Transcript
Error 36 contact for supply sensor T1 open check the data in Error mode boiler data during error 1 2 3 4 5 6 error operational status supply temp. return temp. kW burner % pump check the wiring 1 = 36 2 = 00 3 = -22 4 = xx* 5 = 00 6 = xx* *= variable value check the wiring for the sensor the wiring is OK but the error is repeated remove the plug from the flow sensor as a result of which Error 31 occurs replace the sensor Installation & Servicing Instructions Rinnai E-Series 15.2.17 83