EA460
Self Excited Automatic Voltage Regulator 120V or 240V
Compatible with Newage* Stamford SX460 regulator
Sensing Input
Voltage
 Voltage regulation < +/- 1%
 Soft start voltage ramping
 Sensing voltage loss protection
Frequency
 120 or 240 Vac sensing, jumper selectable
 Under frequency roll off protection
Output
Voltage
Current
 With under frequency LED indicator
Resistance
*All manufacturer names, numbers, symbols and descriptions are used for reference purpose only and do not imply that any part is the product of
these manufacturer.
Specifications
Sensing Input
Voltage 120 (95-132) or 240 (190-264) Vac
1 phase 2 wire jumper selectable
Output
9. Turn the stability potentiometer clockwise until
instability is shown, and then turn it anticlockwise
slightly still both meter mention in (5) and (6)
shown stable.
1. SPECIFICATION
Features
External Volts Adjustment
+/- 7% with 1K ohm 1 watt trimmer
Unit Power Dissipation
Max. 10 watts
Frequency
50 / 60 Hz jumper selectable
Soft Start Ramp Time
Voltage
Max. 90 Vdc at 207 Vac input
Under Frequency Protection
Current
Continuous 4A
Set Point
95% Hz (Factory Knee Point Setting)
Intermittent 10A for 10 sec.
Slope
170% down to 30 Hz
Resistance Min. 15 ohms
Environment
2 sec.
< +/- 1% (with 4% engine governing)
Storage Temperature
-40 - +85 °C
Build Up Voltage
Residual volts at AVR terminal > 5 Vac
Relative Humidity
Max. 95%
Thermal Drift
0.05% per °C change in AVR ambient
Vibration
3.3Gs @ 100-2K Hz
45.0
20.0
Under Frequency Protection
Set point
95% Hz
Max. 90 VDC @ 207 VAC
Continuous 4A
Intermittent 6A for 10 sec.
Min. 15 ohm
4. ADJUSTMENTS
( UFRO )
Slope
170% down to 30 Hz
Voltage Regulation
< ± 1.5% ( with 4% engine governing )
Soft Start Ramp Time
2 sec.
Voltage Build-up
Residual voltage at AVR terminal > 5 VAC
Dimensions
135mm L * 100mm W * 49mm H
Thermal Drift
0.05% per °C change in AVR ambient
Weight
243g ± 2%
● As using 50Hz, please connect a jumper between
Com and 50Hz. As 60Hz, between Com and 60 Hz.
2. When operations, please do not touch the
warning signal of the heat sink.
1. Connect F1, F2 to DC output port.
2. Connect the sensing port at 7, 8 (the factory setup
is 220V, if 110V is required, please join 3, 4)
VOLT
Voltage adjustment
STAB
Stability adjustment
UFRO
Setting under frequency protection knee point
3. External voltage regulator is as Figure 4.
4. Connect a jumper from COM to the 50Hz
terminal for 50Hz operation.
Note :
Dimensions
135.0 (L) x 100.0 (W) x 45.0 (H) mm
Weight
243 g +/- 2%
Please install 5A 250V fuse at power input port
as Figure 4.
135.0
114.0
Physical Specification
3. NOTICE OF USE
UFRO LED
STAB
5.4
1. Ensure all the wire of the regulator are correctly
connected and the proper fuse (5A250V) is
installed.
2. Turn voltage potentiometer full anticlockwise
( lowest voltage level).
3. If used, turn external voltage potentiometer to the
middle position.
full
5. Connect a 110VDC meter across the field with
proper polarity.
1. The connection and examination procedures
must be executed by the profession engineers.
6. Connect a 300VAC meter across line to neutral
of generator.
2. Place the EA460 inside of the generator,
especially the moisture-proof and anticorrosive
space.
3.2 Startup Procedure
7. Start and run the generator at no load and rated
speed. The generator output voltage should build
up to a minimum level if the voltage does not
build up, It may cause by low residual voltage of
generator. Refer to field flashing section in
generator manual.
1. The surface temperature pf the EA460 will be
over 60 °C.
8. Slowly adjust voltage potentiometer until the
generator voltage reach the proper value.
High Temperature
UNITS : mm
Wiring and adjustment
Figure 4
60HZ
40
20
0
10
20
30
40
50
60
1. When there is no connection to VR, 1 and 2 must be joined.
2. When LED lamp is light on, it means the frequency isn’t enough ,The output voltage will decrease to
prevent over load exciting current to damage the exciter field winding.
80
6. TROUBLE SHOOTING
60
SYMPTOM
40
Voltage does not
build up
11
50HZ
60
( (%
% OF
OFMONINAL)
NOMINAL)
GENERATOR OUTPUT VOLTAGE
80
11
((%
% OF
OF MONINAL)
NOMINAL)
GENERATOR OUTPUT VOLTAGE
Note :
100
20
0
1
FREQUENCY (HZ)
SOFT START (V/Sec)
Frequency Compensation Curves
Figure 2
Soft Start Curve
Figure 3
2
CAUSE
Out voltage high
Out voltage instable
CORRECTION
Residual voltage below 5VAC
Flash generator field with proper method
Incorrect wiring
Check wiring diagram for proper connection
Power/sensing or field wires not
connected
Connect the wires properly
Generator not up to speed
Out voltage low
Increase generator speed
Poor adjustment is made
Read start procedure carefully and adjust again
Frequency roll-off
Increase generator speed
Incorrect voltage selection
Read user’s manual to select correct voltage
Poor adjustment is made
Read start procedure carefully and adjust again
Incorrect voltage selection
Read user’s manual to select correct voltage
Poor adjustment is made
Read start procedure carefully and adjust again
Field voltage requirement lower
the rang of regulator
Inquire our distributor to solve
Use only original supplied spare protection fuse for fuse replacement.
Please accept our sincere apology if any modification in performance, specification or appearance is
made without prior notice.
______________________________________________________________________________________
______________________________________________________________________________________
4
EA460
EA460
4.2 Voltage Adjustment
WARNING
Overly field flashing may damage the AVR or
generator excitation winding.
Please make sure you have read and
understand the contents of the instruction
manual prior to installation. Incorrect wiring
connection may result in irreversible damage
to the product and other equipments.
2. If used, a 1000 ~ 1500Ω 1/2 watt potential meter
may be connected to terminals VR and VR, refer
to Figure 4.
4.3 Stability Adjustment
1. Adjust the front panel STAB control the system
stable. Rotation of the front panel STAB control
in the counter-clockwise (CCW) direction will
speed response time. If rotated too for CCW, the
generator voltage my oscillate (hunt).
2. Rotated the front panel STAB control CCW until
the system start oscillating and then rotate cw
just past the point where oscillation occurred.
5. FIELD FLASHING
When the regulator is operated with the generator
for the first time, the polarity of residual magnetism
may be reversed or too small to achieve the
necessary build-up voltage for the regulator. If
reversing the field connections does not induce
build-up, and the residual voltage is less than the
specified value of 5 VAC, shut down the
Prime-mover and proceed with the following steps :
EA460
STAB
120
3. Adjust the front panel U/F control until the output
voltage low about 5V than nominal voltage. ( For
50Hz applications, the frequency “Roll-off” is
factory preset to 45Hz, for 60Hz operation, the
frequency is 55Hz).
______________________________________________________________________________________
EA460
2. All voltage readings are to be taken
with an average-reading voltmeter
Meggers and high-potential test
equipment must not be used. Use of
such equipment could damage the
AVR.
100
4. If residual voltage is greater than 5VAC, but AVR
still unable to build up voltage, please replace
with another AVR.
2
ATTENTION
120
3. Disconnect the AVR AC power input terminals
and restart the generator, re-measure the
residual voltage. If this voltage is greater than
5VAC, reconnect voltage regulator, and voltage
build-up should be successful. If measured less
than 5VAC, repeat steps 1 and 2.
______________________________________________________________________________________
1. AVR can be mounted directly on the
engine, genset, switchgear, control
panel, or any position that will not
affects operation. For dimension
reference, please see Figure 1.
LED
clockwise
3.1 See Figure 1
VOLT
UFRO
2. Allow approximately 3 seconds before removing
the DC source.
1. Adjust the front panel VOLT to vary the generator
nominal voltage.
3.3 System Startup
4. Turn stability potentiometer
(highest stability level).
1. With the Prime-mover at rest and the regulator’s
field output wires disconnected, apply a DC
source ( NOT grounded ) of no more than 3~12
VDC with Positive to F+ and Negative to F-, in
series with a current-limiting resistor of 3~5 ohms
20 watt. (The set battery is a suitable source.)
1. Startup engine and build voltage.
2. Adjust the engine speedy down to low frequency.
VOLT
Outline Drawing
Figure 1
4.1 Frequency Roll-off Adjustment
● To reset the frequency roll-off, proceed as follow :
2. WIRING (Refer to Figure 4)
AVR Control Function
100.0
80.0
10.Interrupt regulator power for a short time
(approximately 1 to 2 second). If the voltage still
stable, the adjustment is now completed.
Otherwise increase the stability slightly, repeat
procedure (10) until stability is reached.
Unit Power Dissipation
Max. 10 watt
Operation Temperature -40 - +70 °C
Volts Regulation
Mechanical Specifications
External Volts Adjustment
±7% with 1K ohm 1 watt trimmer
95 ~ 132 VAC or 190 ~ 264 VAC
1 phase, jumper selectable
50 / 60 Hz, selectable
5