Download here - Voltsys.com
Transcript
Maintenance 000286AG Message displayed Codes Alarm displayed Cause 8 Solution Ground Fault Red LED Ground Fault The alarm is triggered when a ground dispersion current is detected in the DC section of the system. The alarm is accompanied by light-up of the red LED on the front of the inverter. Degauss error --- Degaussing state fail Input OV E002 Input Over voltage This alarm is triggered when the inverter input voltage (from the wind turbine) exceeds the threshold set for proper operation. The alarm is triggered before reaching the absolute threshold beyond which the inverter will be damaged. When the inverter input voltage exceeds the Over Voltage threshold, the inverter will not start because the alarm is triggered. It is necessary to measure the input voltage inside the inverter using a voltmeter. If it is higher than the maximum operating range voltage the alarm is genuine and the configuration of the wind turbine must be checked. If it is lower than the maximum operating range voltage the alarm is induced by an internal malfunction and you should contact the Power-One Service No Parameters E003 Internal Parameters Error The main microcontroller is not able to initialise the two DSPs (booster stage and inverter stage) properly. This is usually due to communication problems on the inverter’s internal bus. This is an internal error in the inverter that cannot be verified externally. If the problem persists (even after the inverter has been turned off and then on again), contact the PowerOne Service. Bulk OV E004 Bulk Over voltage Internal error in the inverter. The alarm is triggered when the voltage at the ends of the bulk condensers exceeds the Over Voltage threshold. The alarm may be due to causes external to the inverter. an excessive inverter input voltage may be read as a state of over voltage for bulk capacities. In this case it is advisable to check the inverter input voltage. If the value is close to the input OV threshold the wind turbine configuration should be adjusted. The alarm may also be due to causes internal to the inverter, and in this case it is necessary to contact the Power-One Service. Comm.Error E005 Internal Communication Error This alarm is triggered when there are Internal error in the inverter that cannot be verified externally. communication problems between the If the problem persists (even after the inverter has been control devices inside the inverter turned off and then on again), contact the Power-One Service. IGBT Sat E007 IGBT Saturation The alarm is triggered when one of the Every time the error occurs, the inverter attempts to restore active inverter devices is in a state of normal operation. If the error only occurs sporadically it saturation. may be induced by a sudden transition in the grid voltage or in the input voltage, but it is not due to a malfunction in the inverter.If the error is repeated frequently, consult the AN “Riso and Ileak Troubles Solving Guide” on the Power-One web portal (www.power-one.com). If the error relates to an internal malfunction it will continue to occur, and it is therefore necessary to contact the PowerOne Service. Internal error E009 Internal Error Internal error in the inverter Internal error in the inverter that cannot be verified externally. If the problem persists (even after the inverter has been turned off and then on again), contact the Power-One Service. Bulk Low E010 Low Bulk Voltage The alarm may be due to causes external to the inverter. a reduced input voltage in the inverter (only slightly higher than the activation voltage) that is not accompanied by a sufficient supply of power from the wind turbine (a state typical of periods of low wind). If the error message is triggered sporadically this may be due to causes outside the inverter (low wind and therefore low availability of power for the wind turbine). If the problem is repeated systematically even in the presence of high wind and with an input voltage significantly higher than the activation voltage, contact the Power-One Service. Ramp Fail E011 Bulk ramp timeout Internal error in the inverter relating to the time required by the DC-DC (Booster) circuit to operate at steady state Internal error in the inverter that cannot be verified externally. If the problem persists (even after the inverter has been turned off and then on again), contact the Power-One Service. - 82 - Check the connections on the DC side of the inverter and repeat the commissioning procedure. Check that the safeguards used to protect against transitory external over voltages are adequate and in a proper state of repair. Remove them and try again. Replace them if necessary. If the error is repeated frequently, consult the AN “Riso and Ileak Troubles Solving Guide” on the Power-One web portal (www.power-one.com).