Download Hardware Manual - ICP DAS USA`s I

Transcript
WinCON 8000
Compact Windows CE.NET Controller
Hardware User’s Manual
REV 4.1.0.01a
2003/10/3
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 1
Warranty
All products manufactured by ICP DAS are warranted against defective
materials for a period of one year from the date of delivery to the
original purchaser.
Warning
ICP DAS assumes no liability for damages consequent to the use of this
product. ICP DAS reserves the right to change this manual at any time
without notice. The information furnished by ICP DAS is believed to be
accurate and reliable. However, no responsibility is assumed by ICP
DAS for its use, nor for any infringements of patents or other rights of
third parties resulting from its use.
Copyright
Copyright 2003 by ICP DAS. All rights are reserved.
Trademark
The names used for identification only maybe registered trademarks of
their respective companies.
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 2
Table of Contents
•
INTRODUCTION ......................................................................................4
•
PACKAGE LIST & RELEASE NOTE ...................................................................................................................................4
•
WINCON 8000 SERIES.......................................................................................................................................................5
•
CONTENTS OF CD AND CF MEMORY CARD .......................................................................................................................7
•
HARDWARE INFORMATION ...............................................................8
•
FRONT VIEW OF WINCON8000 .........................................................................................................................................8
•
SPECIFICATIONS ................................................................................................................................................................9
•
APPLICATIONS ......................................................................................10
•
QUICK START ........................................................................................11
•
MECHANICAL INFORMATION .........................................................12
5.1
DIMENSIONS………………………………………………………………………………………………..…….12
5.2
DIMENSIONS RAIL MOUNTING….………………………………………………………………………………..12
5.3
WALL MOUNTING……………………………………………………………………………………………….12
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 3
•
Introduction
• Package List & Release Note
Package List
In addition to this manual, the package includes the following items:
One set of WinCon 8000 hardware
One Compact Flash Memory Card for storing system files
One hardware user’s manual (this manual)
One release note
One software utility CD with Software User’s Manual included
Note
If any of these items are missing or damaged, contact the local distributors for
more information. Save the shipping materials and cartons in case you want to
ship in the future.
Release Note
It is recommended that you read the release note & README.TXT first.
The release note is included in the box. And the README.TXT is given in the
CD\README.TXT. Some important information is provided in the release
note & CD\README.TXT
Ordering Information
Call distributor for details.
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 4
• WinCon 8000 Series
The WinCon 8000 is the flagship compact embedded controller manufactured by ICP
DAS. Its leading technology gives you all of the best features of both traditional PLCs
and Windows capable PCs. The WinCon 8000 system is powered by Windows
CE.NET and brings Windows programming style and skill into the world of PC-based
PLCs. Application developers can directly develop their own programs in Microsoft’s
Visual Studio .NET and Embedded Visual tools with the WinCon SDK, and then
download them into WinCon 8000 for use. Or, they can port their favorite SCADA
software onto WinCon 8000 for even easier application development. For SCADA
applications, we also provide a product model embedded with InduSoft Web Studio
run-time version to meet this need.
The model type of WinCon-8000 is defined as W-8X3X, as shown in the above
figure. The Second number shows the number of slots coming with the main
controller unit. Currently, we provide two types: 3 and 7 slots. The last number
defines the application platform and may be 1, 0, 7 or 9. 1 stands for the Master
controller and it means that users need to design the application program by
themselves. 0 represents the slave controller and it means ICP DAS will provide a
firmware in the system to run the default application. However, this function will be
released in the future and depends on client requests. The number 7 indicates the
IsaGraf soft PLC application platform and that means the user can develop and run
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 5
the soft PLC program within the controller. The number 9 provides the SCADA
application platform with InduSoft Web studio Run-time version on the system. And
that means the user can use the development tool InduSoft Web studio to develop the
application and download it to the controller.
For more detailed product
specifications, please refer to the following product model table.
Model
Description
W-8331
W-8731
W-8337
W-8737
Embedded
Controller
ISaGRAF
Embedded
Controller
W-8339
W-8739
InduSoft
Embedded
Controller
CPU
Speed
206MHz
206MHz
206MHz
Embedded
OS
Windows
CE .NET
Windows
CE .NET
Windows
CE .NET
Slot
Flash
SDRAM
3
7
3
7
32
Mbyte
64Mbyte
32
Mbyte
64Mbyte
32
Mbyte
64Mbyte
3
7
Peripherals
10BaseT Ethernet
Port×1
VGA Port×1
CF Slot×1
USB×1
PS/2 Keyboard×1
PS/2 Mouse×1
RS-232×1
RS-485×1
FRnet×1(Option)
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 6
• Contents of CD and CF memory card
CD :
WinCon8000 SDK
WinCon Utilities
Source code for demo programs
Software User’s Manual
InduSoft User’s Manual
References are given in ReadMe.txt in the CD
CF memory card (default is 128 Mbytes):
WinCon8000 System files
WinCon Utilities
Demo programs
InduSoft system (for W-8739/W-8339 only)
Directories for FTP server and Http server
References are given in Software User’s Manual bundled CD
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 7
• Hardware Information
The WinCon 8000 system competes in performance with Industrial PCs, but is
lower in price. The system provides VGA and PS/2 keyboard/mouse ports for
local visualization and management. Users’ control programs and data can be
saved in persistent storage via Compact Flash and USB interfaces. Also, there
is communications capability via the built-in Ethernet and RS 232/485
interfaces.
• Front View of WinCon8000
The following figure shows the WinCon8000 hardware. Included are the main
controller with HMI, serial communication, FR net interface and I/O expansion
interface.
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 8
• Specifications
Main Control Unit
Intel Strong ARM CPU, 206MHz
SRAM: 64M bytes
Flash Memory: 32M bytes
EEPROM: 16K bytes
64-bit hardware unique serial
number
Built-in Watchdog Timer
Real Time Clock
10 Base T: NE2000 compatible
1 VGA port:
320x240x16 to 1024x768x16
Default is 640x480x16
2 PS/2 port: Keyboard and Mouse
1 Compact Flash slot: CF memory card
1 USB 1.1 Host: USB drive or USB
mouse
Reset button
Power LEDs
Cabinet
COM0: Internal use
COM1: Serial Control for 87K Series Modules in Slots
COM2: RS-232
COM3: RS-485
FRnet(Option)
I/O Expansion Slots:
3-slot for W-8331
7-slot for W-8731
Power Supply: 20W, Unregulated +10Vdc to +30Vdc
Environment:
Operating Temp.: -25°C to +75°C
Storage Temp.: -30°C to +85°C
Humidity: 5~95%
Dimensions:
418x110x75.5mm(7 slot)
418x110x75.5mm(3 slot)
I/O module (optional)
I-8000 serial modules, which include DI, DO, AO, AI...
I-87K serial modules, which include DI, DO, AO, AI...
I-7000 serial modules, which include DI, DO, AO, AI... (external, via RS-485 port)
For more information, please refer to the relevant catalog or http://www.icpdas.com.
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 9
• Applications
The following figure shows the general application areas and structure. Com2
is the standard RS232 interface, which can be connected with a modem.
Com3 is the RS-485 interface, which can be used to control ICP DAS DCON I7000 serial modules, I-8000 controllers and I-87K expansion racks. The
FRnet system is an optional control interface.
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 10
• Quick Start
Step 1. Make sure the bundled CF memory card is in the CF slot.
Step 2. Plug in your PS/2 keyboard and mouse.
Step 3. Plug in your VGA monitor.
Step 4. Connect the WinCon8000 to your LAN
Step 5. Insert your 8K/87K series I/O modules into the I/O expansion slots.
Step 6. Connect the COM ports to your external devices.
Step 7. Connect DC power and turn it on.
Step 8. Windows CE .NET starts up. Please refer to the software user’s manual
for further operations and developing your own applications.
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 11
• Mechanical Information
5.1 Dimensions
5.2 DIN Rail Mounting
5.3 Wall Mounting
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 12
5.4 Controller cover
A cover protects the reset button and provides note writing areas on the top of
the WinCon. The I/O Unit area is used to record what expansion modules are
placed in each slot. The Memo area is for general use. The access
procedure is as below:
Step 1: Use hand to push down the cover.
Step 2: Swing open the cover, as shown in the below figure.
The Expansion I/O setting record is on the main controller unit. The memo
area is on the inside of the cover, as shown below. Note that the reset key
access hole is at the upper right corner of the protected area.
(a)
(b)
WinCon8000 Series Hardware user’s Manual, October/2003, 4.1.0.01a 13
(c)