Download Altronix SMP3PMP4
Transcript
SMP3CTX Series - Installation Guide Al tro M nix od el Nu m be r Ac c Di esso s r M tribu y Po od ti w u o e Nu le(s n r ) m b Fu er o f se d O Ou ut tput PT pu s C Ou ts In tp d u Ra ivid ts tin ual g O Su (am utp p) ut pe rv 11 ised In 5VA pu C tC /2 ur 30 re VA 12 nt C / (a 2 Ou 4V m p) tp D ut C T Cu o r re tal nt (a m p) SMP3CTX Series Power Supply Configuration Reference Chart: SMP3CTX - 1 - - - - .65 / .35 2.5 SMP3PMCTX - 1 - - - x .65 / .35 2.5 SMP3PMCTXX - 1 - - - x .65 / .35 2.5 PD4 4 x - 3.5 x .65 / .35 2.5 PD4CB 4 - x 2.5 x .65 / .35 2.5 PD8 8 x - 3.5 x .65 / .35 2.5 SMP3PMP8CB PD8CB 8 - x 2.5 x .65 / .35 2.5 SMP3PMP16 PD16W 16 x - 3.5 x .65 / .35 2.5 PD16WCB 16 - x 2.5 x .65 / .35 2.5 SMP3PMP4 SMP3PMP4CB SMP3PMP8 SMP3PMP16CB Overview: These units will convert a 115VAC or 230VAC, 50/60Hz input, into a regulated 12VDC or 24VDC output up 2.5 amp of continuous load current (see specifications). Specifications: • • • • • Universal 115/230VAC input. Maximum charge current .5 amp. Filtered and electronically regulated outputs. Built-in charger for sealed lead acid or gel type batteries. Automatic switch over to stand-by battery when AC fails (zero voltage drop). • AC input and DC output LED indicators. • Short circuit and thermal overload protection. • Complete with power supply, power distribution module (when applicable), enclosure, cam lock & battery leads. • Power on-off switch. Supervised models only: • AC fail supervision (form "C" contacts). • Low battery supervision (form "C" contacts). Power Supply Voltage Output Specifications: * Output VDC Switch Position Max. Load DC 12VDC SW1 - Closed (Fig. 1b, pg. 3) 2.5 amp 24VDC SW1 - Open (Fig. 1b, pg. 3) 2.5 amp *Specified at 25˚ C ambient. Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 4). Secure enclosure to earth ground. 2. Set SW1 on the power supply board to the desired DC output voltage (Power Supply Voltage Output Specification Chart). SMP3CTXseries -1- 3. Connect AC power to terminals marked [L & N], connect ground to terminal marked [G] (if used). Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting). 4. Measure output voltage before connecting devices. This helps avoid potential damage. 5. Connect devices to be powered: a. For Power Supply Board connect to terminals marked [– DC +]. b. For Power Distribution Module(s) connect devices to be powered to terminal pairs 1 to 4 marked [1P & 1N thru 4P & 4N] (Fig. 2, pg. 3), 1 to 8 marked [1P & 1N thru 8P & 8N] (Fig. 3, pg. 3), or 1 to 16 marked [1P & 1N thru 16P & 16N] (Fig. 4, pg. 3) carefully observing correct polarity. *Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit, AC mains should be removed. 6. When using stand-by batteries, they must be lead acid or gel type. Connect battery to terminals marked [– BAT +] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. Note: When batteries are not used a loss of AC will result in the loss of output voltage. For supervised models only: 7. Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs marked [NC, C, NO] (Fig. 1a, pg. 3). LED Diagnostics: Red (DC) Green (AC) Power Supply Status ON ON OFF OFF ON OFF ON OFF Normal operating condition. Loss of AC, Stand-by battery supplying power. No DC output. Loss of AC. Discharged or no stand-by battery. No DC output. Terminal Identification: Terminal Legend Function/Description L, G, N Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral, G to ground (if used). – DC + 12VDC / 24VDC @ 2.5 amp continuous non-power limited output. *AC FAIL NC, C, NO Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1 amp @ 120VAC / 28VDC. *Low Battery NC, C, NO Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1 amp @ 120VAC / 28VDC Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC. – BAT + Stand-by battery connections. Maximum charge rate .5 amp. *Note: Supervised models only PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module PD4/PD4CB 1P to 4P 1N to 4N -2- Terminal Legend PD8/PD8CB PD16W/PD16WCB 1P to 8P 1P to16P 1N to 8N 1N to 16N Function/ Description Positive DC power outputs. Negative DC power outputs. SMP3CTXseries Fig. 1 CAUTION: De-energize unit prior to servicing. OFF ON 5A 250V L N Green Lead Power Supply Board AC FAIL NC 115/230VAC power mains Power Distribution Module(s) NC C NO LOW BAT C NO NO NC NC C AC FAIL C NO Fig. 1a INPUT G Wire Strap (from Enclosure to Door) LOW BAT --- DC + OPEN - 24VDC CLOSED - 12VDC --- BAT + Fig. 1b OPEN - 24VDC CLOSED - 12VDC 12VDC Rechargeable Battery (optional) 12VDC Rechargeable Battery (optional) CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery. Power Distribution Module(s): Fig. 2 F1 F1 Used on PTC Models F2 F3 F4 Fig. 4 1P, 2P,3P,4P = FUSED OUTPUT S 1N, 2N, 3N, 4N = OMMON C OUTPUT S 1 2 3 4 5 6 7 8 LED 2N 3P 3N 4P 4N INPUT P O U T P UST N 2P P OW E R N DC Output to devices From Power Supply Board (Factory Installed) N 1N 9 10 11 12 13 14 15 16 P P 1P C O MM O N common outputs protected outputs XFMR Input S Used on PTC Models Fig. 3 OFF SW1 1 2 3 4 5 6 7 8 ON 1 P D1 FUSED POWER OUTPUTS R1 LED 3.5A 250V N INPUT COMMON POWER OUTPUTS DC Output to devices SMP3CTXseries For continuous protection against risk of fire replace fuses with same type and rating. From Power Supply Board (Factory Installed) -3- Enclosure Dimensions for: • SMP3CTX • SMP3PMCTX • SMP3PMP4 • SMP3PMP4CB • SMP3PMP8 • SMP3PMP8CB • SMP3PMP16 • SMP3PMP16CB 1.40" 4.85" 4.85" 1.40" 1.20" 3.25" Top 12.50" 1.20" 0.75" 1.20" 11.00" 0.75" 0.9375" 1.40" 1.40" 5.10" 5.10" 13.5”H x 13”W x 3.25”D Enclosure accommodates up to two (2) 12VDC/7AH batteries. Left Also available to accommodate up to two (2) 12VDC/12AH batteries (please contact Altronix). Right 5.10" 6.5625" 0.9375" 3.25" 3.25" Bottom 3.25" 1.00" 1.00" 1.00" Enclosure Dimensions for: • SMP3PMCTXX 1.500" 10.50" 4.615" 4.615" 1.00" 1.500" 1.750" 15.5”H x 12.23”W x 4.5”D Enclosure accommodates up to two (2) 12VDC/12AH batteries. 1.375" 1.125" 4.500" 12.230" 1.250" 4.500" 1.100" 1.250" 1.100" 0.910" 0.910" 1.500" 1.500" 2.000" 15.500" 2.000" 5.000" 5.000" 0.790" 1.250" 1.100" 1.250" 1.750" 1.500" 4.615" 4.615" 1.500" Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: [email protected], Made in U.S.A. H02J IISMP3CTX series - Rev. 051105 -4- MEMBER SMP3CTXseries