Download Installation Manual SCC Care Ovens
Transcript
Installation Manual Safety instructions Explanations of the icon's Danger! Immediate dangerous situation, that can endanger severe injury or death Warning! Possibly dangerous situation, that possibly can endanger severe injury or death. Attention! Possibly dangerous situation, that can endanger minor injury. Corrosive substances Fire hazard! Danger of burning! Attention: Inobservance can cause material damages. Tips and tricks for installation V11 -2- Danger! High voltage. Caution danger of life Inobservance can endanger severe injury or death. Safety instructions Warning! Wrong installation, service, maintenance or cleaning as well as unauthorized changes on the unit can cause damages, injuries or even death. Read the installation manual carefully before installing the unit. This unit may only be used for preparing food in commercial kitchens. Every other usage is against definition and therefore dangerous. Warning! Only gas units - If the unit is installed underneath an extraction hood, it must be made sure that the hood is switched on during operation of the unit – Waste gases! - If the gas unit is connected to a chimney, it must be made sure that the exhaust line will be cleaned on a regular basis subject to local regulations – Fire hazard! (For this purpose also contact the installer) - Don't put any material on the exhaust pipes of the unit – Fire hazard! - The area underneath the unit may not be blocked or closed by any material– Fire hazard! - The unit may only be operated in a calm environment – Fire hazard! Safety measures in case of smell of gas: - Immediately close the gas supply. - Don't touch any electrical switching element - ventilation of the room. - Avoid open flame or sparks - Use an external telephone and inform your local gas authority (in case the local gas authority can not be reached inform the operation centre of the fire brigade). -3- V11 Dear customer The warranty excludes glass damage, light bulbs and sealing material as well as damage caused by improper use, installation,maintenance, repair by untrained/unqualified personnel and scaling of components We reserve the right to make technical changes in the interest of progress! Quote in the event of a query: Dealer Appliance model: Appliance no.: ______________________________________ Installer Set to gas type: ______________________________________ Your appliance was checked by: Safety stickers „Max. rack height for containers with liquid“ are in the Starter Kit. After Installation of the unit, this sticker has to be fixed to the unit in a height of 1600 mm (see examples) 1600 (63") 1600 (63") ______________________________________ Warning To avoid scalding, do not use loaded containers with liquids or cooking goods which becomes fluid by heating in higher levels than those which can be easily observed. (DIN: IEC 60335-2-42) Danger of scalding! V11 -4- Installation instructions Attention: The named standards are valid for Germany. In all other countries follow the local standards and valid instructions. Damages based on installation not complying with the directives given hereunder are not covered by warranty terms. The requisite connections (water, electricity, gas) must only be carried out by suitably qualified technicians in compliance with local regulations. Check for any transport damage. Should there be any signs of transport damage, inform your dealer/freight forwarder immediately! Dumping of old units. At the end of its service life, the unit must not be disposed of with the general waste and must not be placed in the recycling containers at local authority collection points. We will be happy to help you with the disposal of your unit. First time commissioning valid for SelfCooking® Center with CareControl When commissioning your new, intelligent SelfCooking Center® for the first time, you will be asked to start an automatic self test. The duration of this self test is approximately 15 minutes and is necessary to adapt the SelfCooking Center® to the specific environmental conditions. Fire hazard! Remove packing material, starter kit as well as containers and grids from intereior cabinet. 11:30 m s 11:29 m s Start Start close cabinet door Press Start-key, Self test is running, remaining running time is shown Leave hinged racks respectively mobile oven racks inside the cabinet, Interior cabinet door must not be opened during the complete process of the self test. Opening the interior cabinet door interrupts the self test and when switching on the unit the next time you will be asked to start the self test again. This procedure does not apply to Combi Master units. -5- V11 Table of content Installation Manual Safety instructions Safety instructions Dear customer Installation instructions Table of content Table of content Transport of units Recommended minimum clearance Installation type 6x1/1, 6x2/1, 10x1/1, 10x2/1 GN Installation type 6x1/1, 6x2/1, 10x1/1, 10x2/1 GN Installation Type 20x1/1 GN, 20x2/1 GN Levelling mobile oven racks 20x1/1 and 20x2/1 GN Electrical connection Electrical connection Water connection CareControl Water connection Selection of water filter Selection of water filter Gas connection pictures Gas connection Gas connection / Gas consumption Drain connection Ventilation, technical data, heat emission Option Option Option Mobile floor models 20x1/1GN and 20x2/1GN Mobile floor models 20x1/1GN and 20x2/1GN Mobile floor models 20x1/1GN and 20x2/1GN Mobile floor models 20x1/1GN and 20x2/1GN Mobile floor models 20x1/1GN and 20x2/1GN Mobile floor models 20x1/1GN and 20x2/1GN Connected loads in accordance with VDE Guideline Conversion tables V11 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 -6- Table of content Schematic drawing 6x1/1 GN CareControl Schematic drawing 6x1/1 GN Gas CareControl Schematic drawing 6x2/1 GN CareControl Schematic drawing 6x2/1 GN Gas CareControl Schematic drawing 10x1/1 GN CareControl Schematic drawing 10x1/1 GN Gas CareControl Schematic drawing 10x2/1 GN CareControl Schematic drawing 10x2/1 GN Gas CareControl Schematic drawing 6x1/1 GN Schematic drawing 6x1/1 GN Gas Schematic drawing 6x2/1 GN Schematic drawing 6x2/1 GN Gas Schematic drawing 10x1/1 GN Schematic drawing 10x1/1 GN Gas Schematic drawing 10x2/1 GN Schematic drawing 10x2/1 GN Gas Schematic drawing 20x1/1 GN Schematic drawing 20x1/1 GN Gas Schematic drawing 20x2/1 GN Schematic drawing 20x2/1 GN Gas Schematic drawing 20x1/1 GN Electric, mobile Schematic drawing 20x1/1 GN Gas, mobile Schematic drawing 20x2/1 GN Electric, mobile Schematic drawing 20x2/1 GN Gas, mobile 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 -7- V11 Transport of units Transport of units Transport of units using a pallet 1 6x1/1 GN: 920mm/36 1/4" 6x2/1 GN: 1120mm/44 1/8" 10x1/1 GN: 920mm/36 1/4" 10x2/1 GN: 1120mm/44 1/8" Transport of units without a pallet, 20x1/1 GN and 20x2/1 GN units only. Put a piece of wood between pallet jack and left guide rail of the trolley pic. 3, 4 Attention Make sure that the unit is secured against tilting, when transporting it. 2 20x1/1 GN: 950mm/37 1/2" 20x2/1 GN: 1150mm/45 1/4" 3 20x1/1 GN: 920mm/36 1/4" 20x2/1 GN: 1140mm/45" Remove all containers/mobile oven racks from the cabinet. For floor model, remove corner mountings from the pallet. Take unit off the pallet. Attention Observe the weight of the units. Use carrying aid to avoid injuries. Wear safety boots. Weight see technical data on page 24 Observe door height pic. 5 X= Required door width when transporting units without pallet: 6x1/1GN 840 mm (33 1/8”) 6x2/1GN 1040 mm (41”) 10x1/1GN 840 mm (33 1/8”) 10x2/1GN 1040 mm (41”) 20x1/1GN 920 mm (36,1/4”) 20x2/1GN 1140-mm (45“) 4 5 20x1/1 GN / 20x2/1 GN: 1900mm/75" Center of Gravity F r o n t V11 pic. 1,2 D o o r /1GN) X (6x1/1 - 20x2 2x2", 50x50mm -8- Recommended minimum clearance 1 Minimum clearance left/ right/ rear 50 mm (2”) (except floor models). pic. 1 50mm/2" 50mm/2" 50mm/2" On floor models (20x1/1 GN and 20x2/1 GN) there must be a minimum clearance of 500 mm (approx 20”) on the left side of the unit, for installing the power cable Minimum clearance when there are heat sources on the left-hand side is 350 mm (14”). pic 2 2 Attention: A safety shut down can occur if the ambient temperature on the left hand side of the unit is too high. Option: Heat shield see page 25 ≥ 350mm 14" 3 50mm/2" 500mm/ 20" 50mm/2" We recommend a distance of 500 mm (20”) on the left hand side of the unit for carrying out maintenance work. pic. 3 Attention: - Do not install deep fat fryer at the rear side of the unit. - The units must only be installed in frost-free rooms. -9- V11 Installation type 6x1/1, 6x2/1, 10x1/1, 10x2/1 GN Because of safety reasons table units shall only be installed on original stands of the manufacturer. In this case the maximum rack height is 1600 mm (63") 1 2 A 6x1/1 /10x1/1 GN: 745,5mm (29 3/8") 6x2/1 10x2/1 GN: 965,5mm (38") A 64,5mm 2 5/8" 64,5mm 2 5/8" If Gas units are installed on a table or on the kitchen floor (combi duo) then: a) press the retaining plates (ET-No.:12.00.519) into the lower part of the pedestal and fasten with the enclosed nuts. b) the plate must be fitted to the surface using either screws and dowels or studs and nuts or the special adhesive. pic. 1 The retaining plates are not included in the scope of supply Attention: The centre height of the drain pipe is 63 mm (2 1/2”). When installing combi duo observe the drain height of the bottom unit. + _ 10mm 5006.0213 3 + _ 10mm Option: Using 110 mm (4 3/8”) legs and height adjustable transport trolley for extended space underneath unit. See page 25 Stands for gas appliances must be fixed to the floor using the fixing set part no.: 8700.0317 either with screws and dowels, or with the special adhesive supplied. pic. 2 Fixing set is not included in the scope of supply, Slide the stand into the fixing brackets and level it. Place the unit on the stand. The feet of the unit must be secured by means of the locating pins of the stand pic. 3 4 V11 Ensure that the unit is level - 10 - pic. 4 Installation type 6x1/1, 6x2/1, 10x1/1, 10x2/1 GN 1 Attention: If the unit is mounted on a mobile stand or base cabinet, the unit must be additionally secured against slipping by a chain or cable in order to prevent damage to the electricity, water or gas supply line. pic. 1 2 Only valid for SelfCooking Center with CareControl produced as of 28.09.2008: At the bottom side of the SelfCooking Center a cover over the care pump is installed. This cover is secured in the upper position during transportation. If the SelfCooking Center will be installed on a table or on base cabinet then the cover must be lowered. - Loose the screw at the front side of this cover pic. 2 - Cover must lay on the table respectively on the top of the base cabinet. pic. 3 3 - 11 - V11 Installation Type 20x1/1 GN, 20x2/1 GN Installation type 20x1/1 GN, 20x2/1 GN Ensure that the unit is level 1 pic. 1 Fix the floor locks, (supplied with the fixing set) to the floor with either screws and pins or with the special adhesive. pic. 2 Next slide the unit into the floor locks pic. 2 The mobile oven rack must be level when standing inside the unit pic. 3 2 Attention: Observe height of the drain pipe + _ 10mm Option: Using leg extension for more space underneath unit. Install height extension for mobile oven rack see page 26 A 20x1/1 GN: 732,5 mm / 28 7/8" 20x2/1 GN: 937,5 mm / 37" A 64,5mm 2 5/8" 64,5mm 2 5/8" 5006.02 13 3 V11 - 12 - Levelling mobile oven racks 20x1/1 and 20x2/1 GN If the floor is not level, an access ramp (not supplied) will be required. The incline must not exceed 4°. pic. 1,2 1 Warning: If the incline exceeds 4°, hot cooking liquid can slop out of the cooking containers. Danger of scalding! Attention: An incorrect levelled trolley can cause malfunction during operating the unit (e. g. during Cleanjet) 2 Option: Access ramp see page 26 If there is a drain grill in front of the floor unit, a ramp should be placed over it to enable the mobile oven rack to be used. pic. 3 max 4 3 - 13 - V11 Electrical connection 1 5 mm 2 L 1 L 2 L 3 N Danger Observe local regulations and standards during installation General information see next page Electrical units s¬ ¬%ACH¬APPLIANCE¬REQUIRES¬AN¬INDEPENDENT¬FUSED¬ power supply line s¬ ¬!¬PERMANENT¬ELECTRICAL¬CONNECTION¬MUST¬BE¬ provided for the units. Units manufactured as of 01.08.2007 can either be connected permanent or by using a plug s¬ ¬4ABLE¬UNITS¬8¬'.¬¬8¬'.¬ARE¬ equipped with a power cable, which is directly connected to the main contactor. The cable comes without plug and is approx. 2,5 m (8 ft) long. Warning Observe colour coding of the wires. Wrong connection can cause electric shock 3 4 V11 Attention: Wrong connection can cause damages (e. g. fan motor) s¬ #OLOUR¬CODING¬OF¬WIRES¬ yellow/green = earth blue = neutral brown, grey or black = Phase L1, L2, L3 s¬ ¬&LOOR¬UNITS¬8¬'.¬AND¬8¬'.¬ARE¬ delivered without power cable s¬ ¬4HE¬MAIN¬CONTACTOR¬TABLE¬UNITS¬AND¬THE¬MAIN¬ terminals (floor models) are located in the electrical compartment and are accessible after removing the left side panel. pic. 1/2 - 14 - Electrical connection Gas units s¬ ¬7E¬RECOMMEND¬AN¬INDEPENDENT¬FUSED¬POWER¬ supply line. s¬ ¬!¬PERMANENT¬ELECTRICAL¬CONNECTION¬MUST¬BE¬ provided for the units. s¬ ¬!LL¬UNITS¬ARE¬EQUIPPED¬WITH¬A¬POWER¬CABLE¬WITHout plug, approx. 2,5 m (8 ft) long. s¬ 4HE¬MAIN¬TERMINALS¬ARE¬LOCATED¬IN¬THE¬ELECTRICAL¬ compartment and are accessible after removing the left side panel. pic. 1/2 s¬¬5NIT¬SHOULD¬BE¬CONNECTED¬TO¬A¬FUSED¬SPUR¬ observe local electrical regulations s¬ !TTENTION Observe polarity of the mains! No burner function with wrong polarity! s¬ ¬/NSITE¬INSTALLATION¬PROVIDE¬ACCESSIBLE¬ALLPOLE¬ disconnection device with a minimum of a 3 mm contact gap. s¬ ¬4HE¬CIRCUIT¬DIAGRAM¬IS¬LOCATED¬BEHIND¬THE¬HINGED¬ control panel. s¬ 3PECIAL¬VOLTAGES¬AVAILABLE¬ON¬REQUEST s¬ ¬4HE¬CROSSSECTION¬OF¬THE¬POWER¬CABLES¬MUST¬BE¬ based on the current consumption and on local regulations. s¬ !PPLICABLE¬STANDARDS¬%.¬¬)%#¬ s¬ &OR¬ELECTRICAL¬CONNECTION¬DATA¬SEE¬PAGE¬ s¬¬"EFORE¬DISCONNECTING¬OR¬RECONNECTING¬UNIT¬%NSURE¬ electrical supply is isolated. For appliance connections, precise dimensions and connection points, see pages 36 and following. Warning Observe colour coding of the wires. Wrong connection can cause electric shock Attention: Wrong connection can cause damages (e. g. fan motor) s¬ ¬#OLOUR¬CODING¬OF¬THE¬POWER¬CABLE¬ yellow/green = earth, blue = Neutral brown, grey or black = Phase L1 (L2) Gas and electrical units s¬ ¬4HE¬STUD¬FOR¬THE¬EARTH¬BONDING¬IS¬LOCATED¬ON¬ the bottom side, underneath the control panel. Connect the wire for the earth bonding to this stud. pic. 3/4 General information: s¬ ¬&OLLOW¬THE¬INSTALLATION¬INSTRUCTIONS¬AND¬THE¬ information on the rating plate when connecting the unit. s¬ ¬#OMPLY¬WITH¬ALL¬LOCAL¬REGULATIONS¬AND¬STANDARDS s¬ ¬7E¬RECOMMEND¬AN¬INDEPENDENT¬FUSED¬POWER¬ supply line for each appliance. s¬ ¬5NITS¬MUST¬BE¬CONNECTED¬TO¬AN¬EARTH¬LEAKAGE¬ circuit breaker. Power cable : s¬ ¬4HE¬EXCHANGE¬OF¬THE¬POWER¬CABLE¬MAY¬ONLY¬BE¬ carried out by the manufacturer, his service agents or similar qualified personal Electrical units s¬ ¬#ONNECT¬AN¬(2.&¬SUPPLY¬CABLE¬MINIMUM¬ tighten the cable gland and the strain relief s¬ #ONNECT¬THE¬SUPPLY¬AS¬FOLLOWS Grey terminal: L1, L2, L3 (non-phase-sequence-dependent) Blue terminal: Neutral (only 3N AC) Yellow/green terminal: Earth connection Gas: s¬ ¬5NITS¬THE¬POWER¬CABLE¬HAS¬TO¬BE¬EXCHANGED¬A¬ power cable with the following minimum quality has to be used: H05 RN-F 3x2,5 mm2 s¬)F¬THE¬GAS¬UNIT¬X¬¬X¬'.¬IS¬PROTECTED¬ by means of a safety cut-out it must observe that this cut-out is at least of characteristic “C”. - 15 - V11 Water connection CareControl 6x1/1GN - 10x1/1GN E/G 1 3 2 1 6x2/1GN - 10x2/1GN E/G 2 3 1 2 Legend to water connections valid for: pic. 1/2 - SelfCooking Center table units with CareControl manufactured as of 28.09.2008: 1 = Common water supply 3/4” cold water 30°C/86°F In case of split water connection 2 = Cold water supply 3/4” (for quenching and hand shower 30°C/86°F). 3 = Treated water connection 3/4” (steam generator, moistening, cleaning, max. 60 °C/140°F). Legend to water connections valid for: pic. 3 - SelfCooking Center floor units with CareControl manufactured as of 28.09.2008: 1 = Common water supply 3/4” cold water max. 30°C/86°F In case of split water connection 2 = Cold water, max 30°C/86°F, connection 3/4” (quenching) 3 = Treated water connection 3/4” (steam generator, moistening, hand shower, max 60°C/140°F) 20x1/1GN - 20x2/1GN E/G s¬ ¬)NSTALL¬INDIVIDUAL¬SHUTOFF¬VALVE¬FOR¬EACH¬APPLIANCE 3 s¬ ¬2INSE¬THE¬WATER¬SUPPLY¬LINE¬PRIOR¬TO¬CONNECTION¬TO¬ the unit! s¬ ¬#ONNECTED¬WATER¬PRESSURE¬MUST¬BE¬IN¬THE¬RANGE¬ 150 kPa - 600 kPa, recommended 300 kPa 3 1 2 Maximum flow rate for each unit 6x1/1, 10x 1/1: 20 l/min 6x2/1, 10x2/1, 20x1/1, 20x2/1: 25 l/min Average total water consumption is as follows (values excluding usage of hand shower) Unit size: 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 12,0 l/h 32 l/h 25,2 l/h 41,4 l/h 49,8 l/h 60,0 l/h V11 - 16 - Water connection Note: The manufacturer recommends especially on model Combi Master a preventive check of your equipment 6 months after installation to determine actual scale build up. This should be done by a trained technician. 4 3 1 Water treatment: For filter selection see pages 18/19 Treated water with a water hardness less than 6 °e may not be supplied, because such water can react aggressive and corrosive which can reduce the life cycle of the unit. 2 5 Connecting SelfCooking Center to water with hardness less than 8,75°e: To avoid an excessive build up of foam the soft water switch should be set to "ON" in the basic settings. This can be done by a trained technician. 3 2 1 In most cases it is not necessary to install a filter or water treatment for water supply. The integrated SC-automatic changes the water in the steam generator at regular intervals automatically. However under certain water conditions different filter applications (A, B, C, D see page 18) might be necessary. 6 2 3 1 Legend to water connections valid for: pic. 4-6 - SelfCooking Center without CareControl: - Combi Master Floor models pic. 4 Table models electric pic. 5 Table models gas pic. 6 1 = Common water supply 3/4” cold water max. 30°C/86°F In case of split water connection 2 = Cold water, max 30°C/86°F, connection 3/4” (quenching) 3 = Treated water connection 3/4” (steam generator, moistening, hand shower, max 60°C/140°F) - 17 - V11 Selection of water filter Please consult your local water supply board for advise on chlorine (Cl2), chloride (Cl-) and hardness of the water 1 30C/86F A)Particle filter pic. 1/2 When the water contains sand, iron particles or suspended matter, we recommend a 5-15 μm (micro meter) particle filter: 300 kPa 43,5 psi F I L T E R 300 kPa 43,5 psi max. 60C/140F B)Active carbon filter pic. 1/2 When the level of chlorine (Cl2) in the water exceeds 0.2 mg/l (= ppm) (information available from the water company), an active carbon filter should be installed. 30C/86F 300 kPa 43,5 psi 2 2 3 150-600kpa 21,75-87 psi R 3/4" R3/4" 150-600kpa 21,75-87 psi 3/4" 1/2" 1/2" A C)Complete De-Ionization pic. 1/2 When the water has a chloride Cl- concentration above 70 mg/l (= 70 ppm), a complete deionization system should be installed to avoid corrosion. Note: Make sure a minimum conductivity of 50 μS/cm (micro Siemens) remains in the water. B C D 3/4" max. 60°C max. 140°F D)Water softener: pic. 1/2 Valid for SelfCooking Center with CareControl These models will remove scale all by itself providing that the units are used as prescribed. These means a water softener is not needed. Valid for SelfCooking Center without CareControl and Combi Master: A water softener is recommended when a high level of scale (not containing chloride) is experienced. Systems recommended: H+ Ion Exchanger. Sodium ion exchangers (as used in dishwashers) must not be used. Treated water with a water hardness less than 6 °e may not be supplied, because such water can react aggressive and corrosive which can reduce the life cycle of the unit. Amongst others the following filter manufacturers offer adequate filter applications: Brita, Falk. V11 - 18 - Selection of water filter Important for treated water connection: Split the water supply to standard and treated water connection for each unit to extend filter capacity! See pictures 1/2/3 page 16 Remove T-connection at water inlet Connect cold untreated water to inlet position “2” Connect treated water to inlet position “3” Filter capacity: Average treated water consumption is as follows (values excluding usage of hand shower) 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 3,0 l/h 8 l/h 6,3 l/h 10,4 l/h 12,5 l/h 15,0 l/h Maximum flow rate 16 l/min Important for filter connection: Water supply hose / pipe size 1/2” minimum Connection to filter : 3/4” If a combination of filters is fitted, the sequence A-B and C or D of the filters in the direction of flow must be observed pic. 2 - 19 - V11 Gas connection pictures 1 6x1/1 GN: 3/4" 6x2/1 GN: 3/4" 10x1/1 GN: 3/4" 10x2/1 GN: 3/4" 5 RATIONAL ! mbar 6 2 20x1/1 GN: 3/4" 20x2/1 GN: 3/4" ! mbar 7 3 4 180 mm 7 1/4” V11 - 20 - Gas connection Important! To ensure that the burner settings made at the factory conform with the actual installation conditions, the waste gas (C0, C02) from the steam and hot-air burners must be analysed during commissioning. The corresponding values must be documented inside the unit. If the undiluted C0 values are above 1000 ppm, the burner settings must be checked and if necessary adjusted by engineers trained and certified by the company. Warning Incorrect connection can engender fire hazard! Comply with local gas authority regulations! Follow installation instructions! s¬ ¬#HECK¬THAT¬THE¬GAS¬TYPE¬SUPPLIED¬IS¬SUITABLE¬FOR¬ the unit. s¬ ¬4HE¬DIAMETER¬OF¬THE¬PIPE¬MUST¬COMPLY¬WITH¬LOCAL¬ regulations s¬ ¬)NNER¬THREAD¬OF¬GAS¬CONNECTION¬ PIC¬ s¬ ¬'AS¬STOP¬VALVE¬SUPPLIED¬FOR¬EACH¬UNIT s¬ ¬'AS¬CONNECTION¬WITH¬GAS¬OUTLET¬SOCKET¬IS¬ possible. s¬ ¬!LL¬GAS¬SUPPLY¬CONNECTORS¬MUST¬COMPLY¬WITH¬LOCAL¬ regulations. s¬ ¬4HE¬UNIT¬MUST¬BE¬SECURED¬AGAINST¬MOVEMENT s¬ ¬#HECK¬THE¬GAS¬SUPPLY¬LINE¬FOR¬LEAKAGE¬ PIC¬ Attention: s¬ ¬4HE¬UNIT¬IS¬ONLY¬TO¬BE¬CONNECTED¬TO¬THE¬GAS¬ supply by a locally approved gas installer. It is vital to ensue that the gas connection pipes as well as the connection pipes for the associated gas metering systems match the stipulated pipe widths. s¬ ¬)F¬THE¬FLOW¬PRESSURE¬DEVIATES¬FROM¬THE¬SPECIFIED¬ flow pressure (see table), inform the gas authorities. If the flow pressure of natural gas exceeds 30 mbar (12,04 in w. c.), the unit must not be switched on and the gas supply must be disconnected. s¬¬¬Attention: The gas parts are designed for a maximum flow pressure of 65 mbar (26,09 in w. c.) Type A3, B13, B23 gas unit A3: Ambient-air-dependent gas-powered cooking range with fan assisted burners without exhaust collector. For UK market can be used when replacing similar equipment in kitchens where instal- lation of the air inlet/extraction was prior to September 2001 & providing there is a documented risk assessment to ensure that there will always be sufficient make-air and extraction available when running the equipment. Please observe Current Gas Regulations. B13 Ambient-air-dependent gas-powered cooking range with fan assisted burners with exhaust collector. B23 Ambient-air-dependent gas-powered cooking range with fan assisted burners without exhaust collector. s¬¬!UTOMATIC¬DIRECT¬IGNITION¬WITH¬IGNITION¬MONITOR Installation of draft diverter pic. 4 The draft diverter is not shipped with the unit, but can be ordered under the following part numbers: Unit size: Art. Nos.: 6x1/1 GN 70.00.396 6x2/1 GN 70.00.398 10x1/1 GN 70.00.397 10x2/1 GN 70.00.399 20x1/1 GN 70.00.400 20x2/1 GN 70.00.401 Gas exhaust system s¬¬4HE¬MINIMUM¬CLEARANCE¬TO¬THE¬CEILING¬OF¬THE¬ exhaust pipes is 200 mm s¬¬#HECK¬THAT¬GAS¬EXHAUST¬PIPES¬ARE¬LEAK¬PROOF¬IN¬ accordance with local regulations s¬¬7ASTE¬GAS¬PIPES¬OF¬ALUMINIUM¬OR¬OTHER¬MATERIALS¬ which are not resistant to temperatures up to 200°C should not be used because of the high waste gas temperatures! Gas exhaust system can be connected to the following: (observe your local regulations) 1. Extractor hood pic. 5 2. Fan roof pic. 6 3. Directly into the flue pic. 7 - 21 - V11 Gas connection / Gas consumption Room ventilation Warning The rooms in which these appliances are installed must be well ventilated, in order to prevent an unacceptable build-up of harmful combustion products. Danger of suffocation! We recommend to service the gas units at least once a year in accordance with the specified standards Gas consumption Gas type Required flowpressure Nat. gas H G20 Nat. gas L G25 18-25 mbar 20-30 mbar LPG G30 LPG G31 25-57,5 mbar 25-57,5 mbar Gas type Required flowpressure Nat. gas H G20 Nat. gas L G25 18-25 mbar 20-30 mbar LPG G30 LPG G31 25-57,5 mbar 25-57,5 mbar Wobbe index (15°C, 1013mbar) Wi Ws MJ/m3 MJ/m3 45,67 50,72 37,38 41,52 MJ/m3 MJ/m3 80,58 87,33 74,75 81,19 Wobbe index (15°C, 1013mbar) Wi Ws MJ/m3 MJ/m3 45,67 50,72 37,38 41,52 MJ/m3 MJ/m3 80,58 87,33 74,75 81,19 max. consumption on nominal heat load 6x1/1 GN 11 kW 1,2 m3/h 1,4 m3/h 12 kW 1,01 kg/h 1,04 kg/h 6x2/1 GN 21,5 kW 2,3 m3/h 2,6 m3/h 23 kW 1,93 kg/h 2,03 kg/h 10x1/1 GN 21,5 kW 2,3 m3/h 2,6 m3/h 23 kW 1,93 kg/h 2,03 kg/h max. consumption on nominal heat load 10x2/1 GN 32 kW 3,4m3/h 3,9 m3/h 34 kW 2,86 kg/h 3,01 kg/h 20x1/1 GN 43 kW 4,6 m3/h 5,3 m3/h 46 kW 3,86 kg/h 4,05 kg/h 20x2/1 GN 64 kW 6,8 m3/h 7,9m3/h 67 kW 5,63 kg/h 6,03 kg/h Exhaust gas- and room volume Unit size Room size free ventilation Room size permanent ventilation Combustion air supply Waste gas volume Waste gas temperature 6x1/1 GN 44,0 m3 22,0 m3 17,6 m3/h 31,4 m3/h 310°C 6x2/1 GN 86,0 m3 43,0 m3 34,4 m3/h 81 m3/h 450°C 10x1/1 GN 86,0 m3 43,0 m3 34,4 m3/h 76,6 m3/h 490°C 10x2/1 GN 128,0 m3 64,0 m3 51,2 m3/h 116 m3/h 460°C 20x1/1 GN 172,0 m3 86,0 m3 68,8 m3/h 140,6 m3/h 390°C 20x2/1 GN 256 m3 128 m3 102,4 m3/h 233.3 m3/h 465°C Free ventilation = Combustion air supply through windows and doors Permanent ventilation = Combustion air supply by two openings to the outside with a free cross section of 150 cm2 (one opening near the ceiling, the other opening near the floor) Attention: Data are calculated under German standards Room size free ventilation = 4 x Kilowatt power of the unit (e. g. unit 6x1/1 GN: 11KW x 4 = 44 m3) Room size permanent ventilation = 2 x Kilowatt power of the unit (e. g. unit 6x1/1 GN: 11KW x 2 = 22 m3) Combustion air supply = 1,6 x Kilowatt power of the unit (e. g. unit 6x1/1 GN: 11KW x 1,6 = 17,6 m3/h) Observe local regulation/standards for calculating the values! V11 - 22 - Drain connection 1 200-300mm (8 - 12 “) 3x45° 250-300mm (10 - 12 “) min. 3° / 5% Ø 50mm (2”) max. 1m (3 ft.) 2 min. 3° / 5% Ø 50mm (2”) 70mm (2 3/4“) max. 1m (3 ft.) 3 s¬ ¬4HE¬APPLIANCE¬COMPLIES¬WITH¬THE¬RELEVANT¬ regulations (DVGW, SVGW, KIWA, WRC) Attention Use pips capable of withstanding steam temperature, don't use hoses s¬ ¬$RAINWATER¬CONNECTION¬SET¬ Art. no.: 60.70.464 s¬ 7ELDING¬OF¬DRAIN¬PIPE¬TO¬THE¬UNITS¬DRAIN¬IS¬NOT¬ permissible (welding can cause damages to the unit) s¬ ¬$.¬¬PIPE with constant gradient (min. 5% or 3°); do not reduce the diameter of the pipe. s¬ ¬&IXED¬CONNECTION¬WITH¬ODOUR¬LOCK¬PERMISSIBLE¬A¬ ventilated drain line is integral to the appliance pic. 1,2 s¬ ¬7HERE¬THERE¬IS¬AN¬EXISTING¬FLOOR¬DRAIN¬WITHOUT¬AIR¬ trap, a clear outflow of 2 cm (1”) must be provided. pic. 3 ¬s¬ ¬7E¬RECOMMEND¬TO¬CONNECT¬EVERY¬UNIT¬TO¬A¬SEPArate drain. s¬ ¬5NITS¬X'.¬UP¬TO¬X'.¬CAN¬BE¬CONnected either to a wall drain or to a floor drain s¬ 5NITS¬X'.¬OR¬X'.¬CAN¬ONLY¬BE connected to a floor drain. Option: For reduction of steam escape via the ventilation pipe a condensate collector or an additional ascending pipe can be used. See pages 26/27 Option table models: Using 110 mm (approx. 4”) legs for extended space underneath unit. Height adjustable transport trolley, see page 25 Option floor models: Using leg extension for more space underneath unit. Install height extension for mobile oven rack see page 26 Note drainage dimensions: short-term pumped discharge volume of steam generator 0.7 l/sec (0,18 gal/sec.) s¬ ¬!VERAGE¬WASTE¬WATER¬TEMPERATURE¬ª# s¬ ¬!PPLICABLE¬STANDARD¬$).¬¬0ART¬ Attention: The centre height drain pipe of table models is 63 mm (2 1/2”) and floor models is 70 mm (2 7/8”). - 23 - V11 Ventilation, technical data, heat emission Ventilation: An exhaust hood is not essential. If one is fitted, bear the following points in mind: s¬ ¬#OMPLY¬WITH¬ALL¬LOCAL¬REGULATIONS¬AND¬STANDARDS s¬ ¬4HE¬HOOD¬SHOULD¬PROJECT¬¬MM¬¬FT¬IN¬FRONT¬OF¬THE¬APPLIANCE s¬ ¬)NSTALL¬A¬GREASE¬FILTER¬IN¬THE¬PROJECTING¬PART¬OF¬THE¬HOOD s¬ ¬!N¬EXHAUST¬HOOD¬IS¬AVAILABLE¬AS¬AN¬OPTION¬FOR¬X¬¬X¬'.¬UNITS¬ s¬ &OR¬INSTALLATION¬OF¬THE¬HOOD¬PLEASE¬FOLLOW¬THE¬INSTRUCTION¬OF¬THE¬CORRESPONDING¬INSTALLATION¬MANUAL¬ Technical data: Noise emission level: <70dBA Hoseproofness: IPX5 Heat emission: Electrical units: 6x1/1 GN latent: 2.143 kJ/h sensible: 2.727 kJ/h 6x2/1GN 4.167 kJ/h 5.000 kJ/h 10x1/1 GN 3.529 kJ/h 4.615 kJ/h 10x2/1 GN 6.667 kJ/h 9.474 kJ/h 20x1/1 GN 7.200 kJ/h 9.000 kJ/h 20x2/1 GN 12.500 kJ/h 14.286 kJ/h Gas units: latent: sensible: 6x2/1GN 4.167 kJ/h 5.000 kJ/h 10x1/1 GN 3.529 kJ/h 4.286 kJ/h 10x2/1 GN 6.667 kJ/h 9.231 kJ/h 20x1/1 GN 7.200 kJ/h 8.780 kJ/h 20x2/1 GN 11.583 kJ/H 13.636 kJ/H 6x1/1 GN 2.143 kJ/h 2.571 kJ/h Weight of electric units: SCC units: 6 x 1/1 GN: 110,0 kg 6 x 2/1 GN: 142,5 kg 10 x 1/1 GN: 135,5 kg 10 x 2/1 GN: 182,0 kg 20 x 1/1 GN: 258,0 kg 20 x 2/1 GN: 332,0 kg Mobile: 20 x 1/1 GN: 275,5 kg 20 x 2/1 GN: 352,0 kg Weight of gas units: SCC units: 6 x 1/1 GN: 126,0 kg 10 x 1/1 GN: 154,5 kg 20 x 1/1 GN: 286,0 kg Mobile: 20 x 1/1 GN: 303,5 kg CM units without 6 x 1/1 GN: 99,0 kg 10 x 1/1 GN: 124,5 kg 20 x 1/1 GN: 251,5 kg 6 x 2/1 GN: 133,0 kg 10 x 2/1 GN: 175,5 kg 20 x 2/1 GN: 326,0 kg 20 x 1/1 GN: 269,0 kg 20 x 2/1 GN: 346,0 kg 6 x 2/1 GN: 168,0 kg 10 x 2/1 GN: 198,0 kg 20 x 2/1 GN: 370,5 kg CM units without 6 x 1/1 GN: 121,0 kg 10 x 1/1 GN: 148,0 kg 20 x 1/1 GN: 261,0 kg 6 x 2/1 GN: 158,5 kg 10 x 2/1 GN: 189,5 kg 20 x 2/1 GN: 369,5 kg 20 x 2/1 GN: 390,5 kg 20 x 1/1 GN: 278,5 kg 20 x 2/1 GN: 389,5 kg Right of technical modifications reserved. V11 - 24 - Option Heat shield left and right 1 50 mm Unit size: 6x1/1GN 6x1/1GN 10x1/1GN 10x1/1GN 6x2/1GN 10x2/1GN 20x1/1GN 20x2/1GN Art.-No.: 60.70.390 left Art.-No.: 60.70.736 right Art.-No.: 60.70.391 left Art.-No.: 60.70.743 right Art.-No.: 60.70.392 Art.-No.: 60.70.393 Art.-No.: 60.70.394 Art.-No.: 60.70.395 If the minimum required distance to heat sources on the left or right side (right side only 6x1/1 GN and 10x1/1 GN) can not be maintained a heat shield will help to reduce the heat stress to the unit pic 1 2 Height extension of table units. 3 (6x1/1 GN up to 10x2/1GN) Should the distance between floor and bottom of table units be too low (e.g. when installing combi duo), then the standard lower parts of the legs can be replaced by longer legs (110 mm). Art.-No.: 12.00.224 pic. 2 Attention: In this case the height of the upper rail in the cooking cabinet exceeds 1600 mm (63”) When using mobile oven racks and transport trolleys the height difference can be compensated by a height adjustable transport trolley. pic. 3 Height adjustable trolley: Unit size: 6x1/1 and 10x1/1 GN Art.-No.: 60.60.188 6x2/1 and 10x2/1 GN Art.-No.: 60.70.160 - 25 - V11 Option 1 2 3 Foot extension for floor units Art.-No.: 60.21.179 Should the distance be too low between floor and bottom of floor units , foot extensions for floor units can be used pic 1 Attention: In this case the height of the upper rail exceeds 1600 mm (63”). When using these foot extensions a height compensation of the mobile oven rack must be carried out by adding an additional frame. pic. 2 20x1/1GN Art.-No.: 60.21.184 20x2/1GN Art.-No.: 60.22.184 Ramp for mobile oven rack floor models 20x1/1GN Art.-No.: 60.21.080 20x2/1GN Art.-No.: 60.22.181 If the floor underneath the unit is not level the mobile oven rack ramp can level out this uneveness. The adjustment range of the legs is between +/- 10 mm . pic. 3 4 V11 Condensation breaker Under critical installation conditions (e.g. installation in front kitchens), escape of steam at the vent pipe can be reduced by fitting a condensation breaker pic. 4 Unit size: 6x1/1GN / 10x1/1GN Art.-Nos.: 8710.1309 - 26 - Option Also for reducing the steam escape at the drain pipe an additional vent pipe can be fitted to the drain pipe. In this extra vent pipe holes must be drilled where air is sucked in and condensates the steam pic 1/2 1 2 8 mm 1/8" Interfaces a) A serial interface (RS232) is not standard, but can be retrofitted into all units. Unit size 6x1/1GN - 10x2/1GN Art.-No.: 87.00.006 20x1/1GN - 20x2/1GN Art.-No.: 87.00.007 b) SCC units are equipped with USB interface as a standard. - 27 - V11 Mobile floor models 20x1/1GN and 20x2/1GN Attention: The following warning stickers are affixed to the unit: Sticker: "Don't push on operator panel" Sticker: "Don't pull on door handle" Sticker: Observe before transport of unit When moving the unit the following must be observed: 1. Don`t push at the operator panel. This can destroy the control unit behind it. 2. Don`t pull the unit using the door handle, this can damage the door lock mechanism. Prior to the transport of the unit observe the following procedure: 1. Read installation and/or user manual. 2. Disconnect all supply lines at the unit to avoid damages. 3. Move unit only by using the handle V11 - 28 - Mobile floor models 20x1/1GN and 20x2/1GN Sticker: "Danger of tipping over" Sticker: "Danger of tipping over" Sticker: "Attention: For taking the unit off of the pallet at least 2 persons are necessary" Sticker: "Attention: For taking the unit off of the pallet at least 2 persons are necessary" When moving the unit the power cord must be secured against damage, therefore at the top rear side of the unit the enclosed holding device must be installed. - Undo the tapping screw at the left rear side and fasten the holding device with the screw to the top cover. - 29 - V11 Mobile floor models 20x1/1GN and 20x2/1GN For taking the unit off of the pallet see next page. 1 20x1/1 GN: 940mm/37 1/2" 20x2/1 GN: 1150mm/45 1/4" 2 For transport of the unit with or without pallet the following minimum measures have to be observed: With pallet width height 20x1/1GN 940 mm (37 1/8") 1990 mm (78 3/8") 20x2/1GN 1150 mm (45 3/8") 1990 mm (78 3/8") w/o pallet width height 20x1/1GN 905 mm (35 3/4") 1840 mm (72 1/2") 20x2/1GN 1118 mm (44 1/8") 1840 mm (72 1/2") pic. 1 Attention: The unit may only be moved / transported when it is switched off and all supply lines are disconnected. When moving the unit take the trolley out of the cooking cabinet. 3 For pulling the unit out of the site, in case there is not enough space at the left or right side: - Cool down the unit below 40°C (100°F) - Open cabinet door - Pull at the interior cabinet. pic. 2 Attention When pulling the unit out of the site the door can close accidentally. Crushing hazard! For transport of the unit: a) Empty steam generator. Procedure see operator manual. b) Disconnect water supply, drain and additionally on gas units the gas supply line at the connection points at the unit. c) Only exception is the power cord installed in electric units 3 NAC 400V and gas units. These units can be connected with plug. In this case, for transport, the power cord must be protected against damage by hooking it up in the holding device at the rear side of the unit pic. 3 V11 - 30 - Mobile floor models 20x1/1GN and 20x2/1GN 1 - The unit is delivered on a special transport pallet. This pallet can be used several times. Therefore don't dispose the pallet. pic. 1 Attention: To avoid injuries make sure that always two persons are available for taking the unit off of the pallet. Crushing hazard! 2 3 For rolling the unit off the pallet, proceed as follows: a) There are rails stored on the pallet underneath the unit. Fix these rails to the right side of the pallet using the enclosed screws (screw driver 13 mm) pic. 2 b) Remove the retaining bracket at the left and right side of the base frame of the unit by loosing the corresponding screws (screw driver 19 mm). pic. 3 c) Stick the handle, which is enclosed in the scope of delivery (handle of the trolley) into the holes of the right base frame. Take trolley out of the cooking cabinet and roll the unit down from the pallet. pic. 4 d) When using the pallet again for transportation fix the unit to the pallet using the retaining brackets and the corresponding screws. For moving the unit the handle of the trolley can be used. Stick the handle either in the right or the left openings of the base frame. pic. 5 5 4 - 31 - V11 Mobile floor models 20x1/1GN and 20x2/1GN ca. 800 mm appox. 31” 1 - Minimum space of 50 mm (2") at the left, right and rear side of the unit must be maintained. For connecting power, gas and water we recommend a space of 500 mm (20") at the left side of the unit. At sites where not enough space is available make sure, that all supply lines are long enough for moving the unit that far forward that the supply lines can be connected and disconnected. pic. 1 Attention: - Should the ambient temperature at the left side of the unit be too high a safety shut down can occur. - Do not install fryer at the rear side of the unit. - The unit's must only be installed in frost-free rooms. - The floor at the site must be level. A height adjustment of the unit is not possible. 2 - The unit must be secured at the site by pressing the brakes of the casters. pic. 2 - Additionally the unit is equipped with fixing plates pic 3 These plates can either be glued to the floor with a special adhesive or with screws and dowels. Screws and dowels are not included in the scope of delivery. Run the unit onto these plates. Secure the unit with the slider and fasten the slider with the nuts. 3 - Trolley must stand level inside the unit. Attention: An incorrect levelled trolley can cause malfunction during operating the unit (e. g. during Cleanjet) 5006.02 13 V11 Attention: Observe height of the drain. - 32 - Mobile floor models 20x1/1GN and 20x2/1GN - Additionally the unit must be secured against slipping by a chain or cable in order to prevent damage to the electricity or gas supply line. Therefore a hole is in the left frame at the rear for connecting the chain or cable. pic. 1/2 1 Attention: To avoid damages on the supply lines, the restraint cable must be shorter than water, gas and electrical lines 2 Supply lines Wall 3 4 1. Electric connection Attention: Observe your local regulations! Basic hints and colour coding of the wires see pages 14 and 15. Electric units: s¬ ¬Each appliance requires an independent fused power supply line s¬¬4HE¬UNITS¬X¬'.¬AND¬X¬'.¬ are delivered without power cord and without plug. On units with voltage version 3 NAC 400V a connection with cable and plug is possible. s¬ ¬4HE¬CONNECTION¬TERMINALS¬ARE¬LOCATED¬IN¬THE¬ELECtric compartment. To get access open left side panel pic. 3 Gas units: s¬ ¬7E¬RECOMMEND¬an independent fused power supply line for each unit. s¬ ¬4HE¬UNITS¬ARE¬DELIVERED¬WITH¬A¬POWER¬CORD¬ approx 2,5 m ( 8 ft) long without plug. s¬ ¬4O¬GET¬ACCESS¬TO¬THE¬TERMINALS¬OPEN¬LEFT side panel. 2. For drain connection we suggest to have a floor drain at the rear left side of the unit. In this case a drain pipe with elbow piece can be connected to the unit. The pipe should have a clear outflow (air gap) of 2 cm (1”) above the floor drain pic. 4 - 33 - V11 Connected loads in accordance with VDE Guideline Electric units: Power kW Electricity consumption A 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 3 AC 200V 10,1 19,5 17,5 34,5 34,5 57,5 3 AC 230V 10 21 19 37k 37 62 3 NAC 400V 10 21 19 37 37 62 3 AC 400V 10 21 19 37 37 62 3 NAC 415V 10,5 22,5 20,5 40,5 40,5 66,5 3 AC 440V 10 21 19 37 37 62 3 AC 480V 10 21 19 37 37 62 6x1/1 6x2/1 10x1/1 10x2/1 24 53,5 48 100 25 53 48 93 14,5 30,5 27,5 53,5 14,5 30,5 27,5 53,5 14,5 31,5 28,5 56,5 13 28 25 49 12 25,5 23 44,5 20x1/1 100 93 53,5 53,5 56,5 49 44,5 20x2/1 166 156 89,5 89,5 92,5 81,5 75 Fuse protection = A 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 3 AC 200V 35 63 63 100 100 200 3 AC 230V 35 63 63 100 100 200 3 NAC 400V 16 32 32 63 63 100 3 AC 400V 16 32 32 63 63 100 3 NAC 415V 16 32 32 63 63 100 3 AC 440V 16 32 32 63 63 100 3 AC 480V 15 30 25 50 50 80 Gas units: Power kW 1NAC 100V 1NAC 110V 1NAC 120V 1NAC 127V 1NAC 220V 1NAC 230V 1NAC 240V 2 AC 200V 2 AC 220V 2 AC 230V 2 AC 240V Electricity consumption A 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 6x1/1 6x2/1 10x1/1 10x2/1 20x1/1 20x2/1 0,3 0,4 0,39 0,6 0,7 1,1 3 4.0 3,9 6,0 7 11 0,3 0,4 0,39 0,6 0,7 1,1 2,7 3,6 3,5 5,5 6,4 10 0,3 0,4 0,39 0,6 0,7 1,1 2,5 3,3 3,2 5,0 5,8 9.2 0,3 0,4 0,39 0,6 0,7 1,1 2,4 3,2 3,1 4,7 5,5 8,7 0,3 0,4 0,39 0,6 0,7 1,1 1,4 1,6 1,6 2,1 3,6 4,5 0,3 0,4 0,39 0,6 0,7 1,1 1,3 1,8 1,7 2,6 3,0 4,8 0,3 0,4 0,39 0,6 0,7 1,1 1,2 1,7 1,6 2,5 2,9 4,6 0,3 0,4 0,39 0,6 0,7 1,1 1,5 2.0 1,95 3,0 3,5 5,5 0,3 0,4 0,39 0,6 0,7 1,1 1,4 1,9 1,8 2,7 3,2 5,0 0,3 0,4 0,39 0,6 0,7 1,1 1,3 1,8 1,7 2,6 3,0 4,8 0,3 0,4 0,39 0,6 0,7 1,1 1,2 1,7 1,6 2,5 2,9 4,6 The maximum allowable tolerance of the supply voltage (supply voltage see name plate) is in the range of -15% up to +10% V11 - 34 - Conversion tables 1 °dH 1 °f 1 °e 1 ppm 1 mmol/l 1 gr/gal (US) 1 mval/kg °dH 1 0,56 0,8 0,056 5,6 0,96 2,8 °f 1,79 1 1,43 0,1 0,001 1,71 5,0 1 °dH: 10,00 mg CaO/kg (Germany) 17,86 mg CaCO3/kg 7,14 mg Ca2+/kg 1 °f : 5,60 mg CaO/kg (France) 10,0 mg CaCO3/kg 4,00 mg Ca2+/kg 1 °e : 8,01 mg CaO/kg (GB) 14,3 mg CaCO3/kg 5,72 mg Ca2+/kg kPa 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 1,2 1,4 1,6 1,8 2 2,5 3 3,5 mbar 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 25 30 35 psi 0,0147 0,0294 0,0441 0,0588 0,0735 0,0882 0,1029 0,1176 0,1323 0,147 0,1764 0,2058 0,2352 0,2646 0,294 0,3675 0,441 0,5145 °e 1,25 0,70 1 0,07 0,0007 1,20 3,5 ppm 17,9 10,0 14,32 1 100 17,1 50 mmol/l 0,1783 0,1 0,14 0,01 1 0,171 0,5 gr/gal(US) 1,044 0,584 0,84 0,0584 0,00058 1 2,922 mval/kg 0,357 0,2 0,286 0,02 2 0,342 1 1 ppm : (USA) 0,56 mg CaO/kg 1 gr/gal : 9,60 mg CaO/kg 1,0 mg CaCO3/kg (USA) 64,8 mg CaCO3/gal 0,40 mg Ca2+/kg 17,11 mg CaCO3/kg 1 mmol/l : 56,00 mg CaO/kg 6,85 mg Ca2+/kg (chem. conz.) 100,0 mg CaCO3/kg 39,98 mg Ca2+/kg 1 mval/kg : 28,00 mg CaO/kg (Milliäquivalent) 50,0 mg CaCO3/kg 19,99 mg Ca2+/kg inch/wc 0,4014 0,8028 1,2042 1,6056 2,0070 2,4084 2,8098 3,2112 3,6126 4,0140 4,8168 5,6196 6,4224 7,2252 8,0280 10,0350 12,0420 14,0490 kPa 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10 20 30 40 50 100 - 35 - mbar 40 45 50 55 60 65 70 75 80 85 90 95 100 200 300 400 500 1000 psi 0,588 0,6615 0,735 0,8085 0,882 0,9555 1,029 1,1025 1,176 1,2495 1,323 1,3965 1,47 2,94 4,41 5,88 7,35 14,7 inch/wc 16,0560 18,0630 20,0700 22,0770 24,0840 26,0910 28,0980 30,1050 32,1120 34,1190 36,1260 38,1330 40,1400 80,2800 120,4200 160,5600 200,7000 401,4000 V11 Schematic drawing 6x1/1 GN CareControl ( 33 3/8 ) 771 ( 30 3/8 67 ( 2 5/8 ) 6 ) 4 711 ( 28 ) 68 ( 2 3/4 ) 546 ( 21 1/2 ) ) 7 136 (5 3/8) 81 ) 208 (8 1/4) 3 min. 50 (2) 533 (21) Width of passage 1200 (47 1/4) (7 ) min. 50 (2) ( 8 5/8 1 ( 3 1/4 ) ) 220 (3 3/8) 178 86 717 ( 28 1/4 130 (5 1/8) 371 (14 5/8) 84 ( 3 3/8 A 552 ( 21 3/4 ) 5/8 (2 65 min. 50 (2) 121 ) 4 ( 4 7/8 A 5 ) 41 (1 5/8) 68 ( 2 3/4 47 (1 7/8) 63 (2 1/2) 757 (29 3/4) 100 (4) top rail 637 (25) 35 ( 1 1/2 ) 847 2 120 ° 1 rstset point 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) Measures in mm(inch) V11 - 36 - ) Schematic drawing 6x1/1 GN Gas CareControl ( 33 3/8 771 ) ( 30 3/8 67 ) ( 2 5/8 A 47 (1 7/8) 208,5 86 (3 1/2) 87 84 552 ) ) ( 21 3/4 ) 5/8 (2 8 130,5 ( 5 1/8 ) 717 ( 28 1/4 min. 50 (2) 121 65 4 1 121,5 (4 3/4) (8 1/4) (3 3/8) 5 282,5 (11 1/8) ( 21 1/2 ) ) ( 4 7/8 A 58 (2 3/8) ( 2 1/2 ) ) ( 3 3/8 546 68 ( 2 3/4 371 (14 5/8) 711 ( 28 ) 114,5 ( 4 1/2 ) 8 4 ) ) ( 2 3/4 391 ( 15 1/2 ) 63 6 68 ) 41 (1 5/8) 757 (29 3/8) 489,5 ( 19 3/8 100 (4) top rail 637 (25) 48,5 ( 2 ) 847 7 9 10 136 (5 3/8) 3 81 130 ( 21 ) ( 3 3/8 ) ( 5 1/8 ) 120 533 Width of passage ) ( 47 1/4 86 ( 3 1/4 ) min. 50 (2) min. 50 (2) 1200 (7 ) ( 8 5/8 ) 220 178 2 ° 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) 1 rstset point - 37 - V11 ) Schematic drawing 6x2/1 GN CareControl ( 42 1/8 ) 971 ( 38 1/4 ) 67 ( 2 5/8 63 6 4 893 ( 35 1/4 ) 88 ( 30 1/2 ( 3 1/2 ) ) A ( 36 1/8 ) 76 201 (8) 7 128 (5) ( 29 ) min. 50 (2) 738 2 Width of passage 1500 ( 59 ) min. 50 (2) 3 (3 ) 77 ( 30 1/8 ) 5/8 229 (9 ) ( 11 ) (2 917 ) ( 3 3/4 ) 65 764 ) 94 281 124 ( 4 7/8 4 min. 50 (2) A ( 5 1/8 ) 130 (3 ) 776 1 45 (1 3/4) ( 3 1/2 ) 5 476 (18 3/4) 88 47 (1 7/8) ( 2 1/2 ) 757 (29 3/4) 100 (4) top rail 637 ( 25 ) 35 ( 1 1/2 ) 1069 12 0° 1 rstset point 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) Measures in mm(inch) V11 - 38 - ) Schematic drawing 6x2/1 GN Gas CareControl ( 42 1/8 ) 971 ( 38 1/4 ) 67 ( 2 5/8 6 474 ( 18 3/4 88 ) ( 30 1/2 ( 11 7/8) 8 73 ( 3 ) 301 201 ) 86 140 ( 5 1/2 ) 476 (18 3/4) 114 ( 4 1/2 ) ) ) ) 5/8 917 ( 36 1/8 (2 ( 3 3/8) 76 (3 ) A 764 ( 30 1/8 65 min. 50 (2) 130 ( 5 1/8 ) 4 5 ( 3 1/2 ) ) (8 ) A 1 124 (4 7/8) ( 35 1/4 776 ) 45 (1 3/4) 893 ) 8 4 88 ( 3 1/2 ) ( 30 1/4 47 (1 7/8) 63 ( 2 1/2 ) 768 58 (2 3/8) 757 (29 3/4) 100 (4) top rail 637 ( 29 ) 48,5 (2 ) 1069 7 9 10 128 (5 1/8) 2 77 (3 ) 124 ( 4 7/8 min. 50 (2) ( 29 ) ( 3 3/4 ) ) 120 ° 738 94 Width of passage ( 59 ) (9 ) min. 50 (2) 1500 281 229 ( 11 ) 3 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) 1 st set point - 39 - V11 ) Schematic drawing 10x1/1 GN CareControl ( 33 3/8 ) 771 ( 30 3/8 67 ( 2 5/8 ) 63 (2 1/2) 6 711 ( 28 ) 68 ( 2 3/4 ) ( 3 3/8 84 ) 136 (5 3/8) 81 ) 7 3 min. 50 (2) 2 120 ° 533 (21) Wegbreite Width of passage 1200 (47 1/4) (7 ) ( 8 5/8 min. 50 (2) V11 208 (8 1/4) ( 3 1/4 ) ) 220 178 (3 3/8) 717 ( 28 1/4 130 (5 1/8) 86 A 552 ( 21 3/4 ) 5/8 (2 min. 50 (2) 121 ) ( 4 7/8 65 4 1 ) 546 ( 21 1/2 ) A 5 41 (1 5/8) ) 4 371 (14 5/8) 68 ( 2 3/4 47 (1 7/8) 1017 (40) 100 (4) top rail 909 (35 3/4) 35 ( 1 1/2 ) 847 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) Measures in mm(inch) 1 rstset point - 40 - ) Schematic drawing 10x1/1 GN Gas CareControl ( 33 3/8 ) 771 ( 30 3/8 67 ) ( 2 5/8 ) (3 5/8) 47 (1 7/8) 208,5 91,5 87 84 ) 552 ) 8 130,5 ( 5 1/8 ) ( 21 3/4 ) 5/8 (2 65 4 717 ( 28 1/4 min. 50 (2) 121 ) ( 4 7/8 A A 1 285,5 (11 1/4) (8 1/4) 5 176 (7) 68 ( 2 3/4 ( 21 1/2 ) ( 3 3/8 546 (3 1/2) 711 ( 28 ) 371 (14 5/8) ) 114,5 ( 4 1/2 ) 8 4 ) ( 2 3/4 58 (2 3/8) ( 2 1/2 ) 63 6 68 ) 391 ( 15 1/2 ) 41 (1 5/8) 1017 (40) 489,5 ( 19 3/8 100 (4) top rail 909 (35 3/4) 48,5 (2) 847 7 9 10 136 (5 3/8) 3 81 130 ( 21 ) ( 3 3/8 ) ( 5 1/8 ) 120 533 Width of passage ) ( 47 1/4 86 ( 3 1/4 ) min. 50 (2) min. 50 (2) 1200 (7 ) ( 8 5/8 ) 220 178 2 ° 1 st set point - 41 - 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) V11 ) Schematic drawing 10x2/1 GN CareControl ( 42 1/8 ) 971 ( 38 1/4 ) 67 ( 2 5/8 63 6 4 893 ( 35 1/4 ) 88 ( 30 1/2 ( 3 1/2 ) ) A 7 128 (5) (3 ) 77 ( 36 1/8 ) 76 201 (8) ( 29 ) min. 50 (2) 2 12 738 Width of passage 1500 ( 59 ) min. 50 (2) 3 0° 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) Measures in mm(inch) Raststellung 1 rstset point V11 ( 30 1/8 ) 5/8 229 (9 ) ( 11 ) (2 917 ) ( 3 3/4 ) 65 764 ) 94 281 124 ( 4 7/8 4 min. 50 (2) A ( 5 1/8 ) 130 (3 ) 776 1 45 (1 3/4) ( 3 1/2 ) 5 476 (18 3/4) 88 47 (1 7/8) ( 2 1/2 ) 1017 (40) 100 (4) top rail 909 ( 35 3/4 ) 35 ( 1 1/2 ) 1069 - 42 - ) Schematic drawing 10x2/1 GN Gas CareControl ( 42 1/8 ) 971 ( 38 1/4 ) 67 ( 2 5/8 6 ( 30 1/4 474 ( 18 3/4 ) 8 4 893 ( 35 1/4 776 88 ) ( 30 1/2 1 ( 3 1/2 ) 278,5 ( 11 ) ) 764 ( 30 1/8 114 ( 4 1/2 ) 8 73 ( 3 ) ) 86 476 (18 3/4) 140 76 ( 3 3/8) ( 5 1/2 ) 5/8 ) (2 ) ) 65 917 ( 36 1/8 4 min. 50 (2) ( 5 1/8 ) 130 (3 ) A 45 (1 3/4) ( 8 ) 201 A 5 192 (7 5/8) 88 ( 3 1/2 ) ) 47 (1 7/8) 100 (4) 63 ( 2 1/2 ) 768 58 (2 3/8) 1017 (40) top rail 909 ( 35 3/4 ) 57 (2 1/4) 1069 7 9 10 128 (5 1/8) 2 77 (3 ) 124 ( 4 7/8 min. 50 (2) ( 29 ) ( 3 3/4 ) ) 120 738 ( 59 ) 1500 (9 ) min. 50 (2) 94 Width of passage 281 229 ( 11 ) 3 ° 1 rstset point - 43 - 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) V11 ) Schematic drawing 6x1/1 GN 771 (33 3/8 ) ( 30 3/8 ) 67 (2 5/8 ) 63 (2 1/2 ) 4 6 (28 ) 371 (14 5/8) ( 28 1/4 ) 717 /8) (2 5 65 ( 21 3/4 ) (2 3/8) A 552 58 4 (5 1/8) A (4 1/4) 1 208,5 (8 1/4) 41 (1 5/8) (3 3/8 ) (21 1/2) 130 546 5 68 (2 3/4 ) 84 711 68 (2 3/4 ) 107 47 (1 7/8 ) 757 100 (4) ( 29 3/4) 35 (1 1/2 ) 847 7 (3 1/4) 81 191 (7 1/2) 3 2 12 0 533 (21) 226 (9 ) 136 (5 3/8) 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) Measures in mm(inch) V11 - 44 - Schematic drawing 6x1/1 GN Gas ( 33 3/8 ) 771 (28 ) 9 47 (1 7/8) 121,5 (4 3/4) 41 87 (3 1/2) (28 1/4) 7 86 (3 3/8) 10 136 (5 3/8) ( 3 1/4 ) 81 2 140 176 (5 1/2) (7 ) 12 0 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) 533 (21 ) 161 ( 6 3/8 ) 3 371 (14 5/8) ( 21 3/4 ) 717 8 552 65 (2 5 /8 ) A 208,5 (8 1/4) (1 5/8) 282,5 (11 1/8) 130,5 (5 1/8 ) 209 5 ( 3 3/8 ) (21 1/2) 121 4 (4 7/8) A 1 8 68 ( 2 3/4 ) 84 711 546 ( 8 1/4) (15 1/2 ) 4 6 68 (2 3/4) 114,5(4 1/2) (2 3/8 ) 391 (19 3/8 ) 58 757 ( 2 1/2 ) 489,5 67 (2 5/8 ) (30 3/8 ) 63 100 (4 ) (29 3/4) 48,5 (2 ) 847 - 45 - V11 Schematic drawing 6x2/1 GN 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) Measures in mm(inch) V11 - 46 - Schematic drawing 6x2/1 GN Gas ( 42 1/8) 971 ( 38 1/4 ) (18 3/4) 4 6 140 (5 1/2) 476 (18 3/4) 8 (30 1/8 ) 65 86 (3 3/8) 124 (4 7/8) 76 A /8) 5 (2 4 114 (4 1/2 ) 201 (8) (36 1/8 ) A 5 301 (11 7/8) ( 3) ( 30 1/2) ( 5 1/8) 130 776 1 8 88 (3 1/2 ) 45 (1 3/4) ( 35 1/4 ) 917 893 764 88 ( 3 1/2 ) 47 (1 7/8 ) 474 67 (2 5/8) (30 1/4 ) 58 (2 3/8 ) 757 768 63 ( 2 1/2 ) 100 (4 ) ( 29 3/4) 48,5 ( 2) 1069 7 9 10 73 ( 3 ) (3 ) 77 128 (5 1/8) 131 167 ( 5 1/4) (6 5/8) 12 0 704 ( 27 3/4 ) 283 235 ( 11 1/8 ) ( 9 3/8 ) 3 2 - 47 - 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) V11 Schematic drawing 10x1/1 GN 771 ( 33 3/8 ) ( 30 3/8) 67 (2 5/8 ) 63 100 (4 ) (2 1/2 ) 47 (1 7/8 ) 1017 (40 ) 35 (1 1/2 ) 847 4 711 (28 ) (2 3/4 ) 5 68 (2 3/4 ) (3 3/8 ) 68 A 208,5 (8 1/4) (2 5 65 ( 5.1 ) ( 28 1/4 ) (2 3/8 ) 717 58 4 ( 21 3/4 ) (4 1/4 ) 552 107 /8 A 371 (14 5/8) ) 130 84 546 (21 1/2) 1 41 (1 5/8) 6 7 ( 3 1/4 ) 81 191 (7 1/2 ) 3 V11 2 12 0 533 (21 ) 226 ( 9) 136 (5 3/8) 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) Measures in mm(inch) - 48 - Schematic drawing 10x1/1 GN Gas (33 3/8 ) ( 30 1/2 ) 771 67 (2 5/8 ) 1017 (40 ) 48,5 ( 2 ) 847 47 (1 7/8) 58 63 8) 208,5 (8 1/4) 7 91,5 (3 5/8) 41 (1 5/8) 285,5 (11 1/4) A 176 (7) 87 (3 1/2) 371 (14 5/8 ) ( 21 3/4 ) ( 28 1/4 ) 717 552 9 10 3 2 140 176 (3 1/4 ) 81 136 (5 3/8) ( 5 1/2 ) ( 7) 12 0 533 (21) 209 161 (6 3/8 ) 1 5 5/ (2 4 8 (8 1/4 ) 8 ( 2 3/4 ) 84 (21 1/2) 65 A ( 4 7/8 ) (5 1/8 ) (15 1/2 ) ( 3 3/8 ) 68 121 546 130,5 ( 2 3/8 ) ( 2 1/2 ) (4 ) 100 711 ( 28 ) 68 (2 3/4 ) (4 1/2 ) 391 4 6 114,5 489,5 (19 3/8 ) - 49 - 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 50 (2) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) V11 Schematic drawing 10x2/1 GN ( 42 1/8 ) 971 67 ( 2 5/8) ( 38 1/4 ) 8) 764 ( 2 3/8) 476 (18 3/4) 917 ( 36 1/8 ) 65 45 (1 3/4) 7 ( 3) 77 226 128 (5) 3 2 12 0 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 70 (2 3/4) Measures in mm(inch) 704 ( 27 3/4 ) ( 9) 261 ( 10 3/8 ) 201 (8) 5/ 107 ( 4 1/4) V11 A 76 (2 1 5 ( 3 1/2 ) ( 3) ( 30 1/2 ) (5 1/8 ) 130 4 88 ( 35 1/4 ) ( 30 1/8 ) 893 776 58 (1 7/8) 4 6 88 ( 3 1/2 ) A 47 63 (2 1/2) 100 ( 4 ) 1017 (40 ) 35 (1 1/2 ) 1069 - 50 - Schematic drawing 10x2/1 GN Gas 1069 (42 1/8 ) 10 100 (4 ) 63 ( 2 1/2 ) 768 7 45 (1 3/4) 201 (8) 86 (3 3/8) 9 10 3 2 77 ( 3) 128 (5 1/8) 131 (5 1/4) 167 (6 5/8) 12 0 704 ( 27 3/4 ) 283 5 235 5 192 (7 5/8) 76 ( 3 ) 8 ( 9 3/8) A 5 476 (18 3/4) (2 1 278,5 (11) 917 ( 36 1/8 ) 65 ) /8 764 ( 30 1/8 ) (5 1/8) 130 4 114 (4 1/2) 8 88 (3 1/2 ) 140 (5 1/2) 893 ( 35 1/4 ) A (11 1/8 ) 474 (18 3/4 ) 4 6 776 ( 30 1/2 ) 73 ( 3 ) ( 30 1/4 ) 58 ( 2 3/8 ) 1017 (40 ) 9 88 ( 3 1/2 ) 67 (2 5/8) 47 (1 7/8) 57 (2 1/4) 971 ( 38 1/4 ) 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 70 (2 3/4) 8 = Gas supply 3/4” 9 = Exhaust pipe steam 10 = Exhaust pipe hot air Measures in mm(inch) - 51 - V11 Schematic drawing 20x1/1 GN 791 ( 31 1/8 ) ( 34 5/8 ) 67 135 ( 5 3/8 ) 160 (6 3/8) 143 70 ( 5 5/8 ) ( 2 7/8 ) 1782 ( 70 1/4 ) 35 (1 1/2 ) 879 28 (1 1/8 ) 717 ( 28 1/4 ) 5 164 ( 6 1/2 ) 537 (21 1/8) 126 (5 ) ( 24 7/8 ) 40 (1 5/8 ) 4 630 A 4 A 5 1 47 (1 7/8) ( 31 1/2 ) ( 2 3/4 ) 371 (14 5/8) 797 53 54 ( 2 1/8 ) 70 ( 17 ) (2 1/8 ) 431 6 199,5 (7 7/8) 7 153 (6 1/8) 2 12 0 568 (22 3/8 ) 152 3 V11 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 70 (2 3/4) Measures in mm(inch) 34 (1 3/8 ) (6 ) 104 (4 1/8 ) - 52 - ( 2 5/8 ) Schematic drawing 20x1/1 GN Gas ( 34 5/8 ) 791 ( 31 1/8 ) 67 ( 2 5/8 ) 135 ( 5 3/8 ) 145 ( 5 3/4) 160 ( 6 3/8 ) 143 ( 5 5/8 ) 70 ( 2 7/8 ) 1782 ( 70 1/4 ) 51 ( 2 ) 879 8 70 ( 2 7/8 ) 4 9 104 (4 1/8) 8 2 12 0 568 (22 3/8 ) 3 34 (1 3/8) 153 (6 1/8) (6 ) 152 216 ( 8 1/2) 7 302,5 (12) (7) 176 371 (14 5/8) 199,5 (7 7/8) 86 (3 3/8) 109,5 (4 3/8) A 717 ( 28 1/4 ) 40 (1 5/8) 630 ( 24 7/8 ) 5 164 ( 6 1/2 ) 537 ( 21 1/8 ) A 126 ( 5 ) 560 ( 22 1/8 ) 4 1 320 (12 5/8) 28 ( 1 1/8 ) 53 (2 1/8) 797 ( 31 1/2 ) 87 (3 1/2) 54 ( 2 1/8) 47 (1 7/8) 431 ( 17 ) 6 10 11 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain, 5 = Electrical connection 6 = Earth bonding7 = Venting pipe DN 70 (2 3/4) 8 = Gas supply 3/4”, 9 = Exhaust pipe steam 10/11 = Exhaust pipe hot air Measures in mm(inch) - 53 - V11 Schematic drawing 20x2/1 GN 996 ( 39 1/4) 67 ( 2 5/8 ) 4 A 195 (7 3/4) A 835 ( 33) 481 (19) 40 (1 5/8) 711 ( 28 ) 126 (5) 1 28 (1 1/8) 922 ( 36 3/8) 4 5 49 (2) 1002 ( 39 1/2 ) 53 (2 1/8) 54 ( 2 1/8 ) 160 (6 3/8 ) 108 ( 4 1/4) 582 ( 23 ) 6 135 ( 5 3/8 ) 143 ( 5 5/8 ) 70 ( 2 7/8 ) 1782 ( 70 1/4) 35 (1 1/2) 1084 ( 42 3/4 ) 7 5 151(6 ) 164 (6 1/2) 104 (4 1/8) 34 (1 3/8) 152 ( 6 ) 128 (5 1/8) 2 12 0 V11 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain 5 = Electrical connection 6 = Earth bonding 7 = Venting pipe DN 70 (2 3/4) Measures in mm(inch) 730 (28 3/4 ) 3 - 54 - Schematic drawing 20x2/1 GN Gas ( 42 3/4 ) 67 ( 2 5/8 ) 996 ( 39 1/4 ) 8 108 ( 4 3/8 ) 28 ( 1 1/8 ) 40 (1 5/8 ) 8 144 (5 5/8) 481 (19) 835 ( 33 ) 164 (6 1/2 ) 922 ( 36 3/8 ) A 711 ( 28 ) A 9 5 151 ( 6 ) 12 0 1 = Common water supply (cold water) 2 = Water supply, cold water 3 = Water supply, soft and warm water 4 = Drain, 5 = Electrical connection 6 = Earth bonding7 = Venting pipe DN 70 (2 3/4) 8 = Gas supply 3/4”, 9 = Exhaust pipe steam 10/11 = Exhaust pipe hot air Measures in mm(inch) 730 (28 3/4) ( 6 1/2 ) 11 128 (5 1/8) 34 (1 3/8 ) (6) 152 104 (4 1/8 ) 164 10 279 (11) 2 7 86 (3 3/8) 197 (7 3/4) 4 127 (5) 53 (2 1/8 ) 298 (11 3/4) 195 (7 3/4) 49 (2) 1002 ( 39 1/2 ) 3 1 4 54 ( 2 1/8 ) 126 ( 5 ) 147 ( 5 7/8 ) 70 ( 2 7/8 ) ( 5 5/8 ) 143 582 ( 23 ) 6 516 ( 20 3/8 ) 160 (6 3/8) 135 ( 5 3/8 ) 1782 ( 70 1/4 ) 57 ( 2 1/4 ) 1084 - 55 - V11 Schematic drawing 20x1/1 GN Electric, mobile 879 [ 34-5/8] 50 [ 2 ] 791 [ 31-1/8 ] 707 [ 27-7/8 ] 1487 [ 58-1/2 ] 56 [ 2-1/4 ] 36 [ 1-3/8 ] 1237 [ 49 ] 199 [ 8 ] 197 [ 8 ] 445 [ 17-1/2 ] 47 [ 1-7/8 ] 931 [ 36-5/8 ] 1018 [ 40-1/8 ] V11 - 56 - min. 666 [ 26-1/4 ] - max. 810 [7/8] 738 [ 29 ] 847 [ 33-3/8 ] 905 [ 36 ] mm [inch] 150 [ 5-7/8 ] 125 [ 4-7/8 ] abnehmbar demountable 56 [ 2-1/4 ] Schematic drawing 20x1/1 GN Gas, mobile [ 34-5/8 ] 50 [ 2] 791 [ 31-1/8 ] [ 2-1/4 ] [ 5-7/8 [ 4-7/8 125 ] ] 56 150 [ 39-5/8 ] abnehmbar demountable 1007 931 [ 36-5/8 1023 [ 40-1/4 ] 36 ] [ 12-5/8 [ 12 ] 200 [ 8 ] 86 [ 3-3/8 ] min. 666 [ 26-1/4 738 [ 49 ] 320 303 [ 1-3/8 847 ] 905 [ 29 ] [ 33-3/8 ] 56 [ 2-1/4 ] ] [ 36 ] ] - 57 - mm [inch] [ 8] [ 17-1/2 198 445 ] ] [ 3-3/8 [ 6-7/8 87 176 [ 4] ] 47 [ 1-7/8 ] 1252 110 1787 [ 70-3/8 ] 879 V11 Schematic drawing 20x2/1 GN Electric, mobile 1084 [ 42-5/8 ] 50 [ 2 ] 1787 [ 70-3/8 ] 1007 [ 39-5/8 ] 150 [ 5-7/8 ] 125 [ 4-7/8 ] 56 [ 2-1/4 ] abnehmbar demountable 36 [ 1-3/8 ] min. 777 [ 30-5/8 ] - max. 849 [33-1/2] 849 [ 33-3/8 ] 1052 [ 41-3/8 ] 1119 [ 44 ] - 58 - mm [inch] 1443 [ 57 ] 195 [ 7-5/8 ] 260 [ 10-1/4 ] 487 [ 19-1/8 ] 49 [ 1-7/8 ] 1131 [ 44-1/2 ] 1223 [ 48-1/8 ] V11 996 [ 39-1/4 ] 145 [ 5-3/4 ] Schematic drawing 20x2/1 GN Gas, mobile [ 42-5/8 50 [2] 56 [ 2-1/4 ] 36 [ 1-3/8 ] ] 996 [ 39-1/4 777 [ 30-5/8 ] 1787 [ 70-3/8 ] 1084 1131 1223 ] ] min. 849 [ 33-3/8 1052 1119 ] [ 41-3/8 145 [ 5-3/4 ] [ 44 ] - 59 - mm [inch] [ 10-1/4 [ 19-1/8 260 487 ] ] ] [5] 127 ] [ 57 ] [ 12 ] [ 11 ] [ 7-3/4 ] 144 [ 48-1/8 195 [ 7-5/8 ] 86 [ 3-3/8 ] [ 5-5/8 49 [ 1-7/8 ] 1452 298 279 [ 44-1/2 197 ] [ 5-7/8 [ 4-7/8 150 125 1007 ] [ 39-5/8 ] abnehmbar demountable V11 ] UK 80.01.017 · V-11 · Technical Services · Md · 06/2009