circuits
■ Need to measure multiple points
■ Need to measure micro-power such as
standby power
■ Need to measure existing equipment
without line stoppage
■ Need to load analog data or pulse data
Recommended model
KW8M 1 A / 5 A CT input type
• Capable of direct input from 1 A / 5 A CT in the secondary
side and up to 4,000 A CT in the primary side without using
a dedicated CT
KW2G Series
• Expandable, as needed, to up to 7 expansion units.
• Able to measure micro-power.
• Simple measurement function enables measuring CT power only.
• The environmental conditions and power can be monitored
by using expansion units. (Analog input and pulse input types)
■ Need to simply visualize data on
Eco-POWER METER
■ Need to reduce initial costs
■ Need to use the Eco-POWER METER for trials
■ Need alternative cable communications
(RS485 and LAN)
■ Need to measure three-phase four-wire
systems
■ Need to collect data wirelessly
■ Need to reduce installation costs and
man-hour of data collection
■ Need to flexibly alter equipment layout
■ Need to bypass cabling difficulties
■ Need waterproofing for use of water
■ Need to monitor demand
■ Need low-cost power meter
■ Need capability to measure 200 V
three-phase three-wire system, etc.
KW1M-H / KW2G-H
• Main unit has built-in memory.
• Transfer of data to SD memory card allows visualization on
PC screens, and with the KW2G-H, no wiring needed
except for operating power supply.
KW1M Series (except AKW1110)
and KW8M Series
• Direct measurement even of three-phase, four-wire 400 V AC
system can be done without VT.
KW1M-R
• Installation costs reduced because no wires are needed for communications.
• Auto routing system for easy wireless set up
• RS485 connection enables other Eco-POWER METERs
to be ready for wireless communications.
KW4M
• IEC IP66 certified protective structure
KW1M-H /
KW8M High performance type
• Built-in simple demand function
• Alarm outputs when demand target value is exceeded.
* Demand function of Eco-POWER METER is that of Japanese specifications.
KW1M (AKW1110), KW4M
and KW7M
• Space-saving design at a reasonable price achieve
visualization.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
USEFUL FUNCTIONS
1 A / 5 A CT input type
When you want to use a general-purpose CT
Without using a dedicated CT, direct input from up to 4,000 A CT
in the primary side, 1 A or 5A CT in the secondary side is possible.
KW8M
1 A / 5 A CT input type
You can measure with a direct connection to an already-installed large-capacity general-purpose CT.
Other Eco-POWER METER Series
KW8M 1 A / 5 A CT input type
When taking dedicated CT measurements of more than 600 A
When taking large-capacity general-purpose CT measurements of more than 600 A
Breaker
Breaker
Power source
K Secondary side current
Power source
Short circuit or less than
0.1 Ω resistance
CT (Secondary side current: 5 A)
K Secondary side current
AKW4801C
CT (Secondary side current: 1 A / 5 A)
L
L
L
Production
equipment
K
K
CT
is not
required.
L
AKW8115
Production
equipment
AKW8111
Eco-POWER METER Series accuracy does not include CT error. For dedicated CT measurements of more than 600 A, two CTs are necessary, but since
the 1 A / 5 A CT input type KW8M, direct input from a single CT is possible, and you can carry out measurement with higher accuracy than provided by
other Eco-POWER METER Series models.
For measurements of less than 600 A, measurement from a single CT, whether dedicated or general-purpose, is possible.
Inverter (primary side) measurement function
For measurement of inverter power supply
equipment introduced for saving energy
Owing to general susceptibility to high frequency interference, it is said to
be difficult to accurately measure power supplied by inverters.
Entire Eco-POWER METER Series
*Only Eco-POWER METERs with power
measurement function
Our customers expressed strong demand for a line-up of Eco-POWER METERs that would enable measurement
of inverter power supplies (primary side).
Ideal for measuring inverter power for large equipment, lighting, etc.
Compressor
Molding machine
Application example
Lighting
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
USEFUL FUNCTIONS
Unit expansion possible function
Up to 8 units! expandable to suit conditions of
use without waste!
No.1
No.2
Main unit
(
No.3
Expansion
Expansion
unit
unit
Power
Power
measurement measurement
and
Pulse output
)
(
No.4
)
Expansion
unit
(Pulse input)
No.5
No.6
Expansion
unit
(Analog input)
No.7
You can get pulse output from each measurement circuit
No.8
Application example
Expansion unit (AKW2160G) can be used to monitor integrated electric power value according to measured power or to issue
alarms from pulse output, and can be controlled by PLC or other host system.
Using pulse output it is easy to connect to other companies’ equipment with pulse input functions.
Pulse output
Pulse input equipment
Pulse output
Air-conditioning
such as PLC, etc.
Display cases for
freezers and refrigerator
Alarm output can be used to
trigger warning light flashes.
Main unit
CT
CT
Power
measurement
Power measurement
Expansion unit
Power measurement
and Pulse output
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
Easy wire-saving expandability brings diversity of measurement
KW2G
KW2G-H
Eliminate excess wiring by using up to seven expansion units to add-on the required
number of CT inputs for your application.
8 units in total
Connector for easy expansion!
Up to 7 expansion units can be added
Main unit
Expansion unit
Wiresaving
Up to
16 circuits
(
Wiresaving!
Power supply
Space
saving
)
Single-phase
two-wire
system
Measurement data
CT CT
CT CT
CT CT
CT CT
CT CT
CT CT
CT CT
CT CT
Maxi- 16 circuits (single-phase two-wire system)
mum 8 circuits (single-phase three-wire system
and three-phase three-wire system)
Connectable to various sensors as well as electric power
Application example
Air/water consumption, temperature, humidity, illumination and other environmental conditions along with power can be
monitored by using expansion units for pulse/analog input.
■ Power measurement
• Main unit (AKW2010G)
• Main unit (AKW2020G)
• Expansion unit (AKW2110G)
• Expansion unit (AKW2160G)
■ Pulse input
■ Analog input
• Main unit (AKW2010G) = one input
• Expansion unit (AKW2182G) = two inputs
• Main unit (AKW2020G) = one input
• Expansion unit (AKW2152G) = two inputs
Air Flow
Monitor
EWA1
Office area
Light
sensor
Air Flow
Monitor
EWA1
Factory area
28°C
Thermometer
Motion
sensor
28°C
Distribution board Motion sensor × 2
Power measurement:
1 point
Pulse input:
2 points
Temperature × 1
Illumination × 1
Analog input:
2 points
Air Flow Monitor
EWA1
Compressor × 2
Power measurement:
2 points
Integrated flow data × 2 Instantaneous flow data × 2
Pulse input:
2 points
Analog input:
2 points
Main unit
Main unit
Expansion unit
Expansion unit
Pulse input
Analog input
Power
measurement
Pulse input
Analog input
USEFUL FUNCTIONS
SD memory card function
Easy to implement, visualization of energy
usage made easy!
KW1M-H
KW2G-H
Measurement data is automatically saved to an SD
memory card.
Data collection is possible without a network.
• Data can be saved at intervals of 1, 5, 10, 15, 30, or 60 minutes.
• Previous power usage is displayed on screen (For KW1M-H: up to 1.5 years worth, for
KW2G-H: up to 8 days worth).
• Lithium battery backup eliminates worries during power outage.
• Data is stored to memory of main unit when an SD memory card is not inserted.
Measurement data that is saved to the SD card can be easily displayed
in graph form using the free KW View software tool.
• No complicated settings are required. Data from multiple Eco-POWER METERs
can be compared in a single graph.
• In addition to electrical power, create comparison graphs for pulse data or analog
data loaded by KW2G-H expansion unit (pulse input type and analog input type).
Ideal for switchboards or embedded devices
Application example
SD memory card compatibility enables economical implementation without the need to set up an external data loggers and a
LAN or other network connection for measuring and storing the data. Takes only a small space in an electrical switchboard or
embedded device and is ideal for small-scale measurement.
For a small space
KW1M-H
CT
KW View
For measurements at remote locations
Production equipment
Application example
Using the free KW Watcher software, you can simultaneously graph data stored in the Data logger as well as on the SD
memory card.
LAN
RS485
Analog
CT
Pulse
KW2G-H
DLL
KW1M
Air Flow Monitor
EWA1
KW Watcher
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
Wireless capability
Easy wire-saving in existing facilities
where wiring is difficult
KW1M-R
Going wireless reduces the labor and installation cost for implementation
10%
Cost of power meter
90%
Labor and installation cost
About
half!
Cost of wiring materials and labor
15%
Cost of power meter
20 to 30%
Labor and installation cost
* Based on internal research
Actual costs depend on site conditions.
Wireless auto routing allows easy communications setting via the built-in screen.
Using RS485 connection also enables wireless communications other Eco-POWER METERs besides the
KW1M-R
Master unit
Wired devices can also be
integrated into the network
Slave unit
KW8M
Automatically build a wireless network
You can connect to up to 99
MEWTOCOL devices,
247 MODBUS (RTU)
devices (incl. slave units).
RS485
Ideal for installation where wiring is difficult or where equipment layout flexibility is required Application example
DLL
Storing data
(logging)
RS485
Wirelessly surveillance
in-store electric power
KW1M-R
Eco-POWER METER
(Built-in wireless type)
Master unit
RS485
CT
Wall-mounted type
KW1M
display cases for
RS485 Eco-POWER METER freezers and refrigerator
(Standard type)
KW Watcher
CT
KW1M-R
Eco-POWER METER
(Built-in wireless type)
Slave unit
CT
RS485
LAN
In-place type display
cases for freezers
and refrigerator
CT
* Up to 99 Eco-POWER METERs can be
connected.
Remote surveillance reduces man-hour
*Please contact our sales offices for more information about which areas this product can be used.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
USEFUL FUNCTIONS
Micro-power measurement function
You can even visualize standby power
Standby power is a key to saving energy
By understanding both operating power and standby power, you can reduce
non-operational energy wastage and initiate power-saving activities that go
beyond what was formerly possible.
KW2G
KW2G-H
KW2G and KW2G-H can also measure fine currents.
When the load current declines, micro-power measurement mode is automatically activated (auto range
switching function).
Before
With
improvement
Measurement of
standby power
Wastage eliminated
Integrated
electric power
(kWh)
Integrated
electric power
(kWh)
Standby power
Operating power
Operating power
Measured load
Measured load
Simple measurement function
For existing equipment that must stay
switched on and sequential measurement
KW2G
Ideal for existing facilities where it is better not to switch off equipment and for sequential measurement
KW2G-H
Application example
No power supply wiring needed for the measuring the load! Because
connection to the CT is possible, electric power measurement can be done
without powering down the equipment.
STEP1
Phase and wire system setting (for
each unit)
STEP2
Set simple measurement mode
STEP3
Voltage and power factor setting
(common to each unit)
100 V AC
CT
STEP4
Set simple measurement mode
Power source
for main unit
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
Simple demand function
Affordable peak demand control!
Estimate power consumption peak demand and get support for power
management and cost-efficiency.
KW1M-H
KW8M
High performance type
Operation overview of simple demand control
Alarm output and display
Estimated demand
(kW)
Demand value (kW)
Demand target value
(kW)
The simple demand function averages electric
power during 30-minute periods and estimates
demand on a per-minute basis.
Present demand
(kW)
P
t
Remaining time (T - t)
t
Start
Demand period T (minute)
0 minute
15 minutes
Finish
* Not compatible with pulse input.
30 minutes Only works with CT input (power measurement).
* The demand function of Eco-POWER METER is that of Japanese specifications.
Demand control for cost-efficiency
Application example
If demand exceeds present demand or estimated demand target values, an alarm alerts the customer.
For onsite surveillance
• Light up an alarm lamp
• When demand exceeds
limit value, alarm signals
by a buzzer, graded
flashing lights, etc.
On-screen
display and more
intense flashing
Power
measurement
Switchboard
CT
Alarm output (Pulse output)
For remote surveillance
RS485
Customer
• Able to
control
power load
within
demand
target value
• ON/OFF demand status is
informed through RS485
communication
*Simple demand should be treated as a rough guide. Power-use scheduling is set by the Eco-POWER METER.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Performance
PERFORMANCE COMPARISON
Main unit
Product name
KW2G
: Available
○
— : Not available
Expansion unit
KW2G-H
KW1M
Standard type
KW2G / KW2G-H
Standard type SD memory card type Power measurement
Power measurement
and Pulse output
Pulse input Analog input
KW1M-H
SD memory
card type
Appearance
Model No.
Mounting method
Dimensions (mm inch)
(W × H × D)
DIN rail (sold separately)
Screw installation
Mounting frame (sold separately)
In panel mounting
On panel mounting
DIN
DIN
DIN
DIN
DIN
DIN
AKW2010G
AKW2020G
AKW2110G
AKW2160G
AKW2152G
AKW2182G
50×95×65
1.97×3.74×2.56
○
○
—
○
—
—
—
Phase and wire system
Input measured voltage
(Select with setting mode)
Single-phase two-wire system
Single-phase three-wire system
Three-phase three-wire system
Three-phase four-wire system
—
Communication
○
—
—
100 to 240 V AC
100/200 V AC system
○
○
○
○
○
○
—
Load measurement for
400 V AC system (Note 1)
Current transformer (CT)
—
○
Operating power supply
—
○
○
○
—
○
○
○
—
—
External voltage transformer (VT) required.
Dedicated type: 5 A, 50 A, 100 A, 250 A, 400 A and 600 A
Interface
○
○
○
○
—
—
○
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Screw
AKW1110
○
—
—
○
—
○
—
—
○
—
○
—
—
○
25×95×65
0.98×3.74×2.56
DIN
Frame
AKW1111
75×90×50
2.95×3.54×1.97
○
○
○
○
DIN
Screw
Frame
AKW1121
○
○
○
○
○[Mounting frame (sold separately) is required.]
100/200 V AC
system
○
○
○
—
External voltage
transformer (VT)
required.
100/200/400 V AC system
○
○
○
○
○
○
○
○
Transformer not required
Direct input possible
Dedicated type: 5 A, 50 A, 100 A, 250 A, 400 A
and 600 A
Conforming to RS485
Communication
protocol
MEWTOCOL/MODBUS (Selectable with setting mode)
Restrictions apply. Please check communication specifications column.
Number of connected units
99 (max.)
1 point
1 point
—
—
2 points
—
—
1 point
1 point
Number of pulse output point
1 point
1 point
—
1 point
—
—
1 point
1 point
1 point
Number of analog input point (Note 3)
—
—
—
—
—
2 points
—
—
—
—
Excess alarm output
Number of pulse input point (Note 2)
Instantaneous active electric power
Current value
Stand-by electric power
Preset value
Demand (Note 4)
○
○
○
○
—
Main unit memory function
—
External memory function
—
Calendar timer function
—
Simple measurement
Integrated electric power
Instantaneous electric power
Measuring items
Current
Voltage
Electricity charge (Note 5)
Conversion carbon dioxide value
Power factor
Frequency
Hour meter
Pulse count value
Tool and software
(free of charge)
Simultaneous power and
pulse measurement
KW Monitor
KW Watcher
KW View
KW Network monitor
Standard
○
○
○
○
○
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
○ (Active)
○
○
○
○
—
—
CE and S-MARK
—
○
○
○
○
○
—
—
○
○
○
○
—
—
—
—
—
—
—
—
—
—
—
—
—
—
○
○
○ (Active, Reactive, Apparent, Regenerative)
○ (R, N/S, and T)
○ (RS, RT, and TS)
○
○
○
○
Displayed on Displayed on
the main unit the main unit
○
○
○
○
—
○
○
—
—
—
○
○
○
○
○
○
○
—
—
—
—
—
—
—
○
○
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
CE
CE and S-MARK
—
—
○
○ (Note 6)
—
○
○
○
○
○
○
○
○
—
—
—
—
CE
CE and S-MARK
—
○ When connected to AKW2020G
—
—
○ (Active)
○ (Active)
○ (R and T)
○ (R and T)
○
○
—
Notes: 1) A VT (secondary side rated voltage: 110 V) is needed to measure loads that exceed rated input voltage.
2) Input method: contact/non-voltage contact (open collector)
3) To set input range of analog input unit using setting mode and select voltage 0 to 5 V/1 to 5 V, current 0 to 20 mA/4 to 20 mA.
4) The demand function of Eco-POWER METER is that of Japanese function.
5) Eco-POWER METER is primarily designed for managing energy saving. It is not intended to be used for billing.
6) Displayed on the main unit
—
—
—
—
—
○
○
○
○
○
○
○
○
—
○ (Active) ○ (Active)
○ (Active) ○ (Active)
○ (R, S, and T) ○ (R, S, and T)
○ (R, S, and T) ○ (RS, RT, and TS)
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
—
○
—
CE and S-MARK
—
KW SERIES
: Available
○
— : Not available
Product name
KW1M-R
Built-in wireless type (Note 1)
KW4M DIN□48
KW7M
DIN rail
MEWTOCOL
type
KW8M DIN48×96
MODBUS
type
High
performance
type
1A/5A
CT input type
Frame
Frame
AKW8111H
AKW8115
Appearance
DIN
*
Screw
DIN
Model No.
Mounting method
Dimensions (mm inch)
(W × H × D)
Master unit
Slave unit
AKW1000
AKW1131
75×90×50 2.95×3.54×1.97
(Excluding the antenna)
○
○
DIN rail (sold separately)
Screw installation
Mounting frame (sold separately)
—
On panel mounting
○
Phase and wire system
—
—
Three-phase three-wire system
—
Three-phase four-wire system
—
—
Current transformer (CT)
—
Communication
Load measurement for
400 V AC system (Note 2)
Number of connected units
AKW8111
48×96×98.5
1.89×3.78×3.88
—
○
○ [Terminal socket (sold separately) is required.]
○
—
—
100/200/400 V
AC system
—
Single-phase three-wire system
Communication
protocol
AKW5112
AKW5212
○
○
○
○
—
—
—
—
—
—
○
○
○
○
○
○
—
100 to 240 V AC
Single-phase two-wire system
Interface
Frame
○
Operating power supply
Input measured voltage
(Select with setting mode)
Screw
22.5×75×100
Screw terminal type: 48×48×81.9 1.89×1.89×3.22
0.89×2.95×3.94
11-pin type: 48×48×87.5 1.89×1.89×3.44
○
—
Frame
AKW5111
AKW5211
AKW7111
—
○
In panel mounting
DIN
*Terminal socket (sold
separately) is required.
100/200 V AC system
○
○
○
○
○
○
○
—
External voltage transformer
(VT) required.
○
○
○
○
○
○
○
○
Transformer not required.
Direct input possible.
Dedicated type:
5 A, 50 A, 100 A, 250 A and 400 A
Conforming to
RS485/RS232C
—
100/200/400 V AC system
○
○
○
—
Transformer not
required.
Direct input possible.
Dedicated type: 5 A,
50 A, 100 A, 250 A,
400 A and 600 A
—
Dedicated type: 5 A, 50 A, 100 A,
250 A, 400 A and 600 A
(Note 4)
Conforming to RS485
MEWTOCOL/MODBUS (Selectable with setting mode)
Restrictions apply. Please check communication
specifications column.
MEWTOCOL/MODBUS
(Selectable with setting mode)
MEWTOCOL
MODBUS
MEWTOCOL/MODBUS (Selectable with setting mode)
Restrictions apply. Please check communication specifications column.
MEWTOCOL: Up to 99 units
MODBUS: Up to 247 units
99 (max.)
—
1 point
—
1 point
1 point
1 point
1 point
1 point
Number of pulse output point
—
1 point
1 point
1 point
1 point
1 point
1 point
1 point
Number of analog input point
—
—
—
—
—
—
—
Instantaneous active electric power
—
Current value
—
Stand-by electric power
—
Preset value
—
Demand (Note 5)
—
Excess alarm output
Number of pulse input point (Note 3)
○
○
○
○
○
○
○
—
—
—
—
—
—
—
○
—
—
○
○
○
—
—
Main unit memory function
—
—
—
—
—
—
External memory function
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Calendar timer function
Measuring items
Simple measurement
—
Integrated electric power
—
Instantaneous electric power
—
Current
—
Voltage
—
Electricity charge (Note 6)
—
Conversion carbon dioxide value
—
Power factor
—
Frequency
—
Hour meter
—
Pulse count value
—
Simultaneous power and
pulse measurement
Tool and software
(free of charge)
○
—
KW Monitor
—
KW Watcher
—
KW View
—
KW Network monitor
Standard
○
—
—
—
○
○
○
○
○
○
—
○
—
—
○
○
○
○
—
—
—
—
—
○ (Active)
○ (Active)
○ (Active)
○ (Active)
○ (Active, Reactive, Apparent)
○ (Active)
○ (Active)
○ (Active)
○ (Active)
○ (Active, Reactive, Apparent)
(R,
S,
and
T)
(CT1
and
CT2)
(CT1
and
CT2)
(CT1
and
CT2)
○
○
○
○
○ (CT1, CT2, and CT3)
(between 1 and 2, ○ (between 1 and 2, ○ (between 1 and 2,
(between
P1
and
P0, between P2 and P0, between P3 and P0)
○ (RS, RT, and TS) ○between
○
2 and 3)
between 2 and 3)
between 2 and 3)
○
○
○
○
○
○
○
—
—
—
—
○
○
○
—
—
—
○
○
○
○
—
—
—
○
○
○
○
—
○
○
○
○
○
○
—
○
○
○
○
○
○
—
—
—
○
○
○
○
—
○
○
○
○
○
○
—
○
○
○
○
○
○
—
— (Note 1)
○
—
—
—
—
—
—
—
—
—
—
—
—
CE and S-MARK
CE, UL, and S-MARK
Notes: 1) Please contact our sales offices for more information about which areas this product can be used.
2) A VT (secondary side rated voltage: 110 V) is needed to measure loads that exceed rated input voltage.
3) Input method: contact/non-voltage contact (open collector)
4) Commercially available current transformer (CT) (When using secondary current 1 A or 5 A and when primary current is 4,000 A or less)
5) The demand function of Eco-POWER METER is that of Japanese function.
6) Eco-POWER METER is primarily designed for managing energy saving. It is not intended to be used for billing.
CE and S-MARK
Tool & Software
SOFTWARE TOOL
KW View
For KW1M-H / KW2G-H
For easy visualization of measurement data collected by an SD memory card
Verification
Display tool
Power
CO2
Charge
Pulse
Analog
■ Simply load the measurement data (CSV file) collected in an SD/SDHC memory card
into your PC.
You can then display the data as a graph by month, day and hour, and print it out.
■ Using easy operation, you can manage Eco-POWER METER data for up to 99 units.
■ KW1M-H graph shows display is in 60 minutes units (fixed).
KW2G-H graph shows display is in 15, 30 or 60 minutes units (fixed).
■ Data for integrated electric power, pulse data (count values), analog data (converted
to digital values) can now be displayed graphically.
■ Automatic device recognition.
KW1M-H
SD memory card type
Before and after chart of integrated electric power KW View
KW2G-H
SD memory card type
PC
* Analog data (converted digital values) are only displayed on the graph for each hour.
KW Watcher
Graph comparing integrated electric power KW View
and temperature (analog)
Compatible with all products (if data is stored by DLL or DLU)
For easy “visualization” of data collected in DLL and DLU*
Measurement monitoring software
Management
■ Collected files stored according to unit of time on the Data
Power
CO2
Charge
Analog
Primary
unit
Time
set OK
logger, are downloaded as required to a PC and graphs
and numerical data can be displayed for simple electric power, water amount,
temperature, primary unit and air flow amount measurement values.
■ Measurement is in 15 min, 30 min, and 60 min units.
■ KW1M-H / KW2G-H data stored on SD memory cards can also be displayed.
(Requires change of KW Watcher settings)
Pulse
Before and after chart of integrated electric power KW Watcher
LAN
RS485
KW2G
*DLL is the abbreviation for Data Logger Light.
DLU is the abbreviation for Web Datalogger Unit.
DLL
PC
Electric power use broken down by facility
KW Watcher
KW1M
KW4M
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
All software tool can be downloaded*, free of charge, from our website.
You can also check the required operating environments.
*Customer registration is required before you download.
KW Monitor
For easy visualization of real-time Eco-POWER METER data
Software for centralized control by PC
Analysis and Eco-POWER METER setting
■ You can directly access the Eco-POWER METER via
your PC.
Data can be constantly collected and easily displayed
numerically or in graph form.
■ Logging can be selected among 1 sec, 5 sec, 10 sec,
15 sec, 30 sec, 60 sec, 1 min, 5 min, 10 min, 15 min, 30
min, and 60 min units.
(Depending on communication conditions and number of
connections, data may not be acquired for the collection
period.)
■ Electrical power can be measured either integrated or
instantaneous.
■ With simple demand functions both logging and demand
estimation can be performed simultaneously.
Display of warning messages according to target value
settings is useful for energy management.
■ Data for integrated electric power, pulse data (count
values), analog data (converted to digital values) can
now be displayed graphically.
■ Communication protocol compatibility only with
MEWTOCOL
Eco-POWER METER setting
Integrated /
Instantaneous
power
CO2
Charge
Pulse
Analog
Current
Voltage
Weld
time
Power
factor
Frequency
Counter
Demand
Time
set OK
Terminal
setting
Graph showing hour integrated value and total integrated value KW Monitor
LAN
RS485
KW2G
KS1
Signal Converter
KW7M
PC
* KW2G series units are also able
to directly connect one-to-one with
a PC via USB port.
KW8M
■ For each Eco-POWER METER, settings can all be set, changed, or stored
on a PC.
(Storage of setting values is possible only, via USB transfer, with the KW2G series.)
■ Since changes can be made to multiple Eco-POWER METERs at the same
time, the labor of setting units one at a time is saved.
Setting screen
KW Monitor
KW Network Monitor
For wireless network tree check
Built-in wireless type
For KW1M-R
Software for wireless network check
Verification
■ This software is useful for making the “visualization” of network at the time of
installation or occurrence of a problem.
■ You can check the connection status of the wireless network and the terminal devices
by connecting your PC to the master unit and carrying out simple operations, which
will help you to quickly resolve problems.
■ This software can read out an error log stored in KW1M-R (master unit).
Wireless network confirmation screen KW Network Monitor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Specifications
KW2G / KW2G-H
Main
unit
* AKW2020G and AKW2160G have only CE certification
marking.
Expansion
unit
AKW2010G
AKW2020G
KW2G
KW2G-H
KW2G / KW2G-H COMMON FEATURES
●Up to 7 expansion units can be added as required without need for power
or other wiring.
Up to 16 circuits (single-phase two-wire) or 8 circuits (single-phase threewire; three-phase three-wire)
●If an expansion unit (pulse input and analog input type) is used, flow,
temperature, humidity and other environmental conditions can be
monitored.
●By using an expansion unit (power measurement and pulse output), pulse
output is possible for each measuring circuit.
●Capable of various types of measurement.
Simultaneous measurement of regenerative power (instantaneous),
micro-power, inverter power (primary side), electrical power and pulse
(flow, etc.)
AKW2110G
AKW2160G AKW2152G AKW2182G
FEATURES OF KW2G-H
●Simple measurement function enables measurement
of electric power of only the CT.
●Via USB connection with a PC, using KW Monitor,
you can easily check initial settings and operating
status.
●Quick installation: The units fit DIN rails.
●Pulse output width can be freely set in the range of
1 to 100 ms; finer power values can be output to an
external counter.
●Because pulse input status is displayed, the
operational status of external connected devices can
be monitored.
●Internal memory
Automatic logging function (read by SD memory
card).
Automatic logging of measurement data on
expansion units.
●Built-in battery (clock and log data backup).
ORDER GUIDE
Product name
Phase and wire system Operating power supply Input measured voltage Current transformer (sold separately)
Main unit (Standard type)
KW2G /
KW2G-H
EcoPOWER
METER
Single-phase two-wire
system
Dedicated type
100 to 240 V AC
100 / 200 V AC
Single-phase three-wire
5 A, 50 A, 100 A,
system
50 / 60 Hz
system
Power measurement
250 A, 400 A, 600 A
Three-phase three-wire
Power measurement and
system
Pulse output (Note 1)
Expansion
Pulse input
Number of input points
Input method
unit
2 channels
Contact / No contact (open collector)
(Note 2)
Analog input
Number of input points
Input range
Voltage: 0 to 5 V / 1 to 5 V (Note 3) Current: 0 to 20 mA / 4 to 20 mA (Note 3)
2 channels
(Note 2)
Main unit (SD memory card type)
Model No.
AKW2010G
AKW2020G
AKW2110G
AKW2160G
AKW2152G
AKW2182G
Notes: 1) Use a main unit (standard type) of Ver. 1.04 or later and a main unit (SD memory card type) of Ver.1.01 or later.
2) Use a main unit (standard type) of Ver. 1.02 or later. 3) Select with setting mode
MEASUREMENT ITEMS
Power measurement (for AKW2010G, AKW2020G, AKW2110G and AKW2160G)
Item
Unit
Data display range
Integrated electric power
kWh/MWh
(Active) (Note 1)
Active (Note 2)
kW
Instantaneous
Reactive (Note 2)
kvar
electric power
Apparent
kVA
R-current
A
N/S-current
A
Current
T-current
A
R (RS)-voltage
V
S (RT)-voltage
V
Voltage
T (TS)-voltage
V
Electricity charge (Note 3)
Conversion carbon dioxide value
kg-CO2
Power factor (Note 2) Displayed on the main unit
Frequency
Hz
Pulse count value (Note 4)
0.00 to 9999.99 kWh to 9999.99 MWh,
0.00 to 9999999.99 kWh (when 9-digit display)
−9999.99 to 0.000 to 9999.99
−9999.99 to 0.00 to 9999.99
0.00 to 9999.99
0.000 to 6000.00
0.000 to 6000.00 (calculated value)
0.000 to 6000.00
0.0 to 9999.9
0.0 to 9999.9 (calculated value)
0.0 to 9999.9
0.00 to 999999
0.00 to 999999
−1.00 to 1.00 (without identify leading phase and lagging phase)
47.5 to 63.0
0 to 999999
Pulse input (for AKW2152G)
Item
Pulse count value (Note)
Data display range
0 to 999999
Note: The number of displayed digit of pulse count value differs according to the prescale set by pre-scale setting mode.
Analog input (for AKW2182G)
Item
Converted digital value (Note)
Data display range
−999999 to 999999
Note: The number of displayed digits of the converted digital values differs according to
the preset decimal point position.
Notes: 1) KW2G / KW2G-H can measure regeneration electric power. Integrated electrical power is not integrated (not subtracted) when detecting regeneration electric power.
2) While detecting regeneration electric power, minus is displayed on instantaneous active electric power and power factor.
3) Eco-POWER METER is designed chiefly to manage saving energy. It is neither intended nor can it be legally used for billing.
4) Displayed digit of pulse counter differs according to the pre-scale set by pre-scale setting mode.
SPECIFICATIONS
For details, please refer to the Eco-POWER METER user’s manual.
Main unit specifications
Item
Specifications
Rated operating voltage
Rated frequency
Rated power consumption
Allowable operating voltage range
Allowable momentary power-off time
Ambient temperature
Ambient humidity
Display method
Number of connectable expansion units
Power failure memory method
Weight
100 to 240 V AC (Add to main unit)
50 / 60 Hz common
Main unit: 6 VA, Expansion unit (Power measurement, Power measurement and Pulse output, and Analog input): 0.5 VA / unit, Expansion unit (Pulse input): 1.0 VA /unit (240 V AC at 25 °C 77 °F)
85 to 264 V AC (85 % to 110 % of rated operating voltage)
10 ms
-10 to +50 °C +14 to +122 °F (-25 to +70 °C -13 to +158 °F) at storage
30 to 85 % RH (at 20 °C 68 °F), non-condensing
LCD with backlight (green), Upper: 5-digit (7-segment 1-digit + 16-segment 4-digit), Lower: 6-digit (7-segment)
Max. 7 units
EEPROM (more than 1,000,000 overwrite), Memory items: setting value and integral measuring value
Main unit (Standard type): 180 g, Main unit (SD memory card type): 185 g, Expansion unit (Power measurement): 80 g, Expansion unit (Power measurement and Pulse output, Pulse input and Analog input): 85 g
Electric power input specifications (for AKW2010G, AKW2020G, AKW2110G and AKW2160G)
Item
Specifications
Integrated electric power and Instantaneous electric power
Accuracy Current
without
Voltage
error in CT
Temperature characteristics
and VT
Frequency characteristics
Within ± (2.0 % F.S. + 1 digit) (at 20 °C 68 °F, rated input, rated frequency, power factor 1) *Accuracy coverage: 10 to 100 % of rated current
Within ± (1.0 % F.S. + 1 digit) (at 20 °C 68 °F, rated input, rated frequency, power factor 1) *Accuracy coverage: 10 to 100 % of rated current
Within ± (1.0 % F.S. + 1 digit) (at 20 °C 68 °F, rated input, rated frequency, power factor 1)
Within ± (1.0 % F.S. + 1 digit) (Range of -10 to +50 °C 14 to 122 °F, rated input, power factor 1)
Within ± (1.0 % F.S. + 1 digit) (Frequency change ± 5 % based on rated frequency, rated input, power factor 1)
( )
KW SERIES
Memory specifications of main unit (for AKW2020G)
Item
Specifications
15 min (00 hr. 00 min 00 sec after the day) (fixed)
(Instantaneous value) Integrated electric power (1) (2), Instantaneous active electric power (1) (2), Instantaneous reactive electric power (1) (2), Instantaneous
File type 1
apparent electric power (1) (2), R-current (1), R (T)-current (2), S (N)-current, R/RS-voltage (1), R (T/TS)-voltage (2), RT-voltage, Power factor (1) (2),
(instantaneous Save data
Frequency, Count value, Converted digital value for CH0, Converted digital value for CH1, Pulse count value for CH0 and Pulse count value for CH1
value) (Note 1)
Save data amount 96 records per file (max. approx. 8 days worth of data)
Save cycle
15 min (00 hr. 00 min 00 sec after the day) (fixed)
File type 2
Save data
(Difference value) Integrated electric power (1) (2), Count value, Pulse count value for CH0 and Pulse count value for CH1
(difference
value) (Note 1) Save data amount 96 records per file (max. approx. 8 days worth of data)
Select among 1 min, 5 min, 10 min, 15 min, 30 min, or 60 min
(Saved timing) When 1 min is selected: 00 sec after the minute
When 5 min is selected: 00, 05, 10, 15, 20, 25, 30... min after the hour
Save cycle
When 10 min is selected: 00, 10, 20, 30, 40, 50 min after the hour
When 15 min is selected: 00, 15, 30, 45 min after the hour
File type 3
When 60 min is selected: 00 min after the hour
(instantaneous
value detail)
Integrated electric power (1) (2), Instantaneous active electric power (1) (2), Instantaneous reactive electric power (1) (2), Instantaneous apparent
(Note 1)
Save data
electric power (1) (2), R-current (1), R (T)-current (2), S (N)-current, R/RS-voltage (1), R (T/TS)-voltage (2), RT-voltage, Power factor (1) (2), Frequency,
Count value, Converted digital value for CH0, Converted digital value for CH1, Pulse count value for CH0 and Pulse count value for CH1
Save data amount Max. 720 records, 12 hours approx. worth of data (when the save cycle is set to one minute)
Main unit display
Integrated electric power by day (latest data covering 8 days period) / Integrated electric power by hour (latest data covering 12 hours period)
Calendar timer function
Time accuracy Monthly accuracy: ±30 sec (at 25 °C 77 °F)
Content of battery backup
Time measurement and Log data
Battery life (Note 2)
2 years approx. (at 25 °C 77 °F, in power-off state)
Logging functions
Save cycle
Notes: 1) Using the setting mode, you can select whether or not to write to the SD memory card for each of file types 1, 2, and 3. Files can be created for each unit.
2) When the battery gets low, the BATT display will start flashing. Please replace the battery in accordance with the battery replacing procedure. Also, battery life will be shortened if the main unit is
used in a high temperature environment.
* While measuring, data is collected in the memory of main unit. If, while measuring, the memory capacity of main unit is reached, data will be overwritten in succession starting from the oldest data. Initialization of the main unit memory is possible.
External memory specifications (for AKW2020G)
• SD memory card slot
Item
Specifications
Support media
Supported format
standards
SD memory card (Note 1)
Compliant with SD and SDHC
standards (Note 2)
Notes:
1) Operation verified SD memory card: Panasonic Corporation SD/SDHC
memory card 2 GB and 4 GB class 4 and over
2) To format SD memory cards, please download and use the formatting
software available on the Panasonic website.
The file system on a SD memory card that was formatted using standard PC
software does not comply with the SD memory card standard.
Communication specifications
Specifications
RS485 communication
Item
Protocol
Transmission function
Isolation status
Number of connected units
Transmission distance
Transmission speed
Transmission format
Communication method
Synchronous system
Ending resistance
<SD memory card handling precautions>
Data saved on an SD memory card may be lost in the following
cases. Please note that Panasonic Industrial Devices SUNX is not
responsible for any losses of recorded data and other direct and
indirect damages.
1) When a customer or a third party incorrectly uses the SD memory card
2) When the SD memory card is affected by static electricity or
electrical noise
3) When the SD memory card is taken out or the power is turned off
while the SD memory card access LED of the unit is flashing (during
data writing)
* It is recommended that you constantly back up important data to
another medium.
MEWTOCOL / MODBUS (RTU) (selectable with setting mode)
Isolated with the internal circuit
99 units max. (Note 1) (Note 2)
1,200 m 3,937 ft max. (Note 3)
38,400 / 19,200 / 9,600 / 4,800 / 2,400 bps (selectable with setting mode)
Data length: 8-bit / 7-bit (selectable with setting mode) (Note 4)
Parity: Not available / Odd number / Even number (selectable with setting mode)
Stop bit: 1-bit / 2-bit (selectable with setting mode)
Half-duplex
Synchronous communication method
120 Ω approx. (built-in)
USB communication (Note 5)
Computer link (MEWTOCOL)
Isolated with the internal circuit
12 Mbps (Full-speed)
-
Notes:
1) For RS485 converter on the computer side, we recommend SI-35 and SI-35USB (from LINE EYE Co.,Ltd.).
2) When using SI-35, SI-35USB or PLC from our company (which can be connected up to 99 units), up to 99 Eco-POWER METER can be connected. [When using C-NET adapter, up to 32 Eco-POWER
METER (max.)] In case using this system with the other devices, up to 31 Eco-POWER METER can be connected.
3) Please check with the actual devices when some commercial devices with RS485 interface are connected. The number of connected devices, transmission distance, and transmission speed may be
different according to using transmission line.
4) With MODBUS (RTU) protocol, it works only with 8-bit. 5) When using the USB port, install the dedicated USB driver.
Pulse input specifications (for AKW2010G, AKW2020G and AKW2152G)
Item
Input mode
Max. counting speed
Pulse input
(Min. input signal width)
Input signal
Output mode
Decimal point
Prescale
Range
Item
Specifications
Addition (Fixed)
50 kHz / 30 Hz (Select with setting mode)
0.01 ms (When 50 kHz selected) /
16.7 ms (When 30 Hz selected), ON : OFF ratio = 1 : 1
Contact / No contact (open collector)
• Impedance when shorted: Max. 1 kΩ
• Residual voltage when shorted: Max. 2 V
• Impedance when open: Min. 100 kΩ
HOLD (Over count)
Setting possible up to under 3-digit
0.001 to 100.000 (Set with setting mode)
Number of output point
Insulation method
Output type / Output capacity
Pulse width (when pulse output with integrated
active electric power selected)
ON state voltage drop
OFF state leakage current
1 point
Optical coupler
Open collector / 100 mA 30 V DC
1 to 100 ms (selectable with setting
mode) (Note 1)
1.5 V or less
100 μA or less
0.001 kWh, 0.01 kWh, 0.1 kWh,
1 kWh, 10 kWh, 100 kWh /
Power alarm (AL-P) / Current alarm (AL-C) / Stand-by
power alarm (AL-S) / Counter (Cnt)
(Note 2, 3)
Analog input specifications (for AKW2182G)
Item
Number of input points
Input range (Select Voltage
with setting mode) Current
Converted digital value
Resolution
Overall precision
Voltage
Input impedance
Current
Voltage
Absolute
maximum input
Current
Input protection
Pulse output (Transistor output) specifications (for AKW2010G, AKW2020G and AKW2160G)
Specifications
Specifications
2 channels
0 to 5 V / 1 to 5 V (selectable with setting mode)
0 to 20 mA / 4 to 20 mA (selectable with setting mode)
0 to 4000 (decimal number) (Note)
1/4000 (12 bits)
±1 % F.S. or less (-10 to +55 °C +14 to 131 °F)
440 kΩ
125 Ω
- 0.3 to +10 V
- 2 to + 30 mA
Diode
Pulse output unit
(selectable with setting mode)
Notes: 1) Pulse width setting is possible using main unit software AKW2010G Ver. 1.04 or later
and AKW2020G Ver. 1.01 and later.
2) For normal operation of other functions, to switch on minimal pulse width of 1 to 10 ms,
the maximum pulse output interval is 25 ms.
Consequently, a minimum measurable pulse unit output setting of 40 pulses or less per 1
second is recommended.
How to calculate
Unit for pulse output: PL-P > Max. measurement power (kW) / 3,600 sec × 4 pulse/sec
When the pulse output unit is 0.001, the maximum power that can be properly measured
by pulse output is 144 kW (3600 sec × 40 pulse/sec × 0.001).
Cautions:
(1) Count errors may occur if the pulse output is set to 40 pulses or more per 1 second.
(2) If the pulse output OFF time is set too short, count errors by connected counters,
PLCs (Programmable Logic Controllers) may occur.
3) These count output specifications are only for the main unit.
Note: Digital conversion value differs according to the scaling conversion value set by setting mode.
If the analog input value exceeds the upper or lower limit, the digital value will preserve the
upper or lower limit.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Feature & Specifications
KW1M / KW1M-H / KW1M-R
Master
unit
AKW1111
AKW1110
AKW1121
KW1M
AKW1000
KW1M-H
KW1M COMMON FEATURES
AKW1131
KW1M-R
FEATURES OF KW1M-H
● Internal memory (Read by SD memory card)
● Built-in battery (for clock and log data backup)
● Calendar timer function.
● Simple demand function.
● Output of alarm signal is possible using the
“alarm setting”.
● 50 mm 1.97 inch thickness makes it perfect for
control panel installations.
● Selectable screw, DIN rail and panel
installation.
● Display switchable between electrical power
and electricity charge usage.
● Display of calculated CO2 value possible
● Measurement of inverter power supplies
(primary side) is available.
Slave
unit
FEATURES OF KW1M-R
● Wireless capabilities eliminate need for LAN
installation.
● Auto routing system for easy setup of a
wireless network.
● Compatible with a wide range of AC power
supply and directly installable in a distribution
board.
● RS485 connection enables Eco-POWER
METERs other than KW1M-R to be ready for
wireless communications.
● Calendar timer function.
● Wired/Wireless selection function (AKW1131
only)
● Please contact our sales offices for more
information about which areas this product can
be used.
ORDER GUIDE
Product name
KW1M (Standard type)
KW1M-H (SD memory card type)
KW1M-R
Built-in
wireless
type
Phase and wire system
Single-phase two-wire system
Single-phase three-wire system
Three-phase three-wire system
Three-phase four-wire system (Note 1)
-
Master unit (Note 2, 3)
Slave unit
Single-phase two-wire system
Single-phase three-wire system
Three-phase three-wire system
Three-phase four-wire system
Operating
power supply
Input measured
voltage
100 / 200 V AC system
100 to 240 V AC
50 / 60 Hz
100 / 200 / 400 V AC system
(Select with setting mode)
Current transformer
(sold separately)
Dedicated type
5 A, 50 A, 100 A,
250 A, 400 A and 600 A
Model No.
AKW1110
AKW1111
AKW1121
-
-
AKW1000
100 / 200 / 400 V AC system
(Select with setting mode)
Dedicated type
5 A, 50 A, 100 A,
250 A, 400 A and 600 A
AKW1131
Notes: 1) For a three-phase four-wire system, exclude AKW1110 from the selection.
2) AKW1000 can serve as either a “master unit” or a “slave unit (as a repeater)” by being selected in the master unit/slave unit setting mode (MODE 1).
3) AKW1000 does not have a power measurement function.
MEASUREMENT ITEMS (Not applicable for AKW1000)
Item
Instantaneous electric power (Active)
Unit
kW
Data display range
0.00 to 9999.99
0.00 to 9999.99 MWh
Integrated electric power (Active)
kWh/MWh
R-current
A
0.0 to 6000.0
S-current (Note 1)
A
0.0 to 6000.0
T-current
A
0.0 to 6000.0
R (RS)-voltage
V
0.0 to 9999.9
S (RT)-voltage (Note 1)
V
0.0 to 9999.9
T (TS)-voltage
V
0.0 to 9999.9
Electricity charge (Note 2)
-
0.00 to 999999
kg-CO2
0.00 to 999999
Current
Voltage
Conversion carbon dioxide value
0.00 to 9999999.99 kWh (when 9-digit display)
Power factor (Note 1)
-
Frequency (Note 1)
-
47.5 to 63.0 Hz
ON-time
h (Hour)
0.0 to 99999.9
OFF-time
h (Hour)
0.0 to 99999.9
Hour meter
Pulse count value (Note 1)
-
0.00 to 1.00 [Identify leading phase (–) or lagging phase] (Only in range of phase angle θ = –90° to +90°)
0 to 999999
Notes: 1) Excluding AKW1110
2) Eco-POWER METER is designed chiefly to manage saving energy. It is neither intended nor can it be legally used for billing.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
SPECIFICATIONS
For details, please refer to the Eco-POWER METER user’s manual.
Main unit specifications
Item
Rated operating voltage
Rated frequency
Rated power
consumption
Allowable operating voltage range
Allowable momentary power-off time
Ambient temperature
Ambient humidity
Wireless specifications (for AKW1000 and AKW1131)
Item
Direct sequence spread spectrum (DS-SS)
100 m 328 ft (Obstacle-free straight-line distance)
1 mW
2,405 to 2,480 MHz
16 channels (The auto-scanning function can
Number of channels
automatically select an unassigned channel.)
Wireless transmission speed 250 kbps
1 : N communication, Auto routing system (N: Up to 247 units)
Communication style
Number of repeaters: 8 repeaters (between the
Repeater function
master unit and the target slave unit) (Note)
Note: Since the unit does not have a repeater setting function, use the dedicated tool
“KW Network Monitor” to check the actual number of repeaters.
Pulse input specifications (for AKW1111, AKW1121 and AKW1131)
Input mode
Max. counting speed
Pulse input
(Min. input signal width)
Input signal
(at 20 °C 68 °F)
Mode
Decimal point
Range
Prescale
Specifications
Addition (Fixed)
2 kHz / 30 Hz (Select with setting mode)
0.25 ms (When 2 kHz selected) / 16.7 ms (When
30 Hz selected), ON : OFF ratio = 1 : 1
Contact / No voltage contact (open collector)
• Impedance when shorted: Max. 1 kΩ
• Residual voltage when shorted: Max. 2 V
• Impedance when open: Min. 100 kΩ
HOLD (Over count)
Setting possible up to under 3-digit
0.001 to 100.000 (Set with setting mode)
Communication specifications
Item
Power
failure
memory
method
AKW1000
FROM (more than 100,000 overwrite)
AKW1110, AKW1111,
EEPROM (more than 100,000 overwrite)
AKW1112 and AKW1131
170 g approx. (AKW1110 and AKW1111), 180 g approx.
(AKW1121), 160 g approx. (AKW1000), 170 g approx. (AKW1131)
* Excluding the antenna and battery
Weight
Electric power input specifications
Improved measurement accuracy
Item
Specifications
Integrated electric power
and Instantaneous
electric power
Within ± (2.0 % F.S. + 1 digit) (at 20 °C 68 °F, rated input, rated
frequency, power factor 1)
Accuracy coverage: 5 to 100 % of rated current
Within ± (1.0 % F.S. + 1 digit) (at 20 °C 68 °F rated input, rated
frequency, power factor 1)
Accuracy coverage: 5 to 100 % of rated current
Current
Accuracy
without
error in
CT and
VT
( )
Voltage
Within ± (1.0 % F.S. + 1 digit) (at 20 °C 68 °F rated input, rated
frequency, power factor 1)
Hour meter
Within ± (0.01 % +1 digit) (at 20 °C 68 °F) [In case power on start
or current energizing: within ± (0.01 % + 1 sec + 1 digit) (at 20 °C
68 °F)]
Temperature
characteristics
Within ± (1.0 % F.S. + 1 digit) (Range of -10 to 50 °C 14 to 122 °F,
rated input, power factor 1)
Frequency characteristics
Within ± (1.0 % F.S. + 1 digit) (Frequency change ± 5 % based on
rated frequency, rated input, power factor 1)
Specifications of the pulse output (transistor output) of integrated electric active power
Item
Number of output point
Insulation method
Output type
Output capacity
Pulse width
ON state voltage drop
OFF state leakage current
Pulse output unit
(selectable with setting
mode) (Note 3)
Specifications
1 point
Optical coupler
Open collector
100 mA 30 V DC
100 ms approx.
1.5 V or less
100 μA or less
0.001 kWh, 0.01 kWh, 0.1 kWh, 1 kWh, 10 kWh, 100 kWh / Power alarm
(AL-P) / Current alarm (AL-C) / Stand-by power alarm (AL-S) (Note 1) /
Counter output (Cnt) (Note 1) / Demand alarm (OEM) (Note 2)
Notes: 1) For AKW1111, AKW1121, and AKW1131 2) For AKW1121 only
3) We recommend the setting of minimum unit for pulse output for measurement shown as below.
Output pulse: 4 pulses or less per 1sec
Count errors may occur if pulse output unit is set so that 4 or more pulses are output per 1 second.
- How to calculate Unit for pulse output: PL-P > Max. measurement power (kW) / 3,600 sec × 4 pulse/sec
RS232C communication (for AKW1000 only)
Protocol
Specifications
LCD with backlight Upper: green, 4-digit, 16-segment
Lower: amber, 6-digit, 7-segment
Display method
Specifications
Wireless system type
Communication distance
Radio wave output
Frequency band
Item
Item
Specifications
100 to 240V AC
50 / 60 Hz common
6 VA (AKW1110), 8 VA (AKW1111, AKW1121 and
AKW1131), 5 VA (AKW1000) (240 V AC at 25 °C 77 °F)
85 to 264 V AC (85 % to 110 % of rated operating voltage)
10 ms
-10 to +50 °C 14 to 122 °F
(-25 to +70 °C -13 to +158 °F) at storage
30 to 85 % RH (at 20 °C 68 °F), non-condensing
Specifications
RS485 communication
MEWTOCOL and MODBUS (RTU) (Note 5) (Note 6)
(selectable with setting mode)
Isolated with the internal circuit
Max. 99 units (Note 2, 3)
1,200 m 3,937 ft (Note 1) / 38,400, 19,200, 9,600, 4,800 or 2,400 bps
15 m 49 ft / 115,200, 57,600, 38,400, 19,200, 9,600, 4,800,
For AKW1000: 115,200, 57,600, 38,400, 19,200, 9,600, 4,800, 2,400 or
2,400 or 1,200 bps (selectable with setting mode)
1,200 bps (selectable with setting mode)
Data length: 8-bit / 7-bit (selectable with setting mode) (Note 4), Parity: Not available / Odd number / Even number (selectable with setting mode), Stop bit: 1 bit (fixed)
Half-duplex / Synchronous communication method
Enable / Disable (selectable with setting mode) (If you enable the flow control
function, the counterpart equipment must also be compatible with flow control.)
120 Ω approx. (built-in)
MEWTOCOL: 2,048 bytes, MODBUS (RTU): 256 bytes
MEWTOCOL: 2,048 bytes (Note 7), MODBUS (RTU): 256 bytes (Note 7)
MEWTOCOL and MODBUS (RTU) (Note 5)
Isolation status
Number of connected units
Transmission distance / Transmission speed
Transmission format
Communication method / Synchronous system
Flow control
Ending resistance
Data buffer (Max. data byte size for send and receive one time)
Notes: 1) Please check with the actual devices when some commercial devices with RS485 interface are connected.
The number of connected devices, transmission distance, transmission speed may be different according to using devices or transmission line.
2) For RS485 converter on the computer side, we recommend SI-35 and SI-35USB (from LINE EYE Co., Ltd.).
3) When using SI-35,SI-35USB or our PLC (which can be connected up to 99 units), up to 99 Eco-POWER METER units can be connected. (However, 32 units max. using connection with C-NET adapter)
In case using this system with the other devices, up to 31 Eco-POWER METER units can be connected.
4) With MODBUS (RTU) protocol for RS485 communication, it works only with data length 8-bit. 5) You don’t have to select a protocol for the 1:1 communications of AKW1000 (only if both units are AKW1000).
6) AKW1131 cannot be used for data communications via RS485. It may result in malfunction.
7) Command sending to/receiving from an AKW1131 station: Max. reading: 26 points (57 bytes), Max. writing: 23 points (55 bytes)
* Modbus Protocol is a communications protocol developed for PLCs by Modicon Inc.
Memory specifications of main unit (for AKW1121)
Item
File type 1
instantaneous
value
(
File type 2
difference
value
(
)
File type 3
instantaneous
value detail
(
)
Save cycle
Save data
Save data
amount
Save cycle
Save data
Save data
amount
Save cycle
)
Save data
Save data
amount
Main unit display
Specifications
60 min (on the hour) (fixed)
(Instantaneous value) Integrated electric power, Instantaneous electric
power, Current, Voltage, Power factor, Frequency, and Count value
24 records per file (max. approx. 1.5 years worth of data)
60 min (on the hour) (fixed)
(Difference value) Integrated electric power and Count value
24 records per file (max. approx. 1.5 years worth of data)
Select among 1 min, 5 min, 10 min, 15 min, 30 min, or 60 min
(Saved timing)
When 1 min is selected: 00 sec after the minute
When 5 min is selected: 00, 05, 10, 15, 20, 25, 30... min after the hour
When 10 min is selected: 00, 10, 20, 30, 40, 50 min after the hour
When 15 min is selected: 00, 15, 30, 45 min after the hour
When 60 min is selected: 00 min after the hour
Integrated electric power, Instantaneous electric power, Current,
Voltage, Power factor, Frequency, and Count value
Max. 5,760 records, 4 days approx. period (when the save cycle
is set to one minute)
Integrated electric power by month (latest data covering 1.5 year period)
/ Integrated electric power by day (latest data covering 1 month period) /
Integrated electric power by hour (latest data covering 24 hours period)
External memory specifications
<SD memory card slot> (for AKW1121 only)
Item
Support media
Supported format
standards
Specifications
SD memory card (Note 1)
Compliant with SD and SDHC
standards (Note 2)
Notes:
1) Operation verified maker: Panasonic Corporation
SD/SDHC memory card 2 GB, 4 GB and 8 GB
2) To format SD memory cards, please download and use the
formatting software available on the Panasonic website.
The file system on a SD memory card that was formatted
using standard PC software does not comply with the SD
memory card standard.
Calendar timer specifications (for AKW1000 and AKW1121)
Item
Time accuracy
Content of
battery backup
Battery life
Specifications
Monthly accuracy: ± 240 sec (at –10 °C 14 °F)
Monthly accuracy: ± 70 sec (at 25 °C 77 °F)
Monthly accuracy: ± 240 sec (at 50 °C 122 °F)
Time measurement and log data
(for AKW1121)
2 years approx. (at ambient temperature
25 °C 77 °F) (in power-off state)
< SD memory card handling
precautions >
Data saved on an SD memory card
may be lost in the following cases.
Please note that Panasonic Industrial
Devices SUNX is not responsible for
any losses of recorded data and other
direct and indirect damages.
1) When a user or a third party
incorrectly uses the SD memory
card
2) When the SD memory card is
affected by static electricity or
electrical noise
3) When the SD memory card is taken
out or the power is turned off while
the SD memory card access LED
of the unit is flashing (during data
writing)
* It is recommended that you
constantly back up important data to
another medium.
Feature & Specifications
KW4M / KW7M / KW8M
KW4M
FEATURES
Features of KW4M
● Easy on-panel mounting with included
mounting frame.
● Protective structure: IEC IP66 (Only the panel
front with rubber gasket).
● UL-compliant.
● Measurement of inverter power supplies
(primary side) is available.
Common Features
of KW8M
KW7M
KW8M
KW8M High performance type
● Log data is stored to memory of main unit.
● Built-in battery (for clock and log data backup).
● Simple demand function.
● Compatible with systems of up to threephase four-wire.
● Easy on-panel mounting with included
mounting frame.
● Measurement of inverter power
supplies (primary side) is available.
KW8M 1 A / 5 A CT input type
● Capable of direct input from 1 A / 5 A CT in the
secondary side without using dedicated CT.
● High current circuit measurement.
Features of KW7M
● DIN rail type ideal for installation in a panel.
● Slim, 22.5 mm 0.89 in wide: easily mounts
anywhere.
● Measurement of inverter power supplies
(primary side) is available.
ORDER GUIDE
Product name
KW4M
Eco-POWER
METER
DIN □48 type
Protocol
Phase and wire system Input measured voltage Current transformer (sold separately) Terminal type
MEWTOCOL
MODBUS (RTU)
MEWTOCOL
MODBUS (RTU)
KW7M
Eco-POWER METER DIN rail type
KW8M
Eco-POWER
METER
DIN 48 × 96
type
Screw terminal
Single-phase two-wire system
Single-phase three-wire system 100 / 200 V AC system
Three-phase three-wire system
Dedicated type
5 A, 50 A, 100 A,
250 A and 400 A
Single-phase two-wire system
Single-phase three-wire system 100 / 200 V AC system
Three-phase three-wire system
Single-phase two-wire system
High performance type Single-phase three-wire system
Three-phase three-wire system
1 A / 5 A CT input type Three-phase four-wire system
11-pin
Dedicated type
5 A, 50 A, 100 A,
250 A, 400 A and 600 A
100 / 200 / 400 V AC
system (Select with
setting mode)
Model No.
AKW5111
AKW5112
AKW5211
AKW5212
Screw terminal
(M3 / M2 screw)
AKW7111
Screw terminal
(M3 “+ / –” screw)
AKW8111H
AKW8111
U.R.D., Ltd. CTL-CL series separate
CT recommended (Check the
specifications before use.)
AKW8115 (Note)
Note: Since a dedicated CT is not used, please use a 4,000 A or less type (secondary current: 1 A or 5 A).
MEASUREMENT ITEMS
KW4M
KW8M
Item
Instantaneous electric power
Integrated electric power
L1 (CT1) - phase current
L2 (CT2) - phase current
Voltage between 1-2
Voltage
Voltage between 2-3
Yen
Electricity Dollars
charge
Euros
(Note)
Yuan
No currency
Conversion carbon dioxide value
ON-time
Hour meter
OFF-time
Pulse count value
Current
Unit
Data display range
kW
0.00 to 9999.99
0.00 to 9999.99 kWh and after
kWh
10.00 MWh to 9999.99 MWh
MWh When 9-digit display: 0.00 to
9999999.99 kWh
A
0.0 to 6000.0
A
0.0 to 6000.0
V
0.0 to 9999.9
V
0.0 to 9999.9
JPY
0 to 999999
$
0.0 to 99999.9
EUR
0.0 to 99999.9
CNY
0 to 999999
CHG
0 to 999999
kg-CO2 0.0 to 999999
h (Hour) 0.0 to 99999.9
h (Hour) 0.0 to 99999.9
Count 0 to 999999
KW7M
Item
Unit
Instantaneous electric power
Integrated electric power
L1 (CT1) - phase current
Current
L2 (CT2) - phase current
Voltage between 1-2
Voltage
Voltage between 2-3
Electricity charge (Note)
kW
kWh
A
A
V
V
Data display range
0.00 to 999999.99
0.00 to 9999999.9
0.0 to 6000
0.0 to 6000
0.0 to 9999
0.0 to 9999
0.00 to 99999999
Item
Unit
Data display range
Integrated Active
electric
Reactive
power
Apparent
Active
Instantaneous
Reactive
electric power
Apparent
CT1 - phase
current
CT2 - phase
Current
current
CT3 - phase
current
Voltage between
P1 and P0
Voltage between
Voltage
P2 and P0
Voltage between
P3 and P0
Electricity charge (Note)
kWh
kvarh
kVAh
kW
kvar
kVA
0.00 to 9999999.9
0.00 to 9999999.9
0.00 to 9999999.9
0.00 to 9999999.99
-99999.99 to 0.00 to 999999.99
0.00 to 9999999.99
Power factor
Frequency
ON-time
OFF-time
Pulse count value
Hour meter
A
0.0 to 6000
A
0.0 to 6000
A
0.0 to 6000
V
0.0 to 9999
V
0.0 to 9999
V
0.0 to 9999
0.0 to 99999999
Displayed on 0.00 to 1.00 [with identify leading phase
the main unit (LEAD) or lagging phase (LAG)]
-1.00 to 0.00 to 1.00
Communication Only in range of phase angle θ = –90°
to 0 to +90°
Hz
47.5 to 63.0
(
Time
-
)
0.0 to 99999.9
0.0 to 99999999
Note: Eco-POWER METER is primarily designed to manage saving energy. It
is neither intended nor can it be legally used for billing.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
SPECIFICATIONS
For details, please refer to the Eco-POWER METER user’s manual.
KW4M
Main unit specifications
Item
Specifications
Rated operating voltage
Rated frequency
Rated power consumption
Allowable operating voltage range
Allowable momentary power-off time
Ambient temperature
Ambient humidity
Vibration resistance
Shock resistance
Display method
Power failure memory method
Protection
Weight
100 to 120 V AC / 200 to 240 V AC
50 / 60 Hz common
8 VA (240 V AC at 25 °C 77 °F)
85 to 132 V AC / 170 to 264 V AC (85 % to 110 % of rated operating voltage)
10 ms
-10 to +50 °C 14 to 122 °F (-25 to +70 °C -13 to +158 °F) at storage
30 to 85 % RH (at 20 °C 68 °F), non-condensing
10 to 55 Hz (1cycle / min), single amplitude: 0.75 mm 0.03 in (1 hour on 3 axes)
Min. 294 m/s2 (5 times on 3 axes)
6-digit, 7-segment (set value) with backlight and 4-digit, 16-segment (mode), LCD upper section: green, lower section: amber
EEPROM (more than 100,000 overwrite)
IEC standard IP66 (only front panel with rubber gasket)
* Mounted in a row, waterproofing property will be lost.
140 g approx. (screw terminal type), 130 g approx. (11-pin type)
KW7M
Main unit specifications
Item
Specifications
Rated operating voltage
Rated frequency
Rated power consumption
Allowable operating voltage range
Allowable momentary power-off time
Ambient temperature
Ambient humidity
Vibration resistance
Shock resistance
Display method
Power failure memory method
Weight
100 to 120 V AC / 200 to 240 V AC
50 / 60 Hz common
6 VA (240 V AC at 25 °C 77 °F)
85 to 132 V AC / 170 to 264 V AC (85 % to 110 % of rated operating voltage)
10 ms
-10 to +50 °C 14 to 122 °F (-25 to +70 °C -13 to +158 °F) at storage
30 to 85 % RH (at 20 °C 68 °F), non-condensing
10 to 55 Hz (1cycle / min), single amplitude: 0.375 mm 0.01 in (1 hour on 3 axes)
Min. 294 m/s2 (5 times on 3 axes)
8-digit, 7-segment LED
EEPROM (more than 100,000 overwrite)
100 g approx.
KW8M
Main unit specifications
Item
Specifications
Rated operating voltage
Rated frequency
Rated power consumption
Allowable operating voltage range
Allowable momentary power-off time
Ambient temperature
Ambient humidity
Vibration resistance
Shock resistance
Display method
Power failure memory method
Weight (without mounting bracket)
100 to 240 V AC
50 / 60 Hz common
8 VA (240 V AC at 25 °C 77 °F)
85 to 264 V AC (85 % to 110 % of rated operating voltage)
10 ms
-10 to +50 °C 14 to 122 °F (-25 to +70 °C -13 to +158 °F) at storage
30 to 85 % RH (at 20 °C 68 °F), non-condensing
10 to 55 Hz (1cycle / min), single amplitude: 0.375 mm 0.01 in (1 hour on 3 axes)
Min. 294 m/s2 (5 times on 3 axes)
8-digit, 7-segment LED
EEPROM (more than 100,000 overwrite)
235 g approx. (AKW8111), 250 g approx. (AKW8111H high performance type), 265 g approx. (AKW8115 1 A / 5 A CT input type)
Note: Analog input terminals: No. 11 to 20 / Pulse input terminals: No. 4 and 5
KW4M / KW7M / KW8M
Electric power input specifications
Item
Improved measurement accuracy
Specifications
Integrated electric power and Within ± (2.0 % F.S. + 1 digit) (at 20 °C 68 °F, rated input, rated frequency, power factor 1) (Note 1)
Instantaneous electric power Accuracy coverage: 5 to 100 % of rated current
Within ± (1.0 % F.S. + 1 digit) (at 20 °C 68 °F rated input, rated frequency, power factor 1)
Current
Accuracy coverage: 5 to 100 % of rated current
Accuracy
without error in
Voltage
Within ± (1.0 % F.S. + 1 digit) (at 20 °C 68 °F rated input, rated frequency, power factor 1)
CT and VT
Within ± (0.01 % +1 digit) (at 20 °C 68 °F)
Hour meter (Note 2)
[In case power on start or current energizing: Within ± (0.01 % + 1 sec + 1 digit) (at 20 °C 68 °F)]
Temperature characteristics Within ± (1.0 % F.S. + 1 digit) (Range of -10 to +50 °C 14 to 122 °F, rated input, power factor 1)
Frequency characteristics
Within ± (1.0 % F.S. + 1 digit) (Frequency change ± 5 % based on rated frequency, rated input, power factor 1)
Notes: 1) Integrated electric power (active/apparent) and instantaneous electric power (active/apparent) of AKW8115: within ± (1.0 % F.S. + 1 digit) (at 20 °C
68 °F, rated input, rated frequency, power factor 1)
Accuracy coverage: 5 to 100 % of rated current
2) Excluding KW7M
(
)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Option
DEDICATED CURRENT TRANSFORMER (CT) AND OPTIONS
DEDICATED CURRENT TRANSFORMER (CT)
ORDER GUIDE (Dedicated CT cannot be used with the AKW8115.)
Primary side rated current
AKW4801C
100 A
AKW4802C
250 A
AKW4803C
400 A
AKW4804C
50 A/100 A
AKW4506C
Clamp-on type
Through type
Model No.
5 A/50 A
250 A/400 A
AKW4507C
600 A
AKW4508C (Note 2)
Notes: 1) For except AKW8115, please order in accordance with the type of
power distribution system you will be measuring.
(Even if you will be using a secondary side 5 A CT, you will need an
AKW4801C.)
2) AKW4508C can be used with an Eco-POWER METER compatible
with 600 A type CT.
AKW4801C
AKW4802C
AKW4506C
AKW4803C
AKW4804C
AKW4507C
AKW4508C
Specifications
Type
Model No.
Item
Primary side rated current
Secondary side rated current
Winding (Turn)
Ratio error
Through hole
Clamp-on type
AKW4802C
AKW4803C
AKW4801C
AKW4804C
AKW4506C
Through type
AKW4507C
AKW4508C
5 A/50 A
1.67 mA/16.7 mA
3,000
100 A
250 A
400 A
50 A/100 A
250 A/400 A
600 A
33.3 mA
125 mA
200 mA
16.7 mA/33.3 mA 125 mA/200 mA
200 mA
3,000
2,000
2,000
3,000
2,000
3,000
± 2.0% F.S.
± 1.0% F.S.
ø10 mm ø0.39 in ø16 mm ø0.63 in ø24 mm ø0.94 in ø36 mm ø1.42 in ø17 mm ø0.67 in
ø36 mm ø1.42 in
Breakdown voltage (initial)
1,000 V AC / 1 min (Between
2,000 V AC / 1 min (Between
2,000 V AC / 1 min (Between
1,000 V AC / 1 min (Between
through hole and output lead wire) through hole and output lead wire) through hole and output lead wire) through hole and output lead wire)
Insulation resistance (initial)
Functional vibration resistance
Vibration resistance
Functional shock resistance
Shock resistance
Output protection level
Permissible clamping frequency
Ambient temperature range
Storage temperature
Ambient humidity
Weight (Trunk cable included)
Min. 100 MΩ (at 500 V DC megger) (Between through hole and output lead wire)
10 to 55 Hz (1 cycle / min), single amplitude: 0.15 mm 0.01 in (10 min on 3 axes)
10 to 55 Hz (1 cycle / min), single amplitude: 0.375 mm 0.01 in (1 hour on 3 axes)
Min. 98 m/s2 (4 times on 3 axes)
Min. 294 m/s2 (5 times on 3 axes)
± 7.5 V with clamp element
± 3.0 V with clamp element
± 7.5 V with clamp element
± 3.0 V with clamp element
100 times approx.
―
–10 to +50 °C +14 to +122 °F (without frost and non-condensing)
–20 to +60 °C –4 to +140 °F (without frost and non-condensing)
35 to 85 % RH (at 20 °C 68 °F non-condensing)
60 g approx.
90 g approx.
200 g approx.
295 g approx.
70 g approx.
200 g approx.
215 g approx.
Notes: 1) Dedicated CT are dedicated for low voltage under 440 V AC system. They can not be used for high voltage circuit.
2) In each type of Eco-POWER METER excluding AKW8115, a combination of commercially secondary side 5 A CTs and dedicated CTs for 5 A (AKW4801C) is used
for measuring high voltage circuits; therefore, AKW4801C is definitely necessary. For details, confirm with each respective user’s manual.
3) Since dedicated CTs cannot be used when measuring with AKW8115, please be careful and do not purchase a dedicated CT by mistake.
4) For the AKW8115 CT, current transformers manufactured by U.R.D. Co., Ltd. (clamp-on type CT CTL-CL series) are recommended. Please confirm the
specification beforehand.
5) Dedicated CT are not included with Eco-POWER METERs.
6) Each dedicated CT includes a 1 m 3.3 ft trunk cable, respectively.
OPTIONS
Trunk cable
Intermediate power cable
Product name
Trunk cable for CT
Option of EcoPOWER METER
dedicated CT
Model No.
3 m 9.8 ft
5 m 16.4 ft
10 m 32.8 ft (special order)
AKW4703
Product name
Model No.
AKW4705
Intermediate power cable
AKE2811
AKW4710
Note: For any type of trunk cable, please connect no more than one.
Antenna with cable:
For KW1M-R
200 ± 10 7.87 ± 0.39
Pencil type antenna:
For KW1M-R
Note: We recommend using an intermediate power cable when attaching the
dedicated CT to a non-“Y” split power cable.
Antenna extension cable:
For KW1M-R (Note)
RS232C cable:
For KW1M-R (master unit)
Cable length: 2 m 6.6 ft
One unit
* Packed with AKW1000
and AKW1131
Model No.: AKW1803
One unit
Model No.: AKW1802
Cable length: 2 m 6.6 ft
One unit
Model No.: AKW1804
Model No.: AKR1801
Note: When an antenna extension cable is used, radio wavel attenuation occurs.
With a single extension cable, the communications distance is reduced by about 30 %: use only after prior confirmation that the system is functioning
KW SERIES
Required for installation inside switchboard
Mounting rails (applicable for DIN and IEC standards):
For KW4M pin type (AKW5211 and AKW5212), KW7M, KW2G /
KW2G-H, and KW1M / -H / -R
Fastening plate:
For KW4M pin type (AKW5211 and AKW5212), KW7M, KW2G /
KW2G-H, and KW1M / -H / -R
1,000 ± 1 39.37 ± 0.04
5.5
0.22
0.20 0.59 0.39 0.59
0.11R 0.59 0.39 0.59 0.20
5 15 10 15
2.75R 15 10 15 5
Length: 1 m
3.3 ft
Aluminum
50
1.97
12
0.47
M4
M0.16
10
0.39
40−5.5×15 0.22×0.59 Oval hole
35 24
1.38 0.94
DIN rail terminal socket:
For KW4M 11-pin type (AKW5211 and AKW5212)
1.5
0.06
27
1.06
Model No.: ATA4806
ATA4806
10
0.39
UP
Model No.: AT8-DLA1
* For holding DIN rails
7.5 0.30
30.5
1.20
70
2.76
Model No.: ATC180041 50
1.97
Required for installation on control panel
45
1.77
* Sold separately
34.6
1.36
21
0.83
ø31.4
ø1.24
43.4
1.71
Mounting frame:
For KW1M and KW1M-H
75.4 2.97
2-19
2-0.75
ø30
ø1.18
2-1.2
2-0.05
85.4 3.36
Model No.: AT78051
Model No.: AT8-DP11
86.2 3.39
Model No.: AKW1822
4
0.16
60 2.36
79.4 3.13
Convenient when installation is on control panel.
Protective cover for DIN 48 size (flexible type) : For KW4M
Terminal protective cover: For KW4M screw terminal type (AKW5111 and AKW5112)
47.5
1.87
50
1.97
11.5 0.45
50
1.97
04
0.
0
.2
R
R1
R0
Model No.: AKW4823
R5
Model No.: AQM4803
38 1.50
11.5 0.45
30
1.18
11
0.43
4-R0.5
4-R0.02
60.4 60.4
81.4 81.4
11-pin cap:
For KW4M 11-pin type (AKW5211 and AKW5212)
4- 4-R
R 1.
0. 2
05
Rear terminal socket:
For KW4M 11-pin type (AKW5211 and AKW5212)
80 3.15
R2
8
.0
R0
Model No.: AKW8822
88 3.46
92 3.62
0.88 22.3 24.5 0.96
75 2.95
45 + 00.4
1.77 + 0.02
0
6
0.24
Model No.: AKW4822
45 +− 0.6
0
1.77 +− 0.02
0
19 0.75 20 0.79
9 × 8.4 = 75.6
9 × 0.33 = 2.97
1.6
R2 .08 0.06
1.77 +− 0.02
0
2 × × R0
2
4.2
0.17
(R
Terminal cover: For all types KW8M
30
8 1.18
8
R2 .0
14.2
R2 0.0
× R0
19 0.56
×
2 ×
2 ×R
0.75
2
2
(R
)
110 ± 0.2
4.33 ± 0.01
45
+ 0.6
−0
125 4.92
16.5
0.65 92 + 00.4 3.62 + 0.02
0
2.1
(R
4.2
0.17
24
0.94
4.2
0.17
R2 8
.0
R0
1.6
0.06
Mounting frame: For all types KW8M
* For fixing
5 70 ± 0.2 2.76 ± 0.01 2 × R2 2 × R0.08
0.20
12.2
)
0.48
2.1
)
80 3.15
40
1.57
12.2
0.48
Mounting frame: For KW4M
Model No.: AKT8801
Others
Screwdriver for terminal
socket: For KW7M
Backup battery: For KW1M-H, KW1M-R (master unit)
and KW2G-H main unit
* Packaged with AKW1000, AKW1121 and AKW2020G
Model No.: AFP0806
Model No.: AFPG804
Backup battery: For high performance
type KW8M (AKW8111H) only
* Packaged with the main unit
Model No.: AFC8801
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
Dimensions
DIMENSIONS
Unit: mm in, Tolerance: ± 1.0 ± 0.04
KW2G (Standard type) and KW2G-H (SD memory card type)
/ AKW2020G
Terminal arrangement (for AKW2010G / AKW2020G)
Terminal
protection
cover
60 2.36
Terminal
protection
cover
Connector for current
transformer (CT)
25
0.98
14
0.55
35.4 1.39
90
3.54
Connector label
Remove when
connecting an
expansion unit.
(69) (2.72) (With a DIN rail)
Two hooks
Use these hooks when connecting
an expansion unit.
65 2.56
60 2.36
16.4
0.65
25 0.98
35.4 1.39
90 3.54
95 3.74
62.2 2.45
49.4 1.94
DIN rail
sold
separately
Input
terminal
(M3)
23 0.91
(Without cover)
Two hooks
Use these hooks
when connecting
an expansion unit.
(69) (2.72) (With a DIN rail)
5 0.20 3 0.12
Connector for current transformer (CT)*
Output
terminal
(M3)
14 0.55
Pulse input
Phase and wire
system
Single-phase
two-wire system
Measured
Single-phase
voltage
three-wire system
input
Three-phase
three-wire system
Between
terminals
(1)−(2)
(P1-P0)
(1)−(2)−(3)
(P1-P0-P2)
(1)−(2)−(3)
(P1-P0-P2)
Terminal
Input voltage
100 to 240 V AC (100 to 240 V and
after) (Line voltage)
100 to 120 V AC (100 to 120 V and
after: 3W) (Phase voltage)
100 to 240 V AC (100 to 240 V 3 and
after) (Line voltage)
Connector label
Remove when
connecting an
expansion unit.
*AKW2110G and
AKW2160G only
Function
+
−
Terminal type
M3
Terminal arrangement (for AKW2152G)
Terminal No.
(1)
(2)
(3)
(4)
Function
Terminal type
+
−
+
−
CH0
CH1
M3
* The “-“ terminals are connected internal. (Between channels:
non-isolated)
Terminal arrangement (for AKW2182G)
Terminal No.
(1)
(2)
(3)
(4)
Function
V/I
Voltage/Current
COM
Common
V/I
Voltage/Current
COM
Common
CH0
CH1
Terminal type
M3
* The “COM” (common) terminals are connected internal.
(Between channels: non-isolated)
<Wiring diagrams>
Single-phase two-wire system
* One dedicated CT is required for one load.
DIN hook
Use these hooks when connecting on the DIN rail
1
2
Main
breaker
When measuring two
circuits, connect the P1
and P2 terminals in series.
Eco-POWER METER
protection breaker
P1
P0
1
P2
2
P. IN
−
6
9
+
4
−
8
+
7
10
−
11
E
L
K
CT2
Load protection
breaker
Main unit
L
K
Load protection
CT1
breaker
L
K
CT2
Load protection
breaker
Expansion unit
RS485
(Without cover)
L
K
Load protection
CT1
breaker
N.C.
3
P. OUT
+
5
(AKW2160G)
M3
“+ / −” screw
RS485
Terminal No.
(1)
(2)
(Expansion unit) AKW2110G / AKW2160G / AKW2152G / AKW2182G
AKW2152G and
AKW2182G
Pulse output
Terminal arrangement (for AKW2160G)
5
3
0.20 0.12
DIN hook
Use these hooks when
connecting on the DIN rail
Function
Terminal type
Measured voltage input
P1 and P0 also serve as the terminals
M3.5
“+ / −” screw
for the operating power supply.
No connection
P1
P0
P2
NC
+
−
+
−
+
−
E
The input voltage to each terminal is as follows.
6.9
0.27
USB 2.0 port
MiniB
(□47.6) (□1.87)
62.2 2.45
M3-7P
Fastening torque:
0.5 to 0.6 N•m
DIN rail
sold
separately
(□49.4) (□1.94)
95
3.74
SD memory
card slot*
*SD memory
card slot only
applies to
AKW2020G.
Terminal No.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
Load (4) Load (3)
Load (2) Load (1)
Load side
50
1.97
16.4
0.65
M3.5-4P
Fastening torque:
0.8 to 1.0 N•m
Power supply side
(Main unit) AKW2010G
When an expansion unit is connected
Single-phase three-wire system / Three-phase three-wire system
Eco-POWER METER
protection breaker
P1
P0
1
P2
2
9
+
L
L
Main unit
3
4
P. IN
−
6
K
CT2
N.C.
P. OUT
+
5
L
Load (1)
K
Load CT1
protection
breaker
Load side
R R1
Main
N S 2 breaker
T T3
Load (2)
Power supply side
* Two dedicated CT are required for one load.
−
8
+
7
10
−
RS485
11
E
K
Load CT1
protection
breaker
L
K
CT2
Expansion unit
When an expansion unit is connected
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]
KW SERIES
● Be sure to wire correctly according to the terminal arrangement and wiring diagrams.
● For details, please refer to the Eco-POWER METER user’s manual.
Unit: mm in, Tolerance: ± 1.0 ± 0.04
KW1M-R Built-in wireless type
(Master unit) AKW1000
Mounting hole dimensions Terminal arrangement
67 ± 0.5 2.64 ± 0.20
0.04 ± 0.02
82 ± 0.5 3.23 ± 0.20
2 × M4
1 ± 0.5
0.04 ± 0.02
50 1.97
47 1.85
25.1 0.99
8 0.31
R1
R0
.04
×
2
No connection
RS
CS
RS232C
E N.C. N.C. RS CS
9 10 11 12 13
−
8
+
7
35.4 1.39
90 3.54
82 3.23
RS485
1
2
3
N.C.
4
SD
5
RD
6
SG
RS232C
* Use a straight cable for RS232C connections.
P=8.7
P=0.34
(Slave unit) AKW1131
(54*) (2.13*)
(55*) (2.17*)
* When installing
DIN rail
Mounting hole dimensions Terminal arrangement
67 ± 0.5 2.64 ± 0.20
M3 (Fastening torque: 0.5 to 0.6 N•m)
)
le
ho
g
in
(M
1 ± 0.5
0.04 ± 0.02
2
×
ø5
ø0
.2
0
1 ± 0.5
0.04 ± 0.02
(1)
(2)
(3)
(4)
(5)
(6)
R1
R0
(7)
(8)
(9)
M3.5
(10)
“+ / −” screw
(11)
(12)
(13)
Function
+
RS485
−
E
+
Pulse output
−
+
Pulse input
−
* Because the RS485(E) terminal does not have an SG (signal
ground) terminal, the ground wire of the shielded cable should
not be connected.
50 1.97
47 1.85
25.1 0.99
8 0.31
.04
The input voltage to each terminal is as follows.
Phase
Between
and wire
Input voltage
terminals
system
Operating power Single-phase
100
to
240
V
AC
(100 to 240 V and after)
(1)−(2)
supply input
two-wire
(Line voltage)
Single-phase
0 to 440 V AC (0 to 440 V and after)
(3)−(4)
two-wire
(Line voltage)
Single-phase (3) (4) (5)
0 to 220 V AC (0 to 220 V to: 3W)
−
−
Measured
three-wire
(Phase voltage)
0 to 440 V AC (0 to 440 V 3 and after)
voltage input Three-phase (3) (4) (5)
− −
three-wire
(Line voltage)
Three-phase (3) (4) (5) (6) 0 to 254 V AC (0 to 254 V 3N and after)
− − −
four-wire
(Phase voltage)
0.24
1.1 ±0.5
0.04 ± 0.02
71 2.80
60 2.36
58 2.28
35.4 1.39
Terminal
82 3.23
6
Terminal type Terminal No. Terminal type
L
N
P1
M3.5
Measured P0 “+ / −” screw
voltage
P2
input
P3
2 × M4
ou
0.04 ± 0.02
nt
18.2
0.72
Function
Operating
power supply
82 ± 0.5 3.23 ± 0.20
39.1
1.54
11 11
1 ± 0.5
0.43 0.43
67.8 2.67
M3 (Fastening torque: 0.5 to 0.6 N•m)
75 2.95
P=7.62
67 2.64
P=0.30
90 3.54
Function
+
−
E
RS232C
RS485
M3.5 (Fastening torque: 0.8 to 1.0 N•m)
Connector for current
transformer (CT)
(7)
(8)
(9)
M3
(10)
“+ / −” screw
(11)
(12)
(13)
Phase and Between
Terminal
Input voltage
wire system terminals
Operating power Single-phase (1) (2) 100 to 240 V AC (100 to 240 V and after)
−
two-wire
(Note) (Line voltage)
supply input
Operating power supply
100 to 240 V AC
50 / 60 Hz
Terminal
cover
(transparent)
(1)
(2)
(3)
(4)
(5)
(6)
The input voltage to each terminal is as follows.
0.24
1.1 ± 0.5
0.04 ± 0.02
71 2.80
60 2.36
58 2.28
6
1 ± 0.5
0.04 ± 0.02
ø5
ø0
.2
0
M3 (Fastening torque: 0.5 to 0.6 N•m)
75 2.95
67 2.64
P=7.62
P=0.30
Terminal type Terminal No. Terminal type
L
N
No connection
M3.5
SD “+ / −” screw
RS232C RD
SG
(M
ou
nt
in
g
1 ± 0.5
ho
le
)
Terminal
cover
(transparent)
67.8 2.67
Function
Operating
power supply
P=8.7
P=0.34
(54*) (2.13*)
M3.5 (Fastening torque: 0.8 to 1.0 N•m)
(55*) (2.17*)
* When installing
DIN rail
<Wiring diagrams>
AKW1131 When measuring load with rated input voltage
(100 to 200 V AC system and 400 V AC system)
Single-phase two-wire system *One dedicated CT is required.
Single-phase three-wire system / Three-phase three-wire system
* Two dedicated CT are required.
E
9
−
11
+
10
+
12
+
Power supply side
0.1 A 30 V DC
1
2
1
2
3
4
P1
Operating power supply
100 to 240 V AC
50 / 60 Hz
5
7
CT1
Measured voltage input
CT1
L
Three-phase four-wire system * Three dedicated CT are required.
Pulse output Pulse input
E
9
−
11
+
10
+
12
−
13
Power supply side
1
R1
S2
T3
N4
2
Operating power supply
100 to 240 V AC
50 / 60 Hz
3
4
P1
5
P0
6
P2
P3
Measured
voltage input
−
+
9
10
11
+
12
−
13
CT1
CT2
CT3
K
L
Direction of CT
1
R R1
NS2
T T3
2
3
Operating power supply
100 to 240 V AC
50 / 60 Hz
4
P1
5
P0
CT1 CT2
6
(Note 2)
P2
* Leave CT3 open.
Measured voltage input
CT1
CT2
K
L
Direction of CT
Notes: 1) Do not wire to (5), (6) terminal. They are connected
internal.
2) Do not wire to (6) terminal. They are connected internal.
CT1 CT2 CT3
0.1 A 30 V DC
Load side
−
8
8
E
0.1 A 30 V DC
* Leave CT2 and CT3 open.
K
+
7
−
6
(Note 1) (Note 1)
P0
Direction of CT
RS485
Pulse output Pulse input
RS485
−
13
Power supply side
−
8
Load side
+
7
Load side
RS485 Pulse output Pulse input
Dimensions
DIMENSIONS
Unit: mm in, Tolerance: ± 1.0 ± 0.04
KW1M (Standard type) and KW1M-H (SD memory card type)
AKW1110/AKW1111/AKW1121
2
×
ø
1 ± 0.5
ø 5
0.04 ± 0.02 0. (Mo
20 u
nt
in
g
ho
le
)
• For mounting hole dimensions, please refer to the KW1M-R
"Mounting hole dimensions" on page 25.
Terminal arrangement (for AKW1110)
75 2.95
39.1
1.54
67 2.64
1 ± 0.5
11 11
0.04 ± 0.02
0.43 0.43
67.8
2.67
M3 (Fastening torque: 0.5 to 0.6 N•m)
18.2
0.72
90 3.54
82 3.23
6
1.1 ± 0.5
0.24 0.04 ± 0.02
SD memory
card slot*
39.1
1.54
Terminal
cover
(transparent)
Connector for
current transformer
(CT)
Terminal No.
(1)
(2)
(3)
(4)
(5)
(6)
(7) (Note 1)
(8)
(9)
(10) (Note 2)
(11)
(12)
(13) (Note 1)
(14) (Note 1)
Terminal
cover
(transparent)
AKW1110/AKW1121
Connector for
current transformer
(CT)
P1
P0
P2
Terminal type
Measured voltage
input
No connection
+
–
E
+
–
M3
“+ / −” screw
RS485
Pulse output
No connection
Notes: 1) The (7), (13) and (14) terminals are connected internal to analog input
terminal. Cannot use extending wiring.
2) Because the RS485(E) terminal does not have an SG (signal ground)
terminal, the ground wire of the shielded cable should not be connected.
The input voltage to each terminal is as follows. (for AKW1110)
1 ± 0.5
11
0.43 67.8 0.04 ± 0.02
2.67
18.2
0.72
*SD memory card slot
only applies to SD
memory card type
KW1M-H.
Function
Operating power
supply
No connection
L
N
Terminal
Phase and wire system Between terminals
(1)−(2)
Operating power supply input Single-phase two-wire
Single-phase two-wire
(4)−(5)
Measured voltage input Single-phase three-wire (4)−(5)−(6)
Three-phase three-wire (4)−(5)−(6)
AKW1111
<Wiring diagrams>
Input voltage
100 to 240 V AC (100 to 240 V and after) (Line voltage)
0 to 220 V AC (0 to 220 V and after) (Line voltage)
0 to 110 V AC (0 to 110 V to: 3W) (Phase voltage)
0 to 220 V AC (0 to 220 V 3 and after) (Line voltage)
AKW1110 When measuring load with rated input voltage (100 to 200 V AC system)
Single-phase three-wire system / Three-phase three-wire system
Single-phase two-wire system *One dedicated CT is required.
* Two dedicated CT are required.
13
14
2
3
4
5
6
CT1
+
8
−
9
E
10
+
11
−
12
13
14
1
2
3
4
5
6
7
(Note)
0.1 A 30 V DC
7
N.C.
(Note) (Note)
(Note) P1 P0
Operating power supply
Measured
100 to 240 V AC
voltage input
50 / 60 Hz
1
2
* Leave CT2 and CT3 open.
CT1
L
K
Direction of CT
Power supply side
Power supply side
(Note) (Note)
0.1 A 30 V DC
1
P.OUT
RS485
−
12
+
11
Load side
E
10
−
9
Note: Do not wire to (3), (6), (7), (13), (14) terminal. They are connected
internal.
(Note)
CT1 CT2
N.C.
(Note)
(Note) P1 P0 P2
Operating power supply
Measured
100 to 240 V AC
voltage input
50 / 60 Hz
RR1
NS2
TT3
* Leave CT3 open.
CT1
Load side
RS485 Pulse output
+
8
CT2
L
K
Direction of CT
Note: Do not wire to (3), (7), (13), (14) terminal. They are connected internal.
AKW1111 When measuring load with rated input voltage (100 to 200 V AC system and 400 V AC system)
Single-phase two-wire system *One dedicated CT is required.
Single-phase three-wire system / Three-phase three-wire system
* Two dedicated CT are required.
+
Power supply side
1
1
2
2
3
4
P1
7
CT1
0.1 A 30 V DC
Operating power supply
100 to 240 V AC
50 / 60 Hz
5
CT1
L
Direction of CT
+
12
−
13
0.1 A 30 V DC
Power supply side
1
R1
S2
T3
N4
2
3
Operating power supply
100 to 240 V AC
50 / 60 Hz
4
P1
P0
CT2 CT2 CT3
6
5
P2
P3
Measured
voltage input CT1
CT2
CT3
K
L
Load side
−
11
+
10
9
−
+
10
11
−
+
12
13
1
RR1
NS2
TT3
2
3
Operating power supply
100 to 240 V AC
50 / 60 Hz
4
P1
5
P0
CT1 CT2
6
(Note)
P2
Measured
voltage input
* Leave CT3 open.
CT1
CT2
L
K
Direction of CT
Terminal arrangement (for AKW1111)
Pulse output Pulse input
E
9
8
Note: Do not wire to (6) terminal.
They are connected internal.
Three-phase four-wire system * Three dedicated CT are required.
−
8
E
0.1 A 30 V DC
* Leave CT2 and CT3 open.
Note: Do not wire to (5), (6) terminal. They are connected internal.
RS485
−
6
(Note) (Note)
P0
Measured
voltage input
K
+
7
Pulse output Pulse input
RS485
−
13
+
12
Power supply side
−
11
+
10
Load side
E
9
−
8
Load side
RS485 Pulse output Pulse input
+
7
Direction of CT
Terminal No.
(1)
(2)
(3)
(4)
(5)
(6)
L
N
P1
P0
P2
P3
(7)
(8)
(9)
(10)
(11)
(12)
(13)
+
E
+
+
-
Function
Terminal type
Operating power supply
Measured voltage input
M3.5
“+ / −” screw
RS485
Pulse output
M3
“+ / −” screw
Pulse input
* Because the RS485(E) terminal does not have an SG (signal ground)
terminal, the ground wire of the shielded cable should not be connected.
The input voltage to each terminal is as follows.
Terminal
Operating power
supply input
Phase and wire system
Between terminals
Input voltage
Single-phase two-wire
(1)−(2)
100 to 240 V AC (100 to 240 V and after) (Line voltage)
(3)−(4)
(3)−(4)−(5)
0 to 440 V AC (0 to 440 V and after) (Line voltage)
0 to 220 V AC (0 to 220 V to: 3W) (Phase voltage)
Single-phase two-wire
Measured voltage Single-phase three-wire
KW SERIES
AKW1121 When measuring load with rated input voltage (100 to 200 V AC system and 400 V AC system)
Single-phase two-wire system
Single-phase three-wire system / Three-phase three-wire system
* Two dedicated CT are required.
1
2
−
12
+
11
E
10
−
14
+
13
Power supply side
3
4
N.C.
5
6
1
2
−
9
1
2
E
10
+
11
−
12
−
14
+
13
CT1 CT2
0.1 A 30 V DC
7
(Note) (Note)
P1 P0
Measured
voltage input
Operating power supply
100 to 240 V AC
50 / 60 Hz
+
8
CT1
0.1 A 30 V DC
Power supply side
−
9
* Leave CT2 and CT3 open.
Load side
+
8
P.OUT Pulse input
RS485
RS485 Pulse output Pulse input
CT1
L
K
Direction of CT
3
N.C.
4
5
6
7
(Note)
P1 P0 P2
Operating power supply
Measured
100 to 240 V AC
voltage input
50 / 60 Hz
R R1
* Leave CT3 open.
CT1
NS2
TT 3
CT2
L
K
Note: Do not wire to (7) terminal.
They are connected internal.
Note: Do not wire to (6), (7) terminal. They are connected internal.
Load side
*One dedicated CT is required.
Direction of CT
Terminal arrangement (for AKW1121)
No.
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Three-phase four-wire system
* Three dedicated CT are required.
−
9
1
2
E
10
−
12
+
11
Pulse input
−
14
+
13
0.1 A 30 V DC
3
4
N.C.
5
CT1 CT2 CT3
6
7
Power supply side
P1 P0 P2 P3
Operating power supply
Measured
100 to 240 V AC
voltage input CT1
50 / 60 Hz
R1
CT2
S2
CT3
T3
N4
K
L
5.5
0.22
(□44.5) (□1.75)
V
Pulse input
Terminal type
11-pin type
Screw terminal type
1
1, R, R
RS485 (–)
2
2, N, S
CT1 (k)/IN
3
3, T, T
CT1 (ℓ), CT2 (ℓ)
4
RS485 (+)
CT2 (k)
5
RS485 (–)
0V
M3.5
6 Pulse output (+) Pulse output (+) “+ / −”
screw
7 Pulse output (–) Pulse output (–)
8
CT1 (k)/IN
1, R, R
9 CT1 (ℓ), CT2 (ℓ)
2, N, S
10
CT2 (k)
3, T, T
11
0V
RS485 (+)
kW/kWh
A
14.5
0.57
EcoPOWER METER
Panasonic
MODE Lock
1 2 OP CT1
3 4
CT2
CHARGE
M3
“+ / −” screw
Pulse
output
No.
MODE Lock
1 2 OP CT1
3 4
CT2
MODE
SET
TIME
COUNT
V
CHARGE
(□44.5) (□1.75)
EcoPOWER METER
TIME
RS485
Terminal arrangement
11-pin type (AKW5211/AKW5212)
5.5
0.22
COUNT
Terminal type
Unit: mm in, Tolerance: ± 1.0 ± 0.04
87.5
3.44
SET
Function
Terminal
Phase and wire system Between terminals
Input voltage
Operating power supply input Single-phase two-wire
(1)−(2)
100 to 240 V AC (100 to 240 V and after) (Line voltage)
Single-phase two-wire
(4)−(5)
0 to 440 V AC (0 to 440 V and after) (Line voltage)
Single-phase three-wire (4)−(5)−(6) 0 to 220 V AC (0 to 220 V to: 3W) (Phase voltage)
Measured voltage input
Three-phase three-wire (4)−(5)−(6) 0 to 440 V AC (0 to 440 V 3 and after) (Line voltage)
Three-phase four-wire (4)−(5)−(6)−(7) 0 to 254 V AC (0 to 254 V 3N and after) (Phase voltage)
Direction of CT
Screw terminal type (AKW5111/AKW5112)
MODE
+
–
E
+
–
+
–
The input voltage to each terminal is as follows.
KW4M
Panasonic
No.
(8)
(9)
(10)
(11)
(12)
(13)
(14)
* Because the RS485(E) terminal does not have an SG (signal ground)
terminal, the ground wire of the shielded cable should not be connected.
Load side
P.OUT
RS485
+
8
Function
Terminal type
L
Operating
N power supply
No connection
M3
P1
“+ / −” screw
P0
Measured
P2 voltage input
P3
kW/kWh
A
KW4M
KW4M
□48
□1.89
81.9
3.22
□48
□1.89
73
2.87
Note: A DIN rail terminal socket (ATC180041) should be
used for 11-pin type KW4M Eco-POWER METER.
Unit: mm in, Tolerance: ± 1.0 ± 0.04
KW7M
M3 Phoenix terminal
Terminal arrangement
A
V
kW
No.
1
2
3
4
5
6
7
8
9
DIN rail
KW M
kWh
Lock T/R
MODE
M2 Phoenix terminal
OUT
75 2.95
CHARGE
ITEM
SHIFT
SET
Eco-POWER METER
97 3.82
22.5
0.89
(4)
(0.16)
100 3.94
8.1
0.32
CT1 CT2
11
0.43
AKW8111/AKW8111H
Screw-type bracket (included)
24.1
0.95
MODE OPTION
SET
48
1.89
SHIFT
Terminal cover
(sold separately)
91 3.58
106.2 4.18
96
3.78
96
3.78
Gasket (included)
ITEM
START
STOP
48
1.89
11.5
0.45
98.5 3.88
104.5 4.11*
* With the terminal
M3 + / –
cover attached
Fastening torque:
0.6 to 1.0 N•m
Terminal type
Phoenix terminal
M3 “−” screw
Phoenix terminal
M2 “−” screw
* Because the RS485(E) terminal does not have an
SG (signal ground) terminal, the ground wire of the
shielded cable should not be connected.
KW8M, KW8M (High performance type) and KW8M (1 A / 5 A CT input type)
AKW8115
Function
1, R, R
2, N, S
3, T, T
No connection
Pulse output (+)
Pulse output (–)
RS485 (+)
RS485 (–)
RS485 (E)
Unit: mm in, Tolerance: ± 1.0 ± 0.04
Terminal arrangement
No.
Function
1
No connection
2 Operating power
supply
3
4
Pulse input
5
6
Pulse output
7
8
RS485
9
10
L
N
+
–
+
–
+
–
E
No.
11
12
13
14
15
16
17
18
19
20
Function
Terminal type
P1
P0
Measured voltage
input
P2
P3
CT1 (+)
M3
Measured CT input
“+ / −” screw
CT1 (−)
for AKW8111 and
CT2 (+)
AKW8111H
CT2 (−)
Measured current
CT3 (+)
input (for AKW8115)
CT3 (−)
(
)
* Because the RS485(E) terminal does not have an SG (signal ground) terminal,
the ground wire of the shielded cable should not be connected.
CE Marking
KW SERIES
CE MARKING
■ Acquisition of CE marking
When using in the application conforming to EN61010-1/IEC61010-1,
make sure to satisfy the following conditions.
[Environmental conditions]
• Overvoltage category II, Pollution degree 2
• Indoor use
• An ambient temperature of -10 to 50°C 14 to 122°F
• An ambient non-condensing humidity of 35 to 85%RH (at 20°C
68°F)
• Altitude of 2,000 m 6,562 ft or less
[Mount the product in a place with]
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gasses
• Few mechanical vibrations or shocks
• No exposure to direct sunlight
• No large capacity electromagnetic switches or cables through
which large current is flowing
■ Applicable standard
Safety
EN61010-1
standard
EMI
Radiation interference field strength
EN61326-1 Noise terminal voltage
Static discharge immunity
RF electromagnetic field immunity
EFT/B immunity
EMC
Surge immunity
EMS
Conductivity noise immunity
EN61326-1
Power frequency magnetic field
immunity
Voltage dip / Instantaneous stop /
Voltage fluctuation immunity
Others
CISPR11 class A
CISPR11 class A
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
KW SERIES
ENERGY EFFICIENCY SUPPORT EQUIPMENT LINEUP
Visualize Air Consumption
Data collection and storage
Monitoring by LAN (Ethernet)
DLL
KS1 Signal Converter
Air Flow Monitor EWA1
• Ultrasonic type resistant to oil mist
• No need to use dedicated filters
• Pipe size: 25A (1B) to 200A (8B)
(Data Logger Light)
• Collecting and storing power, pulse and analog data of
Eco-POWER METER
• Provided with a USB port and an SD/SDHC memory card slot
• Equipped with an AC/DC power supply
• Provided with a RS232C/RS485 communication port
[MEWTOCOL / MODBUS (RTU)]
• Converting RS232C/RS485 power
data for communications by LAN
For cases where wired connection is difficult
KR20 Wireless Unit
Wireless Sensor EWR1
Master unit
Slave unit
• Wireless communications of RS232C/RS485 power data
• 2.4 GHz band wireless communications
• Compliant with wireless standards of Europe and Japan
• Wireless communications of illuminance data/temperature and
humidity data
• Radially connect slave units with the master unit at the center
• 2.4 GHz band wireless communications
* Please contact our sales offices for more information about which areas this product can be used.