Prices as of October 15, 2015. Check Web site for most current prices.
Analog PLC
C0-02DR-D $139.00
4 DC Input/4 Relay Output; 2 Analog In/2 Analog Out Micro PLC
General Specifications
140 mA
Current Consumption at 24VDC
Terminal Block Replacement Part No. C0-16TB
5.6 oz (160 g)
Weight
Wiring Diagram
C0-02DR-D
24VDC
C1
X1
See Discrete I/O
Specifications - Inputs
(X1 through X4)
+
X2
+
X3
PWR
X4
RUN
C2
ERR
Y1
L
Y2
L
PORT1
Y3
L
TX1
Y4
L
See Discrete I/O
Specifications Outputs
(Y1 through Y4)
6-27 VDC
6-240 VAC
RX1
AD1V
Transmitter 0-5V
TX2
AD1I
Transmitter 4-20mA
RX2
AD2V
Transmitter 0-5V
AD2I
Transmitter 4-20mA
PORT2
PORT3
ACOM
RS-485
DA1I
RX3
DA2V
DA2I
+
Equivalent Discrete Input Circuit
C0-02DR-D Discrete I/O Specifications - Inputs
ON Voltage Level
OFF Voltage Level
Minimum ON Current
Maximum OFF Current
OFF to ON Response
ON to OFF Response
Status Indicators
Commons
X1-2: Typ 5 mA @ 24 VDC
X3-4: Typ 4 mA @ 24 VDC
X1-2: 4.7 kq @ 24 VDC
X3-4: 6.8 kq @ 24 VDC
X1-2: > 19 VDC
X3-4: > 19 VDC
X1-2: < 4 VDC
X3-4: < 7 VDC
X1-2: 4.5 mA
X3-4: 3.5 mA
X1-2: 0.1 mA
X3-4: 0.5 mA
X1-2: Typ 5 µs Max 20 µs*
X3-4: Typ 2 ms Max 10 ms
X1-2: Typ 5 µs Max 20 µs*
X3-4: Typ 3 ms Max 10 ms
Logic Side (4 points, green LED)
1 (4 points/common)
* Threshold level is 70% amplitude.
Internal Module Circuitry
Optical Isolator
Input
X1-X2
+
+
To high
response
circuit
24
VDC
Optical Isolator
+
+
Input
X3-X4
24
VDC
COM
C1
C0-02DR-D Temperature Derating Chart
4
Inputs
3
Points
Input Impedance
NOTE: When using Analog
PLCs, you must use CLICK
programming software version V1.12 or later.
IMPORTANT: You can use only one terminal (voltage
or current) per channel. You must also select the
analog type (voltage or current) in the CPU built-in
I/O setup in the CLICK programming software (pulldown menu Setup > CPU Built-in I/O Setup).
X1 - X4
Input Current
30 VDC Resistive
300,000 cycles
30 VDC Solenoid
50,000 cycles
120 VAC Resistive
500,000 cycles
120 VAC Solenoid
200,000 cycles
ON to OFF = 1 cycle
See Analog I/O
Specifications Voltage & Current
Input
(AD1V through AD2I)
Transmitter
P/S
4 (Source/Sink)
Inputs per Module
Operating Voltage Range 24 VDC
21.6 - 26.4 VDC
Input Voltage Range
Voltage & Load Type Load Current: 1 A
See Analog I/O
Specifications - Voltage
& Current Output
(DA1V through DA2I)
DA1V
TX3
Typical Relay Life (Operations)
at Room Temperature
*
2
1
0
0
32
10
50
20
68
30
85
40
104
50 55 °C
122 131 °F
Surrounding Air Temperature (°C/°F)
* Use every other input.
There are no ZIPLink
pre-wired PLC connection cables and modules
for the Analog PLCs.
(Cannot mix discrete I/O
and analog I/O signals
in a ZIPLink cable.)
Book 1 (14.3)
eCL-62
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Analog PLC
Company
Information
Internal Module Circuitry
6-27 VDC
6-240 VAC
Y1 - Y4
C0-02DR-D Discrete I/O Specifications - Outputs
Output Type
AC Frequency
Maximum Current
Minimum Load Current
Maximum Inrush Current
OFF to ON Response
ON to OFF Response
Status Indicators
Commons per Module
Fuse
4
6-27 VDC6 (-15%/+10%)/
6-240 VAC (-10%/+10%)
Relay, form A (SPST)
47-63 Hz
1 A/point
5 mA @ 5 VDC
3 A for 10 ms
< 15 ms
< 15 ms
Logic Side (4 points, red LED)
1 (4 points/common)
Do-More
PLCs Overview
*
COM
C2
Do-More H2
PLC
Do-More T1H
PLC
Outputs
3
None
DirectLOGIC
DL105
*
2
1
DirectLOGIC
DL205
0
0
32
C0-02DR-D Analog Specifications - Voltage Input
2 (voltage/current selectable)
Number of Channels
0 - 5 VDC (6 VDC Max.)
Input Range
12 bit
Resolution
50 ms
Conversion Time
150 kq
Input Impedance
±2 LSB maximum
Input Stability
±1.2% maximum
Full-Scale Calibration Error
±5 mV maximum
Offset Calibration Error
Accuracy vs. Temperature Error ±100 ppm / °C maximum
Analog Voltage Input Circuit
10
50
20
68
30
85
40
104
50 55 °C
122 131 °F
DirectLOGIC
DL305
Surrounding Air Temperature (°C/°F)
* Use every other output.
C0-02DR-D Analog Specifications - Current Input
2 (voltage/current selectable)
Inputs per Module
4 - 20 mA (sink)
Input Range
12 bit
Resolution
50 ms
Conversion Time
200 q
Input Impedance
±2 LSB
Input Stability
±1% maximum
Full-Scale Calibration Error
±0.1 mA maximum
Offset Calibration Error
Accuracy vs. Temperature Error ±100 ppm / °C maximum
Internal Module Circuitry
ADxV
A/D
Converter
ACOM
150kΩ
A/D
Converter
ACOM
+
Transmitter
P/S
Transmitter
P/S
C0-02DR-D Analog Specifications - Voltage Output
Outputs per Module
Output Range
Resolution
Conversion Time
2 (voltage/current selectable)
0 - 5 VDC
12 bit
1 ms
2 kq minimum (output current
Load Impedance
2.5 mA maximum)
±0.8% maximum
Full-Scale Calibration Error
±5 mV maximum
Offset Calibration Error
Accuracy vs. Temperature Error ±100 ppm / °C maximum
Outputs per Module
Output Range
Resolution
Conversion Time
Loop Supply Voltage
2 (voltage/current selectable)
4 - 20 mA (sink)
12 bit
1 ms
DC 18 - 30 V
250q
Load Power Supply:
DC 18V: 600q maximum
Load Impedance
DC 24V: 900q maximum
DC 30V: 1200q maximum
±1% maximum
Full-Scale Calibration Error
±0.1 mA maximum
Offset Calibration Error
Accuracy vs. Temperature Error ±100 ppm / °C maximum
Analog Current Output Circuit
Analog Voltage Output Circuit
DAxV
ACOM
Internal Module Circuitry
DAxI
Internal Module Circuitry
D/A
Converter
Load
250Ω
typical
D/A
Converter
ACOM
100Ω
+
Transmitter P/S
18-30VDC
Book 1 (14.3)
www.automationdirect.com/click-plc
Universal
Field I/O
Software
Other HMI
C0-02DR-D Analog Specifications - Current Output
DA1V - DA2I
Productivity
3000
ViewMarq
Industrial
Marquees
200Ω
+
Productivity
2000
C-More Micro
HMI
ADxI
Current
Transmitter
DirectLOGIC
DL405
C-More
HMI
Analog Current Input Circuit
Internal Module Circuitry
Load
2kΩ minimum
DirectLOGIC
DL05/06
C0-02DR-D Temperature Derating Chart
4
AD1V - AD2I
Voltage
Transmitter
DirectLOGIC
PLCs Overview
* Varistor Joule Rating: 20 J
This circuit does not contain built-in protection.
Install protection elements such as a fuse outside the module if necessary.
Points
Operating Voltage Range
CLICK PLC
OUTPUT
Y1-Y4
L
Outputs per Module
Control Systems
Overview
Equivalent Output Circuit
C0-02DR-D (cont’d)
CLICK PLCs
eCL-63
Communications
Appendix
Book 1
Terms and
Conditions
Prices as of October 15, 2015. Check Web site for most current prices.
Choosing Expansion I/O Modules
Analog I/O Modules
(continued)
Analog Combo I/O Modules
C0-4AD2DA-1
C0-4AD2DA-2
0-20mA In
4-20mA Out
0-10V
CH1
0V
CH1
0V
INPUT
INPUT
CH2
0V
CH2
0V
CH3
0V
CH3
0V
CH4
0V
CH4
0V
CH1
0V
CH1
0V
OUTPUT
OUTPUT
CH2
0V
CH2
0V
24V
0V
24V
0V
C0-4AD2DA-1
C0-4AD2DA-2
Analog Combo I/O Modules
Part Number
C0-4AD2DA-1
C0-4AD2DA-2
General Specifications
For All CLICK PLC
Products
These general specifications apply to all
CLICK PLCs, optional I/O modules, and
optional power supply products. Please
refer to the appropriate I/O temperature
derating charts under both the PLC and
I/O module specifications to determine
best operating conditions based on the
ambient temperature of your particular
application.
Analog Input Type
Analog Output Type
4 channel, current (0-20 mA),
13 bit
4 channel, voltage (0-10 V),
13 bit
2 channel, current sourcing
(4-20 mA), 12 bit
4 channel, voltage
(0-10 V), 12 bit
External Power
Required
24 VDC
24 VDC
General Specifications
Power Input Voltage Range
Maximum Power Consumption
Maximum Inrush Current
Acceptable External Power Drop
Operating Temperature
Storage Temperature
Ambient Humidity
Environmental Air
Vibration
Shock
Noise Immunity
Emissions
Agency Approvals
Other
20-28 VDC
5 W (No 5 V use from communication port)
30 A (less than 1ms)
Max 10 ms
Analog, analog combo I/O modules only: 32°F to 140°F (0°C to 60°C);
All other modules: 32°F to 131°F (0°C to 55°C), IEC 60068-2-14 (Test
Nb, Thermal Shock)
–4°F to 158°F (–20°C to 70°C)
IEC 60068-2-1 (Test Ab, Cold)
IEC 60068-2-2 (Test Bb, Dry Heat)
IEC 60068-2-14 (Test Na, Thermal Shock)
30% to 95% relative humidity (non–condensing)
No corrosive gases. Environmental pollution level is 2 (UL840)
MIL STD 810C, Method 514.2, EC60068-2-6
JIS C60068-2-6 (Sine wave vibration test)
MIL STD 810C, Method 516.2, IEC60068-2-27, JIS C60068-2-27
Comply with NEMA ICS3-304, Impulse noise 1μs, 1000V
EN61000-4-2 (ESD), EN61000-4-3 (RFI), EN61000-4-4 (FTB)
EN61000-4-5 (Surge), EN61000-4-6 (Conducted)
EN61000-4-8 (Power frequency magnetic field immunity)
RFI: No interference measured at 150 and 450 MHz (5w/15cm)
EN55011:1998 Class A
UL508 (File No. E157382, E316037); CE (EN61131-2)
RoHS
Book 1 (14.3)
eCL-40
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
CLICK Specifications
Company
Information
Control Systems
Overview
CLICK PLC
PLC Unit Specifications
Do-More
PLCs Overview
Basic, Standard and Analog PLC Unit Specifications
Control Method
I/O Numbering System
Ladder Memory (steps)
Total Data Memory (words)
Contact Execution (boolean)
Typical Scan (1k boolean)
RLL Ladder Style Programming
Run Time Edits
Scan
CLICK Programming Software for
Windows
Built-in Communication Ports
FLASH Memory
Built-in Discrete I/O points
Built-in Analog I/O Channels
Number of Instructions Available
Control Relays
System Control Relays
Timers
Counters
Interrupt
Subroutines
For/Next Loops
Math (Integer and Hex)
Drum Sequencer Instruction
Internal Diagnostics
Password Security
System Error Log
User Error Log
Memory Backup
Battery Backup
Calendar/Clock
I/O Terminal Block Replacement
Communication Port & Terminal
Block Replacement
24 VDC Power Terminal Block
Replacement
Do-More H2
PLC
Basic PLC
Standard PLC
Analog PLC
Stored Program/Cyclic
execution method
Stored Program/Cyclic
execution method
Stored Program/Cyclic
execution method
Fixed in Decimal
8000
8000
< 0.6us
1-2 ms
Yes
No
Variable / fixed
Fixed in Decimal
8000
8000
< 0.6us
1-2 ms
Yes
No
Variable / fixed
Fixed in Decimal
8000
8000
< 0.6us
1-2 ms
Yes
No
Variable / fixed
Yes
Yes
Yes
DirectLOGIC
DL205
Yes (two RS-232 ports)
Yes (two RS-232 ports and
one RS-485 port)
Yes (two RS-232 ports and
one RS-485 port)
DirectLOGIC
DL305
Standard on PLC
8 inputs, 6 outputs
No
21
2000
1000
500
250
Yes (external: 8 / timed: 4)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Super Capacitor
No
ADC p/n C0-16TB
Standard on PLC
8 inputs, 6 outputs
No
21
2000
1000
500
250
Yes (external: 8 / timed: 4)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Super Capacitor + Battery
Yes (battery sold separately;
part # D2-BAT-1)
Yes
ADC p/n C0-16TB
Standard on PLC
4 inputs, 4 outputs
2 inputs, 2 outputs
21
2000
1000
500
250
Yes (external: 4 / timed: 4)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Super Capacitor + Battery
Yes (battery sold separately;
part # D2-BAT-1)
Yes
ADC p/n C0-16TB
N/A
ADC p/n C0-3TB
ADC p/n C0-3TB
Appendix
Book 1
ADC p/n C0-4TB
ADC p/n C0-4TB
ADC p/n C0-4TB
Terms and
Conditions
No
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL405
Productivity
2000
Productivity
3000
Universal
Field I/O
Software
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Communications
Book 1 (14.3)
www.automationdirect.com/click-plc
CLICK PLCs
eCL-41
Prices as of October 15, 2015. Check Web site for most current prices.
CLICK Specifications
PLC Units Specifications (continued)
Ethernet Basic and Standard PLC Unit Specifications
Control Method
I/O Numbering System
Ladder Memory (steps)
Total Data Memory (words)
Contact Execution (boolean)
Typical Scan (1k boolean)
RLL Ladder Style Programming
Run Time Edits
Scan
CLICK Programming Software for
Windows
Built-in Communication Ports
FLASH Memory
Built-in Discrete I/O points
Built-in Analog I/O Channels
Number of Instructions Available
Control Relays
System Control Relays
Timers
Counters
Interrupt
Subroutines
For/Next Loops
Math (Integer and Hex)
Drum Sequencer Instruction
Internal Diagnostics
Password Security
System Error Log
User Error Log
Memory Backup
Battery Backup
Calendar/Clock
I/O Terminal Block Replacement
Communication Port & Terminal
Block Replacement
24 VDC Power Terminal Block
Replacement
Ethernet Basic PLC
Ethernet Standard PLC
Stored Program/Cyclic execution method
Fixed in Decimal
8000
8000
< 0.2us
< 1ms
Yes
Yes
Variable / fixed
Stored Program/Cyclic execution method
Fixed in Decimal
8000
8000
< 0.2us
< 1ms
Yes
Yes
Variable / fixed
Yes
Yes
Yes (one Ethernet port and
one RS-232 port)
Standard on PLC
8 inputs, 6 outputs
No
21
2000
1000
500
250
Yes (external: 8 / timed: 4)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Super Capacitor + Battery
Yes (battery part # D2-BAT-1)
Yes
ADC p/n C0-16TB
Yes (one Ethernet port, one RS-232 port and
one RS-485 port)
Standard on PLC
8 inputs, 6 outputs
No
21
2000
1000
500
250
Yes (external: 8 / timed: 4)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Super Capacitor + Battery
Yes (battery part # D2-BAT-1)
Yes
ADC p/n C0-16TB
N/A
ADC p/n C0-3TB
ADC p/n C0-4TB
ADC p/n C0-4TB
Book 1 (14.3)
eCL-42
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
CLICK Specifications
Company
Information
Control Systems
Overview
PLC Features
CLICK PLC
Basic PLCs
Standard PLCs
Mounting
Tab
Mounting
Tab
Sliding
Latch
PLC Mode
Switch
8 Discrete
Input
Points
LED Status
Indicators
Do-More
PLCs Overview
PLC Mode
Switch
Sliding
Latch
C0-01DD1-D
LED Status
Indicators
Do-More H2
PLC
8 Discrete
Input
Points
PWR
RUN
ERR
PORT1
RX1
6 Discrete
Output
Points
Communication
Ports
TX2
6 Discrete
Output
Points
RX2
PORT2
PORT3
RS-485
TX3
RX3
Sliding
Latch
Power
Terminal
24V
0V
N.C.
G
Mounting
Tab
Sliding
Latch
Power
Terminal
24V
0V
N.C.
G
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
TX1
Communication
Ports
Do-More T1H
PLC
Mounting
Tab
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
2000
Productivity
3000
Universal
Field I/O
Software
C-More
HMI
Analog PLCs
PLC Mode
Switch
C0-02DD1-D
C-More Micro
HMI
Bottom of PLC
(Same on all models)
Mounting
Tab
ViewMarq
Industrial
Marquees
Sliding
Latch
Other HMI
C1
X1
X2
X3
LED Status
Indicators
PWR
X4
RUN
C2
ERR
Y1
Y2
PORT1
Y3
TX1
Y4
RX1
+V
AD1V
Communication
Ports
TX2
AD1II
AD1
RX2
AD2V
PORT2
PORT3
4 Discrete
Inputs
4 Discrete
Outputs
2 Analog
Inputs
Communications
Power
Terminal
al
24V
0V
N.C.
G
Appendix
Book 1
Terms and
Conditions
AD2II
AD2
RS-485
ACOM
DA1V
TX3
DA1II
DA1
RX3
DA2V
2 Analog
Outputs
DA2II
DA2
Power
Terminal
24V
0V
N.C.
G
Sliding
Latch
Mounting
Tab
Book 1 (14.3)
www.automationdirect.com/click-plc
CLICK PLCs
eCL-43
Prices as of October 15, 2015. Check Web site for most current prices.
CLICK Specifications
PLC Features (continued)
Ethernet Basic PLCs
Ethernet Standard PLCs
Mounting
Tab
C0-10DD1E-D
C0-10DD1E-D
D
PLC Mode
Switch
C1
X2
2
PWR
RUN
RUN
RUN
ERR
Communication
Ports
X3
3
X4
4
STOP
STOP
X5
5
LNK/ACT
ETHER
NET
100MBIT
X6
6
TX2
RX2
RS-232
RS
232
C1
1
X1
1
LED Status
Indicators
X2
2
PWR
RUN
RUN
RUN
R
PWR
RUN
ERR
X8
8
C3
3
Y1
6 Discrete
Output
Points
Y2
2
Y3
3
Y4
4
Communication
Ports
PO
RT3
PORT3
PO
ORT
ORT3
T3
TX
X3
TX
TX3
3
Y6
6
RX
RX
X3
3
RX3
+V
V
S
Sliding
Latch
L
Mounting
Tab
8 Discrete
Input
Points
C2
2
X6
6
X7
7
X8
8
C3
3
PORT2
X2
TX2
TX2
X
RX2
RX2
PORT2
PORT2
RS 232
RS-232
Y5
5
Sliding
Latch
X5
5
LNK/ACT
PO
PORT
ORT1
ORT1
PORT1
ETHER
NET
TX
TX
X1
TX1
100MBIT
RX
X
X1
RX1
X7
7
X3
3
X4
4
STOP
STOP
ERR
PORT1
C4
4
Power
wer
Terminal
rminal
24V
0V
N.C.
G
C0-11DD1E-D
C0-11DD1EC0-01DD1-D
C0C0
01DD1-D
01DD1
-D
D
PLC Mode
Switch
C2
2
PORT1
PORT2
S
Sliding
Latch
L
8 Discrete
Input
Points
X1
LED Status
Indicators
Mounting
Tab
Y1
1
Y2
2
Y3
3
Y4
4
RS-485
R
RS-4
RS-485
S
S-4
485
85 5
+
_
LG
G
C4
4
6 Discrete
Output
Points
Y5
5
Y6
6
+V
V
Sliding
Latch
Power
Terminal
24V
0V
N.C.
G
Mounting
Tab
Bottom of Ethernet PLC
(Same on all models)
Power
Terminal
al
24V
0V
N.C.
G
Book 1 (14.3)
eCL-44
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
CLICK Specifications
Company
Information
Control Systems
Overview
PLC LED Status Indicators
Power Good
Off
Power Failure
Do-More
PLCs Overview
Basic CPUs
Basic PLC
POWER LED (Green)
On
CLICK PLC
Do-More H2
PLC
Do-More T1H
PLC
RUN LED (Green)
On
PLC Run Mode
Initializing
Blink System
PLC Program
Off Mode
DirectLOGIC
PLCs Overview
INPUT LEDs (Green)
On
Input True
Off
Input False
DirectLOGIC
DL05/06
ERROR LED (RED)
Self Diagnostic
Error
Self
Diagnostic
Blink Warning
DirectLOGIC
DL105
On
Off
DirectLOGIC
DL205
OUTPUT LEDs (Red)
No Error
TX & RX LED (Green)
On Comm Port Data Active
On
Output True
Off
Output False
DirectLOGIC
DL305
Off No Communication
DirectLOGIC
DL405
On
Power Good
Off
Power Failure
Productivity
3000
C0-01DD1-D
RUN LED (Green)
On
Universal
Field I/O
PLC Run Mode
Initializing
Blink System
PLC Program
Off Mode
ERROR LED (RED)
Self Diagnostic
Error
Self
Diagnostic
Blink Warning
On
Off
Productivity
2000
Standard PLC
Standard
CPUs
POWER LED (Green)
No Error
TX & RX LED (Green)
On Comm Port Data Active
INPUT LEDs (Green)
PWR
RUN
ERR
On
Input True
Off
Input False
PORT1
TX1
C-More
HMI
C-More Micro
HMI
RX1
TX2
RX2
OUTPUT LEDs (Red)
PORT2
PORT3
Software
RS-485
TX3
RX3
On
Output True
Off
Output False
ViewMarq
Industrial
Marquees
Other HMI
Off No Communication
Communications
On
Power Good
Off
Power Failure
Analog CPUs
RUN LED (Green)
On
ERROR LED (RED)
Diagnostic
On Self
Error
Diagnostic
Blink Self
Warning
Off
No Error
TX & RX LED (Green)
On Comm Port Data Active
Off No Communication
Terms and
Conditions
C0-02DD1-D
C1
PLC Run Mode
Initializing
Blink System
PLC Program
Off Mode
Appendix
Book 1
Analog PLC
POWER LED (Green)
X1
X2
INPUT LEDs (Green)
On
Input True
Off
Input False
X3
PWR
X4
RUN
C2
ERR
Y1
Y2
PORT1
Y3
TX1
Y4
RX1
+V
OUTPUT LEDs (Red)
On
Output True
Off
Output False
AD1V
TX2
AD1 I
RX2
AD2V
PORT2
PORT3
AD2 I
RS-485
ACOM
DA1V
TX3
DA1 I
RX3
DA2V
DA2 I
Book 1 (14.3)
www.automationdirect.com/click-plc
CLICK PLCs
eCL-45
Prices as of October 15, 2015. Check Web site for most current prices.
CLICK Specifications
PLC LED Status Indicators
POWER LED (Green)
On
Power Good
Off
Power Failure
Ethernet Basic PLC
Ethernet Basic CPU
RUN LED (Green)
On
Initializing
Blink System
PLC Program
Off Mode
ERROR LED (RED)
Diagnostic
On Self
Error
Diagnostic
Blink Self
Warning
Off
C0-10DD1E-D
C0-10D
D1E--D
D
PLC Run Mode
No Error
C1
X1
X2
PWR
RUN
R
ERR
X4
STOP
S
C2
2
PORT1
X5
LNK/ACT
ETHER
NET
100MBIT
X6
Input True
Off
Input False
X8
C3
3
PORT2
Y1
TX2
Y2
RX2
OUTPUT LEDs (Red)
Y3
Y4
LNK/ACT LED (Green)
C4
4
Connected to the network
Y6
Y5
On
Output True
Off
Output False
+V
V
Blink Communicating
Off
On
X7
RS-232
RS
232
On
INPUT LEDs (Green)
X3
RUN
Disconnected from the network
100MBIT LED (Orange)
TX & RX LED (Green)
On
Communicating at 100Mbps
On Comm Port Data Active
Off
Communicating at 10Mbps or
disconnected from the network
Off No Communication
POWER LED (Green)
On
Power Good
Off
Power Failure
Ethernet Standard PLC
Standard Ethernet PLC
C0-11DD1E-D
C0-11D
D1E--D
D
RUN LED (Green)
On
Initializing
Blink System
PLC Program
Off Mode
ERROR LED (RED)
Self Diagnostic
Error
Diagnostic
Blink Self
Warning
On
Off
C1
1
PLC Run Mode
No Error
X1
X2
2
PWR
RUN
ERR
On
Connected to the network
X3
3
X4
4
STOP
STOP
C2
2
PORT1
X5
5
LNK/ACT
ETHER
NET
100MBIT
X6
6
Input True
Off
Input False
C3
3
Y1
Y2
2
RX2
Y3
3
RS-232
RS
232
RX
X3
RX3
On
X8
8
TX2
TX3
TX
X3
INPUT LEDs (Green)
X7
7
PORT2
PO
ORT3
PORT3
LNK/ACT LED (Green)
RUN
RUN
Y4
4
RS-485
RS-485
485
5
+
_
LG
G
C4
4
Y5
5
Y6
6
OUTPUT LEDs (Red)
On
Output True
Off
Output False
+V
V
Blink Communicating
Off
Disconnected from the network
TX & RX LED (Green)
100MBIT LED (Orange)
On Com Port Data Active
On
Communicating at 100Mbps
Off No Communication
Off
Communicating at 10Mbps or
disconnected from the network
Book 1 (14.3)
eCL-46
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Product Dimensions and Installation
Ground Braid
Copper Lugs
It is important to understand the
installation requirements for your CLICK
system.
Your knowledge of these
requirements will help ensure that your
system operates within its environmental
and electrical limits.
Panel or
Single Point
Ground
Panel
Star Washers
Plan for Safety
This catalog should never be used as a
replacement for the user manual.
Star Washers
2 in.
50.8 mm
minimum
You can purchase, download free, or view
online the user manuals for these products. Manual C0-USER-M is the user
manual for the CLICK PLC. The user
manual contains important safety information that must be followed. The system
installation should comply with all appropriate electrical codes and standards.
2 in.
50.8mm
minimum
3 in.
76.2 mm
minimum
NOTE: There is a mimimum clearance requirement of 2 inches(51 mm)
between the CLICK PLC and the panel door or any devices mounted in
the panel door. The same clearance is required between the PLC and any
side of the enclosure. A minimum clearance of 3 inches (76 mm) is required
between the PLC and a wireway or any heat producing device.
PORT1
TX1
RX1
TX2
RX2
PORT2
RUN
PWR
RUN
ERR
CLICK PLCs must be mounted properly to ensure ample airflow for cooling
purposes. It is important to follow the
unit orientation requirements and to verify
that the PLC’s dimensions are compatible
with your application. Notice particularly
the grounding requirements and the
recommended cabinet clearances.
STOP
Mounting Orientation
Air
Flow
Book 1 (14.3)
eCL-24
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Product Dimensions and Installation
Company
Information
Control Systems
Overview
Latch tabs
Connecting the Modules
Together
CLICK PLC
3
Do-More
PLCs Overview
Connecting Modules
CLICK PLCs, I/O modules and power
supplies connect together using the
extension ports that are located on the
side panels of the modules (no PLC backplane/base required).
1. R
emove extension port covers and slide
the latch tabs forward.
2. A
lign the module pins and connection
plug, and press the I/O module
onto the right side of the PLC.
3. S lide the latch tabs backward to lock
the modules together.
Do-More H2
PLC
2
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
1
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
2000
Supports up to eight I/O modules
Productivity
3000
Universal
Field I/O
DIN Rail Mounting
Mounting
Surface Mounting
Upper
Mounting Tab
Software
C-More
HMI
The CLICK PLC system, which includes the
CLICK power supplies, PLC units, and I/O
modules, can be mounted in one of two
ways.
1. D
IN rail mounted
2. S urface mounted using the built-in
upper and lower mounting tabs.
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Pull tab
down.
Push tab
up until...
Lower
Mounting Tab
Click
Communications
Appendix
Book 1
Power Supply
Module
Unit Dimensions
The dimensional drawings here and on
the next page show the outside dimensions of the CLICK power suppy, PLC,
and I/O modules. The CLICK PLC system
is designed to be mounted on standard
35mm DIN rail, or it can be surface
mounted.
Allow proper spacing from
components within an enclosure.
2.6
[0.102]
PLC Unit
34.9
[1.37]
53.5
[2.11]
Unit Dimensions
mm [inches]
I/O Module
27
[1.06]
13.5
[0.46]
Terms and
Conditions
75
[2.95]
85
5
[3.35]
.35]
5
other
Maximum system:
4
[0.16]
Power Supply + PLC + 8 I/O modules.
"
9.2
[0.36]
www.automationdirect.com/click-plc
9.4
[0.37]
Book 1 (14.3)
CLICK PLCs
eCL-25
Prices as of October 15, 2015. Check Web site for most current prices.
Product Dimensions and Installation
Unit Dimensions
Power Supply
mm [inches]
PLC Unit
I/O Module
Book 1 (14.3)
eCL-26
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Networking the CLICK PLC
Company
Information
Control Systems
Overview
Built-in Communications
Ports
Port 1 & 2 LED
Status Indicators
TX1 and TX2 (Green)
STOP
Off The Comm Port is not sending data.
PORT1
TX1
RX1
TX2
RX1 and RX2 (Green)
RX2
On The Comm Port is receiving data.
PORT2
Off The Comm Port is not receiving data.
Port 1, 2, & 3 LED
Status Indicators
RUN
ERR
TX1, TX2 and TX3 (Green)
PORT1
TX1
On The Comm Port is sending data.
RX1
Off The Comm Port is not sending data.
TX2
RX2
PORT2
RX1, RX2 and RX3 (Green)
On The Comm Port is receiving data.
Off The Comm Port is not receiving data.
PORT3
RS-485
TX3
RX3
Do-More T1H
PLC
Com Port 3
Standard and Analog PLCs
Basic PLC
Use: Programming Port / Serial Communications
(Slave only)
Physical: 6 pin, RJ12, RS-232
Communication speed (baud): 38400 (fixed)
Parity: Odd
Station Address: 1
Data length: 8 bits
Stop bit: 1
Protocol: Modbus RTU (slave only)
Use: Serial Communications
Physical: 6 pin, RJ12, RS-232
Communication speed (baud): 1200,
2400, 4800, 9600, 19200, 38400,
57600, 115200
Parity: odd, even, none
Station Address: 1 to 247
Data length: 8 bits (Modbus RTU) or
7, 8 bits (ASCII)
Stop bit: 1,2
Protocol: Modbus RTU
(master/slave) or ASCII in/out
Use: Serial Communications
Physical: 3 pin, RS-485
Communication speed (baud): 1200,
2400, 4800, 9600, 19200, 38400,
57600, 115200
Parity: odd, even, none
Station Address: 1 to 247
Data length: 8 bits (Modbus RTU) or
7, 8 bits ( ASCII)
Stop bit: 1,2
Protocol: Modbus RTU
(master/slave) or ASCII in/out
Default
-
Port 1
Port 1 Pin Descriptions
6 pin RJ12 Phone
Type Jack
1
Com Port 1 Specifications
Com Port 3
Specifications
Standard and Analog PLCs
Do-More H2
PLC
Com Port 2
Com Port 2
Com Port 2
Specifications
Basic PLCs
On The Comm Port is sending data.
Com Port 1
6
There are LED indicators located to the
left of each communications port to
indicate when the port is transmitting or
receiving.
Com Port 1
1
2
3
4
5
6
0V
5V
RXD
TXD
NC
0V
Power (-) connection (GND)
Power (+) connection
Receive data (RS-232)
Transmit data (RS-232)
No connection
Power (-) connection (GND)
Port 2
Port 2 Pin Descriptions
6 pin RJ12 Phone
Type Jack
38400
Odd
1
1
2
3
4
5
6
0V
5V
RXD
TXD
RTS
0V
Power (-) connection (GND)
Power (+) connection
Receive data (RS-232)
Transmit data (RS-232)
Request to send
Power (-) connection (GND)
8 bits
Port 3
RS-485
Port 3 Pin Descriptions
1
2
3
Signal A
(RS-485)
Signal B
- (minus)
(RS-485)
Logic
LG
Ground(0 V)
+ (plus)
DirectLOGIC
DL305
Productivity
2000
Productivity
3000
Universal
Field I/O
Software
Other HMI
Communications
Appendix
Book 1
Terms and
Conditions
8 bits
1
Modbus RTU
Port Setup
Use CLICK programming software to
easily configure the communications
ports.
Book 1 (14.3)
www.automationdirect.com/click-plc
DirectLOGIC
DL205
ViewMarq
Industrial
Marquees
Default
Odd
1
DirectLOGIC
DL105
C-More Micro
HMI
Modbus RTU
38400
DirectLOGIC
DL05/06
C-More
HMI
1
-
DirectLOGIC
PLCs Overview
DirectLOGIC
DL405
1
LED Status Indicators
Do-More
PLCs Overview
6
Basic, Standard and Analog PLCs have
two built-in RS-232 communications ports.
Standard and Analog PLCs also have one
built-in RS-485 communications port.
One RS-232 port supports the Modbus
RTU protocol only and can be used as the
programming port. The other ports support
either Modbus RTU or ASCII protocol. Both
RS-232 ports supply 5V DC, so you can
connect a monochrome C-more Micro HMI
panel without an additional power supply.
CLICK PLC
CLICK PLCs
eCL-27
Networking the CLICK PLC
Prices as of October 15, 2015. Check Web site for most current prices.
Built-in Communications
Ports
LNK/ACT LED (Green)
Blink Communicating
Off
RU
R
RUN
PWR
RUN
S
STOP
ERR
PORT1
Disconnected from the network
LNK/ACT
ETHER
NET
100MBIT
100MBIT LED (Orange)
PORT2
On
Communicating at 100Mbps
Off
Communicating at 10Mbps or
disconnected from the network
TX2
RX2
RS-232
RS
232
Ethernet Standard PLCs
Port 1
Com Port 1 Specifications
Port 1 Pin Descriptions
8 pin
RJ45
Phone
8 pin
RJ45
Type Jack
1
Use: Programming and Ethernet Communication
Physical: 8 pin, RJ45, Ethernet
Communication speed (Mbps): 10/100
Protocol: Modbus TCP
Use: Serial Communication
Physical: 6 pin, RJ12, RS-232
Communication speed (baud): 2400,
4800, 9600, 19200, 38400, 57600,
115200
Parity: odd, even, none
Station Address: 1 to 247
Data length: 8 bits (Modbus RTU) or
7, 8 bits (ASCII)
Stop bit: 1,2
Protocol: Modbus RTU
(master/slave) or ASCII in/out
Port 11 &
& 22 LED
Port
LED
StatusIndicators
Indicators
Status
Connected to the network
Com Port 3
Ethernet Basic PLC
Com Port 2
Specifications
Ethernet Basic PLCs
On
Com Port 2
Com Port 2
8
There are LED indicators located to
the left of each communication port to
indicate when the port is transmitting or
receiving.
Com Port 1
Default
-
1
2
3
4
5
6
7
8
Port 2
pin RJ12
RJ12 Phone
66pin
Phone
Type Jack
Type
Jack
38400
1
LED Status Indicators
Com Port 1
Odd
1
6
Ethernet Basic and Standard PLCs have one
built-in Ethernet communications port and
one RS-232 communications port. Ethernet
Standard PLCs also have one built-in
RS-485 communications port. The Ethernet
port supports the Modbus TCP protocol.
The RS-232 and RS-485 ports support either
Modbus RTU or ASCII protocol. The RS-232
port supplies 5 VDC, so you can connect a
monochrome C-more Micro HMI panel
without an additional power supply.
TX+
TXRX+
NC
NC
RXNC
NC
Transmit Data (+)
Transmit Data (-)
Receive data (+)
Not connected
Not connected
Receive Data (-)
No connection
No connection
Port 2 Pin Descriptions
1
2
3
4
5
6
0V
5V
RXD
TXD
RTS
0V
Power (-) connection (GND)
Power (+) connection
Receive data (RS-232)
Transmit data (RS-232)
Request to send
Power (-) connection (GND)
8 bits
1
Modbus RTU
TX2 (Green)
On The Comm Port is sending data.
Off The Comm Port is not sending data.
Com Port 3
Specifications
RX2 (Green)
On The Comm Port is receiving data.
Off The Comm Port is not receiving data.
Ethernet Standard PLCs
Port 1, 2 & 3 LED
Port
1, Indicators
2, & 3 LED
Status
Status Indicators
LNK/ACT LED (Green)
On
Connected to the network
Blink Communicating
Off
Disconnected from the network
RUN
ERR
100MBIT LED (Orange)
On
Communicating at 100Mbps
Off
Communicating at 10Mbps or
disconnected from the network
STOP
PORT1
38400
Port 3 Pin Descriptions
1
2
3
Signal A
(RS-485)
Signal B
- (minus)
(RS-485)
Logic
LG
Ground(0 V)
+ (plus)
Odd
1
8 bits
1
Modbus RTU
PORT2
Port Setup
RX2
RS-232
On The Comm Port is sending data.
PORT3
Off The Comm Port is not sending data.
TX3
RX2 and RX3 (Green)
-
Port 3
RS-485
RS-485
LNK/ACT
ETHER
NET
100MBIT
TX2
TX2 and TX3 (Green)
Use: Serial Communication
Physical: 3 pin, RS-485
Communication speed (baud): 2400,
4800, 9600, 19200, 38400, 57600,
115200
Parity: odd, even, none
Station Address: 1 to 247
Data length: 8 bits (Modbus RTU) or
7, 8 bits ( ASCII)
Stop bit: 1,2
Protocol: Modbus RTU
(master/slave) or ASCII in/out
Default
RX3
RS-485
+
_
LG
Use CLICK programming software to
easily configure the communication
ports.
On The Comm Port is receiving data.
Off The Comm Port is not receiving data.
Book 1 (14.3)
eCL-28
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Networking the CLICK PLC
Company
Information
Control Systems
Overview
CLICK PLC
Typical Communication Applications
Do-More
PLCs Overview
The diagrams on these three pages illustrate the typical uses for the CLICK PLC’s communication ports.
Port 1 (RS-232) – Modbus RTU Slave Mode Only
Do-More H2
PLC
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
Port 1
DirectLOGIC
DL05/06
C-more and C-more
Micro-Graphic Panel
PC
Another CLICK PLC
DirectLOGIC
DL105
Other Devices
Supporting Modbus RTU
Master Mode
Basic, Standard
and Analog PLC
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
C-more Micro-Graphic panels (monochrome models only) can get 5 VDC power
from Com port 1 or 2.
Example
Productivity
2000
C-more 3 Inch
Micro-Graphic
Panel
Productivity
3000
Universal
Field I/O
CLICK PLC
Port 1
Software
C-More
HMI
DV-1000CBL
serial cable
C-More Micro
HMI
The Color Micro-Graphic panel or the second
Monochrome Micro-Graphic panel needs a separate 24 VDC power source (see the note below).
ViewMarq
Industrial
Marquees
Port 1 or 2
Other HMI
NOTE: CLICK’s (RS-232) Port 1 and Port 2 can provide 5 VDC power to the panel, but not at the same time. If a C-more Micro-Graphic
panel is connected to both ports, then at least one of the panels must be powered by a C-more Micro DC power adapter, EA-MG-P1
or EA-MG-SP1, or another 24 VDC power source. Color C-more Micro-Graphic panels must also be powered from a separate 24 VDC
source.
Do not use the following Direct LOGIC devices with CLICK’s Port 1 or 2:
Warning: The following DirectLOGIC PLC devices cannot be used with a CLICK PLC’s Port 1 or Port 2:
Handheld Programmer for DL05, DL06, DL105, DL205 & D3-350 CPUs, p/n D2-HPP
Handheld Programmer for DL405 CPUs, p/n D4-HPP-1
Timer/Counter Access for DL05, DL06, DL105, DL205, DL405 & D3-350 CPUs, p/n DV-1000
D2-HPP
D4-HPP-1
DV-1000
Book 1 (14.3)
www.automationdirect.com/click-plc
CLICK PLCs
eCL-29
Communications
Appendix
Book 1
Terms and
Conditions
Prices as of October 15, 2015. Check Web site for most current prices.
Networking the CLICK PLC
Port 1 (Ethernet) – Modbus TCP
Modbus TCP Client (Master) Devices
Port 1
PC
All CLICK
Ethernet PLCs
Another CLICK
Ethernet PLC
Other Devices
Supporting
Modbus TCP
Client Mode
C-more Panel
Modbus TCP Server (Slave) Devices
Other Devices Supporting
Modbus TCP Server Mode
ViewMarq Display
Another CLICK
Ethernet PLC
SR55 Soft Starter
GS1 Drive
GS3 Drive
Book 1 (14.3)
eCL-30
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Networking the CLICK PLC
Company
Information
Control Systems
Overview
CLICK PLC
Port 2 (RS-232) – Modbus RTU or ASCII
Port 3 (RS-485; Standard, Ethernet Standard and Analog PLCs Only) – Modbus RTU or ASCII
All PLCs have RS-232 port 2, but only Standard, Analog and Ethernet Standard PLCs have RS-485 port 3.
Ports 2 and 3 allow networking to similar devices.
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
Port 2
Port 2
DirectLOGIC
PLCs Overview
Port 3
Modbus RTU
Modbus RTU Master Devices
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Basic PLC
Ethernet Basic PLC
Productivity
2000
Standard or Analog PLC
Ethernet Standard PLC
PC
Another CLICK PLC
Productivity
3000
Universal
Field I/O
See Note on previous page about
connecting a C-more Micro-Graphic
panel to Port 1 or 2.
Software
C-More
HMI
C-more and C-more
Micro-Graphic Panel
Other Devices
Supporting Modbus RTU
Master Mode
ASCII
Communications
Appendix
Book 1
Other devices
that can send
ASCII data.
Terms and
Conditions
Modbus RTU Slave Devices
Weigh Scale
Other Devices
Supporting Modbus
RTU Slave Mode
Devices that RECEIVE ASCII messages
Serial Printer
ViewMarq
Display
ViewMarq
Industrial
Marquees
Other HMI
Devices that SEND ASCII messages
Barcode
Reader
C-More Micro
HMI
Other devices
that can receive
ASCII data.
Another CLICK PLC
SOLO Temperature
Controller
(CLICK Port 3 Only)
Book 1 (14.3)
www.automationdirect.com/click-plc
CLICK PLCs
eCL-31
Prices as of October 15, 2015. Check Web site for most current prices.
Power Supplies
Power Supplies
The CLICK PLC family offers two 24 VDC
power supplies. They are identical except
for the output current.
It is not mandatory to use one of these
CLICK power supplies for the CLICK PLC
system. You can use any other 24 VDC
power supply that Automationdirect.com
offers, including the PSP24-DC12-1 12
VDC to 24 VDC converter shown below.
C0-00AC Power Supply
Limited auxiliary AC power supply allows
you to power the 24 VDC CLICK C0 series
PLCs with 100-240 VAC supply power.
The 0.5A DC power supply is capable of
controlling the PLC plus a limited configuration based on the power budget of each
I/O module. The C0-00AC is a lowcost solution for applications requiring
only minimal I/O and power consumption. This power supply will not support a
fully-populated CLICK PLC system with all
possible I/O module combinations.
C0-01AC Power Supply
Expanded auxiliary AC power supply allows
you to power the 24 VDC CLICK C0 series
PLCs with 100-240 VAC supply power.
The 1.3A DC power supply is capable
of supporting a fully-populated CLICK
PLC system with all possible I/O module
combinations, with no concerns for
exceeding the power budget.
PSP24-DC12-1 DC-DC Converter
With this DC-DC converter you can
operate the CLICK PLC with 12 VDC input
power.
CLICK 24 VDC Power Supply Ratings
Part Number
C0-00AC
C0-01AC
Output Current
Price
0.5 A
1.3 A
$29.00
$39.00
C0-00AC
C0-00AC Power Supply Specifications
Input Voltage Range
Input Frequency
Input Current (typical)
Inrush Current
Output Voltage Range
Output Current
Over Current Protection
Weight
85-264 VAC
47-63 Hz
0.3 A @ 100 VAC, 0.2 A @ 200 VAC
30 A
23-25 VDC
0.5 A
@ 0.65 A (automatic recovery)
5.3 oz (150g)
C0-01AC Power Supply Specifications
Input Voltage Range
Input Frequency
Input Current (typical)
Inrush Current
Output Voltage Range
Output Current
Over Current Protection
Weight
85-264 VAC
47-63 Hz
0.9 A @ 100 VAC, 0.6 A @ 200 VAC
30 A
23-25 VDC
1.3 A
@ 1.6 A (automatic recovery)
6.0 oz (170g)
85-264 VAC
Power Source
Input Terminals
PSP24-DC12-1 DC-DC Converter Specifications
Input Voltage Range
Input Power (no load)
Startup Voltage
Undervoltage Shutdown
Output Voltage Range
Output Current
Short Circuit Protection
Weight
CLICK Power Supply
24 VDC
Output Power
Terminals
(for CLICK PLC, I/O or
field device, etc.)
9.5-18 VDC
1.0 W max.
C0-01AC
8.4 VDC
7.6 VDC
24-28 VDC (adjustable)
1.0 A
Current limited at 110% typical
7.5 oz (213g)
CLICK PLC
24 VDC
Output Power
Terminals
(for CLICK PLC, I/O or
field device, etc.)
85-264 VAC
Power Source
Input Terminals
PSP24-DC12-1
24V
0V
G
24 VDC power is supplied to the PLC
unit through wiring connected from the
power supply output to the 4-pin 24 VDC
input connector located on the bottom
of the PLC unit.
Book 1 (14.3)
eCL-32
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Power Budgeting
Company
Information
Control Systems
Overview
Power Budgeting
There are two areas to be considered when determining the
power required to operate a CLICK PLC system. The first area
is the power required by the CLICK PLC, along with the internal
logic side power that the CPU provides to its own I/O and any
connected I/O modules that are powered through the PLC
expansion port; plus any device, such as a C-more Micro-Graphic
panel, that is powered through one of the communications ports.
It is strongly recommended that the power source for the logic
side be separate from the power source for the field side to help
eliminate possible electrical noise.
The second area is the power required by all externally connected
I/O devices. This should be viewed as the field side power
required. The field side power is dependent on the voltage used
for a particular input or output device as it relates to the wired
I/O point, and the calculated load rating of the connected device.
Refer to the Power Budgeting example shown on the following
page. The table shows required current for a CLICK PLC, two
I/O modules, and a C-more Micro. Use the total amperage
values to select the properly sized power supply.
Power budgeting requires the calculation of the total current the
24 VDC power source needs to provide to CLICK’s logic side,
and also a separate calculation of the total current required for all
devices operating from the field side of the PLC system.
CLICK PLC
Do-More
PLCs Overview
Do-More H2
PLC
Do-More T1H
PLC
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
2000
Productivity
3000
CLICK 24 VDC Power Supply
C0-00AC or C0-01AC
Other 24 VDC Power Supply
Example: PSP24-60S
Universal
Field I/O
Software
PLC Current Consumption (mA)
Part Number
Power Budget External
24 VDC
24 VDC
(logic side) (field side)
Basic PLC Units
120
60
C0-00DD1-D
C0-00DD2-D
120
0
C0-00DR-D
C0-00AR-D
Standard PLC Units
140
60
C0-01DD1-D
C0-01DD2-D
C0-01DR-D
140
0
C0-01AR-D
Analog PLC Units
140
60
C0-02DD1-D
C0-02DD2-D
140
0
C0-02DR-D
Ethernet Basic PLC Units
120
60
C0-10DD1E-D
C0-10DD2E-D
120
0
C0-10DRE-D
C0-10ARE-D
Ethernet Standard PLC Units
140
60
C0-11DD1E-D
C0-11DD2E-D
140
0
C0-11DRE-D
C0-11ARE-D
I/O Module Current Consumption (mA)
Power Budget External
24 VDC
24 VDC
(logic side) (field side)
Discrete Input Modules
Part Number
30
C0-08ND3
30
C0-08ND3-1
40
C0-16ND3
30
C0-08NE3
40
C0-16NE3
30
C0-08NA
Discrete Output Modules
50
C0-08TD1
50
C0-08TD2
80
C0-16TD1
80
C0-16TD2
80
C0-08TA
100
C0-04TRS
100
C0-08TR
0
0
0
0
0
0
15
0
100
0
0
0
0
I/O Module Current Consumption
(continued) (mA)
Power Budget External
Part Number
24 VDC
24 VDC
(logic side) (field side)
Discrete Combo I/O Modules
80
50
C0-16CDD1
80
0
C0-16CDD2
80
0
C0-08CDR
Analog Input Modules
20
65
C0-04AD-1
23
65
C0-04AD-2
25
0
C0-04RTD
25
0
C0-04THM
Analog Output Modules
20
145
C0-04DA-1
20
85
C0-04DA-2
Analog Combo I/O Modules
25
75
C0-4AD2DA-1
20
65
C0-4AD2DA-2
C-more Micro-Graphic Panel
Monochrome
90
0
only
Book 1 (14.3)
www.automationdirect.com/click-plc
CLICK PLCs
eCL-33
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Communications
Appendix
Book 1
Terms and
Conditions
Prices as of October 15, 2015. Check Web site for most current prices.
Power Budgeting
Power Budgeting Using the
CLICK Programming Software
The CLICK Programming software can also
be used for power budgeting. Based on the
amperage rating of the power supply selected
in the first column, your power budget is
calculated by subtracting each consecutive
module’s power consumption from the total
available power budget. If you exceed the
maximum allowable power consumption the
power budget row is highlighted in red.
Power Budgeting Example
Current Consumption (mA) Example
Part Number
C0-00DD1-D
C0-16ND3
C0-16TD1
C-more Micro
Total:
Power Budget External
24 VDC
24 VDC
(logic side) (field side)
120
40
80
90
330
60
0
100
0
160*
* Add in calculated load of connected I/O devices.
Power Supply
(C0-01AC)
PLC Module
(C0-00DD1-D)
I/O Module
(C0-16ND3)
Port 1
or
Port 2
I/O Module
(C0-16TD1)
C-more
Micro-Graphic
Panel
Only monochrome models
can be powered from port 1 or 2.
Book 1 (14.3)
eCL-34
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Wiring System for CLICK PLCs
Wiring Solutions using the ZIPLink Wiring System
ZIPLinks eliminate the normally tedious process of wiring between
devices by utilizing prewired cables and DIN rail mount connector
modules. It’s as simple as plugging in a cable connector at either
end or terminating wires at only one
end. Prewired cables keep installation clean and efficient, using half the
space at a fraction of the cost of standard terminal blocks.
ZIPLinks are available in a variety of styles to suit your needs,
including feedthrough connector module. ZIPLinks are available for all Basic, Standard and Ethernet CLICK PLC units and
most discrete and analog I/O modules.
Pre-printed I/O-specific adhesive label
strips for quick marking of ZIPLink
modules are provided with ZIPLink cables.
Solution 1: CLICK PLC and I/O Modules to ZIPLink
Connector Modules
When looking for quick and easy I/O-to-field termination, a ZIPLink
connector module used in conjunction with a prewired ZIPLink
cable, consisting of an I/O terminal block at one end and a multipin connector at the other end, is the best solution.
Use the “CLICK PLC PLC Unit ZIPLink Selector” table and
CLICK I/O ZIPLink selector tables located in this section:
1. Locate your PLC or I/O module.
2. Select a ZIPLink Module.
3. Select a corresponding ZIPLink Cable.
Solution 2: CLICK PLC and I/O Modules to 3rd
Party Devices
When wanting to connect I/O to another device within close proximity of the I/O modules, no extra terminal blocks are necessary
when using the ZIPLink Pigtail Cables. ZIPLink Pigtail Cables are
prewired to an I/O terminal block with color-coded pigtail with
soldered-tip wires on the other end.
Use the I/O Modules to 3rd Party Devices selector tables
located in the ZIPLink section:
1. Locate your PLC or I/O module.
2. S elect a ZIPLink Pigtail Cable that
is compatible with your 3rd party
device.
Solution 3: GS Series and DuraPulse Drives
Communication Cables
Need to communicate via Modbus RTU to a drive or a network of
drives?
ZIPLink cables are available in a wide range of
configurations for connecting to PLCs and SureServo, SureStep,
Stellar Soft Starter and AC drives. Add a ZIPLink communications
module to quickly and easily set up a multi-device network.
Use the Drives Communication selector tables located in the
ZIPLink section:
1. Locate your Drive and type of communications.
2. Select a ZIPLink cable and other associated hardware.
Solution 4: Serial Communications Cables
ZIPLink offers communications cables for use with CLICK PLCs that
can also be used with other communications devices. Connections
include a 6-pin RJ12 connector which can be used in conjunction
with the RJ12 Feedthrough module.
Use the Serial Communications Cables selector table located
in the ZIPLink section:
1. Locate your connector type
2. Select a cable.
Book 1 (14.3)
eCL-48
CLICK PLCs
1-800-633-0405
Prices as of October 15, 2015. Check Web site for most current prices.
Wiring System for CLICK PLCs
Company
Information
Control Systems
Overview
PLC
PLC Unit
C0-00DD1-D
C0-00DD2-D
C0-00DR-D
C0-00AR-D
C0-01DD1-D
C0-01DD2-D
C0-01DR-D
C0-01AR-D
C0-10DD1E-D
C0-10DD2E-D
C0-10DRE-D
C0-10ARE-D
C0-11DD1E-D
C0-11DD2E-D
C0-11DRE-D
C0-11ARE-D
C0-02DD1-D
C0-02DD2-D
C0-02DR-D
CLICK PLC ZIPLink Selector
ZIPLink
# of Terms Component
Module
Part No.
CLICK PLC Discrete Output Module ZIPLink Selector
I/O Module
ZIPLink
Cable
Part No.
C0-08TD1
C0-08TD2
C0-08TR
C0-08TA
20
Feedthrough
ZL-RTB20
ZL-C0-CBL20 *
# of Terms Component
11
Module
Part No.
Feedthrough
ZL-RTB20
Feedthrough
Fuse
Relay (sinking)
Feedthrough
ZL-RTB20
ZL-RFU20 2
ZL-RRL16-24-1
ZL-RTB20
Cable
Part No.
ZL-C0-CBL11 *
20
No ZIPLinks are available for analog PLC Units.
Part
# of Terms Component Module
No.
C0-08ND3
C0-08ND3-1
C0-08NE3
C0-08NA
11
C0-16ND3
20
C0-16NE3
20
Feedthrough
ZL-RTB20
Feedthrough
Sensor
Feedthrough
Sensor
ZL-RTB20
ZL-LTB16-24
ZL-RTB20
ZL-LTB16-24
Cable Part
No.
ZL-C0-CBL11 *
ZL-C0-CBL20 *
1 Note: The C0-04TRS relay output is derated not to exceed 2A per point maximum
when used with the ZIPLink wiring system.
2 Note: Fuses (5 x 20 mm) are not included. See Edison Electronic Fuse section
for (5 x 20 mm) fuse. S500 and GMA electronic circuit protection for fast-acting
maximum protection. S506 and GMC electronic circuit protection for time-delay
performance. Ideal for inductive circuits.
To ensure proper operation, do not exceed the voltage and current rating of
ZIPLink module. ZL-RFU20 = 2A per circuit.
Do-More H2
PLC
Do-More T1H
PLC
C0-16TD1
20
ZL-C0-CBL20*
C0-16TD2
20
Fuse
ZL-RFU20 2
ZL-C0-CBL20 *
C0-04TRS1
20
Relay (sourcing)
Feedthrough
ZL-RRL16-24-2
ZL-RTB20
DirectLOGIC
DL105
ZL-C0-CBL20 *
DirectLOGIC
DL205
Combo
Module
C0-16CDD1
C0-16CDD2
C0-08CDR
# of Terms Component
Module
Part No.
Cable
Part No.
20
Feedthrough
ZL-RTB20
ZL-C0-CBL20 *
11
Feedthrough
ZL-RTB20
ZL-C0-CBL11 *
CLICK PLC Analog I/O Module ZIPLink Selector
I/O Module
ZIPLink
Analog
Module
C0-04AD-1
C0-04AD-2
C0-04RTD
C0-04THM
C0-04DA-1
C0-04DA-2
C0-4AD2DA-1
C0-4AD2DA-2
# of
Terms
11
11
20
11
11
11
20
20
Component
Feedthrough
Feedthrough
Module
Part No.
ZL-RTB20
ZL-RTB20
Cable
Part No.
ZL-C0-CBL11 *
ZL-C0-CBL11 *
No ZIPLinks are available for RTD and thermocouple
modules.
Feedthrough
Feedthrough
Feedthrough
Feedthrough
ZL-RTB20
ZL-RTB20
ZL-RTB20
ZL-RTB20
ZL-C0-CBL11 *
ZL-C0-CBL11 *
ZL-C0-CBL20 *
ZL-C0-CBL20 *
* Select the cable length by replacing the * with: Blank = 0.5m, -1 = 1.0m,
or -2 = 2.0m.
DirectLOGIC
DL05/06
DirectLOGIC
DL305
DirectLOGIC
DL405
Productivity
2000
Productivity
3000
Universal
Field I/O
Software
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Communications
Appendix
Book 1
Terms and
Conditions
Book 1 (14.3)
www.automationdirect.com/click-plc
Do-More
PLCs Overview
DirectLOGIC
PLCs Overview
CLICK PLC Combo I/O Module ZIPLink Selector
I/O Module
ZIPLink
CLICK PLC Discrete Input Module ZIPLink Selector
I/O Module
ZIPLink
Input
Module
Output
Module
CLICK PLC
CLICK PLCs
eCL-49