The operation and functions described in this manual are available from Software Version Mx4100-023, Mx4200-023 and
Mx4400-023 onwards.
www.advancedco.com
This page is intentionally left blank.
www.advancedco.com
Contents
1
INTRODUCTION
1.1
1.2
1.3
2
2.1
2.2
2.3
2.4
2.5
2.6
3
5
STANDARDS
CAUTIONS AND W ARNINGS
GENERAL DESCRIPTION
5
6
6
CONTROLS AND INDICATIONS
7
GRAPHICAL DISPLAY
LED STATUS INDICATORS
CONTROL BUTTONS
NAVIGATION BUTTONS
NUMBER AND LETTER BUTTONS
BUZZER
OPERATION
3.1
ACCESS LEVELS
3.1.1 Changing from Access Level 1 to Level 2
3.1.1.1
3.1.1.2
Menu Access
Control Buttons at Level 1
3.1.2 Changing from Access Level 2 to 1
3.2
FIRE ALARM CONDITION
3.2.1 Detailed Fire Alarm Information
3.2.2 Investigation Delays
3.3
FAULT CONDITION
3.4
DISABLEMENT CONDITION
3.4.1 Disabled Inputs
3.4.2 Disabled Outputs
3.5
ALARM CONDITION
3.6
MENU FUNCTIONS
3.6.1 Using the Buttons to Navigate Menus
3.6.1.1
3.6.1.2
Selecting Menu Options
Selecting Individual Zone Numbers
3.7
VIEWING
3.7.1 View - Fires
3.7.2 View - Faults
3.7.3 View - Alarms
3.7.4 View - Disabled
3.7.5 View - Inputs
3.7.6 View - Outputs
3.7.7 View - Panel
3.7.8 View - Log
3.7.8.1
3.7.8.2
Event Log
Alarm Counter
3.7.9 View - Network
3.7.10
View - Logic
3.8
DISABLING
3.8.1 Disable - Zones and Inputs
3.8.2 Disable - Outputs
3.8.2.1
3.8.2.2
3.8.2.3
3.8.2.4
3.8.2.5
3.8.2.6
All Sounder Outputs
All Other Outputs
Selected Outputs
Fire Routing Output
Fault Routing Output
Pager
3.8.3 Disable - Controls
3.8.4 Disable - Delay-Mode
3.8.5 Disable – User ID
3.8.6 Disable – Groups
3.9
ENABLING
3.9.1 Enable - Zones and Inputs
3.9.2 Enable - Outputs
3.9.3 Enable - Delay-Mode
3.9.3.1
Extend Delays
www.advancedco.com
7
8
8
9
9
9
10
10
10
10
11
11
11
12
13
14
15
15
16
16
17
18
18
18
19
19
19
19
19
19
20
21
22
22
22
22
23
23
23
24
25
25
25
25
25
25
25
26
27
27
28
28
28
28
28
3
3.9.3.2
4
Holiday / Inhibit
28
3.9.4 Enable - Groups
3.9.5 Enable - Change-Time
3.9.6 Enable - Remote
3.10
TESTING
3.10.1
Test - Zones
3.10.2
Test - Display
3.10.3
Test - Buzzer
3.10.4
Test - Printer
3.10.5
Test - Outputs
3.11
PRINTING
3.11.1
Printer Communications Settings
3.11.2
Set-up Printer
3.11.3
Print Inputs
3.11.4
Print Outputs
3.11.5
Print Faults
3.11.6
Print Disabled
3.11.7
Print - Log
3.11.8
Print - Feed Paper
29
29
30
31
31
32
32
33
33
34
34
34
34
35
35
35
36
36
www.advancedco.com
1 Introduction
1.1 Standards
Advanced Electronics Ltd declare that the products identified below conform to the essential requirements
specified in the Construction Products Directive 89/106/EEC:
0086-CPD-549125
EN54-2: 1997 +A1:2006
Control and indicating equipment for fire detection and fire
alarm systems for buildings
Provided options:
Outputs to Fire Alarm Devices
Output to Fire Routing Equipment
Output to Fault Routing Equipment
Investigation Delays to Outputs
Dependency on more than one alarm signal
Fault Signals from Points
Disablement of Points
Alarm Counter
Test Condition
Standardised Input / Output
EN54-4: 1997 +A1:2002 +A2:2006
Power supply equipment for fire detection and fire alarm
systems for buildings
Mx-4100, Mx-4100/L, Mx-4200, Mx-4200/D, Mx-4400, Mx4400/D, Mx-4400/LE and Mx-4800
In addition, the products comply with the following:
Low Voltage Directive 2006/95/EC
EN60950-1: 2006
Safety of information technology equipment
Electromagnetic Compatibility Directive 2004/108/EC
EN61000-6-3:2001
Emissions, Class B
EN50130-4: 1995 +A1:1998 +A2: 2003
Immunity, Product Family Standard
www.advancedco.com
5
1.2 Cautions and Warnings
STOP
Before commencing with installation or operation of the panel, please read this
manual carefully. If you are unclear on any point DO NOT proceed. Contact the
manufacturer or supplier for clarification and guidance.
Only Trained service personnel should undertake the Installation, Programming and
maintenance of this equipment.
This product has been designed to comply with the requirements of the Low Voltage
Safety and the EMC Directives. Failure to follow the installation instructions may
compromise its adherence to these standards.
This Fire Alarm Control Panel is compliant with the requirements of EN54 parts 2
and 4 (1998).
Where appropriate, reference is made in this manual to the relevant sections of the
EN54 standard for clarification and to ensure that the installation is compliant with
the requirements of EN54.
1.3 General Description
This manual covers the use and operation of the Mx-4100, Mx-4200 Mx-4400 and Mx-4800 Fire Alarm Control
Panels. Refer to the Installation and Commissioning Manual (Document No. 680-014) for details of how to install
and program the panel.
The Mx-4100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel.
The Mx-4200 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to two
loops.
The Mx-4400 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to four
loops.
The Mx-4800 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to
eight loops.
All four panels are designed for use with the Apollo Discovery, Explorer, XP95, Series 90 and Hochiki ESP
ranges of fire detection equipment.
6
www.advancedco.com
2 Controls and Indications
The Mx-4100, Mx-4200, Mx-4400 and Mx-4800 are provided with indications and control functions as shown in
the diagram below and described in the following text. The Mx-4800 has two such display elements, one for
loops 1-4 and the other for loops 5-8. Normal operator level indications, controls and user programming can all
be achieved using either display.
Graphic Liquid
Navigation
Crystal Display
Buttons
SOU N D ER
SIL EN C ED
FIRE
FA U LT
SOU N D ER
FA U LT
DI SA B LE
SOU N D ER
DI SA B LE D
RESET
!
POW ER
DEF
GH I
JKL
MNO
PQRS
TUV
WXYZ
MU TE
SILENCE/
RESOU ND
SYS TEM FA U LT
T EST
AB C
EVAC UATE
DE L AYED
ESC
LED Status
Indicators
Control
Buttons
MEN U
Number and
Letter Buttons
2.1 Graphical Display
The graphical display provides detailed information of the source of fire alarms, faults and warnings. It also
shows menus for use when inspecting or programming the operation of the panel.
Under normal conditions the panel display shows the access level, time, date and status: LEVEL 2
16:05
04 MAR 2006
NORMAL PANEL OPERATION
(Press Menu to View)
www.advancedco.com
7
2.2 LED Status Indicators
The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire
alarm, fault, disabled or test condition.
Function
Colour
Description
FIRE
Red
Indicates that the system has detected a fire alarm condition (flashes on
a new alarm and turns on steady when mute button is pressed).
Fault
Yellow
Indicates that the system has detected a fault condition (flashes on a
new fault and turns on steady when mute button is pressed).
Disable
Yellow
Indicates that part of the system has been disable (i.e. isolated)
Test
Yellow
Indicates that part of the system is in a test condition
Power
Green
Indicates the presence of power
Sounder Silenced
Yellow
Indicates that the sounders have been silenced
Sounder Fault
Yellow
Indicates the presence of a fault in one or more sounder wiring circuits
Sounder Disabled
Yellow
Indicates that one or more sounders have been disabled (i.e. isolated)
System Fault
Yellow
Indicates the presence of a system fault
Delayed
Yellow
Indicates that one or more output circuits are in a delayed operating
condition
Function 1
Red
Fire Brigade Output Activated
Or
Spare function LED
Function 2
Yellow
Fire Brigade Output Disabled
Or
Spare function LED
Function 3
Yellow
Fire Brigade Output Fault
Or
Spare function LED
Function 4
Yellow
Spare function LED
Function 5
Yellow
Spare function LED
The function LED Indicators are programmable and will have been configured and labelled accordingly during
installation and commissioning of the system.
2.3 Control Buttons
!
Reset
Press to reset the panel from a fire alarm condition.
Only available with
Level 2 Access.
Mute
Press to mute the internal buzzer.
Available in both
Level 1 and Level 2
Silence / Resound
Press to silence the sounders.
Only available with
Level 2 Access.
Press again to re-activate the sounders.
Evacuate
Press to initiate a manual evacuation and sound the alarms.
8
Only available with
Level 2 Access.
www.advancedco.com
2.4 Navigation Buttons

Press to scroll through Menu Options.
Press to display more information.
Press to scroll through lists of zones or devices.
Press to confirm entry of numeric or letter information entry.
Press to confirm selection of a menu option.
Press to change some of the configuration options.
✔
2.5 Number and Letter Buttons
GHI
ABC
D EF
JKL
MNO
Used to enter numbers or letters.
PQRS
TUV
ESC
Esc
Menu
WXYZ
MENU
Press to return to a previous menu.
Press to exit the menu functions and return to the normal display.
Press to show or return to Menu Functions.
2.6 Buzzer
The buzzer produces two different sounds to differentiate between fire alarm conditions and fault conditions.
Condition
Operation
Fire Alarm
The buzzer operates with a continuous tone.
Fault
The buzzer operates intermittently.
www.advancedco.com
9
3 Operation
3.1 Access Levels
The panel operation is protected from inadvertent and erroneous misuse by means of four access levels. These
levels are as follows:
Level 1
Level 2
Level 3
Level 4

Untrained user
Authorised User
Service and Maintenance Engineer
Service and Maintenance Engineer – Special Tools required
A Level 1 Untrained User can view the current operational condition of the system and may
MUTE the internal buzzer.
NOTE: Depending on the configuration settings, a Level 1 user may also be permitted to EVACUATE and/or SILENCE
and/or RESET the system by pressing the appropriate button and entering a password.

A Level 2 Authorised User can view the operational condition of the system and may MUTE the
internal buzzer. In addition, the EVACUATE, SILENCE and RESET buttons are enabled and
access to the Level 2 Menu functions is available.
NOTE: There are up to 10 User ID codes available, each with its own password, which can be configured with varying
permissions to specific menu function options.

A Level 3 User has access to program and configure the operation of the panel. This is described in
detail in the Installation and Commissioning Manual (Part Number 680-014).
3.1.1 Changing from Access Level 1 to Level 2
If the panel has an access key switch fitted, use the key in preference to the menu options shown
below.
3.1.1.1 Menu Access
Press the ‘MENU’ button. The level 1 menu will be displayed as shown below:
[ CONTROLS DISABLED ]
ENABLE CONTROLS
LED TEST
VIEW
STATUS
To enable the controls, ensure the “Enable Controls” option is highlighted and then press the ✔ button. The
display then requests entry of the Level 2 or 3 passwords as follows:
[ CONTROLS DISABLED ]
Please Enter Your Password
Enter the password using the number buttons and then press the ✔ button. As each number is entered, an
asterisk (*) is shown on the display. For example:
[ CONTROLS DISABLED ]
Please Enter Your Password
**
If the password is correct, the Level 2 Menu options will be shown.
If the password is incorrect, the display briefly shows the following message.
10
www.advancedco.com
[ CONTROLS DISABLED ]
Please Enter Your Password
Password Not Recognised !
3.1.1.2 Control Buttons at Level 1
If any of the control buttons (Reset, Silence / Resound or Evacuate) are pressed, the display automatically
prompts for the password. Enter the password as above
3.1.2 Changing from Access Level 2 to 1
If the panel has an access key switch fitted, use the key switch.
Alternatively, if passwords are used, select the “Disablement” menu and then select “Disable/Controls” – see
section 3.8.3 for details.
3.2 Fire Alarm Condition
When the system registers a fire alarm condition the Red Fire Indicator illuminates, the internal buzzer sounds
(continuously) and the display shows the zone in which the fire originated. The sounders, relays and other
outputs will be turned on depending on the programming in the panel. An example of the display is shown
below: FIRE STARTED IN ZONE 0001
BASEMENT WEST
KITCHEN
<CALL POINT
.
>
< Location Text for First Zone
< Location Text and Type of Device
[
1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
The upper part of the display shows the origin of the fire. The lower part of the display shows the number of
zones in a fire alarm condition and the last zone to enter the fire alarm condition. This lower fire alarm status
display is always present when the panel has registered a fire alarm condition.
If more than one fire alarm condition occurs, the total number of zones in an alarm condition and the last zone in
an alarm condition will be updated on the display. If the sounders were silenced, they will sound again whenever
the fire spreads to a new zone.
FIRE STARTED IN ZONE 0001. More Alarms>
BASEMENT WEST
KITCHEN
<CALL POINT >
< Location Text for First Zone
< Location Text and Type of Device
[
2 Zones in Fire][Last Fire in Z0005]
BASEMENT EAST
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
Press the ‘MUTE’ button to silence the internal buzzer (the FIRE LED will change from flashing to steady
illumination).
When the panel is enabled for Level 2 Access or, if configured, by entering a password at Level 1, the following
functions are available.
Press the ‘SILENCE / RESOUND’ button to silence the sounders.
Press the ‘SILENCE / RESOUND’ button again to re-activate the sounders.
Press the ‘RESET’ button to clear the alarm condition and restore the panel to normal operation.
Press the ‘EVACUATE’ button to initiate a manual evacuation and to activate the sounders. The display will
show this fire alarm condition. For example:
www.advancedco.com
11
FIRE STARTED IN ZONE 0100
MAIN RECEPTION
Evacuation Key
<SWITCH
.
>
[
1 Zone in Fire][Last Fire in Z0100]
MAIN RECEPTION
< Location Text for First Zone
< Confirmation of Evacuation
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
3.2.1 Detailed Fire Alarm Information
Press the  buttons to view a list of all zones in a fire alarm condition.
Zone
0001
0005
FIRE-LOCATION
BASEMENT WEST
BASEMENT EAST
Scroll 
More>
< List of Zones in Alarm including
< Zone No. and location text
If more detail regarding the source of any fires is required, press the  buttons to highlight the required zone
in alarm and press the  button to show further information. For example:
[
FIRES IN ZONE 001 ]
LP ADRS DEVICE LOCATION
1 001.0 KITCHEN
More>
[
2 Zones in Fire][Last Fire in Z0005]
BASEMENT EAST
< List of devices within the Zone
< that are in Alarm
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
This shows that the device at address 1 on the loop initiated the fire in Zone 1. If there are more Zone 1 devices
in alarm, these will be shown in the list. Press the  buttons to scroll through the devices.
Press the  button or the ‘Esc’ button to return to the previous display. If no button is pressed within 15seconds, the display automatically reverts to the main display.
12
www.advancedco.com
3.2.2 Investigation Delays
The Investigation Delay Function can be disabled or enabled as required by EN54: 2.
Refer to Section 3.8.4.
If the Investigation Delay Function (Stage 1 / Stage 2 Investigation Delay) is enabled, a fire alarm is registered
at the panel but does not immediately activate the sounders. On registering the alarm, the display shows:
FIRE STARTED IN ZONE 0001
.
BASEMENT WEST
KITCHEN
<TEMPERATURE>
OUTPUT DELAY
30 s (Press 0 to extend)
[
1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST
< Location Text for First Zone
< Location Text and Type of Device
< Delay Timer (Stage 1)
The Output Delay Timer shows the amount of time left for investigation.
If the alarm is not acknowledged before the Stage 1 timer elapses, the panel will enter a full alarm condition and
will activate the sounders.
Pressing the ‘0’ button acknowledges the alarm. This extends the time allowed to investigate the source of the
fire.
FIRE STARTED IN ZONE 0001
.
BASEMENT WEST
KITCHEN
<TEMPERATURE>
OUTPUT DELAY 120 s
[
1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST
< Location Text for First Zone
< Location Text and Type of Device
< Delay Timer (Stage 2)
The cause of the alarm can now be investigated. If the alarm is a false alarm, pressing the ‘RESET’ button will
clear the alarm condition. This must be done before the Stage 2 timer has elapsed or the panel will enter a full
alarm condition and will activate the sounders.
Note: The EVACUATION button will terminate the investigation delays and activate all programmed sounders.
www.advancedco.com
13
3.3 Fault Condition
When the system registers a fault condition the Yellow Fault Indicator is illuminated, the internal buzzer sounds
intermittently and the display shows the cause of the fault in more detail.
An example of the display is shown below:
ZONE 0001
BASEMENT WEST
RESTAURANT
1 Zone
DEVICE MISSING
(MULTI.SENSOR)
In Fault
More>
< Location Text for First Zone
< Location Text and Type of Device
< No. of Zones in FAULT
If more than one fault condition occurs, these will be shown on the display. If the internal buzzer was muted, it
will sound again when a new fault condition is registered.
When the fault condition is corrected, the panel automatically clears the appropriate fault Status Indicators and
Display information.
Press the ‘MUTE’ button to silence the internal buzzer (the general FAULT LED will change from flashing to
steady illumination). The display then shows the current time and date and service centre telephone number
along with the indication of the fault.
FOR SERVICE CALL
01234 567890
1 Zone
LEVEL 2
16:05
04 MAR 2006
In Fault
More>
< Panel access level
< Service Call Number
< and Time / Date
< No. of Zones in FAULT
To obtain more detailed information about the faults, press the  button. The display then presents a list of all
of the zones in a fault condition with the first fault highlighted. For example:
[
2
ZONE
1
100
Zones in Fault]
LOCATION
BASEMENT
RECEPTION
More>
< Number of zones in fault
< Zone #, Location Text for each
< zone
Press the  buttons to highlight the required fault and then press the  button to show further information.
For example:
[
Faults in Zone 0001 ]
LP ADRS STATE
1 004.0 DEVICE MISSING
More>
< Address, fault condition
Press the  button to show further information on device location, type analogue/digital values etc.
Press the ‘ESC’ key to return to the previous display.
If no button is pressed within a minute, the display automatically reverts to the main display.
14
www.advancedco.com
3.4 Disablement Condition
If any zones, input devices or output devices have been disabled, the DISABLE Indicator is illuminated. In
addition, the SOUNDER DISABLE Indicator is illuminated if one or more sounder circuits or devices have been
disabled. The display indicates the presence of zone disablement conditions in the lower half of the display as
follows:
LEVEL 2
16:05
04 MAR 2006
1 Zone With Disablements
More>
When the disablement conditions are removed, the appropriate indications are cleared from the display and
from the Indicators. When all disablement conditions are removed, the DISABLE Indicator is also turned off.
To obtain more detailed information about the disablement conditions, press the  button. The display will then
present the disablement conditions in the following sequence:


Zone / Individual Inputs.
Outputs
3.4.1 Disabled Inputs
The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For
example:
[
2 Zones with Inputs Disabled]
ZONE MODE
LOCATION
0001 PART DISABLED BASEMENT WEST
0002 ALL DISABLED BASEMENT EAST
More>
< Zone, disablement condition and
< location text
The display shows the status as ALL DISABLED if every input device within the zone has been disabled and
shows the status as PART DISABLED if there is at least one input device within the zone still active.
Press the  buttons to highlight the required zone and then press the  button to view the location text
assigned to the zone in full. For example:
Press the  button again to view the inputs within the zone and their status. For example:
[ Inputs in Zone 0001 ]
Mode
Lp Adrs
State
Enabled
1 001.0 Normal
Disabled 1 002.0 Normal
Enabled
1 003.0 Normal
Enabled
1 004.0 Normal
<More>
The display shows the current disablement condition (mode) for each input as either enabled or disabled. In
addition, the detection loop (LP), address (ADRS) and type of input are shown. Press the  buttons to scroll
through the inputs.
Press the  button to show further information on device location, type analogue/digital values etc.
Press the ‘ESC’ key to return.
If there are Outputs also disabled, these will now be shown.
www.advancedco.com
15
3.4.2 Disabled Outputs
The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For
example:
[ 2 Zones with Outputs Disabled]
Zone Mode
Location
0001 DISABLED BASEMENT WEST
0100 DISABLED RECEPTION
More>
< Zones with location text where
< outputs are disabled
Press the  buttons to highlight the required zone and then press the  button to view the individual outputs
and their disablement condition. For example:
[ Outputs in Zone 0100]
Mode
Lp Adrs
State
Disabled 0 001.0 Off
Disabled 0 001.1 Off
Enabled
0 011.0 *Off
Enabled
0 004.0 Off
More>
Sounder
Sounder
Relay
Relay
A
B
1
2
The above example shows that the panel sounder circuits are disabled.
A * symbol preceding the state (e.g. *Off) indicates the device has been configured as an inverted output (e.g. a
fault relay that is designed to de-energise when a fault occurs).
Press the  buttons to scroll through the list of individual outputs within the selected zone. Press the ‘Esc’
button to return to previous views and the main display.
3.5 Alarm Condition
When the system registers a pre-alarm or plant alarm condition, the internal buzzer sounds intermittently and
the display shows the cause of the fault in more detail. An example of the display is shown below:
ZONE 0001
BASEMENT WEST
RESTAURANT
1 Zone
In Alarm
PRE-ALARM
(MULTI.SENSOR)
More>
< Location Text for First Zone
< Location Text and Type of Device
< No. of Zones in Alarm
To obtain more detailed information about the alarms, press the  button. The display then presents a list of all
zones in an alarm condition.
16
www.advancedco.com
3.6 Menu Functions
The following Menu Functions are available at Level 2. The display shows the primary Level 2 Menu and the
Level 2 User as follows:
[Level 2 Menu]
VIEW
TEST
User 1 Node
DISABLE
PRINT
STATUS
1
ENABLE
COMMISSION
The following table gives a list of the Level 2 Menu Functions, the sub-functions available within each main
function and a brief description for each function.
Main Menu Option
Sub Menus
Comments
VIEW
Fires
View Zones and Inputs that are reporting a fire alarm condition.
Faults
View Zones and Inputs that are reporting a fault condition.
Alarms
View Zones and Inputs that are reporting an alarm condition.
Disabled
View Zones, Inputs and Outputs that are disabled.
Inputs
View the current state of Inputs.
Outputs
View the current operational condition of all output circuits / devices.
Log
View the Event Log / Alarm Counter
Panel
View the operational state, voltage and current loading of the panel input and
output circuits.
Network
DISABLE
View Network diagnostics
Zone / Inputs
1
Outputs 1
Controls
Disable sounder outputs or other devices.
2
Cancel Level 2 access.
Delay-Mode
User ID
ENABLE
Turn off the Stage 1 / Stage 2 Investigation Delay Operation
2
Return Level 2 access to the default User 1
Groups
Disable a user-defined disablement group
Zone / Inputs
Enable a complete zone or an individual input.
Outputs
Enable sounder outputs or other devices.
Groups
Enable a user-defined disablement group
Delay-Mode
Change-Time
Remote
TEST
PRINT
Disable a complete zone or an individual input.
Zones
1
Turn on the Stage 1 / Stage 2 Investigation Delay Operation
1
Allows authorised level 2 users to change time.
Permits remote access controls
Configure one or more zones for walk test.
Display
Test the Graphics Display, Status Indicators and Keyboard.
Buzzer
Test the Internal Buzzer
Printer
Test the connection to the Printer
Outputs
Test Output Devices
Inputs
Print the status of inputs
Ouputs
Print the status of outputs
Faults
Print the fault conditions
Disabled
Print the disabled conditions
Log
Print the Event Log. (All Events of Fire Only Events Selectable).
Feed Paper
Set-up
1
Advance the paper in the printer
Configure the printer connection and automatic print options
STATUS
--
Returns the display to the normal operating display without wating for the timeout
COMMISSION
---
Enter the Level 3 Commissioning and Panel Programming Functions
1
2
This option can be configured per Level 2 User ID. User 1 does not have permission to change these options.
Not required if a key switch is fitted to change access levels.
www.advancedco.com
17
3.6.1 Using the Buttons to Navigate Menus
Press the ‘Menu’ button to bring up the display menu.
3.6.1.1 Selecting Menu Options
The Level 2 Menu is shown below:
[Level 2 Menu]
VIEW
TEST
User 1 Node
DISABLE
PRINT
STATUS
1
ENABLE
COMMISSION
Press the  buttons to highlight the required menu option and then press the ✔ button to select it.
For example, press the  button followed by the  button to highlight the PRINT option (as shown below) and
then press the ✔ button to select this option.
[Level 2 Menu]
VIEW
TEST
User 1 Node
DISABLE
PRINT
STATUS
1
ENABLE
COMMISSION
Press the ‘Esc’ button from within a menu option to return to the previous menu.
Press the ‘Esc’ button from the Main Level 2 Menu (shown above) to return to the normal operating display.
If a button is not pressed for one minute (15-seconds if the panel is in a fire alarm condition) the display will
automatically revert to the normal operating display. Press the ‘Menu’ button to return directly to the Level 2
Menu display previously shown.
3.6.1.2 Selecting Individual Zone Numbers
When the display is showing a list of Zone Numbers, it is possible to select a specific zone number by using the
number keys. For example, if the display is showing a list of zones:
[ Inputs]
Zone
Mode
0001
Enabled
0002
Enabled
0008
Enabled
0009
Enabled
More>
Location
BASEMENT WEST
BASEMENT EAST
GROUND FLOOR
MAIN RECEPTION AREA
To select a particular Zone, move to the zone number column. The existing zone number will then be
highlighted.
Enter the required Zone Number using the number buttons, for example 12.
[ Inputs]
Zone
Mode
# 12 Enabled
0002
Enabled
0008
Enabled
0009
Enabled
More>
Location
BASEMENT WEST
BASEMENT EAST
GROUND FLOOR
MAIN RECEPTION AREA
Finally press the ✔ button to confirm. The display will then show a new list of Zones with the selected Zone
highlighted at the top of the list.
If the number is entered incorrectly, press the ‘Esc’ button.
18
www.advancedco.com
3.7 Viewing
[View Menu]
FIRES
INPUTS
FAULTS
OUTPUTS
User 1 Node
ALARMS
PANEL
DISABLED
NETWORK
1
LOG
LOGIC
Note that Fires, Faults, Alarms and Disablements are all normally shown without having to select the view
menu. If, however, you wish to manually View any of these, they can be selected from this menu as required.
3.7.1 View - Fires
This function shows the Zones and Inputs that are currently in a Fire Alarm condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.2 for further information.
If there are no Zones or Inputs in a Fire Alarm condition, the display automatically reverts to the Main View
Menu.
3.7.2 View - Faults
This function shows the Zones, Inputs and Outputs that are currently in a Fault condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.3 for further information.
3.7.3 View - Alarms
This function shows the Zones and Inputs that are currently in an Alarm condition. These may occur if:


The Zone or Input is currently in a Fire Test condition and / or
Inputs that are configured to generate an alarm or pre-alarm condition when operated are active.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display.
3.7.4 View - Disabled
This function shows only Inputs and Outputs that are currently in a Disabled condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.4 for further information.
If there are both Inputs and Outputs in a Disabled condition, the display presents the inputs first, followed by the
outputs.
If there are no Inputs or Outputs in a Disabled condition, the display does not change and continues to show the
Main View Menu.
3.7.5 View - Inputs
This function shows the current operational condition for all Zones and Individual Inputs. The display presents a
list of all of the zones containing input devices, with the first zone highlighted. For example:
www.advancedco.com
19
[ Inputs]
Zone Mode
0001 Enabled
0002 ALL DISABLED
0008 Enabled
0009 Enabled
More>
Location
BASEMENT WEST
BASEMENT EAST
GROUND FLOOR
MAIN RECEPTION AREA
Press the  buttons to highlight the required zone and then press the  button to view the full location text
Press the  button again to view the inputs within the zone and their status. For example:
[ Inputs in Zone 0008]
Mode
Lp Adrs
State
Enabled
1 001.0 Normal
Disabled 1 002.0 Normal
Enabled
1 003.0 Normal
Enabled
1 004.0 Normal
<More>
The display shows the current disablement condition (mode) for each input as either enabled or disabled. In
addition, the detection loop (Lp), address (Adrs) and input state are shown.
Press the  buttons to scroll through the inputs.
Press the  button to show further information on device location, type analogue/digital values etc.
Press the ‘Esc’ button to return to previous view.
3.7.6 View - Outputs
This function shows the current operational condition for all Outputs.
[Outputs]
More>
Zone
Mode
0008
ENABLED
0100
ENABLED
Location
GROUND FLOOR
MAIN RECEPTION
Press the  buttons to highlight the required zone and then press the  button to view the individual outputs.
For example:
[ Outputs In Zone 0008]
Mode
Lp Adrs
State
Enabled 1 032.0 Off
Enabled 1 056.0 Off
Enabled 2 011.1 *On
Enabled 3 026.1 Off
More>
SOUNDER
SOUNDER
RELAY
RELAY
A * symbol preceding the state (e.g. *On) indicates the device has been configured as an inverted output (e.g. a
fault relay that is designed to de-energise when a fault occurs).
20
www.advancedco.com
3.7.7 View - Panel
The View Panel Option provides a diagnostic readout of the operational condition and readings for the internal
panel electronic circuits. When the option is selected, the display shows a list of the circuits. For example:
[Panel Circuits]
ITEM DESCRIPTION
VALUE
01.0 Sounder A
5.6V
01.1 Sounder B
5.6V
02.0 Sounder A Load
0mA
02.1 Sounder B Load
0mA
STATE
Normal
Normal
Normal
Normal
The following table lists the internal panel circuits and indicates the values that can be displayed.
Item
Description
Value Range
Normal
Possible States
01.0
Sounder A
01.1
Sounder B
0V – 14V
5.5V
Normal
Open Circuit, Short Circuit
02.0
Sounder A Load
02.1
Sounder B Load
0mA – 1000mA
4
Normal
Too High
03.0
Battery
0V – 30V
>25.0V
Normal
Too High, Too Low
04.0
Charger
0V – 30V
27.6V
Normal
Too High, Too Low
05.0
Earth Monitor
0V – 30V
1.3V
Normal
Too High, Too Low
0mA – 500mA
4
Normal
Too High
0mA – 500mA
4
Normal
Open Circuit, Too High, Short
Circuit
24V – 32V
4
Normal
24V – 32V
4
Normal
L/H
L
Normal
06.0
3
Aux Supply
st
6
07.0
1 Loop Load
08.0
1 Loop V.Out
09.0
3
st
st
1 Loop V.In
6
6
10.0
to
5
Panel Switch Inputs
10.7
Programmable inputs
Normal
L/H
L
Normal
11.0
Relay 1
–
–
Normal
11.1
Relay 2
–
–
Normal
11.2
Output 1
–
–
Normal
11.3
Output 2
–
–
Normal
Press the  buttons to scroll through the panel internal circuits. Press the ‘Esc’ button to return to the main
view menu.
NOTE: Additional panel circuits may be shown depending on the system configuration and installed options.
3
The MX-4400 also displays Sounders C and D.
Depends on the panel configuration, installation and current operating condition (i.e. fire alarm).
The voltage shown is the voltage of the battery as measured under full load conditions. If this voltage falls below 23.0V under full load test,
the panel will indicate a Too Low condition.
6
Loop Load, V.Out and V.In displayed for each loop driver (2 on MX-4200, 4 on MX4400).
4
5
www.advancedco.com
21
3.7.8 View - Log
After selecting to view the log option the display presents a pop-up window to allow selection between a view of
all of the event history, a view of only the fire alarms that have occurred or a view of the fire alarm counter.
ALL EVENTS
FIRE EVENTS ONLY
ALARM COUNTER
.
Press the  buttons to highlight the required menu option and then press the ✔ button to select it. The
display then shows the appropriate list of events.
3.7.8.1 Event Log
The display will always show the most recent event to have occurred, e.g.
[View Fire Events]
Time/Date Node Lp:Addr
10:54:23
1
1:001.0
14/03/02 FIRE ALARM
BASEMENT
ROOM 10
Entry 0076
Zone
001
64
< Number of Highlighted Event
<
<
<
<
Time, Origin and Zone
Date, Event and Analogue Value
Zone Text Description
Device Location Description
In the above example, the latest fire occurred (Event No. 76) at 10:54 am on March 14, 2006. This fire alarm
originated at the device at address 001(Addr) on Loop 1 (Lp) on Panel No. 1 (Panel). The device was in Zone
001. The analogue value registered by the device (64) has also been recorded. The lower two lines show the
zone and device location texts descriptions for ease of identification.
Press the  buttons to scroll through the fire alarm events logged in the system. Press the  button to show
more recent events and press the  button to show earlier events.
To view the details for a specific Log Entry Number, it is possible to select the record by typing in the required
number using the number keys.
Press the ✔ button to confirm. The display will then display the required record.
Press the ‘Esc’ button to return to the main view menu.
3.7.8.2 Alarm Counter
Alarm Counter.
Section 7.13
The Panel records the number of times that the fire alarm condition has
occurred at the panel.
[View Alarm Counter]
0000000033
In the above example, the panel has entered the fire alarm condition 33 times since it was installed.
The panel increments the count by one each time it changes from the normal condition to indicate a fire alarm
condition. Whilst in the fire alarm condition, and until it is reset, further fire alarm events do not increment the
counter.
Press the ‘Esc’ button to return to the main view menu.
3.7.9 View - Network
This Option can be used to obtain diagnostic information when a network is used to connect other panels or
remote terminals. The access level of all panels on the network can be checked from this display:
22
www.advancedco.com
[NETWORK – Press 0 to Clear]
Node Status
1 LOCAL
2 Level-2
3 Level-1
4
-
More>
Additional network diagnostics are available by selecting the “More>” option.
For further information, refer to the Ad-Net network manual (Document No. 680-027).
Pressing '0' allows the stored network status information to be cleared.
3.7.10 View - Logic
This is a diagnostic aid to assist engineers when first commissioning a complex fire system.
3.8 Disabling
On selecting the Disable Menu, the display shows four possible options. For example:
[Disable]
ZONE/INPUTS
DELAY-MODE
User 1 Node
OUTPUTS
USER-ID
1
CONTROLS
GROUPS
Press the  buttons to highlight the required menu option and then press the ✔ button to select it.
3.8.1 Disable - Zones and Inputs
This option provides the means to disable a complete zone, disable all input devices except call points or
disable individual input devices.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
On selecting this option, the display shows a list of the current zones and their current disablement status. For
example:
[
0 Zones with Inputs Disabled] More>
Zone
Mode
Location
0001
Enabled
BASEMENT WEST
0002
Enabled
BASEMENT EAST
0008
Enabled
GROUND FLOOR
0009
Enabled
MAIN RECEPTION AREA
Press the  buttons to scroll through the available zones, or key in a specific zone number.
www.advancedco.com
23
To disable the entire zone, move over to the Mode column and highlight the existing mode. Press the ✔ button
and a pop-up window appears showing the three possible options: ALL INPUTS
ALL EXCEPT CALL POINTS
SELECTED INPUTS
.
Press the  buttons to scroll through and highlight the required option and then press the ✔ button to select
it.
If ALL INPUTS is chosen, the pop-up window disappears and the State of the Zone is changed to ALL
DISABLED.
If the ALL EXCEPT CALL POINTS is chosen, the pop-up window disappears and the State of the Zone is
changed to PART DISABLED (if there are actually call points in this zone) or is changed to ALL DISABLED if
there are no call points within this zone.
If SELECTED INPUTS is chosen, the pop-up window disappears and a list of the input devices within the
selected zone is presented. For example:
[ Inputs in Zone 001]
Mode
Lp Adrs State
Enabled
1 001.0 Normal
Disabled
1 002.0 Normal
Enabled
1 003.0 PRE-ALARM
Enabled
1 004.0 Normal
More>
Press the  button to more information on the inputs, including full device text, type, analogue value etc.
Press the  buttons to scroll through and highlight the required input and then press the ✔ button to disable
it. Pressing the ✔ button when the input is already disabled will enable the input.
Press the ‘Esc’ button to return.
3.8.2 Disable - Outputs
The Disable Outputs Option enables the isolation of some or all of the outputs. If disabled, the outputs will not
activate in the event of a fire alarm or other programmed event.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
[Disable]
Please Enter Your Password
Enter the password as normal. Once a valid password has been entered, a pop-up window is shown on the
display to select the type of outputs to disable. Scroll down to view / select the available options.
ALL SOUNDER STYLE OUTPUTS .
ALL OTHER OUTPUTS
SELECTED OUTPUTS
FIRE ROUTING
↓
FAULT ROUTING
PAGER
The selection list only contains Fire Routing, Fault Routing and Pager options if these are configured on the
panel.
24
www.advancedco.com
3.8.2.1 All Sounder Outputs
Press the  buttons to scroll through and highlight the ALL SOUNDER OUTPUTS Option and then press the
✔ button to disable them. The display automatically reverts to the Main Disable Menu.
The ‘Sounder Disabled’ Indicator will be illuminated.
On networked systems, this only disables the outputs connected to this panel.
3.8.2.2 All Other Outputs
Press the  buttons to scroll through and highlight the ALL OTHER OUTPUTS Option and then press the ✔
button to disable them. The display automatically reverts to the Main Disable Menu.
On networked systems, this only disables the outputs connected to this panel. This will disable all
outputs other than sounder type outputs including the fire and fault routing outputs.
3.8.2.3 Selected Outputs
Press the  buttons to scroll through and highlight the ONLY SELECTED OUTPUTS Option and then press
the ✔ button to select it. The display then shows a list of Zones containing outputs. For example:
[ 2 Zones with Outputs Disabled]
Zone
Mode
Location
0008
ENABLED GROUND FLOOR
0100
ENABLED MAIN RECEPTION
More>
Press the  buttons to scroll through and highlight the required Zone and then press the  button to view the
outputs within this zone. For example:
[ Outputs In Zone 0008]
Mode
Lp Adrs State
Enabled 1 032.0 Off
Enabled 1 056.0 Off
Enabled 2 011.1 *On
Enabled 3 026.1 Off
More>
SOUNDER
SOUNDER
RELAY
RELAY
Press the  buttons to scroll through and highlight the required Output and then press the ✔ button to
change the device mode. The device mode will change from Enabled to Disabled and vice-versa.
Press the ‘Esc’ button to return to the Zone list and to the Main Disable Menu.
3.8.2.4 Fire Routing Output
Press the  buttons to scroll through and highlight the FIRE ROUTING OUTPUT Option and then press the
✔ button to disable it. The display automatically reverts to the Main Disable Menu.
This feature disables the output connected to this panel only.
The ‘Fire Routing Disabled’ Indicator will be illuminated.
3.8.2.5 Fault Routing Output
Press the  buttons to scroll through and highlight the FAULT ROUTING OUTPUT Option and then press the
✔ button to disable it. The display automatically reverts to the Main Disable Menu.
This feature disables the output connected to this panel only.
3.8.2.6 Pager
Press the  buttons to scroll through and highlight the PAGER OUTPUT Option and then press the ✔ button
to disable it. The display automatically reverts to the Main Disable Menu.
This feature disables the output connected to this panel only.
3.8.3 Disable - Controls
Disabling Controls will cancel Level 2 access and return the panel to Level 1 operation.
If the panel has an access key switch fitted, use the key switch in preference to the menu option shown
below.
www.advancedco.com
25
[Disable]
User 1 Node
ZONE/INPUTS
DELAY-MODE
OUTPUTS
USER-ID
1
CONTROLS
GROUPS
Press the  buttons to highlight the Controls option and then press the ✔ button to select it.
The display then prompts for password entry. Enter the password as normal.
When a valid password has been entered, the control button functions and menu functions are disabled and the
level 1 menu display will be shown: [ CONTROLS DISABLED ]
ENABLE CONTROLS
VIEW
The display will automatically revert to the normal operating display after a few seconds.
3.8.4 Disable - Delay-Mode
This operation will cancel the Investigation Delay mode.
[Disable]
ZONE/INPUTS
DELAY-MODE
User 1 Node
OUTPUTS
USER- ID
1
CONTROLS
GROUPS
Press the  buttons to highlight the Delay-Mode option and then press the ✔ button to select it.
If the delays are configured in the panel, the display shows the following pop-up window when the Disable
Delay-Mode Option is selected. (Note: This delay function can only be configured using the PC Programming
Tool).
NO INVESTIGATION DELAY
PERMANENT DELAY
.
Press the ✔ button to select NO INVESTIGATION DELAYS and disable the operation of the Stage 1 / Stage 2
Investigation Function. Otherwise, press the ESC to cancel and keep the investigation delays in operation.
If the investigation delays are in operation then the “Delayed” LED Indicator is illuminated. When the
investigation delays are disabled and turned off, the “Delayed” LED Indicator is turned off.
Press ‘Esc’ to cancel and make no change to the current operational setting.
If the delays are not configured in the panel, the display briefly shows “NOT CONFIGURED” before returning to
the Disable Menu Options.
26
www.advancedco.com
3.8.5 Disable – User ID
This operation will cancel the current User ID and return to the default User 1. User 1 can perform all actions
except those defined as programmable (refer to the menu table).
[Disable]
ZONE/INPUTS
DELAY-MODE
User 5 Node
OUTPUTS
USER-ID
1
CONTROLS
Press the  buttons to highlight the User-ID option and then press the ✔ button to select it.
[Disable]
ZONE/INPUTS
DELAY-MODE
User 1 Node
OUTPUTS
USER-ID
1
CONTROLS
GROUPS
NOTE: If configured to operate with a timeout and if there has been no user activity after the programmable
period of time (default “No Timeout”), the panel will automatically cancel a User ID and return the panel to User
1 ID access. This is to ensure that access to restricted options is automatically cancelled.
3.8.6 Disable – Groups
Disablement Groups are a means of disabling / enabling custom groups of devices. The commands are
command across the network of panels and can be invoked from any panel. The installer will have configured
these groups.
If no groups exist, selection of this option will show a NOT CONFIGURED message.
Some typical examples are:
Stage Smoke Detectors
Floor 2 Sounders
ALL Sounders
The display will show, for example:
[Disable Group]
User 5 Node
Group Invoke Description
1 . Stage Smoke Detectors
2
Floor 2 Sounders
3
ALL Sounders
1
Press the  buttons to scroll through and highlight the required option and then press the ✔ button to disable
it. The display will show that the command has been invoked (activated).
[Disable Group]
User 5 Node
Group Invoke Description
1 . ok
Stage Smoke Detectors
2
Floor 2 Sounders
3
ALL Sounders
1
The GENERAL DISABLE and any specific disable indicators will be illuminated on the panel(s).
www.advancedco.com
27
3.9 Enabling
On selection of the Enable Menu Option, the display shows the available Enable Functions.
[Enable]
ZONE/INPUTS
DELAY-MODE
User 1 Node
OUTPUTS
CHANGE-TIME
1
GROUPS
REMOTE
Press the  buttons to highlight the required menu option and then press the ✔ button to select it.
3.9.1 Enable - Zones and Inputs
Selecting this option will show a list of zones containing disabled input devices. Either the complete zone, or
individual devices within the zone can then be enabled (Display format is virtually identical to the Disable
displays).
3.9.2 Enable - Outputs
When this option is selected, pop-up menu appears asking if you want to enable ALL SOUNDER OUTPUTS,
ALL OTHER OUTPUTS, ONLY SELECTED OUTPUTS, the FIRE ROUTING OUTPUT, the FAULT ROUTING
OUTPUT or the PAGER OUTPUT. If ONLY SELECTED OUTPUTS is selected, the display will list only zones
containing outputs that have been disabled. The individual outputs within the zone can then be enabled.
(The display format is virtually identical to the Disable displays).
3.9.3 Enable - Delay-Mode
This option allows the enablement of Investigation Delays and other related functions.
The Investigation Delays can be invoked as manual operation delays (Permanent and Once Only), Automatic
delays (configured to run with a time clock) and Extend delays. A further option is provided to Inhibit delays for
holiday periods. The options that appear in the menu depend on the installation configuration programmed by
the installer.
On selection of the ENABLE DELAY option, the display will show a pop-up menu list. For example:
NO INVESTIGATION DELAY
PERMANENT DELAY
AUTOMATIC
↓
↓ Indicates if there are more options configured.
Press the  buttons to scroll through and highlight the required option and then press the ✔ button to enable
it.
The display will confirm the selection and indicate WORKING whilst it performs the operation. On completion, it
reverts to the pop-up menu.
For Extended and Holiday/Inhibit, further menus are presented.
3.9.3.1 Extend Delays
To extend any current automatic delays (for example overtime working).
Extend Delays for : ..0 hour(s)
Use the number keys to enter the required number of hours beyond the current configured end time.
3.9.3.2 Holiday / Inhibit
The panel can be enabled to prevent any pre-programmed daily automatic delays from activating during holiday
periods. On selection, the display shows:
28
www.advancedco.com
[Inhibit Delay End Date]
TIME = 15:49
DATE = 02/07/08
WED 02 JUL 2008
Press the  buttons to select the time / date fields. Enter the required time and date using the number
buttons.
Any pre-configured automatic delays or manual delays will be immediately suspended and the panel will
operate without any investigation delays.
On reaching the time / date programmed, the panel will automatically revert to use any investigation delays as
programmed and configured.
3.9.4 Enable - Groups
This option allows the re-enabling of User-defined Disablement Groups. The display is identical to the disable
option.
3.9.5 Enable - Change-Time
Allows the clock time to be changed.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
For example:
[SET TIME/DATE]
TIME = 15:28
DATE = 15/04/06
SAT 15 APR 2006
To change the settings, use the  buttons to highlight the required option. Directly enter the new time or date
using the number buttons. As soon as a number button is pressed, the display will clear the current setting and
show the new value as it is entered. For example:
[SET TIME/DATE]
TIME = 1-:-DATE = 15/04/06
SAT 15 APR 2006
If this panel is connected to a network, ALL panels on the network will assume this new value.
www.advancedco.com
29
3.9.6 Enable - Remote
Information on the detectors connected to the panel and on the condition of all zones can be obtained with an
ipGateway interface.
In addition, the user can be assisted with operations such as disabling / enabling a detector from external
commands over a TCP/IP system. In order to ensure this only happens with the consent of the user the
REMOTE option must be enabled by the user.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
After selecting the option, a selection list is presented on the display as follows:
[Remote Access Options]
DISABLE REMOTE ACCESS
ALLOW REMOTE ACCESS
.
Use the  buttons to highlight the required option and then press the ✔ button to confirm.
30
www.advancedco.com
3.10 Testing
[Test Menu]
ZONES
DISPLAY
OUTPUTS
User 1 Node
BUZZER
1
PRINTER
Press the  buttons to highlight the required menu option and then press the ✔ button to select it.
3.10.1 Test - Zones
The Test Zones function provides the means to implement a one-person walk test in order to test specific call
points or detectors in one or more zones.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
When the Test Zones option is selected, a pop-up window is shown on the display to select whether the
sounders will activate (for about 10-seconds) when an input device is activated. For example:
WITHOUT SOUNDERS
WITH SOUNDERS
.
Press the  buttons to scroll through and highlight the required option and then press the ✔ button to select
it.
Note that the panel will have been programmed during commissioning to define which of the sounders are
activated during a test.
The display then shows a list of the available Zones and their current test status. For example:
[
0 Zones in Test ]
Zone
Test State
Location
>0001
BASEMENT WEST
0002
BASEMENT EAST
0100
MAIN RECEPTION
Press the  buttons to scroll through and highlight the required zone and then press the ✔ button to change
the Test State. For example:
[
1 Zone in Test ]
Zone
Test State
Location
0001
IN TEST
BASEMENT WEST
0002
BASEMENT EAST
0008
GROUND FLOOR
0009
MAIN RECEPTION AREA
When one or more Zones are placed in a Test State, the Test Indicator will be illuminated. When an input device
is activated (i.e. break glass test on a call point or introducing test smoke into a smoke detector), the bells will
ring (if selected) and the display will indicate that a zone is registering a test condition by showing an
exclamation mark (!) on the display.
[
2 Zones in Test ]
Zone
Test State
Location
0001
IN TEST
! BASEMENT WEST
0002
BASEMENT EAST
0008
GROUND FLOOR
0009
IN TEST
MAIN RECEPTION AREA
When the activating test key is removed from the call point or the smoke clears from the detector chamber, the
panel will automatically reset and clear the test condition.
www.advancedco.com
31
As an alternative to scrolling, a specific zone number can be entered by using the  button to move to the zone
number column, and then typing in the required number, followed by the ✔ button.
If several consecutive zones are to be tested, an alternative to selecting them all individually is to specify a
range of zones as follows: Move to the zone number column and highlighting the first zone to test, then
Press the ✔ button – the display will then ask for the last zone to be tested.
Individual zones can then be toggled in or out of test by pressing the ✔ button.
To leave the Zone Test menu, press the ‘Esc’ button. If there are still any zones in a test condition a pop-up
window with the following options: FINISHED TEST
KEEP ZONES IN TEST
.
Selecting the FINISHED TEST option will cancel all zone tests. The Test LED will then extinguish.
Alternatively, it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the
KEEP ZONES IN TEST option. This will enable the inspection or use of other menu functions and return the
display to the normal operating mode. The Test LED will stay illuminated if this option is selected.
3.10.2 Test - Display
The Test Display option checks the operation of all the Indicators and the Graphic Display. All of the Indicators
are turned on and the entire display is shown in reverse.
During this test, it is possible to test the operation of the ,,,,✔ and 0-9 buttons. When a button is
pressed, it is indicated on the display. For example:
LCD & KEY TEST

Press the ‘Esc’ button to return to the Test Menu. If no button is pressed for 1-minute, the display will
automatically revert to the normal operating display.
3.10.3 Test - Buzzer
[Test Menu]
ZONES
DISPLAY
User 1 Node
BUZZER
1
PRINTER
When the Test Buzzer option is selected, the internal buzzer will sound for about five seconds.
32
www.advancedco.com
3.10.4 Test - Printer
To invoke the printing of a test print sequence, highlight the Test Print Option and press the ✔ button to confirm.
The panel transmits 16 lines of test characters to the printer. The information sent is echoed on the display.
When the test print is completed, the display automatically reverts to the Test Options Menu.
Press the ‘Esc’ button at any time to cancel the test print.
3.10.5 Test - Outputs
Output devices can be individually tested for operation.
To test an individual output device (sounder or relay), highlight the Test Outputs Option and press the ✔ button
to confirm. The display will present a list of the zones that contain output devices.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent operation.
[Outputs]
Zone
Location
0001
BASEMENT WEST
0002
BASEMENT EAST
0037
EAST PLANT ROOM
0100
MAIN RECEPTION
Press the  buttons to scroll and highlight the required zone (or key in the required zone number) and then
press the  button to show the output devices in that zone. For example:
[Loop
Address
005.1
006.0
006.1
007.0
1 Devices]
State
Normal
Normal
Normal
Normal
<More>
Type
Value
SOUNDER
MULTI.SENSOR 16
RELAY
CALL POINT
16
Press the  buttons to scroll and highlight the required zone (or key in the required zone number) and then
press the ✔ button to test the output. The display will prompt to confirm the “Test this device”. Press the ✔
button again to accept. The output device will turn on and this will be confirmed on the display by the status
changing from OFF to ON.
The general “TEST” LED will illuminate whenever an output is in test. The test is cancelled by either pressing
the ESC button or by scrolling to the next / previous device in the list. If the display is left for one minute without
pressing any buttons, the output will revert to its quiescent state.
On networked systems, the Test – Outputs option also supports testing of outputs connected to other panels.
www.advancedco.com
33
3.11 Printing
[Print Menu]
INPUTS
LOG
User 1 Node
1
OUTPUTS
FAULTS
DISABLED
FEED-PAPER
SETUP PRINTER
3.11.1 Printer Communications Settings
The information is sent to the printer in a serial form. If an external printer is used, ensure that the
communications settings in the printer are set as follows:
Interface Type: RS232
Baud Rate:
9600
Parity: None
Data Bits:
8
Stop Bits:
1
3.11.2 Set-up Printer
To enable or set-up the operating characteristics of the printer, highlight the Set-up Printer Option and press the
✔ button to confirm.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
Enter the password as normal. The display then shows a pop-up window giving programming options as
follows:
[FIRES] [ALARMS]
✔
✔
[FAULTS] [TESTS]
-
-
( Printer: Internal External/Wide )
✔
-
The upper line of options determines whether the panel shall automatically print specific events as they occur.
The lower line of options determines whether a printer is connected and its type.
Use the ,,, and ✔ buttons to highlight the required option and change its setting. Pressing the ✔ button
turns the option on (✔ is shown) or off (- is shown) accordingly.
In the above option, an external printer is selected, with automatic printing of fires and alarms.
Setting the wide option will change the printing from the default 40 characters per line to 80 characters per line.
Note: Only faults registered on this panel are printed.
3.11.3 Print Inputs
To print information on any input, highlight the Inputs option and press the ✔ button to confirm. The display will
show the following:
[Inputs]
First Zone
Last Zone
:
:
98
98
(Press → to Start Print)
The display will prompt the zones in use on this panel. For networked systems, it is possible to select any zones
used in the system. Use the arrow () buttons to highlight the first and last zone number and use the number
keys to change the zone number required.
34
www.advancedco.com
Press the  key to start printing.
The display will show the following whilst information is sent to the printer and printed.
WORKING ...
(Press Esc to Stop)
After all information has been printed, the display will automatically revert to the Print Menu. Press the “Esc” key
to stop printing if required.
The printout will show all input points for the zones selected. Information printed includes Device Text, Zone
Number, Loop and address, current status and analogue value.
3.11.4 Print Outputs
To print information on any output, highlight the Outputs option and press the ✔ button to confirm. The display
will show the following:
[Outputs]
First Zone
Last Zone
:
:
98
98
(Press → to Start Print)
The display will prompt the zones in use on this panel. For networked systems, it is possible to select any zones
used in the system. Use the arrow () buttons to highlight the first and last zone number and use the number
keys to change the zone number required.
Press the  key to start printing.
The printout will show all output points for the zones selected. Information printed includes Device Text, Zone
Number, Loop and address, current status and analogue value.
3.11.5 Print Faults
To print information on any faults, highlight the Faults option and press the ✔ button to confirm. The display will
show the following:
[
2 Zones in Fault]
First Zone
Last Zone
:
:
98
99
(Press → to Start Print)
The panel analyses the network and the display will prompt the zones in a fault condition.
Use the arrow () buttons to highlight the first and last zone number and use the number keys to change the
zone number as required.
Press the  key to start printing.
The printout will show the location and state of all input and output points in a fault condition for the zones
selected.
Note: If there aren’t any fault conditions present then selecting this menu option will no effect.
3.11.6 Print Disabled
To print information on any disablement, highlight the Disabled option and press the ✔ button to confirm. The
display will show the following depending on the disabled conditions present:
If there are zones with inputs disabled:
www.advancedco.com
35
[
2 Zone(s) with Inputs Disabled]
First Zone
Last Zone
:
:
98
99
(Press → to Start Print)
If there are zones with outputs disabled:
[
1 Zone(s) with Outputs Disabled]
First Zone
Last Zone
:
:
98
98
(Press → to Start Print)
The panel analyses the network and the display will prompt the zones in a disabled condition.
Use the arrow () buttons to highlight the first and last zone number and use the number keys to change the
zone number as required.
Press the  key to start printing.
The printout will show the location and state of all input and output points in a disabled condition for the zones
selected.
The display always present the zones with inputs disabled first (if any exist). After printing the inputs the display
will present the information on disabled outputs (if any exist).
Note: If there aren’t any disabled conditions present then selecting this menu option will no effect.
3.11.7 Print - Log
To print information from the History Log, highlight the Print Log Option and press the ✔ button to confirm. A
pop-up window will be shown asking if all events, or just fires should be printed.
Highlight the required option using the  buttons and press the ✔ button to confirm.
When the Log Print is completed, the display automatically reverts to the Print Options Menu.
Press the ‘Esc’ button at any time to cancel the log print.
Note: The pop-up window also allows selection of the Fire Alarm Counter. On selection, this is shown on the
display but is not printed.
3.11.8 Print - Feed Paper
Highlight the Feed Paper Option and press the ✔ button to confirm. The display does not change but a
command is sent to the printer to advance the paper.
36
www.advancedco.com
In the event of a fire alarm, call: -
Quick Reference Guide
TEL:
For Service & Maintenance,
contact: -
TEL:
Controls & Indications
Graphic Liquid
Crystal Display
Navigation
Buttons
Navigation Buttons
 
Press to scroll through Menu Options.
Press to display more information.
 
Press to scroll through menu Options.
Press to scroll through lists of zones or
devices.

FI R E
SOU N D ER
SIL EN C ED
FA U LT
SOU N D ER
FA U LT
DI SA B LE
SOU N D ER
DI SA B LE D
Press to confirm entry of numeric or letter
information entry.
Press to confirm selection of a menu
option.
RESET
!
AB C
DEF
GH I
JKL
MNO
PQRS
TUV
WXYZ
Press to change some of the configuration
options.
MU TE
TEST
SYS T EM FA U LT
SILENCE/
RESOU ND
POW ER
DE LAYED
EVAC UATE
Number Buttons
0
LED Status
Indicators
Control
Buttons
Number and
Letter Buttons
to
9wxyz
Esc
Used to enter numbers or letters.
Press to return to a previous menu.
Press to exit the menu functions and return
to the normal display.
For easy reference, cut out and frame / mount on the wall next to the panel.
The panels may be fitted with separate zone fire indicators comprising of 20, 50, 100 or 200 red
indicators – these show the zones in a fire alarm condition.
Menu
In addition, the panels may be fitted with separate indications showing the loaction of fire alarms in
a pictorial display (mimic diagram).
Graphic Display
Press to show or return to Level 1 or Level
2 Menu Functions.
Main User functions are VIEW, TEST,
DISABLE & ENABLE.
Control Buttons
Reset: Press to reset the panel from a
latched condition.
The graphical display provides detailed information of the source of fires, faults and warnings. It
also shows menus for use when inspecting or programming the operation of the panel.
Under normal conditions the panel display shows the time, date and status: -
Mute: Press to mute the internal buzzer.
LEVEL 2
16:05
04 MAR 2006
NORMAL PANEL OPERATION
(Press Menu to View)
Silence / Re-sound: Press to silence the
bells. Press again to re-sound the bells.
Evacuate: Press to initiate a manual
evacuation and sound the alarms.
Level 2 Access is required for Reset, Silence / Re-sound &
Evacuate buttons and for programming Menu functions.
Level 2 operation can be enabled using a key-switch (if
fitted) or by entry of a pass-code.
LED Status Indicators
The following is a typical menu display.
[Level 2 Menu]
VIEW
TEST
DISABLE
PRINT
STATUS
ENABLE
COMMISSION
RED
Separate LED Indicators show the
presence of a fire alarm condition and (if
configured) that the fire brigade has been
called.
YELLOW
Indicate other system operating conditions
including Fault, Test and Disablement
conditions.
GREEN
Indicates the presence of power to the
system – if flashing, indicates that the panel
is running on battery standby power.

Refer to the User Manual (Document Number 680-015) for full operating instructions.
www.advancedco.com
37
This page is intentionally left blank.
38
www.advancedco.com
USER NOTES