Download TeSys Model U - Electrocomponents
Transcript
Control unit information TeSys Model U Starter-controllers Data profile under AS-Interface Control unit present in the product Status Commands D0 D1 D0 D1 Standard Advanced Multifunction Standard Advanced Multifunction Ready (available) Poles closed (running) Forward running Reverse running Register addresses accessible under Modbus Control unit present in the product Identification Register 0…Register 99 Words…Bits Commercial reference, serial number, software version Log Register 100…Register 450 Words…Bits Fault log, Operating log, Log of last 5 trips Status Values Register 451…Register 464 Words…Bits Alarm signalling (bits), Fault signalling (bits) Register 465…Register 473 Words Irms phase 1, phase 2, phase 3. Motor load, thermal status Earth leakage current. Phase imbalance and phase failure Register 474…Register 599 Words…Bits Reserved Configuration Register 600…Register 699 Words…Bits Protection and alarm thresholds, fallback mode and reset mode Commands Register 700…Register 714 Words…Bits Commands Status and values Register 452 Register 455 Register 461 Register 465 Register 466 Configuration Register 602 Register 682 Commands Register 700 Register 704 Bit 0 Bit 1 Bit 2 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 3 Word Word Short-circuit fault Overcurrent fault Thermal overload fault Ready (available) Poles closed Fault Alarms Tripped (“TRIP” position) Fault acknowledgement allowed Reserved Motor running Motor current % (bit 0) Motor current % (bit 1) Motor current % (bit 2) Motor current % (bit 3) Motor current % (bit 4) Motor current % (bit 5) Reserved Motor starting Thermal overload alarm Thermal status value Motor load value (Im/Ir) Bit 0 Bit 1 Bit 2 Value 0 Value 1 Value 2 Value 3 Value 4 Value 5 Manual reset on thermal overload fault Remote reset on thermal overload fault Automatic reset on thermal overload fault Fallback mode validation Outputs OA1 and OA3 unchanged Outputs OA1 and OA3 forced to 0 Outputs OA1 and OA3 unchanged, signalling existence of communication failure Outputs OA1 forced to 1 and OA3 unchanged Outputs OA3 forced to 1 and OA1 unchanged Bit 0 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6…15 LO1 output command OA1 output command OA3 output command Reserved Fault acknowledgement Reserved Trip test Reserved Data accessible Schneider Electric 55