Download AIR CONDITIONER - AHI

Transcript
FILE NO. SVM-08029
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
RAS-12SKSX-1 / RAS-12SASX-1
April, 2008
FILE NO. SVM-08029
CONTENTS
1.
2.
SPECIFICATIONS
CONSTRUCTION VIEWS
2-1
2-2
Indoor Unit
Outdoor Unit
3. WIRING DIAGRAM
4. SPECIFICATION OF ELECTRICAL PARTS
4-1
4-2
Indoor Unit
Outdoor Unit
5. REFRIGERATION CYCLE DIAGRAM
6. CONTROL BLOCK DIAGRAM
7. OPERATION DESCRIPTION
7-1
7-2
7-3
7-4
7-5
7-6
7-7
8.
9.
Remote Control
Outline of Air Conditioner Control
Description of Operation Mode
Low-Temperature Limit Control
ECO Operation
Filter Check Lamp
Auto Restart Function
INSTALLATION PROCEDURE
8-1
8-2
8-3
8-4
8-5
8-6
Safety Cautions
Installation Diagram of Indoor and Outdoor Units
Installation
Indoor Unit
Outdoor Unit
How to Set Remote Control Selector Switch
8-7
Others
TROUBLESHOOTING CHART
9-1
9-2
9-3
9-4
9-5
Troubleshooting Procedure
Basic Check Items
Primary Judgement
Self-Diagnosis by Remote Control (Check Code)
Troubleshooting Flowcharts
9-6
Troubleshooting for Remote Control (Including the Indoor P.C. Board)
10. HOW TO REPLACE THE MAIN PARTS
10-1 Indoor Unit
10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit
-1-
FILE NO. SVM-08029
1. SPECIFICATIONS
MODEL
RAS-12SKSX-1 / RAS-12SASX-1
ITEM
kW
3.58
Phase
Power source
Power consumption
Power factor
V
220 - 240
50
kW
1.27
%
96
Indoor
A
current
Outdoor
A
Starting current
Moisture removal
Refrigerant
Indoor (H/M/L)
23
lit/h
2.0
dB
44/38/33
R22
kg
0.70
Capillary tube
mm
Æ12.7
Flare connection
mm
Æ6.35
Interconnection Connection type
Flare connection
Maximum length
(One way)
m
10*
2
15*
Maximum height
difference
m
6
1
INDOOR UNIT
RAS-12SKSX-1
Height
Dimensions
mm
275
Width
mm
790
Depth
mm
205
Net weight
kg
9
Evaporator type
Finned tube
Indoor fan type
Cross flow fan
High fan
Air-flow volume Medium fan
Low fan
Fan motor output
3
m /h
590
m3/h
470
m3/h
410
W
20
Air filter
Honeycomb woven filter with PP frame
OUTDOOR UNIT
Dimensions
RAS-12SASX-1
Height
mm
Width
mm
660
Depth
mm
240
Net weight
530
kg
27
Condenser type
Finned tube
Outdoor fan type
Air-flow volume
Fan motor output
Compressor
49
48
Connection type
pipe
5.65
5.85
Refrigerant control
Liquid side size
94
0.15
Name of refrigerant
Gas side size
1.31
A
Outdoor (220 - 240 V) dB
Rated amount
3.58
1Æ
Hz
Running
Noise
240 V
220V
Capacity
Propeller fan
m3/h
W
30
W
QK222PCB
1100
Model
Output
Safety device
Fuse, Overload relay
Louver type
Usable outdoor temperature range
1710
1590
Automatic louver
°C
21 ~ 43
–2–
FILE NO. SVM-08029
Note : 1
· Capacity is based on the following temperature conditions.
JIS C9612
Condition
Temperature
Cooling
(DB)
27°C
(WB)
19°C
(DB)
35°C
(WB)
24°C
Indoor unit inlet air temperture
Outdoor unit inlet air temperture
Note : 2
• Charge refrigerant according to the table below.
Refrigerant
*1
No need to charge
extra refrigerant
*2
Need to charge
extra refrigerant
RAS-12SKSX-1 / RAS-12SASX-1
10m or less
Over 10m up to 15m ( 20g/m)
-3 -
FILE NO. SVM-08029
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
790
Air filter
205
Air inlet
63
48
48
Heat exchanger
7
7
63
275
Front panel
Knock out system
49
Knock out system
62
116
69
193
135
480
Installation plate hanger
54
Installation plate hanger
Drain hose (0.50m)
Connecting pipe (0.35m)
(Flare 12.7mm)
235
215
621
distance
to ceiling
60
Minimum
Minimum
distance
275
to wall
170 or more
40
40
170 or more
190
distance
to wall
84.5
Hanger
150
160.5
160.5
Center line
Hanger
150
84.5
Installation plate outline
-4-
23
Remote controller holder
45
Hanger
84.5
235
215
Minimum
113
Connecting pipe (0.40m)
(Flare 6.35mm)
65 or more
84.5
16
Wireless remote control
2-2. Outdoor Unit
FILE NO. SVM-08029
CL
CL
100
600
-5-
FILE NO. SVM-08029
3. WIRING DIAGRAM
Infrared rays receiver
and indication parts.
Heat Exchanger
GRN&YEL
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
CN10
2 3 4 5 6 7 8 9 10 11
CN14 1
1 2 3 4 5 6 7 8 9 10 11
BLK
P04
4
Heat Exchanger
Sensor(TC)
WP-018
DB01
CN01
1 1
2 2
Thermo Sensor(TA)
RY01
CN03
F01
6.3 A
250 VAC
1 1
2 2
BRW
BLU (N)
C27
+
R62
R63
Louver motor
CN11
1 1
2 2
3 3
1
C07 CN10
L01
POWER SUPPLY
(From Power Cord)
2
1Ø 220-240V ~ 50Hz
4
MCU
1
C25
C26
3
2
1 2
CN04 1 2
WHI
BLK
1
PNK
2
INDOOR
OUTDOOR
OUTDOOR
TERMINAL
BLOCK
1(L)
2(N)
CHASSIS
RED
BLK
BLK
RED
CAPACITOR
CAPACITOR
FAN MOTOR
RED
WHI
COMPRESSOR
OVERLOAD RELAY
BLK
5 5
WHI
3 3
BLK
1 1
4
CN31
INDOOR
TERMINAL
BLOCK
YEL
GRY
BRW
IC03
12V
3
GRN&YEL
5 5
5 5
Voltage
Regulator
DC 5 V
SG01
DSA
CN07
WHI
1 1 YEL 1 1
2 2 YEL 2 2
3 3 YEL 3 3
DC 12 V 4 4
4 4
YEL
Switching Power
Supply
GRN&YEL
POWER CORD
R64
3
PNK
WHI
−6−
PNK
TEMP FUSE
73°C
1
2
3
4
5
6
1
2
3
4
5
6
AC Motor
RED
FAN motor
FILE NO. SVM-08029
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
No.
Parts name
Type
1
Fan motor (for indoor)
2
Thermo sensor (TA-sensor)
3
Transformer
4
Microcontroller unit (IC30)
5
Heat exchanger sensor
(TC-sensor)
6
Line filter (L01)
7
Bridge rectifier (DB01)
8
Capacitor (C27)
9
Fuse (F01)
10
Varistor (R62, R63)
11
Louver motor
12
Relay (Comp., RY01)
AFS- 220-20-4AR
Specifications
AC Motor with 145 °C thermo fuse
10k W at 25°C
ST-001
TMP87CM40ANG
10k W at 25°C
*SS11V-06270
DB105G
27mH, 600mA
1.0A, 600 V
EKMH401VSN470MP20S 47mF, 400 V
BET6.3A
T6.3A, 250VAC
SR561K14DL
560 V
MP24Z3T
12VDC
G4A-1A
Rating 25A/AC250V
4-2. Outdoor Unit
No.
Parts name
Type
Specifications
Output (Rated) 990 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
1
Compressor
QK222PCB
Winding resistance (W)
C-R
C-S
(at 25 °C)
2.67
3.92
Output (Rated) 30 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
2
Fan motor (for outdoor)
WLF-240-30A
Winding resistance (W)
(at 20 °C)
3
Running capacitor
DS451155NPQB AC 450 V,1.5µF
4
Running capacitor
(for compressor)
RS44B356U0125S AC 440 V, 35 mF
5
Overload relay
LAAO00A
Red-Black
White-Black
237
380
U/T : 9.0A (80°C), Open : 135±5°C, Close : 75±11°C
-7-
FILE NO. SVM-08029
5. REFRIGERATION CYCLE DIAGRAM
Indoor unit
Heat exchanger
Cooling
0.39 m
(Connecting pipe)
Æ12.7
T1
0.49 m
(Connecting pipe)
Æ6.35
Cross flow fan
P
O.D.:12.7 mm
O.D.:6.35 mm
Packed valve
(Æ12.7)
Packed valve
(Æ6.35)
Cooling
Cooling Compressor
QK222PCB
Capillary tube
Æ1.7 x 800 l
Heat exchanger
Cooling
50Hz
Cooling
Refrigerant
R22 : 0.70 kg.
Propeller fan
Outdoor unit
Standard
pressure P
(MPaG)
Mark (
) means check points of Gas Leak.
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Standard
0.54
10.5
High
27/19
35/24
Overload
0.62
17.0
High
32/23
43/26
Low temperature
0.48
2.0
Low
21/15
21/15
Note
· Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
−8−
FILE NO. SVM-08029
6. CONTROL BLOCK DIAGRAM
Main Unit Control Panel
Heat Exchange sensor
M.C.U.
Operation
Display
Functions
Timer
Display
• Louver Control
Thermo. Sensor
• 3-minutes Delay at Restart
for Compressor
Infrared Rays Signal Reciver
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
• Processing
(Temperature Processing)
• Timer
Compressor
ON/OFF
Signal
Relay Driver, Louver Driver
RY01
Compressor, Outdoor Fan Motor
Infrared Rays
Remote Control
Operation (START/STOP)
Operation
Operation( Mode
)
Selection
AUTO, COOL, DRY, AUTO FAN
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
TIMER 1.3.5.9H
−9−
Indoor Fan
Motor
Louver
ON/OFF
Signal
Relay
REMOTE CONTROL
Filter Sign
Display
• Motor Revolution Control
Noise Filter
220-240 V~, 50Hz
Auto Fan
Sign Display
Louver
Motor
FILE NO. SVM-08029
7. OPERATION DESCRIPTION
1
7-1. Remote control
7-1-1. Function of Push Button
1
2
3
4
5
6
7
8
9
10
11
20
12
123
14
Infrared signal emitter
Set louver button (FIX)
Auto louver button (SWING)
Mode select button (MODE)
Reset button (RST)
On timer button (ON)
Off timer button (OFF)
Reserve button (SET)
Cancel button (CLR)
Check button (CHK)
ECO button (ECO)
Fan speed button (FAN)
Start/Stop button (START/STOP)
Temperature button (
)
TOSHIBA
TEMP.
MODE
AUTO
COOL
DRY
FAN
AUTO
QUIET
B
Hr.ON
AUTO FAN
OFF
TEMP.
214
START/STOP
2
3
4
5
6
7
- 10 -
213
SWING
FIX
FA N
MODE RST CHK ECO
TIMER
ON
OFF
SET
CLR
12
20
11
10
9
8
FILE NO. SVM-08029
7-1-2. Display of Remote Control
All indications, except for the clock time indicator, are displayed by pressing the
1.
Transmission mark
This transmission mark indicates when the
remote controller transmits signals to the indoor
unit.
2.
Mode indicator
Indicates the current operation mode.
(AUTO, COOL, DRY and AUTO FAN)
3.
Temperature indicator
Indicates the temperature setting.
(17°C to 30°C)
4.
ECO indicator
Indicates when the ECO is in activated.
Press the ECO button to start and press it again
to stop operate.
5.
A, B change indicator remote controller
When the remote controller switching function is
set, "B" appears in the remote controller display
(When the remote controller seting is "A", there is
no indication at this position.)
2
1
3
6.
Operation
Indicate when press the operation
ON/OFF button.
7.
FAN speed indicator
Indicates the selected fan speed.
AUTO, QUIET or three fan speed levels
( LOW , MED
, HIGH
can be shown.
Indicate Auto will be appear with Dry operation
only.
8.
7
6
• ••
B •
•
Hr.ON OFF •
• • •
••
7
7
8
4
button.
5
8
− 11 −
ON/OFF TIMER indicator
Indicates when the ON/OFF TIMER operation.
(ON TIMER [Hr. ON], OFF TIMER [OFF]).
FILE NO. SVM-08029
• Turning off the compressor and outdoor f an
when the outdoor unit receives the shut down
command
7-2. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses
a AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
7-2-1. Louver control
parts which operate the compressor and the outdoor
(1) Vertical air flow louver
fan motor, are mounted in the outdoor unit.
Position of veritcal air flow louver is automatically
The air conditioner is mainly controlled by the indoor
controlled according to the operation mode.
unit controller. The controller operates the indoor fan
Besides, position of vertical air flow louver can be
motor based upon commands transmitted by the
arbitrarily set by pressing [FIX] button.
remote control and transfers the operation commands
The
louver position which is set by [FIX] button is
to the outdoor unit.
stored
in the microcomputer, and the louver is
The outdoor unit receives operation
automatically
set at the stored position for the next
commands from the indoor unit, and operates the
operation.
outdoor fan motor and the compressor.
(2) Swing
(1) Role of indoor unit controller
If [SWING] button is pressed when the indoor unit
The indoor unit controller receives the operation
is in operation, the vertical air flow louver starts
commands from the remote control and executes
swinging. When [FIX] button is pressed, it stops
them.
swinging.
• Temperature measurement at the air inlet of the
7-2-2. Indoor Fan Control
indoor heat exchanger by the indoor
temperature sensor
The operation controls the fan speed at indoor unit
• Temperature measurement of the indoor heat
side. The indoor fan (cross flow fan) is operated by
exchanger by the heat exchanger sensor
the phase control induction motor. The fan rotates in 3
• Louver motor control
stages in MANUAL mode, and in 5 stages in AUTO
• Indoor fan motor operation control
mode, respectively. (Table 7-2-1)
• LED display control
1) When setting the fan speed to L, M or H
• Transferring of operation commands to the
on the remote controller, the operation is performed
outdoor unit
with the constant speed shown in Fig. 7-2-1
• Receiving of information of the operation status
Fig (7-2-1)
and judging of the information or indication of
Fan speed
Indication
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
Operations according
control
to the commands
• Operation control of
from the indoor unit
outdoor fan motor
L
Low
M
Med
H
High
2) When setting the fan speed to AUTO on the remote
controller, revolution of the fan motor is controlled
to the fan speed level shown in Table 1 according to
the setup temperature, room temperature, and heat
exchanger temperature.
3) When setting the fan speed to QUIET on the remote
controller, revolution of the fan motor is controlled to
the fan speed level is L-.
Table 7-2-1 Indoor fan and air flow rate
FAN TAP
OPERATION
MODE
UH
Cooling
Fan only
H
M+
M
L+
L
L-
H
M+
M
L+
L
L-
M+
M
L+
L
L-
Model
Dry
RAS-12SKSX-1
rpm
Air flow volume (m /h)
3
UL
UL
SL
SL
1300
1250 11601100 1060 1000
950 800 750 700 650 600
620
590 530 490 470
410 320 290 260 230 200
- 12 -
430
FILE NO. SVM-08029
7-3-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
7-3. Description of Operation Mode
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
OFF OFF
Preset
temp.
°C
OPERATION
display lamp
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When
[FAN] button is set to LOW, MED, or HIGH, the
motor operates with a constant air flow.
(Room temp.) − (Preset temp.)
ON
0
Compressor
7-3-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
ON ON
0.5
Outdoor fan
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
°C
(Room temp.)
(2) When pressing [ ] button on the remote control,
receiving beep sounds from the indoor unit, and
the next operation is performed together with
opening the vertical air flow louver.
(Preset temp.)
(1) The compressor, outdoor fan and operation display
lamp are controlled as shown in Fig. 7-3-2.
Fig. 7-3-2
+3
M+
+2.5
*1
+2
*2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When
[FAN] button is set to LOW, MED, or HIGH, the
motor operates with a constant air flow.
+1.5
(Room temp.) − (Preset temp.)
*3
+1
+0.5
Preset
temp.
0
(Preset temp.: 24 °C)
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 1/4 + L
Preset
temp.
(Linear approximation from M+ and L)
°C
+3
M+
+2.5
*1
+2
+1.5
*2
*3
+1
+0.5
0
-0.5
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 1/4 + L
NOTE2 : The ECO operation can not be set
(Linear approximation
from M+ and L)
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
- 13 -
FILE NO. SVM-08029
(1) The compressor, outdoor fan and operation
display lamp are controlled as shown in
Fig. 7-3-4.
(1) One of 2 operations (Cooling or Fan only)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-3-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
ON:6min.
OFF:4min.
ON:6min.
OFF:4min.
7-3-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
°C
+2
Preset
temp.
0
ON:5min.
OFF:5min.
ON:5min.
OFF:5min.
(Room temp.)
+3
(2) Temporary Auto
When the RESET button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-3-6.
ON
+1
°C
OPERATION
display lamp
Outdoor fan
Compressor
OFF OFF
Fig. 7-3-4
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-3-5.
(Room temp.) − (Preset temp.)
(Preset temp.)
7-3-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
Cooling operation
0
Fan only operation
Room temp.
Preset temp.+1
Fig. 7-3-6
Preset temp.
7-4. Low-Temperature Limit Control
Compressor
ON
ON
ON
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
ON
Outdoor fan
OFF
Indoor fan
L.
*S.L.
OFF
L.
S.L.
OFF
L.
S.L.
L.
*Super Low
Heat exchanger
temperature
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(°C)
6
2
(4) The ECO operations can not be set.
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Fig. 7-4-1
- 14 -
FILE NO. SVM-08029
7-5. ECO Operation
Cooling operation
· The preset temperature will increase 1ºC after the
ECO mode has operated for 1 hour and the
temperature will increase another 1ºC after the ECO
mode has operated for 2 hour. (the value of the preset
temperature on the remote control does not change.)
· The indoor fan speed is L-.
7-6. FILTER CHECK LAMP
When the elapsed time reaches 1000 hours,
the FILTER indicator lights. After cleaning the filters,
turn off the FILTER indicator.
How to Turn Off FILTER Indicator
Press [RESET] button on the indoor unit.
NOTE :
If [RESET] button is pushed while the FILTER
indicator is not lit, the indoor unit will start the
automatic operation.
When you want a temporary operation while
the FILTER lamp lights, press [RESET] button
to turn off the FILTER lamp.
- 15 -
FILE NO. SVM-08029
7-7. Auto Restart Function
This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with
the set operating conditions in the event of a power supply being accidentally shut down.
The operation will resume without warning three minutes after power is restored.
This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
7-7-1. How to Set the Auto Restart Function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on ; the function will not set if the power is off.
Press the [RESET] button located in the center of the front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the event of power supply being accidentally shut down.
• When the unit is standby (Not operating)
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is on standby.
↓
The unit starts to operate.
↓
After approx. three seconds,
The unit beeps three times
and continues to operate.
Hi POWER FILTER
PAP
TIMER
The green indicator is on.
The green indicator blinks
for 5 seconds.
OPERATION
RESET
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
• When the unit is in operation
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is in operation.
↓
The unit stops operating.
↓
PAP
TIMER
OPERATION
The green indicator is turned off.
After approx. three seconds,
The unit beeps three times.
Hi POWER FILTER
The green indicator is on.
The green indicator blinks
for 5 seconds.
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
RESET
Hi POWER FILTER
PAP
TIMER
OPERATION
• While the filter check indicator is on, the RESET button has the function of filter reset button.
- 16 -
FILE NO. SVM-08029
7-7-2. How to Cancel the Auto Restart Function
To cancel auto restart function, proceed as follows :
Repeat the setting procedure : the unit receives the signal and beeps three times.
The unit will be required to be turned on with the remote controller after the main power supply is turned off.
• When the system is on stand-by (not operating)
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is on standby.
↓
The unit starts to operate.
↓
The green indicator is on.
After approx. three seconds,
The unit beeps three times and continues to operate.
Hi POWER FILTER
PAP
TIMER
OPERATION
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
RESET
• When the system is operating
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is in operation.
The green indicator is on.
↓
The unit stops operating.
↓
The green indicator is turned off.
After approx. three seconds,
The unit beeps three times.
Hi POWER FILTER
PAP
TIMER
OPERATION
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
RESET
7-7-3. Power Failure During Timer Operation
When the unit is turned off because of power failure
during timer operation, the timer operation is cancelled. In that case, set the timer operation again.
NOTE :
The Everyday Timer is reset while a command signal
can be received from the remote controller even if it
stopped due to a power failure.
- 17 -
FILE NO. SVM-08029
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be at least polychloroprene sheathed flexible
cord (design H07 RN-F), or cord designation 245 IEC66.(Shall be installed in accordance with national
wiring regulations)
CAUTION
To Disconnect the Appliance from the Main Power Supply
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a
contact separation of at least 3 mm in all poles.
If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply socket in order to disconnect the
appliance completely from the mains.
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED
WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS,
FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R22) WITH ANY OTHER GASEOUS
BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE
REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY
HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE
INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS
IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
Also, make sure the equipment is properly earthed.
• Appliance shall be installed in accordance with national wiring regulations.
If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
• Exposure of unit to water or other moisture before installation could result in electric shock.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read this installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
− 18 −
FILE NO. SVM-08029
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier
before installation. If you experience any problems, or if the installation is not accepted by the supplier, the
service agency will take adequate countermeasures.
− 19 −
FILE NO. SVM-08029
170
mm
65 mm or more
8-2. Installation Diagram of Indoor and Outdoor Units
or m
ore
Hook
1 Installation
For the rear left and left piping
plate
Wall
Hoo
k
170
mm
or m
ore
Air
filte
r
Do not allow the drain hose to get
slack.
(A
tta
ch
Insert the cushion between the indoor
unit and wall, and tilt the indoor unit
for better operation.
to
t
he
nt
p
5
Cut the piping
hole sloped
slightly.
Shield pipe
fro
an
el)
Active-CarbonCatechin filter
Make sure to run the drain hose
sloped downward.
3 Batteries
7 Pan head
4 Remote control holder
wood screw
The auxiliary piping can be connected
to the left, rear left, rear right, right,
bottom right or bottom left.
600 mm or more
Vinyl tape
Apply after carrying
out a drainage test.
2 Wireless remote control
100
.
Before installing the
wireless remote control
mm
or
Right
100
mm
or m
Bottom
right
Saddle
mo
re
600
r
mo
re
mo
m
600
With the remote control cover
open, load the batteries supplied
correctly, observing their
polarity.
2
Rear
right
ore
Extension
drain hose
(Not available,
provided by installer)
mm
o
Batteries
Left
Bottom left
Insulate the refrigerant pipes
separately with insulation, not
together.
rm
ore
6 mm thick heat resisting
polyethylene foam
Wireless remote control
3
Rear
left
Remark :
• Detail of accessory and installation parts can
see in the accessory sheet.
− 20 −
FILE NO. SVM-08029
8-3. Installation
8-3-1. Optional installation parts
Part
Code
Parts name
Q'ty
A
Refrigerant piping
Liquid side : Æ 6.35 mm
Gas side : Æ12.70 mm
One
each
B
Pipe insulating material
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
1
One
each
<Fixing bolt arrangement of outdoor unit>
500 mm
Air inlet
53 mm
280 mm
97 mm
Air outlet
Drain outlet
Fig. 8-3-1
· Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
· Use Æ8 mm or Æ10 mm anchor bolts and nuts.
– 21 –
FILE NO. SVM-08029
8-3-2. Accessory and installation parts
Part
No.
Part name (Q’ty)
1
Part
No.
Part name (Q’ty)
4
Installation plate x 1
2
5
3
Active Carbon-Catechin filter x 2
6
Mounting screw ∅ 4 x 25l x 6
Battery x 2
Others
Part name (Q’ty)
7
Remote control holder x 1
Wireless remote control x 1
Part
No.
Name
Owner’s manual
Installation manual
– 22 –
Pan head wood screw
∅3.1 x 16l x 2
FILE NO. SVM-08029
8-4. Indoor Unit
8-4-2. Cutting a hole and mounting installation
8-4-1. Installation place
plate
• A place which provides the spaces around the
indoor unit as shown in the diagram.
<Cutting a hole>
• A place where there is no obstacle near the air inlet
When installing the refrigerant pipes from the rear.
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
• The indoor unit shall be installed as top of the indoor unit
comes to at least 2 m height. Also, it must be avoided to
put anything on the top of the indoor unit.
Pipe
hole
CAUTION
∅65 mm
• Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner’s manual.)
Indoor unit
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
(Side view)
(Top view)
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (∅65 mm) at
a slight downward slant to the outdoor side.
NOTE
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
Anchor bolt holes
62
Hook
82.5
170
Indoor unit
45
°
85
45°
io
n
ra
e
ng
Reception Remote
control
range
pt
ce
Re
°
75
Fig. 8-4-2
Remote
control
Pipe hole
Hook
Indoor unit
Thread
Pipe hole
Weight
6
Fig. 8-4-1
Fig. 8-4-3
− 23 −
1
Hook
Mounting screw
Installation
plate
2 m or more from floor
<Remote control>
100 mm
FILE NO. SVM-08029
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
CAUTION
• This appliance can be connected to the mains in
either of the following two ways.
(1) Connection to fixed wiring:
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporate in the fixed
wiring. An approved circuit breaker or
switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
NOTE
• Ensure all wiring is used within its electrical rating.
Projection
15 mm or less
5 mm dia. hole
Power source
6
Mounting
screw
s
∅4 x 25s
Clip anchor
(local parts)
50Hz, 220 − 240 V Single phase
Maximum
running current
12A
Plug socket &
fuse rating
16A
Power cord
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate 6 mounting
screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
− 24 −
2
1.5 mm or more
FILE NO. SVM-08029
8-4-4. Wiring connection
<How to connect the connecting cable>
Cord clamp
Terminal block
Terminal cover
Wiring of the connecting cable can be carried out
without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
Screw
1
1 2
Connecting
cable
2
Earth line
abou
t 15
cm
Screw
Screw
Connecting cable
Fig. 8-4-5
60 mm
Earth line
10 mm
10 mm
50 mm
Stripping length of the connecting cable
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
Fig. 8-4-6
NOTE
• Use stranded wire only.
• Wire type : H07RN-F or more
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-7
− 25 −
FILE NO. SVM-08029
8-4-5. Piping and drain hose installation
How to fix the drains cap
1) Insert hexagonal wrench (4 mm) in a center
head.
<Piping and drain hose forming>
*
Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
4 mm
Left
Bottom right
Right
Piping preparation
Bottom left
Die-cutting
Front panel slit
Rear left
Changing
drain hose
Rear right
Fig. 8-4-10
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap.
Application causes deterioration
and drain leakage of the plug.
1. Die-cutting Front panel slit
Cut out the slit on the leftward or right side of the front panel
for the left or right connection and the slit on the bottom
left or right side of the front panel for the bottom left or
right connection with a pair of nippers.
2. Changing drain hose
For leftward connection, bottom leftward connection
and rear leftward connection’s piping, it is necessary to
change the drain hose and drain cap.
How to remove the drains cap
Clip drain cap by needle-nose plier, and pull out.
Insert a hexagon
wrench (4 mm)
Fig. 8-4-11
CAUTION
Firmly insert the drain hose and drain cap; otherwise,
water may leak.
<In case of right or left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Fig. 8-4-8
How to install the drain hose
• The drain hose can be removed by take off
screw, after that twisting and pulling.
• When removing the drain hose, be
careful of any sharp edges of steel
plate. The edges can cause injuries.
Heat insulator
Slit
Fig. 8-4-12
<In case of bottom right or bottom left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
Drain hose
Fig. 8-4-13
Fig. 8-4-9
– 26 –
FILE NO. SVM-08029
<Left-hand connection with piping>
8-4-6. Indoor unit fixing
Bend the connecting pipe so that it is laid within 43 mm 1. Pass the pipe through the hole in the wall, and hook
above the wall surface. If the connecting pipe is laid
the indoor unit on the installation plate at the upper
exceeding 43 mm above the wall surface, the indoor
hooks.
unit may unstably be set on the wall. When bending the 2. Swing the indoor unit to right and left to confirm that
connecting pipe, make sure to use a spring bender so
it is firmly hooked up on the installation plate.
as not to crush the pipe.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
Bend the connection pipe within a radius of 30 mm.
indoor unit toward you to confirm that it is firmly
To connect the pipe after installation of the unit (figure)
hooked up on the installation plate.
(To the forefront of flare)
270 mm
230 mm
Hook here
1
Gas side
1 Installation
plate
Liquid side
2
Hook
43 mm
Outward form of indoor unit
Press
(unhook)
R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)
80
Fig. 8-4-15
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
Use the handle of screwdriver, etc.
Fig. 8-4-14
NOTE
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
Push
Fig. 8-4-16
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Push
Connecting cable
Installation plate
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it, not to crush it.
− 27 −
FILE NO. SVM-08029
8-4-7. Drainage
8-5. Outdoor Unit
1. Run the drain hose sloped downwards.
8-5-1. Installation place
NOTE
• Hole should be made at a slight downward slant on
the outdoor side.
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up to
10 m and can be increased until 15 m but need to
extra charge 20 g/m after over 10 m .
• A place where the drain water does not raise any
• A place where the drain water does not raise any
problems.
Do not form the
drain hose into
a wavy shape.
Do not rise the
drain hose.
50 mm
or more
Do not put
the drain
hose end in
the drainage
ditch.
Do not put
the drain
hose end
into water.
Fig. 8-4-17
2. Put water in the drain pan and make sure that the
water is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
Shield pipe
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-18
CAUTION
Arrange the drain pipe for proper drainage from the
unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain
water collected from dew, which forms on the back of
the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts
at a height above the drain guide.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Wall
Strong
wind
Drain guide
Fig. 8-5-1
Space for pipes
Fig. 8-4-19
− 28 −
FILE NO. SVM-08029
8-5-2. Refrigerant piping connection
(Unit : N· m)
1. Cut the pipe with a pipe cutter.
Roughness
Obliquity
90°
Warp
Fig. 8-5-2
Outer dia.
of copper pipe
Tightening torque
∅6.35
16 to 18 (1.6 to 1.8 kgf·m)
∅9.52
30 to 42 (3.0 to 4.2 kgf·m)
∅12.70
50 to 62 (5.0 to 6.2 kgf·m)
• Tightening torque of flare pipe connections
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
Flare at indoor unit side
A
Die
Pipe
Fig. 8-5-3
Outer dia.
of copper pipe
Flare at outdoor unit side
Fig. 8-5-4
A
Rigid
Imperial
∅ 6.35
0.5 to 1.0
1.0 to 1.5
∅ 9.52
0.5 to 1.0
1.0 to 1.5
∅ 12.70
0.5 to 1.0
1.5 to 2.0
Mark line
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
Fig. 8-5-5
Half union
Flare nut
Externally
threaded side
CAUTION
• Do not apply excess torque.
• Otherwise, the nut may crack depending on the
conditions.
Use a wrench to secure.
Internally
threaded side
Use a torque wrench to tighten.
Fig. 8-5-6
CAUTION
• KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
− 29 −
FILE NO. SVM-08029
8-5-3. Evacuating
<Packed valve handling precautions>
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
·
·
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using
a vacuum pump. Do not use the refrigerant in the
outdoor unit.
For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the piping
length is 20 meters. (15 minutes for 20 meters)
(assuming a pump capacity of 27 liters per minute.)
Then confirm that the compound pressure gauge
reading is -101 kPa (76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
Open the valve stem all the way out; but do not try
to open it beyond the stopper.
Securely tighten the valve stem cap with torque in
the following table:
Gas side
( Æ12.70 mm)
50 to 62 N·m
(5.0 to 6.2 kgf·m)
Gas side
(Æ9.52 mm)
30 to 42 N·m
(3.0 to 4.2 kgf·m)
Liquid side
(Æ6.35 mm)
16 to 18 N·m
(1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Pressure gauge
-101 kPa ( 76 cmHg)
Manifold valve
Handle Hi
(Keep full closed)
Handle Lo
Charge hose
Charge hose
Connecting pipe
Vacuum pump
adapter for
counter-flow
prevention
Vacuum
pump
Packed valve at gas side
Service port
(Valve core (Setting pin))
Packed valve at liquid side
Fig. 8-5-7
- 30 -
Hexagonal wrench
is required.
4m
Fig. 8-5-8
m
FILE NO. SVM-08029
8-6. How to Set Remote Control Selector Switch
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
1(L) 2(N)
75 mm
Terminal
screw
Screw
10 mm
65 mm
Earth
line
Connecting
cable
<Remote control selector switch>
• When two indoor units are installed in the same room or
adjacent two rooms, if operating a unit, two units may
receive the remote control signal simultaneously and
operate. In this case, the operation can be preserved
by setting either one indoor unit or remote control to B
setting. (Both are set to A setting in factory shipment.)
• The remote control signal is not received when the
settings of indoor unit and remote control are different.
• There is no relation between A setting/B setting and A
room/B room when connecting the piping and cables.
<Remote control A-B selection>
To separate using of remote control for each indoor unit
in case of 2 air conditioners are installed nearly.
Terminal block
10 mm Earth line
When two indoor units are installed in the seperated rooms.
It is not necessary to change the selector switches.
Cord clamp
Fig. 8-5-9
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc.)
• Every wire must be connected firmly.
Remote Control B Setup.
1. Press RESET button on the indoor unit to turn the air
conditioner ON.
2. Point the remote control at the indoor unit.
3. Push and hold [CHK] button on the Remote Control by
the tip of the pencil. "00" will be shown on the display
4. Press [MODE] during pushing [CHK] . "B" will show on
the display and "00" will disappear and the air conditioner
will turn OFF. The Remote Control B is memorized.
NOTE : 1. Repeat above step to reset Remote
Control to be A.
2. Remote Control A has not "A" display.
3. Default setting of Remote Control from
factory is A.
MODE
AUTO
COOL
NOTE
• Wire type: H07RN-F or 245 IEC66 (2.0 mm2 or
more)
DRY
AUTO FAN
TEMP.
B
TEMP.
– 31 –
FAN
AUTO
QUIET
B
FILE NO. SVM-08029
8-7. Others
8-7-3. Auto restart setting
8-7-1. Gas leak test
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Check places for
the indoor unit.
Valve cover
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
Electric parts cover
<How to set the auto restart>
Fig. 8-7-1
Check places for
the outdoor unit.
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
• Press and hold the RESET button for about
3 seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press RESET
button for 10 sec.
(The beeper will make a short beep.)
Hi POWER FILTER
PAP
TIMER
OPERATION
RESET
Fig. 8-7-2
– 32 –
FILE NO. SVM-08029
9. TROUBLESHOOTING CHART
9-1. Troubleshooting Procedure
9-2-2. Incorrect cable connection between Indoor
and outdoor units
Follow the details of 9-2. Basic Chec k Items .
If there is no trouble corresponding to 9-2, check
whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
The indoor unit is connected to the outdoor unit with
5 cables (Heat pump model) or 3 cables (Cooling Only
model). Check that the indoor and outdoor units have
been properly connected with terminals assigned the
same numbers. If the connectors are not properly
connected, the outdoor unit will not operate normally,
or OPERATION lamp and TIMER lamp will blink (5Hz).
9-2. Basic Check Items
9-2-1. Power supply voltage
The line voltage must be AC 220 − 240V. If it is not
within this range, the air conditioner may not operate
normally.
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1
to control the air conditioner. If there are any operational problems, check whether or not the problems
correspond to Table 9-2-1. If they correspond to the
Table, they are not problems with the air conditioner,
but they are indispensable operations to control and
maintain the air conditioner properly.
Table 9-2-1
No.
Operation of air conditioner
Descriptions
1
When the main power supply is turned on,
the OPERATION lamp on the indoor unit
blinks.
The OPERATION lamp blinks to indicate that power is turned on.
If the [ ] button is pressed, the lamp stops blinking.
2
The indoor fan motor speed does not change
in the Dry operation.
The indoor fan motor speed is automatically controlled in the Dry
operation.
3
The compressor is not turned off even though The compressor has a function that it is not turned off for
the room temperature is in the range that the 3 minutes after it is turned on even though the room temperature
compressor is turned off.
is in the range that the compressor is turned off.
4
The compressor is not turned on and off even In the Dry operation, the compressor is turned on and off
though the thermo control is operated in the
automatically at the regular intervals, independent of the thermo
Dry operation.
control.
5
The compressor is not turned on even though The compressor is not turned on in the restart delay timer
the room temperature is in the range that the (3-minutes timer) operation. It is also not turned on after the power
compressor is turned on.
supply is turned on because of this timer operation.
6
7
The operation mode changes in the
Automatic operation.
In Automatic operation, the room temperature is detected all time
for control fan speed and the operation mode is changed every
15 minutes according to difference between the room temperature
and the preset temperature.
The Fan only operation continues in the
Automatic operation.
When the room temperature is in the range (Preset temperature
± 1°C), the Fan only operation is selected.
− 33 −
FILE NO. SVM-08029
9-3. Primary Judgement
9-3-2. Failure diagnosis
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air outlet of the
indoor heat exchanger by the indoor temperature
sensor
• Temperature setting of the indoor heat exchanger by
the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the outdoor
unit
The indoor unit diagnoses the operation condition and
indicates the information of the self-diagnosis with the
lamps on the display panel of the indoor unit.
Table 9-3-1
Lamps
Self-diagnosis
A
OPERATION lamp is blinking. (1Hz)
Power failure (when the power supply is turning on)
B
OPERATION lamp is blinking. (5Hz)
Thermo sensor (TA) short or break
C
OPERATION lamp is blinking. (5Hz)
Heat exchanger sensor (TC) short or break
D
OPERATION lamp is blinking. (5Hz)
Indoor fan motor lock or failure
E
OPERATION lamp is blinking. (5Hz)
Indoor P.C. board failure
F
OPERATION and TIMER lamps are blinking.
(5Hz)
Wrong wiring of connecting cable
G
OPERATION, TIMER and FAN ONLY
lamps are blinking.
Cycle failure
• Gas shortage or other refrigerant cycle trouble
• Heat exchanger sensor open, break or short
• Overload relay or thermostat trouble of compressor
Table 9-3-2 Diagnosis by detective operation
Symptom
The remote control
does not work.
The outdoor fan
does not rotate.
Check
Primary judgement
Turn off the power supply once, The remote control
then turn it on. Try to operate
still does not work.
the remote control.
The remote control
works.
The indoor unit (and/or remote
control) is/are defective.
The compressor operates.
The outdoor unit (Outdoor fan
motor) is defective.
The compressor does not operate.
An internal part of the
compressor or PCB is defective.
− 34 −
OK.
FILE NO. SVM-08029
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote
control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the
operation condition and indicate the information of
the self-diagnosis on the display of the remote
control with the check codes. If a fault is detected,
all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
(1) Press [CHK] button with a tip of pencil to set the
remote control to the service mode.
• “00” is indicated on the display of the remote
control.
• The timer lamp on the indoor unit blinks
continuously. (5 times per 1 sec.)
(2) Press [8TEMP.] button.
If there is no fault with a code, the indoor unit will
beep once (Pi) and the display of the remote
control will change as follows:
00
01
02 1d
1E
22
• Check the unit with all 35 check codes (00 to 22).
as shown in Table 9-4-1.
• Press [9TEMP.] button to change the check
code backwards.
TEMP.
START/STOP
SWING
FIX
MODE RST CHK
FAN
If there is a fault, the indoor unit will beep for 10
seconds (Pi, Pi, Pi...).
Note the check code on the display of the remote
control.
• 2-digits alphanumeric will be indicated on the
display.
• All lamps on the indoor unit will blink. (5 times
per 1 sec.)
ECO
TIMER
ON
OFF
SET
CLR
• Alphanumeric characters are used for the check code.
is 5.
is A.
is C.
is 6.
is B.
is D.
(3) Press [START/STOP] button to release the service
mode.
• The display of the remote control returns to as it
was before service mode was engaged.
– 35 –
FILE NO. SVM-08029
Table 9-4-1
Block level
Check
code
Block
Indoor
P.C. board
Diagnosis function
Check
code
Air
Conditioner
status
Symptom
Condition
Judgement and action
Thermo. sensor
short/break.
Continued
operation.
Indicated
when detected
abnormal
1.Check thermo sensor.
2.If it is OK, check
P.C. board.
Heat exchanger
sensor
short/break.
Continued
operation.
Indicated
when detected
abnormal
1.Check heat exchanger
sensor.
2.If it is OK, check
P.C. board.
Indoor fan lock,
abnormality of
indoor fan or
thermal fuse break.
All off
Indicated
when detected
abnormal
1.Check heat thermal
fuse is blow or not?
(Terminal block part.)
2.If the thermal fuse is
not blow, check indoor
fan motor.
(Refer to trouble
shooting flow charts.)
Abnormality of other All off
indoor unit P.C.
board.
Indicated
when detected
abnormal
Replace P.C. borad.
Cable
connection/
Thermal
fuse
Refrigerant
system
1) Wrong wiring or All off
disconnection of
connective cable.
2) Terminal fuse cut
off.
Indicated
when detected
abnormal
1.Check connective
cable correct if wiring is
wrong.
2.Check thermal fuse
and Terminal blocks.
3.If it is OK, check
P.C. board.
Other parts
(including
compressor)
1) Overload relay or All off
thermostat for
compressor
break.
Indicated
when detected
abnormal
1.If overload relay and
themostat for compressor are OK, check
refrigerant cycle.
2.If refrigerant cycle is
OK, check P.C. board.
3. If heat exchanger
sensor is OK, check
overload relay and
themostat for
compressor.
Content detected by the check codes "
" t o " " are stored in memory of the microcomputer even if the
power supply is turned off. Therefore, contents of operations in the past are all displayed.
– 36 −
FILE NO. SVM-08029
9-5. Troubleshooting Flowcharts
9-5-1. Power can not be turned on (No operation at all)
<Preliminary checks>
Operation
(1) Is the supply voltage normal?
(2) Is the connection to the AC output OK.?
Check Items
Main cause
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Countermeasure
Symptom
NO
Does the OPERATION
lamp blink?
YES
Does the power turn on
by pushing the [ ]
button of the remote
control?
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
NO
YES
NO
YES
(No problem)
Does the fuse
(F01) blow?
Remote control is
defective.
YES
Parts (R62, R63, R64, C25,
SG01, C27, DB01, IC01,
T01) are defective.
YES
Wrong wiring of
AC cord or connecting
cable is defective.
Replace the remote
control.
NO
Does the thermal
fuse blow?
(Under PF. Terminal)
Replace the
thermal fuse set.
Check connection.
NO
NO
Is the indication voltage
(DC12V or 5V) of main
P.C. board correct?
YES
Does the CN14
connector the wrong
connecting?
Is the voltage
Refer to the paragraph
NO
across C32 measured
"Pre-check", or defective circuit
DC12V ~ 15V?
before power P.C. board block.
NO
P.C. board is
defective.
Replace the main
P.C. board.
YES
Re-wiring the cable.
YES
Is the secondary
voltage of
transformer
measured DC10~16V?
YES
NO
Shut off the power
supply once, and turn
it on again after
disconnecting the motor
connector CN10*.
Is the secondary
voltage of
transformer
measured DC10~16V?
NO
transformer for
power supply is
defective.
Replace the main
P.C. board.
YES
Motor is defective.
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
− 37−
FILE NO. SVM-08029
9-5-2. Power can not be turned on after replacing indoor P.C. board
<Checking Procedure>
Connect the AC
Power supply
Does the OPERATION
lamp blink?
NO
Is it wired as shown
in Figure below?
YES
Return the wiring of the
power relay is returned to
the normal procedure.
NO
YES
To the paragraph of
"No Power turns on".
RY01
Brown
Black
Green/Yellow
White
CN31
Blue
1 2
Indoor Terminal Block
PC Board
WP-018
Green/Yellow
Power Cord
– 38 −
FILE NO. SVM-08029
9-5-3. Outdoor unit does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
Does the OPERATION lamp blink?
NO
See "Power can not be turned on".
YES
Does the power turn on by pushing
the [ ] button of the remote control?
NO
See "Power can not be turned on".
YES
Is AC 220-240V supplied between
terminal block 1 - 2 ?
NO
Relays RY01, Q02 or IC30 is failure.
YES
Is cable connection between indoor
and outdoor units correct?
NO
Correct cabling between indoor
and outdoor units.
YES
Check items as following procedure
in 9-5-4, 9-5-5, 9-5-6
− 39 −
Replace the
P.C. board.
FILE NO. SVM-08029
9-5-4. Only compressor does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
Does the OPERATION lamp blink?
NO
See "Power can not be turned on".
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
NO
See "Power can not be turned on".
YES
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220-240V?
NO
Relays RY01,Q02 or IC30 is failure.
YES
Is cable connection between indoor
and outdoor units correct?
NO
Correct cabling between indoor
and outdoor units.
NO
Cables between indoor and
outdoor units are defective.
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220-240V?
YES
Are all the cords for compressor normal?
NO
Re-wire or replace the defective cords.
YES
Is the compressor motor winding normal?
(Check the winding resistor.)
NO
Compressor is defective.
YES
Is the capacitor for compressor normal.
NO
Capacitor is defective.
YES
Is the overload relay normal?
NO
Overload relay is defective.
YES
Does the compressor start?
NO
Compressor is defective.
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
NO
Gas shortage (Gas leakage)
YES
Compressor is defective
– 40 −
Replace the
P.C. board.
FILE NO. SVM-08029
9-5-5. Only outdoor fan does not operate
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
Does the OPERATION lamp blink?
NO
See "Power can not be turned on".
YES
Does the power turn on by
pushing the [ ] button
of the remote control?
NO
See "Power can not be turned on".
YES
Is the voltage across the indoor terminal
NO
1-2 : AC 220-240V?
Relays (RY01) or IC30 or Q02 is failure.
YES
Is cable connection between indoor
and outdoor units correct?
NO
Correct cabling between indoor
and outdoor units.
NO
Cables between indoor
and outdoor units are defective.
NO
Correct the wire or
replace the defective cords.
YES
Is the voltage across the terminal
1-2 : AC 220-240V?
YES
Are all the cords for outdoor
fan motor normal?
YES
Is the outdoor fan motor winding normal?
(Check the winding resistance)
NO
Outdoor fan motor is defective.
YES
Is the capacitor for compressor normal?
YES
NO
Capacitor for outdoor
fan motor is defective.
Outdoor fan motor is defective.
– 41 −
Replace the
P.C. board.
FILE NO. SVM-08029
9-5-6. Only the indoor fan does not operate
< Check procedure >
Shut off the
power supply once.
Turn the power supply.
Does the fan stop in
no operating status?
NO
Replace the P.C. board.
Control P.C. board is defective.
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
NO
YES
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
NO
YES
YES
Shut off the power supply.
Change the setting of
cooling to hight fan.
Does the cross flow
fan rotate normally?
NO
NO
YES
Repair the
bearing of
the fan.
Thermal fuse operated
due to prevent
temperature rising cause
of incompleted connecting.
Turn on the power supply.
Does the fan speed
become higher?
NO
Motor control circuit failure
(IC30, IC03, Q08, T01) or 12V
power circuit failire.
Operation
stops
YES
Replace the P.C. board.
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
NO
Replace the fan motor
YES
Normal
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Replace the control
P.C. board.
− 42 −
FILE NO. SVM-08029
9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board)
Push the [
There is no been from
the indoor unit.
The operation lamp of
the air conditioner main
unit does not light.
] button.
Does the transmission
indicator blink?
NO
YES
Is there direct
sunlight on the
receptor of the air
conditioner?
Reset the remote control
by use the tip pencil push
in the RESET hole
NO
YES
Is there any
thyristor
fluorescent light
near by?
NO
Is operation
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
air conditioner?
NO
YES
Push the [
button
YES
]
Battery life
NO
Dose the
transmission
indicator light?
Is operation possible
when setting the
temporary switch of the
air conditioner main unit
to "TEST RUN" or
"TEMPORARY AUTO"?
NO
YES
NO
YES
Is there any
beep and
operation?
YES
Can any signal tone
be heard in a trasistor
radio when transmitting
within 5 cm distance
from the radio?
NO
YES
Remote control
is failure.
P.C. board is failure.
Avoid direct
sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
Replace
P.C. board
Replace the
batteries
− 43 −
Normal
Replace remote
control.
FILE NO. SVM-08029
(2) Inspection procedres
1) When a P.C. board is judged to be defective,
(1) Operating precautions
check for disconnection, burning, or discolora1) When removing the front panel or the P.C. board,
tion of the copper foil pattern or this P.C. board.
be sure to shut off the power supply.
2)
The
P.C. board consists of the following 2 parts
2) When removing the P.C. board, hold the edge of
a.
Main
P.C. board part:
the P.C. board and do not apply force to the
power
relay, indoor fan motor drive circuit and
parts.
control
circuit, C.P.U. and peripheral circuits,
3) When connecting or disconnecting the connecbuzzer
drive
circuit and buzzer.
tors on the P.C. board, hold the Whole housing.
b.
Infrared
rays
receive and indication parts:
Do not pull at the lead wire.
Infrared rays receiver unit and LED.
9-6-1 How to check the P.C. board
− 44 −
FILE NO. SVM-08029
(3) Checking procedure
Table 9-6-1
No.
Procedure
Check Point (Symptom)
Causes
1
Shut off the power supply and
remove the P.C. board assembly
from the electronic parts base.
Remove the connecting cable from
the terminal block.
1. Is the fuse blown?
1. • Application of shock voltage.
• Overload by shor t-circuit of the
par ts.
2
Remove the connector for the motor,
and turn the power on.
If the OPERATION lamp blinks
(0.5 sec. : ON, 0.5 sec. : OFF) when
the power turning on, the checking
points described as 1-4 of right
column are not necessary to
perform.
Voltage check
1.Between 3 of RY01 and CN31
(AC 220~240V)
2. Between + and − of C27
(DC 310 ~ 390V)
3. Between 12V and GND
4. Between 5V and GND
1. • A C power cord is defective.
• P oor contact of the terminal plate.
• Miss wiring of the power relay.
2. • Capacitor (C25, C26, C27) is
.
defective.
• Line filter (L01) is defective.
• Diode (DB01) is defective.
3. T01 are detective.
4. IC02 are defective.
3
Make the operation status by
pushing once the [ ]
button, except the status of [FAN
ONLY], [ON TIMER].
Voltage check
1. Voltage of relay coil. (DC 12V)
Between pin 2 of RY01 and GND
2.Between No. 1 and 2 of
connecting cable terminal block.
(AC 220~240V)
1. Breaking wire of the relay coil,
defective relay driver. (Q02)
2. Poor contact of relay.
4
Start the operation with the system
which the time of the restart delay
timer is shortened.
1. All indicators light for 3 sec..
2. Indicators do not indicate normally
after approximate 3 sec..
ective indicator, or poor
} Def
housing assembly. (CN14)
5
Make the operation status by
pressing once the [ ]
button.
1. The time of the restart delay timer
is shortened.
2. Cool operation
3. Air volume [AUTO]
4. Make the setting temperature lower
enough than room temperature.
5. Continuous operation.
1. Compressor does not operate.
2. OPERATION lamp blinks.
1. The temperature of the indoor
heat exchanger is abnor mally
lower.
2. Poor contact of the heat
exchanger sensor. (The connector
is disconnected.) (CN01)
3. Heat exchanger sensor, main
P.C. board are defective. (Refer to
Table 9-6-2 for the judgment of
defective resistance values.)
4. Main P.C. board is defective.
6
Turn the power on after connecting
the motor connector. Start the
operation with the following
condition.
1. Operation [Cooling]
2. Airflow [High fan]
3. Continuous operation
1.Motor does not rotate. (The key
operation is accepted.)
2. The Motor rotates, but it vibrates
too much.
1. Poor contact of the motor
connector.
2. P.C. board is defective.
− 45 −
FILE NO. SVM-08029
Table 9-6-2 Approximate resistance value of thermo sensor
(kΩ)
Temperature
0°C
10°C
20°C
25°C
30°C
Resistance value
33.8
20.35
12.59
10.00
7.99
9-6-2. How to shorten time of restart delay timer
1 Press [CLR] button while pressing [CHK] button
with a tip of a pencil.
2 Then press [ START/STOP] button to transmit the
signal to the indoor unit.
MODE
AUTO
COOL
TEMP.
FAN
AUTO
QUIET
B
DRY
AUTO FAN
Hr.ON
OFF
TEMP.
START/STOP
SWING
FIX
MODE RST CHK
FAN
ECO
[CHK] button
TIMER
ON
OFF
SET
CLR
[CLR] button
9-6-3. How to set/cancel the self cleaning function
The self cleaning function is set from a factory. To cancel this function, should keep press the
[RESET] button for 20 seconds till can hear the long combination sound and repeat the same
procedure when need to set.
− 46 −
FILE NO. SVM-08029
10. HOW TO REPLACE THE MAIN PARTS
WARNING
• Since high voltages pass through the electrical parts, turn off the power without fail before proceeding with
the repairs.
Electric shocks may occur if the power plug is not disconnected.
• After the repairs have been completed (after the front panel and cabinet have been installed), perform a
test run, and check for smoking, unusual sounds and other abnormalities.
If this check is omitted, a fire and/or electric shocks may occur.
Before proceeding with the test run, install the front panel and cabinet.
• Ensure that the following steps are taken when doing repairs on the refrigerating cycle.
1. Do not allow any naked flames in the surrounding area.
If a gas stove or other appliance is being used, extinguish the flames before proceeding.
If the flames are not extinguished, they may ignite any oil mixed with the refrigerant gas.
2. Do not use welding equipment in an airtight room.
Carbon monoxide poisoning may result if the room is not properly ventilated.
3. Do not bring welding equipment near flammable objects.
Flames from the equipment may cause the flammable objects to catch fire.
• If keeping the power on is absolutely unavoidable while doing a job such as inspecting the circuitry, wear rubber gloves to avoid contact with the live parts.
Electric shocks may be received if the live parts are touched.
High-voltage circuits are contained inside this unit.
Proceed very carefully when conducting checks since directly touching the parts on the control circuit
board may result in electric shocks.
10-1. Indoor Unit
No.

Part name
Front panel
Procedures
Remarks
1) Stop operation of the air conditioner and
turn off its main power supply.
2) Open the air inlet grille, push the arm
toward the outside, and remove the grille.
3) Remove the left and right air filters.
– 47 –
FILE NO. SVM-08029
No.

Part name
Front panel
Procedures
Remarks
4) Press "PUSH" part under the front panel
and remove hooks of the front panel from
the installation plate.
Installation plate
Front panel
Press
5) Remove the front panel fixing screws.
(2 pcs.)
6) Take off three hooks of panel from rear
side.
2 Screws
Three hooks
<How to assemble the front panel>
1) Press three center positions and two lower center positions of the air outlet, and
then hang the hanging hooks (3 pcs.) at the top side of the front panel to the rear
plate.
2) Tighten two screws.
• Incomplete hanging or incomplete pressing may cause a dewdrops or generation
of a fluttering sound.
– 48 –
FILE NO. SVM-08029
No.
Part name
‚
Electric parts
box assembly
Procedures
Remarks
1) Follow the procedure up to 3) in  above.
2) Remove screw of earth lead attached to the
end plate of the evaporator.
3) Remove the lead wire cover, and remove
connector for the fan motor and connector for the louver motor from the electric
parts box assembly.
4) Pull out TC sensor from sensor holder of the
evaporator.
5) Disengage the display unit by simply pushing
at the top of the display unit.
Electric part
box cover
TC sensor
Earth Screw
Fan motor
connector
6) Remove the fixing screw that secures the
electric parts box assembly, and remove the
assembly.
Fixing screw
Louver motor
connector
<How to assemble the electric parts box>
1) Hook the top part of the electric parts box
assembly onto the claws on the back body,
and secure it using the fixing screw.
Now attach the display unit. Connect the
connectors for the fan motor and louver motor.
2) Secure the grounding wire using the fixing
screw. Insert the TC sensor into the sensor
holder.
* Be absolutely sure to loop the grounding
wire and TC sensor leads once at the
bottom.
– 49 –
AC fan motor
connector
FILE NO. SVM-08029
Remarks
No.
Part name
Procedures
ƒ
Horizontal louver
1) Remove shaft of the horizontal
louver from the back body.
(First remove the left shaft, and
then remove other shafts while
sliding the horizontal louver
leftward.)
„
Evaporator
(Heat exchanger)
1) Follow to the procedure in the item ‚ .
2) Remove the pipe holder from the rear side of the main unit.
3) Remove two fixing screws at the left side of the end plate of the heat exchanger.
2 screws
4) Remove one fixing screw on the
heat exchage fixing holder to separate the
heat exchage from the back body.
Heat exchanger fixing
holder
Screw
5) Remove right side of the end plate from
two fixing rib while sliding slightly the
heat exchanger rightward.
Rib on the right side of the end plate
– 50 –
FILE NO. SVM-08029
No.
…
Part name
Bearing
Procedures
Remarks
1) Follow to the procedure in the item „.
2) Remove the two screws used to secure the
bearing base.
Two screws
3) Remove the bearing base.
<Caution at assembling>
• If the bearing is out from the housing, push it
into the specified position and then incorporate
it in the main body.
– 51 –
Bearing
Bearing base
FILE NO. SVM-08029
No.
†
Part name
Fan motor
Procedures
Remarks
1) Follow to the procedure till item „.
2) Loosen the set screw of the cross flow fan.
3) Remove two fixing screws of the motor cover
and them remove the motor cover.
4) Remove two more fixing screws of the
motor band and remove the motor band.
Set screw
Motor cover
Two screws on
motor band
Two Screws
5) Pull the fan motor outward.
– 52 –
FILE NO. SVM-08029
No.
Part name
Procedures
Remarks
‡
Cross flow fan
<Caution at reassembling>
1) To incorporate the fan motor, remove the fan
motor rubber (at shaft core side), incorporate
the motor into the position in the following
figure, and then install the fan motor.
• Install the cross flow fan so that the right
end of the 1st joint from the right of the
cross flow fan is set keeping 70.5 mm from
wall of rear plate of the main unit.
• Holding the set screw, install the cross flow
fan so that U-groove of the fan motor comes
to the mounting hole of the set screw.
• Perform positioning of the fan motor as
follows:
• When assembling the fan motor, the fan
motor must be installed in such a way that
the fan motor leads will be taken out is
positioned at the bottom front.
• After assembling the two hooking claws of
the motor band (right) into the main body,
position the fan motor, insert it, and then
secure the motor band (right) using the two
fixing screws.
U groove
– 53 –
5 mm
FILE NO. SVM-08029
10-2
. . Outdoor Unit
No.
1
Part name
Common
procedure
Procedures
1. Detachment
1) Stop operation of the air conditioner, and
turn off the main switch and breaker of the
air conditioner.
2) Remove the valve cover. (ST1T∅4 x 10s
1 pc)
• After removing screw, remove the valve
cover pulling it downward.
3) Remove the wiring cover (ST1T∅4 x 10s 2
pcs.), and then remove the power cord,
connecting cable, and cord clamp
(ST2T∅4 x 16s 3 pcs.).
4) Remove the upper cabinet.
(ST1T∅4 x 10s 5 pcs.)
• After removing screws, remove the
upper cabinet pulling it upward.
2. Attachment
1) Attach the upper cabinet.
(ST1T∅4 x 10s 5 pcs.)
• Hook the rear side of the upper cabinet
to the claw of the rear cabinet, and then
place it on the front cabinet.
2) After connecting the power cord and
connecting cable, attach the cord clamp
and wiring cover.
• Insert the upper part into the upper
cabinet, and insert the claw which has
been hooked to the lower part into the
square hole, and then fix it with screw.
(ST1T∅4 x 10s 1 pc.)
3) Attach the valve cover. (ST1T∅4 x 10s 1 pc.)
• Insert the upper part to the upper
cabinet, set the hook claw of the valve
cover to square holes (at three
positions) of the main unit, and attach it
pushing upward.
2
Front cabinet
1. Detachment
1) Perform work of item 1 of 1.
2) Remove upper screw (ST1T∅4 x 10s 3 pcs.)
of the front cabinet, and lower screws
(ST1T∅4 x 10s 8 pcs.) of the front cabinet.
• Both side of front cabinet envelop the
unit, so remove it by pulling sideward.
2. Attachment
1) Assemble front cabinet to the unit.
2) Attach the removed screws to the original
positions.
– 54 –
Remarks
Upper cabinet
Wiring cover
Valve cover
Upper cabinet
FILE NO. SVM-08029
No.
3
4
Part name
Fan motor
Compressor
Procedures
1) Perform work of item 1 of 1 and 1 of 2.
2) Remove the flange nut fixing the fan motor
and the propeller fan.
• Flange nut is loosened by turning
clockwise.
(To tighten the flange nut, turn counterclockwise.)
3) Remove the propeller fan.
4) Disconnect the connector for the fan motor
from the ASM-E-PARTS.
5) Remove the fixing screws (4 pcs.) holding
the fan motor by hand so that it does not
fall.
1) Perform work of item 1 of 1,
1 of 2, 3
2) Extract refrigerant gas.
3) Remove the partition board.
(ST1T∅4 x 10s 3 pcs.)
4) Remove the sound-insulation material.
5) Remove the terminal cover of the
compressor, and disconnect the lead wire
of the compressor thermo and the
compressor from the terminal.
6) Remove the pipe connected to the
compressor with a burner.
• Make sure the flame does not touch the
4 way valve.
7) Remove the fixing screw of the base plate
and heat exchanger.
(ST1T∅4 x 10s 2 pcs.)
8) Pull upward the refrigeration cycle.
9) Remove the nut fixing the compressor to
the base plate.
– 55 –
Remarks
Fan motor
Propeller fan
Flange nut
Compressor
FILE NO. SVM-08029
No.
5
Part name
Fan guard
Procedures
Remarks
1. Detachment
1) Perform work of item 1 of 1 and 1 of 2.
Requirement:
Perform the work on a corrugated
cardboard, cloth, etc. to prevent
scratches to the product.
2) Remove the front cabinet, and place it
down so that the fan guard side faces
downwards.
3) Remove the hooking claws by pushing a
minus screwdriver according to the arrow
mark in the right figure, and remove the
fan guard.
Minus screwdriver
Hooking claw
2. Attachment
1) Insert the claws of the fan guard in the
hole of the front cabinet. Push the hooking
claws (8 positions) by your hand and fix
the claws.
Requirement:
This completes all the attaching
work. Check that all the hooking
claws are fixed to the specified
positions.
6
Capacitor for
compressor
1) Perform the common procedure 1.
2) Remove the fixing screw and the capacitor
band.
( 1-Screw ∅4 x 10s)
3) Disconnect the lead wires.
Capacitor for
compressor
Capacitor band
Screws
∅4 x 10s
Capacitor
for fan motor
7
Capacitor for
fan motor
1) Perform the common procedure 1.
2) Remove the fixing screw and the capacitor
band.
( 1-Screw ∅4 x 10s)
3) Disconnect the lead wires.
– 56 –
Screws
∅4 x 10s
FILE NO. SVM-08029
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
407
411
406
403
404
402
Location
No.
Part
No.
402
403
404
405
43T60383
43T69004
43T69005
43T69641
410
Description
405
Location
No.
Part
No.
406
407
410
411
43T69364
43T60366
43T62003
43T69740
TERMINAL
SENSOR;HEAT EXCHANGER
SENSOR;THERMOSTAT
PC BOARD ASSY; WRS-LED
- 57 -
Description
FUSE,TEMPERATURE
POWER CORD
CORD CLAMP
ASM-PCB-SERV
FILE NO. SVM-08029
11-2. Indoor Unit
206
219
209
214
211
203
204
213
212
205
221
215
218
208
223
202
216
217
224
201
Electric Parts Assembly
222
226
207
227
Location
No.
Part
No.
Description
201
202
203
204
205
206
207
208
209
211
212
213
214
43T21397
43T21393
43T22312
43T70313
43T20325
43T49010
43T63002
43T60382
43T82310
43T19333
43T09408
43T03362
43T39327
LOUVER MOTOR
FAN MOTOR
MOLD BEARING ASSEMBLY
DRAIN HOSE
CROSS FLOW FAN ASSEMBLY
PIPE SHIELD
REMOTE CONTROL HOLDER
MOTOR CORD
INSTALLATION PLATE
SENSOR FIX PLATE
PIPE HOLDER
BACK BODY ASSEMBLY
BEARING BASE
Location
No.
Part
No.
Description
215
216
217
218
219
221
222
223
224
226
227
43T39328
43T39329
43T09409
43T79313
43T44406
43T00493
43T80318
43T80319
43T09416
43T62328
43T69437
MOTOR BAND (LEFT)
MOTOR BAND (RIGHT)
HORIZONTAL LOUVER
DRAIN CAP
REFRIGERANT CYCLE ASSEMBLY
PANEL SERVICE ASSEMBLY
AIR FILTER (R)
AIR FILTER (L)
GRILLE OF AIR INLET
TERMINAL COVER
WIRELESS REMOTE CONTROL
- 58 -
FILE NO. SVM-08029
11-3. Outdoor Unit
27
29
28
26
Location
No.
Part
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
43T42335
43T41410
43T49327
43T97001
43T43406
43T00448
43T46332
43T46019
43T47331
43T47333
43T47014
43T00487
43T21361
43T20324
43T47001
Description
BASE PLATE ASSEMBLY
COMPRESSOR
CUSHION,RUBBER
NUT
CONDENSER ASSEMBLY
FIXING PLATE VALVE
VALVE;PACKED 6.35 DIA
VALVE,PACKED 12.7 DIA
BONNET, 6.35 DIA
BONNET, 12.70 DIA
CAPILLARY TUBE; 1.7DIA
FRONT CABINET
FAN-MOTOR
PROPELLER FAN
NUT FLANGE
Location
No.
Part
No.
Description
16
17
18
19
20
21
22
23
24
25
26
27
28
29
43T19335
43T04304
43T39326
43T39325
43T19337
43T00481
43T96305
43T62323
43T19336
43T54301
43T61310
43T55337
43T55325
43T60367
FAN GUARD
PARTITION
MOTOR BASE CONNECTION PLATE
MOTOR BASE
PACKED VALVE COVER
UPPER CABINET
BUSHING
TERMINAL COVER
FIN GUARD
RELAY;OVERLOAD
ELECTRIC PARTS BASE
MF CAPACITOR
CAPACITOR; PLASTIC-FILM
TERMINAL-2P
- 59 -
FILE NO. SVM-03004(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000, THAILAND.
– 75 –