Use an .ini File (Administration>General>User Config File)
Status
Reports the progress of the upload. The upload succeeds even if the file contains
errors, but a system event reports the errors in the event log.
Upload
Browse to the customized file and upload it so that the current Rack PDU can use it to
set its own configuration.
To retrieve and customize the file of a configured Rack PDU, see How to
Export Configuration Settings.
Metered Rack PDU
USER’S GUIDE
Use the settings from one Rack PDU to configure another. Retrieve the config.ini file
from the configured Rack PDU, customize that file (e.g., to change the IP address), and
upload the customized file to the new Rack PDU. The file name can be up to 64
characters, and must have the.ini suffix.
®
Instead of uploading the file to one Rack PDU, you can export the file to multiple Rack
PDUs by using an FTP or SCP script or a batch file and the APC .ini file utility, available
on the Metered Rack PDU Utility CD and the APC Web site www.apc.com/tools/
download.
System Preferences (Administration>General>Preferences)
Color-coding events in the event log
This option is disabled by default. Mark the Event Log Color Coding checkbox to
enable color-coding of alarm text recorded in the event log. System-event entries and
configuration-change entries do not change color.
Text color
Definition
Red
Critical: A critical alarm exists, which requires immediate action.
Orange
Warning: An alarm condition requires attention and could
jeopardize your data or equipment if its cause is not addressed.
Black
Informational event
Green
Normal: No alarms are present.
78