[Wiring Precautions]
The conversion adapter can be used in combination with the following MELSEC-Q series modules.
Do not touch live terminals. There is a danger of electric shock or malfunction.
Shut off the external power supply for the system in all phases before cleaning or
retightening the terminal screws. Failure to do so may result in electric shock or cause the
MELSEC-Q Series module to fail or malfunction. Loose screws can lead to dropping,
shorting, and malfunction. Excessive tightness of the screws can lead to breakage of the
screws, Conversion Adapter, Mounting Bracket, or MELSEC-Q Series Module, possibly
causing the dropping, shorting, and malfunction thereof.
HEAD OFFICE: Hulic KUDAN BLDG.1-13-5,KUDANKITA CHIYODA-KU,TOKYO 102-0073,JAPAN
NAGOYA ENGINEERING OFFICE:139 SHIMOYASHIKICHO-SHIMOYASHIKI,KASUGAI,AICHI 486-0906,JAPAN
 SAFETY PRECAUTIONS 
CAUTION
CAUTION
Do not modify the Conversion Adapter or take it apart. Doing so will cause failure,
malfunction, personal injury, or fire.

Do not drop the Conversion Adapter and Mounting Bracket or do not give a strong impact
to it. This will cause damage.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or minor injury and/or property damage.
Note that failure to observe the
CAUTION level instructions may lead to a serious consequence
according to the circumstances. Always follow the precautions of both levels because they are important
to personal safety.
Please keep this manual in an easy-to-access location for future reference, and be sure to provide the
manual to the end user.
[Precautions before using]
CAUTION
 When making a switch to the MELSEC-Q Series, be sure to consult user's manual supplied
with individual module under the MELSEC-Q Series to confirm differences in various aspects
including performance, function, CPU input/output signals between the two modules.
Round-shaped non-insulated
solderless terminal

When installing the Conversion Adapter, take care not to get your hand snagged on the
Mounting Bracket or the like. Injury may result.

When installing or removing the MELSEC-Q Series Module complete with a Converter
Adapter, be sure to hold it with both hands. Dropping may lead to breakage.
[Wiring Precautions]

Before attempting to install the Unit or carry out the necessary wiring, make certain that the
external power supply, used in the system, is shut off on all three phases. Failure to do so may
result in electric shock or damage to the product.
After installation and wiring, close the terminal block cover before turning on the module for
operation. Failure to do so may result in electric shock.
CAUTION


Carry out wiring for the Conversion Adapter correctly after checking the specification and
terminal arrangement for the module used. Connecting a power supply with a different
voltage rating or incorrect wiring may cause a fire or failure.
Tighten the terminal installation screws and terminal screw securely by applying torque
within the specified limits. Loose screws will cause short circuit, fire or malfunction.
Excessive tightening will damage the screws or the Conversion Adapter which in turn will
cause dropping of parts, short circuit or malfunction.
Round-shaped solderless terminal
with an insulation sleeve
MIN 3.5(※)
MIN
φ3.7
MIN
φ3.7
Y-shaped non-insulated
solderless terminal
MIN 3.5(※)
●Terminal block shape
QY10,QY22
MAX 4.2
TB1
Y00
TB2
Y01 TB3
Y02
TB4
Y03 TB5
Y04
TB6
Y05 TB7
Y06
TB8
Y07 TB9
Y08
TB10
Y09 TB11
Y0A
TB12
Y0B TB13
Y0C
TB14
Y0D TB15
Y0E
TB16
Y0F TB17
COM
TB18
Open TB19
Open
TB20
Open
M3.5 screw
Authorized representative in Europe
5.0 4.2
Authorized representative in Europe is shown below.
Name: Mitsubishi Electric Europe BV
Address: Gothaer strasse 8, 40880 Ratingen, Germany
QY10
(3) Internal connection
Terminal
block
Shape
Quantity
Product
Conversion Adapter
Shape
TB6
Quantity
TB9
TB11
TB12
TB13
TB14
TB15
TB16
1
TB17
TB18
1
TB20
Open
TB19
Open
1
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
MELSEC-Q Series
module
TB2
TB4
TB6
TB8
TB10
TB12
TB14
TB16
TB18
(4) External connection
QX10,QX40,QX40-S1,QX50,QX70
Specifications
Terminal
block
0 to 55℃(Maximum surrounding air temperature 55℃)
TB1
X00
TB2
X01 TB3
X02
TB4
X03 TB5
X04
TB6
X05 TB7
X06
TB8
X07 TB9
X08
TB10
X09 TB11
X0A
TB12
X0B TB13
X0C
TB14
X0D TB15
X0E
TB16
X0F TB17
COM
TB18
Open TB19
Open
TB20
Open
-25 to 75℃
5 to 95%RH,non-condensing
Frequency
Compliant with
Under
5 to 8.4Hz
JIS B 3502 intermittent
8.4 to 150Hz
and
vibration
IEC 61131-2
Under
5 to 8.4Hz
continuous
8.4 to 150Hz
vibration
Constant
Half
acceleration amplitude
-
3.5mm
9.8m/s
2
1.75mm
-
4.9m/s
-
Sweep count
10 times each in
X, Y, Z directions
2
-
-
Compliant with JIS B 3502 and IEC 61131-2
Shock resistance
(147 m/s2, 3 times each in 3 directions X, Y, Z)
Operating atmosphere
No corrosive gases
Operating altitude *1
0 to 2000m
Installation location
Inside a control panel
Overvoltage category *2
II or less
Pollution degree *3
2
*1:Do not use or store under pressure higher than the atmospheric pressure of altitude 0m.
*2:This indicates the section of the power supply to which the equipment is assumed to be connected between
the public electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
*3:This index indicates the degree to which conductive material is generated in terms of the environment in
which the equipment is used.
Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by
condensing must be expected occasionally.
Power
supply(※)
※Power supply
QX40
QX10
QX40-S1
~
100VAC
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
QX50
Signal
name
X00
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
COM
Open
Open
Open
QX70
~
24VDC
5/12VDC
48V
AC/DC
24VDC
QX80H
QX90H
24VDC
5VDC
24VDC
5VDC
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Power
supply(※)
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
Signal
name
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
Y0F
DC
COM
Open
Open
~
12/24VDC 5/12VDC
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Terminal
block
TB1
Y00
TB2
Y01 TB3
Y02
TB4
Y03 TB5
Y04
TB6
Y05 TB7
Y06
TB8
Y07 TB9
Y08
TB10
Y09 TB11
Y0A
TB12
Y0B TB13
Y0C
TB14
Y0D TB15
Y0E
TB16
Y0F TB17
COM
TB18
0V TB19
Open
TB20
Open
QY18A
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
12/24VDC
Signal
name
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
Y0F
COM
0V
Open
Open
Terminal
block
TB1
Y00
TB2
Y00 TB3
Y01
TB4
Y01 TB5
Y02
TB6
Y02 TB7
Y03
TB8
Y03 TB9
Y04
TB10
Y04 TB11
Y05
TB12
Y05 TB13
Y06
TB14
Y06 TB15
Y07
TB16
Y07 TB17
Open
TB18
Open TB19
Open
TB20
Open
L
Power supply(※)
L
Power supply(※)
L
Power supply(※)
L
Power supply(※)
L
Power supply(※)
L
Power supply(※)
L
Power supply(※)
L
Power supply(※)
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
Signal
name
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Open
Open
Open
Open
※Power supply
QX80
TB1
X00
TB2
X01 TB3
X02
TB4
X03 TB5
X04
TB6
X05 TB7
X06
TB8
X07 TB9
X08
TB10
X09 TB11
X0A
TB12
X0B TB13
X0C
TB14
X0D TB15
X0E
TB16
X0F TB17
Open
TB18
COM TB19
Open
TB20
Open
QX70H
※Power supply
QY40P
QY70
QY50
QY80
TB1
TB3
TB5
TB7
TB9
TB11
TB13
TB15
TB17
Terminal
block
QX40H
100/200VAC
or
24VDC
1
-
TB1
Y00
TB2
Y01 TB3
Y02
TB4
Y03 TB5
Y04
TB6
Y05 TB7
Y06
TB8
Y07 TB9
Y08
TB10
Y09 TB11
Y0A
TB12
Y0B TB13
Y0C
TB14
Y0D TB15
Y0E
TB16
Y0F TB17
DC
TB18
COM TB19
Open
TB20
Open
100 to 240VAC
TB19 and TB20 are
open terminals.
2.General Specifications
Vibration
resistance
TB7
TB10
2
This manual
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
TB5
TB8
Terminal block
Mounting bracket
TB3
TB4
Once you have opened the packaging, verify that it contains the following products.
Product
TB1
TB2
Terminal
block
QY22
~
ERNT-ASQTB20
This manual describes specifications, handling and other information about the Conversion Adapter
“ERNT-ASQTB20” available as Renewal Tools for the Mitsubishi General-Purpose Programmable
Controller.
Before attempting to make a switch to MELSEC-Q Series in your installation, consult the user's
manual supplied with individual module under the latter series to learn about how they differ in various
aspects including performance and function.
Signal
name
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
Y0F
COM
Open
Open
Open
※Power supply
1.Overview
Power
supply(※)
Signal
name
X00
X01
X02
X03
X04
X05
X06
X07
COM1
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
COM2
Open
Open
QY40P,QY50,QY70
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Power
supply(※)
Terminal
block
Unit:mm
Power
supply(※)
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
※Power supply
※The minimum length is 5.0 mm when the solderless terminal is attached up side down as shown below.
Compliance to the EMC Directive, which is one of the EU Directives, has been a legal obligation
for the products sold in European countries since 1996 as well as the Low Voltage Directive
since 1997.
Manufacturers who recognize their products are compliant to the EMC and Low Voltage
Directives are required to declare that print a "CE mark" on their products.
TB1
X00
TB2
X01 TB3
X02
TB4
X03 TB5
X04
TB6
X05 TB7
X06
TB8
X07 TB9
COM1
TB10
X08 TB11
X09
TB12
X0A TB13
X0B
TB14
X0C TB15
X0D
TB16
X0E TB17
X0F
TB18
COM2 TB19
Open
TB20
Open
MIN 3.5(※)
Solderless terminal
EMC AND LOW VOLTAGE DIRECTIVES
Terminal
block
Y-shaped solderless terminal
with an insulation sleeve
When disposing of the product, treat it as industrial waste.
WARNING

QY68A
TB1
X00
TB2
Open TB3
X01
TB4
Open TB5
X02
TB6
Open TB7
X03
TB8
Open TB9
X04
TB10
Open TB11
X05
TB12
Open TB13
X06
TB14
Open TB15
X07
TB16
Open TB17
COM
TB18
~
Open TB19
Open 100 to 240VAC
TB20
Open
Unit:mm
MAX 4.2
CAUTION
 Fasten the Conversion Adapter and the Mounting Bracket securely with retaining screws, and
tighten the screws by applying torque within specified limits. Loose screws can lead to the
dropping of the Conversion Adapter or Mounting Bracket, possibly causing breakage thereof.
Excessive tightness of the screws can lead to breakage of the screws, Conversion Adapter,
Mounting Bracket, or MELSEC-Q Series Module, possibly causing the dropping, shorting, and
malfunction thereof.
QX50
●Applicable solderless terminal
CAUTION
Mounting bracket fixing
screws (M3.5 x 6)
 Do not directly touch any conductive parts of Conversion Adapter. Contact will cause
malfunction or failure in the system.
QX40H
QX90H
QY50
Terminal block
[Installation Precautions]
 Use the Conversion Adapter in the environmental conditions that are specified in the general
specification. If the Products are used in any environment beyond the bounds of the general
specification, electric shock, fire, malfunction, or damage to or degradation of the Products will
result.
QX40-S1
QX80H
QY40P
(2) Specifications of the terminal block (conversion adapter accessory)
[Disposal Precautions]

QX40
QX80
QY22
7.3
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
I/O Combined
MIN 3.5(※)

(Always read these precautions prior to use.)
Before using this product, please read this manual carefully and pay full attention to safety to ensure that
the product is used correctly.
The precautions presented in this manual are concerned with this product only. For Programmable
Controller system safety precautions, refer to the user’s manual of the MELSEC-Q series CPU module to
be used.
In this manual, the safety precautions are ranked as “WARNING” and “CAUTION.”
Output
QX28
QX70H
QY18A
QY80
Terminal
block
Signal
name
X00
Open
X01
Open
X02
Open
X03
Open
X04
Open
X05
Open
X06
Open
X07
Open
COM
Open
Open
Open
MIN
3.7

50CM-D180201-A(1509)
MELSEC-Q Series module model
QX10
QX70
QY10
QY70
QX48Y57
Input

User’s Manual
WARNING
Input/Output
WARNING
QX40H,QX70H,QX80H,QX90H
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
MAX
7.3
ERNT-ASQTB20
MIN
3.7
[Startup and Maintenance Precautions]
MAX
7.3
Model
(1) MELSEC-Q Series module
MAX
7.3
Conversion Adapter
Use care to prevent foreign materials including cuttings and wiring debris from entering the
Conversion Adapter or the MELSEC-Q Series Module. These will be cause for fire, failure
or malfunction.
For the details of specifications of the MELSEC-Q series modules not described herein, refer to the user's manual of
the applicable MELSEC-Q series module. Also, check that the specifications of the connected devices meet
the specifications of the MELSEC-Q series module.
MAX
7.3

QX28
3.Product Specifications
CAUTION
8.4
Mitsubishi General-Purpose Programmable Controller
Renewal Tool
~
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
Signal
name
X00
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
Open
COM
Open
Open
100/200VAC
or
24VDC
QY68A
QX48Y57
L
Terminal
block
TB1
Sink
Y00
TB2
Y00 TB3
Y01
TB4
Y01 TB5
Y02
TB6
Y02 TB7
Y03
TB8
Y03 TB9
Y04
TB10
Y04 TB11
Y05
TB12
Source
Y05 TB13
Y06
TB14
Y06 TB15
Y07
TB16
Y07 TB17
Open
TB18
Open TB19
Open
TB20
Open
5 to 24VDC
L
5 to 24VDC
L
5 to 24VDC
L
5 to 24VDC
5 to 24VDC
5 to 24VDC
5 to 24VDC
L
L
L
5 to 24VDC
L
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
Signal
name
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Open
Open
Open
Open
Terminal
block
TB1
X00
TB2
X01 TB3
X02
TB4
X03 TB5
X04
TB6
X05 TB7
X06 24VDC
TB8
X07 TB9
L
COM1
TB10
L
Y08 TB11
L
Y09
TB12
Y0A TB13
L
Y0B
TB14
L
Y0C TB15
L
Y0D
TB16
Y0E TB17
L
DC
TB18
COM2 TB19
Open
TB20
Open
12/24VDC
Terminal
No.
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
Signal
name
X00
X01
X02
X03
X04
X05
X06
X07
COM1
Y08
Y09
Y0A
Y0B
Y0C
Y0D
Y0E
DC
COM2
Open
Open
Model
Input impedance
Response OFF to ON
time
ON to OFF
Internal current consumption
Common terminal
arrangement
Model
16 points
Photocoupler isolation
100 to 120VAC(+10/-15%) 50/60Hz(±3Hz)
8 points
Photocoupler isolation
100 to 240VAC (+10/-15%) 50/60Hz(±3Hz)
Approx.17mA(200VAC,60Hz)
Approx. 8mA(100VAC,60Hz)
Approx.14mA(200VAV,50Hz)
Approx. 7mA(100VAC,50Hz)
Approx.8mA(100VAC,60Hz)
Approx.7mA(100VAC,50Hz)
Max. 200mA within 1ms (132VAC)
Max. 950mA within 1ms (264VAC)
80VAC or higher/5mA or higher(50Hz,60Hz) 80VAC or higher/5mA or higher(50Hz,60Hz)
30VAC or lower/1.7mA or lower(50Hz,60Hz) 30VAC or lower/1.7mA or lower(50Hz,60Hz)
Approx. 12kΩ(60Hz)
Approx. 12kΩ(60Hz)
Approx. 15kΩ(50Hz)
Approx. 15kΩ(50Hz)
15ms or less (100VAC 50Hz,60Hz)
10ms or less (100VAC 50Hz,60Hz)
20ms or less (100VAC 50Hz,60Hz)
15ms or less (100VAC 50Hz,60Hz)
50mA(TYP. All points ON)
50mA(TYP. All points ON)
16 points/common
8 points/common
QX40
(Positive common)
Specification
QX50
(Positive/Negative shared
common,AC)
QX40-S1
(Positive common)
Number of input points
Isolation method
16 points
Photocoupler isolation
Rated input voltage
24VDC (+20/-15%)
Rated input current
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response OFF to ON
time
ON to OFF
Internal current
consumption
Common terminal
arrangement
Approx. 4mA
19V or higher/3mA or higher
11V or lower/1.7mA or lower
Approx. 5.6kΩ
1/5/10/20/70ms or less
1/5/10/20/70ms or less
16 points
Photocoupler isolation
48VDC
48VAC (+10/-15%)
24VDC (+20/-15%)
(+20/-15%) 50/60Hz(±3Hz)
Approx. 6mA
Approx. 4mA
19V or higher/4.0mA or higher 28V or higher/2.5mA or higher
11V or lower/1.7mA or lower 10V or lower/1.0mA or lower
Approx. 3.9kΩ
Approx. 11.2kΩ
0.1/0.2/0.4/0.6/1ms or less
5ms or less 15ms or less
0.1/0.2/0.4/0.6/1ms or less
20ms or less 20ms or less
50mA(TYP. all points ON)
60mA(TYP. all points ON)
Model
Specification
Number of input points
Isolation method
Rated input voltage
Rated input current
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response OFF to ON
time
ON to OFF
Internal current
consumption
Common terminal
arrangement
16 points/common
16 points/common
50mA(TYP. all points ON)
16 points/common
QX70
QX80
(Positive/Negative shared common)
(Negative common)
16 points
16 points
Photocoupler isolation
Photocoupler isolation
5VDC(+20/-10%) 12VDC(+20/-15%) 24VDC (+20/-15%)
Approx. 1.2mA Approx. 3.3mA
Approx. 4mA
3.5V or higher/1mA or higher
19V or higher/3mA or higher
1V or lower/0.1mA or lower
11V or lower/1.7mA or lower
Approx. 3.3kΩ
Approx. 5.6kΩ
1/5/10/20/70ms or less
1/5/10/20/70ms or less
1/5/10/20/70ms or less
1/5/10/20/70ms or less
QX40H
(Positive common)
16 points
Photocoupler isolation
24VDC (+20/-15%)
Approx. 6mA
13V or higher/3mA or higher
8V or lower/1.6mA or lower
Approx. 3.9kΩ
0.1/0.2/0.4/0.6/1ms or less
0.1/0.2/0.4/0.6/1ms or less
55mA(TYP. all points ON)
50mA(TYP. all points ON)
80mA(TYP. all points ON)
16 points/common
16 points/common
8 points/common
Model
QX70H
(Positive common)
QX80H
(Negative common)
QX90H
(Negative common)
16 points
Photocoupler isolation
5VDC(+20/-15%)
Approx. 6mA
3.5V or higher/3mA or higher
1V or lower/1mA or lower
Approx. 470Ω
0.1/0.2/0.4/0.6/1ms or less
0.1/0.2/0.4/0.6/1ms or less
16 points
Photocoupler isolation
24VDC(+20/-15%)
Approx. 6mA
13V or higher/3mA or higher
8V or lower/1.6mA or lower
Approx. 3.9kΩ
0.1/0.2/0.4/0.6/1ms or less
0.1/0.2/0.4/0.6/1ms or less
16 points
Photocoupler isolation
5VDC(+20/-15%)
Approx. 6mA
3.5V or higher/3mA or higher
1V or lower/1mA or lower
Approx. 470Ω
0.1/0.2/0.4/0.6/1ms or less
0.1/0.2/0.4/0.6/1ms or less
80mA(TYP. all points ON)
80mA(TYP. all points ON)
80mA(TYP. all points ON)
8 points/common
8 points/common
8 points/common
Specification
Number of input points
Isolation method
Rated input voltage
Rated input current
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response OFF to ON
time
ON to OFF
Internal current
consumption
Common terminal
arrangement
16 points
Photocoupler isolation
②Output module
Model
QY10
Specification
Number of output points
Isolation method
16 points
Relay isolation
24VDC 2A(resistive load)/point
240VAC 2A(COSΦ=1)/point
8A/common
5VDC 1mA
264VAC 125VDC
10ms or less
12ms or less
No
No
430mA(TYP. all points ON)
16 points/common
Rated switching voltage,
current
Minimum switching load
Maximum switching load
OFF to ON
Response
time
ON to OFF
Surge suppressor
Fuse
Internal current consumption
Common terminal arrangement
Model
Model
8 points
Relay isolation
24VDC 2A(resistive load)/point
240VAC 2A(COSΦ=1)/point
8A/module
5VDC 1mA
264VAC 125VDC
10ms or less
12ms or less
No
No
240mA(TYP. all points ON)
All points independent
QY22
Specification
Number of output points
Isolation method
Rated load voltage
Maximum load current
Maximum inrush current
Leaked current at OFF
Maximum voltage drop at ON
Response OFF to ON
time
ON to OFF
Surge suppressor
Fuse
Internal current consumption
Common terminal arrangement
QY18A
Specification
Number of output points
Isolation method
Rated load voltage
Maximum load current
Maximum inrush current
QY40P
(Sink type)
16 points
Photocoupler isolation
12 to 24VDC (+20/-15%)
0.1A/point,1.6A/common
0.7A 10ms or less
QY50
(Sink type)
16 points
Photocoupler isolation
12 to 24VDC (+20/-15%)
0.5A/point,4A/common
4A 10ms or less
Leaked current at OFF
0.1mA or less
0.1mA or less
Surge suppressor
0.1VDC(TYP.)0.1A
0.2VDC(MAX.)0.1A
1ms or less
1ms or less
(rated load,resistive load)
Zener diode
Fuse
No
0.2VDC(TYP.)0.5A
0.3VDC(MAX.)0.5A
1ms以下
1ms or less
(rated load,resistive load)
Zener diode
6.7A(unchangeable)
(fuse capacity:50A)
Maximum voltage drop at ON
OFF to ON
ON to OFF
Protection function
Internal current consumption
Common terminal arrangement
Yes(overload protection,
overheat protection)
65mA(TYP. all points ON)
16 points/common
To the control panel
Mounting bracket fixing screw M3.5×6
(supplied with Conversion Adapter)
MELSEC-Q Series
Base Unit
1
Precaution
Unit:mm
4
5
<Conversion Adapters with a fixture> <Disconnection detector connector conversion cable>
・ERNT-ASQT68AD-G
・ERNT-ASQT64TCTTBW
・ERNT-ASQT68TD-H01
・ERNT-ASQT64TCRTBW
・ERNT-ASQT68TD-H02
・ERNT-ASQT62TCTTBW
・ERNT-ASQTD61
・ERNT-ASQT62TCRTBW
・ERNT-ASQTD62
・ERNT-ASQTD62D
27.4
Specification
DIN rail
7 points
Photocoupler isolation
12 to 24VDC (+20/-15%)
0.5A/point,2A/common
4A 10ms or less
0.1mA or less
0.2VDC(TYP.)0.5A 0.3VDC(MAX.)0.5A
1ms or less
1ms or less(rated load,resistive load)
Zener diode
4A(unchangeable)(fuse capacity:50A)
No
7 points/common
MELSEC-Q Series
Base Unit
Mounting bracket fixing screw M3.5×6
(supplied with Conversion Adapter)
Precaution
①
1
Conversion Adapter
installation screw
M3×25
Terminal block
(supplied with Conversion Adapter)
2
3
MELSEC-Q Series Module
5
Mounting bracket
(supplied with Conversion Adapter)
4.Mounting and Installation
No
80mA(TYP. all points ON)
16 points/common
95mA(TYP. all points ON)
16 points/common
Duplication Prohibited
This manual may not be reproduced in any form, in part or in whole, without written permission from
Mitsubishi Electric Engineering Company Limited.
©2015 MITSUBISHI ELECTRIC ENGINEERING COMPANY LIMITED ALL RIGHTS RESERVED
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
Conversion Adapter
Terminal block screw (M3.5)
Terminal block installation screw (M4)
4.1 Handling Precautions
(1) Before attempting to install the Unit or carry out the necessary wiring, make certain that the
external power supply, used in the system, is shut off on all three phases. Failure to do so may
result in electric shock or damage to the product.
(2) Do not touch live terminals. There is a danger of electric shock or malfunction.
(3) Do not modify the Conversion Adapter or take it apart. Doing so will cause failure, malfunction,
personal injury, or fire.
(4) Do not touch the energized part of the Conversion Adaptor directly. Contact will cause malfunction
or failure in the system.
(5) Fasten the Conversion Adapter and the Mounting bracket securely with retaining screws, and
tighten the screws by applying torque within specified limits. Loose screws can lead to the
dropping of the Conversion Adapter, or Mounting bracket, possibly causing breakage thereof.
Excessive tightness of the screws can lead to breakage of the screws, Converter Adaptor,
Mounting bracket, or MELSEC-Q Series Module, possibly causing the dropping, shorting, and
malfunction thereof.
(6) Use care to prevent foreign materials including cuttings and wiring debris from entering the
Conversion Adapter or the MELSEC-Q Series Module. These will be cause for fire, failure or
malfunction.
(7) Do not drop the Conversion Adapter and Mounting Bracket or do not give a strong impact to it.
This will cause damage.
4.2 Use Precautions
Width dimension
Depth dimension
of module
The module width The depth required for installation is 128.5 mm (150.5 mm for
dimension is 27.4 QY22). Check the installation condition.
mm.
< Control panel installation >
< DIN rail installation >
Check the
MELSEC-Q
MELSEC-Q
conditions for
Series
Series
wiring space and
Conversion
installation.
Conversion
adapter
※QY22
adapter
128.5mm
150.5mm (※)
Existing wiring
For using the conversion adapter with a fixture and the disconnection detector connector conversion cable for the
temperature control module on the same base unit, use a separately-sold conversion adapter DIN rail mounting
bracket (ERNT-ASQDIN). Refer to the user's manual of the conversion adapter DIN rail mounting bracket for
information on how to install the bracket.
<Conversion Adapters with a fixture> <Disconnection detector connector conversion cable>
・ERNT-ASQT68AD-G
・ERNT-ASQT64TCTTBW
・ERNT-ASQT68TD-H01
・ERNT-ASQT64TCRTBW
・ERNT-ASQT68TD-H02
・ERNT-ASQT62TCTTBW
・ERNT-ASQTD61
・ERNT-ASQT62TCRTBW
・ERNT-ASQTD62
・ERNT-ASQTD62D
5.1 Installation Method
Installation with the Control panel
Mount the MELSEC-Q Series Base
Unit to the control panel.
Refer to the QCPU user’s manual for
how to install them to the control
panel.
Installation with the DIN rail
Mount the DIN rail mounting adapter manufactured
by Mitsubishi Electric to the MELSEC-Q Series
Base Unit.
For how to install the adapter to the MELSEC-Q
Series Base Unit, refer to the QCPU user’s manual.
1 Install the MELSEC-Q Series module to the MELSEC-Q Series Base Unit. In addition, remove
the terminal block attached with the MELSEC-Q Series module after loosening the terminal
block installation screws (2 places up and down).
Product Warranty Details
Please confirm the following product warranty details prior to product use.
Gratis Warranty Terms and Gratis Warranty Range
If any fault or defect (hereinafter referred to as “Failure”) attributable to Mitsubishi Electric Engineering
Company Limited (hereinafter referred to as “MEE”) should occur within the gratis warranty period,
MEE shall repair the product free of charge via the distributor from whom you made your purchase.
 Gratis Warranty Period
MELSEC-Q Series terminal block installation screw
(Secure it in two places, top and bottom.)
※QY22
The installation environment is the same as MELSEC-Q series CPU Module to use. Refer to the user's
manual of the MELSEC-Q Series CPU Module to be used.
No
Weight:140g
4
The gratis warranty period of this product shall be one (1) year from the date of purchase or
delivery to the designated place.
Note that after manufacture and shipment from MEE, the maximum distribution period shall be
six (6) months, and the gratis warranty period after manufacturing shall be limited to eighteen
(18) months.
In addition, the gratis warranty period for repaired products shall not exceed the gratis warranty
period established prior to repair.
 Gratis Warranty Range
2 Secure the mounting bracket to the MELSEC-Q Series module using the mounting bracket
fixing screws (M3.5 × 6). (2 places)
0.5ms以下
0.5ms or less
(resistive load)
No
1.6A(unchangeable)
(fuse capacity:50A)
25.7
【Installation with the DIN rail】
QX48Y57
(Sink type)
4.3 Installation Environment
VOL:0.3VDC
Terminal block
Existing wiring
For using the conversion adapter with a fixture and the disconnection detector connector conversion cable for the
temperature control module on the same base unit, use a separately-sold base adapter (ERNT-ASQBN). Refer to the
user's manual of the base adapter for information on how to install the base adapter.
27.4mm
16 points
Photocoupler isolation
5 to 12VDC (+25/-10%)
16mA/point,256mA/common
40mA 10ms or less
VOH:3.5VDC
(Vcc=5VDC,IOH=0.4mA)
Mounting bracket
Conversion adapter
Conversion Adapter
Terminal block screw (M3.5)
Terminal block installation screw (M4)
8 points
Photocoupler isolation
24VDC (+20/-15%)
Approx. 4mA
19V or higher/3mA or higher
11V or lower/1.7mA or lower
Approx. 5.6kΩ
1/5/10/20/70ms or less
1/5/10/20/70ms or less
80mA(TYP. all points ON)
8 points/common
128.5mm
150.5mm (※)
QY70
(Sink type)
6.External Dimensions
3
QX48Y57
(Positive common)
Model
Item
Tighten the installation screws to the specified torque below. An inappropriate tightening torque could
cause the product to fall or result in a short circuit, product failure or malfunction.
Screw Location
Tightening Torque Range
Mounting bracket fixing screw (M3.5×6)
0.68 to 0.92N・m
Conversion Adapter installation screw (M3×25)
0.43 to 0.57N・m
Terminal block installation screw (M4 screw)
1.02 to 1.38N・m
Terminal block screw (M3.5 screw)
0.59 to 0.88N・m
Mounting bracket
(supplied with Conversion Adapter)
<Output specification>
Number of output points
Isolation method
Rated load voltage
Maximum load current
Maximum inrush current
Leaked current at OFF
Maximum voltage drop at ON
Response OFF to ON
time
ON to OFF
Surge suppressor
Fuse
Protection function
Common terminal arrangement
Conversion Adapter
installation screw
M3×25
Terminal block
(supplied with Conversion Adapter)
2
③I/O Combined module
QX48Y57
<Input specification>
Use
Precautions
16 points
Photocoupler isolation
100 to 240VAC 50/60Hz±5%
0.6A/point,4.8A/common
20A cycle or less
3mA or lower (240V 60Hz) 1.5mA or lower (120V 60Hz)
1.5V or lower
1ms + 0.5 cycles or less
1ms + 0.5 cycles or less (rated load,resistive load)
CR absorber
No
250mA(MAX. all points ON)
16 points/common
【Installation with the Control panel】
MELSEC-Q Series Module
Model
Specification
Number of input points
Isolation method
Rated input voltage
Rated input current
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response OFF to ON
time
ON to OFF
Internal current consumption
Common terminal arrangement
5.2 Tightening Torque
5.Part Names and Installation Method
16 points
Photocoupler isolation
12 to 24VDC(+20/-15%)
0.5A/point,4A/common
4A 10ms or less
0.1mA or less
0.2VDC (TYP.)0.5A 0.3VDC (MAX.)0.5A
1ms or less
1ms or less(rated load,resistive load)
Zener diode
6.7A(unchangeable)(fuse capacity:50A)
No
80mA(TYP. all points ON)
16 points/common
92
Inrush current
ON voltage/ON current
OFF voltage/OFF current
QX28
8 points
Photocoupler isolation
5 to 24VDC (+20/-10%)
2A/point,8A/module
8A 10ms or less
0.1mA or less
0.3VDC (MAX.)2A
3ms or less
10ms or less(resistive load)
Zener diode
No
No
110mA(TYP. all points ON)
All points independent
102
Rated input current
QX10
Number of output points
Isolation method
Rated load voltage
Maximum load current
Maximum inrush current
Leaked current at OFF
Maximum voltage drop at ON
Response OFF to ON
time
ON to OFF
Surge suppressor
Fuse
Protection function
Internal current consumption
Common terminal arrangement
QY80
(Source type)
69mm
Model
Specification
Number of input points
Isolation method
Rated input voltage
Response
time
QY68A
(Sink/Source type)
Specification
①Input module
31.5
(5) MELSEC-Q Series module specification
3 Install the Conversion Adapter to the mounting bracket, and secure it using the Conversion
Adapter installation screws (M3 × 25). (2 places)
Precaution
Before tightening the installation screws, check that the Conversion Adapter has been
securely installed on the MELSEC-Q Series module. Tightening the screws in
floating-off state or tilting state will damage the Conversion Adapter installation screws
and the mounting bracket.
4 Secure the terminal block to the Conversion Adapter with the supplied terminal block
installation screw (M4). (2 places, top and bottom.)
5 Connect the existing wiring to the terminal block.
When any wires are left unconnected, connect them to open terminals or insulate them.
The gratis warranty range shall be limited to normal use based on the usage conditions, methods
and environment, etc., defined by the terms and precautions, etc., given in the instruction
manual, user’s manual and caution labels on the product.
Warranty Period after Discontinuation of Production
(1) MEE shall offer product repair services (fee applied) for seven (7) years after production of the
product has been discontinued. Discontinuation of production shall be reported via distributors.
(2) Product supply (including spare parts) is not possible after production has been discontinued.
Exclusion of Opportunity Loss and Secondary Loss from Warranty
Liability
Regardless of the gratis warranty period, MEE shall not be liable for compensation for damages
arising from causes not attributable to MEE, opportunity losses or lost profits incurred by the user due
to Failures of MEE products, damages or secondary damages arising from special circumstances,
whether foreseen or unforeseen by MEE, compensation for accidents, compensation for damages to
products other than MEE products, or compensation for other work carried out by the user.
Changes in Product Specifications
The specifications given in the catalogs, manuals and technical documents are subject to change
without notice.
This document is a new publication, effective September 2015. Specifications are subject to change
without notice.
Developed September 2015
50CM-D180201-A