Download MCW - MCR - galletti

Transcript
I
MANUALE TECNICO
MCW - MCR
UNITÀ ACQUA-ACQUA E MOTOEVAPORANTI
5 kW - 39 kW
MCW - MCR
1
INDICE
1
LA SERIE ............................................................................................... 2
2
DESCRIZIONE DELL'UNITÀ .................................................................... 3
3
CARATTERISTICHE COSTRUTTIVE ...................................................... 3-4
4
MCW MODELLI E CONFIGURAZIONI ..................................................... 5
5
MCR MODELLI E CONFIGURAZIONI ....................................................... 6
6
MCW C DATI TECNICI NOMINALI .......................................................... 7
7
MCW H DATI TECNICI NOMINALI ......................................................... 8
8
MCR C DATI TECNICI NOMINALI ........................................................... 9
9
MCW C RESE RAFFREDDAMENTO ........................................................ 1 0
1 0 MCW H RESE RAFFREDDAMENTO ....................................................... 1 1
1 1 MCW H RESE RISCALDAMENTO .......................................................... 1 2
1 2 MCR C RESE RAFFREDDAMENTO ......................................................... 1 3
1 3 LIMITI DI FUNZIONAMENTO ................................................................ 1 4
13.1 LIMITI DI FUNZIONAMENTO MCW .......................................................... 14
13.2 LIMITI DI FUNZIONAMENTO MCR ........................................................... 14
1 4 FATTORI DI CALCOLO ........................................................................... 1 5
1 5 PREVALENZA UTILE POMPE ................................................................ 1 5
1 6 PERDITE DI CARICO LATO ACQUA ....................................................... 1 6
1 7 CIRCUITO IDRAULICO LATO UTENTE ................................................... 1 7
1 8 DIMENSIONI DI INGOMBRO MCW ................................................... 18-19
1 9 DIMENSIONI DI INGOMBRO MCR ..................................................... 20-21
2 0 DRY COOLER ........................................................................................ 2 2
20.1 TABELLA ABBINAMENTO DRY COOLER ................................................. 22
2 1 CONDENSATORE REMOTO .................................................................... 2 2
21.1 TABELLA ABBINAMENTO CONDENSATORI REMOTI ............................... 22
21.2 DIMENSIONAMENTO DELLE LINEE FRIGORIFERE .................................... 23
21.3 CARATTERISTICHE TUBO REFRIGERANTE ............................................. 23
21.4 ESEMPI DI COLLEGAMENTO .................................................................. 24
21.4.1Condensatore remoto a monte della motoevaporante ........................... 24
21.4.2Condensatore remoto a valle della motoevaporante .............................. 25
2 2 POSIZIONAMENTO E SPAZI DI INSTALLAZIONE .................................. 2 6
LA SERIE
I refrigeratori, le pompe di calore e le unità motoevaporanti della serie MCW
ed MCR sono concepiti per impieghi in ambito residenziale e commerciale
leggero, con possibili applicazioni anche al settore industriale 24 h/day.
I refrigeratori MCW sono sviluppati in esecuzione completamente carenata
che, grazie anche all’esclusiva adozione dei compressori di tipo scroll,
conferisce all’assieme un’eccezionale silenziosità.
L’ingombro contenuto, l’idraulica preassemblata ed il design gradevole, ne
consentono l’installazione in ambienti non dedicati senza particolari
precauzioni d’uso.
La filosofia di progetto ha favorito lo sviluppo di unità d’altezza contenuta con
connessioni idrauliche o frigorifere (MCR) dall’alto e piping preassemblato
che riducono i tempi ed i costi dell’installazione, oltre che lo spazio tecnico
occupato.
L’ampia possibilità di configurazioni, sia in termini di numero di taglie presenti
nella gamma, sia in termini di accessoriabilità rende la serie MCW il prodotto
ideale per la riduzione dei tempi d’installazione in cantiere.
L’utilizzo esclusivo di componenti di assoluta qualità nelle componenti
frigorifere, idrauliche, elettriche rende le unità MCW dei refrigeratori allo stato
dell’arte in termini d’efficienza, affidabilità e potenza sonora emessa.
Tutte le unità sono in esecuzione monocircuito.
Derivate dalla gamma di refrigeratori condensati ad acqua MCW le motoevaporanti
MCR vengono proposte in esecuzione standard e silenziata per funzionamento
di solo raffreddamento.
Fra le numerose opzioni che completano la macchina sono disponibili
condensatori remoti con ventilatori assiali, a flusso d’aria verticale o
orizzontale, in versione standard e silenziata e la possibilità di recupero
calore (desurriscaldatore 40%).
DICHIARAZIONE DI CONFORMITÀ
La Società Galletti S.p.A. con sede in Via Romagnoli 12/a Bentivoglio (Bologna)
Italia, dichiara, sotto la propria responsabilità, che i refrigeratori d'acqua e pompe
di calore delle serie: (vedi tabella sotto) apparecchi per impianti di condizionamento
dell'aria destinati ad applicazioni per il condizionamento in ambito civile, sono
conformi a quanto prescritto dalle Direttive: 2006/42/CE, 2004/108/CE, 2006/
95/CE, 97/23/CE (PED).
Tali apparecchi, che operano con fluidi del gruppo 2, secondo 97/23/CE, sono il
risultato dell'assemblaggio di componenti [compressori, scambiatori di calore a
piastre saldobrasate, ricevitori di liquido, tubazioni, valvole di regolazione e di
sicurezza] singolarmente dotati, quando previsto, di certificazione ai sensi delle
direttive vigenti: la determinazione della categoria d'appartenenza delle macchine
è il frutto dell'analisi dei componenti soggetti alla PED e corrisponde alla categoria
più alta fra i componenti utilizzati.
Per ogni serie di macchine, la conformità dell'assieme è stata valutata da
organismi notificati ed in applicazione delle procedure di valutazione (moduli) ai
sensi dell'allegato II della direttiva 97/23/CE PED, come riportato nella tabella
seguente:
Bentivoglio li, 20/06/2013
Serie
Range
MCC - MCC H
MCC - MCC H
MCW - MCW / H
MCW - MCW / H
MPE - MPEH MCE - MCEH
MPE - MPEH MCE - MCEH
MPE - MPEH MCE - MCEH
MPE - MPEH MCE - MCEH
MPE - MPEH
MPI
MPI
MPI DC
MPI DC
Grandezza
Size
6 - 7 - 9 - 12 - 15
18 - 22 - 25 - 33 - 37
5 - 7 - 10 - 12 - 15
18 - 20 - 22 - 27 - 31 - 39
4- 5- 7- 8
9 - 10 - 11 - 13 - 15 - 18
19-20-21-23-24-26-27-28-31-32-34-35-39-40
T30 - T34 - T40 - T45
54 - 66
15
27
8 - 10 - 14 - 15 - 18
23 - 27 - 29
MFE
MXE - MXE E
MXE - MXE E
MCP
MCP
5 - 6 - 8 - 12 -13 - 16 - 17 - 20 - 23
9 - 11 - 14 - 16
19 - 21
7- 9
10-13-15-18-27-32-40-T18-T22-T24-T30
42 - 52 - 62 - 72 - 82
91/2/4 - 101/2/4 - 121/2/4
141/2/4 - 161/2/4 - 174 - 194 - 214
41-42-51-52-61-62-71-72-81-82-91-92-111-112131-132-141-142-144-161-162-164-181-182
LCE - LCE H
LEW
CAMPO D'APPLICAZIONE
Le unità MCW-MCR sono destinate al raffreddamento-riscaldamento
di acqua e soluzioni glicolate fino ad un massimo del 30% in peso, in
applicazioni nell'ambito del condizionamento civile, industriale e
tecnologico.
Nel caso di edifici di grande superficie è possibile realizzare la
climatizzazione mano a mano che si procede con la vendita/affitto dei
piani/zone mediante l'installazione di una unità MCW-MCR per ogni
piano in locale tecnico di ridotte dimensioni e diluendo così
l'investimento nel tempo. La possibilità di mantenere all'interno
l'evaporatore consente di non glicolare l'acqua dell'impianto ed inoltre
consente di mantenere in un locale facilmente accessibile tutti i
componenti destinati alla manutenzione ordinaria e non.
Organismo Notificato
Notified body
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
0425
N° certificato
certificate
Procedura di valutazione di conformità
Conformity Compliance Module
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Modulo D1
Categoria PED
PED category
0425
Modulo D1
II
CE + PED
0425
Modulo D1
II
CE + PED
2422/0
Galletti S.p.A.
Luca Galletti
I refrigeratori d'acqua e le pompe di calore sono conformi alla direttiva 97/23/CE
(PED) attraverso modulo D1, approvato dall'ente terzo notificato ICIM N°0425.
RG66001006 - Rev.04
2
È severamente vietata la riproduzione anche parziale di questo manuale
I
II
I
II
I
I
II
II
II
I
II
I
II
I
I
II
I
II
Marcatura
Marking
CE
CE + PED
CE
CE + PED
CE
CE
CE + PED
CE + PED
CE + PED
CE
CE + PED
CE
CE + PED
CE
CE
CE + PED
CE
CE + PED
MCW - MCR
2
DESCRIZIONE UNITÀ
3
A-
Quadro elettrico realizzato e cablato in accordo alla direttiva CEE 72/
23, alla direttiva 89/336 sulla compatibilità elettromagnetica ed alle
norme ad essa collegabili
Tutte le macchine hanno connessioni idrauliche verso l’alto,
contribuendo così ad una notevole limitazione degli spazi tecnici
necessari all’installazione ed alla manutenzione. E’ presente a
richiesta un dispositivo di controllo del flusso dell’acqua. in aggiunta
a tale dispositivo è predisposta una sonda di temperatura acqua in
uscita con funzione di termostato antigelo.
Sono utilizzati solo scambiatori a piastre saldobrasate realizzate in
acciaio inox.
Controllo a microprocessore; la versione Base, presente sulle
macchine standard, è costituita dal controllo Chiller.
Basamento portante in lamiera zincata verniciata. La pannellatura
perimetrale realizzata in lamiera zincata verniciata a forno con polveri
epossipoliesteri (RAL 7035) contribuisce ad una estetica gradevole
adatta ad installazioni anche in ambienti residenziali
A richiesta è possibile dotare le unità di elettropompa e serbatoio di
accumulo incorporati alla macchina; quest’ultimo è posto sulla
mandata del circuito idraulico.
Sulle unità MCW - MCR sono utilizzati solo compressori di tipo Scroll.
STRUTTURA
La serie MCW - MCR è realizzata con basamento portante in lamiera zincata
verniciata a polveri epossipoliestere polimerizzate in forno a 180oC e
pannellatura perimetrale realizzata in Peraluman (lega alluminio / magnesio
5005) per un’efficace protezione contro gli agenti corrosivi.
L’Unità è completamente chiusa, ma accessibile su 3 lati con pannelli
facilmente rimovibili per semplificare al massimo tutte le operazioni di
manutenzione e/o controllo; tutta la manutenzione ordinaria è realizzabile dal
fronte della macchina.
Per il sollevamento dell’unità sono previsti dei fori ø 50 mm sul basamento
in cui infilare i tubi di sollevamento e da cui avere accesso al fissaggio dei
piedini antivibranti, che in ogni caso, visto l’utilizzo esclusivo di compressori
Scroll, non sono indispensabili.
Tutte le viterie ed i sistemi di fissaggio sono realizzati in materiali INOX non
ossidabili, oppure in acciai al carbonio con trattamenti superficiali di
passivazione.
B-
CDE-
F-
G-
A
C
CARATTERISTICHE COSTRUTTIVE
CIRCUITO FRIGORIFERO
Il circuito frigorifero è realizzato impiegando esclusivamente componenti di
primaria marca e operatori qualificati ai sensi della Direttiva 97/23 per tutte
le operazioni di brasatura.
Tutte le macchine sono monocircuito.
B
COMPRESSORI
Sulle unità sono utilizzati solo compressori di tipo scroll, con protezione
termica sugli avvolgimenti e riscaldatore elettrico del carter (pompa di calore)
COMPONENTI FRIGORIFERI
- Filtro deidratare a setaccio molecolare.
- Spia di flusso con indicatore di umidità.
- Valvola termostatica con equalizzazione esterna e funzione MOP integrata.
- Valvola di espansione elettrica a controllo elettronico per l’ottimizzazione
energetica nelle medie stagioni (accessorio).
- Valvola inversione di ciclo (solo pompe di calore).
- Valvole unidirezionali (solo pompa di calore).
- Ricevitore di liquido (solo pompe di calore).
- Pressostati alta e bassa pressione.
- Valvoline schrader per controllo e/o manutenzione.
D
SCAMBIATORI DI CALORE LATO ACQUA
Sono utilizzati solo scambiatori a piastre saldobrasate realizzate in acciaio
inox austenitico AISI 304 con connessioni in AISI 304 L caratterizzato da un
ridotto tenore di carbonio per facilitare le operazioni di brasatura.
G
F
CONDENSATORE REMOTO - OPTIONAL (SOLO PER LE UNITÀ MCR)
Realizzato nella geometria 25x21.65 con tubo da 3/8”, è costituito da alette
in alluminio spessore 0,10 mm e tubi di rame mandrinati sulle medesime per
garantire il completo contatto. Sono disponibili esecuzioni silenziate per tale
componente ed anche l’opzione del controllo di condensazione mediante
regolazione della velocità dei ventilatori.
Il dispositivo di controllo di condensazione (optional) è parte integrante del
condensatore remoto e non richiede, ad esclusione delle versioni in pompa
di calore, collegamenti elettrici con la motoevaporante.
Gli scambiatori a pacco alettato sono realizzati con tecnologie di scambio
avanzate, alette louvered e tubi rigati internamente, per la riduzione dei volumi
e quindi delle cariche di refrigerante.
E
SEZIONE AERAULICA - OPTIONAL (CONDENSATORI REMOTI E DRY COOLER)
I ventilatori adottati sono di tipo assiale con pale a profilo alare. I ventilatori
sono bilanciati staticamente e dinamicamente su due piani, dotati di griglia
di protezione conforme alle EN 60335 - DIN31001-1-2 e montati con
interposizione di gommini antivibranti per ridurre la propagazione di vibrazioni
durante le fasi di modulazione di velocità (optional).
Per contattare l'azienda, per qualsiasi informazione o segnalazione: [email protected]
Per conoscere il peso di ciascuna unità, fare riferimento alla tabella del paragrafo
dati tecnici nominali.
I dati tecnici e dimensionali riportati nella presente documentazione possono
subire variazioni orientate al miglioramento del prodotto.
3
È severamente vietata la riproduzione anche parziale di questo manuale
RG66001006 - Rev.04
MCW - MCR
3
CARATTERISTICHE COSTRUTTIVE
QUADRO ELETTRICO
Realizzato e cablato in accordo alla direttiva CEE 73/23, alla direttiva 89/336
sulla compatibilità elettromagnetica ed alle norme ad essa collegabili.
L’accesso al quadro è possibile previa rimozione del pannello esterno e
l’accesso ai componenti è poi condizionato alla disconnessone dell’unità
dalla rete elettrica mediante il sezionatore generale con funzioni di bloccoporta.
Tutti comandi remoti sono realizzati con segnali a 24 V alimentati da un
trasformatore d’isolamento posizionato nel quadro elettrico.
Tutte le utenze sono protette contro il sovraccarico e contro il cortocircuito,
dotate di protezione termica assolta da catene di termistori annegati negli
avvolgimenti di ciascun motore elettrico.
Su tutte le macchine è montato di serie il relè sequenza fasi che inibisce il
funzionamento del compressore qualora la sequenza delle fasi non sia
rispettata.
Il grado di protezione della macchina è IP 44 ed il quadro con pannello aperto
mantiene un grado di protezione IP20.
In morsettiera sono presenti morsetti per la segnalazione remota di:
- unità accesa/spenta (lampada a 24 V)
- situazione di allarme (lampada a 24 V).
MICROPROCESSORE DI CONTROLLO
I refrigeratori d'acqua e le pompe di calore MCW - MCR sono completi di
controllo a microprocessore:
- controllo dei diversi parametri operativi mediante la tastiera predisposta
sul quadro elettrico;
- inserimento e disinserimento compressori per mantenere il set point
impostato della temperatura acqua in ingresso allo scambiatore acqua/
refrigerante;
- visualizzazione dei parametri di funzionamento;
- gestione e segnalazione di allarmi
- alta / bassa pressione
- antigelo
- flussostato
- allarme pompa
- gestione numero massimo avviamenti compressore;
- conta-ore di funzionamento compressore;
- gestione uscita seriale RS232, RS485 disponibile su richiesta.
RG66001006 - Rev.04
4
È severamente vietata la riproduzione anche parziale di questo manuale
MCW - MCR
4
MODELLI E CONFIGURAZIONI MCW
La serie MCW è composta da 11 modelli, realizzati sia nella versione solo
raffreddamento sia nella versione in pompa di calore.
Le numerose opzioni costruttive sono selezionabili utilizzando il configuratore
ripostato di seguito.
N.B. La scelta di alcune opzioni può impedire la scelta di altre o rendere
obbligatori altri campi. Contattare la Galletti S.p.A per verifica
CODICE
CONFIGURAZIONI / ALLESTIMENTI MACCHINA
15 campi che personalizzano l’unità alle esigenze del cliente:
MCW
005
Campo Carat. Descrizione
1
Refrigerante / Alimentazione elettrica
0
R407C - 230/1/50
1
R407C - 400/3/50 + N
2
R407C- 400/3/50 con trasformatore 230V per ausiliari
2
Microprocessore / valvola espansione
0
base (Chiller) + valvola tradizionale
A
base (Chiller) + valvola elettronica
3
Controllo di condensazione
0
assente
C
modulante-pressostatico con variazione della portata acqua
4
Pompa e serbatoio
0
assente
1
solo pompa
2
pompa più serbaotio
5
Comunicazione remota
0
assente
2
RS485
6
Accessori frigoriferi
0
assente
M
Manometri
7
Opzioni compressore
0
assente
8
Condensatore ad acqua
T
condensatore maggiorato per abbinamento torre/dry
cooler
9
Pannello di comando remoto
0
assente
S
semplificato *
M
a microprocessore
10
Imballo
0
standard
1
gabbia di legno
2
cassa di legno
11
Antivibranti
0
assenti
G
antivibranti di base in gomma
12
Accessori
0
Nessun accessorio
13
Dry cooler / condensatore remoto
0
Assente
A
Dry Cooler
B
Dry Cooler con controllo condensazione
C
Condensatore Remoto
D
Condensatore Remoto con controllo condensazione
14
Dry cooler / condensatore remoto
0
assente
1
standard flusso aria orizzontale
2
standard flusso aria verticale
3
silenziato flusso aria orizzontale
4
silenziato flusso aria verticale
15
Esecuzione
0
standard
S
speciale
Nome commerciale della serie
Refrigeratori d’acqua condensati ad acqua e pompe ei calore acquaacqua reversibili
Modello
Fornisce indicazioni di massima sulla resa in raffreddamento
dei modelli standard
007
010
012
015
018
020
022
027
031
039
Funzionamento
C
H
refrigeratore
pompa di calore
S
L
standard
silenziata
Versione
*
5
In scatola Gewiss con indicatore luminoso di ON, allarme debole (es.
una pompa rotta), allarme grave (es. macchina ferma) e commutatore
ON-OFF. Tutto a 24 Vac sotto trasformatore d’isolamento
È severamente vietata la riproduzione anche parziale di questo manuale
RG66001006 - Rev.04
MCW - MCR
5
MODELLI E CONFIGURAZIONI MCR
La serie MCR è composta da 11 modelli, realizzati nella versione solo
raffreddamento.
Le numerose opzioni costruttive sono selezionabili utilizzando il configuratore
ripostato di seguito.
N.B. La scelta di alcune opzioni può impedire la scelta di altre o rendere
obbligatori altri campi. Contattare la Galletti S.p.A per verifica
Codice
Configurazioni / allestimenti macchina
15 campi che personalizzano l’unità alle esigenze del cliente:
MCR
005
007
010
012
015
018
020
022
027
031
039
Nome commerciale della serie
Refrigeratori d’acqua condensati ad acqua e pompe ei calore acquaacqua reversibili
Modello
Fornisce indicazioni di massima sulla resa in raffreddamento dei
modelli standard
C
refrigeratore
S
L
standard
silenziata
Campo Carat. Descrizione
1
Refrigerante / Alimentazione elettrica
0
R407C - 230/1/50
1
R407C - 400/3/50 + N
2
R407C- 400/3/50 con trasformatore 230V per ausiliari
2
Microprocessore / valvola espansione
0
base (Chiller) + valvola tradizionale
A
base (Chiller) + valvola elettronica
3
Controllo di condensazione
0
assente
4
Pompa e serbatoio
0
assente
1
solo pompa
2
pompa più serbaotio
5
Comunicazione remota
0
assente
2
RS485
6
Accessori frigoriferi
0
assente
M
Manometri
7
Opzioni compressore
0
Assenti
8
Condensatore ad acqua
0
assente
9
Pannello di comando remoto
0
assente
S
semplificato *
M
a microprocessore
10
Imballo
0
standard
1
gabbia di legno
2
cassa di legno
11
Antivibranti
0
assenti
G
antivibranti di base in gomma
12
Accessori
0
Nessun accessorio
13
Dry cooler / condensatore remoto
0
Assente
A
Dry Cooler
B
Dry Cooler con controllo condensazione
C
Condensatore Remoto
D
Condensatore Remoto con controllo condensazione
14
Dry cooler / condensatore remoto
0
assente
1
standard flusso aria orizzontale
2
standard flusso aria verticale
3
silenziato flusso aria orizzontale
4
silenziato flusso aria verticale
15
Esecuzione
0
standard
S
speciale
Funzionamento
Versione
*
RG66001006 - Rev.04
In scatola Gewiss con indicatore luminoso di ON, allarme debole (es.
una pompa rotta), allarme grave (es. macchina ferma) e commutatore
ON-OFF. Tutto a 24 Vac sotto trasformatore d’isolamento
6
È severamente vietata la riproduzione anche parziale di questo manuale
MCW - MCR
6
DATI TECNICI NOMINALI MCW-C Refrigeratori d'acqua
MCW - CS / CL
005 M
005
007 M
007
010 M
5,55
230-1-50
1,32
6,26
12
47
954
28
390
4
1/1
1
1
2,1
77
0,25
47
1"
830
705
453
103
138
55
47
53
45
5,5
400-3-50 + N
1,3
3,17
4,2
24
946
27
386
4
1/1
1
1
2,1
78
0,25
47
1"
830
705
453
103
138
55
47
53
45
7,04
230-1-50
1,74
8,27
15
61
1211
31
498
6
1/1
1
1
2,1
68
0,25
47
1"
830
705
453
106
141
55
47
53
45
7
400-3-50 + N
1,7
3,47
5,1
32
1203
31
494
6
1/1
1
1
2,1
69
0,25
47
1"
830
705
453
106
141
55
47
53
45
9,9
230-1-50
2,34
11,21
23,1
100
1703
27
695
5
1/1
1
1
2,6
60
0,25
47
1"
830
705
453
108
143
59
51
57
49
MCW - CS / CL
015
018
020
022
027
031
039
Potenza frigorifera resa
kW
Alimentazione elettrica
V - ph - Hz
Potenza nominale assorbita
kW
Corrente nominale assorbita
A
Corrente massima assorbita
A
Corrente di spunto
A
Portata d’acqua evaporatore
l/h
Perdite di carico lato evaporatore
kPa
Portata d’acqua condensatore
l/h
Perdite di carico condensatore
kPa
Compressori scroll / circuiti frigoriferi
Nr.
Evaporatore a piastre
Nr.
Condensatore a piastre
Nr.
Contenuto d’acqua circuito utilizzatore dm3
Prevalenza utile pompa (opzione)
kPa
Potenza elettrica pompa (opzione)
kW
Capacità serbatoio accumulo (opzione dm3
Connessioni idrauliche tipo GAS
Dimensioni: altezza
mm
Dimensioni: lunghezza
mm
Dimensioni: profondità
mm
Peso unità standard
kg
Peso unità con pompa e serbatoio
kg
MCW-CS: Livello potenza sonora
dB(A)
MCW-CS: Livello pressione sonora
dB(A)
MCW-CL: Livello potenza sonora
dB(A)
MCW-CL: Livello pressione sonora
dB(A)
14,9
17,8
20,2
26,9
31,2
38,7
3,4
8,58
13
66
2562
27
1039
4
1/1
1
1
3,1
113
0,33
92
1" 1/2
1270
812
508
121
171
61
53
59
51
3,95
9,39
14
74
3062
30
1235
6
1/1
1
1
3,1
92
0,33
92
1" 1/2
1270
812
508
125
175
61
53
59
51
4,4
11,22
16
101
3458
26
1392
5
1/1
1
1
3,6
135
0,45
92
1" 1/2
1270
812
508
167
217
61
53
60
52
21,9
400-3-50 + N
4,9
12,04
17
98
3766
29
1522
6
1/1
1
1
3,6
125
0,45
92
1" 1/2
1270
812
508
203
253
62
54
60
52
6,3
15,56
20
130
4627
26
1885
5
1/1
1
1
3,9
106
0,45
92
1" 1/2
1270
812
508
210
260
62
54
60
52
7,2
18,12
29
130
5367
29
2181
7
1/1
1
1
4,3
82
0,45
92
1" 1/2
1270
812
508
219
269
65
57
63
55
8,9
21,1
32
135
6656
28
2703
7
1/1
1
1
4,6
129
0,75
92
1" 1/2
1270
812
508
233
283
65
57
63
55
Potenza frigorifera resa
kW
Alimentazione elettrica
V - ph - Hz
Potenza nominale assorbita
kW
Corrente nominale assorbita
A
Corrente massima assorbita
A
Corrente di spunto
A
Portata d’acqua evaporatore
l/h
Perdite di carico lato evaporatore
kPa
Portata d’acqua condensatore
l/h
Perdite di carico condensatore
kPa
Compressori scroll / circuiti frigoriferi
Nr.
Evaporatore a piastre
Nr.
Condensatore a piastre
Nr.
Contenuto d’acqua circuito utilizzatore dm3
Prevalenza utile pompa (opzione)
kPa
Potenza elettrica pompa (opzione)
kW
Capacità serbatoio accumulo (opzione dm3
Connessioni idrauliche tipo GAS
Dimensioni: altezza
mm
Dimensioni: lunghezza
mm
Dimensioni: profondità
mm
Peso unità standard
kg
Peso unità con pompa e serbatoio
kg
MCW-CS: Livello potenza sonora
dB(A)
MCW-CS: Livello pressione sonora
dB(A)
MCW-CL: Livello potenza sonora
dB(A)
MCW-CL: Livello pressione sonora
dB(A)
- Potenza raffreddamento: temperatura acqua all'evaporatore 12/ 7°C, temperatura al condensatore 15/30°C.
- Potenza sonora rilevata secondo le norme ISO 3741 - ISO 3744 e EN 29614-1
- Pressione sonora riferita alle seguenti condizioni: in campo libero, distanza 1 metro, fattore di direzionalità pari a 2.
7
È severamente vietata la riproduzione anche parziale di questo manuale
010
012
9,9
12,2
400-3-50 + N 400-3-50 + N
2,3
2,75
4,71
6,7
7
10
46
50
1704
2098
27
31
693
849
5
7
1/1
1/1
1
1
1
1
2,6
2,6
60
124
0,25
0,33
47
92
1"
1" 1/2
830
1270
705
812
453
508
108
118
143
168
59
61
51
53
57
59
49
51
RG66001006 - Rev.04
MCW - MCR
7
DATI TECNICI NOMINALI MCW-H Pompe di calore
MCW - HS / HL
Potenza frigorifera resa
Alimentazione elettrica
Potenza nominale assorbita (in raffreddamento)
Corrente nominale assorbita (in raffreddamento)
Portata d’acqua evaporatore
Perdite di carico lato evaporatore
Portata d’acqua condensatore
Perdite di carico lato condensatore
Potenza termica resa
Potenza nominale assorbita (in riscaldamento)
Corrente nominale assorbita (in riscaldamento)
Portata d’acqua condensatore
Corrente massima assorbita
Corrente di spunto
Perdite di carico lato condensatore
Compressori scroll / circuiti frigoriferi
Evaporatore a piastre
Condensatore a piastre
Contenuto d’acqua circuito utilizzatore
Prevalenza utile pompa (opzione)
Potenza elettrica pompa (opzione)
Capacità serbatoio accumulo (opzione)
Connessioni idrauliche GAS
Dimensioni: altezza
Dimensioni: lunghezza
Dimensioni: profondità
Peso unità standard
Peso unità con pompa e serbatoio
MCW-HS: Livello potenza sonora
MCW-HS: Livello pressione sonora
MCW-HL: Livello potenza sonora
MCW-HL: Livello pressione sonora
kW
V - ph - Hz
kW
A
l/h
kPa
l/h
kPa
kW
kW
A
l/h
A
A
kPa
Nr.
Nr.
Nr.
dm3
kPa
kW
dm3
mm
mm
mm
kg
kg
dB(A)
dB(A)
dB(A)
dB(A)
MCW - HS / HL
Potenza frigorifera resa
Alimentazione elettrica
Potenza nominale assorbita (in raffreddamento)
Corrente nominale assorbita (in raffreddamento)
Portata d’acqua evaporatore
Perdite di carico lato evaporatore
Portata d’acqua condensatore
Perdite di carico lato condensatore
Potenza termica resa
Potenza nominale assorbita (in riscaldamento)
Corrente nominale assorbita (in riscaldamento)
Portata d’acqua condensatore
Perdite di carico lato condensatore
Corrente massima assorbita
Corrente di spunto
Compressori scroll / circuiti frigoriferi
Evaporatore a piastre
Condensatore a piastre
Contenuto d’acqua circuito utilizzatore
Prevalenza utile pompa (opzione)
Potenza elettrica pompa (opzione)
Capacità serbatoio accumulo (opzione)
Connessioni idrauliche GAS
Dimensioni: altezza
Dimensioni: lunghezza
Dimensioni: profondità
Peso unità standard
Peso unità con pompa e serbatoio
MCW-HS: Livello potenza sonora
MCW-HS: Livello pressione sonora
MCW-HL: Livello potenza sonora
MCW-HL: Livello pressione sonora
-
kW
V - ph - Hz
kW
A
l/h
kPa
l/h
kPa
kW
kW
A
l/h
kPa
A
A
Nr.
Nr.
Nr.
dm3
kPa
kW
dm3
mm
mm
mm
kg
kg
dB(A)
dB(A)
dB(A)
dB(A)
005 M
005
007 M
007
010 M
5,3
230-1-50
1,32
6,26
911
25
376
4
6,02
1,67
8,51
1035
12
47
30
1
1
1
2,1
91
0,25
47
1"
830
705
453
106
141
55
47
53
45
5,3
400-3-50 + N
1,3
2,62
911
25
375
4
5,9
1,64
3,28
1015
4,2
24
29
1
1
1
2,1
92
0,25
47
1"
830
705
453
106
141
55
47
53
45
6,8
230-1-50
1,74
8,27
1170
29
485
6
7,75
2,19
11,51
1334
15
61
45
1
1
1
2,1
84
0,25
47
1"
830
705
453
109
144
55
47
53
45
6,8
400-3-50 + N
1,7
3,47
1169
29
482
6
7,6
2,14
4,44
1307
5,1
32
43
1
1
1
2,1
85
0,25
47
1"
830
705
453
109
144
55
47
53
45
9,6
230-1-50
2,34
11,21
1651
25
678
4
10,8
2,96
15,63
1858
23,1
100
32
1
1
1
2,6
78
0,25
47
1"
830
705
453
112
147
59
51
57
49
012
9,6
11,8
400-3-50 + N 400-3-50 + N
2,3
2,75
4,71
5,63
1651
2029
25
29
675
826
4
6
10,6
13,1
2,9
3,47
5,99
7,05
1823
2254
7
10
46
50
31
47
1
1
1
1
1
1
2,6
2,6
79
148
0,25
0,33
47
92
1"
1" 1/2
830
1270
705
812
453
508
112
123
147
173
59
61
51
53
57
59
49
51
015
018
020
022
027
031
039
14,5
17,3
20,1
26,1
30,3
37,5
3,4
7,43
2494
26
1016
4
16
4,28
8,95
2751
13
66
31
1
1
1
3,1
148
0,33
92
1" 1/2
1270
812
508
125
175
61
53
59
51
3,89
7,37
2976
28
1204
6
19,2
4,91
9,88
3303
46
14
74
1
1
1
3,1
140
0,33
92
1" 1/2
1270
812
508
132
182
61
53
59
51
4,4
9,37
3458
26
1392
5
21,6
5,5
11,89
3715
37
16
101
1
1
1
3,6
122
0,45
92
1" 1/2
1270
812
508
175
225
61
53
59
51
21,2
400-3-50 + N
4,9
10,2
3647
27
1483
6
23,59
6,2
12,63
4058
46
17
98
1
1
1
3,6
158
0,45
92
1" 1/2
1270
812
508
209
259
62
54
60
52
6,3
13,15
4489
24
1840
5
29
7,9
16,34
4989
38
20
130
1
1
1
3,9
151
0,45
92
1" 1/2
1270
812
508
221
271
62
54
60
52
7,2
15,23
5212
27
2130
7
33,6
9,1
19,04
5779
50
29
130
1
1
1
4,3
139
0,45
92
1" 1/2
1270
812
508
236
286
65
57
63
55
8,9
17,38
6450
26
2635
7
41,7
11,2
22,34
7173
18
32
135
1
1
1
4,6
149
0,75
92
1" 1/2
1270
812
508
247
297
65
57
63
55
Potenza raffreddamento: temperatura acqua all'evaporatore 12/ 7°C, temperatura al condensatore 15/30°C.
Potenza riscaldamento: temperatura acqua all'evaporatore 15°C, temperatura acqua al condensatore 40/45°C.
Potenza sonora rilevata secondo le norme ISO 3741 - ISO 3744 e EN 29614-1
Pressione sonora riferita alle seguenti condizioni: in campo libero, distanza 1 metro, fattore di direzionalità pari a 2.
RG66001006 - Rev.04
010
8
È severamente vietata la riproduzione anche parziale di questo manuale
MCW - MCR
8
DATI TECNICI NOMINALI MCR-C
MCR - CS / CL
Potenza frigorifera resa
kW
Alimentazione elettrica
V - ph - Hz
Potenza nominale assorbita
kW
Corrente nominale assorbita
A
Corrente massima assorbita
A
Corrente di spunto
A
Portata d’acqua evaporatore
l/h
Perdite di carico lato evaporatore
kPa
Compressori scroll / circuiti frigoriferi
Nr.
Evaporatore a piastre
Nr.
Contenuto d’acqua circuito utilizzatore dm3
Prevalenza utile pompa (opzione)
kPa
Potenza elettrica pompa (opzione)
kW
Capacità serbatoio accumulo (opzione dm3
Dimensioni: altezza
mm
Dimensioni: lunghezza
mm
Dimensioni: profondità
mm
MCR-CS: Livello potenza sonora
dB(A)
MCR-CS: Livello pressione sonora
dB(A)
MCR-CL: Livello potenza sonora
dB(A)
MCR-CL: Livello pressione sonora
dB(A)
MCR - CS / CL
Potenza frigorifera resa
kW
Alimentazione elettrica
V - ph - Hz
Potenza nominale assorbita
kW
Corrente nominale assorbita
A
Corrente massima assorbita
A
Corrente di spunto
A
Portata d’acqua evaporatore
l/h
Perdite di carico lato evaporatore
kPa
Compressori scroll / circuiti frigoriferi
Nr.
Evaporatore a piastre
Nr.
Contenuto d’acqua circuito utilizzatore dm3
Prevalenza utile pompa (opzione)
kPa
Potenza elettrica pompa (opzione)
kW
Capacità serbatoio accumulo (opzione dm3
Dimensioni: altezza
mm
Dimensioni: lunghezza
mm
Dimensioni: profondità
mm
MCR-CS: Livello potenza sonora
dB(A)
MCR-CS: Livello pressione sonora
dB(A)
MCR-CL: Livello potenza sonora
dB(A)
MCR-CL: Livello pressione sonora
dB(A)
005 M
005
007 M
007
010 M
010
012
4,8
230-1-50
1,63
7,63
12
47
825
26
1/1
1
2,1
81
0,25
47
830
705
453
55
47
53
45
4,8
400-3-50 + N
1,6
2,96
4,2
24
825
26
1/1
1
2,1
81
0,25
47
830
705
453
55
47
53
45
6,2
230-1-50
2,16
9,99
15
61
1066
30
1/1
1
2,1
72
0,25
47
830
705
453
55
47
53
45
6,2
400-3-50 + N
2,1
3,77
5,1
32
1067
30
1/1
1
2,1
72
0,25
47
830
705
453
55
47
53
45
8,6
230-1-50
2,96
13,84
23,1
100
1478
26
1/1
1
2,6
67
0,25
47
830
705
453
59
51
57
49
015
018
020
022
027
031
039
13
15,6
17,6
23,5
27,3
33,9
4,3
8,39
13
66
2236
26
1/1
1
3,1
125
0,33
92
1270
812
508
61
53
59
51
5
8,85
14
74
2683
29
1/1
1
3,1
107
0,33
92
1270
812
508
61
53
59
51
5,6
10,76
16
101
3028
26
1/1
1
3,6
145
0,45
92
1270
812
508
61
53
59
51
19,2
400-3-50 + N
6,2
11,52
17
98
3302
29
1/1
1
3,6
136
0,45
92
1270
812
508
62
54
60
52
8
15,04
20
130
4042
26
1/1
1
3,9
122
0,45
92
1270
812
508
62
54
60
52
9,1
16,96
29
130
4695
29
1/1
1
4,3
101
0,45
92
1270
812
508
62
54
60
52
11,2
19,97
32
135
5831
28
1/1
1
4,6
136
0,75
92
1270
812
508
65
57
63
55
8,6
10,76
400-3-50 + N 400-3-50 + N
2,9
3,5
5,36
6,3
7
10
46
50
1480
1851
26
30
1/1
1/1
1
1
2,6
2,6
67
133
0,25
0,33
47
92
830
1270
705
812
453
508
59
61
51
53
57
59
49
51
- Potenza raffreddamento in abbinamento con i condensatori remoti previsti dal manuale: temperatura acqua all'evaporatore 12/ 7°C , temperatura aria di condensazione 35°C
- Potenza sonora rilevata secondo le norme ISO 3741 - ISO 3744 e EN 29614-1
- Pressione sonora riferita alle seguenti condizioni: in campo libero, distanza 1 metro, fattore di direzionalità pari a 2.
9
È severamente vietata la riproduzione anche parziale di questo manuale
RG66001006 - Rev.04
MCW - MCR
9
RESA RAFFREDDAMENTO MCW C
Legenda:
Twe1 Temperatura ingresso acqua evaporatore (utilizzatore)
Twe2 Temperatura uscita acqua evaporatore (utilizzatore)
Twc2 Temperatura uscita acqua condensatore (dissipatore)
PF
Potenza frigorifera
PA
Potenza elettrica assorbita
PD
Potenza termica da dissipare
MCW C
MCW 005 CM
MCW 005 C
MCW 007 CM
MCW 007 C
MCW 010 CM
MCW 010 C
MCW 012 C
RG66001006 - Rev.04
Twc2
Twe1
°C
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
°C
Twe2
°C
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
PF
kW
5,13
5,55
6,04
6,60
7,19
5,10
5,50
5,94
6,37
6,81
6,53
7,08
7,61
8,18
8,77
6,49
7,00
7,53
8,09
8,69
9,23
9,90
10,65
11,43
12,26
9,20
9,93
10,66
11,44
12,21
11,36
12,23
13,10
14,05
15,03
30
PA
kW
1,33
1,32
1,31
1,30
1,28
1,31
1,30
1,29
1,28
1,27
1,75
1,74
1,72
1,71
1,69
1,71
1,70
1,69
1,67
1,65
2,36
2,34
2,32
2,30
2,28
2,31
2,30
2,28
2,26
2,24
2,78
2,75
2,73
2,70
2,66
PD
kW
6,46
6,87
7,35
7,90
8,47
6,41
6,80
7,23
7,65
8,08
8,28
8,82
9,33
9,89
10,46
8,20
8,70
9,22
9,76
10,34
11,59
12,24
12,97
13,73
14,54
11,51
12,23
12,94
13,70
14,45
14,14
14,98
15,83
16,75
17,69
35
PA
kW
1,40
1,40
1,39
1,38
1,38
1,38
1,38
1,38
1,37
1,36
1,88
1,87
1,87
1,86
1,85
1,84
1,84
1,83
1,83
1,82
2,51
2,50
2,50
2,49
2,48
2,46
2,45
2,45
2,45
2,44
2,99
2,99
2,98
2,96
2,95
PF
kW
5,09
5,50
5,94
6,44
6,93
4,99
5,38
5,78
6,20
6,64
6,32
6,80
7,31
7,85
8,39
6,27
6,75
7,28
7,82
8,36
8,95
9,60
10,30
11,04
11,81
8,96
9,66
10,36
11,10
11,82
10,98
11,79
12,63
13,53
14,45
PD
kW
6,49
6,90
7,33
7,82
8,31
6,37
6,76
7,16
7,57
8,00
8,20
8,67
9,18
9,71
10,24
8,11
8,59
9,11
9,65
10,18
11,46
12,10
12,80
13,53
14,29
11,42
12,11
12,81
13,55
14,26
13,97
14,78
15,61
16,49
17,40
PF
kW
4,96
5,35
5,73
6,12
6,53
4,72
5,09
5,48
5,91
6,32
5,93
6,40
6,88
7,38
7,93
5,90
6,39
6,87
7,38
7,93
8,40
9,03
9,71
10,42
11,14
8,47
9,11
9,80
10,50
11,23
10,37
11,15
11,96
12,83
13,75
10
È severamente vietata la riproduzione anche parziale di questo manuale
40
PA
kW
1,57
1,56
1,56
1,55
1,54
1,56
1,55
1,55
1,54
1,53
2,10
2,11
2,10
2,09
2,07
2,07
2,06
2,07
2,06
2,05
2,81
2,81
2,80
2,78
2,78
2,77
2,77
2,76
2,75
2,74
3,34
3,33
3,32
3,31
3,29
PD
kW
6,53
6,91
7,29
7,67
8,07
6,28
6,64
7,03
7,45
7,85
8,03
8,51
8,98
9,47
10,00
7,97
8,45
8,94
9,44
9,98
11,21
11,84
12,51
13,20
13,92
11,24
11,88
12,56
13,25
13,97
13,71
14,48
15,28
16,14
17,04
PF
kW
4,62
4,98
5,33
5,73
6,12
4,42
4,78
5,18
5,57
5,96
5,55
5,97
6,45
6,96
7,46
5,51
5,95
6,44
6,94
7,43
7,83
8,44
9,10
9,76
10,44
7,89
8,53
9,20
9,88
10,58
9,72
10,46
11,25
12,08
12,96
45
PA
kW
1,76
1,75
1,75
1,74
1,74
1,75
1,74
1,74
1,73
1,73
2,36
2,35
2,34
2,33
2,31
2,33
2,33
2,32
2,31
2,30
3,16
3,15
3,14
3,13
3,12
3,12
3,12
3,11
3,10
3,09
3,71
3,71
3,71
3,70
3,69
PD
kW
6,38
6,73
7,08
7,47
7,86
6,17
6,52
6,92
7,30
7,69
7,91
8,32
8,79
9,29
9,77
7,84
8,28
8,76
9,25
9,73
10,99
11,59
12,24
12,89
13,56
11,01
11,65
12,31
12,98
13,67
13,43
14,17
14,96
15,78
16,65
MCW - MCR
9
RESA RAFFREDDAMENTO MCW C
Legenda:
Twe1 Temperatura ingresso acqua evaporatore (utilizzatore)
Twe2 Temperatura uscita acqua evaporatore (utilizzatore)
Twc2 Temperatura uscita acqua condensatore (dissipatore)
PF
Potenza frigorifera
PA
Potenza elettrica assorbita
PD
Potenza termica da dissipare
MCW C
MCW 015 C
MCW 018 C
MCW 020 C
MCW 022 C
MCW 027 C
MCW 031 C
MCW 039 C
Twc2
Twe1
°C
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
°C
Twe2
°C
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
PF
kW
13,79
14,93
16,09
17,33
18,59
16,48
17,84
19,22
20,64
22,06
18,69
20,15
21,63
23,20
24,81
20,34
21,92
23,61
25,39
27,24
25,01
26,95
28,97
31,10
33,37
29,04
31,27
33,60
36,05
38,65
35,99
38,76
41,66
44,70
47,98
30
PA
kW
3,38
3,40
3,42
3,44
3,47
3,94
3,94
3,96
3,95
3,96
4,38
4,40
4,43
4,46
4,49
4,91
4,92
4,90
4,89
4,88
6,31
6,29
6,28
6,26
6,24
7,22
7,20
7,19
7,16
7,13
8,89
8,90
8,91
8,93
8,94
PD
kW
17,17
18,33
19,51
20,77
22,06
20,42
21,78
23,18
24,59
26,02
23,07
24,55
26,06
27,66
29,30
25,25
26,84
28,51
30,28
32,12
31,32
33,24
35,25
37,36
39,61
36,26
38,47
40,79
43,21
45,78
44,88
47,66
50,57
53,63
56,92
35
PA
kW
3,59
3,62
3,65
3,69
3,73
4,24
4,27
4,29
4,32
4,34
4,68
4,72
4,76
4,82
4,88
5,26
5,28
5,31
5,32
5,34
6,72
6,74
6,76
6,77
6,78
7,80
7,81
7,84
7,85
7,86
9,65
9,71
9,77
9,82
9,88
PF
kW
13,41
14,46
15,58
16,73
17,93
15,91
17,15
18,41
19,73
21,06
18,15
19,51
20,92
22,39
23,88
19,63
21,13
22,70
24,38
26,12
24,22
26,04
27,95
29,27
32,07
27,96
30,05
32,24
34,53
36,93
34,59
37,16
39,88
42,75
45,74
11
PD
kW
17,00
18,08
19,23
20,42
21,66
20,15
21,42
22,70
24,05
25,40
22,83
24,23
25,68
27,21
28,76
24,89
26,41
28,01
29,70
31,46
30,94
32,78
34,71
36,04
38,85
35,76
37,86
40,08
42,38
44,79
44,24
46,87
49,65
52,57
55,62
PF
kW
12,64
13,64
14,71
15,82
16,97
15,00
16,17
17,35
18,59
19,87
17,13
18,42
19,78
21,19
22,64
18,50
19,93
21,43
23,03
24,70
22,83
24,57
26,40
28,33
30,35
26,36
28,33
30,43
32,63
34,94
32,69
35,16
37,75
40,48
43,36
40
PA
kW
4,00
4,03
4,06
4,09
4,13
4,73
4,75
4,78
4,80
4,82
5,23
5,27
5,31
5,36
5,41
5,84
5,86
5,89
5,91
5,92
7,48
7,50
7,52
7,53
7,54
8,68
8,71
8,72
8,73
8,74
10,73
10,79
10,85
10,90
10,96
È severamente vietata la riproduzione anche parziale di questo manuale
PD
kW
16,64
17,67
18,77
19,91
21,10
19,73
20,92
22,13
23,39
24,69
22,36
23,69
25,09
26,55
28,05
24,34
25,79
27,32
28,94
30,62
30,31
32,07
33,92
35,86
37,89
35,04
37,04
39,15
41,36
43,68
43,42
45,95
48,60
51,38
54,32
PF
kW
11,83
12,79
13,81
14,85
15,94
14,12
15,17
16,28
17,46
18,68
16,03
17,26
18,56
19,92
21,33
17,31
18,66
20,10
21,62
23,19
21,38
23,02
24,78
26,60
28,51
24,65
26,55
28,53
30,61
32,80
30,71
33,05
35,52
38,10
40,83
45
PA
kW
4,45
4,47
4,51
4,54
4,57
5,27
5,30
5,33
5,35
5,37
5,86
5,89
5,93
5,98
6,03
6,48
6,50
6,54
6,55
6,58
8,32
8,35
8,37
8,38
8,40
9,70
9,72
9,73
9,75
9,75
11,96
12,01
12,07
12,13
12,19
PD
kW
16,28
17,26
18,32
19,39
20,51
19,39
20,47
21,61
22,81
24,05
21,89
23,15
24,49
25,90
27,36
23,79
25,16
26,64
28,17
29,77
29,70
31,37
33,15
34,98
36,91
34,35
36,27
38,26
40,36
42,55
42,67
45,06
47,59
50,23
53,02
RG66001006 - Rev.04
MCW - MCR
10
RESA RAFFREDDAMENTO MCW H
Legenda:
Twe1 Temperatura ingresso acqua evaporatore(utilizzatore)
Twe2 Temperatura uscita acqua evaporatore(utilizzatore)
Twc2 Temperatura uscita acqua condensatore (dissipatore)
PF
Potenza frigorifera
PA
Potenza elettrica assorbita
PD
Potenza termica da dissipare
MCW H
MCW 005 HM
MCW 005 H
MCW 007 HM
MCW 007 H
MCW 010 HM
MCW 010 H
MCW 012 H
RG66001006 - Rev.04
Twc2
Twe1
°C
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
°C
Twe2
°C
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
PF
kW
4,90
5,29
5,75
6,26
6,77
5,31
4,92
5,69
6,09
6,51
6,23
6,69
7,17
7,69
8,22
6,69
6,22
7,18
7,73
8,25
8,88
9,53
10,19
10,93
11,65
9,52
8,84
10,21
10,92
11,64
11,58
10,80
12,40
13,26
14,12
30
PA
kW
1,33
1,33
1,33
1,32
1,32
1,31
1,31
1,31
1,31
1,30
1,80
1,80
1,80
1,79
1,79
1,76
1,75
1,76
1,76
1,75
2,40
2,39
2,39
2,38
2,38
2,34
2,34
2,34
2,33
2,33
2,88
2,88
2,87
2,86
2,85
PD
kW
6,23
6,62
7,08
7,58
8,09
6,62
6,23
7,00
7,40
7,81
8,03
8,49
8,97
9,48
10,01
8,45
7,97
8,94
9,49
10,00
11,28
11,92
12,58
13,31
14,03
11,86
11,18
12,55
13,25
13,97
14,46
13,68
15,27
16,12
16,97
35
PA
kW
1,48
1,48
1,48
1,48
1,47
1,47
1,47
1,47
1,47
1,46
2,01
2,01
2,01
2,00
2,00
1,97
1,98
1,98
1,97
1,97
2,67
2,67
2,67
2,67
2,66
2,63
2,63
2,63
2,63
2,63
3,20
3,20
3,20
3,20
3,18
PF
kW
4,81
5,19
5,58
5,97
6,39
4,67
5,04
5,41
5,80
6,22
5,86
6,30
6,77
7,27
7,77
5,88
6,34
6,82
7,33
7,84
8,39
9,01
9,64
10,33
11,06
8,39
9,03
9,70
10,39
11,08
10,24
10,98
11,77
12,61
13,47
PD
kW
6,29
6,67
7,06
7,45
7,86
6,14
6,51
6,88
7,27
7,68
7,87
8,31
8,78
9,27
9,77
7,85
8,32
8,80
9,30
9,81
11,06
11,68
12,31
13,00
13,72
11,02
11,66
12,33
13,02
13,71
13,44
14,18
14,97
15,81
16,65
PF
kW
4,60
4,95
5,28
5,64
6,02
4,41
4,75
5,10
5,51
5,89
5,50
5,91
6,36
6,85
7,35
5,53
5,95
6,41
6,91
7,40
7,86
8,43
9,07
9,73
10,40
7,88
8,52
9,14
9,81
10,50
9,64
10,35
11,10
11,92
12,73
12
È severamente vietata la riproduzione anche parziale di questo manuale
40
PA
kW
1,66
1,66
1,66
1,66
1,65
1,65
1,65
1,65
1,65
1,64
2,25
2,26
2,25
2,24
2,22
2,21
2,22
2,22
2,22
2,20
3,00
3,00
2,99
2,98
2,98
2,96
2,95
2,96
2,96
2,95
3,56
3,57
3,56
3,56
3,56
PD
kW
6,26
6,61
6,94
7,30
7,67
6,06
6,40
6,75
7,16
7,53
7,75
8,17
8,61
9,09
9,57
7,74
8,17
8,63
9,13
9,60
10,86
11,43
12,06
12,71
13,38
10,84
11,47
12,10
12,77
13,45
13,20
13,92
14,66
15,48
16,29
PF
kW
4,27
4,58
4,92
5,28
5,66
4,11
4,44
4,80
5,18
5,55
5,12
5,51
5,96
6,42
6,90
5,12
5,54
5,99
6,45
6,92
7,30
7,86
8,46
9,08
9,73
7,34
7,94
8,53
9,19
9,83
9,00
9,67
10,39
11,16
11,99
45
PA
kW
1,85
1,85
1,85
1,84
1,84
1,85
1,86
1,86
1,84
1,84
2,50
2,50
2,49
2,47
2,45
2,49
2,49
2,49
2,48
2,48
3,37
3,38
3,36
3,36
3,34
3,32
3,32
3,32
3,31
3,31
3,96
3,98
3,98
3,98
3,97
PD
kW
6,12
6,43
6,77
7,12
7,50
5,96
6,30
6,66
7,02
7,39
7,62
8,01
8,45
8,89
9,35
7,61
8,03
8,48
8,93
9,40
10,67
11,24
11,82
12,44
13,07
10,66
11,26
11,85
12,50
13,14
12,96
13,65
14,37
15,14
15,96
MCW - MCR
10
RESA RAFFREDDAMENTO MCW H
Legenda:
Twe1 Temperatura ingresso acqua evaporatore(utilizzatore)
Twe2 Temperatura uscita acqua evaporatore(utilizzatore)
Twc2 Temperatura uscita acqua condensatore (dissipatore)
PF
Potenza frigorifera
PA
Potenza elettrica assorbita
PD
Potenza termica da dissipare
MCW H
MCW 015 H
MCW 018 H
MCW 020 H
MCW 022 H
MCW 027 H
MCW 031 H
MCW 039 H
Twc2
Twe1
°C
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
°C
Twe2
°C
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
PF
kW
14,34
13,34
15,43
16,56
17,71
16,96
15,73
18,21
19,48
20,75
19,84
18,51
21,26
22,73
24,23
20,83
19,35
22,34
23,95
25,64
25,74
23,98
27,60
29,53
31,58
29,62
27,60
31,74
33,96
36,29
36,55
34,05
39,16
41,90
44,81
30
PA
kW
3,47
3,43
3,52
3,56
3,61
4,06
4,02
4,09
4,12
4,15
4,53
4,47
4,58
4,64
4,71
5,10
5,06
5,13
5,15
5,18
6,49
6,45
6,52
6,55
6,57
7,55
7,51
7,58
7,61
7,64
9,40
9,32
9,47
9,56
9,64
PD
kW
17,81
16,77
18,95
20,12
21,32
21,02
19,75
22,30
23,60
24,90
24,37
22,98
25,84
27,37
28,94
25,93
24,41
27,47
29,10
30,82
32,23
30,43
34,12
36,08
38,15
37,17
35,11
39,32
41,57
43,93
45,95
43,37
48,63
51,46
54,45
35
PA
kW
3,81
3,85
3,89
3,94
3,98
4,48
4,51
4,54
4,58
4,60
4,99
5,04
5,09
5,15
5,22
5,60
5,64
5,68
5,71
5,73
7,17
7,20
7,24
7,21
7,29
8,35
8,38
8,42
8,45
8,48
10,34
10,42
10,50
10,59
10,67
PF
kW
12,60
13,59
14,63
15,71
16,82
14,89
16,02
17,18
18,39
19,63
17,52
18,81
20,18
21,59
23,04
18,32
19,73
21,16
22,69
24,33
22,67
24,37
26,15
28,02
29,99
26,10
28,03
30,07
32,19
34,42
32,29
34,65
37,15
39,79
42,56
13
PD
kW
16,41
17,44
18,52
19,65
20,80
19,37
20,53
21,72
22,97
24,23
22,51
23,85
25,27
26,74
28,26
23,92
25,37
26,84
28,40
30,06
29,84
31,57
33,39
35,23
37,28
34,45
36,41
38,49
40,64
42,90
42,63
45,07
47,65
50,38
53,23
PF
kW
11,84
12,79
13,78
14,81
15,87
14,05
15,09
16,16
17,31
18,50
16,48
17,71
19,02
20,37
21,76
17,21
18,54
19,93
21,40
22,93
21,32
22,91
24,63
26,41
28,27
24,54
26,36
28,30
30,31
32,45
30,41
32,68
35,06
37,58
40,24
40
PA
kW
4,24
4,28
4,32
4,36
4,40
4,99
5,02
5,05
5,09
5,12
5,57
5,62
5,67
5,73
5,80
6,21
6,25
6,29
6,32
6,36
7,96
8,00
8,04
8,07
8,09
9,29
9,34
9,36
9,40
9,42
11,49
11,57
11,66
11,74
11,81
È severamente vietata la riproduzione anche parziale di questo manuale
PD
kW
16,08
17,07
18,10
19,17
20,27
19,04
20,11
21,21
22,40
23,62
22,05
23,33
24,69
26,10
27,56
23,42
24,79
26,22
27,72
29,29
29,28
30,91
32,67
34,48
36,36
33,83
35,70
37,66
39,71
41,87
41,90
44,25
46,72
49,32
52,05
PF
kW
11,06
11,95
12,90
13,89
14,89
13,18
14,15
15,17
16,27
17,37
15,35
16,53
17,78
19,10
20,42
16,04
17,29
18,59
19,97
21,46
19,86
21,41
23,00
24,67
26,46
22,83
24,57
26,43
28,33
30,34
28,48
30,64
32,90
35,29
37,80
45
PA
kW
4,70
4,74
4,78
4,82
4,87
5,55
5,59
5,62
5,65
5,69
6,24
6,28
6,34
6,40
6,47
6,88
6,92
6,97
7,00
7,04
8,86
8,89
8,93
8,97
8,99
10,39
10,42
10,44
10,47
10,49
12,80
12,88
12,96
13,03
13,12
PD
kW
15,76
16,69
17,68
18,71
19,76
18,73
19,74
20,79
21,92
23,06
21,59
22,81
24,12
25,50
26,89
22,92
24,21
25,56
26,97
28,50
28,72
30,30
31,93
33,64
35,45
33,22
34,99
36,87
38,80
40,83
41,28
43,52
45,86
48,32
50,92
RG66001006 - Rev.04
MCW - MCR
11
RESA RISCALDAMENTO MCW H
Legenda:
Twc1 Temperatura ingresso acqua condensatore (utilizzatore)
Twc2 Temperatura uscita acqua condensatore (utilizzatore)
Twe2 Temperatura uscita acqua evaporatore (dissipatore)
PT
Potenza termica in riscaldamento
PA
Potenza elettrica assorbita
MCW H
MCW 005 HM
MCW 005 H
MCW 007 HM
MCW 007 H
MCW 010 HM
MCW 010 H
MCW 012 H
RG66001006 - Rev.04
Twe2
Twc1
Twc2
°C
°C
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
8°C
PT
kW
5,99
5,88
5,70
5,55
5,83
5,70
5,58
5,45
7,74
7,54
7,35
7,14
7,57
7,37
7,20
7,01
10,79
10,51
10,25
10,02
10,54
10,29
10,03
9,77
13,04
12,72
12,41
12,12
9°C
PA
kW
1,34
1,50
1,67
1,84
1,30
1,46
1,64
1,84
1,78
1,98
2,20
2,41
1,69
1,90
2,13
2,39
2,35
2,64
2,96
3,35
2,29
2,57
2,90
3,25
2,79
3,11
3,46
3,88
PT
kW
6,16
6,03
5,86
5,69
6,00
5,86
5,74
5,59
7,96
7,75
7,55
7,33
7,78
7,58
7,40
7,21
11,09
10,81
10,53
10,27
10,84
10,57
10,30
10,04
13,40
13,07
12,74
12,45
10°C
PA
kW
1,34
1,50
1,67
1,84
1,31
1,47
1,65
1,84
1,78
1,98
2,19
2,40
1,70
1,90
2,14
2,39
2,35
2,63
2,96
3,35
2,29
2,58
2,90
3,26
2,79
3,11
3,47
3,89
PT
kW
6,34
6,19
6,02
5,84
6,18
6,05
5,90
5,74
8,19
7,97
7,75
7,54
8,01
7,81
7,60
7,41
11,40
11,12
10,80
10,55
11,16
10,89
10,60
10,31
13,77
13,43
13,10
12,77
11°C
PA
kW
1,34
1,50
1,67
1,84
1,30
1,46
1,64
1,84
1,77
1,98
2,19
2,39
1,69
1,90
2,14
2,39
2,35
2,63
2,96
3,35
2,29
2,58
2,90
3,24
2,79
3,10
3,47
3,88
14
È severamente vietata la riproduzione anche parziale di questo manuale
PT
kW
6,52
6,36
6,18
6,01
6,35
6,22
6,07
5,91
8,42
8,21
7,98
7,76
8,24
8,04
7,81
7,61
11,74
11,42
11,11
10,83
11,47
11,18
10,89
10,58
14,17
13,82
13,46
13,11
PA
kW
1,34
1,50
1,67
1,83
1,30
1,46
1,63
1,83
1,77
1,98
2,18
2,38
1,69
1,90
2,13
2,38
2,35
2,63
2,96
3,34
2,29
2,58
2,89
3,24
2,79
3,10
3,47
3,88
12°C
PT
kW
6,71
6,53
6,33
6,16
6,55
6,39
6,22
6,05
8,65
8,44
8,20
7,99
8,47
8,26
8,03
7,81
12,08
11,73
11,40
11,11
11,78
11,49
11,18
10,84
14,56
14,20
13,84
13,48
PA
kW
1,33
1,50
1,67
1,83
1,30
1,46
1,64
1,83
1,76
1,97
2,17
2,37
1,69
1,90
2,12
2,37
2,34
2,63
2,95
3,33
2,29
2,57
2,89
3,24
2,78
3,10
3,46
3,89
MCW - MCR
11
RESA RISCALDAMENTO MCW H
Legenda:
Twc1 Temperatura ingresso acqua condensatore (utilizzatore)
Twc2 Temperatura uscita acqua condensatore (utilizzatore)
Twe2 Temperatura uscita acqua evaporatore (dissipatore)
PT
Potenza termica in riscaldamento
PA
Potenza elettrica assorbita
MCW H
MCW 015 H
MCW 018 H
MCW 020 H
MCW 022 H
MCW 027 H
MCW 031 H
MCW 039 H
Twe2
Twc1
Twc2
°C
°C
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
35
30
40
35
45
40
50
45
8°C
PT
kW
15,91
15,49
15,08
14,67
19,13
18,63
18,18
17,84
21,52
20,97
20,40
19,86
23,58
22,94
22,31
21,65
28,99
28,22
27,43
26,67
33,59
32,70
31,84
31,00
41,38
40,41
39,48
38,64
PA
kW
3,45
3,82
4,24
4,69
3,95
4,39
4,89
5,42
4,38
4,88
5,46
6,11
5,02
5,56
6,16
6,83
6,38
7,08
7,88
8,77
7,31
8,13
9,07
10,14
9,01
10,00
11,12
12,40
9°C
PT
kW
16,42
15,97
15,53
15,11
19,68
19,14
18,68
18,30
22,16
21,58
21,00
20,42
24,27
23,62
22,92
22,25
29,84
29,04
28,21
27,39
34,55
33,64
32,73
31,83
42,59
41,56
40,58
39,65
10°C
PA
kW
3,47
3,84
4,26
4,71
3,96
4,40
4,90
5,44
4,40
4,90
5,48
6,14
5,04
5,58
6,19
6,85
6,39
7,10
7,89
8,79
7,32
8,14
9,08
10,14
9,05
10,04
11,17
12,43
15
PT
kW
16,93
16,46
16,00
15,55
20,24
19,69
19,20
18,80
22,82
22,21
21,60
20,99
25,00
24,30
23,59
22,87
30,71
29,85
29,00
28,12
35,55
34,58
33,60
32,63
43,83
42,76
41,70
40,69
PA
kW
3,49
3,86
4,28
4,73
3,98
4,42
4,91
5,45
4,43
4,93
5,50
6,17
5,05
5,59
6,20
6,87
6,40
7,11
7,90
8,80
7,33
8,16
9,10
10,16
9,08
10,07
11,20
12,46
È severamente vietata la riproduzione anche parziale di questo manuale
11°C
PT
kW
17,44
16,95
16,47
15,99
20,83
20,24
19,72
19,27
23,47
22,84
22,23
21,62
25,73
25,02
24,24
23,49
31,60
30,72
29,79
28,88
36,54
35,54
34,52
33,49
45,09
43,95
42,85
41,78
PA
kW
3,51
3,88
4,29
4,76
3,99
4,44
4,92
5,47
4,46
4,96
5,53
6,19
5,07
5,61
6,22
6,89
6,41
7,12
7,92
8,81
7,35
8,18
9,11
10,16
9,12
10,11
11,23
12,49
12°C
PT
kW
17,97
17,44
16,94
16,46
21,42
20,81
20,26
19,77
24,16
23,51
22,88
22,26
26,49
25,72
24,93
24,12
32,50
31,56
30,62
29,66
37,59
36,55
35,45
34,37
46,39
45,20
44,03
42,89
PA
kW
3,53
3,90
4,31
4,77
4,00
4,44
4,94
5,48
4,48
4,99
5,57
6,23
5,08
5,62
6,24
6,90
6,43
7,14
7,93
8,83
7,36
8,19
9,12
10,16
9,15
10,15
11,27
12,51
RG66001006 - Rev.04
MCW - MCR
12
RESA RAFFREDDAMENTO MCR C
Legenda:
Twe1 Temperatura ingresso acqua evaporatore (utilizzatore)
Twe2 Temperatura uscita acqua evaporatore (utilizzatore)
Twc2 Temperatura uscita acqua condensatore (dissipatore)
PF
Potenza frigorifera
PA
Potenza elettrica assorbita
PD
Potenza termica da dissipare
MCR C
MCR 005 CM
MCR 005 C
MCR 007 CM
MCR 007 C
MCR 010 CM
MCR 010 C
MCR 012 C
RG66001006 - Rev.04
Twc2
Twe1
°C
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
°C
Twe2
°C
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
PF
kW
4,82
5,23
5,69
6,23
6,78
5,03
5,43
5,85
6,27
6,72
6,85
7,40
7,52
8,02
8,52
6,79
7,34
7,52
8,02
8,54
9,23
9,92
10,65
11,45
12,26
9,10
9,82
10,57
11,32
12,10
11,76
12,65
12,92
13,74
14,61
25
PA
kW
1,28
1,27
1,26
1,24
1,23
1,25
1,24
1,23
1,22
1,21
1,58
1,57
1,75
1,76
1,78
1,52
1,51
1,69
1,71
1,72
2,28
2,26
2,25
2,22
2,20
2,22
2,21
2,19
2,17
2,15
2,59
2,57
2,84
2,88
2,90
PD
kW
6,10
6,50
6,95
7,47
8,01
6,28
6,67
7,08
7,49
7,93
8,43
8,97
9,27
9,78
10,30
8,31
8,85
9,21
9,73
10,26
11,51
12,18
12,90
13,67
14,46
11,32
12,03
12,76
13,49
14,25
14,35
15,22
15,76
16,62
17,51
PF
kW
4,74
5,09
5,45
5,81
6,14
4,75
5,10
5,46
5,83
6,21
6,20
6,63
7,08
7,57
8,06
6,20
6,64
7,10
7,58
8,07
8,60
9,18
9,78
10,44
11,10
8,54
9,17
9,80
10,43
11,08
10,74
11,48
12,23
13,01
13,83
30
PA
kW
1,44
1,46
1,47
1,47
1,48
1,42
1,43
1,44
1,45
1,46
1,91
1,93
1,95
1,96
1,98
1,84
1,87
1,89
1,91
1,93
2,61
2,64
2,66
2,68
2,70
2,55
2,58
2,61
2,63
2,66
3,11
3,14
3,18
3,21
3,24
PD
kW
6,18
6,55
6,92
7,28
7,62
6,17
6,53
6,90
7,28
7,67
8,11
8,56
9,03
9,53
10,04
8,04
8,51
8,99
9,49
10,00
11,21
11,82
12,44
13,12
13,80
11,09
11,75
12,41
13,06
13,74
13,85
14,62
15,41
16,22
17,07
PF
kW
4,49
4,80
5,10
5,44
5,79
4,46
4,80
5,15
5,52
5,88
5,81
6,20
6,64
7,11
7,59
5,78
6,20
6,64
7,10
7,55
8,03
8,60
9,19
9,79
10,41
8,02
8,60
9,21
9,81
10,44
10,07
10,76
11,48
12,24
13,00
35
PA
kW
1,62
1,63
1,64
1,66
1,66
1,59
1,60
1,62
1,63
1,64
2,14
2,16
2,17
2,18
2,19
2,07
2,10
2,12
2,14
2,16
2,93
2,96
2,98
3,01
3,03
2,87
2,90
2,93
2,96
2,98
3,46
3,50
3,54
3,59
3,63
PD
kW
6,11
6,43
6,74
7,10
7,45
6,05
6,40
6,77
7,15
7,52
7,95
8,36
8,81
9,29
9,78
7,85
8,30
8,76
9,24
9,71
10,96
11,56
12,17
12,80
13,44
10,89
11,50
12,14
12,77
13,42
13,53
14,26
15,02
15,83
16,63
PF
kW
4,16
4,46
4,77
5,11
5,42
4,16
4,49
4,82
5,17
5,50
5,40
5,77
6,19
6,65
7,12
5,36
5,76
6,17
6,59
7,02
7,44
7,99
8,53
9,12
9,70
7,45
8,01
8,58
9,16
9,74
9,37
10,01
10,68
11,40
12,13
16
È severamente vietata la riproduzione anche parziale di questo manuale
40
PA
kW
1,80
1,81
1,82
1,83
1,84
1,79
1,81
1,82
1,83
1,84
2,36
2,37
2,38
2,39
2,39
2,32
2,35
2,38
2,40
2,42
3,31
3,34
3,36
3,39
3,42
3,23
3,27
3,30
3,32
3,35
3,86
3,91
3,96
4,01
4,07
PD
kW
5,96
6,27
6,59
6,94
7,26
5,95
6,30
6,64
7,00
7,34
7,76
8,14
8,57
9,04
9,51
7,68
8,11
8,55
8,99
9,44
10,75
11,33
11,89
12,51
13,12
10,68
11,28
11,88
12,48
13,09
13,23
13,92
14,64
15,41
16,20
PF
kW
3,85
4,14
4,43
4,75
5,06
3,85
4,16
4,47
4,78
5,08
5,00
5,35
5,76
6,19
6,64
4,92
5,30
5,71
6,12
6,52
6,85
7,36
7,88
8,42
8,98
6,85
7,37
7,91
8,46
9,01
8,66
9,25
9,89
10,56
11,26
45
PA
kW
1,98
1,99
2,00
2,00
2,01
2,01
2,03
2,04
2,05
2,05
2,58
2,90
2,59
2,59
2,59
2,60
2,63
2,64
2,66
2,67
3,76
3,78
3,82
3,83
3,84
3,64
3,68
3,47
3,72
3,74
4,32
4,36
4,40
4,45
4,49
PD
kW
5,83
6,13
6,43
6,75
7,07
5,86
6,19
6,51
6,83
7,13
7,58
8,25
8,35
8,78
9,23
7,52
7,93
8,35
8,78
9,19
10,61
11,14
11,70
12,25
12,82
10,49
11,05
11,38
12,18
12,75
12,98
13,61
14,29
15,01
15,75
MCW - MCR
12
RESA RAFFREDDAMENTO MCR C
Legenda:
Twe1 Temperatura ingresso acqua evaporatore (utilizzatore)
Twe2 Temperatura uscita acqua evaporatore (utilizzatore)
Twc2 Temperatura uscita acqua condensatore (dissipatore)
PF
Potenza frigorifera
PA
Potenza elettrica assorbita
PD
Potenza termica da dissipare
MCR C
MCR 015 C
MCR 018 C
MCR 020 C
MCR 022 C
MCR 027 C
MCR 031 C
MCR 039 C
Twc2
Twe1
°C
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
10
12
14
16
18
°C
Twe2
°C
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
5
7
9
11
13
PF
kW
13,72
14,82
15,97
17,22
18,45
16,87
18,24
19,69
19,98
21,18
18,78
20,20
21,69
23,29
23,83
20,77
22,43
24,13
24,64
26,23
25,10
27,08
29,10
31,22
32,04
29,97
32,24
32,91
35,05
37,24
35,89
38,61
41,57
44,59
45,83
25
PA
kW
3,37
3,39
3,41
3,44
3,47
3,75
3,75
3,76
4,18
4,26
4,29
4,31
4,33
4,36
4,82
4,73
4,73
4,72
5,22
5,32
6,20
6,19
6,17
6,16
6,75
6,75
6,73
7,44
7,56
7,68
8,71
8,73
8,74
8,75
9,56
PD
kW
17,09
18,21
19,38
20,66
21,92
20,62
21,99
23,45
24,16
25,44
23,07
24,51
26,02
27,65
28,65
25,50
27,16
28,85
29,86
31,55
31,30
33,27
35,27
37,38
38,79
36,72
38,97
40,35
42,61
44,92
44,60
47,34
50,31
53,34
55,39
PF
kW
12,88
13,84
14,83
15,83
16,86
15,52
16,60
17,71
18,82
19,96
17,53
18,73
19,98
21,27
22,59
19,09
20,47
21,89
23,27
24,80
23,37
25,01
26,73
28,46
30,30
27,27
29,15
31,10
33,06
35,40
33,62
35,94
38,34
40,89
46,44
30
PA
kW
3,80
3,87
3,95
4,03
4,11
4,41
4,49
4,56
4,64
4,73
4,94
5,02
5,13
5,23
5,34
5,52
5,59
5,64
5,79
5,88
7,10
7,20
7,30
7,39
7,50
8,05
8,17
8,29
8,41
8,55
9,91
10,09
10,24
10,42
10,60
PD
kW
16,68
17,71
18,78
19,86
20,97
19,93
21,09
22,27
23,46
24,69
22,47
23,75
25,11
26,50
27,93
24,61
26,06
27,53
29,06
30,68
30,47
32,21
34,03
35,85
37,80
35,32
37,32
39,39
41,47
43,95
43,53
46,03
48,58
51,31
57,04
17
PF
kW
12,26
13,00
13,94
14,89
15,85
14,60
15,60
16,62
17,70
18,75
16,48
17,60
18,79
20,06
21,27
17,94
19,20
20,52
21,90
23,28
21,94
23,50
25,08
26,72
28,44
25,59
27,30
29,12
31,01
32,98
31,66
33,90
36,14
38,55
41,04
35
PA
kW
4,14
4,30
4,39
4,47
4,55
4,91
5,00
5,08
5,17
5,26
5,51
5,60
5,72
5,82
5,95
6,11
6,20
6,30
6,40
6,51
7,90
8,00
8,12
8,22
8,34
8,98
9,10
9,24
9,37
9,50
11,03
11,20
11,38
11,57
11,77
PD
kW
16,40
17,30
18,33
19,36
20,40
19,51
20,60
21,70
22,87
24,01
21,99
23,20
24,51
25,88
27,22
24,05
25,40
26,82
28,30
29,79
29,84
31,50
33,20
34,94
36,78
34,57
36,40
38,36
40,38
42,48
42,69
45,10
47,52
50,12
52,81
PF
kW
11,28
12,14
13,02
13,91
14,82
13,67
14,60
15,57
16,58
17,57
15,32
16,37
17,52
18,73
19,93
16,70
17,86
19,07
20,34
21,70
20,42
21,87
23,36
24,94
26,52
23,75
25,41
27,03
28,79
30,59
29,64
31,73
33,92
36,13
38,52
È severamente vietata la riproduzione anche parziale di questo manuale
40
PA
kW
4,70
4,78
4,87
4,95
5,04
5,48
5,57
5,66
5,76
5,85
6,18
6,28
6,39
6,51
6,65
6,77
6,87
6,98
7,10
7,20
8,79
8,91
9,03
9,15
9,26
10,04
10,16
10,32
10,45
10,58
12,31
12,50
12,68
12,86
13,09
PD
kW
15,98
16,92
17,89
18,86
19,86
19,15
20,17
21,23
22,34
23,42
21,50
22,65
23,91
25,24
26,58
23,47
24,73
26,05
27,44
28,90
29,21
30,78
32,39
34,09
35,78
33,79
35,57
37,35
39,24
41,17
41,95
44,23
46,60
48,99
51,61
PF
kW
10,47
11,26
12,09
12,93
14,00
12,73
13,63
14,55
15,47
16,37
14,14
15,11
16,19
17,36
18,51
15,38
16,50
17,63
18,76
20,01
18,84
20,17
21,57
23,02
24,50
21,84
23,36
24,92
26,57
28,26
27,64
29,50
31,58
33,69
35,90
45
PA
kW
5,21
5,29
5,39
5,48
5,47
6,10
6,19
6,28
6,36
6,44
6,93
7,04
7,16
7,28
7,42
7,50
7,60
7,72
7,83
7,93
9,80
9,92
10,04
10,16
10,28
11,23
11,35
11,48
11,58
11,68
13,76
13,96
14,12
14,31
14,49
PD
kW
15,68
16,55
17,48
18,41
19,47
18,83
19,82
20,83
21,83
22,81
21,07
22,15
23,35
24,64
25,93
22,88
24,10
25,35
26,59
27,94
28,64
30,09
31,61
33,18
34,78
33,07
34,71
36,40
38,15
39,94
41,40
43,46
45,70
48,00
50,39
RG66001006 - Rev.04
MCW - MCR
13
LIMITI DI FUNZIONAMENTO
13.1 LIMITI DI FUNZIONAMENTO MCW
I limiti indicati nel diagramma si riferiscono ad un uso continuativo della
macchina, senza impiego di acqua glicolata nel circuito dissipatore.
Per il funzionamento in raffreddamento fare riferimento al paragrafo precedente.
Tensione di alimentazione: ± 10% rispetto al valore nominale
I limiti di funzionamento riportati nei diagrammi sono validi per salti termici
dell’acqua da 3 a 8°C
Legenda:
Temperatura acqua in uscita dall'evaporatore
Twe2
Twc2
Temperatura acqua in uscita dal condenstore
Twc2
(°C)
45
40
Twe2
(°C)
13
9
30
Unità standard
10 12
Standard units
20 25
Twe1
(°C)
13.2 LIMITI DI FUNZIONAMENTO MCR
Tensione di alimentazione: ± 10% rispetto al valore nominale
I limiti di funzionamento riportati nei diagrammi sono validi per salti termici
dell’acqua da 3 a 8°C
Legenda:
Temperatura esterna a bulbo secco
Tbs1
Tw2
Temperatura uscita acqua
5
25
40 43
Twc2
(°C)
FUNZIONAMENTO IN RAFFREDDAMENTO
Per operare con temperature dell'acqua al condensatore inferiori ai 25 °C è
indispensabile adottare (optional) il dispositivo per il controllo di condensazione:
Il controllo mediante modulazione della portata acqua con una valvola a 2 vie
di tipo pressostatico o, per i modelli di taglia superiore, pilotata diretamente
dal microprocessore di bordo.
Nel caso sia necessario operare con temperature maggiori di 43°C e/o
raffreddare fluidi a temperature Twe2 maggiori di 13°C, si deve ricorrere alle
versioni ad R134a disponibili su richiesta, che elevano il limite di temperature acqua all'uscita del condensatore a + 60°C in funzionamento continuativo.
FUNZIONAMENTO IN RAFFREDDAMENTO
Per operare con temperature dell'aria inferiori ai 20 °C è indispensabile
adottare (optional) il dispositivo per il controllo di condensazione:
Il controllo mediante modulazione della velocità dei ventilatori con un
regolatore a taglio di fase permette il funzionamento in fase di raffreddamento
con temperature dell'aria esterna Tbs1 fino a -15 °C .
FUNZIONAMENTO IN RISCALDAMENTO
45
40
42
30
Tbs1
(°C)
20
Con controllo
di condensazione
10
0
Le unità in pompa di calore sono realizzate prevedendo lo scambiatore ad
acqua collegato in controcorrente nel funzionamento in raffreddamento. Per
esecuzioni che prevedono la produzione di acqua a temperatura Twc2
superiori ai valori indicati sono disponibili (optional) sia l’esclusiva inversione
di ciclo anche lato acqua che mantiene sempre il flusso in controcorrente,
sia l’esecuzione ad R134a disponibile a richiesta.
L’R134a è un fluido altobollente caratterizzato da basse pressioni d’esercizio,
che quindi richiede compressori con cilindrata maggiore (+60%) rispetto alle
versioni ad R407C a parità di portata in massa elaborata.
RG66001006 - Rev.04
-15
3
5
7
9
11 13 15
Tw2 (°C)
18
È severamente vietata la riproduzione anche parziale di questo manuale
17
19
MCW - MCR
14
FATTORI DI CALCOLO
Salto termico acqua diverso da 5
Salto termico acqua
Fattore correzione potenza resa
Fattore correzione potenza assorbita
Fattore correzione portata acqua
Fattore correzione perdita di carico
3
0,975
1
1,63
2,64
4
0,99
1
1,24
1,53
5
1
1
1
1
6
1,015
1
0,85
0,72
7
1,03
1
0,74
0,54
30%
-10°C
-18°C
0,989
1,14
1,585
40%
-15°C
-24°C
0,983
1,199
1,86
30%
-10°C
-18°C
0,971
1,07
1,532
40%
-15°C
-24°C
0,96
1,098
1,777
8
1,04
1
0,65
0,42
Funzionamento con miscele acqua-glicole etilenico
Percentuale glicole
Temperatura minima acqua prodotta
Temperatura congelamento miscela (°C)
Fattore correzione potenza resa
Fattore correzione portata acqua
Fattore correzione perdita di carico
0%
5°C
0°C
1
1
1
10%
2°C
-4°C
0,998
1,047
1,157
20%
-5°C
-14°C
0,994
1,094
1,352
Funzionamento con miscele acqua-glicole PROPILENICO
Percentuale glicole
Temperatura minima acqua prodotta
Temperatura congelamento miscela (°C)
Fattore correzione potenza resa
Fattore correzione portata acqua
Fattore correzione perdita di carico
0%
5°C
0°C
1
1
1
10%
2°C
-4°C
0,996
1,022
1,111
20%
-5°C
-14°C
0,985
1,043
1,307
FATTORI DI INCROSTAZIONE
Fattori di incrostazione (m2 °C / W)
Fattore correzione potenza resa
Fattore correzione potenza assorbita
15
4,4 x 10 -5 8,8 x 10 -5 17,6 x 10 -5
0,97
0,94
0,93
0,99
0,99
0,98
0
1
1
PREVALENZA UTILE POMPE
Nel diagramma sottoriportato sono indicate le prevalenze utili delle pompe,
al netto delle perdite di carico dello scambiatore lato utente, valide sia per
unità MCW sia MCR.
Pu
(kPa)
012
012
015
018
020/022
027
031
039
160
140
120
005
007
010
100
80
60
40
20
1,0
2,0
3,0
4,0
Qw (m3/h)
19
5,0
6,0
È severamente vietata la riproduzione anche parziale di questo manuale
7,0
8,0
RG66001006 - Rev.04
MCW - MCR
16
PERDITE DI CARICO LATO ACQUA
Il diagramma riporta le perdite di carico lato acqua pw in funzione della portata acqua Qw, riferite ad una temperatura media dell'acqua di 10°C
SCAMBIATORE DI CALORE LATO UTILIZZATORE MCW - MCR
Dpw
(kPa)
140
005
007
010
012
015
018
020
022
120
100
027
80
60
031
40
039
20
0
0
1000
2000
3000
4000
Qw (l/h)
5000
6000
7000
8000
9000
SCAMBIATORE DI CALORE LATO DISSIPATORE (SOLO MCW)
Dpw
(kPa)
005
140
010
007
012 015
018
020 - 022
027
031
039
120
100
80
60
40
20
0
0
RG66001006 - Rev.04
1000
2000
3000
Qw (l/h)
4000
5000
20
È severamente vietata la riproduzione anche parziale di questo manuale
6000
7000
MCW - MCR
17
CIRCUITO IDRAULICO LATO UTENTE
Nel realizzare il circuito idraulico per l’unità, è buona norma attenersi alle
seguenti prescrizioni e comunque attenersi alla normativa nazionale o locale.
Raccordare le tubazioni al refrigeratore tramite giunti flessibili al fine di evitare
la trasmissione delle vibrazioni e compensare le dilatazioni termiche.
Si consiglia d’installare sulle tubazioni i seguenti componenti:
- Indicatori di temperatura e pressione per la normale manutenzione e
controllo del gruppo.
Il controllo della pressione lato acqua consente di valutare la corretta
funzionalità del vaso d’espansione e d’evidenziare in anticipo eventuali
perdite d’acqua dell’impianto.
- Pozzetti sulle tubazioni d’ingresso ed uscita per i rilievi di temperatura, per
una visione diretta delle temperature d’esercizio.
- Valvole di intercettazione (saracinesche) per isolare l’unità dal circuito
idraulico.
- Filtro metallico (tubazione in ingresso) a rete con maglia non superiore
ad 1 mm, per proteggere gli scambiatori (utilizzo e dissipatore) da
scorie o impurità presenti nelle tubazioni.
- Valvole di sfiato, da collocare nelle parti più elevate del circuito idraulico,
per permettere lo spurgo dell’aria.
(Sui tubi interni macchina sono presenti delle valvoline di sfiato per lo
spurgo di bordo macchina: tale operazione va eseguita con il gruppo privo
di tensione).
- Rubinetto di scarico e ove necessario, serbatoio di drenaggio per permettere
lo svuotamento dell’impianto per le operazioni di manutenzione o le pause
stagionali. (Sul serbatoio d’accumulo optional è previsto un rubinetto di
scarico da 1”: tale operazione va eseguita con il gruppo privo di tensione).
E’ di fondamentale che l’ingresso dell’acqua avvenga in corrispondenza della
connessione contrassegnata con la scritta “Ingresso Acqua”
In caso contrario si correrebbe il rischio di gelare l’evaporatore, dal momento
che il controllo da parte del termostato antigelo verrebbe vanificato ed inoltre
non sarebbe rispettata la circuitazione in controcorrente nel funzionamento
in raffreddamento con ulteriori rischi di malfunzionamento
Il circuito idraulico deve essere realizzato in maniera tale da garantire la
costanza della portata d’acqua nominale (+/- 15%) all’evaporatore in ogni
condizione di funzionamento.
Sulle unità MCW-MCR è previsto di serie un dispositivo per il controllo della
portata dell’acqua (pressostato differenziale) sul circuito idraulico ,nelle
immediate vicinanze dell’evaporatore.
In caso di manomissione di tale dispositivo, la garanzia viene a decadere
immediatamente.
E’ vivamente consigliata l’installazione di una valvola di sicurezza sul circuito
idraulico. In caso di anomalie gravi nell’impianto (ad es. incendio) essa
permetterà di scaricare il sistema evitando possibili scoppi.
Collegare sempre lo scarico ad una tubazione di diametro non inferiore a
quello dell’apertura della valvola, e convogliarlo in zone nelle quali il getto non
possa recare danno alle persone.
Lo schema idraulico rappresenta un circuito idraulico tipo a cui è collegata
un'unità a MCW-MCR completa di gruppo di pompaggio e serbatoio di
accumulo esterni.
VI
VSM
AV
F
Tw
DP
FL
HV
GR
VE
VA
SFA
SA
VI
P
VI
AV
Tw
SIA
RS
RS
Legenda:
Legenda:
p
Descrizione
Pressostato differenziale lato acqua
P
Descrizione
Pompa di circolazione
HV
Evaporatore
AV
Antivibrante
FL
Flussostato
F
VSM
Filtro metallico
Valvola di sicurezza a molla
VE
Vaso di espansione a membrana
VA
Sfiato aria manuale
GR
Gruppo di riempimento
SIA
Serbatoio inerziale di accumulo
SA
Separatore aria
RS
Rubinetto di svuotamento
TW
Pozzetto rilevazione temperatura acqua
VI
Valvola di intercettazione
21
È severamente vietata la riproduzione anche parziale di questo manuale
RG66001006 - Rev.04
MCW - MCR
18
DIMENSIONI DI INGOMBRO MCW
1
2
3
4
5
6
7
8
9
10
Ingresso acqua condensatore (1 1/4" gas)
Uscita acqua condensatore (1 1/4" gas)
Ingresso acqua evaporatore (1 1/4" gas)
Uscita acqua evaporatore (1 1/4" gas)
Ingresso alimentazione elettrica
Serbatoio di accumulo
Manometri refrigerante (opzionali)
Controllo a microprocessore
Quadro elettrico
pompa di ricicolo
Dimensioni in mm
RG66001006 - Rev.04
VISTA DALL'ALTO
VISTA LATO DESTRO
VISTA DALL'ALTO
VISTA FRONTALE
VISTA POSTERIORE
VISTA FRONTALE
VISTA LATO SINISTRO
MCW 005 - 010
22
È severamente vietata la riproduzione anche parziale di questo manuale
MCW - MCR
18
DIMENSIONI DI INGOMBRO MCW
1
2
4
4
5
6
7
8
9
10
Ingresso acqua condensatore (1 1/4 " gas)
Uscita acqua condensatore (1 1/4 " gas)
Ingresso acqua evaporatore (1 1/4" gas)
Uscita acqua evaporatore (1 1/4" gas)
Ingresso alimentazione elettrica
Serbatoio di accumulo
Manometri refrigerante (opzionali)
Controllo a microprocessore
Quadro elettrico
pompa di ricicolo
Dimensioni in mm
VISTA DALL'ALTO
VISTA LATO DESTRO
VISTA FRONTALE
VISTA DALL'ALTO
VISTA POSTERIORE
VISTA FRONTALE
VISTA LATO SINISTRO
MCW 012 - 039
23
È severamente vietata la riproduzione anche parziale di questo manuale
RG66001006 - Rev.04
MCW - MCR
19
DIMENSIONI DI INGOMBRO MCR
MCR 005 - 010
RG66001006 - Rev.04
24
È severamente vietata la riproduzione anche parziale di questo manuale
Dimensioni in mm
MCW - MCR
19
DIMENSIONI DI INGOMBRO MCR
MCR 012 - 039
25
È severamente vietata la riproduzione anche parziale di questo manuale
Dimensioni in mm
RG66001006 - Rev.04
MCW - MCR
20
DRY COOLER
21
CONDENSATORE REMOTO
In abbinamento ai refrigeratori d’acqua condensati ad acqua ed alle
motoevaporanti è possibile abbinare DRY COOLER prodotti da LUVE
CONTARDO.
Nella tabella a fondo pagina sono riportati gli abbinamenti fra modelli di unità
galletti ed unità LUVE già selezionate per un ottimale funzionamento alle
condizioni nominali; per condizioni diverse dalle nominali, verificare
l’abbinamento con la sede.
Le versioni proposte sono:
- DRY COOLER in esecuzione standard, mandata aria orizzontale, completo
di interruttore ON/OFF e cablaggi.
- DRY COOLER in esecuzione standard completo di controllo di velocità,
mandata aria orizzontale, interruttore ON/OFF, sonda temperatura e
cablaggi.
- DRY COOLER in esecuzione standard, mandata aria verticale, completo
di kit gambe, interruttore ON/OFF e cablaggi.
- DRY COOLER in esecuzione standard completo di controllo di velocità,
mandata aria verticale, kit gambe, interruttore ON/OFF, sonda aria e
cablaggi.
- DRY COOLER in esecuzione silenziata, mandata aria orizzontale,completo,
di interruttore ON/OFF e cablaggi.
- DRY COOLER in esecuzione silenziata completo di controllo di velocità,
mandata aria orizzontale, interruttore ON/OFF, sonda temperatura e
cablaggi.
- DRY COOLER in esecuzione silenziata, mandata aria verticale, completo
di kit gambe, interruttore ON/OFF e cablaggi.
- DRY COOLER in esecuzione silenziata completo di controllo di velocità,
mandata aria verticale, kit gambe, interruttore ON/OFF, sonda temperatura
e cablaggi.
In abbinamento ai refrigeratori d’acqua condensati ad acqua ed alle
motoevaporanti è possibile abbinare CONDENSATORI REMOTI prodotti da
LUVE CONTARDO.
Nella tabella a fondo pagina sono riportati gli abbinamenti fra modelli di unità
galletti ed unità LUVE già selezionate per un ottimale funzionamento alle
condizioni nominali; per condizioni diverse dalle nominali, verificare
l’abbinamento con la sede.
Le versioni proposte sono:
- CONDENSATORE REMOTO in esecuzione standard, mandata aria
orizzontale, completo di interruttore ON/OFF e cablaggi.
- CONDENSATORE REMOTO in esecuzione standard completo di controllo
di velocità, mandata aria orizzontale, interruttore ON/OFF, sonda
pressione e cablaggi.
- CONDENSATORE REMOTO in esecuzione standard, mandata aria
verticale,completo di kit gambe, interruttore ON/OFF e cablaggi.
- CONDENSATORE REMOTO in esecuzione standard completo di controllo
di velocità, mandata aria verticale, kit gambe, interruttore ON/OFF, sonda
pressione e cablaggi.
- CONDENSATORE REMOTO in esecuzione silenziata, mandata aria
orizzontale, completo di interruttore ON/OFF e cablaggi.
- CONDENSATORE REMOTO in esecuzione silenziata completi di controllo
di velocità, mandata aria orizzontale, completo di interruttore ON/OFF,
sonda pressione e cablaggi.
- CONDENSATORE REMOTO in esecuzione silenziata, mandata aria
verticale,completi di kit gambe, interruttore ON/OFF e cablaggi.
- CONDENSATORE REMOTO in esecuzione silenziata completo di controllo
di velocità, mandata aria verticale, kit gambe, interruttore ON/OFF, sonda
pressione e cablaggi.
20.1 TABELLA ABBINAMENTO DRY COOLER
21.1 TABELLA ABBINAMENTO CONDENSATORE REMOTO
MODELLO
MCW CL
MCW HL
005
007
010
012
015
018
020
022
027
031
039
RG66001006 - Rev.04
Codice
Codice
MCR Condensatore remotoCondensatore remoto Alimentazione
MODELLO
flusso aria
flusso aria
elettrica
CS
verticale
orizzontale
V - ph - Hz
005
SHVN 7/7 H
SHVN 7/7 V
230-1-50 hz
007
SHVN 7/7 H
SHVN 7/7 V
230-1-50 hz
010
SHVN 13/9 H
SHVN 13/9 V
230-1-50 hz
012
SHVN 13/9 H
SHVN 13/9 V
230-1-50 hz
015
SHVN 20/4 H
SHVN 20/4 V
230-1-50 hz
018
SHVN 20/4 H
SHVN 20/4 V
230-1-50 hz
020
SHVN 23/2 H
SHVN 23/2 V
230-1-50 hz
022
SHVN 23/2 H
SHVN 23/2 V
230-1-50 hz
027
SHVN 38/1 H
SHVN 38/1 V
230-1-50 hz
031
SHVN 38/1 H
SHVN 38/1 V
230-1-50 hz
039
SHVN 46/5 H
SHVN 46/5 V
230-1-50 hz
Codice
Codice
MCR Condensatore remotoCondensatore remoto Alimentazione
MODELLO
CL
flusso aria
flusso aria
elettrica
verticale
orizzontale
V - ph - Hz
005
SHVS 8/2 H
SHVS 8/2 V
230-1-50 hz
007
SHVS 8/2 H
SHVS 8/2 V
230-1-50 hz
010
SHVS 18/0 H
SHVS 18/0 V
230-1-50 hz
012
SHVS 18/0 H
SHVS 18/0 V
230-1-50 hz
015
SHVS 18/0 H
SHVS 18/0 V
230-1-50 hz
018
SHVS 18/0 H
SHVS 18/0 V
230-1-50 hz
020
SHVS 27/1 H
SHVS 27/1 V
230-1-50 hz
022
SHVS 27/1 H
SHVS 27/1 V
230-1-50 hz
027
SHVS 36/0 H
SHVS 36/0 V
230-1-50 hz
031
SHVS 36/0 H
SHVS 36/0 V
230-1-50 hz
039
SHVS 48/1 H
SHVS 48/1 V
230-1-50 hz
Alimentazione
elettrica
V - ph - Hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
Alimentazione
elettrica
V - ph - Hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
230-1-50 hz / 400-3-50 hz
MONOCIRCUITO
005
007
010
012
015
018
020
022
027
031
039
Codice dry-cooler Codice dry-cooler
flusso aria
flusso aria
verticale
orizzontale
SHLR 15 M H
SHLR 15 M V
SHLR 15 M H
SHLR 15 M V
SHLN 24 D H
SHLN 24 D V
SHLN 24 D H
SHLN 24 D V
SHLN 24 D H
SHLN 24 D V
SHLN 29 L H
SHLN 29 L V
SHLN 30 D H
SHLN 30 D V
SHLN 30 D H
SHLN 30 D V
SHLN 50 C H
SHLN 50 C V
SHLN 50 C H
SHLN 50 C V
SHLN 58 D H
SHLN 58 D V
Codice dry-cooler Codice dry-cooler
flusso aria
flusso aria
verticale
orizzontale
SHLR 15 M H
SHLR 15 M V
SHLR 15 M H
SHLR 15 M V
SHLS 19 M H
SHLS 19 M V
SHLS 19 M H
SHLS 19 M V
SHLS 38 D H
SHLS 38 D V
SHLS 38 D H
SHLS 38 D V
SHLS 38 D H
SHLS 38 D V
SHLS 38 D H
SHLS 38 D V
SHLS 38 D H
SHLS 38 D V
SHLS 59 C H
SHLS 59 C V
SHLS 59 C H
SHLS 59 C V
MONOCIRCUITO
MONOCIRCUITO
MCW CS
MCW HS
MONOCIRCUITO
MODELLO
26
È severamente vietata la riproduzione anche parziale di questo manuale
MCW - MCR
21
CONDENSATORE REMOTO
21.2 DIMENSIONAMENTO DELLE LINEE FRIGORIFERE
PARAMETRI GENERALI
Il circuito frigorifero deve essere dimensionato seguendo 3 indicazioni
fondamentali:
-
1.
2.
3.
Refrigerante
Potenza frigorifera
T ev. - Dew Point
Linea gas 0-10m
Linea liquido 0-10m
Linea gas 11-20m
Linea liquido 11-20m
Linea gas 21-30m
Linea liquido 21-30m
21
-
Mantenere il più possibile contenute le perdite di carico del refrigerante
per evitare significativi cali di prestazioni.
Assicurarsi di avere la corretta quantità di olio sul ritorno anche nel
funzionamento ai carichi parziali quando la velocità del refrigerante
è ridotta. La perdita di carico depende dall'entità dell'attrito tra la
rugosità interna del tubo e il gas refrigerante e tale rugosità è anche
responsabile del trascinamento dell'olio. Il trascinamento dell'olio è
più critico sulla linea di aspirazione a causa delle basse tempearture
che ne aumentano la viscosità.
Evitare la formazione di "vapori di flash" sulla linea del liquido con
conseguente malfunzionamento della valvola di laminazione:
mantenere una velocità del liquido bassa per evitare picchi di
pressione durante la chiusura della valvola di espansione.
minima velocità del gas refrigerante per assicurare il trascinamento
dell'olio anche in tubazioni verticali, sulla linea del gas 4 m/s;
sulla linea del liquido, la miscibilità tra olio e refrigerante è totale (nel
campo dei limiti di funzionamento) e non occorre perciò rispettare
nessuna velocità minima.
R407C R407C R407C R407C R407C R407C R407C R407C R407C R407C R407C
kW
4-5
6-7
8-9
10-11,5 11,5-13 14-16 17-18 19-24 25-29 30-34 35-40
°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C 0/+10°C
[mm]
12
12
12
16
16
16
16
22
22
22
28
[mm]
10
10
10
12
12
12
12
16
16
16
18
[mm]
12
12
16
16
16
18
18
22
22
28
28
[mm]
10
10
12
12
12
12
12
16
16
18
18
[mm]
12
12
16
16
16
18
18
22
22
28
28
[mm]
10
10
12
12
12
12
12
16
16
18
18
CONDENSATORE REMOTO
21.3 CARATTERISTICHE TUBO REFRIGERANTE
Diametro
esterno
[mm]
10
12
16
18
22
28
35
42
54
Spessore
[mm]
1
1
1
1
1,5
1,5
1,5
1,5
2
Raggio
di curvatura
[mm]
36
36
46
56
67
96
70
84
108
Pressione
di progetto
[bar]
28
28
28
28
28
28
28
28
28
27
Categoria
tubi PED
 max.carico
unitario
 carico
effettivo
Coefficiente
di sicurezza
A3 P3
A3 P3
A3 P3
A3 P3
A3 P3
A3 P3
A3P3
A3P3
A3P3
[N/mm2 ]
227
227
227
227
227
227
227
227
227
[N/mm2 ]
11,2
14
19,6
21
17,3
23,3
29,8
36,4
35
20,3
16,2
11,6
10,8
13,1
9,8
7,6
6,2
6,4
È severamente vietata la riproduzione anche parziale di questo manuale
RG66001006 - Rev.04
MCW - MCR
21
CONDENSATORE REMOTO
21.4 ESEMPI DI COLLEGAMENTO
21.4.1 Condensatore remoto a monte della motoevaporante
RG66001006 - Rev.04
28
È severamente vietata la riproduzione anche parziale di questo manuale
MCW - MCR
21
CONDENSATORE REMOTO
21.4 ESEMPI DI COLLEGAMENTO
21.4.2 Condensatore remoto a valle della motoevaporante
29
È severamente vietata la riproduzione anche parziale di questo manuale
RG66001006 - Rev.04
MCW - MCR
22
POSIZIONAMENTO E SPAZI DI INSTALLAZIONE
E’ opportuno prestare attenzione ai punti seguenti per determinare il sito
migliore ove installare l’unità ed i relativi collegamenti:
dimensioni e provenienza delle tubazioni idrauliche;
ubicazione dell’alimentazione elettrica;
accessibilità per le operazioni di manutenzione o riparazione;
solidità del piano di supporto;
possibile riverbero delle onde sonore.
Tutti i modelli della serie MCW-MCR sono progettati e costruiti per installazioni
all'interno.
E’ consigliabile interporre tra il telaio di base ed il piano di appoggio un nastro
di gomma rigido.
Qualora si necessitasse di un isolamento più spinto è opportuno l’impiego
di supporti antivibranti a molla.
È necessario garantire gli spazi di servizio indicati nelle figure riportate di
seguito.
RG66001006 - Rev.04
30
È severamente vietata la riproduzione anche parziale di questo manuale
NOTE
www.galletti.it
40010 Bentivoglio (BO) Via Romagnoli 12/a Tel. 051/8908111 - Fax. 051/8908122