Download 50 - daikin tech.co. uk
Transcript
• Outdoor Units • R-410A • RZQS71-100B7V3B 1 AV i7 Bny 0U k 0 S 1 r - o A1t o 07 i d 1S l t4Q pu-Z S•RO • Features Outdoor units for pair, twin, triple, double twin application The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners. During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy. • Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall. • The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level • Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency • An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures. • A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions 50 1 992 • • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS71-100B7V3B 2 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT RZQS71B7V3B RZQS100B7V3B For combination indoor units + outdoor units Indoor Units FCQ71C7VEB FCQ100C7VEB Cooling capacity Standard kW 7.10 10.00 Heating capacity Standard kW 8.00 11.20 Power Input For combination indoor units + outdoor units Cooling Standard kW 2.46 3.83 Heating Standard kW 2.61 3.47 EER Nominal 2.89 2.61 COP Nominal 3.07 3.23 Energy Label Cooling C D Heating D C 1230 1915 FBQ71B8V3B FBQ100B8V3B 7.10 10.00 8.00 11.20 Annual energy consumption kWh Indoor Units Cooling capacity Standard kW Heating capacity Standard kW Power Input For combination indoor units + outdoor units Cooling Standard kW 2.52 3.83 Heating Standard kW 2.40 3.47 EER Nominal 2.82 2.61 COP Nominal 3.33 3.23 Energy Label Cooling C Heating Annual energy consumption kWh Indoor Units Cooling capacity Standard kW Heating capacity Standard kW Power Input For combination indoor units + outdoor units 2 1260 1915 FHQ71BUV1B FHQ100BUV1B 7.10 10.00 8.00 11.20 Cooling Standard kW 2.53 4.15 Standard kW 2.84 3.99 EER Nominal 2.81 2.41 COP Nominal 2.82 2.81 Energy Label Cooling C Heating Cooling capacity Standard kW Heating capacity Standard kW E D Annual energy consumption kWh For combination indoor units + outdoor units 50 Heating Indoor Units Power Input D C 1265 2075 FAQ71BUV1B FAQ100BUV1B 7.10 10.00 8.00 11.20 Cooling Standard kW 2.53 4.08 Heating Standard kW 2.61 3.73 EER Nominal 2.81 2.45 COP Nominal 3.01 3.00 Energy Label Cooling C Heating E D Annual energy consumption kWh Indoor Units 1265 2040 FCQH71C7VEB FCQH100C7VEB 7.10 10.00 8.00 11.20 Cooling capacity Standard kW Heating capacity Standard kW Cooling Standard kW 2.36 3.56 Heating Standard kW 2.34 3.28 Power Input • Split Sky Air • Outdoor Units 993 • Outdoor Units • R-410A • RZQS71-100B7V3B 2 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT For combination indoor units + outdoor units RZQS71B7V3B RZQS100B7V3B EER Nominal 3.01 2.81 COP Nominal 3.42 3.41 Energy Label Cooling B Heating Annual energy consumption kWh 2-2 TECHNICAL SPECIFICATIONS Casing Colour Dimensions Unit 1180 Painted galvanised steel mm 770 770 Width mm 900 900 Depth mm 320 320 Height mm 900 900 Width mm 980 980 Depth mm 420 420 Unit kg 68 68 Packed Unit kg 72 72 mm 857 857 2 2 mm 1.40 1.40 3 3 0.641 0.641 Dimensions Length Nr of Rows Fin Pitch Nr of Passes Face Area 50 m² Nr of Stages 34 Tube type 2 Fin Type WF fin Anti-corrosion treatment (PE) Type Propeller Discharge direction Horizontal Quantity Air Flow Rate (nominal at 230V) Cooling m³/min Heating m³/min Motor Quantity 1 1 54.5 61.3 48.1 61.7 1 Model Motor Speed (nominal) Steps Fan Motor Compressor Quantity Motor Cooling Heating Sound Level (nominal) Cooling Heating Sound Level (Night quiet) 994 Sound Pressure 1 KFD-325-70-8A 8 8 rpm 818 920 Heating rpm 715 920 Output W 70 70 Cooling 1 Model 1 2YC63BXD Type Operation Range 34 Hi-XSS(8) Treatment Fan RZQS100B7V3B Ivory White Height Packing Heat Exchanger 1780 RZQS71B7V3B Material Weight C B Hermetically sealed swing compressor Motor Output W Min °CDB -5.0 -5.0 Max °CDB 46.0 46.0 Min °CWB -15.0 -15.0 Max °CWB 15.5 15.5 Sound Power dBA 65.0 67.0 Sound Pressure dBA 49.0 51.0 Sound Pressure dBA 51.0 55.0 43.0 45.0 1800 dBA • Split Sky Air • Outdoor Units 1800 • Outdoor Units • R-410A • RZQS71-100B7V3B 2 Specifications 2-2 TECHNICAL SPECIFICATIONS Refrigerant RZQS71B7V3B Type Charge kg 2.80 2.80 Control Expansion valve (electronic type) Nr of Circuits Refrigerant Oil 1 1 Type Daphne FVC50K Charged Volume Piping connections Liquid (OD) l 0.8 Quantity 0.8 1 1 Type Flare connection Diameter (OD) Gas mm 9.52 Quantity 9.52 1 1 Type Flare connection Diameter (OD) Drain mm 15.9 Quantity 15.9 3 3 Type Piping Length Hole Diameter (OD) mm Minimum 26 26 m 5 5 Maximum m 30 50 Equivalent m 40 70 Chargeless m 30 30 Additional Refrigerant Charge Installation height difference RZQS100B7V3B R-410A kg/m see installation manual 4PW32097-1 Maximum m Max. internunit level difference m 15 30 0.5 0.5 Heat Insulation 50 2 Both liquid and gas pipes Defrost Method Pressure equalising Defrost Control Sensor for outdoor heat exchanger temperature Capacity Control Method Inverter controlled Safety Devices High pressure switch Fan motor thermal protector Fuse Standard Accessories Item Tie-wraps Quantity 2 Item 2 Installation manual Quantity 1 Notes 1 Nominal cooling capacities are based on : indoor temperature : 270CDB, 190CWB, outdoor temperature : 350CDB Nominal heating capacities are based on : indoor temperature : 200CDB, outdoor temperature : 70CDB, 60CWB 2-3 ELECTRICAL SPECIFICATIONS Power Supply RZQS71B7V3B Name V3 Phase Frequency Voltage Voltage range RZQS100B7V3B Minimum 1 1 Hz 50 50 V 230 V Maximum V Current Recomended fuses Wiring connections For Power Supply A 230 -10% +10% 20 Remark For connection Remark with indoor Power Supply Intake 20 see installation manual 4PW32097-1 see installation manual 4PW32097-1 Outdoor unit only Notes See separate drawings for electrical data • Split Sky Air • Outdoor Units 995 • Outdoor Units • R-410A • RZQS71-100B7V3B 3 Electrical data RZQS71-100BV3 Unit combination Indoor unit Outdoor unit Hz-volts Power supply Comp. Voltage range MCA TOCA MFA MSC RLA 50 OFM kW IFM FLA kW FLA 3D055645A 3 NOTES SYMBOLS MCA TOCA MFA MSC RLA OFM IFM FLA kW 996 : Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (See note 7) (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW) 1 2 3 4 5 6 7 8 RLA is based on the following conditions: Power supply: 50Hz 230V Heating Cooling Indoor temperature 20.0°CDB Indoor temperature 27°CDB/19°CWB Outdoor temperature 7.0°CDB/6.0°CWB Outdoor temperature 35°CDB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the document title of your choice. • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS71-100B7V3B 4 Options Available option for RZQS71-100B7V3 Name of option Kit name RZQS71B7V3B Central drain plug Refrigerant branch piping RZQS100B7V3B KKPJ5F180 Twin KHRQ22M20TA Triple - KHRQ127H Double twin - - Demand adapter kit KRP58M51 3TW26739-1E 50 4 • Split Sky Air • Outdoor Units 997 • Outdoor Units • R-410A • RZQS71-100B7V3B 5 Capacity tables 5-1 Combination table Possible combinations and standard capacity for twin, triple and double twin application Possible indoor combination Simultaneous operation Outdoor models Twin Triple Out Out In In RZQS71B7V3 35-35 (KHRQ22M20TA7) RZQS100B7V3 50-50 (KHRQ22M20TA7) In In Double twin Out In In In In In 35-35-35 (KHRQ127H7) 3TW29069-1 NOTES 50 1 Possible indoor units: FCQ35-125B, FFQ35-60BV, FHQ35-125B, FBQ35-125B, FAQ71-100B, FDQ125B. 2 Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room). 3 When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ). 4 Between brackets are the required Refnet kits mentioned, that are necessary to install the combination. 5 998 • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS71-100B7V3B 5 Capacity tables 5-2 Cooling capacity tables RZQS71BV3 (Pair + Multi) Coefficient of power input. (-) Cooling Capacity range Rated point Cooling capacity (kW) Cooling capacity 230V [50Hz] Indoor EWB Outdoor temp. (°CDB) EDB (°C) (°C) 16.0 18.0 19.0 19.5 22.0 24.0 22 25 27 27 30 32 25 SHC (kW) 4.39 4.82 4.80 4.79 4.73 4.66 TC (kW) 6.47 7.43 7.58 7.66 8.05 8.37 CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85 TC (kW) 6.46 7.20 7.35 7.43 7.81 8.12 30 SHC (kW) 4.43 4.72 4.71 4.70 4.64 4.58 CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93 TC (kW) 6.66 6.95 7.10 7.17 7.55 7.85 35 SHC (kW) 4.62 4.61 4.60 4.59 4.54 4.48 CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02 TC (kW) 6.39 6.67 6.82 6.89 7.26 7.55 40 SHC (kW) 4.49 4.47 4.46 4.46 4.41 4.35 CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D055646A NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length :5m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair) Model AFR (BF) FCQH71C 20 (0.17) FCQ71C 15.5 (0.19) FCQ71B 18 (0.10) FBQ71B 19 (0.11) FHQ71B 17 (0.10) FAQ71B 19 (0.08) FBQ71B 2.52 2.40 FHQ71B 2.53 2.85 FAQ71B 2.53 2.61 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating FCQH71C 2.36 2.34 FCQ71C 2.46 2.61 FCQ71B 2.46 2.61 AFR: BF: EWB: EDB: TC: SHC: PI: CPI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. 50 5 (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Multi) Model AFR (BF) FCQ35Cx2 10.5x2 (0.28x2) FCQ35Bx2 14x2 (0.16x2) FFQ35Bx2 10x2 (0.25x2) FBQ35Bx2 11.5x2 (0.15x2) FHQ35Bx2 13x2 (0.2x2) FCQ35Cx2 2.59 2.75 FCQ35Bx2 2.59 2.75 FFQ35Bx2 2.61 2.70 FBQ35Bx2 2.57 2.47 FHQ35Bx2 2.66 2.85 (Multi) • Split Sky Air • Outdoor Units Model Cooling Heating 999 • Outdoor Units • R-410A • RZQS71-100B7V3B 5 Capacity tables 5-2 Cooling capacity tables RZQS100BV3 (Pair + Twin/triple) Coefficient of power input. (-) Cooling Capacity range Rated point Cooling capacity (kW) Cooling capacity 400V [50Hz] Indoor 50 5 Outdoor temp. (°CDB) EWB EDB (°C) (°C) 16.0 18.0 19.0 19.5 22.0 24.0 22 25 27 27 30 32 25 SHC (kW) 6.19 6.78 6.76 6.75 6.66 6.57 TC (kW) 9.12 10.5 10.7 10.8 11.3 11.8 CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85 TC (kW) 9.10 10.1 10.4 10.5 11.0 11.4 30 SHC (kW) 6.25 6.65 6.63 6.62 6.54 6.45 CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93 35 SHC (kW) 6.51 6.49 6.48 6.47 6.39 6.30 TC (kW) 9.38 9.79 10.0 10.1 10.6 11.1 CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02 TC (kW) 9.00 9.40 9.60 9.71 10.2 10.6 40 SHC (kW) 6.32 6.30 6.29 6.28 6.21 6.13 CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D055647A NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length :5m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair) AFR: BF: EWB: EDB: TC: SHC: PI: CPI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Twin) Model AFR (BF) FCQH100C 32.5 (0.17) Model AFR (BF) FCQ35Cx3 10.5x3 (0.28x3) FCQ100C 23.5 (0.16) FCQ100B 28 (0.16) FBQ100B 27 (0.20) FHQ100B 24 (0.14) FAQ100B 23 (0.10) Model AFR (BF) FCQ50Cx2 12.5x2 (0.21x2) FCQ50Bx2 15x2 (0.16x2) FFQ50Bx2 12x2 (0.16x2) FBQ50Bx2 14x2 (0.15x2) FHQ50Bx2 13x2 (0.1x2) FCQ50Cx2 3.83 3.65 FCQ50Bx2 3.83 3.65 FFQ50Bx2 3.83 3.54 FBQ50Bx2 3.83 3.58 FHQ50Bx2 4.15 3.99 (Triple) FCQ35Bx3 14x3 (0.16x3) FFQ35x2 10x3 (0.25x3) FBQ35x3 11.5x3 (0.15x3) FHQ35x3 13x3 (0.2x3) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating FCQH100C 3.56 3.28 FCQ100C 3.83 3.47 (Twin) FCQ100B 3.83 3.47 FBQ100B 3.83 3.47 FHQ100B 4.15 3.99 FAQ100B 4.08 3.73 (Triple) Model Cooling Heating 1000 FCQ35Cx3 3.83 3.65 FCQ35Bx3 3.83 3.65 FFQ35Bx3 3.83 3.54 FBQ35Bx3 3.83 3.58 FHQ35Bx3 4.15 3.99 • Split Sky Air • Outdoor Units Model Cooling Heating • Outdoor Units • R-410A • RZQS71-100B7V3B 5 Capacity tables 5-2 Cooling capacity tables RZQS71-100BV3 Capacity in function of field piping length for non-inverter Capacity (%) 50 5 Field piping length (m) 3TW29069-3 Cooling Heating • Split Sky Air • Outdoor Units 1001 • Outdoor Units • R-410A • RZQS71-100B7V3B 5 Capacity tables 5-3 Heating capacity tables RZQS71BV3 (Pair + Multi) Coefficient of power input. (-) Heating Rated point Capacity range Heating capacity (kW) Heating capacity 230V [50Hz] Indoor EDB (°C) 16.O 18.O 20.0 21.O 22.O 24.0 −10 CPI (-) 1.12 1.16 1.21 1.23 1.25 1.30 TC (kW) 6.22 6.21 6.20 6.20 6.19 6.19 −5 CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36 NOTES 10 CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08 TC (kW) 8.64 8.62 8.61 8.61 8.60 8.59 CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length :5m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair) Model AFR (BF) FCQH71C 20 (0.17) FCQ71C 15.5 (0.19) FCQ71B 18 (0.10) FBQ71B 19 (0.11) FHQ71B 17 (0.10) FAQ71B 19 (0.08) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating 1002 6 TC (kW) 8.02 8.01 8.00 8.00 7.99 7.98 3D055646A 50 5 TC (kW) 5.68 5.67 5.67 5.66 5.66 5.65 Outdoor temp. (°CWB) 0 TC CPI (kW) (-) 6.75 1.23 6.74 1.28 6.74 1.33 6.73 1.35 6.73 1.38 6.72 1.43 FCQH71C 2.36 2.34 FCQ71C 2.46 2.61 FCQ71B 2.46 2.61 FBQ71B 2.52 2.40 AFR: BF: EWB: EDB: TC: SHC: PI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. CPI: (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Multi) Model AFR (BF) FCQ35Cx2 10.5x2 (0.28x2) FCQ35Bx2 14x2 (0.16x2) FFQ35Bx2 10x2 (0.25x2) FBQ35Bx2 11.5x2 (0.15x2) FHQ35Bx2 13x2 (0.2x2) FCQ35Cx2 2.59 2.75 FCQ35Bx2 2.59 2.75 FFQ35Bx2 2.61 2.70 FBQ35Bx2 2.57 2.47 FHQ35Bx2 2.66 2.85 (Multi) FHQ71B 2.53 2.85 FAQ71B 2.53 2.61 • Split Sky Air • Outdoor Units Model Cooling Heating • Outdoor Units • R-410A • RZQS71-100B7V3B 5 Capacity tables 5-3 Heating capacity tables RZQS100BV3 (Pair + Twin/triple) Coefficient of power input. (-) Heating Capacity range Rated point Heating capacity (kW) Heating capacity 400V [50Hz] Indoor EDB −10 TC (kW) 7.91 7.90 7.89 7.89 7.88 7.87 (°C) 16.O 18.O 20.0 21.O 22.O 24.0 CPI (-) 1.07 1.11 1.15 1.17 1.20 1.24 TC (kW) 8.66 8.65 8.64 8.63 8.63 8.62 −5 Outdoor temp. (°CWB) 0 TC CPI (kW) (-) 9.41 1.17 9.39 1.22 9.38 1.27 9.38 1.29 9.37 1.32 9.36 1.36 CPI (-) 1.12 1.16 1.21 1.23 1.26 1.30 6 TC (kW) 11.2 11.2 11.2 11.2 11.2 11.2 10 CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08 TC (kW) 12.1 12.1 12.1 12.1 12.0 12.0 CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D055647A NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length :5m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair) AFR: BF: EWB: EDB: TC: SHC: PI: CPI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. 50 5 (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Twin) Model AFR (BF) FCQH100C 32.5 (0.17) Model AFR (BF) FCQ35Cx3 10.5x3 (0.28x3) FCQ100C 23.5 (0.16) FCQ100B 28 (0.16) FBQ100B 27 (0.20) FHQ100B 24 (0.14) FAQ100B 23 (0.10) Model AFR (BF) FCQ50Cx2 12.5x2 (0.21x2) FCQ50Bx2 15x2 (0.16x2) FFQ50Bx2 12x2 (0.16x2) FBQ50Bx2 14x2 (0.15x2) FHQ50Bx2 13x2 (0.1x2) FCQ50Cx2 3.83 3.65 FCQ50Bx2 3.83 3.65 FFQ50Bx2 3.83 3.54 FBQ50Bx2 3.83 3.58 FHQ50Bx2 4.15 3.99 (Triple) FCQ35Bx3 14x3 (0.16x3) FFQ35x2 10x3 (0.25x3) FBQ35x3 11.5x3 (0.15x3) FHQ35x3 13x3 (0.2x3) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating FCQH100C 3.56 3.28 FCQ100C 3.83 3.47 (Twin) FCQ100B 3.83 3.47 FBQ100B 3.83 3.47 FHQ100B 4.15 3.99 FAQ100B 4.08 3.73 Model Cooling Heating (Triple) Model Cooling Heating FCQ35Cx3 3.83 3.65 FCQ35Bx3 3.83 3.65 FFQ35Bx3 3.83 3.54 FBQ35Bx3 3.83 3.58 FHQ35Bx3 4.15 3.99 • Split Sky Air • Outdoor Units 1003 • Outdoor Units • R-410A • RZQS71-100B7V3B 6 Dimensional drawing & centre of gravity 6-1 Dimensional drawing unit (mm) RZQS71-100BV3 Hole for anchor bolt 4-M12 1 2 3 4 5 6 7 8 50 3TW25144-1A 6 1004 Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole J34) Control wiring intake (Knock out hole J27) Drain outlet • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS71-100B7V3B 6 Dimensional drawing & centre of gravity 6-2 Centre of gravity RZQS71-100BV3 4TW26069-3 50 6 • Split Sky Air • Outdoor Units 1005 • Outdoor Units • R-410A • RZQS71-100B7V3B 7 Piping diagram RZQS71-100BV3 Electronic expansion valve One way valve One way valve Heat exchanger Filter Service port 5/16″ One way valve One way valve Capillary tube Solenoid valve Receiver Strainer Heat exchanger 4-way valve Muffler Low pressure sensor Muffler One way valve Field piping J9.5 C1220T-0 Service port 5/16″ Filter Field piping J15.9 C1220T-0 Compressor High pressure switch Indoor unit Outdoor unit Heating Cooling Stop valve (with service port 5/16’ flare) 50 O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW26735-1 7 RZQS71-100BV3 Electronic expansion valve One way valve One way valve Heat exchanger Filter Service port 5/16″ One way valve Heat exchanger One way valve Capillary tube Solenoid valve Field piping Filter Receiver Field piping Strainer Indoor unit 4-way valve Muffler Low pressure sensor Muffler Heat exchanger One way valve Branch duct connection Field piping J9.5 Service port 5/16″ Option Field piping J15.9 Compressor Outdoor unit Field piping Filter Indoor unit Field piping Stop valve (with service port 5/16’ flare) Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 1006 High pressure switch • Split Sky Air • Outdoor Units Heating Cooling 3TW26735-2 • Outdoor Units • R-410A • RZQS71-100B7V3B 7 Piping diagram RZQS100BV3 Indoor unit Electronic expansion valve Heat exchanger Stop valve (with service port 5/16’ flare) One way valve One way valve One way valve One way valve Filter Service port 5/16″ Field piping Filter Heat exchanger Capillary tube Field piping Capillary tube Solenoid valve Indoor unit Heat exchanger Receiver Strainer Field piping J9.5 4-way valve C1220T-0 Muffler Field piping Filter Field piping Low pressure switch Muffler Field piping J15.9 C1220T-0 Service port 5/16″ Indoor unit Heat exchanger Branch duct connection (Option) Compressor High pressure switch Outdoor unit Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. Field piping Filter Heating Cooling Field piping O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe • Split Sky Air • Outdoor Units 3TW29075-1 50 7 1007 • Outdoor Units • R-410A • RZQS71-100B7V3B 8 Wiring diagram 8-1 Wiring diagram RZQS71-100BV3 Indoor : Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector NOTE 1. L N Outdoor : Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green ON OFF NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off. El. comp. assy front 50 A1P A2P BS1 C1-C2-C3 DS1 F1U HAP (A1P) HAP (A2P) H1P (A1P) Printed circuit board Printed circuit board (INV) Push button switch (forced def. / pump down) Capacitor Dip switch Fuse (T6, 3A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red) K1M(A2P) K1R(A1P) K2R(A1P) K2R(A2P) L1R M1C M1F PS Q1DI R1-R2 R1T Magnetic contactor Magnetic relay (Y1S) Magnetic relay (Y2S) Magnetic relay Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor Thermistor (air) R2T R3T R4T R5T S1PH S1NPL RC TC V1R 8 1008 • Split Sky Air • Outdoor Units Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal receiver circuit Signal transmission circuit Power module V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F View A Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter Noise filter (with surge absorber) 2TW26736-1B • Outdoor Units • R-410A • RZQS71-100B7V3B 9 Sound data 9-1 Sound pressure spectrum Sound pressure level (dB) RZQS71BV3 - Heating Sound pressure level (dB) RZQS71BV3 - Cooling 3TW29067-1A 3TW29067-2A Octave band center frequency (Hz) NOTES 1 2 3 4 Octave band center frequency (Hz) NOTES Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa 1 2 3 4 Measuring location (discharge side) Measuring location (discharge side) 50 9 Sound pressure level (dB) RZQS100BV3 - Heating Sound pressure level (dB) RZQS100BV3 - Cooling Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa 3TW29077-1A Octave band center frequency (Hz) 3TW29077-2A NOTES 1 2 3 4 Octave band center frequency (Hz) NOTES Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa 1 2 3 Measuring location (discharge side) • Split Sky Air • Outdoor Units 4 Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20µPa Measuring location (discharge side) 1009 • Outdoor Units • R-410A • RZQS71-100B7V3B 9 Sound data 9-2 Sound power spectrum Sound power level (dB) RZQS100BV3 Sound power level (dB) RZQS71BV3 3TW29067-3 Octave band center frequency (Hz) 3TW29077-3 NOTES 50 1 2 3 NOTES dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744 9 1010 Octave band center frequency (Hz) • Split Sky Air • Outdoor Units 1 2 3 dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6µW/m2 Measured according to ISO 3744 • Outdoor Units • R-410A • RZQS71-100B7V3B 10 Installation 10 - 1 Installation method RZQS71~ 100BV3 A. Non stacked installation Legend Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 50 2. Obstacles exist in front of the air inlet 1. Obstacles exist in front of the outlet side 10 Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 • Split Sky Air • Outdoor Units 1011 • Outdoor Units • R-410A • RZQS71-100B7V3B 11 Operation range RZQS71-100BV3 Cooling Model name RZQ71B7V3 Indoor temp. (°CWB) Operation range Allowable range of operation (warming-up) Heating Outdoor temp. (°CWB) Allowable range of operation (pull-down) Outdoor temp. (°CDB) RZQS100B7V3 Indoor temp. (°CDB) Notes: 50 - Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing). - To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed to wind. 3TW29063-1B 11 1012 • Split Sky Air • Outdoor Units