Humidity Controller SUN‐25H User Manual Temperature & Humidity Range
Humidity (0~100%)
( -40~80oC For HS2301 Sensor )
Humidity (0~100%)
( -40~125oC For HS2305 Sensor )
SUN-25H
Output
Main Relay(OUT1)
4. Sensor Connection Method
※ Thank you for purchasing Sunward Engineering team product. The User
Manual is provided for preventing the damage and trouble of product caused by
carelessness and to inform the precise usage. Please keep it in the safe place
and refer to it when you have any doubt during using this product.
1.
Function & Name of Parts
uncun
Aux Output
On2
up
%
dn
set
SUNWARD
On1
Decrease
Main Output
Display
Main Output Display
Setting Button
Increase Button
Decrease Button
Set Button
Display
Current humidity / Setting humidity
Main Output ON/OFF Display
set
Hum, Installer Setting Button
up
dn
Setting Value increase button
Setting Value decrease button
2. Functions
▶ Only for humidity ON/OFF control.
Variation(dIF) 0.1~25.0% , 0~240sec delay timer, Humidifier/Dehumidifier
Selection function
▶ Lock function for installer / Limit function of Set Value
˚Limit the range of set humidity by users⇒ Set limit function
˚Hysteresis ,delay time, Humidifier/Dehumidifier selection⇒Lock function
Humidity
sensor
OUT1
(Main)
Power
AC
100~
220V
‘Err’ to be displayed.
② sensor wire extension method
▶ it is possible within 30m.
①②③④⑤ ⑥ ⑦⑧⑨⑩⑪⑫
You should use the shield inside
cable, in order to prevent
input noise
▶The humidity sensor is electromagnetic
Humidity
sensor
induction method. It should be
①
Red
② Black
③ White
Installed in dry place because
The instruction value may be
Terminal
changed because of moisture or a
①
②
③
sensor
drop of water inside the sensor.
▶The humidity sensor should be
Hum. sensor
Red
Black White
calibrated at least every 2 years.
SUN-25H
③ Sensor Reading compensation
(When the current humidity is different )
▶ If sensor cable is too long or sensor is old, there will be hum variation.
At that time, use current hum compensation function (rSt).
▶ While the current hum is displayed, press set for 3 seconds.
Once dIF displayed, release set. In order to move to rSt (hum
compensation), press set several times.
▶ Input the compensation hum by using up & dn.
If you press set for 3 seconds, it will be saved and the current hum
will be compensated.
For example :
rSt humidity
Current Humidity
20 %
20 %
+
+
-5 %
10 %
15 %
30 %
5. External & Panel Dimension
70+0.6
Power
White
Black
Red
▶ Supply power to the controller
It displays the current humidity.
▶ Press Set button once to set Main output
Hum value in the right picture flashing
< Terminals on Back >
▶To change them, press UP or Dn Key.
If you press UP/DN longer than 1 sec
Power
Increases or decreases quickly
OUT1
AC
sensor
(Main)
100~
※If set Hum limit function
220V
Is working, the setting will be limited
within the range.
▶ If you press Set once again,
①②③④⑤ ⑥ ⑦⑧⑨⑩⑪⑫
the set hum will be saved.
Even if switched-off, the set value
will not be deleted.
AC
▶The current hum is displayed and
220V
Coil terminal
Controller starts to control.
▶For Main Output use terminals 8~10.
Load
Displayed Hum
=
=
<Current Hum>
3. Main Output Set Value Change
SUNWARD ENG
① sensor connection method
▶ Please connect as the right picture
If you connect with the changed
wired or use different type sensor
White
Black
Red
Increase
※ Terminals 9,10 are dedicated for NO status of Main Output.
※ For auxiliary output(alarm/timer) use terminals 5,6 . It will be provided on
system as an option .
PANEL CUT OUT
28+0.6
35
70
(unit: mm)
77
6. Set Value Limit & Lock function
① It is possible that users cannot change the default setting, by using lock
function.
Item Setting
Description
Default
setting
Model
LoC
0
StH
StL
50
40
Locking off. All function setting possible.
Only locking and setting hum function
possible.
Settable high hum value 50
Settable low hum value 40
▶ If you press set for 3 seconds, the value will be saved. After that the
changed value will be applied.
SUN-25H Controller User Manual
Page 1/4
9. Product specification
7 Installer setting
At the current hum, press set
for 3 seconds
On/Off rated control
Installer setting item (OUT1)
Output OFF/ON range 0.1~25.0% AC100~220V (50/60Hz) ±10% Power
Consumption
Approx. below 3VA Sensor
Characteristic
Sensor
Accuracy
Humidity: Capacitance type Humidity Sensor (Allowabe Line Resistance : within 5Ω) HS‐2301 0~ 100%Rh ‐40~85oC
HS‐2305 0~ 100%Rh ‐40~125oC
HS‐2301 ±3% Rh +1digit of displayed value
HS‐2305 ±2% Rh +1digit of displayed value
Variation(dIF)
0.1 ~ 25.0% Control
Output
Relay Contact Output: OUT1 AC250V/ 5A (resistance load)/contact point life time: above 300K times (rated load) Input Sensor
ON delay timer 0~240 Seconds Humidifier "H" and "d"
Dehumidifier Power Voltage
Sensor Input Compensation ‐30.0~+30.0 . Set press – return to Main screen
Set press for 3sec, Data saved
Return to the current hum.
* DIF & TYP Input Value example ① TYP = d (Dehumidifier) Example: Set Hum= 10%, DIF = 2 => Relay ON = 12%, Relay OFF=10% ② TYP = H (Humidifier) Example: set Hum 10%, DIF = 2 => Relay ON : 8%, relay OFF : 10% * dLt =10, relay on after 10 seconds * tyP = d (Dehumidifier), use for decreasing the humidity. * tyP = H (Humidifier), use for increasing the humidity. 8. Factory Default
Control
Method
Setting
Method
Digital Method by increase & decrease key Other
Functions
Sensor input compensation, Delay Timer Humidifier / Dehumidifier selection. Ambient Temp
0Ԩ ~ 50Ԩ ( for control system unit ) Ambient
humidity
Below 85% RH ( for control system unit ) ON/OFF control selection Note: To see the temperature on display , press Dn key in current display Hold set key pressed during SUN25 is off and turn it ON . When StH is appeared , release the button . (if dIF displayed, repeat it again) Factory Setting Item
Setting range upper limit : setting hum is limited
below the assigned value. Setting range lower limit: setting hum is
limited above the assigned value. Lock function except setting Hum change.
ON:lock / OFF :lock cancelled When Lock cancelled, it should be OFF and saved. Set press for 3 seconds, all data saved
and return to the current hum.
SUNWARD ENG
SUN-25H Controller User Manual
Page 2/4
Attentions of application of the Humidity Sensor
(1) Operating and storage conditions
We don't recommend applying RH-range beyond the range stated in this specification.
This
sensor can recover after working in non-normal operating condition to calibrated status, but will
acce
lerate sensors' aging.
(2) Attentions to chemical materials
Vapor from chemical materials may interfere Sensor sensitive-elements and debase Sensor's
sensitivity.
(3) Disposal when (1) & (2) happens
Step one: Keep the Sensor at condition of temperature 50~60Celsius, humidity <10%RH for 2hours;
Step two: After step one, keep the Sensor at condition of temperature 20~30Celsius, humidity >70%
RH for 5 hours.
(4) Attention to temperature's affection
Relative humidity strongly depend on temperature, that is why we use temperature compensation
technology to ensure accurate measurement of RH. But it’s still much better to keep the sensor at
s
ame temperature when sensing.
This sensor should be mounted at the place as far as possible from parts that may cause change to
temperature.
(5) Attentions to light
Long time exposure to strong light and ultraviolet ray may debase Sensor performance.
(6) Attentions to connection wires
The connection wires' quality will affect communication's quality and distance, high quality shieldedwire is recommended.
(7) Other attentions
* Avoid using the sensor under dew condition.
* Don't use this product in safety or emergency stop devices or any other occasion that failure of
the sensor may cause personal injury.
‫نکاتی مھم در استفاده صحيح از سنسور رطوبت‬
‫ در‬. ‫ ﺑﻪ ﻫﻴﭻ وﺟﻪ ﺗﻮﺻﻴﻪ ﻧﻤﻴﮕﺮدد‬، ‫ اﺳﺘﻔﺎده از اﻳﻦ ﺳﻨﺴﻮردر ﻣﺤﺪودة ﻓﺮاﺗﺮاز ﻣﺤﺪوده ذﻛﺮ ﺷﺪه در ﻣﺸﺨﺼﺎت‬: ‫ﺷﺮاﻳﻂ ﻛﺎرﻛﺮد و ﻧﮕﻬﺪاري‬
(1
‫ اﻳﻦ ﺳﻨﺴﻮر ﻣﻴﺘﻮاﻧﺪ دوﺑﺎره ﺑﻪ ﺷﺮاﻳﻂ ﻛﺎﻟﻴﺒﺮه ﺷﺪه اول ﺑﺎز ﮔﺮدد‬، ‫ﺻﻮرت ﻛﺎرﻛﺮد در ﻣﺤﻴﻂ ﻫﺎﻳﻲ ﺑﺎ ﺷﺮاﻳﻄﻲ ﺳﺨﺖ ﺗﺮ از ﻣﺸﺨﺼﺎت ﻧﺎﻣﻲ‬
. ‫ ( ﻣﻲ ﮔﺮدد‬Aging ) ‫وﻟﻲ ﺳﻨﺴﻮر دﭼﺎر ﭘﺪﻳﺪه ﭘﻴﺮ ﺷﺪﮔﻲ‬
. ‫ﺑﺨﺎرﻫﺎي ﻣﻮاد ﺷﻴﻤﻴﺎﻳﻲ ﻣﻤﻜﻦ اﺳﺖ اﺛﺮات ﻣﺨﺮﺑﻲ ﺑﺮ ﺳﻨﺴﻮر داﺷﺘﻪ ﺑﺎﺷﻨﺪ و ﺣﺴﺎﺳﻴﺖ و دﻗﺖ آن را ﺑﺸﺪت ﺗﻨﺰل ﺑﺪﻫﻨﺪ‬
(2
. ‫ ﺑﺮاي ﺑﺎزﻳﺎﺑﻲ ﺳﻨﺴﻮر ﺑﻪ ﺗﺮﺗﻴﺐ ﻣﻮارد زﻳﺮ ﻋﻤﻞ ﻧﻤﺎﻳﻴﺪ‬2 ‫ و‬1 ‫در ﺻﻮرت ﺑﺮوز ﻣﻮارد‬
(3
. ‫درﺻﺪ ﻧﮕﻪ دارﻳﺪ‬10 ‫ درﺟﻪ ﺳﺎﻧﺘﻴﮕﺮاد ﺑﺎ رﻃﻮﺑﺖ زﻳﺮ‬60 ‫ ﺗﺎ‬50 ‫ ﺳﺎﻋﺖ در دﻣﺎي ﺑﻴﻦ‬2 ‫اﻟﻒ( ﺳﻨﺴﻮر را ﺑﺮاي‬
. ‫ درﺻﺪ ﻧﮕﻪ دارﻳﺪ‬70 ‫ درﺟﻪ ﺳﺎﻧﺘﻴﮕﺮاد و رﻃﻮﺑﺖ ﺣﺪاﻗﻞ‬30 ‫ ﺗﺎ‬20 ‫ ﺳﺎﻋﺖ در دﻣﺎي‬5 ‫ب( ﺳﭙﺲ ﺳﻨﺴﻮر را ﺑﺮاي‬
‫ از ﻳﻚ ﺳﻨﺴﻮر دﻗﻴﻖ ﺣﺮارت اﺳﺘﻔﺎده‬، ‫ ﺑﻬﻤﻴﻦ دﻟﻴﻞ ﻣﺎ در اﻳﻦ ﺳﻨﺴﻮر رﻃﻮﺑﺖ‬، ‫ رﻃﻮﺑﺖ ﻧﺴﺒﻲ ﺑﺸﺪت واﺑﺴﺘﻪ ﺑﻪ ﭘﺎراﻣﺘﺮ دﻣﺎ اﺳﺖ‬: ‫ﺗﺎﺛﻴﺮات دﻣﺎ‬
(4
. ‫ وﻟﻲ ﭘﺎﻳﺪاري و ﻳﻜﻨﻮاﺧﺘﻲ دﻣﺎ در ﺣﻴﻦ ﻛﺎر ﺑﻪ ﻛﺎرﻛﺮد ﺑﻬﺘﺮ و دﻗﻴﻘﺘﺮ ﺳﻨﺴﻮر رﻃﻮﺑﺖ ﻛﻤﻚ زﻳﺎدي ﺧﻮاﻫﺪ ﻧﻤﻮد‬. ‫ﻛﺮده اﻳﻢ‬
‫ ﻗﺎﺑﻞ اﻧﺘﻈﺎر‬، ‫ ﻛﺎﻫﺶ ﻧﺴﺒﻲ دﻗﺖ ﺳﻨﺴﻮر در ﺷﺮاﻳﻄﻲ ﻛﻪ در ﻣﻌﺮض ﻃﻮﻻﻧﻲ ﻣﺪت ﻧﻮر ﺷﺪﻳﺪ و اﺷﻌﻪ ﻣﺎوراي ﺑﻨﻔﺶ ﻗﺮار ﮔﻴﺮد‬: ‫ﺗﺎﺛﻴﺮات ﻧﻮر‬
(5
. ‫ ﺑﻨﺎﺑﺮ اﻳﻦ ﺳﻌﻲ ﮔﺮدد ﺳﻨﺴﻮر در ﺷﺮاﻳﻂ ﻓﻮق ﻗﺮار ﻧﮕﻴﺮد‬. ‫اﺳﺖ‬
‫ ﺗﻮﺻﻴﻪ ﻣﺎ اﺳﺘﻔﺎده از ﻛﺎﺑﻞ ﺷﻴﻠﺪ‬. ‫ ﻛﻴﻔﻴﺖ ﺳﻴﻤﻬﺎي ارﺗﺒﺎﻃﻲ ﺑﺮ دﻗﺖ ارﺗﺒﺎط و ﺣﺪاﻛﺜﺮ ﻓﺎﺻﻠﻪ ﻣﻮﺛﺮ ﺗﺎﺛﻴﺮ ﻣﻴﮕﺬارد‬:‫اﺗﺼﺎﻻت و ﺳﻴﻤﻬﺎي ارﺗﺒﺎﻃﻲ‬
(6
. ‫ﺑﺎ ﻛﻴﻔﻴﺖ ﺑﺎﻻ اﺳﺖ‬
‫ ﻫﻤﭽﻨﻴﻦ ﺗﻮﺟﻪ ﻧﻤﺎﻳﻴﺪ ﺑﻪ ﻫﻴﭻ وﺟﻪ از اﻳﻦ ﺳﻨﺴﻮر ﺑﺮاي ﻣﺪارﻫﺎي ﻗﻄﻊ‬. ‫ از اﺳﺘﻔﺎده ﺳﻨﺴﻮر در ﺷﺮاﻳﻂ ﻧﻘﻄﻪ ﺷﺒﻨﻢ ﭘﺮﻫﻴﺰ ﻧﻤﺎﻳﻴﺪ‬: ‫ﺳﺎﻳﺮ ﻧﻜﺎت‬
(7
. ‫ ﭼﺮا ﻛﻪ ﺧﺮاﺑﻲ اﺣﺘﻤﺎﻟﻲ ﺳﻨﺴﻮر ﻣﻤﻜﻦ اﺳﺖ ﺑﺎﻋﺚ آﺳﻴﺐ دﻳﺪﮔﻲ اﻓﺮاد ﮔﺮدد‬، ‫اﺿﻄﺮاري و ﻣﻮﻗﻌﻴﺖ ﻫﺎي ﻧﻈﺎﻳﺮ آن اﺳﺘﻔﺎده ﻧﻜﻨﻴﺪ‬
SUNWARD ENG
SUN-25H Controller User Manual
Page 3/4
‫‪SUNWARD‬‬
‫دفترچه کاربری کنترل رطوبت‬
‫‪Range‬‬
‫‪Sensor Type‬‬
‫‪Model‬‬
‫)‪0-100%(-40~80 C‬‬
‫‪o‬‬
‫)‪0-100%(-40~125 C‬‬
‫‪HS 2301‬‬
‫‪HS 2305‬‬
‫‪Output‬‬
‫‪SUN-25H‬‬
‫‪o‬‬
‫‪Main Output‬‬
‫‪Relay 5A‬‬
‫‪ SET‬را ﺑﻴﺶ از ‪ 5‬ﺛﺎﻧﻴﻪ ﺑﻔﺸﺎرﻳﺪ و ﺗﺎ روﻳﺖ ﻧﻤﺎد ‪ diF‬ﻧﮕﻪ دارﻳﺪ ‪ .‬ﺗﻐﻴﻴﺮ اﻳﻦ ﭘﺎراﻣﺘﺮ‬
‫ﺑﺎ ﻛﻠﻴﺪ ‪ Up‬ﻳﺎ ‪ Dn‬اﻧﺠﺎم ﻣﻴﮕﻴﺮد ‪ .‬در ﻣﺤﺪوده ‪ 0.1‬ﺗﺎ ‪ 25‬ﻣﻴﺘﻮاﻧﻴﺪ آن را ﺗﻨﻈﻴﻢ ﻛﻨﻴﺪ‬
‫و ﺑﺎ ﻛﻠﻴﺪ ‪ SET‬آﻧﺮا ذﺧﻴﺮه ﻛﻨﻴﺪ ‪ .‬ﻓﺸﺎر ﻣﻤﺘﺪ اﻳﻦ ﻛﻠﻴﺪ ﻣﺎ را ﺑﻪ ﺻﻔﺤﻪ ﺟﺎري ﻣﻴﺮﺳﺎﻧﺪ ‪.‬‬
‫‪ diF=3‬ھيسترزيس )حساسيت قطع و وصل رله کنترل(‬
‫‪ON‬‬
‫‪-1‬ﻗﺎﺑﻠﻴﺘﻬﺎي ﻛﻠﻲ‬
‫‬‫‬‫‬‫‪-‬‬
‫ﻛﻨﺘﺮل ﭘﺮوﺳﻪ ﻫﺎي رﻃﻮﺑﺖ زداﻳﻲ ﻳﺎ رﻃﻮﺑﺖ ﺳﺎزي‬
‫ﺣﺴﺎﺳﻴﺖ رﻟﻪ ﻛﻨﺘﺮل ‪ 0.1‬ﺗﺎ ‪ 25.0‬درﺻﺪ‬
‫اﻣﻜﺎن ﺣﺪاﻗﻞ و ﺣﺪاﻛﺜﺮ رﻃﻮﺑﺖ ﺗﻮﺳﻂ ﻛﺎرﺑﺮ‬
‫اﻣﻜﺎن ﻓﺎﺻﻠﻪ ﮔﺬاري ﻗﻄﻊ و وﺻﻞ رﻟﻪ از ﺻﻔﺮ ﺗﺎ ‪ 240‬ﺛﺎﻧﻴﻪ‬
‫‪-‬‬
‫اﻣﻜﺎن ﻗﻔﻞ ﺗﻨﻈﻴﻤﺎت اﺻﻠﻲ ﺑﺮاي ﺟﻠﻮﮔﻴﺮي از دﺳﺘﻜﺎري اﻓﺮاد ﻏﻴﺮ ﻣﺠﺎز‬
‫‪-‬‬
‫‬‫‪-‬‬
‫‬‫‪-‬‬
‫‪OFF‬‬
‫رله اصلی ‪5A‬‬
‫سفيد‬
‫مشکی‬
‫‪8‬‬
‫‪7‬‬
‫‪6‬‬
‫‪5‬‬
‫‪4‬‬
‫قرمز‬
‫‪9 10 11 12‬‬
‫‪-‬‬
‫سنسور رطوبت‬
‫‪3‬‬
‫‪2‬‬
‫‪1‬‬
‫ﺗﻮﺟﻪ ﻛﻨﻴﺪ ﻃﻮل ﺳﻨﺴﻮر رﻃﻮﺑﺖ ﺣﺪاﻛﺜﺮ ‪ 30‬ﻣﺘﺮ و ﺣﺘﻤﺎ از ﺳﻴﻢ ﺷﻴﻠﺪ اﺳﺘﻔﺎده ﻧﻤﺎﻳﻴﺪ‪.‬‬
‫ﺗﺼﺤﻴﺢ ﻗﺮاﺋﺖ ﺳﻨﺴﻮر ﻳﺎ ﺧﻄﺎي اﺣﺘﻤﺎﻟﻲ آن ﺑﻪ روش زﻳﺮ ﻣﻴﺴﺮ اﺳﺖ‪ .‬در ﺣﺎﻟﻲ‬
‫ﻛﻪ رﻃﻮﺑﺖ ﺟﺎري را روي ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ دارﻳﻢ ‪،‬ﻛﻠﻴﺪ ‪ SET‬را ‪ 5‬ﺛﺎﻧﻴﻪ ﺑﻔﺸﺎرﻳﺪ‪ .‬زﻣﺎﻧﻲ‬
‫ﻛﻪ ﻧﻤﺎﻳﺶ ‪ diF‬روﻳﺖ ﺷﺪ ‪ ،‬ﻛﻠﻴﺪ را رﻫﺎ ﻛﻨﻴﺪ‪ .‬ﺑﺎ ﭼﻨﺪ ﺑﺎر ﻓﺸﺎر ﻛﻠﻴﺪ ‪ ، SET‬ﺑﺎ‬
‫دﻳﺪن ‪ ،rSt‬ﻣﻲ ﺗﻮاﻧﻴﺪ ﺗﻮﺳﻂ ﻛﻠﻴﺪ ‪ Up‬ﻳﺎ ‪ Dn‬ﻋﺪد ﻣﻮرد ﻧﻈﺮ را ﺑﺮاي اﺿﺎﻓﻪ ﻛﺮدن و‬
‫ﻳﺎ ﻛﺴﺮ ﻧﻤﻮدن از ﻋﺪد ﻧﻤﺎﻳﺸﻲ ﺗﻨﻈﻴﻢ ﻛﻨﻴﺪ‪ .‬ﺑﺎ ﻓﺸﺎر ‪ 5‬ﺛﺎﻧﻴﻪ اي ﻛﻠﻴﺪ ‪ SET‬ﻋﺪد در‬
‫ﺣﺎﻓﻈﻪ ذﺧﻴﺮه ﻣﻴﺸﻮد‪ .‬ﺑﻪ ﻣﺜﺎل زﻳﺮ ﺗﻮﺟﻪ ﻧﻤﺎﻳﻴﺪ‪:‬‬
‫نمايش تصحيح شده‬
‫‪15.0%‬‬
‫‪30.0%‬‬
‫‪4‬‬
‫=‬
‫=‬
‫پارامتر تصحيح ‪rSt‬‬
‫‪-5.0%‬‬
‫‪10.0%‬‬
‫رطوبت نمايشی‬
‫‪20.0 %‬‬
‫‪20.0 %‬‬
‫‪+‬‬
‫‪+‬‬
‫ﺣﺴﺎﺳﻴﺖ ﻗﻄﻊ ووﺻﻞ رﻟﻪ اول)ﻫﻴﺴﺘﺮزﻳﺲ( ‪ diF‬‬
‫ﻛﻨﺘﺮﻟﺮ ﺑﺮاي ﺗﻨﻈﻴﻢ رﻃﻮﺑﺖ رﻟﻪ اول را ﻗﻄﻊ و وﺻﻞ ﻣﻲ ﻛﻨﺪ‪ .‬ﻣﻴﺘﻮان ﻓﺎﺻﻠﻪ ﻗﻄﻊ و ﻳﺎ وﺻﻞ ﺑﺎ ﻋﺪد‬
‫ﺳﺖ ﭘﻮﻳﻨﺖ را ﺗﻌﻴﻴﻦ ﻧﻤﻮد ‪ .‬اﻳﻦ ﻓﺎﺻﻠﻪ رﻃﻮﺑﺘﻲ را ﻫﻤﺎن ﭘﺎراﻣﺘﺮ ‪ diF‬ﺗﻌﻴﻴﻦ ﻣﻴﻜﻨﺪ ‪ .‬ﺑﺮاي آن ﻛﻠﻴﺪ‬
‫‪Page 4/4‬‬
‫‪49‬‬
‫‪SET50‬‬
‫‪48‬‬
‫‪ON‬‬
‫ﺑﺮاي ﻧﺼﺐ ﺳﻨﺴﻮر ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﺷﻜﻞ زﻳﺮ در ﺳﻴﺴﺘﻤﻬﺎي ﺳﻨﺴﻮر ‪ IC‬ﺳﻴﻢ ﻗﺮﻣﺰ ﺑﻪ‬
‫ﺗﺮﻣﻴﻨﺎل ‪ ، 1‬ﻣﺸﻜﻲ ﺑﻪ ﺗﺮﻣﻴﻨﺎل ‪ 2‬و ﺳﻔﻴﺪ ﺑﻪ ﺗﺮﻣﻴﻨﺎل ‪ 3‬ﻣﺘﺼﻞ ﻣﻴﮕﺮدد‪ .‬ﺗﻮﺟﻪ ﻛﻨﻴﺪ ﻛﻪ‬
‫اﺗﺼﺎل ﻏﻠﻂ ﺳﻴﻤﻬﺎ ﻧﻤﺎﻳﺶ ‪ Err‬را ﺑﻪ دﻧﺒﺎل دارد ﻳﺎ ﻣﻤﻜﻦ اﺳﺖ ﺧﺴﺎراﺗﻲ وارد ﻧﻤﺎﻳﺪ ‪.‬‬
‫‪SET50‬‬
‫‪49‬‬
‫‪tYP=H‬‬
‫دﺳﺘﮕﺎه را روﺷﻦ ﻛﻨﻴﺪ و ﻣﻨﺘﻈﺮ ﻧﻤﺎﻳﺶ رﻃﻮﺑﺖ ﺟﺎري در ﺻﻔﺤﻪ ﺷﻮﻳﺪ‪.‬‬
‫ﻛﻠﻴﺪ ‪ SET‬را ﻳﻚ ﺑﺎر ﺑﻔﺸﺎرﻳﺪ ‪ ،‬ﺻﻔﺤﻪ ﺑﺎﻳﺪ ﭼﺸﻤﻚ زن ﺷﻮد‪.‬‬
‫ﺑﺎ ﻛﻠﻴﺪ ﻫﺎي ‪ UP‬ﻳﺎ ‪ Dn‬ﻣﻴﺘﻮاﻧﻴﺪ ﺳﺖ ﭘﻮﻳﻨﺖ ﺟﺪﻳﺪ را ﺗﻨﻈﻴﻢ ﻧﻤﺎﻳﻴﺪ ‪ .‬در ﺻﻮرت ﻓﺸﺎر‬
‫ﻣﻤﺘﺪ ﻫﺮ ﻳﻚ از ﻛﻠﻴﺪﻫﺎي ﻓﻮق ﺑﻴﺶ از ‪ 3‬ﺛﺎﻧﻴﻪ ‪ ،‬اﻓﺰاﻳﺶ و ﻳﺎ ﻛﺎﻫﺶ اﻋﺪاد روي ﺻﻔﺤﻪ‬
‫ﺳﺮﻳﻌﺘﺮ اﺗﻔﺎق ﻣﻲ اﻓﺘﺪ و در ﻧﻬﺎﻳﺖ ﻣﺤﺪود ﺑﻪ ارﻗﺎﻣﻲ ﻛﻪ در ﺗﻨﻈﻴﻤﻬﺎي ‪ StL ‬و ‪StH‬‬
‫آﻣﺪه ‪ ،‬ﺧﻮاﻫﺪ ﺷﺪ ‪.‬‬
‫ﺑﺎ ﻓﺸﺎر ﻛﻠﻴﺪ ‪ SET‬ﻋﺪد در ﺣﺎﻓﻈﻪ ذﺧﻴﺮه ﻣﻴﮕﺮدد و ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ دﻣﺎي ﺟﺎري را‬
‫ﻧﻤﺎﻳﺶ ﻣﻴﺪﻫﺪ ‪.‬‬
‫ﺷﻤﺎره ﺗﺮﻣﻴﻨﺎل ﻫﺎي رﻟﻪ اﺻﻠﻲ ‪ 10‬و ‪ 9‬و ‪ 8‬اﺳﺖ ‪.‬‬
‫‪110~220‬‬
‫‪VAC‬‬
‫‪50~60Hz‬‬
‫‪51‬‬
‫‪OFF‬‬
‫‪-3‬ﻧﺼﺐ ﺳﻨﺴﻮر و ﺗﺼﺤﻴﺢ ﻗﺮاﺋﺖ‬
‫‪-‬‬
‫‪52‬‬
‫‪tYP=d‬‬
‫‪-2‬ﺗﻨﻈﻴﻢ ﻋﻤﻠﻜﺮد ﺧﺮوﺟﻲ‬
‫‪53‬‬
‫‪47‬‬
‫‪46‬‬
‫وقتی ‪ tYP=d‬تنظيم شده زمانی که رطوبت باالتر از‬
‫‪SET‬برود ‪ ،‬رله اول به منظور کاھش رطوبت و با‬
‫رعايت فاصله رطوبت ‪ diF‬روشن ميگردد ‪ .‬در روند‬
‫کاھش رطوبت به محض کوچکتر شدن رطوبت از‬
‫عدد ‪ SET‬رله اصلی خاموش ميگردد ‪.‬‬
‫وقتی ‪ tYP=H‬تنظيم شده زمانی که رطوبت پايين تر‬
‫از ‪SET‬برود ‪ ،‬با رعايت فاصله ‪ ، diF‬رله اول به‬
‫منظور افزايش رطوبت روشن ميگردد ‪ .‬در روند‬
‫افزايش رطوبت به محض بزرگ تر شدن رطوبت از‬
‫عدد ‪ SET‬رله اصلی خاموش ميگردد ‪.‬‬
‫‪-5‬تايمر تاخيری عملکرد رله اصلی ‪dLt‬‬
‫‪ ‬‬
‫در ﺣﺎﻟﺘﻲ ﻛﻪ رﻃﻮﺑﺖ ﺟﺎري روي ﺻﻔﺤﻪ اﺳﺖ ‪ ،‬ﻛﻠﻴﺪ ‪ SET‬را ﺑﺮاي ﺑﻴﺶ از ‪ 5‬ﺛﺎﻧﻴﻪ ﺑﻔﺸﺎرﻳﺪ ‪.‬‬
‫زﻣﺎﻧﻲ ﻛﻪ ﻧﻤﺎد ‪ diF‬روﻳﺖ ﺷﺪ ‪ ،‬ﻛﻠﻴﺪ را رﻫﺎ ﻛﻨﻴﺪ ‪ .‬ﺑﺎ ﭼﻨﺪ ﺑﺎر ﻓﺸﺎر ﻛﻠﻴﺪ ‪ SET‬ﻫﻤﺰﻣﺎن ﺑﺎ‬
‫ﻧﻤﺎﻳﺶ ﻧﻤﺎد ‪ dLt‬ﻣﻲ ﺗﻮاﻧﻴﺪ ﻋﺪد ﺗﺎﻳﻤﺮ ﻣﻮرد ﻧﻈﺮ را ﺑﺮﺣﺴﺐ ﺛﺎﻧﻴﻪ ﺑﺎ ﻓﺸﺎر ﻛﻠﻴﺪ ‪ Up‬ﻳﺎ ‪Dn‬‬
‫اﻧﺘﺨﺎب ﻛﻨﻴﺪ ‪.‬ﺑﺎ ﻓﺸﺎر ‪ 5‬ﺛﺎﻧﻴﻪ اي ﻛﻠﻴﺪ ‪ SET‬اﻳﻦ رﻗﻢ در ﺣﺎﻓﻈﻪ ذﺧﻴﺮه ﻣﻴﮕﺮدد و ﺑﻪ ﺻﻔﺤﻪ‬
‫ﺟﺎري ﺑﺎز ﻣﻴﮕﺮدد ‪ .‬ﺑﺎ ﺑﺮﻗﺮاري دو ﺷﺮط ‪ ،‬ﻛﻨﺘﺮﻟﺮ رﻟﻪ اﺻﻠﻲ را ﻣﺠﺪدا وﺻﻞ ﻣﻲ ﻧﻤﺎﻳﺪ‪ .‬اول‬
‫رﺳﻴﺪن رﻃﻮﺑﺖ ﺑﻪ ﺣﺪ ﻣﻮرد ﻧﻈﺮ و دوم ﻃﻲ ﺷﺪن ﻫﻤﻴﻦ زﻣﺎن ‪ 240) dLt‬تا ‪ 0‬ثانيه(‬
‫‪-6‬ﺗﻨﻈﻴﻢ رﻟﻪ اول )رﻃﻮﺑﺖ زﻧﻲ ﻳﺎ رﻃﻮﺑﺖ زداﻳﻲ(‬
‫در ﺣﺎﻟﺘﻲ ﻛﻪ دﺳﺘﮕﺎه رﻃﻮﺑﺖ ﺟﺎري را ﻧﻤﺎﻳﺶ ﻣﻴﺪﻫﺪ ‪ ،‬ﻛﻠﻴﺪ ‪ SET‬را ﺑﻴﺶ از ‪ 5‬ﺛﺎﻧﻴﻪ ﺑﻔﺸﺎرﻳﺪ ‪.‬‬
‫زﻣﺎﻧﻲ ﻛﻪ ﻧﻤﺎد ‪ diF‬ﻧﻤﺎﻳﺎن ﺷﺪ ‪ ،‬ﻛﻠﻴﺪ را رﻫﺎ ﻛﻨﻴﺪ ‪ .‬ﺑﺎ ﭼﻨﺪ ﺑﺎر ﻓﺸﺎر ﻛﻠﻴﺪ ‪ SET‬ﺑﻪ ﻧﻤﺎد ‪TyP‬‬
‫ﻣﻲ رﺳﻴﻢ ‪،‬ﻛﻪ ﺑﺮاي ﺗﻌﻴﻴﻦ ﻧﻮع ﻛﺎرﻛﺮد ﻛﻨﺘﺮﻟﻲ رﻟﻪ اول اﺳﺖ ‪ .‬اﮔﺮ ﻋﻤﻞ رﻃﻮﺑﺖ زﻧﻲ را از ﻛﻨﺘﺮﻟﺮ‬
‫ﺑﺨﻮاﻫﻴﻢ اﻳﻦ ﭘﺎراﻣﺘﺮ را روي ‪ H‬ﺗﻨﻈﻴﻢ ﻣﻴﻜﻨﻴﻢ ‪ .‬اﮔﺮ ﻋﻤﻞ رﻃﻮﺑﺖ ﻛﺸﻲ ﻳﺎ ﻛﺎﻫﺶ رﻃﻮﺑﺖ ﻣﺪ‬
‫ﻧﻈﺮ ﺑﺎﺷﺪ ‪ ،‬اﻳﻦ ﭘﺎراﻣﺘﺮ را روي ‪ d‬ﺗﻨﻈﻴﻢ ﻧﻤﺎﻳﻴﺪ ‪.‬‬
‫رﻃﻮﺑﺖ زﻧﻲ‬
‫رﻃﻮﺑﺖ زداﻳﻲ‬
‫ﭘﺎﻳﻴﻦ ﺗﺮ رﻓﺘﻦ رﻃﻮﺑﺖ از ‪ Set‬رﻟﻪ ﻛﻨﺘﺮﻟﻲ را روﺷﻦ ﻣﻴﻜﻨﺪ‬
‫ﺑﺎﻻﺗﺮ رﻓﺘﻦ رﻃﻮﺑﺖ از ‪ Set‬رﻟﻪ ﻛﻨﺘﺮل را روﺷﻦ ﻣﻲ ﻛﻨﺪ‬
‫‪H‬‬
‫‪d‬‬
‫‪tYP‬‬
‫ﺑﺮاي ﺗﻐﻴﻴﺮ اﻳﻦ ﺗﻨﻈﻴﻢ ﺑﺎﻳﺪ ﺑﺎ ﻛﻠﻴﺪ ‪ Up‬ﻳﺎ ‪ Dn‬ﻧﻤﺎد ﻣﻮرد ﻧﻈﺮ ‪ H‬ﻳﺎ ‪ d‬را ﺗﻨﻈﻴﻢ ﻧﻤﺎﻳﻴﺪ و ﺑﺮاي‬
‫ذﺧﻴﺮه در ﺣﺎﻓﻈﻪ دﺳﺘﮕﺎه ﻛﻠﻴﺪ ‪ SET‬را ﺑﻔﺸﺎرﻳﺪ ‪.‬‬
‫‪-7‬ﺣﻔﺎﻇﺖ و اﻳﻤﻨﻲ‬
‫‪LoC‬‬
‫‪ ‬‬
‫ﺑﺮاي ﺟﻠﻮﮔﻴﺮي از دﺳﺘﻜﺎري اﻓﺮاد ﻏﻴﺮ ﻣﺠﺎز و ﻫﻤﭽﻨﻴﻦ ﻣﺤﺪودﻛﺮدن ﻣﺤﺪوده ﺗﻨﻈﻴﻢ ‪ ، SET‬در‬
‫ﺣﺎﻟﺘﻲ ﻛﻪ ﻛﻠﻴﺪ ‪ SET‬ﻓﺸﺎر داده اﻳﺪ ‪ ،‬ﺳﻴﺴﺘﻢ را روﺷﻦ ﻧﻤﺎﻳﻴﺪ ‪ .‬زﻣﺎﻧﻲ ﻛﻪ ﻧﻤﺎد ‪ StH‬را دﻳﺪﻳﺪ‬
‫ﻛﻠﻴﺪ را رﻫﺎ ﻛﻨﻴﺪ ‪ .‬ﺑﺎ ﭼﻨﺪ ﺑﺎر ﻓﺸﺎر ﻛﻠﻴﺪ ‪ SET‬ﺑﻪ ﻧﻤﺎد ‪ LoC‬ﻣﻴﺮﺳﻴﻢ‪ .‬ﺑﺎ ﻳﻜﻲ از ﻛﻠﻴﺪ ﻫﺎي‬
‫‪ Up‬ﻳﺎ ‪ Dn‬آﻧﺮا ﺑﺘﺮﺗﻴﺐ زﻳﺮ ﺗﻨﻈﻴﻢ ﻧﻤﺎﻳﻴﺪ ‪.‬‬
‫تنظيمات کنترلر باز است‬
‫‪0‬‬
‫کليه تنظيمھای کنترلر قفل است‬
‫‪1‬‬
‫‪Loc‬‬
‫ﻧﻜﺘﻪ ‪ :‬ﻓﺸﺎر دﻛﻤﻪ ‪ Dn‬در ﺣﺎﻟﺖ اﺟﺮا‪ ،‬دﻣﺎي ﺟﺎري ﺳﻨﺴﻮر را ﻧﻤﺎﻳﺶ ﻣﻴﺪﻫﺪ ‪.‬‬
‫‪SUN-25H Controller User Manual‬‬
‫‪SUNWARD ENG‬‬