counter Read Counter Input Module Syntax #include <ctools.h> long counter(unsigned counter); Description The counter function reads data from the counter input specified by channel. If the channel number is not valid a COUNTER_BADCOUNTER error is reported for the current task. The value returned by counter is not valid. Notes Refer to the TelePACE Ladder Logic User Manual for an explanation of counter input channel assignments. Use offsets from the symbolic constants COUNTER_START and COUNTER_END to reference counter channels. The constants make programs more portable and protect against future changes to the counter input channel numbering. The IO_SYSTEM resource must be requested before calling this function. This function is provided for backward compatibility. It cannot access all 5000 series I/O modules. It is recommended that this function not be used in new programs. Instead use Register Assignment or call the I/O driver ioRead4Counter directly. See Also counterError, check_error, request_resource, release_resource, ioRead4Counter TelePACE C Tools User and Reference Manual May 9, 2007 99