Download 50 - daikin tech.co. uk

Transcript
• Outdoor Units • R-410A • RZQS71-100B7V3B
1
AV i7 Bny 0U k 0 S 1 r - o A1t o 07 i d 1S l t4Q pu-Z S•RO
•
Features
Outdoor units for pair, twin, triple, double twin application
The Sky Air Inverter is developed for use in shops, restaurants and
small offices. This innovative Daikin unit provides a more
comfortable environment and offers great savings in energy
consumption to shop and office owners.
During start up, the room can be cooled down or heated very quickly.
Once the temperature in the room has reached its set point, the low
power operation starts to save energy.
•
Daikin outdoor units are neat and sturdy and can be mounted easily
on a roof or terrace or simply placed against an outside wall.
•
The use of inverter type outdoor units results in an air conditioning
system with a high energy efficiency and very low sound level
•
Outdoor units are fitted with either a swing or scroll compressor,
renowned for low noise and high energy efficiency
•
An inverter driven compressor allows the capacity to be adjusted
precisely to match variations in room and outside temperatures.
•
A special acryl precoated fin for anti-corrosion treatment on the heat
exchanger ensures greater resistance against severe weather
conditions
50
1
992
•
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS71-100B7V3B
2
Specifications
2-1 NOMINAL CAPACITY AND
NOMINAL INPUT
RZQS71B7V3B
RZQS100B7V3B
For
combination
indoor units +
outdoor units
Indoor Units
FCQ71C7VEB
FCQ100C7VEB
Cooling
capacity
Standard
kW
7.10
10.00
Heating
capacity
Standard
kW
8.00
11.20
Power Input
For
combination
indoor units +
outdoor units
Cooling
Standard
kW
2.46
3.83
Heating
Standard
kW
2.61
3.47
EER
Nominal
2.89
2.61
COP
Nominal
3.07
3.23
Energy Label
Cooling
C
D
Heating
D
C
1230
1915
FBQ71B8V3B
FBQ100B8V3B
7.10
10.00
8.00
11.20
Annual energy consumption kWh
Indoor Units
Cooling
capacity
Standard
kW
Heating
capacity
Standard
kW
Power Input
For
combination
indoor units +
outdoor units
Cooling
Standard
kW
2.52
3.83
Heating
Standard
kW
2.40
3.47
EER
Nominal
2.82
2.61
COP
Nominal
3.33
3.23
Energy Label
Cooling
C
Heating
Annual energy consumption kWh
Indoor Units
Cooling
capacity
Standard
kW
Heating
capacity
Standard
kW
Power Input
For
combination
indoor units +
outdoor units
2
1260
1915
FHQ71BUV1B
FHQ100BUV1B
7.10
10.00
8.00
11.20
Cooling
Standard
kW
2.53
4.15
Standard
kW
2.84
3.99
EER
Nominal
2.81
2.41
COP
Nominal
2.82
2.81
Energy Label
Cooling
C
Heating
Cooling
capacity
Standard
kW
Heating
capacity
Standard
kW
E
D
Annual energy consumption kWh
For
combination
indoor units +
outdoor units
50
Heating
Indoor Units
Power Input
D
C
1265
2075
FAQ71BUV1B
FAQ100BUV1B
7.10
10.00
8.00
11.20
Cooling
Standard
kW
2.53
4.08
Heating
Standard
kW
2.61
3.73
EER
Nominal
2.81
2.45
COP
Nominal
3.01
3.00
Energy Label
Cooling
C
Heating
E
D
Annual energy consumption kWh
Indoor Units
1265
2040
FCQH71C7VEB
FCQH100C7VEB
7.10
10.00
8.00
11.20
Cooling
capacity
Standard
kW
Heating
capacity
Standard
kW
Cooling
Standard
kW
2.36
3.56
Heating
Standard
kW
2.34
3.28
Power Input
• Split Sky Air • Outdoor Units
993
• Outdoor Units • R-410A • RZQS71-100B7V3B
2
Specifications
2-1 NOMINAL CAPACITY AND
NOMINAL INPUT
For
combination
indoor units +
outdoor units
RZQS71B7V3B
RZQS100B7V3B
EER
Nominal
3.01
2.81
COP
Nominal
3.42
3.41
Energy Label
Cooling
B
Heating
Annual energy consumption kWh
2-2 TECHNICAL SPECIFICATIONS
Casing
Colour
Dimensions
Unit
1180
Painted galvanised steel
mm
770
770
Width
mm
900
900
Depth
mm
320
320
Height
mm
900
900
Width
mm
980
980
Depth
mm
420
420
Unit
kg
68
68
Packed Unit
kg
72
72
mm
857
857
2
2
mm
1.40
1.40
3
3
0.641
0.641
Dimensions
Length
Nr of Rows
Fin Pitch
Nr of Passes
Face
Area
50
m²
Nr of Stages
34
Tube type
2
Fin
Type
WF fin
Anti-corrosion treatment (PE)
Type
Propeller
Discharge direction
Horizontal
Quantity
Air Flow Rate
(nominal at
230V)
Cooling
m³/min
Heating
m³/min
Motor
Quantity
1
1
54.5
61.3
48.1
61.7
1
Model
Motor
Speed
(nominal)
Steps
Fan
Motor
Compressor
Quantity
Motor
Cooling
Heating
Sound Level
(nominal)
Cooling
Heating
Sound Level
(Night quiet)
994
Sound Pressure
1
KFD-325-70-8A
8
8
rpm
818
920
Heating
rpm
715
920
Output
W
70
70
Cooling
1
Model
1
2YC63BXD
Type
Operation
Range
34
Hi-XSS(8)
Treatment
Fan
RZQS100B7V3B
Ivory White
Height
Packing
Heat
Exchanger
1780
RZQS71B7V3B
Material
Weight
C
B
Hermetically sealed swing compressor
Motor
Output
W
Min
°CDB
-5.0
-5.0
Max
°CDB
46.0
46.0
Min
°CWB
-15.0
-15.0
Max
°CWB
15.5
15.5
Sound
Power
dBA
65.0
67.0
Sound
Pressure
dBA
49.0
51.0
Sound
Pressure
dBA
51.0
55.0
43.0
45.0
1800
dBA
• Split Sky Air • Outdoor Units
1800
• Outdoor Units • R-410A • RZQS71-100B7V3B
2
Specifications
2-2 TECHNICAL SPECIFICATIONS
Refrigerant
RZQS71B7V3B
Type
Charge
kg
2.80
2.80
Control
Expansion valve (electronic type)
Nr of Circuits
Refrigerant Oil
1
1
Type
Daphne FVC50K
Charged Volume
Piping
connections
Liquid (OD)
l
0.8
Quantity
0.8
1
1
Type
Flare connection
Diameter
(OD)
Gas
mm
9.52
Quantity
9.52
1
1
Type
Flare connection
Diameter
(OD)
Drain
mm
15.9
Quantity
15.9
3
3
Type
Piping Length
Hole
Diameter
(OD)
mm
Minimum
26
26
m
5
5
Maximum m
30
50
Equivalent
m
40
70
Chargeless m
30
30
Additional Refrigerant
Charge
Installation
height
difference
RZQS100B7V3B
R-410A
kg/m
see installation manual 4PW32097-1
Maximum m
Max. internunit level
difference
m
15
30
0.5
0.5
Heat Insulation
50
2
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Standard
Accessories
Item
Tie-wraps
Quantity
2
Item
2
Installation manual
Quantity
1
Notes
1
Nominal cooling capacities are based on : indoor temperature : 270CDB, 190CWB, outdoor temperature : 350CDB
Nominal heating capacities are based on : indoor temperature : 200CDB, outdoor temperature : 70CDB, 60CWB
2-3 ELECTRICAL SPECIFICATIONS
Power Supply
RZQS71B7V3B
Name
V3
Phase
Frequency
Voltage
Voltage range
RZQS100B7V3B
Minimum
1
1
Hz
50
50
V
230
V
Maximum V
Current
Recomended fuses
Wiring
connections
For Power
Supply
A
230
-10%
+10%
20
Remark
For connection Remark
with indoor
Power Supply Intake
20
see installation manual 4PW32097-1
see installation manual 4PW32097-1
Outdoor unit only
Notes
See separate drawings for electrical data
• Split Sky Air • Outdoor Units
995
• Outdoor Units • R-410A • RZQS71-100B7V3B
3
Electrical data
RZQS71-100BV3
Unit combination
Indoor unit
Outdoor unit
Hz-volts
Power supply
Comp.
Voltage range MCA TOCA MFA MSC RLA
50
OFM
kW
IFM
FLA
kW
FLA
3D055645A
3
NOTES
SYMBOLS
MCA
TOCA
MFA
MSC
RLA
OFM
IFM
FLA
kW
996
: Min. Circuit Amps (A)
: Total Over Current Amps (A)
: Max. Fuse Amps (See note 7) (A)
: MSC means the max. current during the
starting of compressor. (A)
: Rated Load Amps (A)
: Outdoor Fan Motor (A)
: Indoor Fan Motor
: Full Load Amps
: Fan Motor Rated Output (kW)
1
2
3
4
5
6
7
8
RLA is based on the following conditions:
Power supply: 50Hz 230V
Heating
Cooling
Indoor temperature 20.0°CDB
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 7.0°CDB/6.0°CWB
Outdoor temperature 35°CDB
TOCA means the total value of each OC set
Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits
Maximum allowable voltage unbalance between phases is 2%
MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
Select wire size based on the larger value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the document title of your choice.
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS71-100B7V3B
4
Options
Available option for RZQS71-100B7V3
Name of option
Kit name
RZQS71B7V3B
Central drain plug
Refrigerant branch piping
RZQS100B7V3B
KKPJ5F180
Twin
KHRQ22M20TA
Triple
-
KHRQ127H
Double twin
-
-
Demand adapter kit
KRP58M51
3TW26739-1E
50
4
• Split Sky Air • Outdoor Units
997
• Outdoor Units • R-410A • RZQS71-100B7V3B
5
Capacity tables
5-1
Combination table
Possible combinations and standard capacity for twin, triple and double twin application
Possible indoor combination
Simultaneous operation
Outdoor models
Twin
Triple
Out
Out
In
In
RZQS71B7V3
35-35
(KHRQ22M20TA7)
RZQS100B7V3
50-50
(KHRQ22M20TA7)
In
In
Double twin
Out
In
In
In
In
In
35-35-35
(KHRQ127H7)
3TW29069-1
NOTES
50
1
Possible indoor units: FCQ35-125B, FFQ35-60BV, FHQ35-125B, FBQ35-125B, FAQ71-100B, FDQ125B.
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the
main unit.
In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
5
998
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS71-100B7V3B
5
Capacity tables
5-2
Cooling capacity tables
RZQS71BV3 (Pair + Multi)
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity (kW)
Cooling capacity
230V [50Hz]
Indoor
EWB
Outdoor temp. (°CDB)
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
25
SHC
(kW)
4.39
4.82
4.80
4.79
4.73
4.66
TC
(kW)
6.47
7.43
7.58
7.66
8.05
8.37
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
6.46
7.20
7.35
7.43
7.81
8.12
30
SHC
(kW)
4.43
4.72
4.71
4.70
4.64
4.58
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
TC
(kW)
6.66
6.95
7.10
7.17
7.55
7.85
35
SHC
(kW)
4.62
4.61
4.60
4.59
4.54
4.48
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
6.39
6.67
6.82
6.89
7.26
7.55
40
SHC
(kW)
4.49
4.47
4.46
4.46
4.41
4.35
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D055646A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB
(heating)
Corresponding refrigerant piping length
:5m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
Model
AFR
(BF)
FCQH71C
20
(0.17)
FCQ71C
15.5
(0.19)
FCQ71B
18
(0.10)
FBQ71B
19
(0.11)
FHQ71B
17
(0.10)
FAQ71B
19
(0.08)
FBQ71B
2.52
2.40
FHQ71B
2.53
2.85
FAQ71B
2.53
2.61
10. Rated power input of each model is tabulated below.
(Pair)
Model
Cooling
Heating
FCQH71C
2.36
2.34
FCQ71C
2.46
2.61
FCQ71B
2.46
2.61
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
50
5
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
(Multi)
Model
AFR
(BF)
FCQ35Cx2
10.5x2
(0.28x2)
FCQ35Bx2
14x2
(0.16x2)
FFQ35Bx2
10x2
(0.25x2)
FBQ35Bx2
11.5x2
(0.15x2)
FHQ35Bx2
13x2
(0.2x2)
FCQ35Cx2
2.59
2.75
FCQ35Bx2
2.59
2.75
FFQ35Bx2
2.61
2.70
FBQ35Bx2
2.57
2.47
FHQ35Bx2
2.66
2.85
(Multi)
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
999
• Outdoor Units • R-410A • RZQS71-100B7V3B
5
Capacity tables
5-2
Cooling capacity tables
RZQS100BV3 (Pair + Twin/triple)
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity (kW)
Cooling capacity
400V [50Hz]
Indoor
50
5
Outdoor temp. (°CDB)
EWB
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
25
SHC
(kW)
6.19
6.78
6.76
6.75
6.66
6.57
TC
(kW)
9.12
10.5
10.7
10.8
11.3
11.8
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
9.10
10.1
10.4
10.5
11.0
11.4
30
SHC
(kW)
6.25
6.65
6.63
6.62
6.54
6.45
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
35
SHC
(kW)
6.51
6.49
6.48
6.47
6.39
6.30
TC
(kW)
9.38
9.79
10.0
10.1
10.6
11.1
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
9.00
9.40
9.60
9.71
10.2
10.6
40
SHC
(kW)
6.32
6.30
6.29
6.28
6.21
6.13
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D055647A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
:5m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
(Twin)
Model
AFR
(BF)
FCQH100C
32.5
(0.17)
Model
AFR
(BF)
FCQ35Cx3
10.5x3
(0.28x3)
FCQ100C
23.5
(0.16)
FCQ100B
28
(0.16)
FBQ100B
27
(0.20)
FHQ100B
24
(0.14)
FAQ100B
23
(0.10)
Model
AFR
(BF)
FCQ50Cx2
12.5x2
(0.21x2)
FCQ50Bx2
15x2
(0.16x2)
FFQ50Bx2
12x2
(0.16x2)
FBQ50Bx2
14x2
(0.15x2)
FHQ50Bx2
13x2
(0.1x2)
FCQ50Cx2
3.83
3.65
FCQ50Bx2
3.83
3.65
FFQ50Bx2
3.83
3.54
FBQ50Bx2
3.83
3.58
FHQ50Bx2
4.15
3.99
(Triple)
FCQ35Bx3
14x3
(0.16x3)
FFQ35x2
10x3
(0.25x3)
FBQ35x3
11.5x3
(0.15x3)
FHQ35x3
13x3
(0.2x3)
10. Rated power input of each model is tabulated below.
(Pair)
Model
Cooling
Heating
FCQH100C
3.56
3.28
FCQ100C
3.83
3.47
(Twin)
FCQ100B
3.83
3.47
FBQ100B
3.83
3.47
FHQ100B
4.15
3.99
FAQ100B
4.08
3.73
(Triple)
Model
Cooling
Heating
1000
FCQ35Cx3
3.83
3.65
FCQ35Bx3
3.83
3.65
FFQ35Bx3
3.83
3.54
FBQ35Bx3
3.83
3.58
FHQ35Bx3
4.15
3.99
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
• Outdoor Units • R-410A • RZQS71-100B7V3B
5
Capacity tables
5-2
Cooling capacity tables
RZQS71-100BV3
Capacity in function of field piping length for non-inverter
Capacity (%)
50
5
Field piping length (m)
3TW29069-3
Cooling
Heating
• Split Sky Air • Outdoor Units
1001
• Outdoor Units • R-410A • RZQS71-100B7V3B
5
Capacity tables
5-3
Heating capacity tables
RZQS71BV3 (Pair + Multi)
Coefficient of power input. (-)
Heating
Rated point
Capacity range
Heating capacity (kW)
Heating capacity
230V [50Hz]
Indoor
EDB
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
−10
CPI
(-)
1.12
1.16
1.21
1.23
1.25
1.30
TC
(kW)
6.22
6.21
6.20
6.20
6.19
6.19
−5
CPI
(-)
1.17
1.22
1.27
1.29
1.32
1.36
NOTES
10
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
8.64
8.62
8.61
8.61
8.60
8.59
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of
power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is
7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
:5m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined
as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
Model
AFR
(BF)
FCQH71C
20
(0.17)
FCQ71C
15.5
(0.19)
FCQ71B
18
(0.10)
FBQ71B
19
(0.11)
FHQ71B
17
(0.10)
FAQ71B
19
(0.08)
10. Rated power input of each model is tabulated below.
(Pair)
Model
Cooling
Heating
1002
6
TC
(kW)
8.02
8.01
8.00
8.00
7.99
7.98
3D055646A
50
5
TC
(kW)
5.68
5.67
5.67
5.66
5.66
5.65
Outdoor temp. (°CWB)
0
TC
CPI
(kW)
(-)
6.75
1.23
6.74
1.28
6.74
1.33
6.73
1.35
6.73
1.38
6.72
1.43
FCQH71C
2.36
2.34
FCQ71C
2.46
2.61
FCQ71B
2.46
2.61
FBQ71B
2.52
2.40
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
CPI:
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
(Multi)
Model
AFR
(BF)
FCQ35Cx2
10.5x2
(0.28x2)
FCQ35Bx2
14x2
(0.16x2)
FFQ35Bx2
10x2
(0.25x2)
FBQ35Bx2
11.5x2
(0.15x2)
FHQ35Bx2
13x2
(0.2x2)
FCQ35Cx2
2.59
2.75
FCQ35Bx2
2.59
2.75
FFQ35Bx2
2.61
2.70
FBQ35Bx2
2.57
2.47
FHQ35Bx2
2.66
2.85
(Multi)
FHQ71B
2.53
2.85
FAQ71B
2.53
2.61
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
• Outdoor Units • R-410A • RZQS71-100B7V3B
5
Capacity tables
5-3
Heating capacity tables
RZQS100BV3 (Pair + Twin/triple)
Coefficient of power input. (-)
Heating
Capacity range
Rated point
Heating capacity (kW)
Heating capacity
400V [50Hz]
Indoor
EDB
−10
TC
(kW)
7.91
7.90
7.89
7.89
7.88
7.87
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
CPI
(-)
1.07
1.11
1.15
1.17
1.20
1.24
TC
(kW)
8.66
8.65
8.64
8.63
8.63
8.62
−5
Outdoor temp. (°CWB)
0
TC
CPI
(kW)
(-)
9.41
1.17
9.39
1.22
9.38
1.27
9.38
1.29
9.37
1.32
9.36
1.36
CPI
(-)
1.12
1.16
1.21
1.23
1.26
1.30
6
TC
(kW)
11.2
11.2
11.2
11.2
11.2
11.2
10
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
12.1
12.1
12.1
12.1
12.0
12.0
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
3D055647A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
3
SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
:5m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
(Pair)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
50
5
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
(Twin)
Model
AFR
(BF)
FCQH100C
32.5
(0.17)
Model
AFR
(BF)
FCQ35Cx3
10.5x3
(0.28x3)
FCQ100C
23.5
(0.16)
FCQ100B
28
(0.16)
FBQ100B
27
(0.20)
FHQ100B
24
(0.14)
FAQ100B
23
(0.10)
Model
AFR
(BF)
FCQ50Cx2
12.5x2
(0.21x2)
FCQ50Bx2
15x2
(0.16x2)
FFQ50Bx2
12x2
(0.16x2)
FBQ50Bx2
14x2
(0.15x2)
FHQ50Bx2
13x2
(0.1x2)
FCQ50Cx2
3.83
3.65
FCQ50Bx2
3.83
3.65
FFQ50Bx2
3.83
3.54
FBQ50Bx2
3.83
3.58
FHQ50Bx2
4.15
3.99
(Triple)
FCQ35Bx3
14x3
(0.16x3)
FFQ35x2
10x3
(0.25x3)
FBQ35x3
11.5x3
(0.15x3)
FHQ35x3
13x3
(0.2x3)
10. Rated power input of each model is tabulated below.
(Pair)
Model
Cooling
Heating
FCQH100C
3.56
3.28
FCQ100C
3.83
3.47
(Twin)
FCQ100B
3.83
3.47
FBQ100B
3.83
3.47
FHQ100B
4.15
3.99
FAQ100B
4.08
3.73
Model
Cooling
Heating
(Triple)
Model
Cooling
Heating
FCQ35Cx3
3.83
3.65
FCQ35Bx3
3.83
3.65
FFQ35Bx3
3.83
3.54
FBQ35Bx3
3.83
3.58
FHQ35Bx3
4.15
3.99
• Split Sky Air • Outdoor Units
1003
• Outdoor Units • R-410A • RZQS71-100B7V3B
6
Dimensional drawing & centre of gravity
6-1
Dimensional drawing
unit (mm)
RZQS71-100BV3
Hole for anchor bolt
4-M12
1
2
3
4
5
6
7
8
50
3TW25144-1A
6
1004
Gas pipe connection J15.9 flare
Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake (knock out hole J34)
Control wiring intake (Knock out hole J27)
Drain outlet
• Split Sky Air • Outdoor Units
• Outdoor Units • R-410A • RZQS71-100B7V3B
6
Dimensional drawing & centre of gravity
6-2
Centre of gravity
RZQS71-100BV3
4TW26069-3
50
6
• Split Sky Air • Outdoor Units
1005
• Outdoor Units • R-410A • RZQS71-100B7V3B
7
Piping diagram
RZQS71-100BV3
Electronic expansion
valve
One way valve
One way valve
Heat exchanger
Filter
Service port
5/16″
One way valve
One way valve
Capillary tube
Solenoid valve
Receiver
Strainer
Heat exchanger
4-way valve
Muffler
Low pressure
sensor
Muffler
One way valve
Field piping J9.5 C1220T-0
Service port
5/16″
Filter
Field piping J15.9 C1220T-0
Compressor
High pressure
switch
Indoor unit
Outdoor unit
Heating
Cooling
Stop valve
(with service port 5/16’ flare)
50
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
3TW26735-1
7
RZQS71-100BV3
Electronic expansion
valve
One way valve
One way valve
Heat exchanger
Filter
Service port
5/16″
One way valve
Heat exchanger
One way valve
Capillary
tube
Solenoid valve
Field piping
Filter
Receiver
Field piping
Strainer
Indoor unit
4-way valve
Muffler
Low pressure
sensor
Muffler
Heat exchanger
One way valve
Branch duct
connection
Field piping J9.5
Service port
5/16″
Option
Field piping J15.9
Compressor
Outdoor unit
Field piping
Filter
Indoor unit
Field piping
Stop valve
(with service port 5/16’ flare)
Note: 1. The pipes between the branch and the indoor units
should have the same size as the indoor connections.
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
1006
High pressure
switch
• Split Sky Air • Outdoor Units
Heating
Cooling
3TW26735-2
• Outdoor Units • R-410A • RZQS71-100B7V3B
7
Piping diagram
RZQS100BV3
Indoor unit
Electronic expansion
valve
Heat exchanger
Stop valve
(with service port 5/16’ flare)
One way
valve
One way
valve
One way
valve
One way
valve
Filter
Service port
5/16″
Field piping
Filter
Heat exchanger
Capillary
tube
Field piping
Capillary tube
Solenoid valve
Indoor unit
Heat exchanger
Receiver
Strainer
Field piping J9.5
4-way valve
C1220T-0
Muffler
Field piping
Filter
Field piping
Low pressure
switch
Muffler
Field piping J15.9
C1220T-0
Service port
5/16″
Indoor unit
Heat exchanger
Branch duct
connection
(Option)
Compressor
High pressure
switch
Outdoor unit
Note: 1. The pipes between the branch and the
indoor units should have the same size as the indoor
connections.
Field piping
Filter
Heating
Cooling
Field piping
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split Sky Air • Outdoor Units
3TW29075-1
50
7
1007
• Outdoor Units • R-410A • RZQS71-100B7V3B
8
Wiring diagram
8-1
Wiring diagram
RZQS71-100BV3
Indoor
: Live
: Neutral
: Field wiring
: Protective earth (screw)
: Wire clamp
: Terminal
: Connector
NOTE 1.
L
N
Outdoor
: Relay connector
Colours
BLK: Black / ORG: Orange / BLU: Blue /
WHT: White / RED: Red / YLW:Yellow /
BRN: Brown / GRN: Green
ON
OFF
NOTES:
1. Refer to the optional manual, for connection wiring to
X6A.
2. Confirm the method of setting the selector switches
(DS1) by service manual. When the unit is shipped by
factory all switches are set to be off.
El. comp. assy front
50
A1P
A2P
BS1
C1-C2-C3
DS1
F1U
HAP (A1P)
HAP (A2P)
H1P (A1P)
Printed circuit board
Printed circuit board (INV)
Push button switch (forced def. / pump down)
Capacitor
Dip switch
Fuse (T6, 3A/250V)
Light emitting diode (service monitor green)
Light emitting diode (service monitor green)
Light emitting diode (service monitor red)
K1M(A2P)
K1R(A1P)
K2R(A1P)
K2R(A2P)
L1R
M1C
M1F
PS
Q1DI
R1-R2
R1T
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay (Y2S)
Magnetic relay
Reactor
Motor compressor
Motor fan
Power circuit
Earth leakage breaker (30mA)
Resistor
Thermistor (air)
R2T
R3T
R4T
R5T
S1PH
S1NPL
RC
TC
V1R
8
1008
• Split Sky Air • Outdoor Units
Thermistor (coil)
Thermistor (discharge pipe)
Thermistor (suction pipe)
Thermistor (power module)
Pressure switch (high)
Pressure sensor (low)
Signal receiver circuit
Signal transmission circuit
Power module
V2R-V3R
V1T
X6A
X1M
Y1E
Y1S
Y2S
Z1C, Z2C
Z3C, Z4C
Z1F
View A
Diode module
IGBT
Connector (Option)
Terminal strip
Expansion valve
4-way valve
Solenoid valve
Noise filter
Noise filter (with surge absorber)
2TW26736-1B
• Outdoor Units • R-410A • RZQS71-100B7V3B
9
Sound data
9-1
Sound pressure spectrum
Sound pressure level (dB)
RZQS71BV3 - Heating
Sound pressure level (dB)
RZQS71BV3 - Cooling
3TW29067-1A
3TW29067-2A
Octave band center frequency (Hz)
NOTES
1
2
3
4
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20µPa
1
2
3
4
Measuring location
(discharge side)
Measuring location
(discharge side)
50
9
Sound pressure level (dB)
RZQS100BV3 - Heating
Sound pressure level (dB)
RZQS100BV3 - Cooling
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20µPa
3TW29077-1A
Octave band center frequency (Hz)
3TW29077-2A
NOTES
1
2
3
4
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20µPa
1
2
3
Measuring location
(discharge side)
• Split Sky Air • Outdoor Units
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20µPa
Measuring location
(discharge side)
1009
• Outdoor Units • R-410A • RZQS71-100B7V3B
9
Sound data
9-2
Sound power spectrum
Sound power level (dB)
RZQS100BV3
Sound power level (dB)
RZQS71BV3
3TW29067-3
Octave band center frequency (Hz)
3TW29077-3
NOTES
50
1
2
3
NOTES
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic intensity 0dB = 10E-6µW/m2
Measured according to ISO 3744
9
1010
Octave band center frequency (Hz)
• Split Sky Air • Outdoor Units
1
2
3
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic intensity 0dB = 10E-6µW/m2
Measured according to ISO 3744
• Outdoor Units • R-410A • RZQS71-100B7V3B
10
Installation
10 - 1 Installation method
RZQS71~ 100BV3
A. Non stacked installation
Legend
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
B. Stacked installation
50
2. Obstacles exist in front of the air inlet
1. Obstacles exist in front of the outlet side
10
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in lateral
connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
• Split Sky Air • Outdoor Units
1011
• Outdoor Units • R-410A • RZQS71-100B7V3B
11
Operation range
RZQS71-100BV3
Cooling
Model name
RZQ71B7V3
Indoor temp. (°CWB)
Operation range
Allowable range of operation
(warming-up)
Heating
Outdoor temp. (°CWB)
Allowable range of operation (pull-down)
Outdoor temp. (°CDB)
RZQS100B7V3
Indoor temp. (°CDB)
Notes:
50
- Depending on operation and installation conditions, the indoor unit can change over to
freeze-up operation (indoor de-icing).
- To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install
the outdoor unit in a location not exposed to wind.
3TW29063-1B
11
1012
• Split Sky Air • Outdoor Units