Instruction Manual Supplement
D103858X012
DVC6200 SIS
March 2014
Control Schematics for FIELDVUE™ DVC6200 SIS
Digital Valve Controller
The below drawings are guidelines ONLY, and should be modified/changed for site specific conditions. The guidelines
are not specific to individual user needs, applications, process conditions, environmental conditions, or safe state
functions and should be finalized in consultation with your local business partner before implementation. References
to the make and model number of specified third party vendor products is not to be construed as an endorsement
from Emerson Process Management—Fisher Controls International LLC.
For clarification or consultation, please contact your Local Business Partner who will consult Fisher Global Industry
Sales.
The attached schematics provide examples of a DVC6200 SIS in different modes (point-to-point mode or multi­drop
mode). The DVC6200 SIS can operate through a command signal from either a DCS (basic process control system,
BPCS) or logic solver (safety instrumented system, SIS). These are basic schematics that have been developed to
provide details of the connections between the control system and user interface. Drawings indicated as “PST Only”
depict the use of a DVC6200 SIS with a reverse acting relay (relay B).
These drawings are for reference ONLY and it may be possible to have many different combinations or permutations of
such schematics.
www.Fisher.com
Instruction Manual Supplement
DVC6200 SIS
D103858X012
March 2014
DISPLAY
ALARMS
ESDV STATUS
IN PROGRESS
Valve Stuck (PST Unsuccessful)
Options Available:
­LCP100 Local Control Panel or
external pushbutton
­SIL 2 Capable 4­20 mA position
transmitter or discrete switch
­Discrete switch can be configured
for position or alert annunciation
Notes:
­Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
­Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
AI or DI*
SERIAL
IN
Benefits:
­SIL 3 Capable digital valve controller
­Valve Shutdown and PST capability
­PST with DVC6200 SIS provides
diagnostic coverage
OUT
OUT
IN
Optional
Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
DO
IN
ValveLink™
Software
0­24V DC + HART
LC340
OUT
HART
MULTIPLEXER**
Optional LCP100 or
External Pushbutton PST
BPCS
SIS
FIELD
Scenario 1: SIS with DO to DETT FIELDVUE DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer
2
Instrument
Air Supply
Instruction Manual Supplement
DVC6200 SIS
D103858X012
March 2014
DISPLAY
ALARMS
IN PROGRESS
ESDV STATUS
Options Available:
­LCP100 Local Control Panel or
Valve Stuck (PST Unsuccessful) external pushbutton
­SIL 2 Capable 4­20 mA position
transmitter or discrete switch
­Discrete switch can be configured
for position or alert annunciation
AI or DI*
SERIAL
IN
Notes:
­Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
Benefits:
­SIL 3 Capable digital valve controller
­Valve Shutdown and PST capability
­PST with DVC6200 SIS provides
diagnostic coverage
OUT
OUT
IN
Optional
Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
Non-HART AO
IN
ValveLink
Software
4-20 mA + HART
Instrument
Air Supply
HF341/
HF340***
OUT
HART
MULTIPLEXER**
Optional LCP100 or
External Pushbutton PST
BPCS
SIS
FIELD
Scenario 2: SIS with AO to DETT DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer
***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HARTr communication
3
Instruction Manual Supplement
DVC6200 SIS
D103858X012
March 2014
DISPLAY
ALARMS
IN PROGRESS
ESDV STATUS
Valve Stuck (PST Unsuccessful)
Options Available:
­LCP100 Local Control Panel or
external pushbutton
­SIL 2 Capable 4­20 mA position
transmitter or discrete switch
­Discrete switch can be configured
for position or alert annunciation
Benefits:
­SIL 3 Capable digital valve controller
­Valve Shutdown and PST capability
­PST with DVC6200 SIS provides
diagnostic coverage
­Trigger diagnostics capture
shutdown event and reset
Notes:
­Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
AI or DI*
OUT
IN
Optional
Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
HART AO
IN
OUT
Instrument
Air Supply
4-20 mA + HART
HART Pass Through
ValveLink
Software
BPCS
Asset Management System
Optional LCP100 or
External Pushbutton PST
SIS
FIELD
Scenario 3: SIS with HART I/O to DETT DVC6200 SIS
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
4
Instruction Manual Supplement
DVC6200 SIS
D103858X012
March 2014
DISPLAY
ALARMS
IN PROGRESS
ESDV STATUS
Options Available:
­LCP100 Local Control Panel or
Valve Stuck (PST Unsuccessful) external pushbutton
­SIL 2 Capable 4­20 mA position
transmitter or discrete switch
­Discrete switch can be configured
for position or alert annunciation
Benefits:
­Prevents spurious trips on loss of
electrical power to DVC6200 SIS
­PST with DVC6200 SIS provides
diagnostic coverage
­Trigger diagnostics captures safety
demand and reset
‐Solenoid health monitoring
Notes:
‐ DVC6200 SIS with Relay B in ETT
configuration for PST diagnostic only
­Loss of pneumatic supply to DVC6200 SIS
exhausts air to valve
DO
SERIAL
0-24 V DC
IN
IN
OUT
AI or DI*
Non-HART AO
IN
OUT
OUT
4-20 mA
HF341/
HF340***
OUT
Optional Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
S
IN
Y
HART
Instrument
Air Supply
4-20 mA + HART
MULTIPLEXER**
ValveLink
Software
BPCS
Optional LCP100 or
External Pushbutton PST
SIS
FIELD
Scenario 4: SIS with DO to DETT Solenoid X BPCS with AO to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer
***HF341/HF340 may be required with legacy hosts to provide proper impedance to support HART communication
5
Instruction Manual Supplement
DVC6200 SIS
D103858X012
March 2014
DISPLAY
ALARMS
Valve Stuck (PST Unsuccessful)
ESDV STATUS
IN PROGRESS
Options Available:
­LCP100 Local Control Panel or
external pushbutton
­Integral 4-20 mA position
transmitter or discrete switch
Benefits:
­Prevents spurious trip on loss of
electrical power to DVC6200 SIS
­Trigger diagnostics captures safety
demand and reset
­PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
Notes:
‐ DVC6200 SIS with Relay B in ETT
configuration for PST diagnostic only
­Loss of pneumatic supply to DVC6200 SIS
exhausts air to valve
DO
0-24 V DC
IN
OUT
AI or DI*
OUT
Optional Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
S
IN
HART AO
IN
Y
4-20 mA + HART
OUT
Instrument
Air Supply
ValveLink
Software
BPCS
Asset Management System
Optional LCP100 or
External Pushbutton PST
SIS
FIELD
Scenario 5: SIS with DO to SOV X BPCS with HART I/O to DVC6200 SIS (PST Only)
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
6
Instruction Manual Supplement
DVC6200 SIS
D103858X012
DISPLAY
March 2014
IN PROGRESS
ESDV STATUS
Options Available:
­LCP100 Local Control Panel or
external pushbutton
Valve Stuck (PST Unsuccessful) ­SIL 2 Capable 4­20 mA position
transmitter or discrete switch
­Discrete switch can be configured
for position or alert annunciation
Benefits:
­SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
­Trigger diagnostics captures safety
demand and reset
­PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
ALARMS
Notes:
­Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
DO
IN
0-24 V DC
OUT
Optional Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
AI or DI*
OUT
S
IN
Instrument
Air Supply
HART AO
ValveLink
Software
BPCS
Asset Management System
HART Pass Through
IN
SIS
OUT
4-20 mA + HART
Optional LCP100 or
External Pushbutton PST
FIELD
Scenario 6: SIS with HART I/O to DETT DVC6200 SIS X SIS DO to DETT Solenoid
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
7
Instruction Manual Supplement
DVC6200 SIS
D103858X012
March 2014
DISPLAY
IN PROGRESS
ESDV STATUS
OUT
OUT
Notes:
­Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
‐ Single DO is a common cause failure point
­Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
Optional Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
AI or DI*
SERIAL
IN
Benefits:
­SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
­Wiring to both SOV and DVC6200 SIS
saves I/O
­PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
Options Available:
­LCP100 Local Control Panel or
Valve Stuck (PST Unsuccessful) external pushbutton
­SIL 2 Capable 4­20 mA position
transmitter or discrete switch
­Discrete switch can be configured
for position or alert annunciation
ALARMS
IN
S
DO
IN
ValveLink
Software
LC340
OUT
HART
MULTIPLEXER**
BPCS
Instrument
Air Supply
0-24 V DC
SIS
Optional LCP100 or
External Pushbutton PST
FIELD
Scenario 7: SIS with single DO to DETT DVC6200 SIS and DETT SOV
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink software or 475 Field Communicator can be used in lieu of multiplexer
8
Instruction Manual Supplement
DVC6200 SIS
D103858X012
March 2014
Options Available:
­LCP100 Local Control Panel or
external pushbutton
­SIL 2 Capable 4­20 mA position
Valve Stuck (PST Unsuccessful) transmitter or discrete switch
­Discrete switch can be configured
for position or alert annunciation
DISPLAY
ESDV STATUS
IN PROGRESS
Benefits:
­SIL3 Capable digital valve controller
‐Redundant DVC6200 SIS and SOV
­PST with DVC6200 SIS provides
diagnostic coverage
‐Solenoid health monitoring
ALARMS
Notes:
­Loss of electrical power or pneumatic
supply to DVC6200 SIS exhausts air to valve
­Trigger diagnostics or capture of
demand/reset strokes unavailable since
power to DVC6200 SIS is interrupted during
a demand
DO
SERIAL
0-24 V DC
IN
IN
OUT
OUT
Optional Position Feedback
(4­20 mA Analog
or 1 A Discrete Switch)
AI or DI*
OUT
IN
0-24 V DC + HART
Instrument
Air Supply
DO
IN
ValveLink
Software
LC340
OUT
HART
Optional LCP100 or
External Pushbutton PST
MULTIPLEXER**
BPCS
S
SIS
FIELD
Scenario 8: SIS with separate DO to DETT DVC6200 SIS and DETT SOV
Example Drawing Only, may require modifications to meet site specific requirements
*Position Monitor AI or DI may reside in SIS or BPCS
**PC with ValveLink Software or 475 Field Communicator can be used in lieu of multiplexer
9
DVC6200 SIS
March 2014
Instruction Manual Supplement
D103858X012
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, and ValveLink are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co.
Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART is a mark owned by the
HART Communication Foundation. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
10
E 2014 Fisher Controls International LLC. All rights reserved.