Download Installation and Venting Instructions
Transcript
CHIMNEY ADAPTER KITS KGACA02014FC KGACA02015FC Installation and Venting Instructions NOTE: See Table 1 for Furnace Models allowed to be used with this kit. NOTE: Read the entire instruction manual before starting the installation. KEEP THESE INSTRUCTIONS WITH THE FURNACE. ! could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury, or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. MASONRY CHIMNEY APPLICATIONS CAUTION These kits and furnaces shall be applied in accordance with the following section titled Chimney Adapter Application Requirements. The Masonry Chimney Application Requirements section with Tables A and B inside the back page of this instruction identifies a very small number of exterior masonry chimney applications that are permitted without the use of the chimney adapter kit. PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury. C.S.A design--certified furnaces for use with chimney adapter kits on masonry chimneys are identified on their rating plates (all Table 1 furnace models except 58YAV and 393AAV). These markings identify which chimney adapter kit number is permitted to be used with each furnace model number. Chimney adapter kits are for use with ONLY furnaces having factory--authorized chimney adapter kit numbers marked on the furnaces. CHIMNEY ADAPTER APPLICATION REQUIREMENTS This chimney adapter kit is permitted in accordance with NFGC and NSCNGPIC as an ALTERNATIVE VENTING DESIGN. The requirements that follow in part A apply to both single--furnace and multiple--appliance applications. After completing part A, continue to part B for a single furnace application, or continue to part C for a multiple appliance application. After completing part B or C, continue to the INSTALLATION OF CHIMNEY ADAPTER section. A. SINGLE FURNACE and MULTIPLE APPLIANCES (Single furnace, and single furnace and draft hood--equipped water heater(s) vented into a chimney.) 1. This kit is permitted to be used in any building in which the space surrounding the furnace is not depressurized by more than 0.02 in wc (5Pa) below outdoor pressure by equipment such as exhaust fans and clothes dryers. 2. Temperature of air surrounding furnace and vent connector(s) shall be 60_F (42_C) or warmer. 3. Furnace rating plate (58YAV/393AAV: top and clearance-to--combustible -- construction labels) is marked with kit number that is permitted to be used. 4. Chimney construction shall be in good condition and shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances NFPA 211--2006 in the United States and to a Provincial or Territorial Building Code in Canada (in its absence, the National Building Code of Canada). See inspection chart on next page. 5. High altitude: Although appliance input is derated starting at 2000 ft altitude, use sea level input for all altitudes in this chimney sizing instruction. 6. Furnace vent connector lateral length, clay tile liner size, and chimney height shall conform to Table 2. These kits are permitted to be used with only the following furnace models (See Table 1). Do not use this kit with any other furnace models. SAFETY CONSIDERATIONS Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the unit, and other safety precautions that may apply. Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1--2006. In Canada, refer to the National Standard of Canada, Natural Gas and Propane Installation Codes (NSCNGPIC), CAN/CGA--B149.1 and .2--M00. Wear safety glasses and work gloves. Have a fire extinguisher available during start--up, adjustment procedures, and service calls. Recognize safety information. This is the safety--alert symbol ! . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. The words DANGER, WARNING, and CAUTION are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which 1 Table 1 – Kit Usage KIT PART NO. KGACA02014FC FURNACE MODEL FURNACE SIZE USED WITH 58STA / STX / DLA / DLX / CTA / CTX / CVA / CVX / PHA / PHX 045--- 08 045--- 12 310 / 311 / 312 / 313 / 315AAV / JAV PG8MAA / JAA /MEA / JEA 024045 036045 58YAV 393AAV 070--- 08 024070 135--- 16 135--- 20 135--- 22 048135 060135 066135 136--- 20 060135 58STA / STX / DLA / DLX / CTA / CTX / CVA / CVX / PHA / PHX KGACA02015FC 310 / 311 / 312 / 313 / 315AAV / JAV PG8MAA / JAA / MEA / JEA 58YAV 393AAV 070--- 08 070--- 12 070--- 16 090--- 14 090--- 16 090--- 20 024070 036070 048070 070--- 12 036070 042090 048090 060090 091--- 14 042091 110--- 12 110--- 16 110--- 20 110--- 22 036110 048110 066110 111--- 16 048111 155--- 20 155--- 22 — — 060155 066155 — — 155--- 20 060155 — — — — The furnace and kit combinations are C.S.A. design--certified as ALTERNATIVE VENTING DESIGNS. Table 2 – Chimney Requirements FURNACE MODEL SIZES CHIMNEY ADAPTER KIT NUMBER FURNACE VENT CONNECTOR LATERAL MAXIMUM LENGTH FT (M) CHIMNEY CLAY TILE LINER MAXIMUM NOMINAL SIZE OR INSIDE AREA IN OR IN2 (MM or MM2) CHIMNEY MAXIMUM HEIGHT FT (M) MODELS 310 / 311 / 312 / 313 / 315AAV / JAV, 58STA / STX / PHA / PHX / DLA / DLX/ CTA / CTX/ CVA / CVX , PG8MAA / JAA / MEA / JEA KGACA02014FC 9 (3) 8 X 8 or 42.7 (203 X 203 or 27548) 30 (9) 24045 / 045--- 08 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 25 (8) KGACA02014FC 9 (3) 8 X 8 or 42.7 (203 X 203 or 27548) 30 (9) 036045 / 045--- 12 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 25 (8) KGACA02014FC 9 (3) 8 X 8 or 42.7 (203 X 203 or 27548) 30 (9) 024070 / 070--- 08 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 25 (8) KGACA02014FC 9 (3) 8 X 8 or 42.7 (203 X 203 or 27548) 30 (9) 036070 / 070--- 12 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 25 (8) KGACA02014FC 9 (3) 8 X 8 or 42.7 (203 X 203 or 27548) 30 (9) 048070 / 070--- 16 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 25 (8) 042090 / 090--- 14 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 048090 / 090--- 16 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 060090 / 090--- 20 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 036110 / 110--- 12* KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 048110 / 110--- 16 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 060110 / 110--- 20 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 066110 / 110--- 22 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 048135 / 135--- 16* KGACA02015FC 10 (3) 12 X 12 or 83.3 (305 X 305 or 53742) 35 (11) 060135 / 135--- 20* KGACA02015FC 10 (3) 12 X 12 or 83.3 (305 X 305 or 53742) 35 (11) 066135 / 135--- 22* KGACA02015FC 10 (3) 12 X 12 or 83.3 (305 X 305 or 53742) 35 (11) 060155 / 155--- 20* KGACA02015FC 10 (3) 12 X 12 or 83.3 (305 X 305 or 53742) 35 (11) 066155 / 155--- 22* KGACA02015FC 10 (3) 12 X 12 or 83.3 (305 X 305 or 53742) 35 (11) MODELS 393AAV and 58YAV KGACA02014FC 9 (3) 8 X 8 or 42.7 (203 X 203 or 27548) 30 (9) 024070 / 070--- 08 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 25 (8) KGACA02014FC 9 (3) 8 X 8 or 42.7 (203 X 203 or 27548) 30 (9) 036070 / 070--- 12 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 25 (8) 042091 / 091--- 14 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 048111 / 111--- 16 KGACA02014FC 9 (3) 8 X 12 or 63.6 (203 X 305 or 41032) 35 (11) 060135 / 135--- 20 KGACA02015FC 10 (3) 12 X 12 or 83.3 (305 X 305 or 53742) 35 (11) 060155 / 155--- 20 KGACA02015FC 10 (3) 12 X 12 or 83.3 (305 X 305 or 53742) 35 (11) *Chimney must be minimum height specified in the furnace installation instructions. 7. Maintain required clearance to combustible materials. See furnace for Minimum--Clearances--to--Combustible--Construction label, which includes minimum clearance to chimney adapter. 8. Appliance application and operation has significant impact on successful chimney performance. Follow furnace in- stallation instructions in general and, in particular, the APPLIANCE APPLICATION REQUIREMENTS in the VENTING REQUIREMENTS section. See the NFGC, NSCNGPIC, or authority having jurisdiction for all other venting requirements. 2 CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1-2006 and NFPA 211-2006 Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian Installation Code CSA-B149.1-05 in Canada. Crown condition: Missing mortar or brick? Rebuild crown Yes No Is Chimney property lined with clay tile liner? No Yes Is liner and top seal in good condition? No Repair liner or top seal or reline chimney as necessary. Yes Debris in cleanout? Mortar, tile, metal vent, fuel oil residue? Repair Yes Yes No Chimney exposed to outdoors below roof line? Remove mortar and tile debris No Yes No Condensate drainage at bottom of chimney? Yes Mortar of tile debris? No Remove metal vent or liner. Clay tile misalignment, missing sections, gaps? Reline Yes Consult Part B of Not Suitable chimney adapter venting instructions for No application suitability. Is chimney lined Suitable with properly sized. listed liner or Yes Type-B vent? Install chimney adapter per instructions. Not Suitable Yes Is chimney to be dedicated to a single furnace? No Consult Part C of chimney adapter venting instructions for application suitability Line chimney with properly sized, listed flexible metal liner or Type-B vent per NFGC or NSCNGPIC Vent Sizing Tables and liner or vent manufacturer’s Installation instructions. Suitable Install chimney adapter per instructions. No Chimney is acceptable for use. A08245 B. SINGLE FURNACE (Single furnace without a draft hood--equipped water heater vented into a chimney.) 1. The 99 percent winter design temperature* shall determine permitted locations for clay tile -- lined masonry chimneys as shown in Table 3 : 2. Type -- B double -- wall metal vent (with up to 4 elbows) shall be used exclusively for furnace vent connector. 3. Furnace vent connector shall be same size as Chimney Adapter outlet. 4. See Table 2 for maximum length of furnace vent connector lateral. NOTE: See Figure 1 while reviewing the following requirements. 5. The minimum chimney size shall conform to Table 4. 6. See Table 2 for maximum chimney size and maximum chimney height. 3 Table 3 – Permitted Chimney Location MINIMUM 99% WINTER DESIGN TEMPERATURE* --- 25°F (--- 32°C) or Warmer +17°F (--- 8°C) or Warmer PERMITTED CHIMNEY LOCATION Interior Masonry Chimney{ Exterior Masonry Chimneys} * The 99% Winter Design Dry ---Bulb (db) temperatures are found in the 2005 ASHRAE Fundamentals Handbook CD and Chapter 28. Figure G---19 in the NFGC (Appendix G) also provides winter design temperatures for some locations. {Chimneys not exposed to the outdoors below the roof ---line. }Chimneys with one or more sides exposed to the outdoors below the roof line. Table 4 – Single--Furnace -- Masonry Chimney Flue Capacity with Type--B Double--Wall Vent Connector VENT HEIGHT H FT (M) 6 (2) 8 (2) 10 (3) 15 (5) 20 (6) 30 (9) 35 (11) LATERAL L FT (M) 2 (.6) 5 (2) 2 (.6) 5 (2) 8 (2) 2 (.6) 5 (2) 10 (3) 2 (.6) 5 (2) 10 (3) 2 (.6) 5 (2) 10 (3) 2 (.6) 5 (2) 10 (3) 2 (.6) 5 (2) 10 (3) MINIMUM “NAT MAX’ INTERNAL AREA OF MASONRY CHIMNEY FLUE, SQUARE IN. 38 50 63 78 FURNACE INPUT RATING IN THOUSANDS OF BTU PER HOUR NAT NAT NAT NAT NAT 86 130 180 247 320 82 117 165 231 298 93 145 198 266 350 88 134 183 247 328 83 127 175 239 318 103 162 221 298 388 96 148 204 277 365 87 139 191 263 347 114 179 250 336 441 107 164 231 313 416 97 153 216 296 394 124 201 274 375 491 116 184 254 350 463 107 172 237 332 440 137 216 303 421 558 128 198 281 393 526 115 184 236 373 500 143 168 315 435 577 134 206 291 406 544 121 192 273 386 517 28 95 NAT 401 376 446 423 410 491 466 444 562 513 567 627 597 566 717 83 48 741 706 669 NOTE: Table 4 was extracted from “NAT Max” columns in Table 13.1 in Chapter 13 of NFPA54/ANSI Z223.1 ---2006 in United States, or Table 1 of Appendix C in CAN/ CSA---B149.1 ---05 in Canada. Table 5 – Permitted Vent Material MINIMUM 99% WINTER DESIGN TEMPERATURE* --- 25°F (--- 32°C) to --- 10° (--- 23°C) CHIMNEY LOCATION FURNACE VENT CONNECTOR MATERIAL Interior Masonry Chimneys{ Listed Type--- B Double--- Wall Metal Pipe Exterior Masonry Chimneys} Interior Masonry Chimneys{ --- 10°F (--- 23°C) or Warmer Exterior Masonry Chimneys} Not Permitted Listed Type--- B Double--- Wall Metal Pipe or Single--- Wall Galvanized Steel Pipe Listed Type--- B Double--- Wall Metal Pipe WATER HEATER VENT CONNECTOR MATERIAL Listed Type--- B Double--- Wall Metal Pipe or Single--- Wall Galvanized Steel Pipe Not Permitted Listed Type--- B Double--- Wall Metal Pipe or Single--- Wall Galvanized Steel Pipe Listed Type--- B Double--- Wall Metal Pipe or Single--- Wall Galvanized Steel Pipe *The 99% Winter Design Dry ---Bulb (db) temperatures are found in the 2005 ASHRAE Fundamentals Handbook CD and Chapter 28. Figure G---19 in the NFGC (Appendix G) also provides winter design temperatures for some locations. {Chimneys not exposed to outdoors below roof ---line. }Chimneys with 1 or more sides exposed to outdoors below roof ---line. C. MULTIPLE APPLIANCES (Single furnace common--vented with a draft hood--equipped water heater(s) into a chimney.) 1. The minimum 99 percent winter design temperature* and chimney location shall determine permitted vent connector material as shown in Table 5: 2. Furnace vent connector rises shall not exceed 3 ft. (.9M) 3. An operational draft hood--equipped water heater shall be common--vented with furnace. Additional draft hood-equipped appliances are permitted to be common--vented with furnace. 4. Each vent connector is permitted up to 4 elbows. 5. Furnace vent connector shall be same size as Chimney Adapter outlet. 6. Water heater vent connector shall be 4--in. (102 mm)diameter with no more than 6 ft. (2 M) of lateral (horizontal connector length), with water heater draft hood outlet sizes of 3-- and 4--in. (76 and 102 mm) diameter. Use a 3-- X 4--in. (76 X 102 mm)vent increaser with a 3--in. (76 mm) draft hood outlet. 7. Water heater gas inputs* shall not exceed the following rates as shown in Table 6. NOTE: See Fig. 1 while reviewing the following requirements. 4 Table 6 – Max Water Heater Input VENT HEIGHT H --- FT (M) 1 4--- inch dia. (102 mm) Connector Rise R Ft. (M) Water Heater Maximum Input Rating in Thousands of BTU per Hour B S .3 40 39 6 (2) 2 1 8 (2.5) 2 3 1 .6 .9 .3 52 61 41 52 61 40 .6 .9 53 62 52 62 .3 42 41 3 10 (3) 2 3 1 .6 .9 .3 54 63 44 53 62 43 15 (4.5) 2 3 1 .6 .9 .3 55 64 46 54 63 45 20 (6) 2 3 1 30 (9) 2 3 1 50 (15) 2 3 1 100 (30) 2 3 .6 .9 .3 56 65 48 57 65 47 .6 .9 58 66 57 65 .3 51 50 .6 .9 61 69 60 68 .3 50 49 .6 .9 60 68 59 67 B=Listed Type ---B Double ---Wall metal pipe. S=Single ---Wall galvanized---steel pipe. These rise requirements are based on NFGC and NSCNGPIC. Table 7 – Minimum Masonry Chimney Internal Area (Multiple Appliances) Vent Height H Ft. (M) 6 (2) 8 (2) 10 (3) 15 (5) 20 (6) 30 (9) 35 (11) MINIMUM ”NAT+NAT” INTERNAL AREA OF MASONRY CHIMNEY FLUE, SQ. IN. (SQ. MM) 28 (18064) 38 (24516) 50 (32258) 63 (40645) 78 (50322) 113 (72903) Combined Appliance Maximum Input Rating in Thousands of Btu per Hour NAT NAT NAT NAT NAT NAT +NAT +NAT +NAT +NAT +NAT +NAT NP 103 143 188 246 NP NP 119 163 218 278 408 NP 131 177 236 302 454 106 152 212 283 365 546 122 172 243 325 419 648 137 198 278 381 496 749 NP NP 291 401 524 792 NP --- Not Permitted Table 8 – Permitted Exceptions to Minimum 99% Winter Design Temperature and Furnace Connector Diameter Chimney Clay Tile Liner Nominal Size or Inside Area In. or Sq. In (mm or Sq. mm) Furnace 8 x 8 or 42.7 8 x 12 or 63.6 12 x 12 or 83.3 Model (203 x 203 or 27548) (203 x 305 or 41032) (305 x 305 or 53742) Sizes Furnace Type --- B Vent Connector Diameter In. (mm) 6 (152) 5 (127) 4 (102) 6 (152) 5 (127) 4 (102) 7 (178) 6 (152) 5 (127) MODELS 310 / 311 / 312 / 313 / 315AAV / JAV and 58STA / STX / PHA / PHX / DLA / DLX / CTA / CTX / CVA / CVX and PG8MAA / JAA / MEA / JEA 024045 / 045 ---08 036045 / 045 ---12 024070 / 070 ---08 +5 ---10 ---10 036070 / 070 ---12 ---10 ( ---23)‡‡ ---10 ( ---23) ---10 ( ---23) NP NP NP (15)* ( ---23)**†† ( ---23)* 048070 / 070 ---16 042090 / 090 ---14 ---10 ---10 048090 / 090 ---16 ---10 ( ---23)†† NP ---10 ( ---23)†† NP NP NP NP ( ---23)† ( ---23)† 060090 / 090 ---20 036110 / 110 ---12 048110 / 110 ---16 ---10 ( ---23)‡ NP NP ---10 ( ---23)‡ NP NP NP NP NP 060110 / 110 ---20 066110 / 110 ---22 048135 / 135 ---16 ---10 ---10 ---10 ---10 060135 / 135 ---20 NP NP NP NP NP ( ---23)*†,†† ( ---23)*†† ( ---23)†† ( ---23)* 066135 / 135 ---22 060155 / 155 ---20 NP NP NP NP NP NP ---10 ( ---23)‡ NP NP 066155 / 155 ---22 MODELS 393AAV and 58YAV 024070 / 070 ---8 +5 ---10 ---10 ---10 ( ---23)‡‡ ---10 ( ---23) ---10 ( ---23) NP NP NP (15)* ( ---23)**†† ( ---23)* 036070 / 070 ---12 ---10 ---10 042091 / 091 ---14 ---10 ( ---23)†† NP ---10 ( ---23)†† NP NP NP NP ( ---23)† ( ---23)† 048111 / 111 ---16 ---10 ( ---23)‡ NP NP ---10 ( ---23)‡ NP NP NP NP NP ---10 ---10 ---10 ---10 060135 / 136 ---20 NP NP NP NP NP ( ---23)*†,†† ( ---23)*†† ( ---23)†† ( ---23)* 060155 / 155 ---20 NP NP NP NP NP NP ---10 ( ---23)‡ NP NP NP = Not Permitted Temperatures in parentheses are Celsius temperatures. * Furnace connector rise shall be at least 3 ft. (.9 M) {Chimney height shall be at least 10 ft. A higher chimney height is required, if the furnace installation instructions specify a higher chimney height. }Furnace connector rise shall be at least 2 ft or chimney height shall be at least 15 ft. (5 M) ** 6 ---in. X 5 ---in. (152 X 127 mm) or 6 ---in. X 4 ---in. (152 X 102 mm) tapered furnace vent connector decreaser is permitted at chimney inlet opening. However, better resistance to chimney condensation will result, if connector diameter is not reduced. {{4 ---in. X 3 ---in. (102 X 76 mm) tapered water heater vent connector decreaser is permitted at chimney inlet opening. However, better resistance to chimney condensation will result, if connector diameter is not reduced. }}Either ** or {{ is permitted, but not both. 5 8. Minimum chimney size shall conform to ”NAT+NAT” columns for common vent capacity in Table 13.2c in Chapter 13 of NFPA54/ANSI Z223.1--2006 in United States, or Table C 7 of Appendix C of CAN/CSA-B149.1--05 in Canada. The chimney sizing requirements in Table 7 (below) were extracted from these codes. 9. Permitted exceptions to --10_F (--23_C) minimum 99 percent winter design temperature and furnace connector diameters are provided in Table 8. If Table 8 permits a furnace connector size that is smaller than the chimney adapter outlet, a tapered decreaser is permitted at the chimney adapter outlet. 10. Manifolded common--vent connectors: See Fig. G.1(k) in NFPA54/ANSI Z223.1--2006 in USA or Fig. C.9 in CAN/ CSA--B149.1--05 in Canada. For chimney heights of 8 ft or more, Type--B manifolded common--vent connectors with no elbows are permitted. The manifolded common-vent connector diameter shall be 1 in. (25 mm) greater than required furnace vent connector size. The combined horizontal length of longest vent connector (furnace or water heater) plus manifolded common--vent connector shall not exceed vent connector lateral specified in section A.6. Each connector is permitted up to 2 elbows. No exceptions from Table 8 are permitted. The minimum winter design temperature permitted with manifolded common-vent connector is --10_F (--23_C). 5. 6. INSTALLATION OF CHIMNEY ADAPTER 1. Turn off gas supply at manual gas valve before turning off electric power supply to furnace. 2. Turn off electric power supply to furnace at disconnect switch. 3. The chimney adapters must always be installed for vertical flow of vent gas from bottom to top of chimney adapter. AIR--FLOW 4. UPFLOW AND HORIZONTAL APPLICATIONS NOT NEEDING STRAIGHT VENT PIPE INTERNAL TO FURNACE (horizontal flow not permitted with 393AAV/58YAV): KIT NO. KGACA02014FC: Attach chimney adapter to furnace flue elbow (collar on 393AAV/58YAV) with 2 sheet metal screws (field--supplied) through two 1/8--in. (3 mm) holes at inlet (small end) of chimney adapter. (See Fig. 2 or 3.) If a 1/8--in. (3 mm) hole at inlet is not accessible, remove three screws that hold elbow to inducer, attach chimney adapter to elbow, then reattach elbow to inducer (not applicable to 393AAV/58YAV). KIT NO. KGACA02015FC: Use same procedure as above, except a standard 4--in. dia. to 5--in. dia. (102 to 127 mm) vent pipe increaser (field--supplied) is required between furnace elbow and chimney adapter. (393AAV/58YAV: use 5--in. (127 mm) dia. X 12--in. (305 mm) long pipe, one end oval, instead of increaser.) DOWNFLOW AND HORIZONTAL AIR--FLOW APPLICATIONS HAVING A STRAIGHT VENT PIPE INTERNAL TO FURNACE (not permitted with 393AAV/58YAV): KIT NO. KGACA02014FC: Complete installation of flue pipe (and elbows) to exit furnace casing. If downflow furnace flue pipe exits casing through lower--left door opening, route the flue pipe through an accessory vent guard external to the casing. Attach chimney adapter to furnace flue where it exits the furnace casing or vent guard with three sheet metal screws (field--supplied) through two factory--punched 1/8--in. (3 mm)holes and a third fielded-drilled 1/8--in. (3 mm) hole at inlet (small end) of chimney adapter. Third hole should be 90_ from other two holes. KIT NO. KGACA02015FC: Use same procedure as 7. 8. 9. 10. 6 above for KGACA02014FC, except a standard 4--in. dia.-to--5--in. (102 to 127 mm) dia. vent pipe increaser (field-supplied) is required between the furnace flue and the chimney adapter. Remove lock nut from fitting on free end of electrical conduit attached to chimney adapter. Route wire ends through a 7/8--in. (22 mm) hole in furnace casing near the chimney adapter. Secure conduit to furnace with lock nut. If Vent Guard is used on downflow furnace, cut a notch in Vent Guard flange to provide access to 7/8--in. (22 mm) hole in furnace casing for conduit attachment. See, Fig. 8--12 & 13 for wiring connections. Furnaces other than 393AAV.58YAV: Find furnace red wires that connect to draft safeguard switch (DSS). Disconnect red wire with insulated, female, 3/16--in. (8 mm) quick--connect terminal from DSS, and connect this red wire to orange wire from blocked vent shutoff switch (BVSS) of chimney adapter that has insulated, male, 3/16--in. (8 mm) quick-connect terminal. Male and female 3/16--in. (8 mm) terminals must be oriented so that insulators fit together. Connect other chimney adapter BVSS orange wire to DSS terminal from which red wire was disconnected. Position orange wire terminal similar to remaining red wire terminal on DSS so that orange wire is directed away from hot elbow. The BVSS should be in series with the DSS. 393AAV/58YAV furnaces: Find furnace orange wires that connect to draft safeguard switch (DSS). DSS has 1/4--in. (6 mm) quick--connect terminals. Without disconnecting either orange wire at DSS, cut one of these wires about 3 in. (76 mm) from 1/4--in. (6 mm) terminal. Cut terminals off free ends of both orange wires of chimney adapter BVSS close to the terminals. Strip and splice the cut ends of the orange wires in the furnace to the cut ends of the orange wires of the chimney adapter BVSS with field-supplied wire nuts. The BVSS should be in series with the DSS. NOTE: For applications where the chimney adapter wire leads will not reach the DSS, use the factory--supplied extension wires between the chimney adapter BVSS leads and the DSS. A metal wire--routing clip is included in the kit to secure the orange extension wires away from hot surfaces and rotating parts. Extension wires are not applicable to 393AAV/58YAV. No other wire connection changes should be made for chimney adapter. Be certain that no terminals can be shorted to other circuits or to any grounded parts. Refer to Fig. 1. Secure a Type--B draft hood connector to top of chimney adapter with 3 sheet metal screws (field-supplied). Install Type--B double--wall metal vent connector from draft hood connector to chimney flue opening in accordance with vent pipe manufacturer’s Installation Instructions. The horizontal portion of venting system shall maintain a minimum of 1/4--in. upward slope per linear foot away from furnace, and shall be rigidly supported every 5 ft. or less with hangers and straps to ensure that there will be no movement after installation. The connector shall conform to size, rise, and lateral requirements under Venting Requirements and Table 2 of these instructions. Do NOT use the NFGC or NSCNGPIC vent connector sizing requirements. Complete installation of water heater Type--B double--wall vent connector in same manner as used for furnace connector, except that a chimney adapter is not required at Type--B draft hood connector for water heater. (Not required for single appliance, Venting Requirements Section B.) START--UP, ADJUSTMENT, AND SAFETY CHECK nace chimney adapter, or leakage from vent system), the common--venting chimney system must be corrected. g. After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliances to their previous conditions of use. 2. Check chimney adapter BVSS. This test is required, in addition to the test of the DSS required by the furnace installation instructions. The purpose of the BVSS is to cause safe shutdown of furnace, if furnace vent connector or chimney becomes blocked. a. Disconnect power to furnace, and remove vent connector from chimney adapter. Be sure to allow time for vent pipe to cool down before handling pipe. b. Place jumper wire across DSS terminals to electrically by--pass DSS so that if DSS opens, furnace does not shutdown until BVSS opens. c. Restore power to furnace and set room thermostat 5_F (--15_C) above room temperature. d. After normal start--up, allow furnace to operate for 2 minutes, then block chimney adapter outlet 100 percent. Furnace should shut off within 2 minutes. e. REMOVE JUMPER WIRE FROM DRAFT SAFEGUARD SWITCH! f. Remove blockage and reconnect vent connector to chimney adapter. g. Wait 5 minutes, then reset BVSS and DSS. 3. With furnace blower operating, check for air leakage from supply--air plenum or coil casing that could interfere with BVSS operation. If air leaks are found they must be properly sealed. 4. Leave Installation Instructions for chimney adapter and for furnace near furnace. 1. Complete Start--Up, Adjustment, and Safety Check in furnace Installation Instructions. Adjust furnace air temperature rise to be near high end of air temperature rise range specified on furnace rating plate (without exceeding high end of rise range). A higher air temperature rise reduces chimney condensation. While doing furnace check, the following steps shall be performed with each appliance that is connected to common vented chimney. Put each appliance in operation while other appliance(s) are not in operation. a. Inspect venting system for blockage or restriction, leakage, corrosion, and other deficiencies that could cause an unsafe condition. b. Insofar as practical, close all building doors and windows, and all doors between space in which appliances are located and other spaces of building. Turn on clothes dryer and any appliance not connected to this chimney flue. Turn on all exhaust fans such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. c. Follow operating instructions for each appliance being checked. Adjust each thermostat so appliance will operate continuously. d. Test for vent gas spillage at water heater draft hood (when applicable) and at furnace chimney adapter relief openings after 5 minutes of main burner operation. Use the flame of a match or candle. e. Operate ALL appliances that are common--vent connected to chimney flue, and again test for vent gas spillage. f. If improper venting is observed during any of above tests (e.g., vent gas spillage at water heater draft hood or fur- 7 CONNECTOR HORIZONTAL LENGTHS CLAY TILE-LINED MASONRY CHIMNEY TILE LINER SIZE INSIDE NOMINAL (OUTSIDE) CHIMNEY HEIGHT VENT CONNECTOR RISES FURNACE DIA SINGLE SINGLE WALL OR TYPE-B WALL OR (SEE TYPE-B TABLE 5) (SEE TABLE 5) WATER HEATER DIA CHIMNEY ADAPTER DRAFT HOOD-EQUIPPED WATER HEATER (NOT REQUIRED FOR SINGLE APPLIANCE) FAN-ASSISTED FURNACE A97515 Fig. 1 -- Furnace and Water Heater Vent Connectors, Chimney Adapter, and Chimney 4-IN. TO 5-IN. DIA. VENT PIPE INCREASER ON FLUE COLLAR 2 SCREWS 180° APART TO SECURE CHIMNEY ADAPTER TO FURNACE FLUE COLLAR CONDUIT BLOCKED VENT SHUTOFF SWITCH CHIMNEY ADAPTER OUTLET FOR VENT CONNECTION 2 SCREWS 180° APART TO SECURE VENT PIPE INCREASER TO FURNACE FLUE COLLAR CHIMNEY ADAPTER INLET AND FURNACE FLUE COLLAR CONDUIT 3 SCREWS 120° APART TO SECURE CHIMNEY ADAPTER INLET TO VENT PIPE INCREASER BLOCKED VENT SHUTOFF SWITCH CHIMNEY ADAPTER OUTLET FOR VENT CONNECTION NOTE: Conduit may need to be located at front of chimney adapter to provide clearance to an evaporator coil casing. A08191 A08192 Fig. 2 -- Chimney Adapter Secured to Upflow Furnace Flue Collar (Sizes up through 110,000 Btuh input) Fig. 3 -- Chimney Adapter Secured to Upflow Furnace Flue Collar (Sizes of 132,000 and 154,000 Btuh input) 8 A08196 A08193 Fig. 6 -- Chimney Adapter Secured to Flue Collar, Internal Flue Pipe, and Vent Elbow on Horizontal--Right Furnace Fig. 4 -- Chimney Adapter Secured to Upflow Furnace Flue Collar A08195 Fig. 7 -- Chimney Adapter Secured to Upflow Furnace Flue Collar A08194 Fig. 5 -- Chimney Adapter Secured to Upflow Furnace Flue Collar (Sizes of 132,000 and 154,000 Btuh input) 9 A08064 Fig. 8 -- 313AAV/JAV, 58PHA/PHX, PG8MEA/JEA Deluxe Single--Stage Furnace Wiring Diagram with Chimney Adapter 10 A08224 Fig. 9 -- Models other than 393AAV / 58YAV Standard Single--Stage Furnace Wiring Diagram with Chimney Adapter 11 12 L E G E N D EAC-1 SPARE 2 SPARE 1 GND GV GVR 1, 2 HSI HSIR HUM IDM IDR ILK J1 JB LED LGPS BFANR BHT/CLR BLWR BLWM BVSS CAP CPU DSS EAC-1 EAC-2 FRS 1, 2 FSE FU 1 FU 2 RED START BRN 2 YEL ORN CAP GRN/YEL PR1 PL2 WHT BRN RED GRN/YEL 1 WHT BLK BLK WHT ILK JB DSS RED BLK NOTE #11 WHT BLK GRN/YEL IDM BVSS (WHEN USED) ORG Fig. 10 -- Models other than 393AAV / 58YAV Deluxe Single--Stage Furnace Wiring Diagram with Chimney Adapter 13. 14. EQUIPMENT GROUND PLUG RECEPTACLE FIELD SPLICE FIELD EARTH GROUND 15. 10. 11. 12. FIELD WIRING SCREW TERMINAL PL2 CPU 24VAC 115VAC COM 24V FRS2 LS1 FSE L2 IDM EAC-2 NOTE #3 GV PRS NOTE #11 LS2 (WHEN USED) NOTE #10 BVSS (WHEN USED) BLWM DSS START LGPS (WHEN USED) FRS1 HSI OL CAP SCHEMATIC DIAGRAM (NATURAL & PROPANE GASES) If any of the original equipment wire is replaced use wire rated for 105°C. Use only copper wire between the disconnect switch and the furnace junction box (JB). This wire must be connected to furnace sheet metal for control to prove flame. Symbols are electrical representation only. Solid lines inside PCB are printed circuit board conductors and are not included in legend. Replace only with a 3 amp fuse. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL). Neutral connections are interchangeable within the NEUTRAL connector block. Blower motor speed selections are for average conditions, see installation instructions for details on optimum speed selection. Factory connected when BVSS (Chimney Adapter Accessory Kit) is not installed. Factory connected when LGPS is not used. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset after three hours. Blower-on delay: gas heating 25 seconds, cooling or heat pump 2 seconds. Blower-off delay: gas heating selections are 90, 120, 150 or 180 seconds, cooling or heat pump 90 seconds or 5 seconds when DHUM is ON. YELLOW lead not on all motors. PL1-7 PL1-9 PL1-11 PL1-3 PL1-5 PL1-10 PL1-1 GVR-1 PL1-4 PL1-2 PL1-8 PL1-6 2 1 COM LO MED LO MED HI HI PL3 SPARE-1 NOTE #15 COOL HEAT EQUIPMENT GROUND G GVR-2 SEC-2 2 1 BHT/CLR PCB NOTE #5 TEST/TWIN NOTE #6 SEC-1 TRAN PR1 EAC-1 HSIR FAN L2 NEUTRAL BFANR Y1 DHUM Y/Y2 W R HUM NOTES: 1. 2. 3. 4. 5. 6. 7. 8. 9. IDR BLWR L1 ILK FU1 L1 TO 115VAC FIELD DISCONNECT SWITCH CONDUCTOR ON CONTROL PCB FIELD WIRING (24VAC) FIELD WIRING (115VAC) FACTORY WIRING (24VAC) FACTORY WIRING (115VAC) PCB CONTROL TERMINAL UNMARKED TERMINAL LIMIT SWITCH, AUTO-RESET, SPST(N.C.) AUTO-RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH (N.C.) PRINTED CIRCUIT BOARD CONTROL 11-CIRCUIT PCB CONNECTOR 2-CIRCUIT CONNECTOR 2-CIRCUIT HSI, CONNECTOR PRESSURE SWITCH, SPST-(N.O.) COMPONENT TEST & TWIN TERMINAL TRANSFORMER-115VAC/24VAC JUNCTION GND FUSE OR CIRCUIT BREAKER & DISCONNECT SWITCH (WHEN REQ’D) NOTE #2 NEUTRAL WHT FU2 L1 BLK WHT WHT RED (WHEN USED) RED LS2 NOTE #10 ORG LS1 (WHEN USED) LGPS RED FRS2 BLK PCB PL1 PL2 PL3 PRS TEST/TWIN TRAN LS 1, 2 OL 1 2 RED BLU FRS1 RED PL3 PRS WHT (COM) FSE RED NOTE #5 GRN/YEL GV NEUTRAL CONNECTION DIAGRAM CONTINUOUS-FAN SELECT RELAY, SPDT BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR RELAY, SPST-(N.O.) BLOWER MOTOR, PERMANENT-SPLIT-CAPACITOR BLOCKED VENT SHUTOFF SWITCH, MANUAL-RESET, SPST -(N.C.) CAPACITOR MICROPROCESSOR AND CIRCUITRY DRAFT SAFE GUARD SWITCH, AUTO-RESET, SPST -(N.C.) ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FLAME-PROVING ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE (FIELD INSTALLED & SUPPLIED) EQUIPMENT GROUND GAS VALVE-REDUNDANT GAS VALVE RELAY, DPST-(N.O.) HOT SURFACE IGNITER (115 VAC) HOT SURFACE IGNITER RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) INDUCED DRAFT MOTOR, SHADED-POLE INDUCED DRAFT MOTOR RELAY, SPST-(N.O.) BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.) BLOWER - OFF DELAY JUMPER SELECTOR JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES - AMBER LOW GAS PRESSURE SWITCH, SPST-(N.O.) RED (LO) NOTE #15 YEL (MED HI) OL L1 FAN HEAT BLWM BLWR BLK (HI) BLU PL1 BFANR L2 BHT/CLR COOL BLU (MED LO) WHT (COM) LED SEC-1 EAC-2 SEC-2 HUM TEST/TWIN R Y/Y2 180 J1 120 1 2 3 4 5 6 7 8 9 10 11 150 90 G Com 24V W DHUM FU1 NOTE #6 NOTE #8 TRAN Y1 NEUTRAL BLW PCB HSI YEL PRINTED CIRCIUT BOARD 327560-101 REV. D BLOWER OFF-DELAY JUMPER SELECT OR PRINTED CIRCIUT BOARD A02140 A08225 Fig. 11 -- Models other than 393AAV / 58YAV Two--Stage Furnace Wiring Diagram with Chimney Adapter 13 PRINTED CIRCIUT BOARD 14 1 AB CD PL7 OFF 123 OFF 123 OFF 123 AC Y1 DHUM G Com W/W1 Y/Y2 R 24V Air Conditioning (Adjustable Airflow -CFM) Air Conditioning Relay, SPST (N.O.) Air Conditioning Relay Defeat Jumper Blower Motor (ECM) Blocked Vent Safety Switch, Manual Reset, SPST (N.C.) CF Continuous Fan (Adjustable Airflow -CFM) COMMR Communication Relay, SPDT CPU Microprocessor 7 Circuitry DHUM DHUM Connection (24VAC 0.02 Amps) DSS Draft Safeguard Sw., Auto-Reset, SPST (N.C.) EAC-1 Electronic Air Cleaner Connection (115VAC 1.0 Amp Max.) EAC-2 Electronic Air Cleaner Connection (Common) FRS Flame Rollout Switch, Man. Reset, SPST(N.C.) FSE Flame-Proving Sensor Electrode FUSE Fuse, 3 Amp, Automotive Blade Type, Factory Installed GV Gas Valve GVR Gas Valve Relay, DPST (N.O.) HPS High-Heat Pressure Switch, SPST (N.O.) HPSR High-Heat Pressure Switch Relay, SPST (N.C.) HSI Hot Surface Igniter (115VAC) HSIR Hot Surface Igniter Relay, SPST (N.O.) HUM 24VAC Humidifier Connection (0.5 Amp Max.) HUMR Humidifier Relay, SPST (N.O.) IDM Inducer Draft Motor, 2-Speed, Shaded Pole IDR Inducer Motor Relay, SPST (N.O.) IHI/LOR Inducer Motor Speed Change Relay, SPDT W2 OFF A/C ACR ACRDJ BLWM BVSS PL1 OFF 123 1 1 CF 1 4 1 OFF 123 1 YEL LPS RED NOTE #13 NEUTRAL - L2 BLK L1 PL2 WHT DSS ORN 1 BLK WHT WHT WHT BLU PL12 IND NOTE #7 BLK 4 BLK WHT COM HI BLWM PL10 HSI PL14 ILK JB GRN/YEL CONDUCTOR ON WIRING (24VAC) FIELD CONTROL WIRING (24VAC) Fig. 12 -- Models other than 393AAV / 58YAV Variable--speed Furnace Wiring Diagram with Chimney Adapter PLUG RECEPTACLE GROUND EQUIPMENT SCREW TERMINAL FIELD WIRING CONTROL RED R COMMR HUM 13. 14. 11. 12. 10. 2 NOTE #5 PCB IHI/LOR BVSS CPU HUMR GVR HPSR DSS PL12 10 16 1 7 PL1-6 2 1 PL14 EAC-2 4 PL1-1 NOTE #3 C PL1-10 M GV LGPS (WHEN USED) PL1-3 PL1-4 FU1 HI HPS LPS IDM L2 24VAC TRAN FSE PL1-5 SEC1 SEC2 115VAC L2 BLWM L1 NOTE #6 NOTE #8 PL1-2 PL1-12 PL1-8 FRS1 5 3 PL13 PL11 3 COM LO HI 4 HSI PL10 2 1 2 1 SCHEMATIC DIAGRAM 1 2 3 EAC-1 PL2 EQUIPMENT GROUND IND NOTE #7 PCB 4 L2 HSIR L2 (WHEN USED) NOTE #12 PL12 3 CPU ACR EAC L1 1 (WHEN USED) LS2 IDR NOTE #5 PL3 ILK TO 115VAC FIELD-DISCONNECT SWITCH If any of the original equipment wire is replaced use wire rated for 105∞C. Use only copper wire between the disconnect switch and the furnace junction box (JB). This wire must be connected to furnace sheet metal for control to prove flame. Symbols are electrical representation only. Solid lines inside PCB are printed circuit board conductors and are not included in legend. Replace only with a 3 amp fuse. Inductor is used with 3/4 hp and 1 hp ECM Blower motors. Factory connected when (LGPS) not used. Blower off-delay, gas heating selections are (90, 120, 150, 180) seconds, cooling or heat pump 90 seconds or 5 seconds when dehumidify call is active. Ignition lockout will occur after four consecutive unsuccessful trials for ignition. Control will auto-reset after three hours. Inducer motor (IDM) contains internal auto-reset thermal overload switch. Factory connected when BVSS is not used. BVSS used when Chimney Adapter Accessory Kit is installed. Any of the 5 wires shown within the NEUTRAL L2 box can be connected to any terminal within the box. Blower motor (BLWM) is locked-rotor overload protected by redundant electronic control circuits. NOTES: COM Y/Y2 G Y1 DHUM W2 1. 2. 3. 4. 5. 6. 7. 8. 9. LS1 GND W/W1 FRS2 PRINTED CIRCIUT BOARD FACTORY CONTROL WIRING (115VAC) FACTORY POWER CONTROL TERMINAL TERMINAL JUNCTION FRS2 BLK WHT FU2 54 3 2 1 2 1 LO GRN/YEL RED FUSED OR CIRCUIT BREAKER DISCONNECT SWITCH (WHEN REQ'D) NOTE #2 NEUTRAL L1 LS1 10 16 1 7 PL13 BLK RED BLK RED 2 BLK ORN IDM PL11 WHT 3 WHT RED FSE RED LS2 (WHEN USED) RED LGPS (WHEN USED) BVSS (WHEN USED) NOTE #8 ORN NOTE #12 Blower Door Interlock Switch, SPST (N.O.) Inductor (Note #7) Light Emitting Diode for Status Codes Low Gas Pressure Switch, SPST (N.O.) Low-Heat Pressure Switch, SPST (N.O.) Limit Switch, Auto-Reset, SPST (N.C.) Printed Circuit Board 12-Circuit Connector 4-Circuit HSI & IDM Connector 4-Circuit ECM BLWM Connector 4-Circuit Model Plug Connector 4-Circuit Communication Connector 2-Circuit OAT Connector 2-Circuit HSI Connector IDM Connector (3-Circuit) 1-Circuit Inductor Splice Connector 16-Circuit ECM Blower Ctrl. Connector 5-Circuit ECM Blower Power Connector Manual Switch, Status Code Recall, SPST (N.O.) Manual Switch, Low-Heat Only, SPST(N.O.) Manual Switch, Low-Heat Rise Adj. SPST (N.O.) Manual Switch, Comfort/Efficiency Adjustment, SPST (N.O.) SW1-5 Manual Switch, Cooling CFM/Ton, SPST (N.O.) SW1-6 Manual Switch, Component Test, SPST (N.O.) SW1-7,8 Manual Switches, Blower Off-Delay, SPST(N.O.) SW4-1 Manual Switch, Twinning Main (OFF) / Sec. (ON) SW4-2&3 FOR FUTURE USE TRAN Transformer, 115VAC / 24VAC ILK IND LED LGPS LPS LS 1, 2 PCB PL1 PL2 PL3 PL4 PL7 PL9 PL10 PL11 PL12 PL13 PL14 SW1-1 SW1-2 SW1-3 SW1-4 STATUS CODE LEDS COMM MODEL SIZE 875 1050 1 1225 1225 1225 070 DEF. 525 2 700 525 700 2 875 1050 1225 1400 1 1400 090 DEF. 110,135, 700 875 2 1050 1225 1400 1750 1 2100 DEF. 155 1. Default A/C airflow when A/C switches are in OFF position 2. Default cont. fan airflow when CF switches are in OFF position HUM PL9 PL3 GRN/YEL BRN GRY RED OFF 123 FUSE 3-AMP FRS1 123 SEC-2 SEC-1 A/C OR CF AIRFLOW SELECTION CHART BASED ON 350 CFM/TON PL8 HI BRN HPS BLU PL12 L E G E N D NOTE #3 C GRN/YEL GV PL4 - MODEL PLUG CHART MODEL MODEL PIN RESISTANCE K PLUG SIZE 1-4 2-3 HK70EZ 11 5.1 070 001 24 5.1 090 003 5.1 33 110 004 39 5.1 135 005 51 5.1 155 006 90 SEC 120 SEC 150 SEC 180 SEC M CONNECTION DIAGRAM OFF 123 ACRDJ EAC-1 SW1-7,8 BLOWER OFF DELAY SELECTION RED GRN YEL BLU EAC-2 OAT YEL PL4 SW1 VS HSI HI LO OFF OFF OFF OFF SW4 327562-101 REV. C 7 8 7 8 7 8 7 8 RED GRN YEL BLU ACRDJ TRAN A02160 Fig. 13 -- 393AAV / 58YAV Single Stage Furnace Wiring Diagram with Chimney Adapter A00304 15 GV GVR HI/LO HSI HSIR HUM IDM IDR ILK JB LED LGPS LS OL ALS BLWR BLWM BVSS CAP CPU DSS EAC-1 EAC-2 FL FRS FSE FU1 FU2 1 HSI 2 1 2 PL5 PL2 PL3 SEC-2 6 5 4 9 8 7 3 2 1 SEC-1 PL1 LED 1 2 3 BLK WHT COM PR2 L2 IDM GRN/YEL EAC-2 HEAT SPARE-2 EAC-1 24 VAC-3A FU1 FUSE BLOWER SPEED COOL SPARE-1 SELECT HI/LO RELAY BLWR GVR 225 SEC 180 SEC 135 SEC TEST/TWIN HUM G R Y W COM BLU WHT (COM) RED (LO) BLU (MED LO) NOTE #7 YEL (MED HI) WHT FRS1 FSE LS ORN ILK OL BRN BRN GND WHT BLK FU2 NEUTRAL L1 FUSED DISCONNECT SWITCH (WHEN REQ’D) NOTE #4 CAP GRN/YEL WHT (COM) WHT BLK PLUG RECEPTACLE FIELD SPLICE EQUIPMENT GROUND FIELD GROUND FIELD WIRING TERMINAL CONDUCTOR ON PCB FIELD WIRING (24VAC) FIELD WIRING (115VAC) FACTORY WIRING (24VAC) FACTORY WIRING (115VAC) PCB TERMINAL UNMARKED TERMINAL JUNCTION YEL GRN/YEL NOTE #5 GV NOTE #15 NOTE #13 (WHEN USED) LGPS PRINTED CIRCUIT BOARD 9-CIRCUIT CONNECTOR 2-CIRCUIT PCB CONNECTOR 3-CIRCUIT IDM CONNECTOR 2-CIRCUIT HSI/PCB CONNECTOR PRESSURE SWITCH, SPST-(N.O.) COMPONENT TEST & TWIN TERMINAL TRANSFORMER-115VAC/24VAC JB BLWM START PCB PL1 PL2 PL3 PL5 PRS TEST/TWIN TRAN BLK RED BLU FL PRS FRS2 GRN/YEL ORN (WHEN USED) NOTE #11 ALS (WHEN USED) NOTE #11 NOTE #14 ORN (WHEN USED) NOTE #14 BVSS ORN BLK (HI) RED WHT RED ORN DSS AUXILIARY LIMIT SWITCH, OVERTEMP. -MANUAL RESET, SPST-(N.C.) BLOWER MOTOR RELAY, SPST-(N.O.) BLOWER MOTOR BLOCKED VENT SHUTOFF SWITCH, SPST - (N.C.) CAPACITOR MICROPROCESSOR AND CIRCUITRY DRAFT SAFEGUARD SWITCH ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FUSIBLE LINK FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FLAME PROVING ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE (FIELD INSTALLED & SUPPLIED) GAS VALVE-REDUNDANT OPERATORS GAS VALVE RELAY, DPST-(N.O.) BLOWER MOTOR SPEED CHANGE RELAY, SPDT HOT SURFACE IGNITOR (115 VAC) HOT SURFACE IGNITOR RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.) INDUCED DRAFT MOTOR INDUCED DRAFT RELAY, SPST-(N.O.) BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES LOW GAS PRESSURE SWITCH, SPST-(N.O.) LIMIT SWITCH, AUTO RESET, SPST(N.C.) AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW. LEGEND BLK IDR BLK 120 VAC L1 PR1 HSIR BLK 90 SEC BLOWER OFF DELAY SELECTION CHART NOTE #9 (NOT ON ALL MODELS) WHT PCB WHT SW2 BLOWER OFF DELAY SW1 1.5 AMP TRAN L1 HSIR IDR CPU BLWR GVR-2 SEC-1 TRAN PR1 EAC-2 EAC-1 PL2 HI/LO GVR-1 GVR SEC-2 24VAC PR2 PL1 9 NOT USED CAP FL (WHEN USED) NOTE #14 BVSS FSE NOTE #5 GV ALS (WHEN USED) NOTE #13 PRS LGPS (WHEN USED) LS FRS2 IDM BLWM START NOTE #14 NOTE #15 DSS NOTE #13 (WHEN USED) NOTE #11 FRS1 NOT USED OL 6 NOT USED 5 8 2 3 4 1 7 2 3 PL3 HSI LO MED LO MED HI HI COM 1 2 1 NOTE #7 2 PL5 1 COM COOL SPARE-1 115VAC HI/LO SPARE-2 HEAT EQUIPMENT GROUND SCHEMATIC DIAGRAM (NATURAL GAS & PROPANE) L2 1. If any of the original equipment wire is replaced use wire rated for 105°C. 2. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL). 3. Blower motor speed selections are for average conditions, see installation instructions for details on optimum speed selection. 4. Use only copper wire between the disconnect switch and the furnace junction box (JB). 5. This wire must be connected to furnace sheetmetal for control to detect flame. 6. Replace only with a 3 amp fuse. 7. Yellow lead not on all motors. 8. Blower-on delay, gas heating 45 seconds, cooling or heat pump 2 seconds. 9. Blower-off delay, gas heating 90, 135, 180 or 225 seconds, cooling or heat pump 90 seconds. (135 seconds only on some models) 10. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset after three hours. 11. When used, auxiliary limit switch (ALS) is on some downflow models only. When used, FL is on upflow models only. 12. Some models may have spade quick connect terminals. 13. Factory connected when LGPS is not used. 14. Factory connected when BVSS is not used. BVSS used when Chimney Adapter Accessory Kit is installed. 15. Gas valve leads are interchangeable on single stage valves. 322869-101 REV. H NOTES: COM G Y W R NOTE #12 HUM FU1 IDR HSIR BLWR NOTE #6 L2 NOTE #4 TEST/TWIN ILK L1 TO 115VAC FIELD DISCONNECT MASONRY CHIMNEY APPLICATION REQUIREMENTS 17 to 26_F (--- 8 to --- 3_C) VENT HEIGHT FT. (M) 6 (1.8) 8 (2.4) 10 (3) 15 (5) 20 (6) 30 (9) --- 10 to 4_F (--- 23 to --- 16_C) 6 (2) 8 (2) 10 (3) 15 (5) 20 (6) 30 (9) INTERNAL AREA OF CHIMNEY IN.2 (mm2) 12 (7742) 19 (12258) 28 (18064) 38 (24516) Local 99% Winter Design Temperature: 17 to 26_F (--- 8 to --- 3_C)* 0 55 99 141 52 74 111 154 NR 90 125 169 NR NR 167 212 NR NR 212 258 NR NR NR 362 Local 99% Winter Design Temperature: 5 to 16_F (--- 15 to --- 9_C)* NR 78 121 166 NR 94 135 182 NR 111 149 198 NR NR 193 247 NR NR NR 293 NR NR NR 377 Local 99% Winter Design Temperature: --- 10 to 4_F (--- 23 to --- 16_C)* NR NR 145 196 NR NR 159 213 NR NR 175 231 NR NR NR 283 NR NR NR 333 NR NR NR NR Local 99% Winter Design Temperature: --- 11_F or lower (--- 24_C or lower)* Not recommended for any vent configuration *The 99% Winter Design Dry ---Bulb (db) temperatures are found in the 2005 ASHRAE Fundamentals Handbook CD and Chapter 28. Table 9 – Combined Appliance Maximum Input Rating in Thousands of Btu per Hr VENT HEIGHT FT (M) 6 (2) 8 (2) 10 (3) 15 (5) 20 (6) 30 (9) 6 (2) 8 (2) 10 (3) 15 (5) 20 (6) 30 (9) --- 11_F or lower (--- 24_C or lower) If a clay tile--lined masonry chimney is used, an alternative venting design might be required, such as a listed chimney lining system or this listed chimney adapter kit. ONE OF THE FOLLOWING METHODS SHALL BE USED TO DETERMINE IF AN ALTERNATIVE VENTING DESIGN IS NOT REQUIRED. In the USA -- Refer to Sections 13.1.11 and 13.2.22 of NFPA54/ANSI Z223.1--2006 or the authority having jurisdiction to determine whether relining is required. If relining is required, use a properly sized listed metal liner, Type--B vent, or a listed alternative venting design, such as this listed chimney adapter kit (with a furnace listed for use with this kit), a listed chimney lining system, or a Type--B common vent. In Canada (Also permitted in the USA) -- A 78 or 80 percent AFUE, hot surface ignition, Category I, fan--assisted furnace is permitted to be vented into a clay tile--lined masonry chimney that is exposed to the outdoors below the roof line, provided: Multiple Appliances -- (A single furnace common--vented with a draft hood--equipped water heater(s) into a chimney.) 1. Vent connector is Type--B double--wall, and 2. The furnace is common vented with at least one draft hood--equipped appliance, and 3. The combined appliance input rating is less than the maximum capacity given in Table 9A, and 4. Input rating of each space heating appliance is greater than minimum input rating given in Table 9B and 5. The authority having jurisdiction approves. If all of these conditions cannot be met, an alternative venting design is required, such as this listed chimney adapter kit (with a furnace listed for use with this kit), a listed chimney lining system, or a Type--B common vent. Single Appliance -- (A single furnace vented into a chimney.) -Category I, fan assisted furnaces without draft hoods are not permitted to be vented into clay tile--lined masonry chimneys that are exposed to the outdoors below the roof line. Table 10 – Minimum Allowable Input Rating of Space--Heating Appliances in Thousands of Btu per Hr INTERNAL AREA OF CHIMNEY IN.2 (mm2) 12 19 28 38 (7742) (12258) (18064) (24516) 74 119 178 257 80 130 193 279 84 138 207 299 NR 152 233 334 NR NR 250 368 NR NR NR 404 16 7-IN. (179 mm) DIA OUTLET RESET SWITCH 7 3/4″ (197 mm) 5-IN. (127 mm) INLET KGACA02015FC 1/8-IN. (3 mm) DIA. HOLES 6-IN. (152 mm) DIA. OUTLET RESET SWITCH 8 1/4″ (209 mm) 1/8-IN. (3 mm) DIA. HOLES 4-IN. (102 mm) INLET A08240 Fig. 14 -- Chimney Adapters 17 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-644-5544 [ ] Packaged Service Training [ ] Classroom Service Training A94328 Copyright 2008 CAC / BDP D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in USA. Edition Date: 04/08 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 18 Catalog No: IIK---KGACA ---01 Replaces: AG--GACA--06