[MONITORING] (SUP-) menu
rEF-
Code
Description
M [HMI Frequency ref.]
LFr
g
SEt-
Variation range
drC-
0 to 500 Hz
I-0-
Frequency reference for control via built-in display terminal or remote display terminal.
CtL-
M [Internal PID ref.]
rPI
g
0 to 100%
FUnFLt-
Internal PID reference
Parameter is only visible if [PID feedback ass.] (PIF) is not set to [No] (nO), page 81.
M [Frequency ref.]
FrH
COM-
0 to 500 Hz
SUP-
Frequency reference before ramp (absolute value).
M [Output frequency]
rFr
- 500 Hz to + 500 Hz
This parameter is also used for the +/- speed function using the jog dial on the keypad or display terminal.
It displays and validates operation (see page 58). In the event of a loss of line supply, [Output frequency]
(rFr) is not stored and the +/- speed function must be re-enabled in [MONITORING] (SUP-) and [Output
frequency] (rFr).
SPd1
or
SPd2
or
SPd3
M [Cust. output value]
[Cust. output value] (SPd1), [Cust. output value] (SPd2) or [Cust. output value] (SPd3) depending on the
[Scale factor display] (SdS) parameter, page 40 ([Cust. output value] (SPd3) in the factory setting)
M [Motor current]
LCr
Estimation of current in the motor
M [Motor power]
Opr
100% = nominal motor power, calculated using the parameters entered in the [MOTOR CONTROL]
(drC-) menu
M [Mains voltage]
ULn
This parameter gives the line voltage via the DC bus, both in motor mode or when the motor is stopped.
M [Motor thermal state]
tHr
100% = nominal thermal state
118% = "OLF" threshold (drive overload)
M [Drv. Therm att.]
tHd
100% = nominal thermal state
118% = "OHF" threshold (drive overheating)
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and set from within the configuration menu for the corresponding function, their description is detailed in
these menus, on the pages indicated, to aid programming.