Download Installation Instructions and User Guide 15mm
Transcript
Installation Instructions and User Guide Domestic Valve Solutions 15mm & 22mm In-Line Thermostatic Mixing Valve Installation Instructions and User Guide 15mm & 22mm In-Line Thermostatic MixingP405UA Valve P405 and TMV3/TMV2 Combined P405 and P405UA TMV3 / TMV2 Combined It is important that these guidance notes are read and fully understood prior to product installation t is important that these guidance notes are read and fully understood prior to product installation The Pegler Yorkshire Model P405 mixing valve must be installed in accordance with the reg local water company and the Water Supply (Water Fittings) Regulations 1999. Approvals P405 When used as a TMV3 (TYPE3) valve: IMPORTANT INTRODUCTION NOTES The valves covered by these instructions have been tested and certified as being in compliance with BS 7942:2000 and NHS Estates Model Engineering Specification D 08. This product is certified under the BuildCert TMV3 scheme and has been independently tes the location of the mixing valve and should always be recognised test laboratory WRc-NSF and is a Water Regulations Advisory Scheme (WRAS) and listed in the Water Fittings and Materials Directory. inproduct an accessible location. Installation Before installation, the hot and cold water supply Separate isolation valves must be installed on the hot and cold water inlet supplies. To ens systems must bethermostatic thoroughly remove performance of the mixingflushed valve, the to isolating valvesany should preferably be ful always be fullythat open during operation. dirt/debris may have accumulated. Failure to do The mixing valve is supplied with filter elements but it is advisable to additionally install soY-strainers may adversely affect the performance of the on the hot and cold water supplies. The isolating valves and strainers should be close as valve. practicable to the location of the mixing valve and should always be in an accessib mixing Before installation, the hot and cold water supply systems must be thoroughly flushed to re Valves operating outside the requirements of these standards are not covered by the TMV3 Scheme and are not guaranteed to operate as Type 3 valves. alves The installer should be aware of his duty of care and responsibility in ensuring that compliance with regulations is maintained. The valve is not guaranteed to function correctly to the TMV3 specification unless it is installed and used in accordance with these instructions. Regular servicing is essential to ensure continued safe operation of this thermostatic mixing valve. The recommended service interval must be based on the operating outside these cold conditions can not valve response to the in-service water failure test results. This Pegler Yorkshire Model P405 in-line thermostatic dirt/debris that may have accumulated. Failure to do so may adversely affect the performa Conditions of normal Use mixing valve. CONDITIONS OF NORMAL USE Table 1 Table 1 Operating Range High Pressure Low Pressure Maximum static pressure - bar 10 10 Hot & cold flow pressure - bar 1.0 to 5 0.2 to 1 Hot supply temperature - °C 52 to 65 52 to 65 Cold supply temperature - °C 5 to 20 5 to 20 Minimum hot inlet to mixed outlet temperature differential =10°C Minimum hot inlet to mixed outlet temperature differential =10°C Note: Valves operating outside these conditions can be guaranteedby by the to operate as Type be not guaranteed theScheme Scheme to operate as Ty 3 valves. The highest flow rates will be achieved under balanced pressure conditions, but the pressure at the valve hest flow rates be achieved balanced pressure conditions, but the pressure at the val mixing valve,will available in 15mm andunder 22mm sizes, is inlets must be within a ratio of 5:1 under flow fittedof into5:1 applications ust be intended within toa beratio under where flowthe conditions and the and ofofpipework conditionssize and the sizelayout and layout pipework andand fitting reliable control of hot water temperature is necessary fittings must take this into account. ke this tointo account. prevent scalding. In the event of cold water supply failure, the product will shut off the hot water supply. FITTING Water regulations Before installation, the system operating conditions of inlet pressures, hot water temperature and hot and nstallation, theYorkshire system operating The Pegler Model P405 mixingconditions valve must be of inlet pressures, hot water temperature and hot a cold water flow rates should be determined and installed in accordance with the regulations of the ter flow rates should be determined and confirmed confirmed to be within thethe expected conditions of norm to be within expected conditions of local water company and the Water Supply (Water normal use. Fittings) Regulations 1999. Valves must operate in either a high pressure setting Approvals must operate in either a high pressure setting or a low pressure setting valves not or a low pressure setting valves are not are capable of capable o operation with, for instance hot water supply in on with, for instance hot water supply in one pressure range and cold water supply inone the other This product is certified under the BuildCert TMV3 pressure range and cold water supply in the other e range. In these it istested necessary boostrange. oneInpressure or reduce the other so scheme and has conditions been independently by the to eitherpressure these conditions it is necessary to recognised laboratory WRc-NSF and is a Water range. h supplies are test within a common pressure either boost one pressure or reduce the other so Regulations Advisory Scheme (WRAS) approved product and listed in the Water Fittings and Materials Directory. that both supplies are within a common pressure range. location of the mixing valve is important to ensure Correct that itlocation is accessible commissioning and of the mixingfor valve is important to Installation ensure that it is accessible for commissioning and g. servicing. Separate isolation valves must be installed on the hot • The valve body is and cold water inlet supplies. To ensure proper performance of the thermostatic valve,for the Cold and a clearly valve body is clearly marked mixing with ‘C’ blue marked with ‘C’ for Cold and a isolating valves should preferably be full bore and cator and ‘H’ for Hot and a red indicator. blue indicator and always be fully open during operation. ‘H’ for Hot and valve must be valve correctly connected to thebutrespective supplies. The mixing is supplied with filter elements a red indicator. The it is advisable to additionally install Y-strainers on the valve must be hot and cold water supplies. The isolating valves and correctly connected strainers should be installed as close as practicable to to the respective supplies. 2 use of sealing compounds must be avoided since they may intrude into the water supply and • The use of sealing compounds must be avoided since they may intrude into the water supply and impair the valve performance. Exploded view of angled valve assembly PRESSURE TAKE-OFF POINT PLUG The Pegler Model Yorkshire P405UA mixing valve is optionally p SEAL the tailpiece arrangement shown above. This allows the connec be parallel to the mixed water outlet for ease of piping layouts. HEADWORK non-return valves, filters, isolation valves and test points The Pegler Yorkshire Model P405 thermostatic mixing valve is supplied with the tail pieces, inlet filter screen and main body gasket seals separately located in the packing box. Each tail piece comprises: a housing with union nut and an internally fitted, WRAS approved non-return valve. SEAL The assemblies comprise an integral full bore ball valve and inFILTER MESH UNION this arrangement is used, the requirements for isolation valves UNION NUT SEAL regarded as fulfilled. Assembly Procedure ISOLATION VALVE HANDLE Exploded view of angled valve assembly • Unpack the main valve assembly and check that the bores are free of debris and the end sealing faces are clean. • Unpack the two tailpieces and confirm they are complete with union nuts and compression nuts and olives. • Locate the sealing gaskets, insert them into the union nuts against the faces of the tailpieces and screw the union nuts onto the valve until a tight seal has been made. • Remove the compression nuts and olives from the tailpieces. Locate the inlet filter screens and insert them into the bore of the tailpieces up to the shoulder. • Assemble the valve to the pipework and ensure the hot and cold water pipes have full penetration into the tailpiece. • Tighten the compression nuts ensuring that the end of the pipe remains in contact with the filter element. ISOLATION VALVE Application The Pegler Yorkshire Model P405 thermostatic mixing valve has been independently tested by WRc-NSF against the requirements of BS 7942:2000 and NHS D08APPLICATION and certified as complying with the requirements of the TMV3 Scheme and is suitable for use in the The Pegler Yorkshire Model P405 thermostatic mixing valve has been designations shown in the table below. the requirements of BS 7942:2000 and NHS D08 and certified as com Scheme and is suitable for use in the designations shown in the table Valves approved for designation for use ‘HP’ only:- If a water supplyfor is designation fed by gravityfor then the supply Valves approved use ‘HP’ only:- If a water s pressure should be verified to ensure the the conditions of of use are supply pressure should be verified to ensure conditions use are appropriate for the valve. Exploded viewpipe of tail pipe assembly Exploded view of tail assembly Table 2 – Required maximum set outlet temperatures commissioning. Table 2 – Requiredatmaximum set outlet temperatures at com Application Bidet Designation HP-B LP-B Maximum Set Mixed Water Temperature 38°C The Pegler Model Yorkshire P405UA mixing valve is Shower HP-S 41°C optionally withP405UA angled assemblies in lieu The Pegler Modelprovided Yorkshire mixing valve is of optionally provided with angled LP-S assemblies in lieu of the tailpiece arrangement shown above. This allows the tailpiece arrangement shown above. This allows the connections of the hot and cold water supplies Washbasin HP-W 41°C to the connections of the hot outlet and cold to layouts. The angled valve LP-Wassemblies incorporate be parallel to the mixed water forwater easesupplies of piping be parallel tofilters, the mixed water outlet easetest of piping non-return valves, isolation valvesforand points Bath* HP-T44 44°C layouts. The angled valve assemblies incorporate LP-T44 non-return valves, filters, isolation valves and test Bath* HP-T46 46°C points. (assisted) LP-T46 The assemblies comprise an integral fullfull bore strainer in an angled housing. When The assemblies comprise an integral boreball ballvalve and in-line *22mmonly only *22mm this arrangement is used, the in requirements for isolation valve and in-line strainer an angled housing. When valves and Y-strainers previously mentioned are regarded asarrangement fulfilled. is used, the requirements for this The range of available temperature adjustment is 35°C to 48°C BUT isolation valves and Y-strainers previously mentioned theThe terminal should never be set to a temperature tha range offitting available temperature adjustment is Exploded of angled valve assembly areview regarded as fulfilled. outlet for the application (Table 2). 35°Ctemperature to 48°C BUT the mixed water temperature at the terminal fitting should never be set to a Note: temperature that exceeds the maximum set outlet 46°C is the maximum recommended mixed water temperature from t temperature for the application (Table 2). 3 takes account of the allowable temperature tolerances inherent in the losses in metal baths. 46°C is not a safe bathing temperature for adults or children. Note: • • 46°C is the maximum recommended mixed water temperature from the bath tap. The maximum temperature takes account of the allowable temperature tolerances inherent in thermostatic mixing valves and temperature losses in metal baths. 46°C is not a safe bathing temperature for adults or children. Bath* HP-T44 44°C The British Burns Association recommends 37°C to LP-T44 37.5°C Bath* as a comfortable HP-T46 bathing temperature 46°C for children. In premises (assisted) LP-T46 covered by the Care Standards Act 2000, the maximum mixed water outlet temperature *22mm only is 43°C. using a close fitting spanner, reduce the mixed outlet temperature by turning clockwise. increase the mixed water outlet temperature by turning counter clockwise. When the valve has been installed with the correct conditions of use it is advised that the valve is subjected to exercise prior to the commissioning at the application temperature. With hot and cold water flowing through the valve, operate the valve from full cold to full hot at least three times. With the valve at the full cold position bring the valve to the correct application temperature by turning the spanner counter clockwise. If the valve overshoots thisthe temperature, returntemperature the valve to theatfull cold The range of available temperature mixed water COMMISSIONING (TMV 3) adjustment is 35°C to 48°C BUT condition, and the resetmaximum it to the correct the terminal fitting should never be set to a temperature that exceeds set temperature +0-2°C. Do not set a valve on a lowered temperature valve must be under (Table normal site outlet The temperature forcommissioned the application 2). as this will not provide consistent operation. system conditions and after establishing supply Note: conditions with the hot and cold water supplies open, When set maximum to the required temperature for the systemrecommended running to allow temperatures and 46°C is leave the maximum mixed water temperature from the the bathvalve tap.isThe temperature the applicationmixing carry out 5 cold isolation tests takes account ofto the allowable valves andwater temperature pressures stabilise and temperature be checked. tolerances inherent in thermostatic to further exercise the valve. losses in metal baths. commissioning, thefor following 46°C isPrior nottoa commencing safe bathing temperature adults or children. Commissioning Test sequence checks should be carried out. The British Burns Association recommends 37°C to 37.5°C as a comfortable bathing temperature for children. adjust thebring temperature water in • Thecovered designation of the thermostatic valve maximum In premises by the Care Standards mixing Act 2000, the mixed water outlet is 43°C. With the valve at the fullAfter cold position thetemperature valveoftothe themixed correct application tempera accordance withovershoots the valve application (see Table matches the application. spanner counter clockwise. If the valve this temperature, return the valve to 2) and the carry out the following sequence: COMMISSIONING (TMV 3)and temperaturescondition, • The supply pressures are withinand reset it to the correct temperature +0-2°C. Do not set a valve on a lower 1.Record the temperature of the hot and cold water this will not provide consistent operation. the operating range of the valve. supplies. The valve must be valves commissioned under site system conditions and after establishing • Isolating and strainers are normal provided. When set to2.Record the system required temperature forthe the application therunning temperature of mixed water carry at theout 5 cold wa supply conditions with the hot and water supplies open,is leave the to allow temperatures • The supply temperatures arecold within the rangethe valve to further largest draw-off flow rate. and pressures to stabilise checked. permitted for the and valvebeand by guidance exercise the valve. 3.Record the temperature of the mixed water flow information on the prevention of legionella etc. Commissioning Testbe sequence carried at a smaller Prior to commencing commissioning, the following checks should out. draw-off flow rate, which shall be measured. If all these conditions are met, proceed to set the After adjust temperature of thethe mixed accordance with thevalve valve application 4.Isolate cold water water in supply to the mixing • temperature The designation of the below. thermostatic mixing valvethe matches the application. as described The Pegler Yorkshire 2) and the carry out the following sequence: and range monitor • model The supply pressures and temperatures are within the operating ofthe themixed valve.water temperature recording P405 thermostatic mixing valve is supplied 1. Record the temperature of the hot and cold water supplies. the maximum temperature achieved and the final • factory Isolating set valves at 43°Cand but strainers the valve are mayprovided. be simply 2. Record the temperature of the mixed water at the largest draw-off flow stabilised temperature. • adjusted The supply forthe the valve and bythe guidance information aftertemperatures installation. are within the range permitted 3. Record temperature of mixed water flow at a smaller draw-off fl 5.Record the equipment, thermometer etc. used for on the prevention of legionella etc which shall be measured. thethe measurements. If all these conditions met, proceed to set the temperature as described below. The mixed waterare temperature at the terminal fitting 4. Isolate cold water supply to the mixing valve and monitor the mixed Note:factory The final stabilised should not and the fina The Pegler model thermostatic mixing valve temperature is supplied setthe at maximum 43°C temperature but temperature the valve may mustYorkshire never exceed theP405 maximum temperature recording achieved exceed the values in Table 3. be simply adjusted after installation. setting for the particular application (See Table 2). temperature. 5. Record the equipment, etc. used for the measurements. The mixed temperature at the terminal fitting must never exceed thermometer the maximum Note, water It is not possible to install one thermostatic Note: The final stabilised temperature should not exceed the values in Table3 temperature setting for the particular application (See Table 2). 3 Note, It is to not possible to install mixing valve to supply two differing applications Table – Guide maximum stabilised one thermostatic mixing valve tohigher supply two differing applications unlessrecorded the temperature unless the temperature of the setting is temperatures during of the higherlimited settingtoisthat limited thatapplication. of the lower application. commissioning of thetolower Table 3 – Guide to maximum stabilised temperatures recorded during comm • •Remove capon ontop topofofthe the valve with the supplied Allen key or other suitable tool. Removethe the plastic plastic protective protective cap Application Mixed water temperature °C valve with the supplied Allen key or other suitable Bidet 40 tool. o using a close fitting spanner, Shower 43 reduce theWashbasin mixed outlet 43 temperature turning Bath by (44°C fill) 46 clockwise. Bath (46°C fill) 48 o increase the mixed water outlet temperature by turning counter clockwise. 4 After correct commissioning secure the protective cap u supplied screw. The Pegler Yorkshire model P405 is sup two protective caps. One blue TMV 3 cap and one whit Ensure that the blue colour TMV 3 cap is fitted as this w Bath (46°C fill) 48 With an acceptable mixed water temperature complete the Commissioning test sequence detailed above. If the final mixed water temperature is greater than the values in Table 3 and/or the maximum After correct commissioning secure temperature the protective cap theThe corresponding from the previous supplied exceeds screw. Pegler value Yorkshire model P405 is s test results by more than about 2°C the need for two protective caps. One blue TMV 3 cap service work is indicated (see TMV servicing and and one wh cleaning Ensure that theinstructions). blue colour TMV 3 cap is fitted as thi the valve has been commissioned to the TMV 3 stand In-service tests should be carried out with a frequency which identifies a need for service work before an unsafe water temperature can result. Frequency of in-service testing 6 to 8 weeks after commissioning carry out the test sequence detailed above. AfterIn correct commissioning secure(TMV the protective Service Testing 3) cap 12 to 15 weeks after commissioning carry out the test using the supplied screw. The Pegler Yorkshire model sequence detailed above. P405 is supplied with two protective caps. One blue ofTMV in-service testing monitor andobtained, recordthethe performance o Depending on the results following TMVThe 3 cap purpose and one white 2 cap. Ensure that theis to regularly of actions mustcan be followed: bluethermostatic colour TMV 3 cap is fitted as valve. this will indicate the mixing Deterioration incourse performance indicate the need for serv valve has been commissioned to the TMV 3 standard. valve and/or water supplies. • If no significant changes (e.g.<1 °C) in mixed water temperature are recorded between In Service Testing (TMV 3) using commissioning and testing at 6 to 8 weeks,equipment or Carry out the test sequence detailed below the same or equivalent as between commissioning and testing at 12 to The purpose of in-service testing is to regularly commissioning the valve. 15 weeks, the next in-service test can be deferred monitor and record the performance of the to 24 to 28 weeks after commissioning. thermostatic mixing valve. Deterioration in • If small changes (e.g.1 to the 2 °C)application. in mixed water performance can indicate the need for service • Check the designation of work the on thermostatic valve matches temperature are recorded in only one of the valve and/or water supplies. • Check that the supply pressures and temperatures are within the operating range these periods, necessitating adjustment of the mixed water temperature, then the next inservice Carry out the test sequence detailed below using test can be deferred to 24 to 28 weeks after the same or equivalent equipment as used for commissioning. commissioning the valve. • If small changes (e.g.1 to 2 °C) in mixed water temperature are recorded in both of these • Check the designation of the thermostatic valve periods, necessitating adjustment of the mixed matches the application. water temperature, then the next in-service • Check that the supply pressures and temperatures test should be carried out at 18 to 21 weeks after are within the operating range of the valve. commissioning. • Check that the supply temperatures are within the • If significant changes (e.g. >2 °C) in mixed water range permitted for the valve and by guidance temperature are recorded in both of these information on the prevention of legionella etc periods, necessitating service work, then the next • Check there have been no significant changes in in-service test should be carried out at 18 inlet supply temperatures and pressures since to 21 weeks after commissioning. commissioning or the previous in service test. The general principle to be observed after the first If significant changes have occurred it is 2 or 3 in-service test is that the intervals of future recommended to re-commission the valve. tests should be set to those which previous tests have shown can be achieved with no more than a If the mixed water temperature has changed small change in mixed water temperature. significantly from the previous test results (e.g.>1°C), It is recommended that In-Service Tests are carried record the change and before re-adjusting the mixed out once every 6 months as a minimum. water temperature carry out the following checks; Note: • All in-line or integral strainers are clean • Any in-line or integral non-return valves or other anti-backsiphonage devices are in good working order. • Any isolation valves are fully open. 5 If there is a residual flow during the commissioning or in service test during the cold water supply isolation test then this is acceptable providing the temperature of the water seeping from the valve is no more than 2°C above the designated maximum mixed water outlet temperature setting of the valve as defined in Table 2. The mixing valve is supplied with filter elements but it is advisable to additionally install Y-strainers on the hot and cold water supplies. The isolating valves and strainers should be installed as close as practicable to the location of the mixing valve and should always be in an accessible location. Temperature readings should be taken at the normal flow rate after allowing the system to stabilise. The sensing part of the thermometer probe must be fully submerged in the water that is to be tested. Any TMV that has been adjusted or serviced must be re-commissioned and re-tested in accordance with the manufacturer’s instructions. Before installation, the hot and cold water supply systems must be thoroughly flushed to remove any dirt/debris that may have accumulated. Failure to do so may adversely affect the performance of the mixing valve. P405 When used as a TMV2 (TYPE 2) Valve IMPORTANT INTRODUCTION NOTES The valves covered by these instructions have been tested and certified as being in compliance with BS EN 1111:1999 and BS EN 1287:1999. Valves operating outside the requirements of these standards are not covered by the TMV2 Scheme and are not guaranteed to operate as Type 2 valves. CONDITIONS OF NORMAL USE CONDITIONS OF NORMAL USE Table 4 Table 4 Operating Range Maximum static pressure - bar Hot & cold flow pressure - bar Hot supply temperature - °C Cold supply temperature - °C Mixed water temperature - °C BS EN 1111 High Pressure 10 1.0 to 5 55 to 65 ≤ 25 Maximum 46 BS EN 1287 Low Pressure 10 0.1 to 1 55 to 65 ≤ 25 Maximum 46 The installer should be aware of his duty of care and responsibility in ensuring that compliance with regulations is maintained. The valve is not guaranteed Minimum hot inlet to mixed outlet temperature differential =10°C Minimum hot inlet to mixed outlet temperature to function correctly to the TMV2 specification Note: Valves operating outside these conditions can not be guaranteed by the Scheme to operate as T unless it is installed and used in accordance with 2 valves. differential =10°C these instructions. Regular servicing is essential to The highest flow rates will be achieved under balanced pressure conditions, but the pressure at the va Note: Valves outside these conditions can ensure continued safe operation of this thermostatic inlets must be within a ratio operating of 5:1 under flow conditions and the size and layout of pipework and fittin must take this into account. not be guaranteed by the Scheme to operate as Type mixing valve. The recommended service interval is no 2 valves. FITTING greater than 12 months. This Pegler Yorkshire Model P405 in-line thermostatic mixing valve, available in 15mm and 22mm sizes, is intended to be fitted into applications where the reliable control of hot water temperature is necessary to prevent scalding. In the event of cold water supply failure, the product will shut off the hot water supply. Water regulations The Pegler Yorkshire Model P405 mixing valve must be installed in accordance with the regulations of the local water company and the Water Supply (Water Fittings) Regulations 1999. Approvals This product is certified under the BuildCert TMV2 scheme and has been independently tested by an approved testing laboratory WRc-NSF and is a Water Regulations Advisory Scheme (WRAS) approved product and listed in the Water Fittings and Materials Directory. Before installation, the system operating conditions of inlet pressures, hot and cold inlet temperature a hot and cold flow rates should be determined confirmedunder to be within the expected condition Thewater highest flow rates will be and achieved balanced of normal use shown in Table 4. pressure conditions, but the pressure at the valve Valves must operate in either high pressure setting a lowunder pressureflow setting. These valves are not inlets must be awithin a ratio ofor5:1 capable of operation with, for instance hot water supply in one pressure range and cold water supply theconditions size and pipework and the other conditions pressure range.and In these it is layout necessaryof to either boost one pressure or reduce th other so that both supplies within a common pressure range. fittings mustare take this into account. If your water supply cannot meet these conditions then the valve cannot be guaranteed to operate as Type 2 valve. FITTING Operating pressures above 5.0 Bar will require the installation of a pressure reducing valve. Correct location of the mixing valve is important to ensure that it is accessible for commissioning and servicing. Before installation, the system operating conditions of inlet pressures, hot and cold inlet temperature and The valve body is clearly marked with ‘C’ for Cold and a blue hotand and flow rates should be determined indicator, ‘H’ cold for Hotwater with a red indicator. The valve must be correctly connected to the respective supplies. and confirmed to be within the expected conditions of normal use shown in Table 4. • • The use of sealing compounds must be avoided since they may intrude into the water supply an impairValves the valvemust performance. operate in either a high pressure setting • The valve must be so installed that it is readily accessible for commissioning and maintenance wh beingcapable installed in of accordance with TMV2. operation with, for instance hot water • The valve must be installed with isolation valves on both the hot and cold water systems as close possible the valve; so as to allow the valve be commissioned and it tested theto other pressure range. In to these conditions is correctly. or a low pressure setting. These valves are not supply in one pressure range and cold water supply in necessary either pressure orwater reduce thetherefore in-line The valve is suppliedto with integralboost strainersone on the hot and cold supplies strainers should be required. other sonotthat both supplies are within a common • pressure range. If your water supply cannot meet these conditions then the valve cannot be guaranteed to operate as a Type 2 valve. Installation Separate isolation valves must be installed on the hot and cold water inlet supplies. To ensure proper performance of the thermostatic mixing valve, the isolating valves should preferably be full bore and always be fully open during operation. Operating pressures above 5.0 Bar will require the installation of a pressure reducing valve. Correct location of the mixing valve is important to ensure that it is accessible for commissioning and servicing. 6 Exploded view of tailpiece assembly • The valve body is Exploded view of tail pipe assembly ld and a clearly blue marked with ‘C’ for Cold and a blue indicator and ‘H’ for Hot and spective supplies. a red indicator. The valve must be correctly connected to the respective supplies. The Pegler Yorkshire Model P405UA mixing valve is since they may intrude into the water supply and The Pegler Model Yorkshire P405UA mixing valve is optionally p optionally provided with angled assemblies in lieu of the tailpiece arrangement shown above. This allows the connec the tailpiece arrangement shown above. This allows be parallel to the mixed water forwater easesupplies of piping the connections of the hot outlet and cold to layouts. non-return valves, filters, isolation valves and test points be parallel to the mixed water outlet for ease of g valve is supplied with the tail pieces, inlet filter piping layouts. ed in the packing box. • The valve must be so installed that it is readily The assemblies comprise an integral full bore ball accessible forfitted, commissioning andapproved maintenance non-return valve and in-line strainer in an angled housing. When and an internally WRAS when being installed in accordance with TMV2. The assemblies comprise an integral full borefor ball valve and inthis arrangement is used, the requirements isolation valves and strainers previously mentioned are valves this arrangement is used, the requirements for isolation • The valve must be installed with isolation valves on regarded regarded as fulfilled. as fulfilled. both the hot and cold water systems as close as possible to the valve; so as to allow the valve to be Exploded ofvalve angled valve assembly Exploded view of view angled assembly commissioned and tested correctly. • The use of sealing compounds must be avoided since they may intrude into the water supply and impair the valve performance. PRESSURE TAKE-OFF POINT PLUG that the bores are free of debris and the end sealing are • The valve is supplied with integral strainers on the hot and cold water supplies therefore in-line complete nuts and compression strainerswith shouldunion not be required. SEAL nuts HEADWORK • Thenuts valve is fitted with integral “listed” non-return the union against the faces of the tailpieces and valve cartridges which command the water supply, tight seal has been made. valve is protected therefore the thermostatic against cross-flow due to unbalanced line pressures and om the tailpieces. Locate the inlet filter screens as required by the Water Supply (Water Fittings) p to the shoulder. Regulations 1999. sure the hot and cold water pipes have full ISOLATION SEAL FILTER MESH UNION NUT UNION SEAL VALVE HANDLE Assembly Procedure the end of the pipe remains in contact with the filter • Unpack the main valve assembly and check that the bores are free of debris and the end sealing faces APPLICATION ISOLATION VALVE are clean. • Unpack the two tailpieces and confirm they areThe Pegler Yorkshire Model P405 thermostatic mixing valve has been complete with union nuts and compression nuts the requirements of BS 7942:2000 and NHS D08 and certified as com and olives. Scheme and is suitable for use in the designations shown in the table • Locate the sealing gaskets, insert them into the APPLICATION union nuts against the faces of the tailpieces and Valves approved for designation for use ‘HP’ only:- If a water s screw the union nuts onto the valve until a tight Theshould Pegler Yorkshire Model thermostatic mixing of use are supply pressure be verified to P405 ensure the conditions seal has been made. valve has been independently tested by WRc-NSF • Remove the compression nuts and olives from the against the requirements of BS EN 1287 (Low Pressure tailpieces. Locate the inlet filter screens and LP) and BS EN 1111 (High Pressure-HP) and insert them into the bore of the tailpieces up to the certified as complying with the requirements of the shoulder. TMV2 Scheme and is suitable for use in the maximum set outlet temperatures at com • Assemble the valve to the pipework and ensureTable the 2 – Required designations shown in the table (next page). hot and cold water pipes have full penetration into Application Designation Maximum Mixed the tailpiece. Valves approved for designation for Set use ‘HP’ only:Water Temperature • Tighten the compression nuts ensuring that the end If a water supply is fed by gravity then the supply of the pipe remains in contact with the filter Bidet pressureHP-B should be verified to ensure38°C the conditions element. of use are appropriate for the valve. LP-B Shower Washbasin 7 HP-S LP-S HP-W LP-W 41°C 41°C APPLICATION The Pegler Yorkshire Model P405 thermostatic mixing valve has been independently tested by WRc-NSF against the requirements of BS EN 1287 (Low Pressure-LP) and BS EN 1111 (High Pressure-HP) and certified as complying with the requirements of the TMV2 Scheme and is suitable for use in the designations shown in the table below. • Remove the plastic protective cap on top of the valve with Table 5 – Recommended set mixed water outlet temperatures o using reduc temp clock Valves approved for designation for use ‘HP’ only:- If a water supply is fed by gravity then the supply pressure should be verified to ensure the conditions of use are appropriate for the valve. Table 5 – Recommended set mixed water outlet temperatures Pressure Application Shower Wash basin Bidet Bath (Tub) 15mm HP HP HP HP 22mm HP and LP HP and LP HP and LP HP Maximum set mixed water temperature 41°C 41°C 38°C 44°C o increa outle clock The above temperatures are recommended by the Thermostatic Mixing Valve (manufacturers) Association as relevant settings for the varying applications shown. This is the maximum commissioning temperature but valves may exceed this by 2°C in use. The range of available temperature adjustment is 35°C to 48°C but 46°C is the maximum recommended mixed water temperature from a bath tap. The maximum temperature takes account of the allowable temperature tolerances inherent in thermostatic mixing valves and temperature losses in metal baths. 46°C is not a safe bathing temperature for adults or children. The above temperatures are recommended by the Thermostatic Mixing Valve (manufacturers) Association as relevant settings for the varying applications • using a close fitting When the valve has beenspanner, installedreduce with the the correct conditions o shown. This is the maximum commissioning mixed prior outlettotemperature by turningatclockwise. the commissioning the application tempe temperature but valves exceed this by 2°C in use. The British Burns Association recommends 37°C may to 37.5°C as a comfortable bathing temperature for children. to exercise In premises covered by the Care Standards Act 2000, the maximum mixed water outlet temperature is 43°C. • increase the mixed water outlet by to full hot at through the valve, operate the valvetemperature from full cold COMMISSIONING (TMV 2) turning counter clockwise. The range of available temperature adjustment is The valve35°C must be to commissioned under46°C normal site conditions and after establishing 48°C but is system the maximum recommended supply conditions with the hot and cold water supplies open, leave the system running to allow temperatures When the valve has been installed with the correct and pressures to stabilise and be checked. mixed water temperature from a bath tap. The conditions of use it is advised that the valve is maximum temperature takes of the Prior to commencing commissioning, the following checksaccount should be carried out. allowable subjected to exercise prior to the commissioning at temperature inherent inthethermostatic • The designation of thetolerances thermostatic mixing valve matches application. • The supply pressures and temperatures are within the operating range of the valve. the application temperature. With hot and cold water mixing valves and temperature losses in metal baths. • Isolating valves and strainers are provided. flowing through the valve, operate the valve from full 46°C is not a safe bathing temperature for adults If all these conditions are met, proceed to set the temperature as described below. cold to full hot at least three times. or children. The Pegler Yorkshire P405 thermostatic mixing valve is supplied factory set at 43°C but the valve may be simply adjusted after installation. The set mixed water temperature at the terminal fitting must never exceed 46°C • With the valve at the full cold position bring the valve to the correct application temperature by turning the spanner counter clockwise. If the valve overshoots this temperature, return the valve to the full cold condition, and reset it to the correct temperature +0-2°C. Do not set a valve on a lowered temperature as this will not provide consistent operation. The British Burns Association recommends 37°C to 37.5°C as a comfortable bathing temperature for children. In premises covered by the Care Standards Act 2000, the maximum mixed water outlet temperature is 43°C. Remove the plastic protective cap on top of the valve with the supplied Allen key or other suitable tool. COMMISSIONING (TMV 2) The valve must be commissioned under normal site system conditions and after establishing supply conditions with the hot and cold water supplies open, leave the system running to allow temperatures and pressures to stabilise and be checked. When the valve is set to the required temperature for the application carry out 5 cold water isolation tests to further exercise the valve. • Set the mixed water temperature to the required value. It is advisable to use a calibrated digital thermometer for checking the inlet and outlet temperatures. Prior to commencing commissioning, the following checks should be carried out. • • • The designation of the thermostatic mixing valve matches the application. The supply pressures and temperatures are within the operating range of the valve. Isolating valves and strainers are provided. If all these conditions are met, proceed to set the temperature as described below. • Measure and record the temperature of the hot and cold water supplies at the inlets to the valve. • Measure and record the temperature of the water discharging from the valve at the greatest draw-off flow rate. • In the absence of other temperatures being specified those detailed in Table 5 are the desired settings. The Pegler Yorkshire P405 thermostatic mixing valve is supplied factory set at 43°C but the valve may be simply adjusted after installation. The set mixed water temperature at the terminal fitting must never exceed 46°C Once the required mixed outlet temperature has been achieved, isolate the cold water supply and monitor and record the mixed water temperature including the maximum and final temperatures achieved. The mixed water temperature should never exceed 46°C. • Remove the plastic protective cap on top of the valve with the supplied Allen key or other suitable tool. 8 Once the required mixed outlet temperature has been achieved, isolate the cold monitor and record the mixed water temperature including the maximum and achieved. Thesecure mixed water temperature should exceed 46°C.the After correct commissioning the protective Isolate the coldnever water supply and RECORD cap using the supplied screw. The Pegler Yorkshire Model P405 is supplied with two protective caps. One blue TMV 3 cap and one white TMV 2 cap. Ensure that the white colour TMV 2 cap is fitted as this will indicate the valve has been commissioned to the TMV 2 standard. maximum temperature achieved. After 5 seconds, if water is still flowing RECORD the temperature of the flow. Restore the cold water supply and RECORD the stabilised mixed water outlet temperature. • If there is no significant change to the stabilised set outlet temperature (±2°C or less deviation from the original setting) and the fail safe shut-off is functioning, then the valve is working correctly and no further service work is required. After correct secure theexceeds protective ca • If thecommissioning maximum mixed water temperature supplied screw. The Yorkshire Model P405 is the previous testPegler results by more than 2°C then the need for service the valve is indicated. protective caps. One work blueonTMV 3 cap and one white that the•white colour TMV 2 cap is fitted The equipment used in these In-Service Tests as this will should be RECORDED to andthe should preferably be the has been commissioned TMV 2 standard. same as that used at installation. Note: If there is a residual flow during the commissioning Record all the equipment used during commissioning. the annual verification (cold water supply isolation Record all the equipment used during or commissioning. test) then this is acceptable providing the temperature of the water seeping from the valve is no more than 2°C above the designated maximum mixed water outlet temperature setting of the valve (See Table 5). In Service testing (TMV 2) The Pegler Yorkshire Model P405 thermostatic mixing valve will provide satisfactory service and a high level of protection, provided it is maintained and subjected to In-Service Testing. Temperature readings should be taken at the normal flow rate after allowing the system to stabilise. The sensing part of the thermometer probe must be fully submerged in the water that is to be tested. Any TMV that has been adjusted or serviced must be re-commissioned and re-tested in accordance with the manufacturer’s instructions. Approximately 6-8 weeks after commissioning, the following tests should be undertaken. • Check the temperature of the hot and cold water supplies - RECORD • Check the temperature of the mixed water temperature at the greatest draw off flow rate – RECORD • Check there have been no significant changes in inlet supply temperatures and pressures since commissioning or the previous in service test. If significant changes have occurred it is recommended to re-commission the valve. In the absence of any other instruction or guidance, it is recommended that In-Service Tests are carried out once every 12 months as a minimum. If the temperature is outside of the expected range it will be necessary to remove and clean the valve in accordance with the following instructions. TMV Cleaning and Servicing Instructions (TMV 2 & TMV 3) If the mixed water temperature has significantly changed from that measured at installation (e.g. > 1°C), RECORD the change and before making any adjustments to the valve confirm that:- Most domestic water supplies contain calcium which will separate out when the water is heated in a system. The degree and speed of scaling may vary depending on factors such as water flow rates, system design, the hardness of the water and the temperature to which the water is heated. Deposits of scale may over time form in the valve, particularly at the hot inlet. The formation of the scale may adversely affect the performance of the valve which will be detected during the in-service testing. If this occurs it will be necessary to remove the valve for de-scaling and servicing. • Strainer elements in the hot and cold water supplies are clean and undamaged. • Non-return valves are clean and operating correctly. • Isolation valves are operating correctly and are set in the fully open position. If the mixed water temperature is acceptable, the following additional observations should be made:- 9 30.0° • Isolate the hot and cold supply. • Remove the valve to a clean working area. • Remove the protective cap. • Unscrew the headwork of the valve. • Carefully remove the element and valve assembly and put to one side. • Remove the main spring and flow guide and carefully put to one side. • Inspect the components for contamination or damage. • Clean or replace as necessary • Remove the two o rings • Clean the valve body and headwork using a propriety de-scaler • Thoroughly rinse the body and headwork in clean water. • Carefully fit new o rings from the service kit taking care to ensure they are not damaged and are correctly located. • Lubricate the o rings with the lubricant provided. • Re-fit the flow guide and spring lubricating the flow guide around the greatest diameter with the lubricant provided • Lubricate the shuttle valve with the lubricant provided • Re-fit the shuttle valve and element assembly. • Re-fit the headwork ensuring correct tightening • Re-fit the valve assembly • If after cleaning the valve, and replacing the o ring seals, the valve does not function correctly, it may be necessary to replace the thermal element. 2 1 3 7 A-1 4 A-2 6 A-1 A-2 B C D E F G Exploded view of TMV assembly Spare part order code 854550 854551 854447 854454 854449 (15mm), 854450 (22mm) 854451 (15mm), 854452 (22mm) 854456 (15mm), 854457 (22mm) 854455 (15mm), 817012 (22mm) Description Blue TMV 3 Protective cap complete with screw White TMV 2 Protective cap complete with screw Hexagon key Service kit Tailpiece Strainer kit Angle valve strainer kit Sealing washer Wafer Strainer For genuine spares and technical assistance contact:Pegler Yorkshire St Catherine’s Avenue Doncaster South Yorkshire DN4 8DF PRESSURE TAKE-OFF POINT PLUG SEAL Tel: Fax: HEADWORK SEAL FILTER MESH UNION NUT 4 5 UNION SEAL ISOLATION VALVE HANDLE ISOLATION VALVE Spares In order to ensure that the Model P405 thermostatic mixing valve continues to provide satisfactory service, only GENUINE Pegler Yorkshire spare parts must be used. 10 01302 560560 01302 560206 Our brands: UK Sales Free Phone: 0800 156 0010 Free Fax: 0808 156 1011 Email:[email protected] Export Tel: +44 (0) 1302 855 656 Fax: +44 (0) 1302 730 513 Email:[email protected] Technical Help Free Phone: 0800 156 0050 Free Fax: 0808 156 1012 Email:[email protected] Brochure Hotline Free Phone: 0800 156 0020 Free Fax: 0808 156 1011 Email:[email protected] www.pegleryorkshire.co.uk Pegler Yorkshire Group Limited St. Catherine’s Avenue, Doncaster, South Yorkshire, DN4 8DF, England. Tel: 0844 243 4400 Fax: 0844 243 9870 Also available from Pegler Yorkshire: LUXURY TAP SOLUTIONS Registered in England Company No. 00401507 Registered Office: Haigh Park Road, Stourton, Leeds, West Yorkshire, LS10 1RT, England. All brand names and logo styles are registered trademarks. Maintaining a policy of continual product development, Pegler Yorkshire reserves the right to change specifications, design and materials of products listed in this leaflet without prior notice. code ref: 02499185